43
Guide to Configuration of BTS Environment Alarms on the BSC6000 For internal use only Document code Product name GSM BSC6000 Target readers Overseas &Domestics Product version All Versions Edited by Documentation Dept. WN Document version V1.1 Guide to Configuration of BTS Environment Alarms on the BSC6000 Drafted by: Tian Baihe Date: 2008-03-26 Reviewed by: Wang Dong , Liu Ying , Li Kai Date: 2008-03-28 Approved by: Liu Ying Date: 2008-04-26 2022-08-22 HUAWEI Confidential Page1, Total43

GSM BSC6000 Guide to Configuration of BTS Environment Alarms on the BSC6000-20080530-B-V1.1

Embed Size (px)

DESCRIPTION

BSC6000 Guide to Configuration of BTS Environment Alarms on the BSC6000

Citation preview

Guide to Configuration of BTS Environment Alarms on the BSC6000For internal use only

Document codeProduct nameGSM BSC6000

Target readersOverseas &DomesticsProduct versionAll Versions

Edited byDocumentation Dept. WNDocument versionV1.1

Guide to Configuration of BTS Environment Alarms on the BSC6000Drafted by:Tian BaiheDate:2008-03-26

Reviewed by:Wang Dong , Liu

Ying , Li KaiDate:2008-03-28

Approved by:Liu YingDate:2008-04-26

Huawei Technologies Co, LtdAll Rights Reserved41 Basic Knowledge

41.1 Sensor

41.1.1 Dry-Contact Boolean Value Output Sensor

51.1.2 OC-output Boolean Value Output Sensor

51.1.3 Voltage-output Boolean Value Output Sensor

51.1.4 Analog Input Sensor

51.2 Survey of Environment Alarm

51.2.1 Introduction to the Environment Alarm

61.2.2 Sensors of the BTS

81.2.3 Cables Related to BTS Alarms

81.2.4 BTS Monitoring Unit

112 Configuring BTS Environment Alarms

112.1 Purpose

112.1.1 Decentralized Management of Environment Alarm IDs

122.1.2 Centralized Management of Environment Alarm IDs

122.2 Configuring BTS Environment Alarm in BSC6000 V900R001+M2000 V2R3

132.2.2 Modifying the NE Environment Alarm Name Through the BSC6000 Local Maintenance Terminal

152.2.3 Modifying the Name of NMS Environment Alarm

182.3 Configuring BTS Environment Alarm in BSC6000 V900R003+M2000 V2R3

182.3.1 Planning User-Defined Environment Alarm IDs of BSC6000 R900R003

202.3.2 Binding Environment Alarm ID Parameters on the MML Local Maintenance Terminal

222.3.3 Modifying the BTS Environment Alarm Name and Definition on the BSC6000 Local Maintenance Terminal

252.3.4 Modifying the Name of M2000V2R3 Environment Alarm

252.4 Configuring BTS Environment Alarm in BSC6000 V900R003+M2000 V2R6

262.4.2 Binding the Parameters of the NE BTS Environment Alarm ID through M2000V2R6

272.4.3 Modifying the Name and Definition of the M2000V2R6 Environment Alarm

303 Difference of Environment Alarm Configurations Between BSC6000 Versions

303.1 Differences of Environment Alarm Configurations Between BSC6000 Versions

343.2 Environment Alarm Configuration in V9R1 Upgraded to V9R3 or Later Versions

TOC \h \z \t "Figure Description" \c

4Figure 1-1 Connection mode of the passive dry-contact Boolean value output sensor

4Figure 1-2 Connection mode of the active dry-contact Boolean value output sensor

5Figure 1-3 Connection mode of the OC-output Boolean value output sensor

5Figure 1-4 The connection mode of the voltage-output Boolean value output sensor

6Figure 1-5 Networking of BTS environment alarm equipment

7Figure 1-6 Wiring terminal of the door status sensor

7Figure 1-7 Wiring terminal of the water sensor

7Figure 1-8 The wiring terminal of the smoke sensor

8Figure 1-9 Wiring terminal of the infrared sensor

8Figure 1-10 Wiring terminal of the humidity and temperature sensor

13Figure 2-1 Login window of BSC6000 local maintenance terminal

14Figure 2-2 Setting the condition for querying the alarm configuration

14Figure 2-3 Alarm query result

15Figure 2-4 Setting parameters of the environment alarm configuration

15Figure 2-5 Successfully setting parameters of the environment alarm configuration

16Figure 2-6 Querying the records of modifying environment alarms on the M2000

17Figure 2-7 Example of the input.txt file

17Figure 2-8 Information displayed in the interface

21Figure 2-9 Login window of BSC6000 Local Maintenance Terminal

21Figure 2-10 Local Maintenance Terminal

22Figure 2-11 Interface of inputting the command parameter.

23Figure 2-12 Interface of the BSC6000 Local Maintenance Terminal

23Figure 2-13 Query Alarm Configuration Settings dialog box

24Figure 2-14 Query Alarm Configuration window

24Figure 2-15 Setting parameters of the environment alarm configuration

25Figure 2-16 Successful setting

26Figure 2-17 M2000 Mobile Element Management System interface

27Figure 2-18 Binding an alarm

28Figure 2-19 NE Alarm Settings tab

28Figure 2-20 Adding the user-defined alarm

31Figure 3-1 Selecting a BTS

32Figure 3-2 Shortcut menu

32Figure 3-3 Configure Site Boards Attributes dialog box

33Figure 3-4 Site Device Attributes dialog box

34Figure 3-5 Enabling the board alarm

1 Basic Knowledge1.1 SensorBased on different types of output signals, the sensors are categorized into the dry-contact Boolean value output sensor, the OC-output Boolean value output sensor, the voltage-output Boolean value output sensor, and the analog input sensor. 1.1.1 Dry-Contact Boolean Value Output SensorThe dry-contact Boolean value output sensors are categorized into: Passive dry-contact Boolean value output sensorA passive dry-contact Boolean value output sensor has no power input terminal, and it generally has two signal output terminals (S+/S-). Figure 1-1 shows the connection mode.Figure 1-1 Connection mode of the passive dry-contact Boolean value output sensor

Active dry-contact Boolean value output sensorAn active dry-contact Boolean value output sensor has two power input terminals (POWER+/POWER-) and two signal output terminals (S+/S-). Figure 1-2 shows the connection mode.Figure 1-2 Connection mode of the active dry-contact Boolean value output sensor

If the level is low when the loop is close, a low-voltage alarm is generated. If the level is high when the loop is open, a high-voltage alarm is generated.1.1.2 OC-output Boolean Value Output SensorThe OC-output Boolean value output sensor has two power input terminals (POWER+/POWER-) and one signal output terminal (Sout). Figure 1-3 shows the connection mode.Figure 1-3 Connection mode of the OC-output Boolean value output sensor

If the level is low when the loop is close, a low-voltage alarm is generated. If the level is high when the loop is open, a high-voltage alarm is generated. 1.1.3 Voltage-output Boolean Value Output SensorThe voltage-output Boolean value output sensor has two power input terminals (POWER+/POWER-) and one signal output terminal (Sout). Figure 1-4 shows the connection mode.Figure 1-4 The connection mode of the voltage-output Boolean value output sensor

The lower level at loop close indicates the lower voltage, while the high level at loop disconnection. 1.1.4 Analog Input SensorThe analog input has a mathematic or linear correlation. The gradually changing current (or the voltage) corresponds to a changing value according to the correlation. For example, the sensor monitors the temperature and inputs an analog value through changing current, and the processor calculates the temperature value according to a mathematic correlation.1.2 Survey of Environment Alarm1.2.1 Introduction to the Environment AlarmTo ensure stable operation of the equipment in a mobile communication equipment room, different sensors and software devices are used to monitor the operation of the equipment in the equipment room in real time, such as the power supply and the environment of the equipment room. The power supply monitoring refers to the monitoring of the mains supply, DC power distribution module, rectifier module, and storage battery. The environment monitoring in the equipment room involves the temperature, humidity, access control, water, smoke, distribution, and door status.With the extended alarm ports on the BTS, the auxiliary equipment of the BTS such as the power supply, switching power supply and storage battery can be monitored. With the Environment Monitoring Unit (EMU), the temperature, humidity, and smoke can be monitored and the intrusion can be detected in real time. The environment can be monitored according to the preset value and alarms are generated when the preset threshold is exceeded. Figure 1-5 shows the networking of the environment alarm system.Figure 1-5 Networking of BTS environment alarm equipment

1.2.2 Sensors of the BTSSensors are used to detect the environment variables of the BTS and report various environment alarms. The sensors special for the BTS are classified into the door status sensor, water sensor, smoke sensor, infrared sensor, and temperature and humidity sensor.

