Upload
eng-amr-elorbany
View
268
Download
15
Tags:
Embed Size (px)
DESCRIPTION
BSC6000 Guide to Configuration of BTS Environment Alarms on the BSC6000
Citation preview
Guide to Configuration of BTS Environment Alarms on the BSC6000For internal use only
Document codeProduct nameGSM BSC6000
Target readersOverseas &DomesticsProduct versionAll Versions
Edited byDocumentation Dept. WNDocument versionV1.1
Guide to Configuration of BTS Environment Alarms on the BSC6000Drafted by:Tian BaiheDate:2008-03-26
Reviewed by:Wang Dong , Liu
Ying , Li KaiDate:2008-03-28
Approved by:Liu YingDate:2008-04-26
Huawei Technologies Co, LtdAll Rights Reserved41 Basic Knowledge
41.1 Sensor
41.1.1 Dry-Contact Boolean Value Output Sensor
51.1.2 OC-output Boolean Value Output Sensor
51.1.3 Voltage-output Boolean Value Output Sensor
51.1.4 Analog Input Sensor
51.2 Survey of Environment Alarm
51.2.1 Introduction to the Environment Alarm
61.2.2 Sensors of the BTS
81.2.3 Cables Related to BTS Alarms
81.2.4 BTS Monitoring Unit
112 Configuring BTS Environment Alarms
112.1 Purpose
112.1.1 Decentralized Management of Environment Alarm IDs
122.1.2 Centralized Management of Environment Alarm IDs
122.2 Configuring BTS Environment Alarm in BSC6000 V900R001+M2000 V2R3
132.2.2 Modifying the NE Environment Alarm Name Through the BSC6000 Local Maintenance Terminal
152.2.3 Modifying the Name of NMS Environment Alarm
182.3 Configuring BTS Environment Alarm in BSC6000 V900R003+M2000 V2R3
182.3.1 Planning User-Defined Environment Alarm IDs of BSC6000 R900R003
202.3.2 Binding Environment Alarm ID Parameters on the MML Local Maintenance Terminal
222.3.3 Modifying the BTS Environment Alarm Name and Definition on the BSC6000 Local Maintenance Terminal
252.3.4 Modifying the Name of M2000V2R3 Environment Alarm
252.4 Configuring BTS Environment Alarm in BSC6000 V900R003+M2000 V2R6
262.4.2 Binding the Parameters of the NE BTS Environment Alarm ID through M2000V2R6
272.4.3 Modifying the Name and Definition of the M2000V2R6 Environment Alarm
303 Difference of Environment Alarm Configurations Between BSC6000 Versions
303.1 Differences of Environment Alarm Configurations Between BSC6000 Versions
343.2 Environment Alarm Configuration in V9R1 Upgraded to V9R3 or Later Versions
TOC \h \z \t "Figure Description" \c
4Figure 1-1 Connection mode of the passive dry-contact Boolean value output sensor
4Figure 1-2 Connection mode of the active dry-contact Boolean value output sensor
5Figure 1-3 Connection mode of the OC-output Boolean value output sensor
5Figure 1-4 The connection mode of the voltage-output Boolean value output sensor
6Figure 1-5 Networking of BTS environment alarm equipment
7Figure 1-6 Wiring terminal of the door status sensor
7Figure 1-7 Wiring terminal of the water sensor
7Figure 1-8 The wiring terminal of the smoke sensor
8Figure 1-9 Wiring terminal of the infrared sensor
8Figure 1-10 Wiring terminal of the humidity and temperature sensor
13Figure 2-1 Login window of BSC6000 local maintenance terminal
14Figure 2-2 Setting the condition for querying the alarm configuration
14Figure 2-3 Alarm query result
15Figure 2-4 Setting parameters of the environment alarm configuration
15Figure 2-5 Successfully setting parameters of the environment alarm configuration
16Figure 2-6 Querying the records of modifying environment alarms on the M2000
17Figure 2-7 Example of the input.txt file
17Figure 2-8 Information displayed in the interface
21Figure 2-9 Login window of BSC6000 Local Maintenance Terminal
21Figure 2-10 Local Maintenance Terminal
22Figure 2-11 Interface of inputting the command parameter.
23Figure 2-12 Interface of the BSC6000 Local Maintenance Terminal
23Figure 2-13 Query Alarm Configuration Settings dialog box
24Figure 2-14 Query Alarm Configuration window
24Figure 2-15 Setting parameters of the environment alarm configuration
25Figure 2-16 Successful setting
26Figure 2-17 M2000 Mobile Element Management System interface
27Figure 2-18 Binding an alarm
28Figure 2-19 NE Alarm Settings tab
28Figure 2-20 Adding the user-defined alarm
31Figure 3-1 Selecting a BTS
32Figure 3-2 Shortcut menu
32Figure 3-3 Configure Site Boards Attributes dialog box
33Figure 3-4 Site Device Attributes dialog box
34Figure 3-5 Enabling the board alarm
1 Basic Knowledge1.1 SensorBased on different types of output signals, the sensors are categorized into the dry-contact Boolean value output sensor, the OC-output Boolean value output sensor, the voltage-output Boolean value output sensor, and the analog input sensor. 1.1.1 Dry-Contact Boolean Value Output SensorThe dry-contact Boolean value output sensors are categorized into: Passive dry-contact Boolean value output sensorA passive dry-contact Boolean value output sensor has no power input terminal, and it generally has two signal output terminals (S+/S-). Figure 1-1 shows the connection mode.Figure 1-1 Connection mode of the passive dry-contact Boolean value output sensor
Active dry-contact Boolean value output sensorAn active dry-contact Boolean value output sensor has two power input terminals (POWER+/POWER-) and two signal output terminals (S+/S-). Figure 1-2 shows the connection mode.Figure 1-2 Connection mode of the active dry-contact Boolean value output sensor
If the level is low when the loop is close, a low-voltage alarm is generated. If the level is high when the loop is open, a high-voltage alarm is generated.1.1.2 OC-output Boolean Value Output SensorThe OC-output Boolean value output sensor has two power input terminals (POWER+/POWER-) and one signal output terminal (Sout). Figure 1-3 shows the connection mode.Figure 1-3 Connection mode of the OC-output Boolean value output sensor
If the level is low when the loop is close, a low-voltage alarm is generated. If the level is high when the loop is open, a high-voltage alarm is generated. 1.1.3 Voltage-output Boolean Value Output SensorThe voltage-output Boolean value output sensor has two power input terminals (POWER+/POWER-) and one signal output terminal (Sout). Figure 1-4 shows the connection mode.Figure 1-4 The connection mode of the voltage-output Boolean value output sensor
The lower level at loop close indicates the lower voltage, while the high level at loop disconnection. 1.1.4 Analog Input SensorThe analog input has a mathematic or linear correlation. The gradually changing current (or the voltage) corresponds to a changing value according to the correlation. For example, the sensor monitors the temperature and inputs an analog value through changing current, and the processor calculates the temperature value according to a mathematic correlation.1.2 Survey of Environment Alarm1.2.1 Introduction to the Environment AlarmTo ensure stable operation of the equipment in a mobile communication equipment room, different sensors and software devices are used to monitor the operation of the equipment in the equipment room in real time, such as the power supply and the environment of the equipment room. The power supply monitoring refers to the monitoring of the mains supply, DC power distribution module, rectifier module, and storage battery. The environment monitoring in the equipment room involves the temperature, humidity, access control, water, smoke, distribution, and door status.With the extended alarm ports on the BTS, the auxiliary equipment of the BTS such as the power supply, switching power supply and storage battery can be monitored. With the Environment Monitoring Unit (EMU), the temperature, humidity, and smoke can be monitored and the intrusion can be detected in real time. The environment can be monitored according to the preset value and alarms are generated when the preset threshold is exceeded. Figure 1-5 shows the networking of the environment alarm system.Figure 1-5 Networking of BTS environment alarm equipment
1.2.2 Sensors of the BTSSensors are used to detect the environment variables of the BTS and report various environment alarms. The sensors special for the BTS are classified into the door status sensor, water sensor, smoke sensor, infrared sensor, and temperature and humidity sensor.
