GEO DISPENSER TRAINING
www.kwangshin.com
GEO Dispenser Training Agenda
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
A. Difference Between GEO Dispenser and Kraus Dispenser
B. Introduce of GEO Dispenser Equipment
C. Explanation of GEO Dispenser Flow Chart and P&ID
D. GEO Dispenser Commissioning
E. Trouble Shooting of GEO Dispenser
F. GEO Breakaway and Nozzle
G. GEO Dispenser Calibration
H. Communication Through SCADA
A. Difference Between GEO/Kraus Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
1. Tube & Valve Part
A. Difference Between GEO/Kraus Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
2. Flow Meter Part
A. Difference Between GEO/Kraus Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
3. Controller Part
B. Introduce of GEO Dispenser Equipment
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
CPU Board
Power Board
Display Board PRESET
Barrier Board
1. Controller Part
B. Introduce of GEO Dispenser Equipment
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
SOLENOID VALVE
AC 220V
CARD Reader
RF-CARD Reader
Start SW
CARD Reader
RF-CARD Reader
THERMAL PRINTER
FLOW METER
POS
FLOW METER
Start SW
SOLENOID VALVE
2. Block Diagram(Control)
B. Introduce of GEO Dispenser Equipment
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
C. Explanation of GEO Dispenser Flow Chart and P&ID
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
1. P&ID
C. Explanation of GEO Dispenser Flow Chart and P&ID
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
2. Flow Chart(Flow Rate Mode)
START
Start S/W ?
Low Sol. V/V OpenHigh Sol. V/V Open
Yes
Flow rate?
High Sol. V/V Close
Flow rate?
Mid Sol. V/V Open
No
No
Yes
Time
Err 17
FRS1
EOF(End Of Flow)
A
A
Max Flow
Err 18
Max Flow
Err 18
A
A
High Sol. V/V Open
END
Flow rate? EOF(End Of Flow)
FRS2
High Sol. V/V CloseMid Sol. V/V CloseLow Sol. V/V Close
Flow rate?
EOF A
A
Max Flow
Err 18
Max Flow
Err 18
A
A
C. Explanation of GEO Dispenser Flow Chart and P&ID
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
3. Flow Chart(Pressure Mode)
START
Start S/W On?
Low Sol. V/V OpenHigh Sol. V/V Open
Yes
Flow rate ?
High Sol. V/V Close
Flowrate? EOP ?
Mid Sol. V/V Open
No
No
Yes
Time
Err 17
FRS1
EOF(End Of Flow)
A
A
Max Flow
Err 18
Max Flow
Err 18
A
EOP Delay Time
A
B
EOPC
C. Explanation of GEO Dispenser Flow Chart and P&ID
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
3. Flow Chart(Pressure Mode) - continued
High Sol. V/V Open
END
Flow rate?EOF ?
EOF(End Of Flow)
FRS2
High Sol. V/V CloseMid Sol. V/V CloseLow Sol. V/V Close
EOF =<EOP =< A
A
Max Flow
Err 18
Max Flow
Err 18
A
A
Flow rate?EOP ?
B
EOP
C
C. Explanation of GEO Dispenser Flow Chart and P&ID
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
3. Flow Chart(Pressure Mode) - continued
B
V/V Close
RESTART Delay Time Flow
EOF =>
V/V Open
BLANK Time
Flow Rate ?
A
EOP ?Flow Rate ?