Door status sensor

The door status sensor is placed at the intersection of the door frame and door. It detects the opening and closing of the door. Figure 1-6 shows the wiring terminal. Figure 1-6 Wiring terminal of the door status sensor

Water sensor

The water sensor is horizontally placed at the places that are subject to be immersed in water in the equipment room. It detects whether the BTS is immersed in water. Figure 1-7 shows the wiring terminal. Figure 1-7 Wiring terminal of the water sensor

Smoke sensor

The smoke sensor is placed at the center of the ceiling. It detects whether the BTS or the equipment room is on fire. Figure shows the wiring terminal. Figure 1-8 The wiring terminal of the smoke sensor

Infrared sensor

The infrared sensor is placed on the wall, 1.5 m above the floor. It detects whether there is illegal intrusion. Figure 1-9 shows the wiring terminal. Figure 1-9 Wiring terminal of the infrared sensor

Humidity and temperature sensor

The temperature and humidity sensor is placed on the wall, 1.5 m above the floor. It detects whether the temperature or humidity exceeds the threshold. Figure 1-10 shows the wiring terminal. Figure 1-10 Wiring terminal of the humidity and temperature sensor

1.2.3 Cables Related to BTS AlarmsDifferent BTS may have different interfaces. For details, see section Correlation Between Expanded Boolean Value Alarms and Cables of BTS in the BTS Alarm Reference.1.2.4 BTS Monitoring UnitTable 1-1 lists the monitoring units and BTS alarm IDs supported by the BTSs of different models. Table 1-1 Mapping between BTSs and monitoring unitsSite TypeMonitoring UnitNumber of Supported Extended Alarms

BTS30TMU24

EAC32

BTS312TMU24

EAC32

BTS3006ATMU24

EAC32

BTS3012ATMU24

EAC32

BTS3002CIOMU4

EAC32

BTS3012DTMU24

DPMU14

EAC32

DEMU40

BTS3012AEDTMU24

DPMU7

DEMU40

BTS3006CDTMU32

APMU3

DPMU7

DEMU32

BTS3002EDTMU32

APMU3

DPMU7

DEMU40

BTS3012_IIDTMU24

DPMU14

EAC32

DEMU40

DBS3036GTMU16

APMU3

DPMU7

DEMU40

BTS3036AGTMU16

APMU3

DPMU7

DEMU40

FMUA4

BTS3036AGTMU16

APMU3

DPMU7

DEMU40

FMUA4

1.2.5 Mapping between cables and monitoring unitsFor more detailsrefer to the accessory as below.

2 Configuring BTS Environment Alarms2.1 PurposeIn the BSC6000 products, the BTS environment alarm IDs are managed in two modes, that is, the decentralized management mode and the centralized management mode. Decentralized management mode In the BSC6000 V900R001 (V9R1 for short), the environment alarms of the BTS and BSC are managed in the decentralized management mode. The discontinuous environment alarm IDs for different BTS types are not suitable for the centralized management and are not easy to use. Centralized management modeIn the BSC6000 V900R003 (V9R3 for short), the environment alarm function is optimized. The environment alarm baseline of Huawei is used to unify environment alarm IDs to one fixed range and the binding correlation between the alarm ID and the BTS monitoring port is established through the M2000 or directly with the MML.In the meantime, to keep the product inheritance, the V9R3 or later versions are compatible with the uncentralized management mode. 2.1.1 Decentralized Management of Environment Alarm IDs In the V9R1, you need to modify the alarm names of the default BTS alarm IDs on the BSC6000 Local Maintenance Terminal (LMT) and the M2000. After modification, the new alarm names are displayed on the M2000 and the BSC.The alarms generated from the same port of the board in the same slot and frame of the same type of BTSs have the same alarm ID. Therefore, in the V9R1 version, after the names of the environment alarm of a BTS is changed, you do not need change the names of the environment alarms that are reported from the same type of BTS deployed during the cutover.In the V9R1 version, a certain type of external environment alarm equipment is connected only to a fixed port of the BTS to satisfy the planning requirement. The alarm IDs are respectively bound with the ports. When the alarm is connected to an idle port due to the port fault, the BTS reports a different alarm ID, which leads to an unidentified alarm.2.1.2 Centralized Management of Environment Alarm IDs In V9R3 or later versions, the environment alarm IDs in centralized management are planned as follows:The valid range of the BSC environment alarm IDs is from 65334 to 65383.

The valid range of the BTS environment alarm IDs is from 65384 to 65533.

The BTS environment alarm ports can be bound to the previously defined alarm ID range through the M2000 (before binding, the port of V9R1 is bound with a fixed environment alarm ID to report the alarm), and the alarm names can be changed on the M2000. After the settings, the environment alarms reported by the BTS are represented by the modified environment alarm ID and alarm name.

Table 2-1 describes the settings related to the centralized management mode of the environment alarm IDs.

Table 2-2 Setting items related to the centralized management of the environment alarm IDsSetting ItemDetailsMethod

Setting the binding relation between the alarm ID and the portThe setting is to bind the vector consisting of the BTS, the cabinet number, frame number, slot number, and the port number with the environment alarm ID to set up a correlation.Make the setting on the M2000 or directly using the MML (that is, the SET ALMPORT command).

Setting related to the port1. The setting is to define the condition for generating the alarm (indicating whether the alarm is generated for receiving the high level or the low level)2. Enable the port (the alarm can be reported only after the port is enabled).

Modifying the alarm attributeThe setting is to modify the alarm name and alarm level of an environment alarm ID. Make the setting on the M2000.

2.2 Configuring BTS Environment Alarm in BSC6000 V900R001+M2000 V2R3The BTS V9R1 environment alarm IDs are managed in the decentralized management mode. Do as follows to configure the environment alarms: Step 2 Modify the names and definitions of BTS environment alarms on the BSC6000. Step 3 Modify the names and definitions of BTS environment alarms on the M2000V2R3. To ensure the name consistency of the same environment alarm IDs on the BSC6000 and the M2000, you need to plan the modification solution for the BTS environment alarm IDs. 2.2.2 Modifying the NE Environment Alarm Name Through the BSC6000 Local Maintenance TerminalYou can change the names of BTS V9R1 environment alarms through the BSC6000 Local Maintenance Terminal by doing as follows:Step 4 Log in to the BSC6000 Local Maintenance Terminal. A window as shown in Figure 2-1 is displayed.Figure 2-11 Login window of BSC6000 local maintenance terminal

Step 5 Choose Alarm Maintenance > Query Alarm Configuration Settings. The Query Alarm Configuration Settings dialog box is displayed, as shown in Figure 2-2.Figure 2-12 Setting the condition for querying the alarm configuration

Step 6 Select Start Alarm ID or End Alarm ID in the Alarm ID area and select the alarm level from the Alarm Severity area as required, and select the values from the Modification Flag, Shield Flag and To Alarm Box Flag drop-down lists according to the actual condition. Then, click OK.

The query result is displayed in the BSC local maintenance terminal, as shown in Figure 2-3. Figure 2-13 Alarm query result

After the alarm configuration is queried successfully, a dialog box prompting successful query is displayed.Step 7 In the Query Alarm Configuration window, right-click the extended alarm ID to be modified. Select Set Environment Alarm Configuration from the shortcut menu. The Set Environment Alarm Configuration dialog box as shown in Figure 2-4 is displayed.Figure 2-14 Setting parameters of the environment alarm configuration

Step 8 Modify the settings of Alarm ID and Alarm Severity and click OK. If the modification succeeds, the Information dialog box is displayed prompting the operation result, as shown in Figure 2-5.Figure 2-15 Successfully setting parameters of the environment alarm configuration

2.2.3 Modifying the Name of NMS Environment AlarmTo modify the alarm name in the NMS environment in the M2000V2R3, you need to modify the SQL script through the M2000 server. For details, see the Guide of Modifying the Alarm Name for M2000V2 Products.

The modification includes the operations such as querying whether the modified environment alarm ID exists, uploading the environment alarm ID definition file, and enabling the modification to the environment alarm to take effect.

