% PERCENT ø DIAMETER ∆T CHANGE OF TEMPERATURE AFF ABOVE FINISHED FLOOR AMP AMPERE APD AIR PRESSURE DROP BTU/H BRITISH THERMAL UNITS PER HOUR CAP CAPACITY CFM CUBIC FEET PER MINUTE CUH-x CABINET UNIT HEATER DESIGNATION D CONDENSATE DRAIN DALT DUCT AIR LEAKAGE TESTING DB DRY BULB db DECIBELS DDC DIRECT DIGITAL CONTROL DN DOWN DP DIFFERENTIAL PRESSURE DX DIRECT EXPANSION EA ENTERING AIR EA EXHAUST AIR EAT ENTERING AIR TEMPERATURE EER ENERGY EFFICIENCY RATIO EF-x EXHAUST FAN DESIGNATION ESP EXTERNAL STATIC PRESSURE °F DEGREES FAHRENHEIT FLA FULL LOAD AMPS FPM FEET PER MINUTE HP HORSEPOWER HZ HERTZ IN INCH/INCHES IU-x INDOOR (SPLIT SYSTEM A/C) UNIT DESIGNATION kA KILO AMPS INTERRUPTING CAPACITY KW KILOWATTS LAT LEAVING AIR TEMPERATURE LBS POUNDS MAX MAXIMUM MBH 1000 BRITISH THERMAL UNITS PER HOUR MCA MINIMUM CIRCUIT AMPS MIN MINIMUM MOP MAXIMUM OVER CURRENT PROTECTION NC NOISE CRITERIA NO NUMBER NTS NOT TO SCALE OA OUTSIDE AIR OU-x OUTDOOR (SPLIT SYSTEM A/C) UNIT DESIGNATION ∆P PRESSURE DIFFERENTIAL PD PRESSURE DROP PH PHASE RA RETURN AIR RPM REVOLUTIONS PER MINUTE RG REFRIGERANT GAS RL REFRIGERANT LIQUID RTU-x ROOFTOP UNIT DESIGNATION SA SUPPLY AIR SCCR SHORT CIRCUIT RATING SD SMOKE DETECTOR SENS SENSIBLE SP STATIC PRESSURE TYP TYPICAL UH-x UNIT HEATER DESIGNATION UL UNDERWRITERS LABORATORIES V VOLTS VAV-x-x VARIABLE AIR VOLUME BOX DESIGNATION VD VOLUME DAMPER VFD VARIABLE FREQUENCY DRIVE W WATTS WB WET BULB THE MECHANICAL SYSTEM HAS BEEN DESIGNED IN ACCORDANCE WITH THE 2012 VIRGINIA UNIFORM STATEWIDE BUILDING CODE. COORDINATE LOCATION OF ALL DUCTWORK, SUPPLY AND RETURN DEVICES, EXHAUST FANS, THERMOSTATS AND OTHER WALL OR CEILING MOUNTED EQUIPMENT WITH REFLECTED PLANS, LIGHT FIXTURES, SPRINKLER SYSTEMS AND ACCESSORIES INSTALLED BY OTHER TRADES SO AS TO PRESENT A NEAT AND ATTRACTIVE INSTALLATION THROUGHOUT THE BUILDING. ALL DUCTWORK SHALL BE CONCEALED UNLESS OTHERWISE NOTED. ARRANGE DUCTWORK PARTICULARLY ABOVE CEILING AS REQUIRED TO CLEAR STRUCTURE, CONDUIT, LIGHTS, ETC., ALLOWING SPACE FOR HANGERS, INSULATION, ETC. DUCT SIZES SHOWN ARE INSIDE FREE AREA DIMENSIONS. REFER TO ARCHITECTURAL DRAWINGS AND LIFE SAFETY PLANS FOR ALL RATED CONDITIONS. MAINTAIN PROPER CLEARANCES PER ELECTRICAL CODE ON ALL VAV BOXES AND OTHER EQUIPMENT. COORDINATE WITH ALL TRADES