Glands_Accessories LSF.pdf

Embed Size (px)

Citation preview

  • 8/13/2019 Glands_Accessories LSF.pdf

    1/44

  • 8/13/2019 Glands_Accessories LSF.pdf

    2/44

    12:2

    12

    Glands

    Cable glands are designed to provide some or all of the following functions in a cabling system:

    Mechanical connection: Locate and anchor cable. Earth continuity: Armour termination.

    Ingress Protection: Protect against dust and liquids.

    Hazardous area: Flameproof protection.

    The design of cable glands are covered by BS6121, which covers size, finish, materials,

    performance, etc. The gland designs are basically a combination of compatibility with cable and

    installation requirements.

    GLAND TYPES

    There are several distinct gland types covered in BS6121 Part 1;

    A Type

    B Type

    C Type

    D1 Type

    E1 Type

    D2 Type

    E2 Type

    Suffixes are used to identify the type of armour on a cable:

    W = single wire armour

    X = wire braid armour

    Y = aluminium wire armour

    Z = steel tape armoured

    Hence, CW would be a single wire armour, whereas CX would be for a braid armour. The only

    difference is in the armour lock which caters for the physical size of the armour.

    ACCESSORIES

  • 8/13/2019 Glands_Accessories LSF.pdf

    3/44

    12

    ACCESSORIES

    12:3

    Gland Type Application/Use

    A1/A2 Indoor/outdoor brass gland for use with unarmoured cable.

    BW Indoor, low-cost, two-part brass gland for use with single wire armoured cable.

    CW Indoor/outdoor brass glands for use with single wire armoured cable.

    Provides seal on outer sheath of cable and separate armour locking ring.

    NB: Aluminium gland available for aluminium wire armoured cable.

    CX Indoor/outdoor brass gland for use with braid armoured cables. Provides

    seal on outer sheath of cable and separate armour locking ring.

    E1W Indoor/outdoor brass gland for use with single wire armour cable. Provides

    seal on inner and outer sheaths of cable, and has separate armour locking ring.

    LSF Glands

    BW Indoor, low cost, two-part brass gland for use with LSF single wire

    armoured cables.

    CW Indoor/outdoor brass gland for use with LSF single wire armoured cables.

    Provides LSF seal onto outer sheath of cable and separate armour locking ring.

    Glands for Hazardous Areas

    A2F Indoor/outdoor brass gland for use with unarmoured cables. For use with

    flameproof or increased safety equipment (E.Exd or E.Exe)

    E1WF Indoor/outdoor brass gland for use with single wire armoured cable.Provides seal on inner and outer sheaths of cable, and has separate locking

    ring. For use with flameproof or increased safety equipment (E.Exd or E.Exe)

    E1XF Indoor/outdoor brass gland for use with braid armoured cable. Provides

    seal on inner and outer sheaths of cable, and has separate armour locking

    ring. For use with flameproof or increased safety equipment (E.Exd or E.Exe).

    E2WF Indoor/outdoor brass gland for use with single wire armoured and lead

    sheathed cables (eg. EEMUA types, BS5308 PT1/Type 3). Provides seal

    onto outer sheath of cable. Inner seal grips and provides earth continuity to

    lead sheath. Design has separate armour locking ring. For use withflameproof or increased safety equipment (E.Exd or E.Exe).

    BARR-X Indoor/outdoor brass barrier gland for use with a braid armoured cable.

    Provides seal on outer sheath of cable, and solid setting compound

    squeezed into the interstices of cable when installed to prevent escape of

    gases through centre of cable. For use with explosion proof equipment.

  • 8/13/2019 Glands_Accessories LSF.pdf

    4/44

    12:4

    12

    I.P Ratings for Cable Glands

    I.P. (Ingress Protection) Ratings detail the degree of protection against solid

    bodies and liquids, and is tested against IEC 144.

    Generally any seal has a rating of IP66.

    However, since they are tested in isolation, when they are in conjunction with a

    piece of equipment this needs to be taken into consideration.

    Generally the following can be taken:-

    1. Gland used in Plain Entry with Backnut - IP54.

    2. Gland used in Plain Entry with sealing washer between gland and equipment

    interface - IP66.

    3. Gland used in Tapped Entry - IP65.

    4. These can be uprated by the use of Sealing washers and Thread Sealants.

    5. Special designs of Gland are available which can achieve an IP Rating of

    IP68. (NB. Interface with equipment then becomes critical.)

    ACCESSORIES

  • 8/13/2019 Glands_Accessories LSF.pdf

    5/44

    12

    12:5

    Degree of Protection IEC 144 I.P. Ratings

    First ProtectionDigit (Against solid bodies)

    0 No protection

    1 Protected against solid bodies larger than 50mm, eg, accidentalcontact with hand.

    2 Protected against solid bodies larger than 12mm, eg, finger.

    3 Protected against solid bodies larger than 2.5mm, eg, tools and wires.

    4 Protected against solid bodies larger than 1.0mm, eg, fine tools andsmall wires.

    5 Protected against dust (no harmful deposits).

    6 Completely protected against dust.

    Second ProtectionDigit (Against Liquids)

    0 No protection.

    1 Protected against vertically falling drops of water (condensation).

    2 Protected against drops of water falling at up to 150 from the vertical.

    3 Protected against rain falling at 600 from vertical.

    4 Protected against splashes of water from all directions.

    5 Protected against jets of water from all directions.

    6 Protected against jets of water of similar force to heavy seas.

    7 Protected against the effects of temporary immersion.

    8 Protected against prolonged effects of immersion under pressure.

    ACCESSORIES

  • 8/13/2019 Glands_Accessories LSF.pdf

    6/44

    12:6

    12

    A1/A2 Brass Gland with Outer Seal

    To BS6121: Part 1.

    Suitable for unarmoured, plastic orrubber sheathed cables.

    Suitable for most indoor and outdoor

    applications.

    Seal rated to IP66

    Glands are supplied in kit form, complete with locknuts and shrouds.

    Up to size 25:- 2 per kit

    Size 32 and above:- 1 per kit

    CABLE & GLAND DETAILS

    E1AW-A1/A2-20SS Pirelli 20SS 3.5 8.5

    E1AW-A1/A2-20S Pirelli 20S 8.0 11.5

    E1AW-A1/A2-20 Pirelli 20 11.0 13.5

    E1AW-A1/A2-25 Pirelli 25 13.0 19.5

    E1AW-A1/A2-32 Pirelli 32 19.0 25.5

    E1AW-A1/A2-40 Pirelli 40 25.0 32.0

    E1AW-A1/A2-50S Pirelli 50S 31.5 37.0

    E1AW-A1/A2-50 Pirelli 50 36.5 43.0

    E1AW-A1/A2-63S Pirelli 63S 42.5 50.0

    Anixter Gland Gland Cable dimensionsPart No. Manu Size accomodated

    Overall diameterMin Max

    ACCESSORIES

  • 8/13/2019 Glands_Accessories LSF.pdf

    7/44

    12

    12:7

    CX Brass Gland with Outer Seal

    BS6121: Part 1

    Suitable for wire braid armoured, plastic or rubber

    sheathed cables.

    Outer seal grips sheath of cable.

    Weatherproof and water proof.

    Seal rated to IP66.

    Design has separate armour locking ring.

    Gland rated to IP66 with use of suitable sealing

    washer or thread sealant at gland interface

    Glands are supplied in kit form, complete with locknuts, earthtags and shrouds.