The procedures for modifying alarm names through the M2000 are as follows:Step 9 Upload the Query_AlarmInfo.sh script to the /tmp directory on the server in the ASCII mode and run the following commands one by one to query the alarm modification records.#. /opt/OMC/svc_profile.sh

#bash

#cd /tmp

#chmod 777 Query_AlarmInfo.sh

#. ./Query_AlarmInfo.sh

Step 10 When the following prompt is displayed, enter the required information following the prompt. The entered information is displayed in the interface and is recorded in the result.txt file in the same directory at the same time. Figure 2-6 shows the information on the screen. Figure 2-16 Querying the records of modifying environment alarms on the M2000

Because the script is case sensitive, ensure that the entered name must be identical with the print name for running the script when you enter the NE name to be modified. You can query multiple environment alarm IDs by running the script once. Because the query for the second time overwrites the first one, you need change the file name of the result.txt file and save it for backup. Step 11 According to the planned modification solution for the BTS environment alarm ID, create an input.txt file with a text editor. Figure 2-7 shows the file format, where, AlarmID refers to the alarm ID to be modified and AlarmName is the new name of this alarm. Figure 2-17 Example of the input.txt file

In the input.txt file, acts as the separator and separates the AlarmID and AlarmName fields. This file is not compatible with any Chinese character and does not allow any blank line. Step 12 The NE and NMS version corresponding to the input.txt file must be indicated and the file is archived to the M2000 for backup. Step 13 Upload the update_alm_exp.sh script and the input.txt file to the /tmp directory on the M2000 server through the ASCII code. These two files must be stored in the same directory. Run the following commands in turn. #. /opt/OMC/svc_profile.sh

#bash

#cd /tmp

#chmod 777 update_alm_exp.sh

#. ./update_alm_exp.sh

Press Enter for each command line in step 5 to run the commands in turn.Step 14 Enter the NE name BSC6000 following the prompt in the interface, as shown in Figure 2-8.Figure 2-18 Information displayed in the interface

Because the script is case sensitive, ensure that the entered name must be identical with the print name for running the script when you enter the NE name to be modified. Step 15 Run the following commands in turn, and restart the alarm server to make the modified alarm name take effect.# . /opt/OMC/svc_profile.sh

# svc_adm -cmd reload# svc_adm -cmd restartsvc FaultService

Step 16 Run the command to check whether all the M2000 servers are started. The command is # svc_adm -cmd status | grep not run.If no information is returned, it means that all services of the M2000 are started.----End2.3 Configuring BTS Environment Alarm in BSC6000 V900R003+M2000 V2R3

This solution is applicable for configuring the environment alarm IDs in the BSC6000 and M2000 V2R3 of V9R3 or later versions.To configure the environment alarm in the BSC6000 V900R003+M2000 V2R3 solution of R3 or later versions, do as follows: Step 17 Bind the environment alarm parameters through the MML on the Local Maintenance Terminal. Step 18 Modify the NE environment alarm names and definitions through the BSC6000 Local Maintenance Terminal.Step 19 Modify the names and definitions of the BTS environment alarm on the M2000V2R3. Step 20 Enable the alarm function on the environment monitoring board in the BSC6000 Local Maintenance Terminal interface in the V9R3 version. The V9R8 version does not involve this step. ----End2.3.2 Planning User-Defined Environment Alarm IDs of BSC6000 R900R003To perform the centralized management to the environment alarms reported from various sites, the environment alarms in V9R3 or later versions are planned as follows: The valid configuration range of the alarm ID over the signal input port in the BSC environment is from 65334 to 65383.The valid configuration range of the alarm ID over the signal input port in the BTS environment is from 65384 to 65533.

Prior to configuring the environment alarms, plan all environment alarm IDs. The planning mode is to allocate one unique environment alarm ID to each kind of environment alarms. For example:54384 indicates Fire Alarm.

54385 indicates Smoke Alarm.The planning of environment alarm IDs complies with the following principles: The planning of the environment alarm ID needs to ensure that all the BSCs under the same M2000 are consistent. If this M2000 is attached to others NEs, keep the same planning with the environment alarms on these NEs as much as possible.

Because the V9R1 version fails to support the environment alarms in the centralized management mode, the reported environment alarm ID can use the default one reported by the BTS. If there are both V9R1 and V9R3 or later versions under this M2000, it occurs that one environment alarm type corresponds to two or more environment alarm IDs (in the R1 version, the environment alarm ID of each type of the BTS may differ). You should evaluate the influence to the system according to the actual situation. The following example explains how to plan the environment alarm IDs of the BSC6000:Set the environment signal input ports on the DEMU board in slot 2 of frame 0 in BTS 3012 as follows:

Step 21 Enable ports 1 to 3 for inputting the BTS environment signals.

Step 22 Set the alarm IDs to 6552765529.

Step 23 Set the alarm names respectively to Fire alarm, Smoke and Water, and set the port type to the digital port.

Step 24 Set the alarm level to the high level.

Step 25 Set the alarm severity to Critical, Major, and Minor.Step 26 According to the site and network planning, you can obtain the following contents, as shown in Table 2-2. By following the principle shown in Figure 1-5 and referring to Table 2-2, connect the sensor to the BTS to set up the channel for reporting alarms. ----EndFor the detailed operations, see related manuals.

Table 2-3 Board-cable-sensor-alarm IDBoard TypeWireSensorAlarm

Pin of the ConnectorWire ColorPort No.BTS Alarm IDInitial BSC Alarm IDTrigger LevelRe-planned Alarm ID

DEMUX1.2White 1Intruder0x916438High Level65527

X1.36Blue

DEMUX1.3White2Fire Panel0x926440High Level65528

X1.37Orange

DEMUX1.4White3Smoke Detector0x936442High Level65529

X1.38Green

2.3.3 Binding Environment Alarm ID Parameters on the MML Local Maintenance Terminal

Prior to the operation, ensure that software version of the MML Local Maintenance Terminal is consistent with the BSC software version of the BTS. This operation is to bind the default BTS environment alarm IDs with the environment alarm IDs planned by the BSC6000. The bound BTS environment alarm ID parameters include the BTS name, the frame and slot location in the monitoring unit, the monitoring port for the BTS environment alarm, the alarm enabling flag, and the alarm signal type and value constraint.The procedures are as follows:Step 27 Starting the BSC6000 Local Maintenance Terminal. Use one of the following three methods to start the BSC6000 Local Maintenance Terminal.

Choose Start > All Programs > Huawei Local Maintenance Terminal > Local Maintenance Terminal. A dialog box is displayed, as shown in Figure 2-13.

On the BSC6000 Local Maintenance Terminal, choose System > Start MML Client.

On the BSC6000 Local Maintenance Terminal, click to start the Local Maintenance Terminal.

The latter two methods are not displayed on the login dialog box.

Figure 2-19 Login window of BSC6000 Local Maintenance Terminal

Step 28 Select the preset office direction. Step 29 Enter the user name and password and select a user type. Step 30 Click Login to start the Local Maintenance Terminal. The Local Maintenance Terminal window is displayed, as shown in Figure 2-10.Figure 2-20 Local Maintenance Terminal

Step 31 To enter the SET ALMPORT command to set the parameter of the port for inputting the environment alarm signal, click . The interface for inputting the parameter is displayed. Enter the parameter, as shown in Figure 2-11.

Figure 2-21 Interface of inputting the command parameter.

The whole command is SET ALMPORT: SITENAME="BTS3012", SRN=0, SN=2, PN=1, SW=OPEN, AID=65527, PT=BOOL, AVOL=HIGH;,where, SITENAME is the name of the BTS, SRN is the frame number of the BTS, SN is the slot number, PN is the port number in the board, SW is the port switch, AID is the alarm ID to be configured, PT is port type, and AVOL is the alarm level.

The operation object of SET ALMPORT is each specific physical environment alarm port. Assuming the DEMU board is configured for N BTSs, to modify alarm ID 6438 over port 1 on the DEMU board, you need run N SET ALMPORT commands to respectively modify these physical ports. You can edit the MML commands in advance and deliver them once in the batch command form.

For the usage of the MML batch command, see the BSC MML Command Reference.

Step 32 Click or press F9 to run the MML command.

Step 33 Repeat steps 5 and 6. All the configurations are completed.

----End2.3.4 Modifying the BTS Environment Alarm Name and Definition on the BSC6000 Local Maintenance TerminalIn section 2.3.2, the parameters of the BTS environment alarm ID are set. The task of this section is to modify the BTS environment alarm name and definition, rename the bound environment alarm ID, and set Alarm Severity and To Alarm Box Flag. The procedures are as follows:Step 34 Log in to the BSC6000 LMT. A window is displayed, as shown in Figure 2-12. Figure 2-22 Interface of the BSC6000 Local Maintenance Terminal

Step 35 Choose Alarm Maintenance > Query Alarm Configuration Settings. The Query Alarm Configuration Settings dialog box is displayed. Select the filter conditions according to the actual situation, as shown in Figure 2-13.Figure 2-23 Query Alarm Configuration Settings dialog box

Step 36 Click OK. The Query Alarm Configuration window is displayed, as shown in Figure 2-14.Figure 2-24 Query Alarm Configuration window

Step 37 Right-click the line where alarm ID 65527 is located and select Set Environment Alarm Configuration from the shortcut menu. The Set Environment Alarm Configuration dialog box is displayed, as shown in Figure 2-15.Figure 2-25 Setting parameters of the environment alarm configuration

Step 38 Change Alarm Name from BTS Custom Environment Alarm 144 to Fire and Alarm Severity from Major to Critical.Step 39 Click OK. The information dialog box is displayed, as shown in Figure 2-16.Figure 2-26 Successful setting

Step 40 Click OK. Repeat steps 4 to 6. All the configurations are completed.----End2.3.5 Modifying the Name of M2000V2R3 Environment AlarmTo modify the alarm name in the NMS environment in the M2000V2R3 version, you need to modify the SQL script through the M2000 server. For details, see Guide of Modifying the Alarm Name for M2000V2 Products.