Door status sensor
The door status sensor is placed at the intersection of the door frame and door. It detects the opening and closing of the door. Figure 1-6 shows the wiring terminal. Figure 1-6 Wiring terminal of the door status sensor
Water sensor
The water sensor is horizontally placed at the places that are subject to be immersed in water in the equipment room. It detects whether the BTS is immersed in water. Figure 1-7 shows the wiring terminal. Figure 1-7 Wiring terminal of the water sensor
Smoke sensor
The smoke sensor is placed at the center of the ceiling. It detects whether the BTS or the equipment room is on fire. Figure shows the wiring terminal. Figure 1-8 The wiring terminal of the smoke sensor
Infrared sensor
The infrared sensor is placed on the wall, 1.5 m above the floor. It detects whether there is illegal intrusion. Figure 1-9 shows the wiring terminal. Figure 1-9 Wiring terminal of the infrared sensor
Humidity and temperature sensor
The temperature and humidity sensor is placed on the wall, 1.5 m above the floor. It detects whether the temperature or humidity exceeds the threshold. Figure 1-10 shows the wiring terminal. Figure 1-10 Wiring terminal of the humidity and temperature sensor
1.2.3 Cables Related to BTS AlarmsDifferent BTS may have different interfaces. For details, see section Correlation Between Expanded Boolean Value Alarms and Cables of BTS in the BTS Alarm Reference.1.2.4 BTS Monitoring UnitTable 1-1 lists the monitoring units and BTS alarm IDs supported by the BTSs of different models. Table 1-1 Mapping between BTSs and monitoring unitsSite TypeMonitoring UnitNumber of Supported Extended Alarms
BTS30TMU24
EAC32
BTS312TMU24
EAC32
BTS3006ATMU24
EAC32
BTS3012ATMU24
EAC32
BTS3002CIOMU4
EAC32
BTS3012DTMU24
DPMU14
EAC32
DEMU40
BTS3012AEDTMU24
DPMU7
DEMU40
BTS3006CDTMU32
APMU3
DPMU7
DEMU32
BTS3002EDTMU32
APMU3
DPMU7
DEMU40
BTS3012_IIDTMU24
DPMU14
EAC32
DEMU40
DBS3036GTMU16
APMU3
DPMU7
DEMU40
BTS3036AGTMU16
APMU3
DPMU7
DEMU40
FMUA4
BTS3036AGTMU16
APMU3
DPMU7
DEMU40
FMUA4
1.2.5 Mapping between cables and monitoring unitsFor more detailsrefer to the accessory as below.
2 Configuring BTS Environment Alarms2.1 PurposeIn the BSC6000 products, the BTS environment alarm IDs are managed in two modes, that is, the decentralized management mode and the centralized management mode. Decentralized management mode In the BSC6000 V900R001 (V9R1 for short), the environment alarms of the BTS and BSC are managed in the decentralized management mode. The discontinuous environment alarm IDs for different BTS types are not suitable for the centralized management and are not easy to use. Centralized management modeIn the BSC6000 V900R003 (V9R3 for short), the environment alarm function is optimized. The environment alarm baseline of Huawei is used to unify environment alarm IDs to one fixed range and the binding correlation between the alarm ID and the BTS monitoring port is established through the M2000 or directly with the MML.In the meantime, to keep the product inheritance, the V9R3 or later versions are compatible with the uncentralized management mode. 2.1.1 Decentralized Management of Environment Alarm IDs In the V9R1, you need to modify the alarm names of the default BTS alarm IDs on the BSC6000 Local Maintenance Terminal (LMT) and the M2000. After modification, the new alarm names are displayed on the M2000 and the BSC.The alarms generated from the same port of the board in the same slot and frame of the same type of BTSs have the same alarm ID. Therefore, in the V9R1 version, after the names of the environment alarm of a BTS is changed, you do not need change the names of the environment alarms that are reported from the same type of BTS deployed during the cutover.In the V9R1 version, a certain type of external environment alarm equipment is connected only to a fixed port of the BTS to satisfy the planning requirement. The alarm IDs are respectively bound with the ports. When the alarm is connected to an idle port due to the port fault, the BTS reports a different alarm ID, which leads to an unidentified alarm.2.1.2 Centralized Management of Environment Alarm IDs In V9R3 or later versions, the environment alarm IDs in centralized management are planned as follows:The valid range of the BSC environment alarm IDs is from 65334 to 65383.
The valid range of the BTS environment alarm IDs is from 65384 to 65533.
The BTS environment alarm ports can be bound to the previously defined alarm ID range through the M2000 (before binding, the port of V9R1 is bound with a fixed environment alarm ID to report the alarm), and the alarm names can be changed on the M2000. After the settings, the environment alarms reported by the BTS are represented by the modified environment alarm ID and alarm name.
Table 2-1 describes the settings related to the centralized management mode of the environment alarm IDs.
Table 2-2 Setting items related to the centralized management of the environment alarm IDsSetting ItemDetailsMethod
Setting the binding relation between the alarm ID and the portThe setting is to bind the vector consisting of the BTS, the cabinet number, frame number, slot number, and the port number with the environment alarm ID to set up a correlation.Make the setting on the M2000 or directly using the MML (that is, the SET ALMPORT command).
Setting related to the port1. The setting is to define the condition for generating the alarm (indicating whether the alarm is generated for receiving the high level or the low level)2. Enable the port (the alarm can be reported only after the port is enabled).
Modifying the alarm attributeThe setting is to modify the alarm name and alarm level of an environment alarm ID. Make the setting on the M2000.
2.2 Configuring BTS Environment Alarm in BSC6000 V900R001+M2000 V2R3The BTS V9R1 environment alarm IDs are managed in the decentralized management mode. Do as follows to configure the environment alarms: Step 2 Modify the names and definitions of BTS environment alarms on the BSC6000. Step 3 Modify the names and definitions of BTS environment alarms on the M2000V2R3. To ensure the name consistency of the same environment alarm IDs on the BSC6000 and the M2000, you need to plan the modification solution for the BTS environment alarm IDs. 2.2.2 Modifying the NE Environment Alarm Name Through the BSC6000 Local Maintenance TerminalYou can change the names of BTS V9R1 environment alarms through the BSC6000 Local Maintenance Terminal by doing as follows:Step 4 Log in to the BSC6000 Local Maintenance Terminal. A window as shown in Figure 2-1 is displayed.Figure 2-11 Login window of BSC6000 local maintenance terminal
Step 5 Choose Alarm Maintenance > Query Alarm Configuration Settings. The Query Alarm Configuration Settings dialog box is displayed, as shown in Figure 2-2.Figure 2-12 Setting the condition for querying the alarm configuration
Step 6 Select Start Alarm ID or End Alarm ID in the Alarm ID area and select the alarm level from the Alarm Severity area as required, and select the values from the Modification Flag, Shield Flag and To Alarm Box Flag drop-down lists according to the actual condition. Then, click OK.
The query result is displayed in the BSC local maintenance terminal, as shown in Figure 2-3. Figure 2-13 Alarm query result
After the alarm configuration is queried successfully, a dialog box prompting successful query is displayed.Step 7 In the Query Alarm Configuration window, right-click the extended alarm ID to be modified. Select Set Environment Alarm Configuration from the shortcut menu. The Set Environment Alarm Configuration dialog box as shown in Figure 2-4 is displayed.Figure 2-14 Setting parameters of the environment alarm configuration
Step 8 Modify the settings of Alarm ID and Alarm Severity and click OK. If the modification succeeds, the Information dialog box is displayed prompting the operation result, as shown in Figure 2-5.Figure 2-15 Successfully setting parameters of the environment alarm configuration
2.2.3 Modifying the Name of NMS Environment AlarmTo modify the alarm name in the NMS environment in the M2000V2R3, you need to modify the SQL script through the M2000 server. For details, see the Guide of Modifying the Alarm Name for M2000V2 Products.
The modification includes the operations such as querying whether the modified environment alarm ID exists, uploading the environment alarm ID definition file, and enabling the modification to the environment alarm to take effect.