    Up to size 25:- 2 per kit

    Size 32 and above:- 1 per kit

    CABLE & GLAND DETAILS

    Anixter Gland Gland Cable dimensions

    Part No. Manu Size accomodated

    Under armour Overall

    Min Max Min Max

    E1AH-CX-20SS Pirelli 20SS - 8.6 8.0 13.2

    E1AH-CX-20S Pirelli 20S - 11.6 8.0 15.8

    E1AH-CX-20 Pirelli 20 - 13.9 12.9 20.8

    E1AH-CX-25 Pirelli 25 - 19.9 17.0 27.2

    E1AH-CX-32 Pirelli 32 - 26.2 23.5 33.5

    E1AH-CX-40 Pirelli 40 - 32.1 29.0 39.9

    ACCESSORIES

  • 8/13/2019 Glands_Accessories LSF.pdf

    8/44

    ACCESSORIES

    12:8

    12

    CXT Brass Gland with Outer Seal

    Gland reference not specified in BS6121:Part 1. However, gland complies in

    all other respects with the design and test requirements of Type A2 cable glands.

    Suitable for wire braid armoured/screened, plastic or rubber sheathed cables. Outer seal grips sheath of cable.

    Weatherproof and water proof.

    Seal rated to IP66.

    Integral knurled armour lock.

    Gland rated to IP66 with use of suitable sealing

    washer or thread sealant at gland interface

    Glands are supplied in kit form, complete with locknuts, earthtags and shrouds.

    Up to size 32:- 2 per kit

    Size 40 and above:- 1 per kit

    CABLE & GLAND DETAILS

    Anixter Gland Gland Cable dimensions

    Part No. Manu Size accomodated

    Overall

    Min Max

    E1AH-CXT-20S CMP 20S 6.1 11.6

    E1AH-CXT-20 CMP 20 6.5 13.9

    E1AH-CXT-25 CMP 25 11.1 19.9

    E1AH-CXT-32 CMP 32 17.0 26.2

    E1AH-CXT-40 CMP 40 22.0 32.1

  • 8/13/2019 Glands_Accessories LSF.pdf

    9/44

    12:9

    12

    ACCESSORIES

    Ultech Nylon Gland with Outer SealFor non-armoured cable

    Suitable for unarmoured, plastic or rubber sheathed cables.

    Polyamide 6 nylon gland with neoprene seal.

    Compact skin-top design

    Quick and easy assembly

    Halogen free and UL94-V2 flammability rated.

    Seal rated IP68 at 5 bar.

    Temperature range: -30C to +80C

    Grey RAL 7001 colour

    ISOMETRIC thread.

    10mm thread length for gland sizes 16-25, 18mm for gland size 32.

    Ultech is a registered trade name of Elkay International

    Glands are supplied in kit form, complete with nylon washer and locknut. Allsizes: 2 per kit.

    NB: Mini-size polyamide 6.6 standard nylon gland is also available for IP66 ratednitrile seal for small diameter cable. Details as follows:-

    CABLE & GLAND DETAILS

    E1AV-ULT-16 Elkay 270-8011 16 5.0 10.0

    E1AV-ULT-20S Elkay 270-8021 20S 6.0 12.0

    E1AV-ULT-20 Elkay 270-8031 20 10.0 14.0

    E1AV-ULT-25 Elkay 270-8061 25 13.0 18.0

    E1AV-ULT-32 Elkay 270-8071 32 18.0 25.0

    Anixter Part Gland Gland Manf. Gland Size Cable DimensionsNumber Manf. Part Number accommodated (mm)

    Overall diameter

    Minimum Maximum

  • 8/13/2019 Glands_Accessories LSF.pdf

    10/44

    ACCESSORIES

    12:10

    12

    Mini - Gland

    Halogen free and UL94-V2 flammability rated.

    -20C to +90C temperature range. Grey RAL 7001 colour.

    ISOMETRIC thread.

    8mm thread length.

    Glands are supplied in kit form with nylon washer and locknut 2 per kit.

    CABLE & GLAND DETAILS

    E1AV-MINI-13 Elkay 239-B M13 2.0 5.0

    Anixter Part Gland Gland Manf. Gland Size Cable Dimensions

    Number Manf. Part Number accommodated (mm)Overall diameter

    Minimum Maximum

  • 8/13/2019 Glands_Accessories LSF.pdf

    11/44

    12

    ACCESSORIES

    12:11

    LSF Standard Cable Gland forNon-Armoured Cable

    Suitable for unarmoured plastic or rubber sheathed cables.

    Polyamide 6.6 nylon gland with nitrile rubber seal.

    Quick and easy assembly.

    Halogen free and UL94-V2 flammability rated.

    Seal rated at IP66.

    -20C to +90C temperature range.

    Black RAL 9005 colour.

    ISO METRIC thread. 11mm thread length

    LSF glands meet following standards:- BS6853 App B5.1, BS7878, BS2782

    M141, IEC 60754-1, IEC 60754-2, BS6425, NES713/Iss 3.

    Glands are supplied in kit form, complete with washer and locknut.

    CABLE & GLAND DETAILS

    E1AV-LSF-20SS Elkay 249-LSF 20SS 4.0 6.0

    E1AV-LSF-20S Elkay 251-LSF 20S 7.0 10.0

    E1AV-LSF-20 Elkay 252-LSF 20 8.0 13.0

    Anixter Part Gland Gland Manf. Gland Size Cable DimensionsNumber Manf. Part Number accommodated (mm)

    Overall diameterMinimum Maximum

  • 8/13/2019 Glands_Accessories LSF.pdf

    12/44

    ACCESSORIES

    12:12

    12

    TECHNICAL DATA

    ASTM Oil No. 2 SAcetaldehyde LAcetic acid (10%) L

    Acetic acid (glacial) LAcetone SAmmonium Hydroxide (35%) SBenzene SBenzyl Alcohol LBromine (liquid) UButyl Alcohol SButyl Acetate SButylamine SCarbon Tetrachloride SChlorine Gas UCitric acid (10%) SCresols UCyclohexane SDiesel oil SDiethyl ether SEthanol SEthylamine LEthylene glycol SFormaldehyde SHexane SHydrochloric acid (10%) UHydrochloric acid (conc) UHydrogen peroxide (35%) L

    Chemical Agent Nylon

    Hydrogen sulphide (gas) SIso-octane SIso-propanol S

    Lubricating oil SMethanol LNitric acid (10%) UNitric acid (conc) UOzone (gas) LParaffin oil SPetrol SPhenol USilicone oils SSodium hydroxide (60%) SSodium hypochlorite (bleach) LStyrene SSulphur dioxide (gas) USulphuric acid (10%) USulphuric acid (70%) UToluene STransformer oil STrichloroethylene LTricresyl phosphate (SKYDROL) STurps SWhite spirit SXylene SZinc chloride U

    Chemical Agent Nylon

    APPLICABLE TO NYLON GLANDS - CHEMICAL

    RESISTANCE

    Listed below is the general chemical resistance

    information for the materials used to manufacture themajority of products in this catalogue.S = SuitableL = Limited suitability

    U = Unsuitable

  • 8/13/2019 Glands_Accessories LSF.pdf

    13/44

    12

    ACCESSORIES

    12:13

    Index EMC Nickel Plated Brass Gland forBraid Screened Cable

    12

    3

    456

    FEATURES.

    1. Compression Nut

    2. Santoprene Seal

    3. Endless Spring

    4. Tapered Ring

    5. O Ring

    6. Gland Body

    For use with braid screened cable to connect screen to the enclosure system.

    Two tapered rings applying force onto an endless spring washer ensure positive

    and intimate contact for efficient screening.

    Screen can continue into enclosure.

    Suitable for systems conforming to EN50082.

    Nickel plated brass gland body with santoprene rubber seal.

    Seal rated IP68 at 1 bar.

    -40 to +135C temperature range. ISO METRIC thread with exception of gland for 4-6mm diameter cable which has

    P.G.7 thread to DIN40430.

    Glands are supplied in kit form complete with locknut. All sizes: 2 per kit.

