4 Introduction
4 Legal elements
3 Regulatory Reform Fire Safety Order 2005
3Di bilit Di i i ti A t 1995 t III (O t 2004)
This Pocket Design & Installation booklet provides a simple guide for the provision of a fire
detection and alarm system in accordance with the recommendations detailed within the British
Standard Code of Practice BS 5839-1:2002
The handbook is designed to act as an aide-memoire and there is no substitute for reading the
full standard, copies of which can be obtained from:
British Standards Institute 389 Chiswick High Road, Chiswick, London W4 4AL
Tel: 020 8996 9001 Web: www.bsi-global .com Email: [email protected]
F I R E D E T E C T I O N S Y S T E M S
Contents
1
8/10/2019 Gent by Honeywell- A6 Installers Guide
http://slidepdf.com/reader/full/gent-by-honeywell-a6-installers-guide 3/16
F I R E D E T E C T I O N S Y S T E M S
3
Any design should be prepared by a competent individual/organisation, who has consulted all interested
parties and created a set of drawings, a specification, a cause & effect or fire plan, a list of Variations andcompleted a G1 Design certificate, detailed within BS 5839-1:2002.
If designs are undertaken without this research being carried out, the fire detection system is unlikely tocomply with the legal requirements. This could result in prosecution of the parties involved, particularlythose within the supply chain as well as the Owner/Occupier.
WARNING: Anyone who takes on the responsibility for design will do so at their own risk and designliability insurance is advisable.
The Designer’s responsibilities:
3 Agree the level of protection or category with Owner/Occupier
3 Justify any Variations and document reasons
3 Detail the detection & alarm zones
3 Prepare specification and drawings including;
3 Siti f l ll i t
System Design
8/10/2019 Gent by Honeywell- A6 Installers Guide
http://slidepdf.com/reader/full/gent-by-honeywell-a6-installers-guide 4/16
F I R E D E T E C T I O N S Y S T E M S
5
Determine the System Categoryor level of protection
Systems designed for Protectionof Property only, fall into two
classifications P1 or P2.
The objective of a Category P1 is to
provide the earliest possible warning
of a fire to minimise the time
between ignition and the arrival of
the fire fighters.
P1 is designed to protect the whole
building whilst P2 is installed in
defined parts of the building only,
hi h h t di
L5
M
8/10/2019 Gent by Honeywell- A6 Installers Guide
http://slidepdf.com/reader/full/gent-by-honeywell-a6-installers-guide 5/16
F I R E D E T E C T I O N S Y S T E M S
7
Detection and Alarm Zones
Generally a building is broken down into smaller compartments to enable the fire fighters tolocate the fire as quickly as possible.
Even if the system is addressable it is still considered beneficial to have a separate ‘at a glance’indication of the location of the fire.
These compartments of a building are called detection zones, which need to comply with thefollowing criteria.
Detection Zones
3 A detection zone should cover no more than 1 storey, unless total floor area is less than
300m2. Voids in the same fire compartment should be included in the same floor zone.
The maximum floor area of a zone should not be greater than 2,000m2, except for some large
open plan areas that incorporate manual call points only, which can be extended to 10,000m2.
Th i h di f
Design Stage 2
8/10/2019 Gent by Honeywell- A6 Installers Guide
http://slidepdf.com/reader/full/gent-by-honeywell-a6-installers-guide 6/16
F I R E D E T E C T I O N S Y S T E M S
9
Manual Call Point
Route of travel 45m max(defined)
Route of travel 30m max(undefined)
8/10/2019 Gent by Honeywell- A6 Installers Guide
http://slidepdf.com/reader/full/gent-by-honeywell-a6-installers-guide 7/16
F I R E D E T E C T I O N S Y S T E M S
11
Smoke sensors complying to BS EN54-7
Traditionally, ‘point’ type smoke sensors have fallen into two main categories, optical or ionisation.
Due to new European Directives for the storage and transport of radioactive sources, ionisationsensors are becoming less favourable and are being replaced by multi-sensors that utilise single or dualoptical chambers that are also combined with heat and/or carbon monoxide sensing elements.
This creates a whole range of sensors that are suitable for detecting different types of fires and yetignore signals that previously have led to false alarms such as white dust or steam particles.
The table below shows the various ‘states’ of these smoke sensor options. This should be readin conjunction with the attached application/risk charts to ensure the correct sensor is used fora particular location.
