    Medium Voltage Distribution

    WIup to 52 kV

    Gas-Insulated Switchgear with Vacuum Circuit-Breaker 1, 2 or 3-phase

    System configuration

  • 7/30/2019 GIS Sieens Wi en 100709

    2/52

    Conditions of Delivery

    The General Conditions of Delivery as amended shall apply.

    Illustrations

    The illustrations are not binding

  • 7/30/2019 GIS Sieens Wi en 100709

    3/523WI EN

    WI Contents

    Overview ..............................................................................................................4

    Features .........................................................................................................4

    Product description ............................................................................................ 5

    Technical description ......................................................................................5

    Components of the switching unit ..................................................................6

    Modular design ............................................................................................... 7

    Single busbar WIA up to 36 kV .....................................................................7

    Double busbar WIB up to 36 kV ...................................................................7

    Single busbar WIA 52 kV, 250 kV BIL ..........................................................8

    Double busbar WIB 52 kV, 250 kV BILL ....................................................... 8

    Operator interfaces ........................................................................................9

    Switchgear panels ........................................................................................ 10

    Current/voltage transformers ....................................................................... 11

    Busbar modules ...........................................................................................13

    Modules ........................................................................................................15

    Interlocks ......................................................................................................16

    Gas compartment monitoring WIA, WIB ...................................................... 17

    Gas-filled compartments of the WIA/ WIB ................................................... 18

    Standards, regulations, provisions and standards.......................................19

    Type designation ..........................................................................................20

    Applied norms .............................................................................................. 21

    Selection tables ................................................................................................22

    WIA/WIB 12 kV ............................................................................................22 WIA/WIB 17 kV ............................................................................................24

    WIA/WIB 24 kV ............................................................................................26

    WIA/WIB 36 kV ............................................................................................28

    WIA/WIB 38 kV ............................................................................................30

    WIA/WIB 40.5 up to 52 kV ........................................................................... 32

    WIA/WIB 1 and 2-pole, for stationary railway traction power supply 50/60 hz......34

    Range of products ............................................................................................ 36

    Single busbar panels WIA ............................................................................ 36

    Double busar panels WIB ............................................................................37

    Disconnector panel ......................................................................................38

    Bus section coupler / riser panel ..................................................................38

    Bus section coupler, Bus coupler, metering panel ....................................... 39

    Cable connections ............................................................................................ 40

    Ecological considerations ...............................................................................43

    Design data .......................................................................................................44

    Space requirements - dimensions and weights ...........................................44

    Busbar connection with fully insulated conductor bars ................................48

    Shipping instructions ....................................................................................... 50

    Delievery, packaging .................................................................................... 50

  • 7/30/2019 GIS Sieens Wi en 100709

    4/524 WI EN

    WI

    FeaturesThe gas-insulated and metal-enclosed switchgear WI has been designed

    for operation in power plants, transformer substations and industrialnetworks.

    The WI switchgear with vacuum circuit-breaker features maximum

    availability, optimum operator safety and clear design using SF6gas as

    insulating medium. The switchgear units are insensitive to environmental

    inuences,suchashumidity,dustandaggressivegases,andoffer

    complete operator safety. Their clear design facilitates operation.

    Essential features

    Parts under medium voltage in SF6atmosphere

    insensitive to air humidity, air pollution and foreign matter

    High degree of operator safety

    complete metal enclosure for all system components under mediumvoltage

    Compact and clear design

    No mechanically moved parts in the busbar section

    No problems with SF6decomposition products

    currents are switched in the vacuum interrupter chamber

    Inert insulating gas SF6protectstheswitchgearagainstre

    Three-pole enclosure of the functional compartments negligible sheath currents

    small number of static and dynamic seals

    few gas compartments, pressure relief devices and gas monitoring

    devices

    easy access

    moderate pressure increase in case of internal arcs

    straightforward kinematics between drive and circuit-breaker or

    three-position switch

    Steel used as enclosure material

    high pressure proofness

    good screening effect against X rays

    Optimum security of operation

    complete interlocking system

    separate actuators for isolation and earthing

    automatic circuit-breaker ON or OFF operation in case of earthing at

    the outgoing feeder

    High capacity current and voltage transformer

    Delivery of prefabricated switchgear panels to the construction site Fully shrouded terminals

    pluggable, fully insulated cable end boxes

    Switchgear extension possible on both sides

    from single to double busbar system.

    Overview

    Single busbar WIA up to 36 kV

  • 7/30/2019 GIS Sieens Wi en 100709

    5/525WI EN

    WI Product description

    Technical description

    WIpanelsaresuitableforconguringsingleordoublebusbarswitchgearin

    conjunction with indoor installation.

    WI switchgear units are completely metal-enclosed. The busbar

    compartmentwhichaccommodatesxedpartsonlyissegregatedgas-tight

    fromtheange-mountedswitchingunit.Theswitchingunitcomprisesthe

    three-position switch with isolating and earthing functions and the vacuum

    circuitbreaker; in case of double busbar systems, there are two three-

    position switches with isolating and earthing functions and the vacuumcircuit-breaker.

    The busbar compartment and the switching unit feature three-pole

    enclosure. Single-pole enclosure is provided in the area of the toroidalcore

    current transformers which are located in an easily accessible position

    outside of the SF6atmosphere. The compact design results in a very clear

    switchgear arrangement with low space requirement; it has the advantagethat a switching unit can be mounted or removed very quickly without the

    busbar requiring isolation from the power supply.

    The panels are equipped with a low-voltage cabinet for the required

    measuring and protection relays or the terminal strips. The high

    performance of the instrument transformers installed means that not onlyelectronic but also conventional protection relays can be deployed.

    Thanks to its design, this panel series permits straightforward extension of

    an existing switchgear on both sides, and extension from single to double

    busbar models.

    Gas-insulated double busbar switchgear WIBRated voltage up to 36 kV; rated peak withstand

    current up to 100 kA; rated current up to 2500 A

  • 7/30/2019 GIS Sieens Wi en 100709

    6/526 WI EN

    WI Product description (contd.)

    Components of the switching unit

    The circuit-breaker in question is a vacuum circuit-breaker. The switching

    unit has been equipped, for its isolating and earthing functions, with athree-position switch featuring the positions:

    Earthing

    The metal-enclosed WI series switchgear is equipped with a separate

    earthing line running along the length of the switchgear.

    Wiring

    Wiringiseffectedwithexiblecables(HO7V-K)inthetechnicallyrequiredcross-sections.

    Corrosion protection

    If desired, the indoor panels WIA and WIB can be provided optionally with

    enhanced corrosion protection. To ensure optimum switchgear protection,

    the environmental installation conditions, such as wind-borne sand,

    aggressivedust(tobedenedassaltdust,cokedust,cementdustetc.),

    vermin(termites),increasedhumiditylevels,aggressiveatmosphere(typeofchemicalsandtheirconcentrationtobedened)mustbespecied.

    Installation locations

    The switchgear has been designed for installation in closed electrical

    operating facilities.

    Connection of cables and bars

    The cables are connected by means of metal-enclosed connectors.

    Switchgear units equipped with multiple connection tanks enable

    connectionofuptove300mm2 cables or two 1250 mm2 cables perphase, depending on the insulation rating.

    Alternatively, fully insulated busbar systems or SF6-insulated conductor

    bars can be used.

    Low voltage cabinet

    The secondary devices for protection relay, control, measurement, billing

    metering and other systems are installed in the low-voltage cabinet. Thelow-voltage cabinet is separated systematically from the primary part, is

    shock-proof and arc-resistant. It is an independent, closed low-voltage

    compartment with mechanical and electrical interfaces to the vertical

    section(screw-fastenedplug-and-socketconnector).

    The clear separation between the rack and the low-voltage cabinet is a

    particularadvantageforthecompanyoperatingtheswitchgear.Retrotting

    spare panels and conversion or replacement of complete low-voltage

    cabinets(e.g.duetoprocesschanges)atalaterdateisalso

    straightforward. The panel remains completely enclosed even if thelow-voltage cabinet is not attached.

    Optional inspection ports can be integrated in the torsion-resistant door ofthe low-voltage cabinet, the door also being able to accommodate

    measuring instruments, control elements and protection relays.

    Disconnector ON(CLOSE)

    Disconnector earthing switch OFF(TRIP)

    Earthing switch ON(CLOSE)

  • 7/30/2019 GIS Sieens Wi en 100709

    7/527WI EN

    WI Product description (contd.)

    Modular design

    Single busbar WIA up to 36 kVTank with vacuum circuit-breaker and disconnector / earthing switch

    Drive with control panel and pressure gauge for gas monitoring

    Tank with busbar

    Supporting structure with cable connection area

    Low voltage cabinet

    Double busbar WIB up to 36 kV

    Tank with vacuum circuit-breaker and disconnector / earthing switch

    Drive with control panel and pressure gauge for gas monitoring

    Tank with busbar 1

    Tank with busbar 2

    Supporting structure with cable connection area

    Low voltage cabinet

    A

    B

    C

    D

    E

    A

    B

    C2

    C1

    D

    E

    A

    B

    D

    E

    C1

    C2

    A

    B

    E

    C

    D

  • 7/30/2019 GIS Sieens Wi en 100709

    8/528 WI EN

    WI Product description (contd.)