The procedures for modifying alarm names through the M2000 are as follows:Step 9 Upload the Query_AlarmInfo.sh script to the /tmp directory on the server in the ASCII mode and run the following commands one by one to query the alarm modification records.#. /opt/OMC/svc_profile.sh
#bash
#cd /tmp
#chmod 777 Query_AlarmInfo.sh
#. ./Query_AlarmInfo.sh
Step 10 When the following prompt is displayed, enter the required information following the prompt. The entered information is displayed in the interface and is recorded in the result.txt file in the same directory at the same time. Figure 2-6 shows the information on the screen. Figure 2-16 Querying the records of modifying environment alarms on the M2000
Because the script is case sensitive, ensure that the entered name must be identical with the print name for running the script when you enter the NE name to be modified. You can query multiple environment alarm IDs by running the script once. Because the query for the second time overwrites the first one, you need change the file name of the result.txt file and save it for backup. Step 11 According to the planned modification solution for the BTS environment alarm ID, create an input.txt file with a text editor. Figure 2-7 shows the file format, where, AlarmID refers to the alarm ID to be modified and AlarmName is the new name of this alarm. Figure 2-17 Example of the input.txt file
In the input.txt file, acts as the separator and separates the AlarmID and AlarmName fields. This file is not compatible with any Chinese character and does not allow any blank line. Step 12 The NE and NMS version corresponding to the input.txt file must be indicated and the file is archived to the M2000 for backup. Step 13 Upload the update_alm_exp.sh script and the input.txt file to the /tmp directory on the M2000 server through the ASCII code. These two files must be stored in the same directory. Run the following commands in turn. #. /opt/OMC/svc_profile.sh
#bash
#cd /tmp
#chmod 777 update_alm_exp.sh
#. ./update_alm_exp.sh
Press Enter for each command line in step 5 to run the commands in turn.Step 14 Enter the NE name BSC6000 following the prompt in the interface, as shown in Figure 2-8.Figure 2-18 Information displayed in the interface
Because the script is case sensitive, ensure that the entered name must be identical with the print name for running the script when you enter the NE name to be modified. Step 15 Run the following commands in turn, and restart the alarm server to make the modified alarm name take effect.# . /opt/OMC/svc_profile.sh
# svc_adm -cmd reload# svc_adm -cmd restartsvc FaultService
Step 16 Run the command to check whether all the M2000 servers are started. The command is # svc_adm -cmd status | grep not run.If no information is returned, it means that all services of the M2000 are started.----End2.3 Configuring BTS Environment Alarm in BSC6000 V900R003+M2000 V2R3
This solution is applicable for configuring the environment alarm IDs in the BSC6000 and M2000 V2R3 of V9R3 or later versions.To configure the environment alarm in the BSC6000 V900R003+M2000 V2R3 solution of R3 or later versions, do as follows: Step 17 Bind the environment alarm parameters through the MML on the Local Maintenance Terminal. Step 18 Modify the NE environment alarm names and definitions through the BSC6000 Local Maintenance Terminal.Step 19 Modify the names and definitions of the BTS environment alarm on the M2000V2R3. Step 20 Enable the alarm function on the environment monitoring board in the BSC6000 Local Maintenance Terminal interface in the V9R3 version. The V9R8 version does not involve this step. ----End2.3.2 Planning User-Defined Environment Alarm IDs of BSC6000 R900R003To perform the centralized management to the environment alarms reported from various sites, the environment alarms in V9R3 or later versions are planned as follows: The valid configuration range of the alarm ID over the signal input port in the BSC environment is from 65334 to 65383.The valid configuration range of the alarm ID over the signal input port in the BTS environment is from 65384 to 65533.
Prior to configuring the environment alarms, plan all environment alarm IDs. The planning mode is to allocate one unique environment alarm ID to each kind of environment alarms. For example:54384 indicates Fire Alarm.
54385 indicates Smoke Alarm.The planning of environment alarm IDs complies with the following principles: The planning of the environment alarm ID needs to ensure that all the BSCs under the same M2000 are consistent. If this M2000 is attached to others NEs, keep the same planning with the environment alarms on these NEs as much as possible.
Because the V9R1 version fails to support the environment alarms in the centralized management mode, the reported environment alarm ID can use the default one reported by the BTS. If there are both V9R1 and V9R3 or later versions under this M2000, it occurs that one environment alarm type corresponds to two or more environment alarm IDs (in the R1 version, the environment alarm ID of each type of the BTS may differ). You should evaluate the influence to the system according to the actual situation. The following example explains how to plan the environment alarm IDs of the BSC6000:Set the environment signal input ports on the DEMU board in slot 2 of frame 0 in BTS 3012 as follows:
Step 21 Enable ports 1 to 3 for inputting the BTS environment signals.
Step 22 Set the alarm IDs to 6552765529.
Step 23 Set the alarm names respectively to Fire alarm, Smoke and Water, and set the port type to the digital port.
Step 24 Set the alarm level to the high level.
Step 25 Set the alarm severity to Critical, Major, and Minor.Step 26 According to the site and network planning, you can obtain the following contents, as shown in Table 2-2. By following the principle shown in Figure 1-5 and referring to Table 2-2, connect the sensor to the BTS to set up the channel for reporting alarms. ----EndFor the detailed operations, see related manuals.
Table 2-3 Board-cable-sensor-alarm IDBoard TypeWireSensorAlarm
Pin of the ConnectorWire ColorPort No.BTS Alarm IDInitial BSC Alarm IDTrigger LevelRe-planned Alarm ID
DEMUX1.2White 1Intruder0x916438High Level65527
X1.36Blue
DEMUX1.3White2Fire Panel0x926440High Level65528
X1.37Orange
DEMUX1.4White3Smoke Detector0x936442High Level65529
X1.38Green
2.3.3 Binding Environment Alarm ID Parameters on the MML Local Maintenance Terminal
Prior to the operation, ensure that software version of the MML Local Maintenance Terminal is consistent with the BSC software version of the BTS. This operation is to bind the default BTS environment alarm IDs with the environment alarm IDs planned by the BSC6000. The bound BTS environment alarm ID parameters include the BTS name, the frame and slot location in the monitoring unit, the monitoring port for the BTS environment alarm, the alarm enabling flag, and the alarm signal type and value constraint.The procedures are as follows:Step 27 Starting the BSC6000 Local Maintenance Terminal. Use one of the following three methods to start the BSC6000 Local Maintenance Terminal.
Choose Start > All Programs > Huawei Local Maintenance Terminal > Local Maintenance Terminal. A dialog box is displayed, as shown in Figure 2-13.
On the BSC6000 Local Maintenance Terminal, choose System > Start MML Client.
On the BSC6000 Local Maintenance Terminal, click to start the Local Maintenance Terminal.
The latter two methods are not displayed on the login dialog box.
Figure 2-19 Login window of BSC6000 Local Maintenance Terminal
Step 28 Select the preset office direction. Step 29 Enter the user name and password and select a user type. Step 30 Click Login to start the Local Maintenance Terminal. The Local Maintenance Terminal window is displayed, as shown in Figure 2-10.Figure 2-20 Local Maintenance Terminal
Step 31 To enter the SET ALMPORT command to set the parameter of the port for inputting the environment alarm signal, click . The interface for inputting the parameter is displayed. Enter the parameter, as shown in Figure 2-11.
Figure 2-21 Interface of inputting the command parameter.
The whole command is SET ALMPORT: SITENAME="BTS3012", SRN=0, SN=2, PN=1, SW=OPEN, AID=65527, PT=BOOL, AVOL=HIGH;,where, SITENAME is the name of the BTS, SRN is the frame number of the BTS, SN is the slot number, PN is the port number in the board, SW is the port switch, AID is the alarm ID to be configured, PT is port type, and AVOL is the alarm level.
The operation object of SET ALMPORT is each specific physical environment alarm port. Assuming the DEMU board is configured for N BTSs, to modify alarm ID 6438 over port 1 on the DEMU board, you need run N SET ALMPORT commands to respectively modify these physical ports. You can edit the MML commands in advance and deliver them once in the batch command form.
For the usage of the MML batch command, see the BSC MML Command Reference.
Step 32 Click or press F9 to run the MML command.
Step 33 Repeat steps 5 and 6. All the configurations are completed.
----End2.3.4 Modifying the BTS Environment Alarm Name and Definition on the BSC6000 Local Maintenance TerminalIn section 2.3.2, the parameters of the BTS environment alarm ID are set. The task of this section is to modify the BTS environment alarm name and definition, rename the bound environment alarm ID, and set Alarm Severity and To Alarm Box Flag. The procedures are as follows:Step 34 Log in to the BSC6000 LMT. A window is displayed, as shown in Figure 2-12. Figure 2-22 Interface of the BSC6000 Local Maintenance Terminal
Step 35 Choose Alarm Maintenance > Query Alarm Configuration Settings. The Query Alarm Configuration Settings dialog box is displayed. Select the filter conditions according to the actual situation, as shown in Figure 2-13.Figure 2-23 Query Alarm Configuration Settings dialog box
Step 36 Click OK. The Query Alarm Configuration window is displayed, as shown in Figure 2-14.Figure 2-24 Query Alarm Configuration window
Step 37 Right-click the line where alarm ID 65527 is located and select Set Environment Alarm Configuration from the shortcut menu. The Set Environment Alarm Configuration dialog box is displayed, as shown in Figure 2-15.Figure 2-25 Setting parameters of the environment alarm configuration
Step 38 Change Alarm Name from BTS Custom Environment Alarm 144 to Fire and Alarm Severity from Major to Critical.Step 39 Click OK. The information dialog box is displayed, as shown in Figure 2-16.Figure 2-26 Successful setting
Step 40 Click OK. Repeat steps 4 to 6. All the configurations are completed.----End2.3.5 Modifying the Name of M2000V2R3 Environment AlarmTo modify the alarm name in the NMS environment in the M2000V2R3 version, you need to modify the SQL script through the M2000 server. For details, see Guide of Modifying the Alarm Name for M2000V2 Products.