TO ENSURE CLEARANCES ARE NOT OBSTRUCTED. INSTALL ALL VAV BOXES BETWEEN 6 INCHES MINIMUM AND 24 INCHES MAXIMUM ABOVE CEILING. FINAL LOCATION OF SPACE THERMOSTATS AND SENSORS SHALL BE APPROVED BY ARCHITECT. INSTALL ALL WALL MOUNTED NON-ADJUSTABLE SENSORS AT 5'-0" FROM FINISHED FLOOR TO TOP OF SENSOR. ADJUSTABLE DEVICE SHALL BE INSTALLED 4'-0' ABOVE FINISHED FLOOR. ALL ROUND BRANCH DUCTS TO DIFFUSERS SHALL MATCH NECK SIZES SHOWN ON SCHEDULE, UNLESS OTHERWISE NOTED. ALL DIFFUSERS, GRILLES AND REGISTERS SHALL BE SIZED TO HAVE A MINIMUM FREE AREA OF 70% AND MEET PERFORMANCE CRITERIA SCHEDULED. PROVIDE A CONTINUOUS RETURN AIR PATH FROM SPACE CEILING RETURN PLENUMS TO THEIR ASSOCIATED ROOFTOP UNIT. IN SPACES HAVING WALLS THAT ARE CONTINUOUS TO DECK, AND FOR WHICH NO TRANSFER DUCT HAS BEEN INDICATED, PROVIDE SLEEVED WALL OPENING WITH TRANSFER "L" DUCT SIZED AT 500 FPM. INDICATED MANUFACTURER'S ARE FOR BASIS OF DESIGN ONLY. ALTERNATE MANUFACTURER'S ARE ALLOWED AS APPROVED. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. A 100 RETURN/EXHAUST GRILLE SUPPLY DIFFUSER DUCTWORK WITH TRANSITION RECTANGULAR DUCT ELBOW WITH TURNING VANES ROUND OR RADIUS DUCT ELBOW 90º RECTANGULAR DUCT ELBOW - TURN UP 90º RECTANGULAR DUCT ELBOW - TURN DOWN 90º ROUND DUCT ELBOW - TURN UP 90º ROUND DUCT ELBOW - TURN DOWN DIFFUSER, REGISTER, AND GRILLE CFM AS INDICATED NEW WORK NOTE VOLUME DAMPER SMOKE DETECTOR LOCATION SD 3/4" DOOR UNDERCUT THERMOSTAT OR TEMPERATURE SENSOR T ROOF MOUNTED EXHAUST FAN D DRAIN PIPING ROUND DUCT ø DIRECTION OF AIR FLOW LINEAR DIFFUSER X FLEXIBLE AIR DUCT TRANSFER DUCT, SIZE AS INDICATED AD DUCT ACCESS DOOR N I G N E L A N O I S S E F O R P R E E Lic. No. 023349 KEVIN D. ALLEN A I N I L T H O F V I R G C O M M O N W E A SHEET NO. J O B N O . : S C A L E : D A T E : A P P R O V E D : C H E C K E D : D R A W N : A S N O T E D R E V I S I O N S : SHT. OF THOMPSON Consulting Engineers 22 ENTERPRISE PARKWAY TELEPHONE: (757) 599-4415 PROJECT NUMBER: 17041 FAX: (757) 599-4113 HAMPTON, VA 23666 104 03-07-18 3/6/2018 3:10:00 PM M-001 GENERAL NOTES, LEGEND AND ABBREVIATIONS ADDITION TO HICKORY MIDDLE SCHOOL 1997 HAWK BLVD, CHESAPEAKE VA 23322 JAR RCP MWT 03/07/18 17005 100% FINAL SUBMITTAL 82 ABBREVIATIONS ABBREVIATIONS GENERAL NOTES GENERAL NOTES LEGEND LEGEND