    Single busbar WIA 52 kV, 250 kV BIL

    Tank with vacuum circuit-breaker and disconnector / earthing switch

    Drive with control panel and pressure gauge for gas monitoring

    Tank with busbar

    Supporting structure with cable connection area

    Low voltage cabinet

    Double busbar WIB 52 kV, 250 kV BILL

    Tank with vacuum circuit-breaker and disconnector / earthing switch

    Drive with control panel and pressure gauge for gas monitoring

    Tank with busbar 1

    Tank with busbar 2

    Supporting structure with cable connection area

    Low voltage cabinet

    A

    B

    C

    D

    E

    A

    B

    C2

    C1

    D

    E

    A

    B

    E

    C

    D

    A

    B

    D

    E

    C1

    C2

  • 7/30/2019 GIS Sieens Wi en 100709

    9/529WI EN

    WI Product description (contd.)

    i , l I

    1

    21

    2

    3

    18

    4

    5

    16

    17

    6

    SS2

    7

    8

    9

    10

    11

    12

    SS1

    13

    14

    15

    Operator interface, double busbar WIB

    i , i l I

    1

    2

    3

    18

    4

    5

    16

    17

    9

    10

    11

    12

    SS1

    13

    14

    Operator interface, single busbar WIA

    Operator interfaces for WIA (single busbar)

    and WIB (double busbar)1 Button circuit-breaker ON

    2 Button circuit-breaker OFF

    3 Opening for charging the energy- storing device by means of a slide

    4 PositionindicatorEnergy-storingdevice(charged/released)5 Circuit-breaker position indicator

    6 Switchpositionindicator,disconnector(SS2)

    7 Openingforoperationofthedisconnector(SS2)

    8 Interrogating lever, disconnector

    9 Earthing switch position indicator

    10 Opening for operation of the earthing switch11 Interrogating lever earthing switch

    12 Switchpositionindicator,disconnector(SS1)

    13 Openingforoperationofthedisconnector(SS1)

    14 Interrogating lever, disconnector15 Mechanical lock-out with cylinder lock

    16 Rating plate17 Insulating gas monitoring device

    18 Operations counter

    SS1:busbar1(correspondstothelowerbusbartank)

    SS2:busbar2(correspondstotheupperbusbartank)

  • 7/30/2019 GIS Sieens Wi en 100709

    10/5210 WI EN

    WI Product description (contd.)

    6

    8

    7

    5

    4

    2

    1

    3

    8

    7

    9 10

    10

    6

    5

    4

    2

    1

    3

    8

    1

    3

    2

    7

    6

    5

    4

    10

    10

    9

    8

    7

    6

    5

    4

    1

    2

    3

    Switchgear panels

    Single busbarSwitchgear panel WIA up to 36 kV

    Double busbar

    Switchgear panel WIB up to 36 kV

    1 Drive mechanism

    2 Vacuum circuit-breaker

    3 Low voltage cabinet

    4 Cable end boxes

    5 Current transformers

    6 Busbar

    7 Disconnector /earthing switch8 Pressure relief device

    1 Drive mechanism

    2 Vacuum circuit-breaker

    3 Low voltage cabinet

    4 Cable end boxes

    5 Current transformers

    6 Busbar I

    7 Disconnector /earthing switch SSI8 Busbar II

    9 Disconnector /earthing switch SSII

    10 Pressure relief device

    Switchgear panel WIA up to 52 kV Switchgear panel WIB up to 52 kV

    1 Drive mechanism

    2 Vacuum circuit-breaker

    3 Low voltage cabinet4 Cable end boxes

    5 Current transformers

    6 Busbar

    7 Disconnector /earthing switch

    8 Pressure relief device

    1 Drive mechanism

    2 Vacuum circuit-breaker

    3 Low voltage cabinet

    4 Cable end boxes

    5 Current transformers

    6 Busbar I

    7 Disconnector /earthing switch SSI

    8 Busbar II

    9 Disconnector /earthing switch SSII

    10 Pressure relief device

  • 7/30/2019 GIS Sieens Wi en 100709

    11/5211WI EN

    WI Product description (contd.)

    Current/voltage transformers

    Current transformersThe current transformers are designed as toroidal-core transformers and

    are put onto the cable outgoing feeder areas with single-pole enclosure.

    The current transformers in line with the busbar consist of identical units.

    There, they are slipped onto the busbar areas which also feature singlepole

    enclosure. The capacity of the current transformers is designed in such a

    way that supply of conventional protective devices is also possible.

    Upto3transformers(3cores)canbeaccommodatedperphaseand

    outgoing feeder. The transformers can also be exchanged subsequently.

    Threecurrenttransformers(3cores)perphasecanalsobeinstalledinline

    with the busbar, in order to measure its currents.

    A special current transformer arrangement is the bus coupler panel withinone panel width. In the double busbar top attachment tank, one core of

    max.80mmheightwithanIDof135mmandanODof195mmcanbe

    installed for each phase. The low voltage is led out via a max. 7-pole line

    which is SF6proof.

    Dimensions

    Outgoing feeder:

    Transformer ID 185 mm

    Transformer OD 275 mm

    Max. stacking height 160 mm

    In line with busbar:

    Minimum ID 185 mm

    Maximum OD 250 mm

    Maximum stacking height for all

    cores incl. intermediate layer225 mm

    Measurement Protection

    /dyn

    (kA) 100

    Ith(3sec) (kA) 40

    Class 0.5 M 5 10 P 40 10 P 10

    Corerating(VA) (VA) up to 15 up to 5 up to 30

    Primary rated current (A) 150 up to 2500

    Secondary rated current (A) 1 or 5

    Current transformer in line

    with the busbar

  • 7/30/2019 GIS Sieens Wi en 100709

    12/5212 WI EN

    WI Product description (contd.)

    on the busbar

    A separate metering panel with a set of inductive voltage transformers isprovided to this effect. Taking account of the high priority of the busbar, a

    disconnector enables isolation of the transformer section. Both

    disconnector and transformer are located in separate compartments.

    Thus, any damage which might occur in the vicinity of the transformer

    does not affect the isolating area or the busbar.

    Performance characteristic

    1

    2

    Ratings: up to 50 VA

    Class: 0.5

    1 Multi-tank

    2 Test cable connector

    Voltage transformer in outgoing feeder cable

    (connectionviamulti-tank)

    Voltage transformer on busbar

    Voltage transformer

    The conventional solution for the inductive voltage transformer is a

    separate single-phase metalenclosed module which can be connected viacable connectors almost anywhere in the busbar area and on the outgoing

    feeder cable, and thus arranged in practically any location as required.

    in the outgoing feeder areaAnother design comprises metal-enclosed inductive voltage transformers

    directlyangemountedtotheoutgoingfeederblock,withtheisolating/

    earthing device mounted upstream. An externally operated isolating

    feature prevents the voltage transformer from being endangered/ put at

    risk during DC tests on the cable.

  • 7/30/2019 GIS Sieens Wi en 100709

    13/5213WI EN

    WI Product description (contd.)

    Busbar modules Gas tank incl. installation parts

    Busbar Coverattachmentonmountingangewithorwithoutpressurerelief.

    Allvebusbarcompartmentsrequireonepressurereliefdevice.Ifitisnot

    possible to mount the device to the ends of the busbar tanks, e.g. if a tankfor voltage transformer connection or a busbar earthing switch is located

    on the busbar end, or if the switchgear consists of over 10 panels, every

    fthpanelisequippedwithapressurereliefdeviceonthemountingange

    Coverattachmentonthestopangeoftheleft-handandright-handend

    panel, with or without pressure relief, to connect metalenclosed voltage

    transformers with cable connection to the front.

    Gas lines incl. pressure gauges; preferably attached to the end panel.

    (Onlyonceforeachgascompartment.)

    Desiccantfor4busbartankseach,orforeachgascompartment.(Cannot

    bemountedonswitchgearpanelsequippedwithpressurereliefdevice.) Compensation element for busbar tanks. Required after 20 single busbarpanels, and after 10 double busbar panels.

    Disconnector for bus sectionalizer

    Earthing switch for bus sectionalizer to the left and right of the

    disconnector

  • 7/30/2019 GIS Sieens Wi en 100709

    14/5214 WI EN

    WI Product description (contd.)

    Accessories (for overall system)

    SF6gas for on-site assembly of the busbar sections

    Special paint Corrosion protection in case of extreme environmental conditions

    Panellabelingaccordingtospecication

    Operating elements, operating crank for vacuum circuit-breaker,

    disconnector, earthing switch; for the busbar sections movable

    segregating cover.

    Star handle spanner

    Hex. spanner

    Castors

    Transportcoverforthebusbartanks(canbereturned)

    Jack rings

    Integrated Voltage Detection System IVIS

    Earthing and short-circuit device, 3-phase incl. operating rod Cable dummy plug

    Cable test socket on cable connector for cable measurement

    Blanking caps for live cable connectors which have been withdrawn

    always required

    optional

    Auxiliary equipment for transport only

    Possible arrangement of the castors

    Castors to be used

    for movements in longitudinal direction

    for transverse movements

    1

    2

    3

    12

    3

  • 7/30/2019 GIS Sieens Wi en 100709

    15/5215WI EN

    WI Product description (contd.)

    ModulesThe modules and attachments shown on this page apply to

    outgoing feeder panels

    incoming feeder panels

    panels with circuit-breaker in case of coupler panels and bus

    sectionalizers.

    Switching device module Gas tank incl. pressure relief device, gas lines and pressure gauge

    Switching devices with three-position switch and vacuum circuit-breaker,

    desiccant

    Drive section module

    Drive casing with drive mechanisms incl. interlocks

    Attachment of drive casing on switching device module incl. connecting

    parts

    Attachments for the vacuum circuit-breaker Motor drive mechanism to charge the energy-storing device

    Auxiliary switch, 8, 12 or 16 contacts; 8 contact elements are required for

    thebasiccircuitry(material:silver[normal],gold,silver-palladium)

    Passingcontactforpulsecontacttimestretching(contactsnormalor

    gold-plated)

    Pushswitchactuatedbyenergystoringdevice.(Pushswitchesforbasiccircuitryincludedinbasicdesign)

    Pushswitch,actuatedbyON-OFFpushbutton.(Thebasicdesign

    includes1pushswitchforeach)

    Shunt closing release, 1 ea.