EOF <
CFRS
EOF(End Of Flow)Max Flow
Err 18
A
CFRS
A
Max Flow
Err 18
A
EOF =>EOF(End Of Flow)
BLANKTIME
EOP >
EOP =<
A
D. GEO Dispenser Commissioning
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Inlet Valve Connect Tube
Inlet Valve Gas Leak Check
Inlet Valve Open
Instrument Gas connect (100psig)
Gas Leak Check
D. GEO Dispenser Commissioning
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
AC Power connect
CPU Junction Box Cable Check
AC Power On
CPU Junction switch ON
Dispenser Power ON
Start SW ON, delay 2 sec, SW_OFF, Valve ON/OFF Test
ShutOff Valve Open
Hose part Gas Leak Check
ShutOff Valve Close
D. GEO Dispenser Commissioning
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
PRESET “F2” PUSH
Unit Price Display – Pressure
Pressure Gauge, Transducer Check
PRESET Setting
D. GEO Dispenser Commissioning
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
SUMMARY of CNG DISPENSER SETUP VALUE(OPTION)
NO RANGE DEFAULT DESCRIPTION
11 0~40 0 Sets pump address used for serial data communication
12 0~2 1 Sets number of decimal places in the price unit display
13 0~2 0 Sets number of decimal places in the amount unit display
14 0~1 1 Select 1 or 3 pressurized lines
15 0~1 1 Sets number of Low solenoid valve On or Off
16 0~1 1 Sets number of Mid solenoid valve on of off
17 0~1 1 Sets of Control Mode(Flow Rate / Pressure)
18 0~1 0 Sets of Temperature Compensation (only Pressure Mode)
19 0~16 4Sets delay timer permitted between an end-of-pressure and true fill termination(only Pressure Mode)
20 0~30 10Sets time delay initated each time any flow control actuated ball valve is activated. (only Pressure Mode)
21 0~3600 3000 Sets operating EOP(End-of-Pressure) - (only Pressure Mode)
22 0~9900 5000 Scales pressure transducer 4~20mA ouput
23 0~15.00 2.5 Sets of EOF(End-Of-Flow)
24 0~65.00 35.0 Sets of Max Flow Rate(Unit Kg/m)
25 0~40.00 10.00 Increased pressure trip point at whice low bank switches to mid bank(FRS1)
26 0~30.00 6.5 Increased pressure trip point at whice mid bank switches to high bank(FRS2)
27 0~500 15 Sets of delay time before EOP check
28 na na NOT USED.
D. GEO Dispenser Commissioning
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
D. GEO Dispenser Commissioning
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Connect the nozzle to the vehicle
ShutOff Valve Open
Operation SW “Start” Position ( Dispenser RUN)
Open Hi, Low valve ON for 4 sec. allowing gas to flow to the car.
During these 4 sec. the CPU reads the Tempereture.
D. GEO Dispenser Commissioning
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Hi Valve Close and Filling begins.
As the pressure in the vehicle tank nears the pressure in low bank storage, the gas flow rate will decrease
When the gas flow rate falls below the PRESET setting FRS1 (e.g. 10.5 kg/min)…
D. GEO Dispenser Commissioning
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Mid valve Open PRESET OPT 15 = 0 : Low V/V Open PRESET OPT 15 = 1 : Low V/V Close
When the gas flow rate falls below the PRESET setting FRS2 (e.g. 6.5 kg/min)…
D. GEO Dispenser Commissioning
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Opens up the Hi valve to finish off the fill. PRESET OPT 16 = 0 : Mid V/V Open PRESET OPT 16 = 1 : Mid V/V Close
The fill will end when either the final fill pressure is reached or the gas flow rate falls below the PRESET setting EOF (e.g. 2.5 kg/min)
D. GEO Dispenser Commissioning
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
At this point the CPU will close all valves and Unit Price “end” Display
Operation SW “Stop” Position
Disconnect the nozzle by turning the handle 180°
This will allow the gas trapped between the vehicles receptacle and check valve to be vented
D. GEO Dispenser Commissioning
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
When the dispenser is off, there is still pressure in the lines up to the nozzle
** Venting the Dispenser
To start venting the dispenser, first close off the inlet ball valves
D. GEO Dispenser Commissioning
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Then open up the venting needle valve
** Venting the Dispenser - continued
D. GEO Dispenser Commissioning
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
** Venting the Dispenser - continued
The gas in the line will now start to escape through the vent tube
D. GEO Dispenser Commissioning
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