The modification includes the operations such as querying whether the modified environment alarm ID has existed, uploading the environment alarm ID definition file and enabling the modification to the environment alarm to take effect.
For the detailed operation, see section 2.2.3 .
2.4 Configuring BTS Environment Alarm in BSC6000 V900R003+M2000 V2R6
This solution is applicable for configuring the environment alarm ID in the BSC6000 and M2000 V2R6 of V9R3 and later versions.The operation to an NE can reach the same result as the operations of setting the environment alarm signal input port on the MML Local Maintenance Terminal and binding the user-defined alarm through the M2000. However, the M2000 provides the function of importing and exporting the configuration script according to the excel file and querying the current NE environment alarm binding correlation, both of which facilitate the operation.The operation of modifying the alarm name carried on the M2000 takes effect on both the M2000 and the NE at the same time, but the operation performed on the NE through the BSC6000 Local Maintenance Terminal only modifies the data on the NE, and it cannot modify the data on the M2000. The alarm name is stored respectively on the M2000 and the NE as the independent data.Therefore, to configure the environment alarm in the BSC6000 V900R003+M2000 V2R3 solution of R3 or later versions, do as follows: Step 41 Bind the parameters of the BTS environment alarm IDs through the M2000V2R6.
Step 42 Modify the names and definitions of BTS environment alarms on the M2000V2R6.
Step 43 Enable the alarm function on the environment monitoring board in the BSC Local Maintenance Terminal interface in the V9R3 version. The V9R8 version does not involve this step.
Besides the parameters in section 2.3.2 , the parameters of the BTS alarm IDs mentioned in this section also include the NE name. The definitions of the environment alarm names are the same as those in section 2.3.2 .2.4.2 Binding the Parameters of the NE BTS Environment Alarm ID through M2000V2R6The operation of binding the parameters of the BTS environment alarm ID is performed by binding and adding the user-defined alarms. The procedures are as follows:Step 44 Log in to the M2000 mobile element management system. Figure 2-17 shows the interface for the successful login.Figure 2-27 M2000 Mobile Element Management System interface
Step 45 Choose Monitor > Settings > NE Alarm Settings. The NE Alarm Settings tab page is displayed in the iManager M2000 Mobile Element Management System window, as shown in Figure 2-18.Figure 2-28 Binding an alarm
Step 46 Click Export Template on the Alarm Binding tab page to export the alarm binding template. Save the template as the binding data.xls file.Step 47 Open the binding data.xls file, fill in the file with the alarm binding information, and save it. Step 48 Click Import in the Alarm Binding tab page to import the binding data.xls file into the client.Step 49 Click Apply on the Alarm Binding tab page.The Information dialog box is displayed to give the operation result.
For the cut over BTS, repeat these procedures. ----End2.4.3 Modifying the Name and Definition of the M2000V2R6 Environment AlarmThe operation of modifying the name and definition of the M2000V2R6 environment alarm is performed by adding the user-defined alarm and adding the user-defined alarm binding. The procedures are as follows.Step 50 Repeat steps 1 and 2 of binding the user-defined alarms. Step 51 As shown in Figure 2-19, select the Alarm Definition tab under the User Defined Alarm tab.Figure 2-29 NE Alarm Settings tab
Step 52 Click Add. The Add User Defined Alarm dialog box is displayed, as shown in Figure 2-20.Figure 2-30 Adding the user-defined alarm
Step 53 Select BSC6000 under Ne Type, set Alarm Name and Alarm Level, and click OK.
The user-defined alarm to be added is displayed in the list on the Alarm Definition tab page, and each record has .
Step 54 Click Apply on the Alarm Definition tab page. disappears. The Information dialog box is displayed to give the operation result.
Repeat these procedures to the BTS newly cut over. ----End3 Difference of Environment Alarm Configurations Between BSC6000 Versions 3.1 Differences of Environment Alarm Configurations Between BSC6000 Versions The default environment alarm IDs reported by the BTS can be reported by the BSC6000 V9R1 to the alarm subsystem and the M2000. The BSC6000 V9R1 does not support to bind the BTS environment alarm port to the specified alarm ID again. In the mean time, the V9R1 supports to modify the name of the default the alarm ID reported by the BTS, but the operation of modifying the alarm name needs to be performed respectively on the M2000 and the BSC6000 Local Maintenance Terminal. In the V9R1 version, the external equipment of the BTS environment alarm can be connected to the fixed port for satisfying the BTS requirement. Because the alarm and the port are bound, the environment alarm reported by the BTS cannot be identified once the connection is changed to another idle port due to the failure on this port.V9R8 is upgraded on the basis of V9R3, and there is not difference in the environment alarm configuration.The V9R3 version supports to bind the BTS environment alarm port with the BTS environment alarm ID range first and then modify the alarm name of the bound alarm ID.In addition, for V9R1 and V9R3, the environment alarm monitoring on the BTS monitoring board needs to be enabled to monitor the environment after the BTS environment alarm ID is set.
The V9R8 version does not involve this step. The process for enabling the environment alarm monitoring on the BTS monitoring board is as follows: Step 55 Select BTS3012 from the Management Tree on the Local Maintenance Terminal (taking BTS3012 as an example), as shown in Figure 3-1.Figure 3-31 Selecting a BTS
Step 56 Right-click BTS3012 and select Configure Site Board Attributes from the shortcut menu, as shown in Figure 3-2.Figure 3-32 Shortcut menu
Step 57 The Configure Site Board Attributes dialog box is displayed. Click Configure Site Board Attributes, as shown in Figure 3-3.Figure 3-33 Configure Site Boards Attributes dialog box
Step 58 The Site Device Attributes dialog box is displayed. Right-click the DEMU board (the DEMU board is taken as an example) to be set, as shown in Figure 3-4.Figure 3-34 Site Device Attributes dialog box
Step 59 Select Configure Board Attributes from the shortcut menu. The Basic Attributes of Site Board dialog box is displayed. On the Configure Site Board Attributes tab page, set Board Parameter Configuration Enabled to Yes, as shown in Figure 3-5.Figure 3-35 Enabling the board alarm
Step 60 Click OK to return to Figure 3-1 and then click OK. The environment alarm monitoring is enabled.3.2 Environment Alarm Configuration in V9R1 Upgraded to V9R3 or Later Versions After V9R1 is upgraded to V9R3, the environment alarm name configured in the V9R1 version is still available. You can handle the configurations after the upgrade in the following ways: 1. If no cutover is performed to add new BTSs to the upgraded BSC6000 or the newly BTSs added to the BSC6000 is of the original type configured in V9R1, the new environment alarms do not need to be configured. However, the original environment alarm cannot be renamed in the V9R3 version after the upgrade. For all the BTSs upgraded to V9R3, you can bind the alarm IDs again and set the alarm name with the method in the V9R3 version, that is, the environment alarm ID is switched from the uncentralized management mode to the centralized management.