    Shunt opening release, 1 or 2 ea. with or without auxiliary spring energy

    store Secondary release, 1 or 2 ea., or in case of design without undervoltage

    release: 3 ea.

    Undervoltage release, with or without time delay

    Blocking coil on ON pushbutton. Always required on coupler switch in

    case of bus section coupler and bus coupler, consisting of 2 panels(switchgearpanel+busriserpanel)

    Blocking coil on OFF pushbutton. Always required on coupler switch in

    caseofbussectioncouplerandbuscoupler,consistingof1or2panel(s)

    (switchgearpanel+busriserpanel)

    Mechanicallock-outwithlock(forvacuumcircuit-breakerandthree-

    positionswitch) Counter

    Attachments for three-position switch Motor-drive mechanism. In case of single busbar: 1 motor-drive

    mechanism each for isolating and earthing movements. In case of doublebusbar: 1 motor-drive mechanism for the isolating movement of busbar 1,

    busbar2andearthingmovementofbusbars1+2.Thevacuum

    circuitbreaker s ON button features a mechanical lock-out.

    An auxiliary switch, 2-20 contact elements each, for disconnecting and

    earthingmovement.(Material:silver(normal),gold,silverpalladium)

    Interlocking solenoid. Single busbar: only in circuit-breaker panel ofcoupler and in bus riser panel of bus sectionalizer. Generally required in

    case of double busbar. If the interlocking solenoids are not installed in

    caseofremotecontrol(motor-drivemechanism)ofthethree-position

    switch, the local actuation is not locked. In this case, mechanical lock-

    outs(locks)arerequiredontheONbuttonofthevacuumircuit-breakerand on the threeposition switch.

    always required

    optional

  • 7/30/2019 GIS Sieens Wi en 100709

    16/5216 WI EN

    WI Product description (contd.)

    InterlocksActuation of the three-position switch and the continuous mechanical

    interlock between circuitbreaker and three-position switch are designed insuch a way that the operator can proceed as usual. This means separate,

    completely interlocked actuation for the switching procedures Establishing

    isolating distance and Earthing. For the earthing procedure, which is onlypossible with the three-position switch in isolated position, the circuit-breaker

    switched off and the circuit-breaker energy-storing device pre-charged, the

    circuitbreaker is connected positively after the contact blades have

    beeninserted into the earthing contacts, and protected against immediate

    mechanical or electrical switching OFF. Vice versa, on de-earthing, the

    circuit-breakerisrstswitchedoffpositivelybeforetheisolatingdistancetothe earthing contacts established. The interlocks ensure that each

    switching operation is always performed completely. Thus, once the

    switching operation has commenced, the motion cannot be reversed, if

    applicable, and the operating lever cannot be removed before it reaches its

    end position.

    The description only refers to the single busbar. In the case of double

    busbars, some of the internal interlocking functions of the panel, as well as

    all inter-panel interlocking functions are performed by electro-mechanical

    interlocks(blockingcoil).

    The following interlocking functions are provided:

    Disconnector does not switch ON while the circuit-breaker or the earthing

    switch are ON

    None of the disconnectors switches OFF while the circuit-breaker or the

    earthing switch are ON Circuit-breaker only switches ON with the disconnector in its end position

    No earthing with disconnector engaged

    No earthing with circuit-breaker ON No earthing without circuit-breaker being in ready-to-operate condition

    Automatic connection of circuitbreaker during earthingAutomatic disconnection of circuit- breaker during de-earthing

    The following has been ensured:

    The operating crank cannot be removed from the disconnector or

    earthing switch before it has reached its end positions completely

    The circuit-breaker cannot be actuated while a switching operation is

    being performed on the disconnector or earthing switch The circuit-breaker cannot be switched off with the three-position switch

    in earthing position

    All interlocks act partly mechanically and partly electrically

    An operating crank can only be inserted on the disconnector or earthing

    switch once the insertion opening has been released via a manualinterrogation system.

    All interlocks also effective when the three-position switch is

    motor-actuated.

  • 7/30/2019 GIS Sieens Wi en 100709

    17/5217WI EN

    WI Product description (contd.)

    Gas compartment monitoring

    Single busbar WIA with bus section coupler

    Gas compartment monitoring

    Double busbar WIB with bus coupler

    Gas connector socket (disposal valve)

    Pressure gauge

    Gas-tight electricalbushing

    Check valve

    1

    2

    1 Gas-filled busbar compartments

    2 Gas-filled circuit-br eaker compartments

    Gas connector socket (disposal valve)

    Pressure gauge

    Gas-tight electricalbushing

    Double check valve

    1

    2

    3

    1 Gas-filled busbar2 compartments

    2 Gas-filled busbar1 compartments

    3 Gas-filled circuit-br eaker compartments

  • 7/30/2019 GIS Sieens Wi en 100709

    18/5218 WI EN

    WI Product description (contd.)

    Gas-lled compartments of the WIA/B series panels

    WIA up to 40.5 kV,

    single busbar

    WIB up to 40.5 kV,

    double busbar

    WIA up to 52 kV,

    single busbar

    WIB up to 52 kV,

    double busbar

    WIA up to 36 kV,

    single busbar

    WIB up to 36 kV,

    double busbar

    Gas-lledcircuit-breaker compartment

    busbar 1 compartment

    busbar 2 compartment

  • 7/30/2019 GIS Sieens Wi en 100709

    19/5219WI EN

    WI

    WI series switchgear units are

    metal enclosed

    SF6 insulated prefabricated and type-tested

    tested for internal faults

    Ambient and operating conditionsWI switchgear units are to be operated under normal operating conditions

    accordingtothespecicationsEN60694ortheIECpublication60694

    (new:IEC62271-1).

    Operation under conditions other than these is only admissible upon

    consultation with and with the consent of the manufacturer.

    Degrees of protection against foreign

    objects and accidental contact

    Other ambient temperatures

    Therated(normal)currentsIN

    speciedintheselectiontablesrefertoa

    maximum ambient switchgear temperature of 40 C.In case of different maximum ambient temperatures T of the switchgear,

    between+25Cand+55C,theappropriatenormalcurrentINT

    can be

    determined from the following formula:

    1) Optional: minus 25 indoors2) Optional up to 55 C in case of reduction of normal currents

    3) Optional up to 40 C in case of reduction of normal currents4) Higher installation altitudes possible on request

    Main electric circuits IP 65

    Drives IP 2X, IP 5X1)

    Low-voltage cabinets and cable connectioncompartments(operatorssidewithcable

    compartmentcoverandsidepanels)

    IP 3X, IP 5X1)

    1) Optional

    105 - T

    65At 25 0C T < 40 0C INT = IN

    At 40 0C < T 55 0C INT = IN105 - T

    650.7

    Ambient conditions

    Temperature class "Minus 25 indoors 1)

    Min./max. ambient temperature C -51) / 40 2)

    Averagevalueover24hours(max.) C 353)

    Maximum installation altitude above sea

    level

    m 1000 4)

    Insulating gas

    Type Sulphurhexauoride(SF6)

    Design pressurepre

    at 20 C MPa 0.03 - 0.05

    StandardsRegulations, provisions and standards

  • 7/30/2019 GIS Sieens Wi en 100709

    20/5220 WI EN

    WI

    Type designationThe type designation of the type-tested, prefabricated panels contains information about their design, rated voltage, insulation

    level, panel width and panel height.

    Example:

    Prefabricated, type-tested WI

    series panel with single busbar, for indoor installation, version A

    Rated peak withstand current 100 kA

    Rated voltage 12 kV; insulation level acc. to list 2

    Panel width: 600 mm, panel height: 2100 mm

    Type designation: WI A 10 / 12-2 / 621

    Type designation

    Series

    Version

    WI . . .

    A

    / . . - .

    Explanation

    Fully insulated (SF6) switchgear panels, primarily for distribution

    substations, for very stringent requirements

    Single busbar, indoorsB

    8

    10

    Double busbar, indoors

    Rated peak withstand current 80

    100

    kA

    kA

    Rated voltage

    Dimension code WI A

    / 12-2

    / 17-2

    / 24-2

    / 36-2

    / 38-2

    / 40.5-2

    / 52-2

    up to 40.5 kV/ 621

    upper rated voltage 12

    17.5

    kV

    kV

    24

    36

    kV

    kV

    Panel width

    38

    40.5

    kV

    kV

    52

    600

    kV

    mm Panel height 2100 mm

    WI

    WI

    A

    B

    WI B

    up to 52

    up to 40.5

    up to 52

    kV

    kV

    / 626

    / 627

    kV/ 633

    600

    600

    mm

    mm

    600 mm

    2664

    2750

    3314

    mm

    mm

    mm

    StandardsRegulations, provisions and standards(contd.)

  • 7/30/2019 GIS Sieens Wi en 100709

    21/5221WI EN

    WI

    Designation IEC standard IEC classes EN standard

    Switchgear IEC 62271-200

    IEC 60694

    (new IEC 62271-1)

    Category for operating

    availability:

    LSC 2A

    Partition class

    (compartmentalization class): PM

    EN 62271-200

    EN 60694

    (new EN 62271-1)

    Behaviour in case of internal faults IEC 60298 EN 60298

    Circuit-breaker IEC 62271-100 M2, E1, C1 EN 62271-100

    Earthing switch IEC 62271-102 E2 EN 62271-102

    Three position disconnector IEC 62271-102 M1 EN 62271-102

    Current transformers IEC 60044-1 EN 60044-1Inductive voltage transformers IEC 60044-2 EN 60044-2

    Voltage detection systems IEC 61243-5

    Protection against accidental contact,foreign objects and water

    IEC 60529 EN 60529

    Erection HD 637 S1

    Operation of electrical equipment EN 50110

    Applied normsWI switchgear units meet the following standards and regulations:

    StandardsRegulations, provisions and standards(contd.)