The modification includes the operations such as querying whether the modified environment alarm ID has existed, uploading the environment alarm ID definition file and enabling the modification to the environment alarm to take effect.

For the detailed operation, see section 2.2.3 .

2.4 Configuring BTS Environment Alarm in BSC6000 V900R003+M2000 V2R6

This solution is applicable for configuring the environment alarm ID in the BSC6000 and M2000 V2R6 of V9R3 and later versions.The operation to an NE can reach the same result as the operations of setting the environment alarm signal input port on the MML Local Maintenance Terminal and binding the user-defined alarm through the M2000. However, the M2000 provides the function of importing and exporting the configuration script according to the excel file and querying the current NE environment alarm binding correlation, both of which facilitate the operation.The operation of modifying the alarm name carried on the M2000 takes effect on both the M2000 and the NE at the same time, but the operation performed on the NE through the BSC6000 Local Maintenance Terminal only modifies the data on the NE, and it cannot modify the data on the M2000. The alarm name is stored respectively on the M2000 and the NE as the independent data.Therefore, to configure the environment alarm in the BSC6000 V900R003+M2000 V2R3 solution of R3 or later versions, do as follows: Step 41 Bind the parameters of the BTS environment alarm IDs through the M2000V2R6.

Step 42 Modify the names and definitions of BTS environment alarms on the M2000V2R6.

Step 43 Enable the alarm function on the environment monitoring board in the BSC Local Maintenance Terminal interface in the V9R3 version. The V9R8 version does not involve this step.

Besides the parameters in section 2.3.2 , the parameters of the BTS alarm IDs mentioned in this section also include the NE name. The definitions of the environment alarm names are the same as those in section 2.3.2 .2.4.2 Binding the Parameters of the NE BTS Environment Alarm ID through M2000V2R6The operation of binding the parameters of the BTS environment alarm ID is performed by binding and adding the user-defined alarms. The procedures are as follows:Step 44 Log in to the M2000 mobile element management system. Figure 2-17 shows the interface for the successful login.Figure 2-27 M2000 Mobile Element Management System interface

Step 45 Choose Monitor > Settings > NE Alarm Settings. The NE Alarm Settings tab page is displayed in the iManager M2000 Mobile Element Management System window, as shown in Figure 2-18.Figure 2-28 Binding an alarm

Step 46 Click Export Template on the Alarm Binding tab page to export the alarm binding template. Save the template as the binding data.xls file.Step 47 Open the binding data.xls file, fill in the file with the alarm binding information, and save it. Step 48 Click Import in the Alarm Binding tab page to import the binding data.xls file into the client.Step 49 Click Apply on the Alarm Binding tab page.The Information dialog box is displayed to give the operation result.

For the cut over BTS, repeat these procedures. ----End2.4.3 Modifying the Name and Definition of the M2000V2R6 Environment AlarmThe operation of modifying the name and definition of the M2000V2R6 environment alarm is performed by adding the user-defined alarm and adding the user-defined alarm binding. The procedures are as follows.Step 50 Repeat steps 1 and 2 of binding the user-defined alarms. Step 51 As shown in Figure 2-19, select the Alarm Definition tab under the User Defined Alarm tab.Figure 2-29 NE Alarm Settings tab

Step 52 Click Add. The Add User Defined Alarm dialog box is displayed, as shown in Figure 2-20.Figure 2-30 Adding the user-defined alarm

Step 53 Select BSC6000 under Ne Type, set Alarm Name and Alarm Level, and click OK.

The user-defined alarm to be added is displayed in the list on the Alarm Definition tab page, and each record has .

Step 54 Click Apply on the Alarm Definition tab page. disappears. The Information dialog box is displayed to give the operation result.

Repeat these procedures to the BTS newly cut over. ----End3 Difference of Environment Alarm Configurations Between BSC6000 Versions 3.1 Differences of Environment Alarm Configurations Between BSC6000 Versions The default environment alarm IDs reported by the BTS can be reported by the BSC6000 V9R1 to the alarm subsystem and the M2000. The BSC6000 V9R1 does not support to bind the BTS environment alarm port to the specified alarm ID again. In the mean time, the V9R1 supports to modify the name of the default the alarm ID reported by the BTS, but the operation of modifying the alarm name needs to be performed respectively on the M2000 and the BSC6000 Local Maintenance Terminal. In the V9R1 version, the external equipment of the BTS environment alarm can be connected to the fixed port for satisfying the BTS requirement. Because the alarm and the port are bound, the environment alarm reported by the BTS cannot be identified once the connection is changed to another idle port due to the failure on this port.V9R8 is upgraded on the basis of V9R3, and there is not difference in the environment alarm configuration.The V9R3 version supports to bind the BTS environment alarm port with the BTS environment alarm ID range first and then modify the alarm name of the bound alarm ID.In addition, for V9R1 and V9R3, the environment alarm monitoring on the BTS monitoring board needs to be enabled to monitor the environment after the BTS environment alarm ID is set.

The V9R8 version does not involve this step. The process for enabling the environment alarm monitoring on the BTS monitoring board is as follows: Step 55 Select BTS3012 from the Management Tree on the Local Maintenance Terminal (taking BTS3012 as an example), as shown in Figure 3-1.Figure 3-31 Selecting a BTS

Step 56 Right-click BTS3012 and select Configure Site Board Attributes from the shortcut menu, as shown in Figure 3-2.Figure 3-32 Shortcut menu

Step 57 The Configure Site Board Attributes dialog box is displayed. Click Configure Site Board Attributes, as shown in Figure 3-3.Figure 3-33 Configure Site Boards Attributes dialog box

Step 58 The Site Device Attributes dialog box is displayed. Right-click the DEMU board (the DEMU board is taken as an example) to be set, as shown in Figure 3-4.Figure 3-34 Site Device Attributes dialog box

Step 59 Select Configure Board Attributes from the shortcut menu. The Basic Attributes of Site Board dialog box is displayed. On the Configure Site Board Attributes tab page, set Board Parameter Configuration Enabled to Yes, as shown in Figure 3-5.Figure 3-35 Enabling the board alarm

Step 60 Click OK to return to Figure 3-1 and then click OK. The environment alarm monitoring is enabled.3.2 Environment Alarm Configuration in V9R1 Upgraded to V9R3 or Later Versions After V9R1 is upgraded to V9R3, the environment alarm name configured in the V9R1 version is still available. You can handle the configurations after the upgrade in the following ways: 1. If no cutover is performed to add new BTSs to the upgraded BSC6000 or the newly BTSs added to the BSC6000 is of the original type configured in V9R1, the new environment alarms do not need to be configured. However, the original environment alarm cannot be renamed in the V9R3 version after the upgrade. For all the BTSs upgraded to V9R3, you can bind the alarm IDs again and set the alarm name with the method in the V9R3 version, that is, the environment alarm ID is switched from the uncentralized management mode to the centralized management.