The switching of the environment alarm ID from the uncentralized management to the centralized management influences the alarm interconnection of the northbound NMS due to the change of the environment alarm ID. In the site with the northbound alarm interconnection, the customer and the field technical personnel should evaluate and adapt (such as planning the environment alarm ID at the NMS level) the influence to the northbound alarm interconnection (such as the alarm ID change).2. If the type of the added BTS is new, use the method in the V9R3 version to bind the alarm ID and modify the alarm name of the cut over BTSs to realize the centralized management. Of course, you can make the settings according to those in the uncentralized management to the BTS environment alarm ID in the V9R1 version. 3. If all the BSCs under the same M2000 are upgraded to V9R3, it is recommended to configure the BSC environment alarm upgraded from V9R1 again in the mode in V9R3 to keep the unified management to the environment alarms under the same M2000.If V9R1 is upgraded to V9R8, the alarm configuration is performed in the same way.2008-05-29HUAWEI ConfidentialPage10, Total35
_1273605195.xlsSheet1
BTS TypeMonitoring EquipmentSubrack No.-Slot No.Monitoring CableCable CoresCore ColorMonitoring Equipment PortPort NO.AlmID
BTS3006CEMUSubrack 3 - Slot 2Cable of the SensorNot ProvidedNot ProvidedS1+/S1-16212
Cable of the SensorNot ProvidedNot ProvidedS2+/S2-26214
Cable of the SensorNot ProvidedNot ProvidedS3+/S3-36216
Cable of the SensorNot ProvidedNot ProvidedS4+/S4-46218
Cable of the SensorNot ProvidedNot ProvidedS5+/S5-56220
Cable of the SensorNot ProvidedNot ProvidedS6+/S6-66222
Cable of the SensorNot ProvidedNot ProvidedS7+/S7-76224
Cable of the SensorNot ProvidedNot ProvidedS8+/S8-86226
Cable of the SensorNot ProvidedNot ProvidedS9+/S9-96228
Cable of the SensorNot ProvidedNot ProvidedS10+/S10-106230
Cable of the SensorNot ProvidedNot ProvidedS11+/S11-116232
Cable of the SensorNot ProvidedNot ProvidedS12+/S12-126234
Cable of the SensorNot ProvidedNot ProvidedS13+/S13-136236
Cable of the SensorNot ProvidedNot ProvidedS14+/S14-146238
Cable of the SensorNot ProvidedNot ProvidedS15+/S15-156240
Cable of the SensorNot ProvidedNot ProvidedS16+/S16-166242
Cable of the SensorNot ProvidedNot ProvidedS17+/S17-176244
Cable of the SensorNot ProvidedNot ProvidedS18+/S18-186246
Cable of the SensorNot ProvidedNot ProvidedS19+/S19-196248
Cable of the SensorNot ProvidedNot ProvidedS20+/S20-206250
Cable of the SensorNot ProvidedNot ProvidedS21+/S21-216252
Cable of the SensorNot ProvidedNot ProvidedS22+/S22-226254
Cable of the SensorNot ProvidedNot ProvidedS23+/S23-236256
Cable of the SensorNot ProvidedNot ProvidedS24+/S24-246258
Cable of the SensorNot ProvidedNot ProvidedS25+/S25-256260
Cable of the SensorNot ProvidedNot ProvidedS26+/S26-266262
Cable of the SensorNot ProvidedNot ProvidedS27+/S27-276264
Cable of the SensorNot ProvidedNot ProvidedS28+/S28-286266
Cable of the SensorNot ProvidedNot ProvidedS29+/S29-296268
Cable of the SensorNot ProvidedNot ProvidedS30+/S30-306270
Cable of the SensorNot ProvidedNot ProvidedS31+/S31-316272
Cable of the SensorNot ProvidedNot ProvidedS32+/S32-326274
DPMUSubrack 3 - Slot 0Cable of the SensorNot ProvidedNot Provided16032
Cable of the SensorNot ProvidedNot Provided26034
Cable of the SensorNot ProvidedNot Provided36036
Cable of the SensorNot ProvidedNot Provided46038
Cable of the SensorNot ProvidedNot Provided56040
Cable of the SensorNot ProvidedNot Provided66042
Cable of the SensorNot ProvidedNot Provided76044
APMUSubrack 3 - Slot 0Cable of the SensorNot ProvidedNot Provided15742
Cable of the SensorNot ProvidedNot Provided25744
Cable of the SensorNot ProvidedNot Provided35746
DOMUSubrack 1 - Slot 0A BTS006C/BTS3002E external alarm cableX1.7/X1.5blue/white14944
A BTS006C/BTS3002E external alarm cableX1.8/X1.5orange/white24946
A BTS006C/BTS3002E external alarm cableX1.9/X1.11green/white34948
A BTS006C/BTS3002E external alarm cableX1.10/X1.11broWn/white44950
Cable of the SensorNot ProvidedNot Provided54952
Cable of the SensorNot ProvidedNot Provided64954
Cable of the SensorNot ProvidedNot Provided74956
Cable of the SensorNot ProvidedNot Provided84958
Cable of the SensorNot ProvidedNot Provided94960
Cable of the SensorNot ProvidedNot Provided104962
Cable of the SensorNot ProvidedNot Provided114964
Cable of the SensorNot ProvidedNot Provided124966
Cable of the SensorNot ProvidedNot Provided134968
Cable of the SensorNot ProvidedNot Provided144970
Cable of the SensorNot ProvidedNot Provided154972
Cable of the SensorNot ProvidedNot Provided164974
Cable of the SensorNot ProvidedNot Provided174976
Cable of the SensorNot ProvidedNot Provided184978
Cable of the SensorNot ProvidedNot Provided194980
Cable of the SensorNot ProvidedNot Provided204982
Cable of the SensorNot ProvidedNot Provided214984
Cable of the SensorNot ProvidedNot Provided224986
Cable of the SensorNot ProvidedNot Provided234988
Cable of the SensorNot ProvidedNot Provided244990
Cable of the SensorNot ProvidedNot Provided254992
Cable of the SensorNot ProvidedNot Provided264994
Cable of the SensorNot ProvidedNot Provided274996
Cable of the SensorNot ProvidedNot Provided284998
Cable of the SensorNot ProvidedNot Provided295000
Cable of the SensorNot ProvidedNot Provided305002
Cable of the SensorNot ProvidedNot Provided315004
Cable of the SensorNot ProvidedNot Provided325006
BTS3002EDOMUSubrack 1 - Slot 0A BTS006C/BTS3002E external alarm cableX1.7/X1.5blue/white14944
A BTS006C/BTS3002E external alarm cableX1.8/X1.5orange/white24946
A BTS006C/BTS3002E external alarm cableX1.9/X1.11green/white34948
A BTS006C/BTS3002E external alarm cableX1.10/X1.11broWn/white44950
Cable of the SensorNot ProvidedNot Provided54952
Cable of the SensorNot ProvidedNot Provided64954
Cable of the SensorNot ProvidedNot Provided74956
Cable of the SensorNot ProvidedNot Provided84958
Cable of the SensorNot ProvidedNot Provided94960
Cable of the SensorNot ProvidedNot Provided104962
Cable of the SensorNot ProvidedNot Provided114964
Cable of the SensorNot ProvidedNot Provided124966
Cable of the SensorNot ProvidedNot Provided134968
Cable of the SensorNot ProvidedNot Provided144970
Cable of the SensorNot ProvidedNot Provided154972
Cable of the SensorNot ProvidedNot Provided164974
Cable of the SensorNot ProvidedNot Provided174976
Cable of the SensorNot ProvidedNot Provided184978
Cable of the SensorNot ProvidedNot Provided194980
Cable of the SensorNot ProvidedNot Provided204982
Cable of the SensorNot ProvidedNot Provided214984
Cable of the SensorNot ProvidedNot Provided224986
Cable of the SensorNot ProvidedNot Provided234988
Cable of the SensorNot ProvidedNot Provided244990
Cable of the SensorNot ProvidedNot Provided254992