  • 7/30/2019 GIS Sieens Wi en 100709

    22/5222 WI EN

    WI

    Type

    WIA

    Panelwidth

    8/12-2/621

    mm

    Rated insulation level

    Ratedvoltage

    Ratedlightningimpulse

    withstandvoltage

    kV kV

    Ratedpowerfrequency

    withstandvoltage

    Ratingsofisolatingdistance

    kV kV/kV

    Designpressure

    Pr

    at20

    0C

    5)

    Ratedfrequency

    bar

    0.8

    Hz

    Rated(normal)current3)

    Ratedpeakwithstandcurrent

    equaltoratedshort-circuit

    makingcurrent

    A

    630

    kA

    80

    Ratedshort-timecurrent

    1s 3s

    kA

    31.5

    kA

    20

    Ratedshort-circuitbreaking

    current

    PercentagevalueoftheDC

    component

    kA

    31.5

    %

    WIA

    WIA

    WIA

    WIA

    8/12-2/621

    8/12-2/621 600

    8/12-2/621

    8/12-2/621

    WIB

    WIB

    WIB

    WIB

    8/12-2/627

    8/12-2/627

    8/12-2/627

    8/12-2/627

    600

    12 75 28 85/32

    12 75 28 85/32

    0.8

    0.8 50/60

    1.3

    1.3

    1250

    1600

    80

    80

    2000

    25001)

    80

    80

    0.8

    0.8

    0.8

    1.3

    50/60

    630

    1250

    80

    80

    1600

    2000

    80

    80

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5 38

    31.5

    31.5

    31.5

    31.5

    20

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    38

    WIBWIA

    WIA

    WIA

    8/12-2/62710/12-2/621

    60010/12-2/621

    10/12-2/621

    WIA

    WIB

    WIB

    WIB

    10/12-2/621

    10/12-2/627

    60010/12-2/627

    10/12-2/627

    12 75 28 85/32

    12 75 28 85/32

    WIB 10/12-2/627

    1.30.8

    50/600.8

    1.3

    25002)

    125080100

    1600

    2000

    100

    100

    1.3

    0.8

    50/600.8

    1.3

    25001)

    1250

    100

    100

    1600

    2000

    100

    100

    31.540

    31.540

    40

    40

    40

    40

    31.540

    3840

    40

    40

    40

    40

    40

    40

    40

    40

    40

    40

    40

    3840

    40

    1.3 25002) 100 40 40 40

    Selection tables

    WIA/WIB 12 kV

    LS = Circuit-breaker

    TS = Three-position switch, disconnector I/O

    ES = Three-position switch, earthing switch I/O

    1) with cooling gas tank, panel height 2750 mm2) with motor-actuated fan3) possiblelimitsandcomponentstted,refertoprojectplanningdocumentsWIno.495424) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report5) minimumservicepressure0.3baratallingpressureof0.8bar;0.7baratallingpressureof1.3bar

  • 7/30/2019 GIS Sieens Wi en 100709

    23/5223WI EN

    WI Selection tables (contd.)

    Rated operating

    sequence

    O-3min-CO-3min-CO

    O-0.3s-CO-3min-CO

    CO-15s-CO

    O-0.3s-CO-15s-CO

    Cablebreakingcurrent

    A

    Smallindirectcurrents

    Ratedbreakingcurrent

    underout-of-phaseconditions

    A kA

    8

    Number of operating

    cycles withoutoverhaul

    mecha-

    nical

    electrical

    Operating times

    with release

    25 W

    LS,TS,E w

    ithrated(normal)current

    10000

    withratedshort-circuit

    breakingcurrent

    Openingtime

    4)

    ms

    160 W 160 W

    Command times

    with release

    25 W

    Openingtime

    4)

    Closingtime

    4)

    ms ms

    Arcduration(max.)

    Off

    ms ms

    160 W 160 W

    Off

    On

    On

    Off

    ms ms

    Chargingtimeformotordrive

    mechanism

    Operatingtimefordisconnector

    andearthingswitchwithmotordrive

    mechanism,160W

    s s

    25 10

    8

    25

    8

    8

    10

    1000

    1000 10000 100 45-65

    10000

    1000

    1000 10000 100 45-65

    33-50 40-70 12 50

    33-50 40-70 12 50

    20 20 12 18

    20 20 12 18

    25 10

    10

    10

    10

    25 10

    10

    10

    10

    10

    10

    10000

    100001000

    1000100 45-65

    10000

    100001000

    1000100 45-65

    33-50 40-70 12 50

    33-50 40-70 12 50

    20 20 12 18

    20 20 12 18

  • 7/30/2019 GIS Sieens Wi en 100709

    24/5224 WI EN

    WI

    Type

    WIA

    Panelwidth

    8/17-2/621

    mm

    Rated insulation level

    Ratedvoltage

    Ratedlightningimpulse

    withstandvoltage

    kV kV

    Ratedpowerfrequency

    withstandvoltage

    Ratingsofisolatingdistance

    kV kV/kV

    Designpressure

    Prat200

    C5)

    Ratedfrequency

    bar

    0.8

    Hz

    Rated(normal)current3)

    Ratedpeakwithstandcurrent

    equaltoratedshort-circuit

    makingcurrent

    A

    630

    kA

    80

    Ratedshort-timecurrent

    1s 3s

    kA

    31.5

    kA

    20

    Ratedshort-circuitbreaking

    current

    PercentagevalueoftheDC

    component

    kA

    31.5

    %

    WIA

    WIA

    WIA

    WIA

    8/17-2/621

    8/17-2/621 600

    8/17-2/621

    8/17-2/621

    WIB

    WIB

    WIB

    WIB

    8/17-2/627

    8/17-2/627

    8/17-2/627

    8/17-2/627

    600

    17.5 95 38 110/45

    17.5 95 38 110/45

    0.8

    0.8 50/60

    1.3

    1.3

    1250

    1600

    80

    80

    2000

    25001)

    80

    80

    0.8

    0.8

    0.8

    1.3

    50/60

    630

    1250

    80

    80

    1600

    2000

    80

    80

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5 38

    31.5

    31.5

    31.5

    31.5

    20

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    38

    WIB

    WIA

    WIA

    WIA

    8/17-2/627

    10/17-2/621

    60010/17-2/621

    10/17-2/621

    WIA

    WIB

    WIB

    WIB

    10/17-2/621

    10/17-2/627

    60010/17-2/627

    10/17-2/627

    17.5 95 38 110/45

    17.5 95 38 110/45

    WIB 10/17-2/627

    1.3

    0.8

    50/600.8

    1.3

    25002)

    1250

    80

    100

    1600

    2000

    100

    100

    1.3

    0.8

    50/600.8

    1.3

    25001)

    1250

    100

    100

    1600

    2000

    100

    100

    31.5

    40

    31.5

    40

    40

    40

    40

    40

    31.5

    40

    3840

    40

    40

    40

    40

    40

    40

    40

    40

    40

    40

    40

    3840

    40

    1.3 25002) 100 40 40 40

    Selection tables (contd.)

    WIA/WIB 17 kV

    LS = Circuit-breakerTS = Three-position switch, disconnector I/O

    ES = Three-position switch, earthing switch I/O

    1) with cooling gas tank, panel height 2750 mm2) with motor-actuated fan3) possiblelimitsandcomponentstted,refertoprojectplanningdocumentsWIno.495424) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report5) minimumservicepressure0.3baratallingpressureof0.8bar;0.7baratallingpressureof1.3bar

  • 7/30/2019 GIS Sieens Wi en 100709

    25/5225WI EN

    WI Selection tables (contd.)

    Rated operating

    sequence

    O-3min-CO-3min-CO

    O-0.3s-CO-3min-CO

    CO-15s-CO

    O-0.3s-CO-15s-CO

    Cablebreakingcurrent

    A

    Smallindirectcurrents

    Ratedbreakingcurrent

    underout-of-phaseconditions

    A kA

    8

    Number of operating

    cycles withoutoverhaul

    mech. electrical

    Operating times

    with release

    25 W

    LS,TS,

    Ewithrated(normal)current

    10000

    withratedshort-circuit

    breakingcurrent

    Openingtime

    4)

    ms

    160 W 160 W

    Command times

    with release

    25 W

    Openingtime

    4)

    Closingtime

    4)

    ms ms

    Arcduration(max.)