The switching of the environment alarm ID from the uncentralized management to the centralized management influences the alarm interconnection of the northbound NMS due to the change of the environment alarm ID. In the site with the northbound alarm interconnection, the customer and the field technical personnel should evaluate and adapt (such as planning the environment alarm ID at the NMS level) the influence to the northbound alarm interconnection (such as the alarm ID change).2. If the type of the added BTS is new, use the method in the V9R3 version to bind the alarm ID and modify the alarm name of the cut over BTSs to realize the centralized management. Of course, you can make the settings according to those in the uncentralized management to the BTS environment alarm ID in the V9R1 version. 3. If all the BSCs under the same M2000 are upgraded to V9R3, it is recommended to configure the BSC environment alarm upgraded from V9R1 again in the mode in V9R3 to keep the unified management to the environment alarms under the same M2000.If V9R1 is upgraded to V9R8, the alarm configuration is performed in the same way.2008-05-29HUAWEI ConfidentialPage10, Total35

_1273605195.xlsSheet1

BTS TypeMonitoring EquipmentSubrack No.-Slot No.Monitoring CableCable CoresCore ColorMonitoring Equipment PortPort NO.AlmID

BTS3006CEMUSubrack 3 - Slot 2Cable of the SensorNot ProvidedNot ProvidedS1+/S1-16212

Cable of the SensorNot ProvidedNot ProvidedS2+/S2-26214

Cable of the SensorNot ProvidedNot ProvidedS3+/S3-36216

Cable of the SensorNot ProvidedNot ProvidedS4+/S4-46218

Cable of the SensorNot ProvidedNot ProvidedS5+/S5-56220

Cable of the SensorNot ProvidedNot ProvidedS6+/S6-66222

Cable of the SensorNot ProvidedNot ProvidedS7+/S7-76224

Cable of the SensorNot ProvidedNot ProvidedS8+/S8-86226

Cable of the SensorNot ProvidedNot ProvidedS9+/S9-96228

Cable of the SensorNot ProvidedNot ProvidedS10+/S10-106230

Cable of the SensorNot ProvidedNot ProvidedS11+/S11-116232

Cable of the SensorNot ProvidedNot ProvidedS12+/S12-126234

Cable of the SensorNot ProvidedNot ProvidedS13+/S13-136236

Cable of the SensorNot ProvidedNot ProvidedS14+/S14-146238

Cable of the SensorNot ProvidedNot ProvidedS15+/S15-156240

Cable of the SensorNot ProvidedNot ProvidedS16+/S16-166242

Cable of the SensorNot ProvidedNot ProvidedS17+/S17-176244

Cable of the SensorNot ProvidedNot ProvidedS18+/S18-186246

Cable of the SensorNot ProvidedNot ProvidedS19+/S19-196248

Cable of the SensorNot ProvidedNot ProvidedS20+/S20-206250

Cable of the SensorNot ProvidedNot ProvidedS21+/S21-216252

Cable of the SensorNot ProvidedNot ProvidedS22+/S22-226254

Cable of the SensorNot ProvidedNot ProvidedS23+/S23-236256

Cable of the SensorNot ProvidedNot ProvidedS24+/S24-246258

Cable of the SensorNot ProvidedNot ProvidedS25+/S25-256260

Cable of the SensorNot ProvidedNot ProvidedS26+/S26-266262

Cable of the SensorNot ProvidedNot ProvidedS27+/S27-276264

Cable of the SensorNot ProvidedNot ProvidedS28+/S28-286266

Cable of the SensorNot ProvidedNot ProvidedS29+/S29-296268

Cable of the SensorNot ProvidedNot ProvidedS30+/S30-306270

Cable of the SensorNot ProvidedNot ProvidedS31+/S31-316272

Cable of the SensorNot ProvidedNot ProvidedS32+/S32-326274

DPMUSubrack 3 - Slot 0Cable of the SensorNot ProvidedNot Provided16032

Cable of the SensorNot ProvidedNot Provided26034

Cable of the SensorNot ProvidedNot Provided36036

Cable of the SensorNot ProvidedNot Provided46038

Cable of the SensorNot ProvidedNot Provided56040

Cable of the SensorNot ProvidedNot Provided66042

Cable of the SensorNot ProvidedNot Provided76044

APMUSubrack 3 - Slot 0Cable of the SensorNot ProvidedNot Provided15742

Cable of the SensorNot ProvidedNot Provided25744

Cable of the SensorNot ProvidedNot Provided35746

DOMUSubrack 1 - Slot 0A BTS006C/BTS3002E external alarm cableX1.7/X1.5blue/white14944

A BTS006C/BTS3002E external alarm cableX1.8/X1.5orange/white24946

A BTS006C/BTS3002E external alarm cableX1.9/X1.11green/white34948

A BTS006C/BTS3002E external alarm cableX1.10/X1.11broWn/white44950

Cable of the SensorNot ProvidedNot Provided54952

Cable of the SensorNot ProvidedNot Provided64954

Cable of the SensorNot ProvidedNot Provided74956

Cable of the SensorNot ProvidedNot Provided84958

Cable of the SensorNot ProvidedNot Provided94960

Cable of the SensorNot ProvidedNot Provided104962

Cable of the SensorNot ProvidedNot Provided114964

Cable of the SensorNot ProvidedNot Provided124966

Cable of the SensorNot ProvidedNot Provided134968

Cable of the SensorNot ProvidedNot Provided144970

Cable of the SensorNot ProvidedNot Provided154972

Cable of the SensorNot ProvidedNot Provided164974

Cable of the SensorNot ProvidedNot Provided174976

Cable of the SensorNot ProvidedNot Provided184978

Cable of the SensorNot ProvidedNot Provided194980

Cable of the SensorNot ProvidedNot Provided204982

Cable of the SensorNot ProvidedNot Provided214984

Cable of the SensorNot ProvidedNot Provided224986

Cable of the SensorNot ProvidedNot Provided234988

Cable of the SensorNot ProvidedNot Provided244990

Cable of the SensorNot ProvidedNot Provided254992

Cable of the SensorNot ProvidedNot Provided264994

Cable of the SensorNot ProvidedNot Provided274996

Cable of the SensorNot ProvidedNot Provided284998

Cable of the SensorNot ProvidedNot Provided295000

Cable of the SensorNot ProvidedNot Provided305002

Cable of the SensorNot ProvidedNot Provided315004

Cable of the SensorNot ProvidedNot Provided325006

BTS3002EDOMUSubrack 1 - Slot 0A BTS006C/BTS3002E external alarm cableX1.7/X1.5blue/white14944

A BTS006C/BTS3002E external alarm cableX1.8/X1.5orange/white24946

A BTS006C/BTS3002E external alarm cableX1.9/X1.11green/white34948

A BTS006C/BTS3002E external alarm cableX1.10/X1.11broWn/white44950

Cable of the SensorNot ProvidedNot Provided54952

Cable of the SensorNot ProvidedNot Provided64954

Cable of the SensorNot ProvidedNot Provided74956

Cable of the SensorNot ProvidedNot Provided84958

Cable of the SensorNot ProvidedNot Provided94960

Cable of the SensorNot ProvidedNot Provided104962

Cable of the SensorNot ProvidedNot Provided114964

Cable of the SensorNot ProvidedNot Provided124966

Cable of the SensorNot ProvidedNot Provided134968

Cable of the SensorNot ProvidedNot Provided144970

Cable of the SensorNot ProvidedNot Provided154972

Cable of the SensorNot ProvidedNot Provided164974

Cable of the SensorNot ProvidedNot Provided174976

Cable of the SensorNot ProvidedNot Provided184978

Cable of the SensorNot ProvidedNot Provided194980

Cable of the SensorNot ProvidedNot Provided204982

Cable of the SensorNot ProvidedNot Provided214984

Cable of the SensorNot ProvidedNot Provided224986

Cable of the SensorNot ProvidedNot Provided234988

Cable of the SensorNot ProvidedNot Provided244990

Cable of the SensorNot ProvidedNot Provided254992

Cable of the SensorNot ProvidedNot Provided264994

Cable of the SensorNot ProvidedNot Provided274996

Cable of the SensorNot ProvidedNot Provided284998

Cable of the SensorNot ProvidedNot Provided295000

Cable of the SensorNot ProvidedNot Provided305002

Cable of the SensorNot ProvidedNot Provided315004

Cable of the SensorNot ProvidedNot Provided325006

BTS3012DEMUSubrack 0 - Slot 2The BTS3012 Boolean input cableW1.36/W1.2blue/whiteNot Provided16438

W1.37/W1.3orange/whiteNot Provided26440

W1.38/W1.4green/whiteNot Provided36442

W1.39/W1.5brown/whiteNot Provided46444

W1.40/W1.6grey/whiteNot Provided56446

W1.41/W1.7blue/redNot Provided66448

W1.42/W1.8orange/redNot Provided76450

W1.43/W1.9green/redNot Provided86452

W1.44/W1.10brown/redNot Provided96454

W1.45/W1.11grey/redNot Provided106456

W1.46/W1.12blue/blackNot Provided116458

W1.47/W1.13orange/blackNot Provided126460

W1.48/W1.14green/blackNot Provided136462

W1.49/W1.15brown/blackNot Provided146464

W1.50/W1.16grey/blackNot Provided156466

W1.51/W1.17blue/yellowNot Provided166422

W1.52/W1.18blue/whiteNot Provided176424

W1.53/W1.19orange/whiteNot Provided186426

W1.54/W1.20green/whiteNot Provided196428

W1.55/W1.21brown/whiteNot Provided206430

W1.56/W1.22grey/whiteNot Provided216432

W1.57/W1.23blue/redNot Provided226434

W1.58/W1.24orange/redNot Provided236436

W1.59/W1.25green/redNot Provided246468

W1.60/W1.26brown/redNot Provided256470

W1.61/W1.27grey/redNot Provided266472

W1.62/W1.28blue/blackNot Provided276474

W1.63/W1.29orange/blackNot Provided286476

W1.64/W1.30green/blackNot Provided296478

W1.65/W1.31brown/blackNot Provided306480

W1.66/W1.32grey/blackNot Provided316482

W1.67/W1.33blue/yellowNot Provided326484

BTS3012EACSubrack 0 - Slot 1Cable of the SensorNot ProvidedNot ProvidedS1+/S1-16438