    E1AH-EMC-7 Elkay 261-1000 PG7 1.5 4.0 4.0 6.0

    E1AH-EMC-16 Elkay 260-1000 M16 3.0 7.0 6.0 8.0

    E1AH-EMC-20 Elkay 260-1250 M20 4.0 8.5 8.0 10.5

    E1AH-EMC-25SSS Elkay 260-1400 M25 6.5 10.0 10.0 11.5

    E1AH-EMC-25SS Elkay 260-1450 M25 8.0 12.0 11.0 14.0

    E1AH-EMC-25S Elkay 260-1500 M25 8.0 12.0 14.0 16.6

    E1AH-EMC-25 Elkay 260-1600 M25 12.5 17.5 17.0 20.0

    E1AH-EMC-32S Elkay 260-1650 M32 15.0 21.0 19.0 23.0

    E1AH-EMC-32 Elkay 260-1700 M32 15.0 21.0 22.0 27.0

    Anixter Part No. Gland Gland Gland Cable Dimensions Accommodated (mm)

    Manf. Manf. Part Size Over Screen Cable Diameter

    No. Min. Max. Min. Max.

  • 8/13/2019 Glands_Accessories LSF.pdf

    14/44

    ACCESSORIES

    2:14

    12

    CW Brass Gland with Outer Seal

    BS6121: Part 1

    Suitable for wire armoured, plastic or rubber

    sheathed cables.

    Outer seal grips sheath of cable.

    Weatherproof and water proof.

    Seal rated to IP66.

    Design has separate armour locking ring (Pirelli glands only).

    Gland rated to IP66 with use of suitable

    sealing washer or thread sealant at gland

    interface

    Brass glands are provided with steel locknuts and aluminium glands are provided

    with aluminium locknuts. For more corrosive environments brass locknuts may

    be supplied.

    Glands are supplied in kit form complete with locknuts, earthtags and shrouds.

    Pirelli Up to size 25: - 2 per kit

    Size 32 and above:- 1 per kit

    CMP Up to size 32:- 2 per kit

    Size 40 and above:- 1 per kit

  • 8/13/2019 Glands_Accessories LSF.pdf

    15/44

    12

    ACCESSORIES

    12:15

    CABLE & GLAND DETAILS

    E1AG-CW-20SSC Pirelli 20SS - 8.6 8.0 13.2

    E1AG-CW-20SS CMP 20SS* - 8.6 8.0 13.4

    E1AG-CW-20SC Pirelli 20S - 11.6 8.0 15.8

    E1AG-CW-20S CMP 20S - 11.6 11.4 15.9

    E1AG-CW-20C Pirelli 20 - 13.9 12.9 20.8

    E1AG-CW-20 CMP 20 - 13.9 15.0 20.9

    E1AG-CW-25C Pirelli 25 - 19.9 17.0 27.2

    E1AG-CW-25 CMP 25 - 19.9 20.3 27.4

    E1AG-CW-32C Pirelli 32 - 26.2 23.5 33.5

    E1AG-CW-32 CMP 32 - 26.2 26.0 33.9

    E1AG-CW-40C Pirelli 40 - 32.1 29.0 39.9

    E1AG-CW-40 CMP 40 - 32.1 31.0 40.4

    E1AG-CW-50SC Pirelli 50S - 38.1 38.0 46.2

    E1AG-CW-50S CMP 50S - 38.1 36.5 46.7

    E1AG-CW-50C Pirelli 50 - 44.0 39.5 52.6

    E1AG-CW-50 CMP 50 - 44.0 43.0 53.1

    E1AG-CW-63S CMP 63S - 50.0 48.9 59.4

    E1AG-CW-63C Pirelli 63 - 55.9 51.3 65.3

    E1AG-CW-63 CMP 63 - 55.9 58.0 65.9

    E1AG-CW-75C Pirelli 75 - 67.9 62.5 78.0

    E1AG-CW-75 CMP 75 - 67.9 64.9 78.5

    Aluminium CW glands for aluminium wire armoured cable

    E1DN-CW-25 Pirelli 25 - 19.9 17.0 27.2

    E1DN-CW-32 Pirelli 32 - 26.2 23.5 33.5E1DN-CW-40 Pirelli 40 - 32.1 29.0 39.9

    E1DN-CW-50SC CMP 50S - 38.1 36.5 46.7

    E1DN-CW-50 Pirelli 50 - 44.0 39.5 52.6

    Anixter Gland Gland Cable dimensions

    Part No. Manu Size accomodated

    Under armour Overall

    Min Max Min Max

    NB Pirelli glands have separate armour locking rings.CMP glands have integral knurled armour lock.

    * Also known as 20/16 (CMP only),

  • 8/13/2019 Glands_Accessories LSF.pdf

    16/44

    ACCESSORIES

    2:16

    12

    BW Brass Gland

    BS6121: Part 1

    Suitable for single wire armoured,

    plastic or rubber sheathed cables. For use in dry, indoor situations.

    Low-cost two-part design.

    IP54

    Shroud may be used for additional

    ingress protection

    Glands are supplied in kit form complete with locknuts, earthtags and shrouds.

    Pirelli Up to size 25: - 2 per kit

    Size 32 and above:- 1 per kit

    CMP Up to size 32:- 2 per kitSize 40 and above:- 1 per kit

    CABLE & GLAND DETAILS

    E1AJ-BW-20SC Pirelli 20S - 11.6 - 15.8

    E1AJ-BW-20S CMP 20S - 11.6 - 16.1

    E1AJ-BW-20C Pirelli 20 - 13.9 - 20.8

    E1AJ-BW-20 CMP 20 - 13.9 - 21.1

    E1AJ-BW-25C Pirelli 25 - 19.9 - 27.2

    E1AJ-BW-25 CMP 25 - 19.9 - 27.4

    E1AJ-BW-32C Pirelli 32 - 26.2 - 33.5

    E1AJ-BW-32 CMP 32 - 26.2 - 34.4

    E1AJ-BW-40C Pirelli 40 - 32.1 - 39.9

    E1AJ-BW-40 CMP 40 - 32.1 - 42.4

    E1AJ-BW-50S CMP 50S - 38.1 - 50.1

    E1AJ-BW-50C Pirelli 50 - 44.0 - 52.6

    E1AJ-BW-50 CMP 50 - 44.0 - 55.7E1AJ-BW-63C Pirelli 63 - 55.9 - 65.3

    E1AJ-BW-63 CMP 63 - 55.9 - 68.2

    E1AJ-BW-75C Pirelli 75 - 67.9 - 78.0

    E1AJ-BW-75 CMP 75 - 67.9 - 82.9

    Anixter Gland Gland Cable dimensions

    Part No. Manu Size accomodated

    Under armour Overall

    Min Max Min Max

  • 8/13/2019 Glands_Accessories LSF.pdf

    17/44

    12

    ACCESSORIES

    12:17

    E1W Brass Gland with Inner andOuter Seals

    BS6121: Part 1

    Suitable for single wire armoured, plasticor rubber sheathed, extruded bedded cables.

    Outer seal grips sheath of cable.

    Inner seal grips bedded layer of cable.

    Weatherproof and waterproof.

    Inner and outer seal rated to IP66

    Gland rated to IP66 with use of suitable sealing washer or thread sealant at

    gland interface.

    Glands are supplied in kit form complete with locknuts, earthtags and shrouds.

    Pirelli Up to size 25: - 2 per kit Size 32 and above:- 1 per kit

    CMP Up to size 32:- 2 per kit Size 40 and above:- 1 per kitNB Pirelli glands have separate armour locking rings.

    CMP glands have integral knurled armour lock.