    Off

    ms ms

    160 W 160 W

    Off

    On

    On

    Off

    ms ms

    Chargingtimeformotordrive

    mechanism

    Operatingtimefordisconnector

    andearthingswitchwithmotor-

    drivemechanism,160W

    s s

    25 10

    8

    8

    8

    8

    25

    8

    8

    10 8

    8

    1000

    1000 10000 100 45-65

    10000

    1000

    1000 10000 100 45-65

    33-50 40-70 14 50

    33-50 40-70 14 50

    20 20 12 18

    20 20 12 18

    25 10

    8

    10

    10

    10

    25 10

    10

    10

    10

    10

    10

    10000

    100001000

    1000100 45-65

    10000

    100001000

    1000100 45-65

    33-50 40-70 14 50

    33-50 40-70 14 50

    20 20 12 18

    20 20 12 18

  • 7/30/2019 GIS Sieens Wi en 100709

    26/5226 WI EN

    WI

    Type

    WIA

    Panelwidth

    8/24-2/621

    mm

    Rated insulation level

    Ratedvoltage

    Ratedlightningimpulse

    withstandvoltage

    kV kV

    Ratedpowerfrequency

    withstandvoltage

    Ratingsofisolatingdistance

    kV kV/kV

    Designpressure

    Prat200C

    5)

    Ratedfrequency

    bar

    0.8

    Hz

    Rated(normal)current3)

    Ratedpeakwithstandcurrent

    equaltoratedshort-circuit

    makingcurrent

    A

    630

    kA

    80

    Ratedshort-timecurrent

    1s 3s

    kA

    31.5

    kA

    20

    Ratedshort-circuitbreaking

    current

    PercentagevalueoftheDC

    component

    kA

    31.5

    %

    WIA

    WIA

    WIA

    WIA

    8/24-2/621

    8/24-2/621 600

    8/24-2/621

    8/24-2/621

    WIB

    WIB

    WIB

    WIB

    8/24-2/627

    8/24-2/627

    8/24-2/627

    8/24-2/627

    600

    24 125 50 145/60

    24 125 50 145/60

    0.8

    0.8 50/60

    1.3

    1.3

    1250

    1600

    80

    80

    2000

    25001)

    80

    80

    0.8

    0.8

    0.8

    1.3

    50/60

    630

    1250

    80

    80

    1600

    2000

    80

    80

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5 38

    31.5

    31.5

    31.5

    31.5

    20

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    38

    WIB

    WIA

    WIA

    WIA

    8/24-2/627

    10/24-2/621

    60010/24-2/621

    10/24-2/621

    WIA

    WIB

    WIB

    WIB

    10/24-2/621

    10/24-2/627

    60010/24-2/627

    10/24-2/627

    24 125 50 145/60

    24 125 50 145/60

    WIB 10/24-2/627

    1.3

    0.8

    50/600.8

    1.3

    25002)

    1250

    80

    100

    1600

    2000

    100

    100

    1.3

    0.8

    50/600.8

    1.3

    25001)

    1250

    100

    100

    1600

    2000

    100

    100

    31.5

    40

    31.5

    40

    40

    40

    40

    40

    31.5

    40

    3840

    40

    40

    40

    40

    40

    40

    40

    40

    40

    40

    40

    3840

    40

    1.3 25002) 100 40 40 40

    Selection tables (contd.)

    WIA/WIB 24 kV

    LS = Circuit-breaker

    TS = Three-position switch, disconnector I/O

    ES = Three-position switch, earthing switch I/O

    1) with cooling gas tank, panel height 2750 mm2) with motor-actuated fan3) possiblelimitsandcomponentstted,refertoprojectplanningdocumentsWIno.495424) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report5) minimumservicepressure0.3baratallingpressureof0.8bar;0.7baratallingpressureof1.3bar

  • 7/30/2019 GIS Sieens Wi en 100709

    27/5227WI EN

    WI Selection tables (contd.)

    Rated operatingsequence

    O-3min-CO-3min-CO

    O-0.3s-CO-3min-CO

    CO-15s-CO

    O-0.3s-CO-15s-CO

    Cablebreakingcurrent

    A

    Smallindirectcurrents

    Ratedbreakingcurrent

    underout-of-phaseconditions

    A kA

    8

    Number of operatingcycles without

    overhaul

    mech. electrical

    Operating times

    with release

    25 W

    LS,TS,

    Ewithrated(normal)current

    10000

    withratedshort-circuit

    breakingcurrent

    Openingtime

    4)

    ms

    160 W 160 W

    Command times

    with release

    25 W

    Openingtime

    4)

    Closingtime

    4)

    ms ms

    Arcduration(max.)

    Off

    ms ms

    160 W 160 W

    Off

    On

    On

    Off

    ms ms

    Chargingtimeformotordrive

    mechanism

    Operatingtimefordisconnector

    andearthingswitchwithmotor-

    drivemechanism,160W

    s s

    31.5 10

    8

    8

    8

    8

    31.5

    8

    8

    10 8

    8

    1000

    1000 10000 100 45-65

    10000

    1000

    1000 10000 100 45-65

    33-50 40-70 14 50

    33-50 40-70 14 50

    20 20 12 18

    20 20 12 18

    31.5 10

    8

    31.5 10

    -

    10000

    100001000

    1000100 45-65

    10000

    100001000

    1000100 45-65

    33-50 40-70 14 50

    33-50 40-70 14 50

    20 20 12 18

    20 20 12 18

  • 7/30/2019 GIS Sieens Wi en 100709

    28/5228 WI EN

    WI

    Type

    WIA

    Panelwidth

    6/36-2/621

    mm

    Rated insulation level

    Ratedvoltage

    Ratedlightningimpulse

    withstandvoltage

    kV kV

    Ratedpowerfrequency

    withstandvoltage

    Ratingsofisolatingdistance

    kV kV/kV

    Designpressure

    Pr

    at200C

    5)

    Ratedfrequency

    bar

    1.3

    Hz

    Rated(normal)current3)

    Ratedpeakwithstandcurrent

    equaltoratedshort-circuit

    makingcurrent

    A

    630

    kA

    63

    Ratedshort-timecurrent

    1s 3s

    kA

    25

    kA

    20

    Ratedshort-circuitbreaking

    current

    PercentagevalueoftheDC

    component

    kA

    25

    %

    42

    WIA

    WIA

    WIA

    WIA

    6/36-2/621

    6/36-2/621 600

    6/36-2/621

    6/36-2/621

    WIB

    WIB

    WIB

    WIB

    6/36-2/627

    6/36-2/627

    6/36-2/627

    6/36-2/627

    600

    36 170 70 195/80

    36 170 70 195/80

    1.3

    1.3 50

    1.3

    1.3

    1250

    1600

    63

    63

    2000

    25001)

    63

    63

    1.3

    1.3

    1.3

    1.3

    50

    630

    1250

    63

    63

    1600

    2000

    63

    63

    25

    25

    25

    25

    25

    25

    25

    25

    25

    25

    42

    42

    25

    25

    42

    42

    25

    25

    20

    25

    25

    25

    25

    25

    25

    25

    42

    42

    25

    25

    42

    42

    WIB

    WIA

    WIA

    WIA

    6/36-2/627

    10/36-2/621

    60010/36-2/621

    10/36-2/621

    WIA

    WIB

    WIB

    WIB

    10/36-2/621

    10/36-2/627

    60010/36-2/627

    10/36-2/627

    36 170 70 195/80

    36 170 70 195/80

    WIB 10/36-2/627

    1.3

    1.3

    50/601.3

    1.3

    25002)

    1250

    63

    100

    1600

    2000

    100

    100

    1.3

    1.3

    50/601.3

    1.3

    25001)

    1250

    100

    100

    1600

    2000

    100

    100

    25

    40

    25

    40

    40

    40

    40

    40

    25

    40

    42

    31

    40

    40

    31

    31

    40

    40

    40

    40

    40

    40

    40

    40

    40

    40

    31

    31

    40

    40

    31

    31

    1.3 25002) 100 40 40 40 31

    Selection tables (contd.)

    WIA/WIB 36 kV

    LS = Circuit-breaker

    TS = Three-position switch, disconnector I/O

    ES = Three-position switch, earthing switch I/O

    1) with cooling gas tank, panel height 2750 mm2) with motor-actuated fan3) possiblelimitsandcomponentstted,refertoprojectplanningdocumentsWIno.495424) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report5) minimum service pressure 0.7 bar

  • 7/30/2019 GIS Sieens Wi en 100709

    29/5229WI EN

    WI Selection tables (contd.)

    Rated operating

    sequence

    O-3min-CO-3min-CO

    O-0.3s-CO-3min-CO

    CO-15s-CO

    O-0.3s-CO-15s-CO

    Cablebreakingcurrent

    A

    Smallindirectcurrents

    Ratedbreakingcurrent

    underout-of-phaseconditions

    A kA

    6.3

    Number of operating

    cycles withoutoverhaul

    mech. electrical

    Operating times

    with release

    25 W

    LS,TS,

    Ewithrated(normal)current

    10000

    withratedshort-circuit

    breakingcurrent

    Openingtime

    4)

    ms

    160 W 160 W

    Command times

    with release

    25 W

    Openingtime

    4)

    Closingtime

    4)

    ms ms

    Arcduration(max.)

    Off

    ms ms

    160 W 160 W

    Off

    On

    On

    Off

    ms ms

    Chargingtimeformotordrive

    mechanism

    Operatingtimefordisconnector

    andearthingswitchwithmotor-

    drivemechanism,160W

    s s

    50 10

    6.3

    6.3

    6.3

    6.3

    50

    6.3

    6.3

    10 6.3

    6.3

    1000

    1000 10000 100 43-65

    10000

    1000

    1000 10000 100 43-65

    29-50 40-65 14 50

    29-50 40-65 14 50

    20 20 12 18

    20 20 12 18

    50 10

    6.3

    6.3

    6.3

    6.3

    50 10

    6.3

    6.3

    6.3

    6.3

    6.3

    10000

    100001000

    1000100 43-65

    10000

    100001000

    1000100 43-65

    40-65 14 50

    40-65 14 50

    1220

    20

    18

    12 18

  • 7/30/2019 GIS Sieens Wi en 100709

    30/5230 WI EN

    WI

    Type

    WIA

    P

    anelwidth

    8/38-2/621

    mm

    Rated insulation level

    R

    atedvoltage

    R

    atedlightningimpulse

    w

    ithstandvoltage

    kV kV

    R

    atedpowerfrequency

    w

    ithstandvoltage

    R

    atingsofisolatingdistance

    kV kV/kV

    D

    esignpressure

    P

    rat200C

    5)

    R

    atedfrequency

    bar

    1.45

    Hz

    R

    ated(normal)current3)