Cable of the SensorNot ProvidedNot ProvidedS2+/S2-26440

Cable of the SensorNot ProvidedNot ProvidedS3+/S3-36442

Cable of the SensorNot ProvidedNot ProvidedS4+/S4-46444

Cable of the SensorNot ProvidedNot ProvidedS5+/S5-56446

Cable of the SensorNot ProvidedNot ProvidedS6+/S6-66448

Cable of the SensorNot ProvidedNot ProvidedS7+/S7-76450

Cable of the SensorNot ProvidedNot ProvidedS8+/S8-86452

Cable of the SensorNot ProvidedNot ProvidedS9+/S9-96454

Cable of the SensorNot ProvidedNot ProvidedS10+/S10-106456

Cable of the SensorNot ProvidedNot ProvidedS11+/S11-116458

Cable of the SensorNot ProvidedNot ProvidedS12+/S12-126460

Cable of the SensorNot ProvidedNot ProvidedS13+/S13-136462

Cable of the SensorNot ProvidedNot ProvidedS14+/S14-146464

Cable of the SensorNot ProvidedNot ProvidedS15+/S15-156466

Cable of the SensorNot ProvidedNot ProvidedS16+/S16-166422

Cable of the SensorNot ProvidedNot ProvidedS17+/S17-176424

Cable of the SensorNot ProvidedNot ProvidedS18+/S18-186426

Cable of the SensorNot ProvidedNot ProvidedS19+/S19-196428

Cable of the SensorNot ProvidedNot ProvidedS20+/S20-206430

Cable of the SensorNot ProvidedNot ProvidedS21+/S21-216432

Cable of the SensorNot ProvidedNot ProvidedS22+/S22-226434

Cable of the SensorNot ProvidedNot ProvidedS23+/S23-236436

Cable of the SensorNot ProvidedNot ProvidedS24+/S24-246148

Cable of the SensorNot ProvidedNot ProvidedS25+/S25-256150

Cable of the SensorNot ProvidedNot ProvidedS26+/S26-266152

Cable of the SensorNot ProvidedNot ProvidedS27+/S27-276154

Cable of the SensorNot ProvidedNot ProvidedS28+/S28-286156

Cable of the SensorNot ProvidedNot ProvidedS29+/S29-296158

Cable of the SensorNot ProvidedNot ProvidedS30+/S30-306160

Cable of the SensorNot ProvidedNot ProvidedS31+/S31-316162

Cable of the SensorNot ProvidedNot ProvidedS32+/S32-326164

BTS3012DPMUSubrack 0 - Slot 15Cable of the SensorNot ProvidedNot ProvidedNot Provided15654

Cable of the SensorNot ProvidedNot ProvidedNot Provided25656

Cable of the SensorNot ProvidedNot ProvidedNot Provided35658

Cable of the SensorNot ProvidedNot ProvidedNot Provided45660

Cable of the SensorNot ProvidedNot ProvidedNot Provided55662

Cable of the SensorNot ProvidedNot ProvidedNot Provided65664

Cable of the SensorNot ProvidedNot ProvidedNot Provided75666

BTS3012DTMUSubrack 0 - Slot 0 or Slot 1Cable of the SensorNot ProvidedNot ProvidedNot Provided14778

Cable of the SensorNot ProvidedNot ProvidedNot Provided24780

Cable of the SensorNot ProvidedNot ProvidedNot Provided34782

Cable of the SensorNot ProvidedNot ProvidedNot Provided44784

Cable of the SensorNot ProvidedNot ProvidedNot Provided54786

Cable of the SensorNot ProvidedNot ProvidedNot Provided64788

Cable of the SensorNot ProvidedNot ProvidedNot Provided74790

Cable of the SensorNot ProvidedNot ProvidedNot Provided84792

Cable of the SensorNot ProvidedNot ProvidedNot Provided94842

Cable of the SensorNot ProvidedNot ProvidedNot Provided104844

Cable of the SensorNot ProvidedNot ProvidedNot Provided114846

Cable of the SensorNot ProvidedNot ProvidedNot Provided124848

Cable of the SensorNot ProvidedNot ProvidedNot Provided134850

Cable of the SensorNot ProvidedNot ProvidedNot Provided144852

Cable of the SensorNot ProvidedNot ProvidedNot Provided154854

Cable of the SensorNot ProvidedNot ProvidedNot Provided164856

Cable of the SensorNot ProvidedNot ProvidedNot Provided174858

Cable of the SensorNot ProvidedNot ProvidedNot Provided184860

Cable of the SensorNot ProvidedNot ProvidedNot Provided194862

Cable of the SensorNot ProvidedNot ProvidedNot Provided204864

Cable of the SensorNot ProvidedNot ProvidedNot Provided214866

Cable of the SensorNot ProvidedNot ProvidedNot Provided224868

Cable of the SensorNot ProvidedNot ProvidedNot Provided234870

Cable of the SensorNot ProvidedNot ProvidedNot Provided244872

BTS3012V2DTMUSubrack 0 - Slot 0 or Slot 1Cable of the SensorNot ProvidedNot ProvidedNot Provided14778

Cable of the SensorNot ProvidedNot ProvidedNot Provided24780

Cable of the SensorNot ProvidedNot ProvidedNot Provided34782

Cable of the SensorNot ProvidedNot ProvidedNot Provided44784

Cable of the SensorNot ProvidedNot ProvidedNot Provided54786

Cable of the SensorNot ProvidedNot ProvidedNot Provided64788

Cable of the SensorNot ProvidedNot ProvidedNot Provided74790

Cable of the SensorNot ProvidedNot ProvidedNot Provided84792

Cable of the SensorNot ProvidedNot ProvidedNot Provided94842

Cable of the SensorNot ProvidedNot ProvidedNot Provided104844

Cable of the SensorNot ProvidedNot ProvidedNot Provided114846

Cable of the SensorNot ProvidedNot ProvidedNot Provided124848

Cable of the SensorNot ProvidedNot ProvidedNot Provided134850

Cable of the SensorNot ProvidedNot ProvidedNot Provided144852

Cable of the SensorNot ProvidedNot ProvidedNot Provided154854

Cable of the SensorNot ProvidedNot ProvidedNot Provided164856

Cable of the SensorNot ProvidedNot ProvidedNot Provided174858

Cable of the SensorNot ProvidedNot ProvidedNot Provided184860

Cable of the SensorNot ProvidedNot ProvidedNot Provided194862

Cable of the SensorNot ProvidedNot ProvidedNot Provided204864

Cable of the SensorNot ProvidedNot ProvidedNot Provided214866

Cable of the SensorNot ProvidedNot ProvidedNot Provided224868

Cable of the SensorNot ProvidedNot ProvidedNot Provided234870

Cable of the SensorNot ProvidedNot ProvidedNot Provided244872

BTS3012AEDPMUSubrack 0 - Slot 15Cable of the SensorNot ProvidedNot ProvidedNPMI-JDC115668

Cable of the SensorNot ProvidedNot ProvidedNPMI-JDC225670

Cable of the SensorNot ProvidedNot ProvidedNPMI-JDC335672

Cable of the SensorNot ProvidedNot ProvidedNPMI-JDC445674

Cable of the SensorNot ProvidedNot ProvidedNPMI-JDC555676

Cable of the SensorNot ProvidedNot ProvidedNPMI-JDC665678

Cable of the SensorNot ProvidedNot ProvidedNPMI-JDC775680

BTS3012AEDTMUSubrack 0 - Slot 0 or Slot 1Cable of the SensorNot ProvidedNot Provided14874

Cable of the SensorNot ProvidedNot Provided24876

Cable of the SensorNot ProvidedNot Provided34878

Cable of the SensorNot ProvidedNot Provided44880

Cable of the SensorNot ProvidedNot Provided54882

Cable of the SensorNot ProvidedNot Provided64884

Cable of the SensorNot ProvidedNot Provided74886

Cable of the SensorNot ProvidedNot Provided84888

Cable of the SensorNot ProvidedNot Provided94890

Cable of the SensorNot ProvidedNot Provided104892

Cable of the SensorNot ProvidedNot Provided114894

Cable of the SensorNot ProvidedNot Provided124896

Cable of the SensorNot ProvidedNot Provided134898

Cable of the SensorNot ProvidedNot Provided144900

Cable of the SensorNot ProvidedNot Provided154902

Cable of the SensorNot ProvidedNot Provided164904

Cable of the SensorNot ProvidedNot Provided174906

Cable of the SensorNot ProvidedNot Provided184908

Cable of the SensorNot ProvidedNot Provided194910

Cable of the SensorNot ProvidedNot Provided204912

Cable of the SensorNot ProvidedNot Provided214914

Cable of the SensorNot ProvidedNot Provided224916

Cable of the SensorNot ProvidedNot Provided234918

Cable of the SensorNot ProvidedNot Provided244920

BTS30TMUSubrack 0 - Slot 14 or Slot 15The extension alarm cable A/ The extension alarm cable BX1.28BLUE(2 BLACK DOT)12246

