GS3055-I InstallationProcess
CONFIDENTIAL
GS3055-I Overview
The GS3055-I is:
1. A universal wireless alarm communicator that can be used as a backup or primary communicator
2. A device which connects the alarm control panel to the GSM network and reports alarm signals directly to a monitoring central station receiver (Sur-Gard System III with a DRL3-IP line card or System II)
3. A digital transmitter which provides full reporting from any control panel that communicates using Contact ID format
CONFIDENTIAL
GS3055-I Service Provider
Who is CONNECT 24?
• CONNECT 24 is the GS3055-I service provider
• CONNECT 24 provides the automated telephone activation system for the activation of GS3055-I units (GVRU, Voice Response Unit)
• CONNECT 24 provides the web-user interface support for the programming of GS3055-I units (future use)
• CONNECT 24 provides account administration, billing and rate plans to GS3055-I customers
CONFIDENTIAL
GS3055-I Enrolment Steps
In order to properly enrol a GS3055-I unit you must follow these steps:
Important Note: Prior to installing a GS3055-I you must first become an authorized dealer. Please consult your central monitoring station for master reseller programs or visit www.connect24.com and complete the authorization form
STEP 1 – Activate your SIM card with Connect 24*
STEP 2 – Initialize the GS3055-I with Connect 24*
STEP 3 – Determine best signal strength location
STEP 4 - Connect the GS3055-I to the control panel
STEP 5 - Program the control panel to use the GS3055-I
STEP 6 – Test the GS3055-I
* Note: GS3055-I unit must be powered down for STEPS 1 and 2
CONFIDENTIAL
GS3055-I SIM Card Activation (GVRU)
Prior to installation, each SIM Card must be activated via the Connect 24 GVRU (1-866-910-3865, option [6]). Activations must be performed at least 24 hours before to installation (initialization)
The following information is required when activating a SIM Card:
1. Installer’s ID Number: Identifies each installer listed on the Dealer Enrolment Form
2. Installer’s PIN Number: Identifies each installer with a 4 digit PIN number
3. The SIM Card Number: (Subscriber Identity Module), 19-20 digits located on SIM Card
Note: Only authorized dealers can activate a SIM Card with CONNECT 24
CONFIDENTIAL
GS3055-I Initialization (GVRU)
GS3055-I initializations can be performed via the Connect 24 GVRU (1-866-910-3865, option [4])
Enter the following information and options when initializing a unit:
1. Profile Number: Represents the Central Station Receiver IP address and Rate Plan
2. Installer’s ID Number: Identifies the installer listed on the Dealer Enrolment Form
3. Installer’s PIN Number: Identifies the installer
4. The Central Station Account Number: Represents the account number that will be transmitted to the Central Station Receiver
5. The SIM Card Number: (Subscriber Identity Module), 19-20 digits located on SIM Card
6. The DNIS Number: (Dialled Number Information Service), Check with your Central Station
7. Test transmission selection: select the required test schedule (no test, daily, weekly or monthly)
8. Determine if GS3055-I unit is the primary or backup communicator: enable/disable TLM (telephone line monitor) option
Note: Only authorized dealers can activate a SIM Card with CONNECT 24
CONFIDENTIAL
GS3055-I Signal Strength Test
To test the signal strength of a GS3055-I:
1. Connect the antenna to the GS3055-I
2. Ensure that the SIM card is installed into the GS3055-I
3. Connect the battery to the GS3055-I
Signal strength levels:
LED#3 and LED#4 ON = Excellent Signal Strength
LED#4 ON = Good Strength
LED#4 Flashing = Poor Signal Strength
Both OFF = No signal Strength
Note: For proper installation, a GS3055-I must have Good or Excellent Signal Strength. If a poor strength is detected, the unit should be relocated or an antenna extension should be used
LED# 3LED #4
CONFIDENTIAL
GS3055-I – Telephone Wiring (Back-up Mode)
To Premise Telephones
From RJ-31X Demarcation
To Power Supply
CONFIDENTIAL
GS3055-I Control Panel Programming
The following control panel programming is required :
• Telephone number * • Account number• Communications format – Contact ID• Reporting codes or select automatic reporting**• Communications enabled
*If communicating only using the GS3055-I (no land-line), programany telephone number **If supported by the control panel
CONFIDENTIAL
GS3055-I Testing
To test the GS3055-I, perform the following:
1. Disconnect the telephone line from the TIP and RING terminals on the GS3055-I
2. Wait for LED 2 (YELLOW) to turn ON (indicates that the unit is in GSM mode)
3. Force the control panel to transmit a signal (i.e. zone alarm, keypad alarm etc.)
4. Connect a handset to RING and TIP on the control panel to verify that the control panel is communicating
CONFIDENTIAL
GS3055-I – Testing Diagram
To Premise Telephones
To Power Supply
Connect the 12V/1.2AH Battery to the GS3055-I
CONFIDENTIAL
GS3055-I Assistance Directory
Connect 24
Phone Number: 1-888-955-5583 (Canada)1-888-251-7458 (US)
Fax: 1-877-224-3676Website: www.connect24.comE-mail: [email protected] Activation and Initialization: 1-866-910-3865
DSC Technical Support
Phone Number: 1-800-387-3630E-mail: [email protected]: www.dsc.com
CONFIDENTIAL
GS3055-I
Questions?