    R

    atedpeakwithstandcurrent

    equaltoratedshort-circuit

    m

    akingcurrent

    A

    630

    kA

    80

    R

    atedshort-timecurrent

    1s 3s

    kA

    31.5

    kA

    20

    R

    atedshort-circuitbreaking

    current

    P

    ercentagevalueoftheDC

    component

    kA

    31.5

    %

    31

    WIA

    WIA

    WIA

    WIA

    8/38-2/621

    8/38-2/621 600

    8/38-2/621

    8/38-2/621

    WIB

    WIB

    WIB

    WIB

    8/38-2/627

    8/38-2/627

    8/38-2/627

    8/38-2/627

    600

    38 200 80 220/90

    38 200 80 220/90

    1.45

    1.45 50/60

    1.45

    1.45

    1250

    1600

    80

    80

    2000

    25001)

    80

    80

    1.45

    1.45

    1.45

    1.45

    50/60

    630

    1250

    80

    80

    1600

    2000

    80

    80

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31

    31

    31.5

    31.5

    31

    31

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31

    31

    31.5

    31.5

    31

    31

    WIB

    WIA

    WIA

    WIA

    8/38-2/627

    8/40.5-2/621

    6008/40.5-2/621

    8/40.5-2/621

    WIA

    WIB

    WIB

    WIB

    8/40.5-2/621

    8/40.5-2/627

    6008/40.5-2/627

    8/40.5-2/627

    40.5185(200)

    85215/90(220/90)

    40.5185(200)

    85215/90(220/90)

    WIB 8/40.5-2/627

    1.45

    1.45

    501.45

    1.45

    25002)

    1250

    80

    80

    1600

    2000

    80

    80

    1.45

    1.45

    501.45

    1.45

    25001)

    1250

    80

    80

    1600

    2000

    80

    80

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31

    31

    31.5

    31.5

    31

    31

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31.5

    31

    31

    31.5

    31.5

    31

    31

    1.45 25002) 80 31.5 31.5 31.5 31

    Selection tables (contd.)

    WIA/WIB 38 kV

    LS = Circuit-breaker

    TS = Three-position switch, disconnector I/O

    ES = Three-position switch, earthing switch I/O

    1) with cooling gas tank, panel height 2750 mm2) with motor-actuated fan3) forpossiblelimitvaluesandcomponentstted,refertotheprojectplanningdocumentsWIno.495424) adm. tolerance range, is not a manufacturing tolerance, for the current value of a specimen, refer to the routine test report5) minimumservicepressureat20C=1.0bar(overpressure)

  • 7/30/2019 GIS Sieens Wi en 100709

    31/5231WI EN

    WI Selection tables (contd.)

    Rated operatingsequence

    O

    -3min-CO-

    3min-CO

    O

    -0.3s-CO-

    3min-CO

    C

    O-

    15s-CO

    O

    -0.3s-CO-

    15s-CO

    C

    ablebreakingcurrent

    A

    S

    mallindirectcurrents

    R

    atedbreakingcurrent

    underout-of-phaseconditions

    A kA

    Number of operatingcycles withoutoverhaul

    mech. electrical

    Operating times

    with release

    25 W

    LS,TS,

    E withrated(normal)current

    10000

    w

    ithratedshort-circuit

    breakingcurrent

    O

    peningtime

    4)

    ms

    160 W160 W

    Command times

    with release

    25 W

    O

    peningtime

    4)

    C

    losingtime

    4)

    ms ms

    A

    rcduration(max.)

    O

    ff

    ms ms

    160 W160 W

    O

    ff

    OnO

    n

    Off

    ms ms

    C

    hargingtimeformotordrive

    m

    echanism

    O

    peratingtimefordisconnector

    andearthingswitchwithmotor-

    drivemechanism,

    160W

    s s

    50 10

    50

    10

    1000

    1000 10000 100 43-65

    10000

    1000

    1000 10000 100 43-65

    40-65 14 50

    40-65 14 50

    20 12 18

    20 12 18

    50 10

    50 10

    10000

    100001000

    1000100 43-65

    10000

    100001000

    1000100 43-65

    40-65 14 50

    40-65 14 50

    20 12 18

    20 12 18

  • 7/30/2019 GIS Sieens Wi en 100709

    32/5232 WI EN

    WI Selection tables (contd.)

    WIA/WIB 40.5 up to 52 kV

    2 vacuum interrupter chambers per conductor

    LS = Circuit-breaker

    TS = Three-position switch, disconnector I/O

    ES = Three-position switch, earthing switch I/O

    1) with cooling gas tank, panel height 3314 mm and with motor-actuated fans2) with motor-actuated fan3) possiblelimitsandcomponentstted,refertoprojectplanningdocumentsWIno.495424) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report5) minimumservicepressureat20C:0.1baratallingpressureof1.45bar;1.8baratallingpressureof2.2bar

    Type

    WIA

    Panelw

    idth

    10/40.5-2/626

    mm

    600

    Rated insulation level

    Ratedv

    oltage

    Ratedlightningimpulse

    withstan

    dvoltage

    kV

    40.5

    kV

    200

    Ratedp

    owerfrequency

    withstan

    dvoltage

    Ratings

    ofisolatingdistance

    kV

    80

    kV/kV

    220/90

    Design

    pressure

    Prat20

    0C

    5)

    Ratedfrequency

    bar

    1.45

    Hz

    50

    Rated(normal)current3)

    Ratedp

    eakwithstandcurrent

    equalto

    ratedshort-circuit

    making

    current

    A

    1250

    kA

    100

    Rateds

    hort-timecurrent

    1s 3s

    kA

    40

    kA

    40

    Rateds

    hort-circuitbreaking

    current

    PercentagevalueoftheDC

    compon

    ent

    kA

    40

    %

    26WIA

    WIB

    WIB

    10/40.5-2/626

    10/40.5-2/633

    10/40.5-2/633600

    WIA

    WIA

    8/52-2/626600

    8/52-2/626

    40.5 200 80220/90

    52

    (60)

    250

    (110)95

    290/110

    1.45

    1.45

    1.4550

    25001) 100

    1250

    25002)

    100

    100

    2.250/60

    2.2

    1250 82

    25001) 82

    40 40

    40

    40

    40

    40

    40

    40

    4026

    31.5 31.5

    31.5 31.5

    31.526

    31.5

    WIB

    WIB

    8/52-2/633

    8/52-2/633600

    52(60)

    250(110)

    95290/110 2.2

    2.250/60

    1250

    25002)

    82

    82

    31.5

    31.5

    31.5

    31.5

    31.5

    31.526

  • 7/30/2019 GIS Sieens Wi en 100709

    33/5233WI EN

    WI Selection tables (contd.)

    Rated operatingsequence

    O-3min-CO-3min-CO

    O-0.3s-CO-3min-CO

    CO-15

    s-CO

    O-0.3s-CO-15s-CO

    Cableb

    reakingcurrent

    A

    50

    Smallin

    directcurrents

    Ratedb

    reakingcurrent

    underout-of-phaseconditions

    A kA

    Number of operatingcycles without

    overhaul

    mech. electrical

    Operating times

    with release

    25 W

    LS,TS,E w

    ithrated(normal)current

    1000010000

    withratedshort-circuit

    breakingcurrent

    Openingtime

    4)

    100

    ms

    50-80

    160 W 160 W

    Command times

    with release

    25 W

    Openingtime

    4)

    Closing

    time

    4)

    ms

    ms

    40-65

    Arcduration(max.)

    Off

    ms

    14

    ms

    50

    160 W 160 W

    Off

    On

    On

    Off

    ms

    ms

    20

    Chargin

    gtimeformotordrive

    mechan

    ism

    Operatingtimefordisconnector

    andearthingswitchwithmotor-

    drivemechanism,160

    W

    s

    12

    s

    18

    50

    50

    1000

    1000

    10000

    100010000 100 50-80

    1000

    1000010000

    1000

    1000

    100 50-80

    40-65 14 50

    40-65 14 50

    20 12 18

    20 12 18

    5010000

    100010000

    1000

    100 50-80 40-65 14 12 18

    50 20

  • 7/30/2019 GIS Sieens Wi en 100709

    34/5234 WI EN

    WI Selection tables (contd.)

    WIA/WIB 1 and 2-POLE, for stationary railway traction power supply 50/60 Hz

    with 2 vacuum interrupter chambers per conductor

    LS = Circuit-breaker

    TS = Three-position switch, disconnector I/O

    ES = Three-position switch, earthing switch I/O

    S = 1-pole

    T = 2-pole

    3) without cooling gas tank and heat sink4) adm. tolerance range, no manufacturing tolerance, current value of one specimen, see routine test report5) minimum service pressure at 20 C 1.8 bar

    Type

    WIA

    Pane

    lwi

    dth

    6/55-S/626

    mm

    600

    Rated insulation level

    Ra

    tedvo

    ltage

    UNM

    acc.

    to

    EN

    5012

    4

    Ra

    tedvo

    ltage

    U

    acc.

    to

    EN

    6069

    4

    kV

    27.5

    kV

    52

    Ra

    tedlig

    htning

    impu

    lse

    withs

    tand

    vo

    ltage

    Ra

    tedpo

    wer

    frequency

    withs

    tand

    vo

    ltage

    kV

    250

    kV

    95

    Ra

    tingso

    fiso

    lating

    distance

    Des

    ignp

    ressure

    Pr

    be

    i20

    0C

    5)

    kV/kV

    290/110

    bar

    2.2

    Ra

    tedfre

    quency

    Ra

    ted(norma

    l)curren

    3)

    Hz

    50/60

    A

    1250

    Ra

    tedpe

    akw

    iths

    tan

    dcurren

    t

    equa

    ltora

    teds

    hort-c

    ircu

    itma-

    kingcurren

    t

    Ra

    tedsh

    ort-t

    imecurren

    t

    1s

    kA

    65

    kA

    25

    3s

    Ra

    tedsh

    ort-c

    ircu

    itbrea

    king

    curren

    t

    kA kA

    25

    Percenta

    geva

    lueo

    fthe

    DC

    compone

    nt

    %

    26WIA

    WIA

    WIA

    6/55-S/626

    6/55-T/626

    6/55-T/626600

    WIA-Z 600

    27.5 52 250 95

    17.5 36 170 70

    290/110 2.2

    2000

    50/601250

    2000

    195/110 2.2 16 2/3 1250

    65 25

    65

    65

    25

    25

    25

    25

    25

    80 31.5 31.5

    26

    46

  • 7/30/2019 GIS Sieens Wi en 100709

    35/5235WI EN

    WI Selection tables (contd.)