X1.9BLUE(2 RED DOT)22248

X1.27GREEN(3 BLACK DOT)32250

X1.8GREEN(3 RED DOT)42252

X1.26ORANGE(3 BLACK DOT)52254

X1.7ORANGE(3 RED DOT)62256

X1.25PINK(3 BLACK DOT)72258

X1.6GRAY(2 RED DOT)82262

X1.14GREEN(3 RED DOT)102268

X1.1PINK(1 RED DOT)172592

X1.20GRAY(3 RED DOT)162594

X1.19GRAY(3 BLACK DOT)152596

X1.18PINK(4 RED DOT)142598

X1.5GREEN(1 RED DOT)212600

X1.10PINK(3 RED DOT)92602

X1.4ORANGE(1 BLACK DOT)202604

X1.8BLUE(1 BLACK DOT)242606

X1.3ORANGE(1 RED DOT)192608

X1.7BLUE(1 RED DOT)232610

X1.2PINK(1 BLACK DOT)182612

X1.6GREEN(1 BLACK DOT)222614

X1.17BLUE(3 BLACK DOT)132616

X1.16BLUE(3 RED DOT)122618

X1.15GREEN(3 BLACK DOT)112620

BTS30EACSubrack 0 - Slot 13Cable of the SensorNot ProvidedNot ProvidedS1+/S1-12402

Cable of the SensorNot ProvidedNot ProvidedS2+/S2-22404

Cable of the SensorNot ProvidedNot ProvidedS3+/S3-32406

Cable of the SensorNot ProvidedNot ProvidedS4+/S4-42408

Cable of the SensorNot ProvidedNot ProvidedS5+/S5-52410

Cable of the SensorNot ProvidedNot ProvidedS6+/S6-62412

Cable of the SensorNot ProvidedNot ProvidedS7+/S7-72414

Cable of the SensorNot ProvidedNot ProvidedS8+/S8-82416

Cable of the SensorNot ProvidedNot ProvidedS9+/S9-92418

Cable of the SensorNot ProvidedNot ProvidedS10+/S10-102420

Cable of the SensorNot ProvidedNot ProvidedS11+/S11-112422

Cable of the SensorNot ProvidedNot ProvidedS12+/S12-122424

Cable of the SensorNot ProvidedNot ProvidedS13+/S13-132426

Cable of the SensorNot ProvidedNot ProvidedS14+/S14-142428

Cable of the SensorNot ProvidedNot ProvidedS15+/S15-152430

Cable of the SensorNot ProvidedNot ProvidedS16+/S16-162386

Cable of the SensorNot ProvidedNot ProvidedS17+/S17-172388

Cable of the SensorNot ProvidedNot ProvidedS18+/S18-182390

Cable of the SensorNot ProvidedNot ProvidedS19+/S19-192392

Cable of the SensorNot ProvidedNot ProvidedS20+/S20-202394

Cable of the SensorNot ProvidedNot ProvidedS21+/S21-212396

Cable of the SensorNot ProvidedNot ProvidedS22+/S22-222398

Cable of the SensorNot ProvidedNot ProvidedS23+/S23-232400

Cable of the SensorNot ProvidedNot ProvidedS24+/S24-242458

Cable of the SensorNot ProvidedNot ProvidedS25+/S25-252460

Cable of the SensorNot ProvidedNot ProvidedS26+/S26-262462

Cable of the SensorNot ProvidedNot ProvidedS27+/S27-272464

Cable of the SensorNot ProvidedNot ProvidedS28+/S28-282466

Cable of the SensorNot ProvidedNot ProvidedS29+/S29-292468

Cable of the SensorNot ProvidedNot ProvidedS30+/S30-302470

Cable of the SensorNot ProvidedNot ProvidedS31+/S31-312472

Cable of the SensorNot ProvidedNot ProvidedS32+/S32-322474

BTS312TMUSubrack 0 - Slot 14 or Slot 15The extension alarm cable A/ The extension alarm cable BX1.28BLUE(2 BLACK DOT)12246

X1.9BLUE(2 RED DOT)22248

X1.27GREEN(3 BLACK DOT)32250

X1.8GREEN(3 RED DOT)42252

X1.26ORANGE(3 BLACK DOT)52254

X1.7ORANGE(3 RED DOT)62256

X1.25PINK(3 BLACK DOT)72258

X1.6GRAY(2 RED DOT)82262

X1.14GREEN(3 RED DOT)102268

X1.1PINK(1 RED DOT)172592

X1.20GRAY(3 RED DOT)162594

X1.19GRAY(3 BLACK DOT)152596

X1.18PINK(4 RED DOT)142598

X1.5GREEN(1 RED DOT)212600

X1.10PINK(3 RED DOT)92602

X1.4ORANGE(1 BLACK DOT)202604

X1.8BLUE(1 BLACK DOT)242606

X1.3ORANGE(1 RED DOT)192608

X1.7BLUE(1 RED DOT)232610

X1.2PINK(1 BLACK DOT)182612

X1.6GREEN(1 BLACK DOT)222614

X1.17BLUE(3 BLACK DOT)132616

X1.16BLUE(3 RED DOT)122618

X1.15GREEN(3 BLACK DOT)112620

BTS312EACSubrack 0 - Slot 13Cable of the SensorNot ProvidedNot ProvidedS1+/S1-12402

Cable of the SensorNot ProvidedNot ProvidedS2+/S2-22404

Cable of the SensorNot ProvidedNot ProvidedS3+/S3-32406

Cable of the SensorNot ProvidedNot ProvidedS4+/S4-42408

Cable of the SensorNot ProvidedNot ProvidedS5+/S5-52410

Cable of the SensorNot ProvidedNot ProvidedS6+/S6-62412

Cable of the SensorNot ProvidedNot ProvidedS7+/S7-72414

Cable of the SensorNot ProvidedNot ProvidedS8+/S8-82416

Cable of the SensorNot ProvidedNot ProvidedS9+/S9-92418

Cable of the SensorNot ProvidedNot ProvidedS10+/S10-102420

Cable of the SensorNot ProvidedNot ProvidedS11+/S11-112422

Cable of the SensorNot ProvidedNot ProvidedS12+/S12-122424

Cable of the SensorNot ProvidedNot ProvidedS13+/S13-132426

Cable of the SensorNot ProvidedNot ProvidedS14+/S14-142428

Cable of the SensorNot ProvidedNot ProvidedS15+/S15-152430

Cable of the SensorNot ProvidedNot ProvidedS16+/S16-162386

Cable of the SensorNot ProvidedNot ProvidedS17+/S17-172388

Cable of the SensorNot ProvidedNot ProvidedS18+/S18-182390

Cable of the SensorNot ProvidedNot ProvidedS19+/S19-192392

Cable of the SensorNot ProvidedNot ProvidedS20+/S20-202394

Cable of the SensorNot ProvidedNot ProvidedS21+/S21-212396

Cable of the SensorNot ProvidedNot ProvidedS22+/S22-222398

Cable of the SensorNot ProvidedNot ProvidedS23+/S23-232400

Cable of the SensorNot ProvidedNot ProvidedS24+/S24-242458

Cable of the SensorNot ProvidedNot ProvidedS25+/S25-252460

Cable of the SensorNot ProvidedNot ProvidedS26+/S26-262462

Cable of the SensorNot ProvidedNot ProvidedS27+/S27-272464

Cable of the SensorNot ProvidedNot ProvidedS28+/S28-282466

Cable of the SensorNot ProvidedNot ProvidedS29+/S29-292468

Cable of the SensorNot ProvidedNot ProvidedS30+/S30-302470

Cable of the SensorNot ProvidedNot ProvidedS31+/S31-312472

Cable of the SensorNot ProvidedNot ProvidedS32+/S32-322474

BTS3006ATMUSubrack 0 - Slot 15The extension alarm cable A/ The extension alarm cable BX1.28BLUE(2 BLACK DOT)12246