** Venting the Dispenser - continued
Notice now that there is still gas trapped between the inlet ball valves and the solenoid valves
D. GEO Dispenser Commissioning
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
** Venting the Dispenser - continued
Manual OpreationLow solenoid Instrument Line -> Mid solenoid Instrument Line connect -> Mid Valve Open
Operation Switch to “Start” Position, this will open up the Hi, Low valves, allowing for the gas trapped to be evacuated
Now maintenance work can be performed on the dispenser
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – EFCP-CPU
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Mutil Tester and AD Barrier connect
AD Barrier
CON1 : 1 CON2 : 1 1.0 ㏀ ~ 4.5 ㏀ OK
CON1 : 3 CON2 : 3 3.5 Ω ~ 4.5 Ω OK
Troubleshooting – AD Barrier
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – EFCP-2010(Manifold Module)PROBLEM POSSIBLE CAUSE SOLUTION
TOO HIGH A PRESSURE DROP FROM STORAGE
FILTERS ARE CLOGGED
a. CLEAN FILTER ELEMENTS WITH COMPRESSED AIR
b. REPLACE FILTER ELEMENTS
NO GAS THROUGH VALVE
1. ACTUATED VALVE IS PREVENTED FROM OPENING
2. SOLENOID IS NOT GETTING POWER TO OPEN OR IS FAULTY
3. SOLENOID IS NOT GETTING INSTRUMENT GAS
a. DISASSEMBLE VALVE AND LOOK FOR DEBRIS NEAR PISTON
b. REFURBISH VALVE ASSEMBLY WITH VALVE REBUILD KIT
c. CHECK THAT VALVE IS RECEIVING APPROPRIATE VOLTAGE
d. REPLACE SOLENOID
GAS FLOWING THROUGH VALVE WHEN NO POWER
TO SOLENOIDS
VALVE PISTON IS NOT SEALING CORRECLY
a. DISSASSEMBLE VALVE AND CHECK FOR SIGNS OF DEBRIS
b. REFURBISH VALVE ASSEMBLY WITH VALVE REBUILD KIT
c. REPLACE VALVE
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – Manifold Valve Maintenance
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – Manifold Valve Maintenance(cont.)
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – Manifold Valve Maintenance(cont.)
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – Manifold Valve Maintenance(cont.)
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – Manifold Valve Maintenance(cont.)
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – Manifold Valve Maintenance(cont.)
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – Manifold Valve Maintenance(cont.)
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – Manifold Valve Maintenance(cont.)
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – Manifold Valve Maintenance(cont.)
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – Manifold Valve Maintenance(cont.)
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – Manifold Valve Maintenance(cont.)
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – Manifold Valve Maintenance(cont.)
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – Manifold Valve Maintenance(cont.)
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – Manifold Valve Maintenance(cont.)
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – Manifold Valve Maintenance(cont.)
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – CNGMASS
LED
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – Hylok ValvesPROBLEM POSSIBLE CAUSE SOLUTION
VALVES ARE LEAKING WHEN
CLOSED1. VALVE SEALS HAVE FAILED a. REPLACE VALVE
Troubleshooting – WIKA IS-20 Pressure Transmitter
PROBLEM POSSIBLE CAUSE SOLUTION
TRANSMITTER NOT SENDING SIGNAL TO MICON (I.E. MICON IS DISPLAYING FAULT CODE co76 AND IS NOT RESOLVED BY
PRESSING RESET SWITCH)
1. WIRING FROM TRANSMITTER TO MICON IS FAULTY
2. TRANSMITTER HAS FAILED
a. CHECK WIRING OF TRANSMITTERb. REPLACE TRANSMITTER
E. Trouble Shooting of GEO Dispenser
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
Troubleshooting – WEH Hose, Nozzle & Breakaway Assembly
PROBLEM POSSIBLE CAUSE SOLUTION
NOZZLE IS LEAKING GAS DURING FILL
1. NOZZLE IS PAST RESERVICING PERIOD OF 3 YEARS OR 20,000 CYCLES
2. NOZZLE HAS BEEN DAMAGED DURING VEHICLE DRIVE AWAY
SEND BACK FOR REFURBISHMENT
HOSE RUPTURED OR SHOWING SIGNS OF
BLISTERING
HOSE HAS BEEN DAMAGED DURING VEHICLE DRIVE AWAY REPLACE HOSES
BREAKAWAY IS DISCONNECTING
WHEN PRESSURIZED
BREAKAWAY HAS BEEN DAMAGED DURING VEHICLE
DRIVE AWAYSEND BACK FOR REFURBISHMENT
F. GEO Breakaway and Nozzle
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
1. Nozzle
F. GEO Breakaway and Nozzle
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
2. Breakaway
G. GEO Dispenser Calibration
180-12, Okog-ri, Cholwon-Myun, Haman, Gyungnam, Korea
Tel : +82-55-589-8000 Fax : +82-55-589-8020 e-mail : [email protected] Web : www.kwangshin.com
CNG050
Receptacle
PG101
Vent
Nozzle
Nozzle
Dispenser EF-050-PROVER Car