    Rated operatingsequence

    O-

    3min

    -CO-

    3min-CO

    O-

    0.3s

    -CO-

    3min-CO

    CO-

    15s-CO

    O-

    0.3s

    -CO-

    15s-CO

    Cablebreakingcurrent

    A

    50

    Smallind

    irectcurrents

    Ratedbreakingcurrent

    underou

    t-of-phaseconditions

    A kA

    12.5

    Number of operatingcycles without over -

    haul

    mech. electrical

    Operating times

    with release

    25 W

    LS,TS,E w

    ithrated(normal)current

    1000010000

    withratedshort-circuit

    breaking

    current

    Opening

    time

    4)

    100

    ms

    50-80

    160 W 160 W

    Command time

    with release

    25 W

    Opening

    time

    4)

    Closingtime

    4)

    ms

    ms

    40-50

    Arcduration(max.)

    Off

    ms

    14

    ms

    50

    160 W 160 W

    Off

    On

    On

    Off

    ms

    ms

    20

    Charging

    timeformotordrive

    mechanism

    Operatingtimefordisconnector

    andearth

    ingswitchwithmotor-

    drivemechanism,

    160

    W

    s

    12

    s

    18

    50 12.5

    50

    1000

    1000

    10000

    100010000 100 50-80

    1000

    10000 10000

    1000

    1000

    100

    40-50 14 50

    25-35 40-50 6-68

    12 18

    20 20

    20

    12 18

  • 7/30/2019 GIS Sieens Wi en 100709

    36/5236 WI EN

    WI Range of products

    Single busbar panels

    Circuit-breaker panel

    With inner cone-type cable connection for

    rated voltage up to 52 kV

    rated short-circuit breaking current up to 40 kA

    ratedbusbarandoutgoingfeeder(normal)currentsupto2500A

    Disconnector panel

    With inner cone-type cable connection for

    rated voltage up to 52 kV

    rated short-time current up to 40 kA

    ratedbusbarandoutgoingfeeder(normal)currentsupto2500A

    Bus section couplerfor

    rated voltage up to 52 kV

    rated short-circuit breaking current up to 40 kA

    ratedbusbar(normal)currentsupto2500A

    connection

    Panel connection

    or

    or

    or

    and Busbarcurrenttransformer

    Surgearrester,pluggable

    Voltagetransformer,pluggable

    Plug-in cablesingle,

    Terminal type3

    or

    or

    or

    or Busbarwith solidinsulation

    Panel

    variants

    Surgearrester,

    pluggable

    Currenttransformer

    Voltagetransformer,

    pluggable

    Busbar attachments

    attachment

    Currenttransformer

    Plug-in cablequadruple

    Plug-in cabletriple

    Plug-in cabledouble

    Plug-in cablesingle

    1)

    1)

    1)

    1)if a surge arrester is used,the number of cables isreduced by one

    1)

    1)

    Circuit-breaker panel

    (Innercone-typecableconnection)

    Bus section coupler

    1) not possible in case of 52 kV

  • 7/30/2019 GIS Sieens Wi en 100709

    37/5237WI EN

    WI Range of products (contd.)

    Double busar panels

    Circuit-breaker panel With inner cone-type cable connection for

    rated voltage up to 52 kV

    rated short-circuit breaking current up to 40 kA

    ratedbusbarandoutgoingfeeder(normal)currentsupto2500A

    Bus section coupler(Circuit-breakerpanelandbusriserpanel)

    With inner cone-type cable connection for rated voltage up to 52 kV

    rated short-circuit breaking current up to 40 kA

    ratedbusbarandoutgoingfeeder(normal)currentupto2500A

    Bus section couplerfor

    rated voltage up to 52 kV rated short-circuit breaking current up to 40 kA

    ratedbusbar(normal)currentupto2500A

    Bus coupler (transverse)for

    rated voltage up to 52 kV

    rated short-circuit breaking current up to 40 kA

    ratedbusbar(normal)currentupto2500A

    Metering panelfor

    rated voltage up to 36 kV

    ratedbusbar(normal)currentupto2500A

    Circuit-breaker panel(Innercone-typecableconnection)

    or

    or

    or

    and Busbarcurrenttransformer

    Surgearrester,pluggable

    Voltagetransformer,pluggable

    Plug-in cablesingle,Terminal type3

    or

    or

    or

    or Busbarwith solidinsulation

    variants

    Surgearrester,

    pluggable

    Currenttransformer

    Busbar attachments

    Panel connectionattachment

    Plug-in cablequadruple

    Plug-in cabletriple

    Plug-in cabledouble

    Plug-in cablesingle

    1)

    1)

    1)

    1) if a surge arrester is used,the number of cables isreduced by one

    Voltagetransformer,

    pluggable

    1)

    1)

    SS2SS1

    1) not possible in case of 52 kV

  • 7/30/2019 GIS Sieens Wi en 100709

    38/5238 WI EN

    WI Range of products (contd.)

    1) not possible in case of 52 kV

    SS2

    SS1

    Panelconnection

    variants

    or

    or

    or

    or Busbar

    with solidinsulation

    Surgearrester,

    pluggable

    Plug-in cablequadruple

    Plug-in cabletriple

    Plug-in cabledouble

    Plug-in cablesingle

    Panelconnectionattachment

    SS2

    SS1

    Panelconnection

    variants

    or

    or

    or

    or Busbar

    with solidinsulation

    Surge

    arrester,pluggable

    Panel connectionattachment

    Currenttransformer

    1)

    1)

    1)

    1) if a surge arrester is used,the number of cables isreduced by one

    Voltagetransformer,

    pluggable

    1)

    1)

    1)

    1) if a surge arrester is used,the number of cables isreduced by one

    Voltagetransformer,

    pluggable

    Plug-in cablequadruple

    Plug-in cabletriple

    Plug-in cabledouble

    Plug-in cablesingle

    1) 1)

    Disconnector panel

    (Innercone-typecableconnection)

    Bus section coupler / riser panel

  • 7/30/2019 GIS Sieens Wi en 100709

    39/5239WI EN

    WI Range of products (contd.)

    1) only up to 40.5 kV

    Abbreviations

    SS1 = Busbar 1

    SS2 = Busbar 2

    SS2

    SS1

    Current

    transformer

    SS2

    SS1

    Currenttransformer

    SS2

    SS1

    Bus coupler

    up to 2000 A

    (1 panel width) 1)

    SS2

    SS1

    Currenttransformer

    Bus section coupler Bus coupler up to 2500 A 1) Disconnector/earthing

    switch in line with busbar

  • 7/30/2019 GIS Sieens Wi en 100709

    40/5240 WI EN

    WI Cable connections

    Cable connections in outgoing feeder blockThe medium-voltage cables are connected to the switchgear panels via

    metal-enclosed inner cone-type plug-in terminations. The panels areequipped with inner cone-type appliance couplers according to EN 50 181.

    Themanufacturersspecicationsoftheregardingselectionandassembly

    of the plug-in terminations must be adhered to. This does not only apply to

    the selection of size, but also to all electrical rated data, in line with the

    switchgears data.

    It is essential that all appliance couplers which are not equipped withplug-in terminations are terminated correctly using voltage-proof and fully

    shrouded insulating terminals/ dummy plugs.

    To this effect, the inner cone-type cable plug-in terminations for attachment

    to WI require capacitive decoupling. The coupling electrodes for the

    capacitive voltage detection system are an integral part of the appliance

    couplers installed in the switchgear panel.

    Cable connections in outgoing feeder

    3 phase switchgear

    panels

    1 phase switchgear

    panels

    2 phase switchgear

    panels

    Inner cone acc. to EN 50181

    Terminal types:

    size 1 630 A

    size 2 800 A

    size3(upto40.5kV) 1250 A

    size3(>40.5upto52kV) 1250 A

    size 4 2500 A

    Single / double busbar Single cable, 3-phase, withoutoutgoing voltage transformer

    12-36 kV 38-40.5 kV

    1x size 1

    1x size 2

    1x size 3

    1x size 4

    Size 4 with supporting structure increased in height

    Single busbar Railway traction power supply with 2 vacuuminterrupter chambers per phase

    1-pole L1 2-pole L1, L3

    1x size 3/S Single cable connection

  • 7/30/2019 GIS Sieens Wi en 100709

    41/5241WI EN

    WI Cable connections (contd.)

    Single / double busbar with 1 vacuum interrupter chamberper conductor/phase

    Multi-cable, 3-phase, without outgoingvoltage transformer

    12 kV - 36 kV 38 kV - 40.5 kV

    2 x size 1

    3 x size 1

    2 x size 2

    3 x size 2

    4 x size 2

    2 x size 3

    3 x size 3

    4 x size 3

    1xsize1+2xsize3

    1xsize2+2xsize3

    Single / double busbar with 2 vacuum interrupter chambersper conductor/phase

    Single- and multi-cable, 3-phase, without outgoing voltage transformer

    40.5 kV

    BIL 200 kV

    52 kV

    BIL 250 kV

    1 x size 3

    1 x size 3/S

    2 x size 3

    2 x size 3/S

    3 x size 3

    3 x size 3/S

    Single busbar for stationary railway traction power supplywith 2 vacuum interrupter chambers per conductor/phase

    Multiple cable without voltage transformer

    1-phase L1 2-phase L1 + L3

    2 x size 3/S

    3 x size 3/S

    4 x size 3/S

    5 x size 3/S

    Multi-cable connection

  • 7/30/2019 GIS Sieens Wi en 100709

    42/5242 WI EN

    WI Cable connections (contd.)