    CABLE & GLAND DETAILS

    E1BA-E1W-20S Pirelli 20S 8.7 11.6 8.0 15.8

    E1BA-E1W-20SC CMP 20S 6.1 11.6 11.4 15.9

    E1BA-E1W-20 Pirelli 20 11.7 13.9 12.9 20.8

    E1BA-E1W-20C CMP 20 6.5 13.9 15.0 20.9

    E1BA-E1W-25 Pirelli 25 13.0 19.9 17.0 27.2

    E1BA-E1W-25C CMP 25 11.1 19.9 20.3 27.4

    E1BA-E1W-32 Pirelli 32 20.0 26.2 23.5 33.5

    E1BA-E1W-32C CMP 32 17.0 26.2 26.0 33.9

    E1BA-E1W-40 Pirelli 40 26.3 32.1 29.0 39.9

    E1BA-E1W-40C CMP 40 22.0 32.1 31.0 40.4

    E1BA-E1W-50S Pirelli 50S 32.2 38.1 38.0 46.2

    E1BA-E1W-50SC CMP 50S 29.5 38.1 36.5 46.7E1BA-E1W-50 Pirelli 50 38.2 44.0 39.5 52.6

    E1BA-E1W-50C CMP 50 35.6 44.0 43.0 53.1

    E1BA-E1W-63 Pirelli 63 50.1 55.9 51.3 65.3

    E1BA-E1W-63C CMP 63 47.2 55.9 58.0 65.9

    E1BA-E1W-75S Pirelli 75S 56.0 61.9 62.0 71.6

    Anixter Gland Gland Cable dimensions

    Part No. Manu Size accomodated

    Under armour Overall

    Min Max Min Max

  • 8/13/2019 Glands_Accessories LSF.pdf

    18/44

    ACCESSORIES

    2:18

    12

    Low Smoke and Fume Gland Kits

    Convenient ready to use kits.

    Contain everything necessary to terminate an LSF cable run - gland(s) withLSF seal(s), backnuts(s), earth tag(s) and LSF shroud(s).

    Zero halogen.

    Complies with the test criteria of BS6724, BS6853 category 1.

    Continuous operating temperature of -500C to 1500C

    Resists most chemicals, solvents, acids, alkalis, oils, moisture, steam and UV

    light.

    Excellent tear resistance.

    NOTE: The materials utilised in these kits are noted for the absence of smoke

    generating constituents, particularly halogens (flourine, bromine and chlorine)

    thus avoiding the hazards of highly irritant and toxic fumes emitted by standard

    materials such as PCP and PVC when exposed to flame.

  • 8/13/2019 Glands_Accessories LSF.pdf

    19/44

    12

    ACCESSORIES

    12:19

    BW Brass Gland - LSF

    To BS6121: Part 1.

    Suitable for single wire armoured,

    plastic or rubber sheathed cables. For use in dry, indoor situations.

    Low cost two-part design.

    IP54.

    LSF shroud may be used for additional

    ingress protection.

    Glands are supplied in kit form, complete with locknuts and shrouds.

    Up to size 25:- 2 per kit

    Size 32 and above:- 1 per kit

    CABLE & GLAND DETAILS

    E1AJ-BW-20SLSF Pirelli 20S - 11.6 - 15.8

    E1AJ-BW-20LSF Pirelli 20 - 13.9 - 20.8

    E1AJ-BW-25LSF Pirelli 25 - 19.9 - 27.2

    E1AJ-BW-32LSF Pirelli 32 - 26.2 - 33.5

    E1AJ-BW-40LSF Pirelli 40 - 32.1 - 39.9

    E1AJ-BW-50LSF Pirelli 50 - 44.0 - 52.6

    E1AJ-BW-63LSF Pirelli 63 - 55.9 - 65.3

    E1AJ-BW-75LSF Pirelli 75 - 67.9 - 78.0

    Anixter Gland Gland Cable dimensions

    Part No. Manu Size accomodated

    Under armour Overall

    Min Max Min Max

  • 8/13/2019 Glands_Accessories LSF.pdf

    20/44

    ACCESSORIES

    2:20

    12

    CW Brass Gland with Outer LSF Seal

    To BS6121: Part 1.

    Suitable for single wire armoured, plastic

    or rubber sheathed cables.

    Outer LSF seal grips sheath of cable.

    Weatherproof and waterproof.

    Seal rated to IP66

    Design has separate armour locking ring.

    Gland rated to IP66 with use of suitable sealing

    washer or thread sealant at gland interface.

    Glands are supplied in kit form, complete with locknuts and LSF shrouds.

    Up to size 25:- 2 per kit

    Size 32 and above:- 1 per kit

    CABLE & GLAND DETAILS

    E1AG-CW-20SSLSF Pirelli 20SS - 8.6 8.0 13.2

    E1AG-CW-20SLSF Pirelli 20S - 11.6 8.0 15.8

    E1AG-CW-20LSF Pirelli 20 - 13.9 12.9 20.8

    E1AG-CW-25LSF Pirelli 25 - 19.9 17.0 27.2

    E1AG-CW-32LSF Pirelli 32 - 26.2 23.5 33.5

    E1AG-CW-40LSF Pirelli 40 - 32.1 29.0 39.9

    E1AG-CW-50SLSF Pirelli 50S - 38.1 38.0 46.2

    E1AG-CW-50LSF Pirelli 50 - 44.0 39.5 52.6

    E1AG-CW-63LSF Pirelli 63 - 55.9 51.3 65.3

    E1AG-CW-75LSF Pirelli 75 - 67.9 62.5 78.0

    Anixter Gland Gland Cable dimensions

    Part No. Manu Size accomodated

    Under armour Overall

    Min Max Min Max

  • 8/13/2019 Glands_Accessories LSF.pdf

    21/44

    12

    ACCESSORIES

    12:21

    Selecting Glands for Hazardous AreasZONE CLASSIFICATION

    Zone 0 (Division 0)

    Explosive gas/air mixture is continuously present or for long periods. No

    equipment should be terminated in this zone.

    Zone 1 (Division 1)

    Explosive gas/air mixture is likely to occur in normal operation.

    Zone 2 (Division 2)

    Explosive gas/air mixture is not likely to occur and if so, only for a short period of time.

    Increased Safety Glands(E.Exe)

    For use in hazardous environments and comply with EN50014 and EN 50019

    (BS5501 Part 1 and Part 6). These glands can only be used where no parts of

    the electrical equipment can produce sparks/arcing or exceeds the gas ignition

    temperature. E.Exe glands are normally recommended for Zone 2 applications

    but can be used in Zone 1, i.e. indirect entry situations.

    Flameproof (E.Exd) Glands

    For use in hazardous environments and comply with EN50014 and EN50018

    (BS5501 Part 1 and Part 5). These glands are approved for direct entry

    applications in Zone 1 areas, IIA, IIB or IIC gas groups with the exception of A2Fglands which are for IIA and IIB groupings - may also be used in Zone 2 areas.

    Explosion Proof Barrier Glands

    For use in hazardous environments and comply with EN50014 and EN 50018

    (BS5501 Part 1 and Part 5). These glands are approved for direct entry

    applications in Zone 1 areas, IIA, IIB, or more commonly IIC gas groups.