S-QUAD SINGLE AND DUAL OPTICAL HEAT MULTI-SENSOR RANGE
SENSOR STATE Description of State set up
OHeat & O2
Heat 0 Medium Optical + A1 Heat*2
l
8/10/2019 Gent by Honeywell- A6 Installers Guide
http://slidepdf.com/reader/full/gent-by-honeywell-a6-installers-guide 8/16
F I R E D E T E C T I O N S Y S T E M S
13
SMOKE detector under pitched roofs
FOR LESS THAN 600mm TREAT AS FLAT CEILING
UP TO600mm
DEEPERTHAN
600mm
8/10/2019 Gent by Honeywell- A6 Installers Guide
http://slidepdf.com/reader/full/gent-by-honeywell-a6-installers-guide 9/16
F I R E D E T E C T I O N S Y S T E M S
15
Ceilings with multiple joists
PERMITTED SPACINGDETAILED IN TABLEBELOW
RATIO BETWEENCEILING HEIGHTSvs BEAM DEPTH &
MAXIMUM SPACING‘M’
M
8/10/2019 Gent by Honeywell- A6 Installers Guide
http://slidepdf.com/reader/full/gent-by-honeywell-a6-installers-guide 10/16
F I R E D E T E C T I O N S Y S T E M S
17
Ceilings with other obstructions or Air Handling units etc
AT LEAST1m FROM
AN AIRHANDLING
UNIT
FREE500mmSPACEBELOW
DETECTOR
STORAGERACKS
8/10/2019 Gent by Honeywell- A6 Installers Guide
http://slidepdf.com/reader/full/gent-by-honeywell-a6-installers-guide 11/16
Siting of BEAM detectors
ONE BEAM DETECTOR COVERS 17.5m USING EXTRA %ALLOWED DUE TO ANGLE OF ROOF
F I R E D E T E C T I O N S Y S T E M S
19
m
1.25m
600mm25º
8/10/2019 Gent by Honeywell- A6 Installers Guide
http://slidepdf.com/reader/full/gent-by-honeywell-a6-installers-guide 12/16
F I R E D E T E C T I O N S Y S T E M S
21
Audible alarm levels within buildings are generally accepted as 65dB(A) throughout. However,the new standard does accept that in certain locations this can be as low as 60dB(A). This allowssome degree of flexibility, although in general the majority of a site must achieve 65dB(A) or
greater to be compliant.
The drawing below illustrates the areas where 60dB(A)is permitted
656565
65
6565
65
6560
60
60
60
65
65
ENCLOSURE OFLESS THAN 60sqm
MINIMUM OF60dB(A)
AREAS OF LESS THAN1m2 OF HABITABLESPACENO MINIMUM
SPECIFIC POINT OFLIMITED EXTENT MAY
BE 60dB(A)
SHADED AREA 500mmFROM BOUNDARY
8/10/2019 Gent by Honeywell- A6 Installers Guide
http://slidepdf.com/reader/full/gent-by-honeywell-a6-installers-guide 13/16
F I R E D E T E C T I O N S Y S T E M S
23
Control equipment & power supplies
The Control panel itself should comply to EN54-2 and any power supply used should complyto EN54-4. Today the majority of Gent fire control panels incorporate their own battery andcharger and as long as the guidelines for loading these systems are complied with, the batteryshould be sufficient to maintain the system for a period of 24 hours with half an hour alarmload thereafter.
It is however recommended that a battery load calculation is carried out to verify the standbyperiod provided by the capacity of the battery supplied.
Irrespective of the size or type of system the control panel should be sited with the followingpoints in mind;
3 In an area of relatively low fire risk
3 On the ground floor entrance which the fire fighters will use
3 In buildings of multiple occupancy, the panel should be sited within a communal area or if
Design Stage 6
8/10/2019 Gent by Honeywell- A6 Installers Guide
http://slidepdf.com/reader/full/gent-by-honeywell-a6-installers-guide 14/16
F I R E D E T E C T I O N S Y S T E M S
25
STANDARD FIRE
RESISTING CABLE
GROUND
FLOOR
SIXTH
FLOOR
FIFTH
FLOOR
FOURTH
FLOOR
THIRD
FLOOR
SECOND
FLOOR
FIRST
FLOOR
Example of a networkedfire alarm in amulti-storey building,
ENHANCED FIRE
Example of a networkedfire alarm in amulti-storey building,
STANDARD FIRE
RESISTING CABLE
8/10/2019 Gent by Honeywell- A6 Installers Guide
http://slidepdf.com/reader/full/gent-by-honeywell-a6-installers-guide 15/16
F I R E D E T E C T I O N S Y S T E M S
27
Inspection and testing of wiring
Prior to any equipment being connected, all installed cables should be subject to a 500V dc
insulation test.These tests should show an insulation value of at least 2Mohm between conductors and
between each conductor and screen or earth.