Cable of the SensorNot ProvidedNot Provided264994
Cable of the SensorNot ProvidedNot Provided274996
Cable of the SensorNot ProvidedNot Provided284998
Cable of the SensorNot ProvidedNot Provided295000
Cable of the SensorNot ProvidedNot Provided305002
Cable of the SensorNot ProvidedNot Provided315004
Cable of the SensorNot ProvidedNot Provided325006
BTS3012DEMUSubrack 0 - Slot 2The BTS3012 Boolean input cableW1.36/W1.2blue/whiteNot Provided16438
W1.37/W1.3orange/whiteNot Provided26440
W1.38/W1.4green/whiteNot Provided36442
W1.39/W1.5brown/whiteNot Provided46444
W1.40/W1.6grey/whiteNot Provided56446
W1.41/W1.7blue/redNot Provided66448
W1.42/W1.8orange/redNot Provided76450
W1.43/W1.9green/redNot Provided86452
W1.44/W1.10brown/redNot Provided96454
W1.45/W1.11grey/redNot Provided106456
W1.46/W1.12blue/blackNot Provided116458
W1.47/W1.13orange/blackNot Provided126460
W1.48/W1.14green/blackNot Provided136462
W1.49/W1.15brown/blackNot Provided146464
W1.50/W1.16grey/blackNot Provided156466
W1.51/W1.17blue/yellowNot Provided166422
W1.52/W1.18blue/whiteNot Provided176424
W1.53/W1.19orange/whiteNot Provided186426
W1.54/W1.20green/whiteNot Provided196428
W1.55/W1.21brown/whiteNot Provided206430
W1.56/W1.22grey/whiteNot Provided216432
W1.57/W1.23blue/redNot Provided226434
W1.58/W1.24orange/redNot Provided236436
W1.59/W1.25green/redNot Provided246468
W1.60/W1.26brown/redNot Provided256470
W1.61/W1.27grey/redNot Provided266472
W1.62/W1.28blue/blackNot Provided276474
W1.63/W1.29orange/blackNot Provided286476
W1.64/W1.30green/blackNot Provided296478
W1.65/W1.31brown/blackNot Provided306480
W1.66/W1.32grey/blackNot Provided316482
W1.67/W1.33blue/yellowNot Provided326484
BTS3012EACSubrack 0 - Slot 1Cable of the SensorNot ProvidedNot ProvidedS1+/S1-16438
Cable of the SensorNot ProvidedNot ProvidedS2+/S2-26440
Cable of the SensorNot ProvidedNot ProvidedS3+/S3-36442
Cable of the SensorNot ProvidedNot ProvidedS4+/S4-46444
Cable of the SensorNot ProvidedNot ProvidedS5+/S5-56446
Cable of the SensorNot ProvidedNot ProvidedS6+/S6-66448
Cable of the SensorNot ProvidedNot ProvidedS7+/S7-76450
Cable of the SensorNot ProvidedNot ProvidedS8+/S8-86452
Cable of the SensorNot ProvidedNot ProvidedS9+/S9-96454
Cable of the SensorNot ProvidedNot ProvidedS10+/S10-106456
Cable of the SensorNot ProvidedNot ProvidedS11+/S11-116458
Cable of the SensorNot ProvidedNot ProvidedS12+/S12-126460
Cable of the SensorNot ProvidedNot ProvidedS13+/S13-136462
Cable of the SensorNot ProvidedNot ProvidedS14+/S14-146464
Cable of the SensorNot ProvidedNot ProvidedS15+/S15-156466
Cable of the SensorNot ProvidedNot ProvidedS16+/S16-166422
Cable of the SensorNot ProvidedNot ProvidedS17+/S17-176424
Cable of the SensorNot ProvidedNot ProvidedS18+/S18-186426
Cable of the SensorNot ProvidedNot ProvidedS19+/S19-196428
Cable of the SensorNot ProvidedNot ProvidedS20+/S20-206430
Cable of the SensorNot ProvidedNot ProvidedS21+/S21-216432
Cable of the SensorNot ProvidedNot ProvidedS22+/S22-226434
Cable of the SensorNot ProvidedNot ProvidedS23+/S23-236436
Cable of the SensorNot ProvidedNot ProvidedS24+/S24-246148
Cable of the SensorNot ProvidedNot ProvidedS25+/S25-256150
Cable of the SensorNot ProvidedNot ProvidedS26+/S26-266152
Cable of the SensorNot ProvidedNot ProvidedS27+/S27-276154
Cable of the SensorNot ProvidedNot ProvidedS28+/S28-286156
Cable of the SensorNot ProvidedNot ProvidedS29+/S29-296158
Cable of the SensorNot ProvidedNot ProvidedS30+/S30-306160
Cable of the SensorNot ProvidedNot ProvidedS31+/S31-316162
Cable of the SensorNot ProvidedNot ProvidedS32+/S32-326164
BTS3012DPMUSubrack 0 - Slot 15Cable of the SensorNot ProvidedNot ProvidedNot Provided15654
Cable of the SensorNot ProvidedNot ProvidedNot Provided25656
Cable of the SensorNot ProvidedNot ProvidedNot Provided35658
Cable of the SensorNot ProvidedNot ProvidedNot Provided45660
Cable of the SensorNot ProvidedNot ProvidedNot Provided55662
Cable of the SensorNot ProvidedNot ProvidedNot Provided65664
Cable of the SensorNot ProvidedNot ProvidedNot Provided75666
BTS3012DTMUSubrack 0 - Slot 0 or Slot 1Cable of the SensorNot ProvidedNot ProvidedNot Provided14778
Cable of the SensorNot ProvidedNot ProvidedNot Provided24780
Cable of the SensorNot ProvidedNot ProvidedNot Provided34782
Cable of the SensorNot ProvidedNot ProvidedNot Provided44784
Cable of the SensorNot ProvidedNot ProvidedNot Provided54786
Cable of the SensorNot ProvidedNot ProvidedNot Provided64788
Cable of the SensorNot ProvidedNot ProvidedNot Provided74790
Cable of the SensorNot ProvidedNot ProvidedNot Provided84792
Cable of the SensorNot ProvidedNot ProvidedNot Provided94842
Cable of the SensorNot ProvidedNot ProvidedNot Provided104844
Cable of the SensorNot ProvidedNot ProvidedNot Provided114846
Cable of the SensorNot ProvidedNot ProvidedNot Provided124848
Cable of the SensorNot ProvidedNot ProvidedNot Provided134850
Cable of the SensorNot ProvidedNot ProvidedNot Provided144852
Cable of the SensorNot ProvidedNot ProvidedNot Provided154854
Cable of the SensorNot ProvidedNot ProvidedNot Provided164856
Cable of the SensorNot ProvidedNot ProvidedNot Provided174858
Cable of the SensorNot ProvidedNot ProvidedNot Provided184860
Cable of the SensorNot ProvidedNot ProvidedNot Provided194862
Cable of the SensorNot ProvidedNot ProvidedNot Provided204864
Cable of the SensorNot ProvidedNot ProvidedNot Provided214866
Cable of the SensorNot ProvidedNot ProvidedNot Provided224868
Cable of the SensorNot ProvidedNot ProvidedNot Provided234870
Cable of the SensorNot ProvidedNot ProvidedNot Provided244872
BTS3012V2DTMUSubrack 0 - Slot 0 or Slot 1Cable of the SensorNot ProvidedNot ProvidedNot Provided14778
Cable of the SensorNot ProvidedNot ProvidedNot Provided24780
Cable of the SensorNot ProvidedNot ProvidedNot Provided34782
Cable of the SensorNot ProvidedNot ProvidedNot Provided44784
Cable of the SensorNot ProvidedNot ProvidedNot Provided54786
Cable of the SensorNot ProvidedNot ProvidedNot Provided64788
Cable of the SensorNot ProvidedNot ProvidedNot Provided74790
Cable of the SensorNot ProvidedNot ProvidedNot Provided84792
Cable of the SensorNot ProvidedNot ProvidedNot Provided94842
Cable of the SensorNot ProvidedNot ProvidedNot Provided104844
Cable of the SensorNot ProvidedNot ProvidedNot Provided114846
Cable of the SensorNot ProvidedNot ProvidedNot Provided124848
Cable of the SensorNot ProvidedNot ProvidedNot Provided134850
Cable of the SensorNot ProvidedNot ProvidedNot Provided144852
Cable of the SensorNot ProvidedNot ProvidedNot Provided154854
Cable of the SensorNot ProvidedNot ProvidedNot Provided164856
Cable of the SensorNot ProvidedNot ProvidedNot Provided174858
Cable of the SensorNot ProvidedNot ProvidedNot Provided184860
Cable of the SensorNot ProvidedNot ProvidedNot Provided194862