    Selecting Barrier Glands as opposed to Conventional Flameproof Glands

    The main applications for the specification of barrier glands in accordance with

    the relevant codes of practice, can be summarised as follows:

    with enclosures containing an ignition source and installed in Group IIC gas areas

    with an enclosure containing an ignition source and in a Zone 1 area where

    the volume of the enclosure exceeds 2 litres

    with cables other than those specified in BS5308, BS5467, BS6116, BS6346

    and 6883

    where 'cold flow' of cable installation is considered a possibility

    to prevent gas migration from one area to another to prevent moisture migration in cables

    where the user assessment considers a barrier gland essential for safety

  • 8/13/2019 Glands_Accessories LSF.pdf

    22/44

  • 8/13/2019 Glands_Accessories LSF.pdf

    23/44

    12

    ACCESSORIES

    12:23

    CABLE & GLAND DETAILS

    E1BN-E1WF-20SS Pirelli 20SS 3.81 8.74 8.0 13.2

    E1BN-E1WF-20S Pirelli 20S 8.0 11.79 8.0 15.8

    E1BN-E1WF-20 Pirelli 20 11.79 14.15 12.9 20.8

    E1BN-E1WF-25 Pirelli 25 14.0 20.12 17.0 27.2

    E1BN-E1WF-32 Pirelli 32 19.7 26.55 23.5 33.5

    E1BN-E1WF-40 Pirelli 40 26.55 32.42 29.0 39.9

    E1BN-E1WF-50 Pirelli 50 38.39 44.33 39.5 52.6

    E1BN-E1WF-63 Pirelli 63 50.27 56.24 51.3 65.3

    Anixter Gland Gland Cable dimensions

    Part No. Manu Size accomodated

    Under armour Overall

    Min Max Min Max

    E1WF Flameproof Gland with Inner & Outer Seals

    Suitable for single wire armoured, plastic or rubber sheathed, extruded bedded cables.

    Outer seal grips sheath of cable.

    Inner seal grips bedded layer of cable.

    Weatherproof and waterproof.

    Inner and outer seal rated to IP66

    Design has separate outer locking ring. Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface.

    For use with flameproof equipment or increased safety equipment.

    Complies with group II C hazardous atmospheres EN50014 and EN50018 (BS5501

    Part 1 and Part 5).

    BASEEFA Approved.

    Zone 1 and Zone 2 applications.

    Pirelli glands are supplied in kit form completPirellie with locknuts, earthtags and shrouds.Up to size 25: - 2 per kit Size 32 and above:- 1 per kit

  • 8/13/2019 Glands_Accessories LSF.pdf

    24/44

    ACCESSORIES

    2:24

    12

    CABLE & GLAND DETAILS

    E1BP-E1XF-16 Pirelli 16 3.81 8.74 8.0 13.2

    E1BP-E1XF-20SS Pirelli 20SS 3.81 8.74 8.0 13.2

    E1BP-E1XF-20S Pirelli 20S 8.0 11.79 8.0 15.8

    E1BP-E1XF-20 Pirelli 20 11.79 14.15 12.9 20.8

    E1BP-E1XF-25 Pirelli 25 14.0 20.12 17.0 27.2

    E1BP-E1XF-32 Pirelli 32 19.7 26.55 23.5 33.5

    E1BP-E1XF-40 Pirelli 40 26.55 32.42 29.0 39.9

    E1BP-E1XF-50S Pirelli 50S 32.42 38.39 38.0 46.2

    E1BP-E1XF-50 Pirelli 50 38.39 44.33 39.5 52.6

    E1BP-E1XF-63S Pirelli 63S 44.33 50.27 50.0 58.9

    Anixter Gland Gland Cable dimensions

    Part No. Manu Size accomodated

    Under armour Overall

    Min Max Min Max

    E1XF Flameproof Gland with Inner & Outer Seals

    Suitable for wire braid armoured, plastic or rubber sheathed, extruded bedded cables.

    Outer seal grips sheath of cable.

    Inner seal grips bedded layer of cable.

    Weatherproof and waterproof.

    Inner and outer seal rated to IP66

    Design has separate outer locking ring.

    Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface.

    For use with flameproof equipment or increased safety equipment (E.Exd or E.Exe).

    Complies with group II C hazardous atmospheres EN50014 and EN50018 (BS5501

    Part 1 and Part 5).

    BASEEFA Approved.

    Zone 1 and Zone 2 applications.

    Pirelli glands are supplied in kit form complete with locknuts, earthtags and shrouds.

    Up to size 25: - 2 per kit Size 32 and above:- 1 per kit

  • 8/13/2019 Glands_Accessories LSF.pdf

    25/44

    12

    ACCESSORIES

    12:25

    CABLE & GLAND DETAILS

    E1BP-EXC-20S-A Pirelli 20S 7.0 12.0 9.0 16.0

    E1BP-EXC-20-A Pirelli 20 8.0 14.4 11.5 21.0

    E1BP-EXC-25-A Pirelli 25 10.5 20.2 18.5 27.5

    E1BP-EXC-32-A Pirelli 32 15.5 26.5 21.0 34.0

    E1BP-EXC-40-A Pirelli 40 23.0 32.5 31.0 41.5

    E1BP-EXC-50-A Pirelli 50 28.5 44.5 36.0 52.5

    E1BP-EXC-63-A Pirelli 63 44.0 56.5 50.0 65.5

    E1BP-EXC-75-A Pirelli 75 53.0 68.5 59.0 78.0

    Anixter Gland Gland Cable dimensions

    Part No. Manu Size accomodated

    Under armour Overall

    Min Max Min Max

    Excelplus Deluge Proof Flameproof & IncreasedSafety Gland with Inner & Outer Seals

    Suitable for wire braid and single wire armoured,

    plastic or rubber sheathed, extruded bedded cables. Outer seal grips sheath of cable.

    Inner seal grips bedded layer of cable.

    Weatherproof, waterproof and deluge proof.

    Inner and outer seal rated to IP67.

    Design has separate armour locking ring and

    additional locking ring to ensure integrity of

    armour lock under vibrating conditions.

    Gland rated to IP67 with use of suitable sealing washer or thread sealant at gland interface. For use with flameproof equipment or increased safety equipment (E.Exd or E.Exe).

    Dual certified.

    Complies with group II C hazardous atmospheres EN50014, EN50018 and

    EN50019 (BS5501 Part 1, Part 5 and Part 6).

    BASEEFA Approved.

    Zone 1 and Zone 2 applications.

    Supplied as gland only.

  • 8/13/2019 Glands_Accessories LSF.pdf

    26/44

    ACCESSORIES

    2:26

    12

    CABLE & GLAND DETAILS

    E1DZ-UNI-20S HAWKE 20S 7.5 11.9 9.5 16.0

    E1DZ-UNI-20 HAWKE 20 9.4 14.3 12.5 20.5

    E1DZ-UNI-25 HAWKE 25 12.1 20.2 16.9 26.0

    E1DZ-UNI-32 HAWKE 32 17.6 26.5 22.0 33.0

    E1DZ-UNI-40 HAWKE 40 23.1 32.5 28.0 41.0

    E1DZ-UNI-50 HAWKE 50 28.9 44.4 36.0 52.6

    E1DZ-UNI-63 HAWKE 63 39.9 56.3 46.0 65.3

    E1DZ-UNI-75 HAWKE 75 50.5 68.2 57.0 78.0

    Anixter Gland Gland Cable dimensions

    Part No. Manu Size accomodated

    Under armour Overall

    Min Max Min Max

    Universal Flameproof & Increased SafetyGland with Inner & Outer Seals

    Suitable for wire braid, single wire, steel tape and strip armoured plastic orrubber sheathed, extruded bedded cables.

    Outer seal grips sheath of cable.

    Inner seal grips bedded layer of cable.

    Weatherproof and waterproof.

    Inner and outer seal rated to IP66

    Design has separate outer locking ring.

    Gland rated to IP66 with use of suitable sealing washer or thread sealant at

    gland interface.

    For use with flameproof equipment or increased safety equipment (E.Exd or

    E.Exe).

    Complies with group II C hazardous atmospheres EN50014, EN50018 and

    EN50019 (BS5501 Part 1, Part 5 and Part 6).

    BASEEFA Approved.

    Zone 1 and Zone 2 applications.

    Incorporates external boot seal which offers protection against moisture

    ingress to the armour.

    Glands are supplied in kit form complete with locknut, earthtag, shroud, nylon

    washer and serrated washers.