    Single / double busbar with 1 vacuum interrupter chamberper conductor/phase

    Multi-cable, 3-phase with 3 outgoingvoltage transformers

    12 kV - 36 kV 38 kV - 40.5 kV

    1 x size 2

    3 x size 2

    4 x size 2

    1 x size 3

    2 x size 3

    3 x size 3

    4 x size 3

    1xsize2+1xsize3

    1xsize2+2xsize3

    1xsize2+3xsize3

    1xsize2+4xsize3

    1xsize1+3xsize3

    Single / double busbar with 2 vacuum interrupter chambersper conductor/phase

    Multi-cable, 3-phase, with 1 outgoing voltage transformer (1-phase in L2)

    40.5 kV

    BIL 200 kV

    52 kV

    BIL 250 kV

    1 x size 3

    1 x size 3/S

    2 x size 3

    3 x size 3/S

    possibleuptorated(normal)currentinoutgoingfeederofmax.1600A

    Single busbar for stationary railway traction power supplywith 2 vacuum interrupter chambers per conductor/phase

    Multi-cable with 1 or 2 voltage transformers

    1-phaseL1

    2-phase L1 + L3

    Voltagetransformers

    L3

    Voltage transformers

    L1 + L3

    1 x size 3/S

    2 x size 3/S

    3 x size 3/S

    4 x size 3/S

    Multi-cable connection with voltage

    transformer in outgoing feeder

  • 7/30/2019 GIS Sieens Wi en 100709

    43/5243WI EN

    WI Ecological considerations

    A WI switchgearsatisestoahighdegreeecologicalrequirementsinviewof environmental protection thanks to

    optimization of material and energy consumption during manufacture compliance with all ecological requirements during its service life theuseofrecyclablematerialsforefcientdisposalattheendofitsservice life.

    Our design directives regarding environmentally compatible design specifythe use of materials which are easily recyclable and can be disassembled.The metals which make up approx. 90 % of the switchgear are easilyrecyclable. At the end of their service life, they are recycled 100 % in theform of homogenous materials.

    Plastics can also be recycled. Thermosetting i.e. non-melting plasticscanbecomminutedandreusedasllersinotherplasticcomponents;thermoplastic - i.e. melting - materials can be recycled in the form ofhomogenous material. This means that the material is conserved, melteddown and used for the construction of new durable parts.

    Toensureefcientandenvironmentallycompatibledisassemblyandassignment of materials by the responsible disposal experts, the

    switchgearsplasticcomponentshavebeenidentiedaccordingly.Moreover, material and utilization data sheets are available to provide thecustomer with an over- view about the materials used. Equally, the disposalcompany is provided with important information regarding the recycling process.

    Thus, the materials used for our products can be reused 100 %.

    This represents a major contribution towards saving primary energy andmaterial resources.

    Allmaterialswereselectedanddevelopedsothate.g.incaseofrewithinbuildings,affectedswitchgearonlyhaveaminorinuenceonthereload(heatdevelopment,pollutantsintheemissions) .

    Anotherimportantecologicalaspectisthelongevityofourproducts(min.30to40years),whichisanextremelylongservicelifecomparedtoothercapital goods. Furthermore, the switchgear units have been designed so asto require little maintenance which would in turn use up energy and material,

    and so as to enable straightforward replacement of part components, e.g. ifnewcontrollershavebeendevelopedonthemarket(upgrading).

    In our gas-insulated switchgear WI, the majority of the switchgear panelhasbeensealedhermeticallyinaninsulatinginertgas(sulphurhexauorideSF

    6whichisneitherreactivenortoxic).Thus,all

    environmentalinuencesreducingtheservicelifeareshutout.Thespecialcharacteristics of the insulating gas also enable an overall size reduction byapprox. 50 percent versus switchgear designed without insulating gas withcomparable technical properties. This again saves a lot of material andenergy required for material production. The portion of insulating gas usedfor WI switchgear amounts to approx. 0.5 percent by weight. Once theswitchgears service life has elapsed, the gas is extracted completely viathedisposalvalveprovidedseriallyineachgas-lled,claddedcompartment, and then recycled. The gas suppliers have developed anefcientrecyclingconcepttothiseffect.

    During normal operation, the gas need not be replenished during the entireservice life of the switchgear. The switchgear is a hermetically sealedpressuresystemacc.toIEC60694(IEC62271-1).

    Average material distribution in gas-insulatedswitchgear units

    Materials Wt. %

    Metals Steel 7

    Copper 6.5

    Aluminium, brass 2

    Plastics Thermosetting plastics 7

    Thermo-plastics 2

    Elastomers 0.5

    Electronics Plastics 0.5

    Metals 1

    Insulating gas Sulphurhexauoride 0.5

  • 7/30/2019 GIS Sieens Wi en 100709

    44/5244 WI EN

    WI Design dataSpace requirements - dimensions andweights

    >500

    >500

    >1000 >1500 1)

    2400

    WIA up to 40.5 kV

    >500

    >500

    >500 >1500

    1)

    >500

    >500

    >1500 1)

    >1000

    WIA up to 52 kV

    2964

    1) smaller gap on request

    Weights:

    WIA up to 40.5 kV approx. 1000 kg

    WIA 52 kV approx. 1350 kg

    280

    673

    1692

    600

    460

    70

    70

    Spacer bars7070

    Flooring ducts

    Top view

    view

  • 7/30/2019 GIS Sieens Wi en 100709

    45/5245WI EN

    WI Design dataSpace requirements - dimensions andweights(contd.)

    WIA up to 52 kV

    >50

    0

    >500 >500

    >10

    00 >1500 1)

    2400

    WIA up to 40.5 kV

    >500

    >500

    >500 >1500

    1) >500

    280

    673

    1692

    600

    460

    70

    70

    Spacer bars7070

    >5

    00

    >500

    >15001)

    >10

    00

    2964

    WIA up to 52 kV

    1) smaller gap on request

    Weights:

    WIA up to 40.5 kV max. 1000 kg

    WIA 52 kV approx. 1350 kg

    Flooring ducts

    Top view

    view

  • 7/30/2019 GIS Sieens Wi en 100709

    46/5246 WI EN

    WI

    WIB up to 40.5 kV

    >500

    >500

    >500 >1500

    1)>500

    280673

    1692

    600

    460

    70

    70Spacer bars

    70

    70

    >500

    >500 >500

    >1000 >1500 1)

    3050

    WIB bis 40,5 kV>50

    0

    >500

    >1500 1)

    >1000

    3614

    WIB bis 52 kV

    1) smaller gap on request

    Weights:

    WIB up to 40.5 kV approx. 1300 kg

    WIB 52 kV approx. 1700 kg

    Flooring ducts

    Top view

    view

    Design dataSpace requirements - dimensions andweights(contd.)

  • 7/30/2019 GIS Sieens Wi en 100709

    47/5247WI EN

    WI

    WIB up to 52 kV

    >500

    >500

    >1000 >1500 1)

    3050

    WIB up to 40.5 kV

    >500

    >500

    >500 >1500

    1)

    280673

    1692

    600

    460

    70

    7070

    70

    Spacer bars

    >500

    >500

    >1500 1)

    >1000

    3614

    WIB up to 52 kV

    1) smaller gap on request

    Weights:

    WIB up to 40.5 kV approx. 900 - 1000 kg

    WIB 52 kV approx. 1100-1500Kg

    Flooring ducts

    Top view

    view

    Design dataSpace requirements - dimensions andweights(contd.)

  • 7/30/2019 GIS Sieens Wi en 100709

    48/5248 WI EN

    WI

    Busbar connection with fully insulated conductor bars

    Direct transfer line. Phase exchange in terminal tank

    Design dataSpace requirements - dimensions andweights(contd.)

  • 7/30/2019 GIS Sieens Wi en 100709

    49/5249WI EN

    WI

    Direct transfer line. Phase exchange in terminal tank

    Transfer line top and bottom by means of supplementary gas tank

    Transfer line at the bottom. Phase exchange required in transfer line

    Design dataSpace requirements - dimensions andweights(contd.)

  • 7/30/2019 GIS Sieens Wi en 100709

    50/5250 WI EN

    WI Shipping instructions

    Transporting the switchgear unitWhen transporting the switchgear unit, it is important to ensure that the

    transportunitsdonotsliportilt(ifnecessary,nailtransportpalletdowntotheloadingsurface).Reusetheoriginalpackagingtostorepartswhich

    have been unpacked for inspection.

    Packaging of the switchgear

    If packed for truck transport, the switchgear unit is delivered on a pallet

    withPEprotectivelm.

    Forsea-worthytransport,theunitsarepackedinsealedaluminiumlm

    with desiccant and in a closed case with tightly closed wooden base. In case of air transport, the switchgear unit is packed in a wooden crate

    withclosedwoodenbaseandwithablisterIPElmasdustprotectionor

    in a wooden case, also with closed wooden base.

    Transport to the site of installationStore under conditions admissible for switchgear operation. Avoid

    condensation.

    During transport to the site of installation, remember that the main weight islocated in the top area of the switchgear top-heavy.

    Transport using a forklift truck: Only transport the switchgear on a pallet.

    Attention top-heavy!

    Transport without pallet: The crane mounting harness must be hooked into

    the jack rings of the switchgear.