X1.9BLUE(2 RED DOT)22248

X1.27GREEN(3 BLACK DOT)32250

X1.8GREEN(3 RED DOT)42252

X1.26ORANGE(3 BLACK DOT)52254

X1.7ORANGE(3 RED DOT)62256

X1.25PINK(3 BLACK DOT)72258

X1.6GRAY(2 RED DOT)82262

X1.14GREEN(3 RED DOT)102268

X1.1PINK(1 RED DOT)172592

X1.20GRAY(3 RED DOT)162594

X1.19GRAY(3 BLACK DOT)152596

X1.18PINK(4 RED DOT)142598

X1.5GREEN(1 RED DOT)212600

X1.10PINK(3 RED DOT)92602

X1.4ORANGE(1 BLACK DOT)202604

X1.8BLUE(1 BLACK DOT)242606

X1.3ORANGE(1 RED DOT)192608

X1.7BLUE(1 RED DOT)232610

X1.2PINK(1 BLACK DOT)182612

X1.6GREEN(1 BLACK DOT)222614

X1.17BLUE(3 BLACK DOT)132616

X1.16BLUE(3 RED DOT)122618

X1.15GREEN(3 BLACK DOT)112620

BTS3006AEMUASubrack 0 - Slot 11Cable of the SensorNot ProvidedNot ProvidedS1+/S1-12402

Cable of the SensorNot ProvidedNot ProvidedS2+/S2-22404

Cable of the SensorNot ProvidedNot ProvidedS3+/S3-32406

Cable of the SensorNot ProvidedNot ProvidedS4+/S4-42408

Cable of the SensorNot ProvidedNot ProvidedS5+/S5-52410

Cable of the SensorNot ProvidedNot ProvidedS6+/S6-62412

Cable of the SensorNot ProvidedNot ProvidedS7+/S7-72414

Cable of the SensorNot ProvidedNot ProvidedS8+/S8-82416

Cable of the SensorNot ProvidedNot ProvidedS9+/S9-92418

Cable of the SensorNot ProvidedNot ProvidedS10+/S10-102420

Cable of the SensorNot ProvidedNot ProvidedS11+/S11-112422

Cable of the SensorNot ProvidedNot ProvidedS12+/S12-122424

Cable of the SensorNot ProvidedNot ProvidedS13+/S13-132426

Cable of the SensorNot ProvidedNot ProvidedS14+/S14-142428

Cable of the SensorNot ProvidedNot ProvidedS15+/S15-152430

Cable of the SensorNot ProvidedNot ProvidedS16+/S16-162386

Cable of the SensorNot ProvidedNot ProvidedS17+/S17-172388

Cable of the SensorNot ProvidedNot ProvidedS18+/S18-182390

Cable of the SensorNot ProvidedNot ProvidedS19+/S19-192392

Cable of the SensorNot ProvidedNot ProvidedS20+/S20-202394

Cable of the SensorNot ProvidedNot ProvidedS21+/S21-212396

Cable of the SensorNot ProvidedNot ProvidedS22+/S22-222398

Cable of the SensorNot ProvidedNot ProvidedS23+/S23-232400

Cable of the SensorNot ProvidedNot ProvidedS24+/S24-242458

Cable of the SensorNot ProvidedNot ProvidedS25+/S25-252460

Cable of the SensorNot ProvidedNot ProvidedS26+/S26-262462

Cable of the SensorNot ProvidedNot ProvidedS27+/S27-272464

Cable of the SensorNot ProvidedNot ProvidedS28+/S28-282466

Cable of the SensorNot ProvidedNot ProvidedS29+/S29-292468

Cable of the SensorNot ProvidedNot ProvidedS30+/S30-302470

Cable of the SensorNot ProvidedNot ProvidedS31+/S31-312472

Cable of the SensorNot ProvidedNot ProvidedS32+/S32-322474

BTS3012ATMUSubrack 0 - Slot 17The extension alarm cable A/ The extension alarm cable BX1.28BLUE(2 BLACK DOT)12246

X1.9BLUE(2 RED DOT)22248

X1.27GREEN(3 BLACK DOT)32250

X1.8GREEN(3 RED DOT)42252

X1.26ORANGE(3 BLACK DOT)52254

X1.7ORANGE(3 RED DOT)62256

X1.25PINK(3 BLACK DOT)72258

X1.6GRAY(2 RED DOT)82262

X1.14GREEN(3 RED DOT)102268

X1.1PINK(1 RED DOT)172592

X1.20GRAY(3 RED DOT)162594

X1.19GRAY(3 BLACK DOT)152596

X1.18PINK(4 RED DOT)142598

X1.5GREEN(1 RED DOT)212600

X1.10PINK(3 RED DOT)92602

X1.4ORANGE(1 BLACK DOT)202604

X1.8BLUE(1 BLACK DOT)242606

X1.3ORANGE(1 RED DOT)192608

X1.7BLUE(1 RED DOT)232610

X1.2PINK(1 BLACK DOT)182612

X1.6GREEN(1 BLACK DOT)222614

X1.17BLUE(3 BLACK DOT)132616

X1.16BLUE(3 RED DOT)122618

X1.15GREEN(3 BLACK DOT)112620

BTS3012AEMUASubrack 0 - Slot 13Cable of the SensorNot ProvidedNot ProvidedS1+/S1-12402

Cable of the SensorNot ProvidedNot ProvidedS2+/S2-22404

Cable of the SensorNot ProvidedNot ProvidedS3+/S3-32406

Cable of the SensorNot ProvidedNot ProvidedS4+/S4-42408

Cable of the SensorNot ProvidedNot ProvidedS5+/S5-52410

Cable of the SensorNot ProvidedNot ProvidedS6+/S6-62412

Cable of the SensorNot ProvidedNot ProvidedS7+/S7-72414

Cable of the SensorNot ProvidedNot ProvidedS8+/S8-82416

Cable of the SensorNot ProvidedNot ProvidedS9+/S9-92418

Cable of the SensorNot ProvidedNot ProvidedS10+/S10-102420

Cable of the SensorNot ProvidedNot ProvidedS11+/S11-112422

Cable of the SensorNot ProvidedNot ProvidedS12+/S12-122424

Cable of the SensorNot ProvidedNot ProvidedS13+/S13-132426

Cable of the SensorNot ProvidedNot ProvidedS14+/S14-142428

Cable of the SensorNot ProvidedNot ProvidedS15+/S15-152430

Cable of the SensorNot ProvidedNot ProvidedS16+/S16-162386

Cable of the SensorNot ProvidedNot ProvidedS17+/S17-172388

Cable of the SensorNot ProvidedNot ProvidedS18+/S18-182390

Cable of the SensorNot ProvidedNot ProvidedS19+/S19-192392

Cable of the SensorNot ProvidedNot ProvidedS20+/S20-202394

Cable of the SensorNot ProvidedNot ProvidedS21+/S21-212396

Cable of the SensorNot ProvidedNot ProvidedS22+/S22-222398

Cable of the SensorNot ProvidedNot ProvidedS23+/S23-232400

Cable of the SensorNot ProvidedNot ProvidedS24+/S24-242458

Cable of the SensorNot ProvidedNot ProvidedS25+/S25-252460

Cable of the SensorNot ProvidedNot ProvidedS26+/S26-262462

Cable of the SensorNot ProvidedNot ProvidedS27+/S27-272464

Cable of the SensorNot ProvidedNot ProvidedS28+/S28-282466

Cable of the SensorNot ProvidedNot ProvidedS29+/S29-292468

Cable of the SensorNot ProvidedNot ProvidedS30+/S30-302470

Cable of the SensorNot ProvidedNot ProvidedS31+/S31-312472

Cable of the SensorNot ProvidedNot ProvidedS32+/S32-322474

BTS3002CIOMUSubrack 0 - Slot 0The BTS3002C alarm cable AW1blue/whiteX1.7/X1.513730

W1orange/whiteX1.8/X1.523732

W1green/whiteX1.9/X1.533734

43736

BTS3002CEACSubrack 0 - Slot 2W5(RS485)Cable of the SensorNot Provided13860

Cable of the SensorNot Provided23862

Cable of the SensorNot Provided33864

Cable of the SensorNot Provided43866

Cable of the SensorNot Provided53868

Cable of the SensorNot Provided63870

Cable of the SensorNot Provided73872

Cable of the SensorNot Provided83874

Cable of the SensorNot Provided93876

Cable of the SensorNot Provided103878

NOTE:

For the BTS3012, the common subrack is defined as subrack 0.

Note that the alarms (labelled Not Provided) are reported through the RS485 communication specification, and you are advised to use the full-colored cables.

Slot 0 and Slot 1 are not operating in active/standby mode.

&L&G&C&F&R&","

&L&D&C&R&P&N

Sheet2

&L&G&C&F&R&","

&L&D&C&R&P&N

Sheet3

&L&G&C&F&R&","

&L&D&C&R&P&N