    All sizes: 1 per kit

  • 8/13/2019 Glands_Accessories LSF.pdf

    27/44

    12

    ACCESSORIES

    12:27

    E2WF (RTLF) Flameproof Gland withInner & Outer Seals

    Suitable for SWA, plastic or rubber oversheathed, lead inner sheath cables.

    Outer seal grips sheath of cable.

    Inner seal grips and provides earth continuity to lead sheath.

    Weatherproof and waterproof.

    Inner and outer seal rated to IP66

    Design has separate outer locking ring.

    RTLF for use with flameproof equipment or increased safety equipment.

    Complies with group II C hazardous atmospheres EN50014 and EN50018

    (BS5501 Part 1 and Part 5).

    BASEEFA Approved. Zone 1 and Zone 2 applications.

    CABLE & GLAND DETAILS

    E1CF-RTLF-20SH-A HAWKE 20S 7.0 9.6 10.5 16.0

    E1CF-RTLF-20H-A HAWKE 20 8.0 12.0 12.9 20.9

    E1CF-RTLF-25H-A HAWKE 25 11.5 17.0 17.0 27.1

    E1CF-RTLF-32SH-A HAWKE 32S 15.0 19.0 25.0 33.3

    E1CF-RTLF-32H-A HAWKE 32 18.0 23.0 25.0 33.3

    E1CF-RTLF-40SH-A HAWKE 40S 20.0 25.0 33.0 42.9

    E1CF-RTLF-40H-A HAWKE 40 23.0 29.0 33.0 42.9

    E1CF-RTLF-50SH-A HAWKE 50S 29.0 35.0 39.5 52.6

    E1CF-RTLF-50H-A HAWKE 50 34.0 40.0 39.5 52.6

    Glands are supplied as gland only.

    Anixter Gland Gland Cable dimensions

    Part No. Manu Size accomodated

    Over lead sheath Overall

    Min Max Min Max

  • 8/13/2019 Glands_Accessories LSF.pdf

    28/44

    ACCESSORIES

    2:28

    12

    UniversalExplosion Proof Barrier Glands

    For plastic or rubber insulated cables with wire braid, single wire, steel tape

    or strip armour, having extruded or taped bedding.

    Solid setting compound is squeezed into the interstices of the cable whengland is installed.

    Compound forms a barrier around individual cores so preventing escape of

    gases through centre of cable.

    Sealing arrangements are rated to IP66.

    Weatherproof and waterproof.

    For use with explosion proof equipment in Zone 1 hazardous areas.

    Complies with group II C qualifies the gland for use under the most onerous

    conditions.

    BASEEFA Approved.

    Approved to EN50014 and EN50018 (BS5501 Part 1 and Part 5)

    CABLE & GLAND DETAILS

    E1BS-UNI-20S-A HAWKE 20S - 10.0 9.5 16.0

    E1BS-UNI-20-A HAWKE 20 - 12.5 12.5 20.5

    E1BS-UNI-25-A HAWKE 25 - 18.4 16.9 26.0

    E1BS-UNI-32-A HAWKE 32 - 24.7 22.0 33.0

    E1BS-UNI-40H-A HAWKE 40 - 29.7 28.0 41.0

    E1BS-UNI-50H-A HAWKE 50 - 41.7 36.0 52.6

    Glands are supplied body only with 2 compound mixes.

    Anixter Gland Gland Cable dimensions

    Part No. Manu Size accomodated

    Under armour OverallMin Max Min Max

  • 8/13/2019 Glands_Accessories LSF.pdf

    29/44

    12

    ACCESSORIES

    12:29

    Brass Earth Tags

    Ensure earth continuity is maintained between the gland and the equipment.

    Aluminium earth tags should be used with aluminium glands.

    NOTE:

    Earth bond connections are specified in IEE wiring regulations and relevant

    Codes of Practice.

    TAG DETAILS

    Anixter ISO Entry Bolt HolePart No. Thread Diameter Diameter

    (mm) (mm)

    E1BG-20R 20 7.2

    E1BG-25R 25 10.3E1BG-32R 32 11.9

    E1BG-40R 40 13.5

    E1BG-50R 50 13.5

    E1BG-63R 63 13.5

    E1BG-75R 75 13.5

  • 8/13/2019 Glands_Accessories LSF.pdf

    30/44

    ACCESSORIES

    2:30

    12

    High Performance Sealing Washers

    Improve the IP rating between the gland

    and the equipment i.e. IP66.

    Fibre or Nylon available according tocustomer preference.

    SEALINGWASHER

    EQUIPMENTINTERFACE

    WASHER DETAILS

    Anixter ISO Entry Washer

    Part No. Thread Diameter Material

    (mm)

    E1DS-20R 20 NYLON

    E1DS-25R 25 NYLONE1DS-32R 32 NYLON

    E1DS-40R 40 NYLON

    E1DS-50R 50 NYLON

    E1DS-63R 63 NYLON

    E1DS-75R 75 NYLON

    E1DT-20 20 FIBRE

    E1DT-25 25 FIBRE

    E1DT-32 32 FIBRE

    E1DT-40 40 FIIBRE

    E1DT-50 50 FIBRE

    E1DT-63 63 FIBRE

    E1DT-75 75 FIBRE

    Galvanised Serrated Washers

    Used to prevent loosening oflocknut

    Mild steel zinc plated

    WASHER DETAILS

    Anixter ISO EntryPart No. Thread Diameter

    (mm)

    E1DY-20 20

    E1DY-25 25

    E1DY-32 32

    E1DY-40 40

    E1DY-50 50

  • 8/13/2019 Glands_Accessories LSF.pdf

    31/44

    12

    ACCESSORIES

    12:31

    Steel, Brass & Aluminium Locknuts

    Used to secure gland body to the equipment where entry hole is not tapped.

    Brass backnuts recommended for most corrosive environments.

    Aluminium backnuts should be used with aluminium glands.

    Steel backnuts are primarily for dry, low humidity environments.

    Steel and aluminium locknuts are available when required.

    LOCKNUT DETAILS

    Anixter ISO Entry Locknut

    Part No. Thread Diameter Material

    (mm)

    E1BK-20R 20 BRASS

    E1BK-25R 25 BRASS

    E1BK-32R 32 BRASS

    E1BK-40R 40 BRASS

    E1BK-50R 50 BRASS

    E1BK-63R 63 BRASS

    E1BK-75R 75 BRASS

  • 8/13/2019 Glands_Accessories LSF.pdf

    32/44

    ACCESSORIES

    2:32

    12

    PC P/PVC Shrouds

    For fitting over cable glands where additional protection against onerous

    weather conditions and corrosion is required.

    Provide an effective seal onto both gland and cable oversheath.

    PCP shrouds are particularly recommended for outdoor and the most hostile

    conditions and are not affected by ultravoilet rays contained in sunlight.

    PVC shrouds for use in dry indoor and most outdoor situations.

    SHROUD DETAILS

    Anixter To Suit Shroud

    Part No. Gland Size Material

    (mm)

    E1BF-20SH 20S PCP

    E1BF-20H 20 PCP

    E1BF-25H 25 PCP

    E1BF-32H 32 PCP

    E1BF-40H 40 PCP

    E1BF-50H 50 PCPE1BF-63H 63 PCP

    E1BF-75H 75 PCP

    E1DR-20SH 20S PVC

    E1DR-20H 20 PVC

    E1DR-25H 25 PVC

    E1DR-32H 32 PVC

    E1DR-40H 40 PVC

    E1DR-50H 50 PVC

    E1DR-63H 63 PVCE1DR-75H 75 PVC

  • 8/13/2019 Glands_Accessories LSF.pdf

    33/44

    12

    ACCESSORIES

    12:33

    Lugs for Medium Voltage Cables

    These compression lugs are based on the standard tin plated connectors

    manufactured by Pirelli, and are suitable for indoor and outdoor applications.Connections are manufactured from thickwall copper tubing and incorporate

    single hole palm. The base of the compression barrel is effectively waterblocked

    via incorporation of a waterproof seal during manufacture.