Cable of the SensorNot ProvidedNot ProvidedNot Provided204864
Cable of the SensorNot ProvidedNot ProvidedNot Provided214866
Cable of the SensorNot ProvidedNot ProvidedNot Provided224868
Cable of the SensorNot ProvidedNot ProvidedNot Provided234870
Cable of the SensorNot ProvidedNot ProvidedNot Provided244872
BTS3012AEDPMUSubrack 0 - Slot 15Cable of the SensorNot ProvidedNot ProvidedNPMI-JDC115668
Cable of the SensorNot ProvidedNot ProvidedNPMI-JDC225670
Cable of the SensorNot ProvidedNot ProvidedNPMI-JDC335672
Cable of the SensorNot ProvidedNot ProvidedNPMI-JDC445674
Cable of the SensorNot ProvidedNot ProvidedNPMI-JDC555676
Cable of the SensorNot ProvidedNot ProvidedNPMI-JDC665678
Cable of the SensorNot ProvidedNot ProvidedNPMI-JDC775680
BTS3012AEDTMUSubrack 0 - Slot 0 or Slot 1Cable of the SensorNot ProvidedNot Provided14874
Cable of the SensorNot ProvidedNot Provided24876
Cable of the SensorNot ProvidedNot Provided34878
Cable of the SensorNot ProvidedNot Provided44880
Cable of the SensorNot ProvidedNot Provided54882
Cable of the SensorNot ProvidedNot Provided64884
Cable of the SensorNot ProvidedNot Provided74886
Cable of the SensorNot ProvidedNot Provided84888
Cable of the SensorNot ProvidedNot Provided94890
Cable of the SensorNot ProvidedNot Provided104892
Cable of the SensorNot ProvidedNot Provided114894
Cable of the SensorNot ProvidedNot Provided124896
Cable of the SensorNot ProvidedNot Provided134898
Cable of the SensorNot ProvidedNot Provided144900
Cable of the SensorNot ProvidedNot Provided154902
Cable of the SensorNot ProvidedNot Provided164904
Cable of the SensorNot ProvidedNot Provided174906
Cable of the SensorNot ProvidedNot Provided184908
Cable of the SensorNot ProvidedNot Provided194910
Cable of the SensorNot ProvidedNot Provided204912
Cable of the SensorNot ProvidedNot Provided214914
Cable of the SensorNot ProvidedNot Provided224916
Cable of the SensorNot ProvidedNot Provided234918
Cable of the SensorNot ProvidedNot Provided244920
BTS30TMUSubrack 0 - Slot 14 or Slot 15The extension alarm cable A/ The extension alarm cable BX1.28BLUE(2 BLACK DOT)12246
X1.9BLUE(2 RED DOT)22248
X1.27GREEN(3 BLACK DOT)32250
X1.8GREEN(3 RED DOT)42252
X1.26ORANGE(3 BLACK DOT)52254
X1.7ORANGE(3 RED DOT)62256
X1.25PINK(3 BLACK DOT)72258
X1.6GRAY(2 RED DOT)82262
X1.14GREEN(3 RED DOT)102268
X1.1PINK(1 RED DOT)172592
X1.20GRAY(3 RED DOT)162594
X1.19GRAY(3 BLACK DOT)152596
X1.18PINK(4 RED DOT)142598
X1.5GREEN(1 RED DOT)212600
X1.10PINK(3 RED DOT)92602
X1.4ORANGE(1 BLACK DOT)202604
X1.8BLUE(1 BLACK DOT)242606
X1.3ORANGE(1 RED DOT)192608
X1.7BLUE(1 RED DOT)232610
X1.2PINK(1 BLACK DOT)182612
X1.6GREEN(1 BLACK DOT)222614
X1.17BLUE(3 BLACK DOT)132616
X1.16BLUE(3 RED DOT)122618
X1.15GREEN(3 BLACK DOT)112620
BTS30EACSubrack 0 - Slot 13Cable of the SensorNot ProvidedNot ProvidedS1+/S1-12402
Cable of the SensorNot ProvidedNot ProvidedS2+/S2-22404
Cable of the SensorNot ProvidedNot ProvidedS3+/S3-32406
Cable of the SensorNot ProvidedNot ProvidedS4+/S4-42408
Cable of the SensorNot ProvidedNot ProvidedS5+/S5-52410
Cable of the SensorNot ProvidedNot ProvidedS6+/S6-62412
Cable of the SensorNot ProvidedNot ProvidedS7+/S7-72414
Cable of the SensorNot ProvidedNot ProvidedS8+/S8-82416
Cable of the SensorNot ProvidedNot ProvidedS9+/S9-92418
Cable of the SensorNot ProvidedNot ProvidedS10+/S10-102420
Cable of the SensorNot ProvidedNot ProvidedS11+/S11-112422
Cable of the SensorNot ProvidedNot ProvidedS12+/S12-122424
Cable of the SensorNot ProvidedNot ProvidedS13+/S13-132426
Cable of the SensorNot ProvidedNot ProvidedS14+/S14-142428
Cable of the SensorNot ProvidedNot ProvidedS15+/S15-152430
Cable of the SensorNot ProvidedNot ProvidedS16+/S16-162386
Cable of the SensorNot ProvidedNot ProvidedS17+/S17-172388
Cable of the SensorNot ProvidedNot ProvidedS18+/S18-182390
Cable of the SensorNot ProvidedNot ProvidedS19+/S19-192392
Cable of the SensorNot ProvidedNot ProvidedS20+/S20-202394
Cable of the SensorNot ProvidedNot ProvidedS21+/S21-212396
Cable of the SensorNot ProvidedNot ProvidedS22+/S22-222398
Cable of the SensorNot ProvidedNot ProvidedS23+/S23-232400
Cable of the SensorNot ProvidedNot ProvidedS24+/S24-242458
Cable of the SensorNot ProvidedNot ProvidedS25+/S25-252460
Cable of the SensorNot ProvidedNot ProvidedS26+/S26-262462
Cable of the SensorNot ProvidedNot ProvidedS27+/S27-272464
Cable of the SensorNot ProvidedNot ProvidedS28+/S28-282466
Cable of the SensorNot ProvidedNot ProvidedS29+/S29-292468
Cable of the SensorNot ProvidedNot ProvidedS30+/S30-302470
Cable of the SensorNot ProvidedNot ProvidedS31+/S31-312472
Cable of the SensorNot ProvidedNot ProvidedS32+/S32-322474
BTS312TMUSubrack 0 - Slot 14 or Slot 15The extension alarm cable A/ The extension alarm cable BX1.28BLUE(2 BLACK DOT)12246
X1.9BLUE(2 RED DOT)22248
X1.27GREEN(3 BLACK DOT)32250
X1.8GREEN(3 RED DOT)42252
X1.26ORANGE(3 BLACK DOT)52254
X1.7ORANGE(3 RED DOT)62256
X1.25PINK(3 BLACK DOT)72258
X1.6GRAY(2 RED DOT)82262
X1.14GREEN(3 RED DOT)102268
X1.1PINK(1 RED DOT)172592
X1.20GRAY(3 RED DOT)162594
X1.19GRAY(3 BLACK DOT)152596
X1.18PINK(4 RED DOT)142598
X1.5GREEN(1 RED DOT)212600
X1.10PINK(3 RED DOT)92602
X1.4ORANGE(1 BLACK DOT)202604
X1.8BLUE(1 BLACK DOT)242606
X1.3ORANGE(1 RED DOT)192608
X1.7BLUE(1 RED DOT)232610
X1.2PINK(1 BLACK DOT)182612
X1.6GREEN(1 BLACK DOT)222614
X1.17BLUE(3 BLACK DOT)132616
X1.16BLUE(3 RED DOT)122618
X1.15GREEN(3 BLACK DOT)112620
BTS312EACSubrack 0 - Slot 13Cable of the SensorNot ProvidedNot ProvidedS1+/S1-12402
Cable of the SensorNot ProvidedNot ProvidedS2+/S2-22404
Cable of the SensorNot ProvidedNot ProvidedS3+/S3-32406
Cable of the SensorNot ProvidedNot ProvidedS4+/S4-42408
Cable of the SensorNot ProvidedNot ProvidedS5+/S5-52410
Cable of the SensorNot ProvidedNot ProvidedS6+/S6-62412
Cable of the SensorNot ProvidedNot ProvidedS7+/S7-72414
Cable of the SensorNot ProvidedNot ProvidedS8+/S8-82416
Cable of the SensorNot ProvidedNot ProvidedS9+/S9-92418
Cable of the SensorNot ProvidedNot ProvidedS10+/S10-102420
Cable of the SensorNot ProvidedNot ProvidedS11+/S11-112422
Cable of the SensorNot ProvidedNot ProvidedS12+/S12-122424
Cable of the SensorNot ProvidedNot ProvidedS13+/S13-132426
Cable of the SensorNot ProvidedNot ProvidedS14+/S14-142428
Cable of the SensorNot ProvidedNot ProvidedS15+/S15-152430
Cable of the SensorNot ProvidedNot ProvidedS16+/S16-162386
Cable of the SensorNot ProvidedNot ProvidedS17+/S17-172388
Cable of the SensorNot ProvidedNot ProvidedS18+/S18-182390
Cable of the SensorNot ProvidedNot ProvidedS19+/S19-192392
Cable of the SensorNot ProvidedNot ProvidedS20+/S20-202394
Cable of the SensorNot ProvidedNot ProvidedS21+/S21-212396
Cable of the SensorNot ProvidedNot ProvidedS22+/S22-222398
Cable of the SensorNot ProvidedNot ProvidedS23+/S23-232400