Earth continuity tests should be carried out on all mains supply circuits as well as an earth loop
impedance in accordance with BS 7671. It is important with the Vigilon system that all earth
leads or screen cables are terminated and connected through each device.
The maximum impedance of each loop or radial circuit should be recorded to ensure it meets the
manufacturers recommendations. In the case of Vigilon this is determined by not exceeding the
recommended maximum cable lengths which for loop circuits should not be greater than 1Km
and a maximum of 100metres for any radial circuit connected on a loop powered interface.
8/10/2019 Gent by Honeywell- A6 Installers Guide
http://slidepdf.com/reader/full/gent-by-honeywell-a6-installers-guide 16/16
GENERAL APPLICATION FOR SENSOR PREFERREDOPTION OPTION 2 OPTION 3 Air extraction ducts Duct detectors Aspiration
Airport terminals Beams** state 0 O2H* state 0 Video Animal houses, stables, zoo’s etc EP heat state 0
Areas of High risk like Historic Houses Aspiration O2HCO* state 1 Radio detection Suggest ti Atria Beams** state 0 AspirationVertically Note use ‘
Battery re-charge rooms O2H* state 0 Flame
Bedroom O2H* state 0 O2H* state 8Bedroom with adjacent Bathroom O2H* state 8 O2HCO* state 0 O2HCO* state 9 Options d
see table
Bedroom with bath & or kitchen attached O2H* state 8 O2HCO* state 0 O2HCO* state 9 Options dinto bedro
Boiler room with coal or coke H* state 5 O2HCO* state 11 Boiler room clean with Gas/Oil/El ectrical source O2H* state 5 O2HCO* state 11
Cable duct ways Linear Heat Beams** state 0 Watch out Car park (enclosed) H* state 0 O2H* state 2 O2H* state 8
Changing rooms alongside showers etc O2HCO* state 9 H* state 0 Clean data processing room O2HCO* state 1 O2H* state 1 Aspiration Watch for
Cold rooms Aspiration Use heat state 0 but avoid fitting near open do
Corridors, stairwells or internal passageways O2H* state 0 Electrical switch or plant rooms O2HCO* state 0 O2H* state 0
Enclosures open to air EP Heat EP Flame
Flour Mills O2HCO* state 9 Flame detector Garage work areas H* state 0 O2HCO* state 9 O2H* state 2 Suggest t Kitchen large commercial H* state 6 O2HCO* state 11 Suggesttim
Kitchen small domestic O2H* state 2 H* state 13 Laundry room large, high ceiling Beams** state 0 O2HCO* state 9 Flame Consider l
Laundry room small, low ceiling O2HCO* state 9 H* state 13
Laundry Storage room O2HCO* state 9 H* state 0 Libraries O2HCO* state 0 Aspiration O2H* state 0
Normal office or working area O2H* state 0 Open high ceilings in Church’s or Cathedrals Beams** state 0 Flames Watch nu
Prison / secure accommodation O2HCO* state 2 O2HCO* state 9 Restaurant area O2H* state 0 H* state 0 Suggest ti
Retail shop High ceilings (e.g. B&Q) Beam state 0 Retail shop Normal ceiling height O2H* state 0 O2HCO* state 0
Room with gas fire O2H* state 0 O2HCO* state 0
Room with Open wood/coal fire O2H* state 2 H* state 0 Scientific Laboratories O2HCO* state 0 Wide varia
Spray booths - spray shops Flame H* state 0 Linear Heat Watch out Steam rooms, sauna or shower areas EP heat O2HCO* state 9
Store rooms O2HCO* state 0 Subject to Tunnels Flame Linear Heat
Warehouse Beams** state 0 O2H* state 0 Option 1 w Warehouse loading bay H* state 0 Flame O2H* state 0
X-ray or other high EMC areas Aspiration O2HCO* state 0 Ignore use
F I R E D E T E C T I O N S Y S T E M S
29
Documentation
On completion of commissioning and usertraining all documentation will have to becollected and handed to the client or theirrepresentative. This will include;
3 Design,InstallationandCommissioningcertificates G1, G2, & G3*
3 Cable and insulation resistance test records
3 “As fitted” drawings of the final installation,including cable run details
3 Product manuals and user instructions
3 System log book
3 A copy of the fire plan documentationagainst which the commissioning engineerprogrammed the system
3 The designer’s specification and a written listof agreed Variations
* For existing systems the G5 Verification Certificate couldreplace G1, G2 & G3.
Note* Versions may include Speech, Sound and strobe or mixture of all features. ** Beams state dependa
SENSOR APPLICATION GUIDE This guide is aimed at providing advice on the most suitable type of sensor fodepending on the particular application and if there are any doubts we suggest you consult one of our field sales a
TABLE 1