    LUG DETAILS

    Anixter To Suit Stud

    Part No. Conductor Size Size(mm2) (mm)

    E1AE-BTHW-70-C12 70 12

    E1AE-BTHW-95-C16 95 16

    E1AE-BTHW-120-C16 120 16

    E1AE-BTHW-150-C16 150 16

    E1AE-BTHW-185-C16 185 16

    E1AE-BTHW-240-C20 240 20

  • 8/13/2019 Glands_Accessories LSF.pdf

    34/44

    ACCESSORIES

    2:34

    12

    Lugs

    The use of compression lugs for securing conductors to terminals has long been

    recognised as offering the optimum combination of electrical integrity, reliability and

    speedy installation. Single hole, two hole and four hole palm lugs available.

    The compression system ensures a high level of termination when used in association

    with tooling supplied by the same manufacturer ensuring that the completed installation

    complies with the standards laid down in BS4579 Part 1 (Compression joints in copper

    conductors). Anixter stocks uninsulated compression lugs, manufactured by Pirelli

    Components, produced from high conductivity electrolytic copper having a tin plated

    finish for operating temperatures up to 1500C and also to prevent corrosion.

  • 8/13/2019 Glands_Accessories LSF.pdf

    35/44

    12

    ACCESSORIES

    12:35

    Anixter To Suit Stud

    Part No. Conductor Size Size

    (mm2) (mm)

    Flex Str.

    E1AE-BT-150-C12 120 150 12E1AE-BT-150-C16 16

    E1AE-BT-185-C10 10

    E1AE-BT-185-C12 150 185 12

    E1AE-BT-185-C16 16

    E1AE-BT-185-C20 20

    E1AE-BT-240-C12 12

    E1AE-BT-240-C16 185 240 16

    E1AE-BT-240-C20 20

    E1AE-BT-300-C12 240 300 12

    E1AE-BT-300-C16 16E1AE-BT-300-C20 20

    E1AE-BT-400-C16 300 400 16

    E1AE-BT-500-C20 400 500 20

    E1AE-BT-630-C20 500 630 20

    Two Hole Palm

    E1AE-BT-150-C12B2 120 150 12

    E1AE-BT-185-C12B2 150 185 12

    E1AE-BT-240-C12B2 185 240 12

    E1AE-BT-300-C12B2 240 300 12

    E1AE-BT-400-C12B2 300 400 12

    E1AE-BT-500-C12B2 400 500 12

    Four Hole Palm

    E1AE-BT-300-C8B4 240 300 8

    E1AE-BT-400-C8B4 300 400 8

    E1AE-BT-500-C8B4 400 500 8

    E1AE-BT-630-C8B4 500 630 8

    Anixter To Suit Stud

    Part No. Conductor Size Size

    (mm2) (mm)

    Flex Str.

    Single Hole Palm

    E1AE-BT-6-C5 4.0 5E1AE-BT-6-C6 to 6

    E1AE-BT-6-C8 6.0 8

    E1AE-BT-6-C10 10

    E1AE-BT-10-C5 10 5

    E1AE-BT-10-C6 6

    E1AE-BT-10-C8 8

    E1AE-BT-10-C10 10

    E1AE-BT-10-C12 12

    E1AE-BT-16-C5 10 16 5

    E1AE-BT-16-C6 6E1AE-BT-16-C8 8

    E1AE-BT-16-C10 10

    E1AE-BT-16-C12 12

    E1AE-BT-25-C6 16 25 6

    E1AE-BT-25-C8 8

    E1AE-BT-25-C10 10

    E1AE-BT-25-C12 12

    E1AE-BT-35-C6 25 35 6

    E1AE-BT-35-C8 8

    E1AE-BT-35-C10 10

    E1AE-BT-35-C12 12

    E1AE-BT-50-C6 35 50 6

    E1AE-BT-50-C8 8

    E1AE-BT-50-C10 10

    E1AE-BT-50-C12 12

    E1AE-BT-70-C8 50 70 8

    E1AE-BT-70-C10 10

    E1AE-BT-70-C12 12

    E1AE-BT-70-C16 16E1AE-BT-95-C10 70 95 10

    E1AE-BT-95-C12 12

    E1AE-BT-95-C16 16

    E1AE-BT-120-C10 10

    E1AE-BT-120-C12 95 120 12

    E1AE-BT-120-C16 16

    E1AE-BT-120-C20 20

    E1AE-BT-150-C10 10

  • 8/13/2019 Glands_Accessories LSF.pdf

    36/44

    ACCESSORIES

    2:36

    12

    Telcleats - Black Polythene & Grey LSF

    Range taking and self adjusting

    Just 8 sizes cover from 10mm to

    51mm diameter Ultraviolet and weather resistant

    Low cost

    Versatile

    One piece

    Single fixing

    LSF cleats are low smoke and fume

    emission and zero halogen

    Coloured grey to distinguish from black coloured Telcleat

    Meets requirements of BS6853 and LUL specification E1042 with regards to

    temperature index, smoke emission and toxicity ratings.

    CLEAT DETAILS

    Anixter Cable Dimensions

    Part No. Accomodated

    Min (mm) Max (mm)

    Black PolytheneE1D-A01 10 15

    E1D-A02 12 17

    E1D-A03 15 20

    E1D-A04 18 24

    E1D-A05 22 29

    E1D-A06 26 34

    E1D-A07 32 42

    E1D-A08 39 51

    Grey LSF

    E1D-A01LSF 10 15

    E1D-A02LSF 12 17

    E1D-A03LSF 15 20

    E1D-A04LSF 18 24

    E1D-A05LSF 22 29

    E1D-A06LSF 26 34

    E1D-A07LSF 32 42

    E1D-A08LSF 39 51

  • 8/13/2019 Glands_Accessories LSF.pdf

    37/44

    Anixter To Suit Conductor Size Shell Internal To Suit

    Cable

    DiameterPart No. Length Diameter

    (mm) (mm) (mm)

    SJK1

    Two Core

    (mm2)

    1.5 to 4.0

    6.0 to 25.0

    35, 50

    70, 95

    120, 150, 185

    240, 300

    400

    Three Core

    (mm2)

    1.5 to 4.0

    6.0, 10.0

    16, 25

    35, 50

    70, 95, 120

    150, 185, 240

    300, 400

    Four Core

    (mm2)

    1.5, 2.5

    4.0 to 10.0

    16

    25, 35, 50

    70, 95, 120

    150, 185

    240, 300, 400

    190

    260

    360

    400

    530

    705

    900

    36

    47

    55

    70

    100

    125

    150

    14.0 - 22.0

    14.0 - 30.0

    20.0 - 37.0

    25.0 - 42.0

    33.0 - 55.0

    45.0 - 74.0

    50.0 - 90.0

    SJK2

    SJK3

    SJK4

    SJK5

    SJK6

    SJK7

    SJK3 and SJK4 kits.

    12

    ACCESSORIES

    12:37

    Straight Cable JointsPolyurethane Resin Encapsulation Suitable for 2, 3, 4 core

    XLPE/PVC SWA Copper Conductor Cables

    Joints comply with BS6910 Part 1.

    Transparent shell to allow inspection of

    joint before application of resin. Joints

    utilise Two-Part Polyurethane resin to

    encapsulate, insulate and protect the

    jointed conductors.

    Resin and hardener are separated by a

    centre peelable seal in Twin Pack Laminated Sachet (completely enclosed mixing).

    Unmixed ingredients have shelf life of 24 months based on average UK temperature.