Cable of the SensorNot ProvidedNot ProvidedS24+/S24-242458
Cable of the SensorNot ProvidedNot ProvidedS25+/S25-252460
Cable of the SensorNot ProvidedNot ProvidedS26+/S26-262462
Cable of the SensorNot ProvidedNot ProvidedS27+/S27-272464
Cable of the SensorNot ProvidedNot ProvidedS28+/S28-282466
Cable of the SensorNot ProvidedNot ProvidedS29+/S29-292468
Cable of the SensorNot ProvidedNot ProvidedS30+/S30-302470
Cable of the SensorNot ProvidedNot ProvidedS31+/S31-312472
Cable of the SensorNot ProvidedNot ProvidedS32+/S32-322474
BTS3006ATMUSubrack 0 - Slot 15The extension alarm cable A/ The extension alarm cable BX1.28BLUE(2 BLACK DOT)12246
X1.9BLUE(2 RED DOT)22248
X1.27GREEN(3 BLACK DOT)32250
X1.8GREEN(3 RED DOT)42252
X1.26ORANGE(3 BLACK DOT)52254
X1.7ORANGE(3 RED DOT)62256
X1.25PINK(3 BLACK DOT)72258
X1.6GRAY(2 RED DOT)82262
X1.14GREEN(3 RED DOT)102268
X1.1PINK(1 RED DOT)172592
X1.20GRAY(3 RED DOT)162594
X1.19GRAY(3 BLACK DOT)152596
X1.18PINK(4 RED DOT)142598
X1.5GREEN(1 RED DOT)212600
X1.10PINK(3 RED DOT)92602
X1.4ORANGE(1 BLACK DOT)202604
X1.8BLUE(1 BLACK DOT)242606
X1.3ORANGE(1 RED DOT)192608
X1.7BLUE(1 RED DOT)232610
X1.2PINK(1 BLACK DOT)182612
X1.6GREEN(1 BLACK DOT)222614
X1.17BLUE(3 BLACK DOT)132616
X1.16BLUE(3 RED DOT)122618
X1.15GREEN(3 BLACK DOT)112620
BTS3006AEMUASubrack 0 - Slot 11Cable of the SensorNot ProvidedNot ProvidedS1+/S1-12402
Cable of the SensorNot ProvidedNot ProvidedS2+/S2-22404
Cable of the SensorNot ProvidedNot ProvidedS3+/S3-32406
Cable of the SensorNot ProvidedNot ProvidedS4+/S4-42408
Cable of the SensorNot ProvidedNot ProvidedS5+/S5-52410
Cable of the SensorNot ProvidedNot ProvidedS6+/S6-62412
Cable of the SensorNot ProvidedNot ProvidedS7+/S7-72414
Cable of the SensorNot ProvidedNot ProvidedS8+/S8-82416
Cable of the SensorNot ProvidedNot ProvidedS9+/S9-92418
Cable of the SensorNot ProvidedNot ProvidedS10+/S10-102420
Cable of the SensorNot ProvidedNot ProvidedS11+/S11-112422
Cable of the SensorNot ProvidedNot ProvidedS12+/S12-122424
Cable of the SensorNot ProvidedNot ProvidedS13+/S13-132426
Cable of the SensorNot ProvidedNot ProvidedS14+/S14-142428
Cable of the SensorNot ProvidedNot ProvidedS15+/S15-152430
Cable of the SensorNot ProvidedNot ProvidedS16+/S16-162386
Cable of the SensorNot ProvidedNot ProvidedS17+/S17-172388
Cable of the SensorNot ProvidedNot ProvidedS18+/S18-182390
Cable of the SensorNot ProvidedNot ProvidedS19+/S19-192392
Cable of the SensorNot ProvidedNot ProvidedS20+/S20-202394
Cable of the SensorNot ProvidedNot ProvidedS21+/S21-212396
Cable of the SensorNot ProvidedNot ProvidedS22+/S22-222398
Cable of the SensorNot ProvidedNot ProvidedS23+/S23-232400
Cable of the SensorNot ProvidedNot ProvidedS24+/S24-242458
Cable of the SensorNot ProvidedNot ProvidedS25+/S25-252460
Cable of the SensorNot ProvidedNot ProvidedS26+/S26-262462
Cable of the SensorNot ProvidedNot ProvidedS27+/S27-272464
Cable of the SensorNot ProvidedNot ProvidedS28+/S28-282466
Cable of the SensorNot ProvidedNot ProvidedS29+/S29-292468
Cable of the SensorNot ProvidedNot ProvidedS30+/S30-302470
Cable of the SensorNot ProvidedNot ProvidedS31+/S31-312472
Cable of the SensorNot ProvidedNot ProvidedS32+/S32-322474
BTS3012ATMUSubrack 0 - Slot 17The extension alarm cable A/ The extension alarm cable BX1.28BLUE(2 BLACK DOT)12246
X1.9BLUE(2 RED DOT)22248
X1.27GREEN(3 BLACK DOT)32250
X1.8GREEN(3 RED DOT)42252
X1.26ORANGE(3 BLACK DOT)52254
X1.7ORANGE(3 RED DOT)62256
X1.25PINK(3 BLACK DOT)72258
X1.6GRAY(2 RED DOT)82262
X1.14GREEN(3 RED DOT)102268
X1.1PINK(1 RED DOT)172592
X1.20GRAY(3 RED DOT)162594
X1.19GRAY(3 BLACK DOT)152596
X1.18PINK(4 RED DOT)142598
X1.5GREEN(1 RED DOT)212600
X1.10PINK(3 RED DOT)92602
X1.4ORANGE(1 BLACK DOT)202604
X1.8BLUE(1 BLACK DOT)242606
X1.3ORANGE(1 RED DOT)192608
X1.7BLUE(1 RED DOT)232610
X1.2PINK(1 BLACK DOT)182612
X1.6GREEN(1 BLACK DOT)222614
X1.17BLUE(3 BLACK DOT)132616
X1.16BLUE(3 RED DOT)122618
X1.15GREEN(3 BLACK DOT)112620
BTS3012AEMUASubrack 0 - Slot 13Cable of the SensorNot ProvidedNot ProvidedS1+/S1-12402
Cable of the SensorNot ProvidedNot ProvidedS2+/S2-22404
Cable of the SensorNot ProvidedNot ProvidedS3+/S3-32406
Cable of the SensorNot ProvidedNot ProvidedS4+/S4-42408
Cable of the SensorNot ProvidedNot ProvidedS5+/S5-52410
Cable of the SensorNot ProvidedNot ProvidedS6+/S6-62412
Cable of the SensorNot ProvidedNot ProvidedS7+/S7-72414
Cable of the SensorNot ProvidedNot ProvidedS8+/S8-82416
Cable of the SensorNot ProvidedNot ProvidedS9+/S9-92418
Cable of the SensorNot ProvidedNot ProvidedS10+/S10-102420
Cable of the SensorNot ProvidedNot ProvidedS11+/S11-112422
Cable of the SensorNot ProvidedNot ProvidedS12+/S12-122424
Cable of the SensorNot ProvidedNot ProvidedS13+/S13-132426
Cable of the SensorNot ProvidedNot ProvidedS14+/S14-142428
Cable of the SensorNot ProvidedNot ProvidedS15+/S15-152430
Cable of the SensorNot ProvidedNot ProvidedS16+/S16-162386
Cable of the SensorNot ProvidedNot ProvidedS17+/S17-172388
Cable of the SensorNot ProvidedNot ProvidedS18+/S18-182390
Cable of the SensorNot ProvidedNot ProvidedS19+/S19-192392
Cable of the SensorNot ProvidedNot ProvidedS20+/S20-202394
Cable of the SensorNot ProvidedNot ProvidedS21+/S21-212396
Cable of the SensorNot ProvidedNot ProvidedS22+/S22-222398
Cable of the SensorNot ProvidedNot ProvidedS23+/S23-232400
Cable of the SensorNot ProvidedNot ProvidedS24+/S24-242458
Cable of the SensorNot ProvidedNot ProvidedS25+/S25-252460
Cable of the SensorNot ProvidedNot ProvidedS26+/S26-262462
Cable of the SensorNot ProvidedNot ProvidedS27+/S27-272464
Cable of the SensorNot ProvidedNot ProvidedS28+/S28-282466
Cable of the SensorNot ProvidedNot ProvidedS29+/S29-292468
Cable of the SensorNot ProvidedNot ProvidedS30+/S30-302470
Cable of the SensorNot ProvidedNot ProvidedS31+/S31-312472
Cable of the SensorNot ProvidedNot ProvidedS32+/S32-322474
BTS3002CIOMUSubrack 0 - Slot 0The BTS3002C alarm cable AW1blue/whiteX1.7/X1.513730
W1orange/whiteX1.8/X1.523732
W1green/whiteX1.9/X1.533734
43736
BTS3002CEACSubrack 0 - Slot 2W5(RS485)Cable of the SensorNot Provided13860
Cable of the SensorNot Provided23862
Cable of the SensorNot Provided33864
Cable of the SensorNot Provided43866
Cable of the SensorNot Provided53868
Cable of the SensorNot Provided63870
Cable of the SensorNot Provided73872
Cable of the SensorNot Provided83874
Cable of the SensorNot Provided93876
Cable of the SensorNot Provided103878
NOTE:
For the BTS3012, the common subrack is defined as subrack 0.
Note that the alarms (labelled Not Provided) are reported through the RS485 communication specification, and you are advised to use the full-colored cables.
Slot 0 and Slot 1 are not operating in active/standby mode.
&L&G&C&F&R&","
&L&D&C&R&P&N
Sheet2
&L&G&C&F&R&","
&L&D&C&R&P&N
Sheet3
&L&G&C&F&R&","
&L&D&C&R&P&N