    Compression connectors for relevant conductor size are SJK1, SJK2,

    Armour bonds included in all kits.

    Simple to use - no special tools required.

    Supplied in resealable box.

  • 8/13/2019 Glands_Accessories LSF.pdf

    38/44

    ACCESSORIES

    2:38

    12

    Claw & Two Bolt Cleats -Aluminium Alloy

    Claw cleats for cable dimensions up to 51mm diameter.

    Two bolt cleats for cable dimensions 51mm and above.

    CLEAT DETAILS

    Anixter Cable Dimensions

    Part No. Accomodated

    Min (mm) Max (mm)

    Claw Cleats

    E1B-BA01 10 13

    E1B-BA02 13 16

    E1B-BA03 16 19

    E1B-BA04 19 22

    E1B-BA05 22 25

    E1B-BA06 25 32

    E1B-BA07 32 38

    E1B-BA08 38 44

    E1B-BA09 44 51

    Two Bolt Cleats

    E1B-BA10 51 57

    E1B-BA11 57 64

    E1B-BA12 64 70

    E1B-BA13 70 76

    E1B-BA14 76 83

    E1B-BA15 83 89

  • 8/13/2019 Glands_Accessories LSF.pdf

    39/44

    12

    ACCESSORIES

    12:39

    Cable Tiles & Warning Tapes

    Plastic warning cable tiles and warning tapes for buried cables and have the

    following warning legend:

    CAUTION CAUTION

    ELECTRIC CABLE BELOW

    CABLE TILE DETAILS

    Anixter Tile

    Part No. Dimensions (mm)

    500315 1000 x 152 x 12

    500314 1000 x 244 x 12

    500313 1000 x 300 x 12

    WARNING TAPE DETAILS

    Anixter Tile

    Part No. Dimensions (mm)

    515319 150mm wide x 100 microns thick

    (365m roll)

  • 8/13/2019 Glands_Accessories LSF.pdf

    40/44

    ACCESSORIES

    2:40

    12

    11kV Indoor Termination Kitsfor 3 Core PILC/PICAS Cables

    Scotchcast termination kits for use on

    11kV indoor terminations for 3 core paperinsulated, belted, lead sheath and

    corrugated aluminium sheath cables.

    Inorganic cold shrink silicone insulator.

    Cold pour Scotchcastresin to insulate

    and fill crotch area.

    Light weight assembly

    No special tools necessary

    Cold shrink technology, no heating required

    11kV rated voltage

    95kV nominal impluse withstand voltage

    700C maximum operating temperature (accelerated ageing test to VDE0278)

    1600C overload temperature (accelerated ageing test to VDE0278)

    Track resistance on silicone insulator as per ASTM [email protected] - 30 hours @3.5kV - 10 hours

    Contents list of kit:

    - EPDM rubber pre-stretched tubes

    - Silicone Glove

    - Silicone pre-stretched tubes

    - Polyetherurethane resin

    - Self amalgamating tapes:

    - Stress control tape- EPR rubber tape

    - Silicone tape

    - Core separator

    - Cable cleaner

    - Gloves

    - Drawing instructions

    Scotchcast is a registered Trade Mark of 3M.

    Anixter 3M Suitable Approx.

    Part No. Part No. for Conductor Kit

    Sizes Weight

    (mm2) (kg)

    E1DW-MT16 MT16 70-400 3.5

  • 8/13/2019 Glands_Accessories LSF.pdf

    41/44

    12

    ACCESSORIES

    12:41

    11kV Indoor Termination Kitsfor 3 Core Polymeric Cables

    Scotchcast termination kits for use on

    11kV indoor terminations for 3 cores XLPEor EPR insulated cables.

    Inorganic cold shrink silicone insulator.

    Light weight assembly

    No special tools necessary

    Cold shrink technology, no heating required

    11kV rated voltage

    95kV nominal impluse withstand voltage

    950C maximum operating temperature (accelerated ageing test to VDE0278)

    2500C overload temperature (accelerated ageing test to VDE0278)

    Track resistance on EPDM insulator as per ASTM 2303-68

    @2.5kV - 5 hours

    Contents list of kit:

    - EPDM rubber pre-stretched tubes

    - EPDM Rubber Glove

    - Self amalgamating tapes:

    - Semi-conducting tape

    - EPR rubber tape

    - Copper earth braid with integral lug

    - Constant force springs

    - Cable cleaner

    - Drawing instructions

    Scotchcast is a registered Trade Mark of 3M.

    Anixter 3M Suitable Approx.

    Part No. Part No. for Conductor Kit

    Sizes Weight

    (mm2) (kg)

    E1DW-MT46 MT46 35-70 3.0

    E1DW-MT47 MT47 95-185 2.5

    E1DW-MT48 MT48 240-400 3.0

  • 8/13/2019 Glands_Accessories LSF.pdf

    42/44

    ACCESSORIES

    2:42

    12

    3M Inline (Straight) Barrier Boot - MB63

    Installation of cable termination to bushing connections in switchgear and

    cable end boxes for straight (in-line) applications.

    Suitable for paper or polymeric cables

    No special tools necessary

    Quick and simple installation

    Cold shrink technology, no heating required

    11kV rated voltage (75kV BIL)

    Track resistant EPDM material

    For use on conductor sizes up to 630mm2

    Dimensions of cable box and bushing dimensions should meet the

    following criteria:

    Dimension Description Min Max

    (mm) (mm)

    A Phase - Earth clearance 18 76*

    B Phase - Phase clearance 36 127*

    C Bushing diameter 50mm up bushing 24 66

    D Bushing length 50 127*

    * For dimensions greater than these no boots are required.

    NB: 3 barrier boots are provided in each kit.

    Anixter 3M Suitable Approx.

    Part No. Part No. for Conductor Kit

    Sizes Weight

    (mm2) (kg)

    E1DW-MB63 MB63 Up to 630 0.8

    "A""B"

    "C"

    "D"

  • 8/13/2019 Glands_Accessories LSF.pdf

    43/44

    12

    ACCESSORIES

    12:43

    3M Pre-Moulded Right Angle Barrier Boot

    Installation of cable termination to bushing connections in

    switchgear and cable end boxes for right angle

    applications. Consists of one large tubular opening to

    fit a porcelain bushing, and a smaller stepped tubular

    opening to cover the cable lugs and fit over the cable

    terminations. A sealing cover is also included which

    allows the connection bolts to be accessed after barrier

    boot has been slipped onto the bushing and

    termination. The sealing cover guarantees an

    electrical sealing of the live parts and is re-enterable.

    Suitable for paper or polymeric cables

    No special tools necessary

    Quick and simple installation

    Re-enterable design

    No heating required

    11kV rated voltage (95kV BIL)

    Track resistant EPDM material

    For use in conductor sizes 35 - 300mm2

    Dimensions of cable box and bushing dimensions should meet the following criteria:

    Dimension Description Min Max

    (mm) (mm)

    A Phase - Earth clearance 30 76*

    B Phase - Phase clearance 70 127*

    C Bushing length 110 127*

    D Bushing diameter at length C(circular bushing) 45** 50

    E Bushing circumference at length C 140** 157

    (eliptical bushing)

    * For dimensions greater than these no boots are required.

    ** Bushings below these minumum dimensions can be catered for using 3Ms MB64/S

    supplementary kit(s) in conjunction with the standard MB 64 kit.

    NB: 3 barrier boots are provided in each kit.

    "B" "A"

    Anixter 3M Suitable Approx.

    Part No. Part No. for Conductor Kit

    Sizes Weight

    (mm2) (kg)

    E1DW-MB64 MB64 35 - 300 1.05

    "C"X

    X

    "D"

    Section XX

    Circular Bushing

    Elliptical Bushing

    "E"

  • 8/13/2019 Glands_Accessories LSF.pdf

    44/44