GENERAL NOTES ABBREVIATIONS LEGEND · PDF filertu-x rooftop unit designation ... all round branch ducts to diffusers shall match neck sizes shown on schedule, ... meet performance

  • Upload
    doannhi

  • View
    217

  • Download
    0

Embed Size (px)

Citation preview

Page 1: GENERAL NOTES ABBREVIATIONS LEGEND · PDF filertu-x rooftop unit designation ... all round branch ducts to diffusers shall match neck sizes shown on schedule, ... meet performance

% PERCENT

ø DIAMETER

∆T CHANGE OF TEMPERATURE

AFF ABOVE FINISHED FLOOR

AMP AMPERE

APD AIR PRESSURE DROP

BTU/H BRITISH THERMAL UNITS PER HOUR

CAP CAPACITY

CFM CUBIC FEET PER MINUTE

CUH-x CABINET UNIT HEATER DESIGNATION

D CONDENSATE DRAIN

DALT DUCT AIR LEAKAGE TESTING

DB DRY BULB

db DECIBELS

DDC DIRECT DIGITAL CONTROL

DN DOWN

DP DIFFERENTIAL PRESSURE

DX DIRECT EXPANSION

EA ENTERING AIR

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EER ENERGY EFFICIENCY RATIO

EF-x EXHAUST FAN DESIGNATION

ESP EXTERNAL STATIC PRESSURE

°F DEGREES FAHRENHEIT

FLA FULL LOAD AMPS

FPM FEET PER MINUTE

HP HORSEPOWER

HZ HERTZ

IN INCH/INCHES

IU-x INDOOR (SPLIT SYSTEM A/C) UNIT DESIGNATION

kA KILO AMPS INTERRUPTING CAPACITY

KW KILOWATTS

LAT LEAVING AIR TEMPERATURE

LBS POUNDS

MAX MAXIMUM

MBH 1000 BRITISH THERMAL UNITS PER HOUR

MCA MINIMUM CIRCUIT AMPS

MIN MINIMUM

MOP MAXIMUM OVER CURRENT PROTECTION

NC NOISE CRITERIA

NO NUMBER

NTS NOT TO SCALE

OA OUTSIDE AIR

OU-x OUTDOOR (SPLIT SYSTEM A/C) UNIT DESIGNATION

∆P PRESSURE DIFFERENTIAL

PD PRESSURE DROP

PH PHASE

RA RETURN AIR

RPM REVOLUTIONS PER MINUTE

RG REFRIGERANT GAS

RL REFRIGERANT LIQUID

RTU-x ROOFTOP UNIT DESIGNATION

SA SUPPLY AIR

SCCR SHORT CIRCUIT RATING

SD SMOKE DETECTOR

SENS SENSIBLE

SP STATIC PRESSURE

TYP TYPICAL

UH-x UNIT HEATER DESIGNATION

UL UNDERWRITERS LABORATORIES

V VOLTS

VAV-x-x VARIABLE AIR VOLUME BOX DESIGNATION

VD VOLUME DAMPER

VFD VARIABLE FREQUENCY DRIVE

W WATTS

WB WET BULB

THE MECHANICAL SYSTEM HAS BEEN DESIGNED IN ACCORDANCE WITH THE 2012 VIRGINIA UNIFORMSTATEWIDE BUILDING CODE.

COORDINATE LOCATION OF ALL DUCTWORK, SUPPLY AND RETURN DEVICES, EXHAUST FANS,THERMOSTATS AND OTHER WALL OR CEILING MOUNTED EQUIPMENT WITH REFLECTED PLANS, LIGHTFIXTURES, SPRINKLER SYSTEMS AND ACCESSORIES INSTALLED BY OTHER TRADES SO AS TO PRESENTA NEAT AND ATTRACTIVE INSTALLATION THROUGHOUT THE BUILDING.

ALL DUCTWORK SHALL BE CONCEALED UNLESS OTHERWISE NOTED.

ARRANGE DUCTWORK PARTICULARLY ABOVE CEILING AS REQUIRED TO CLEAR STRUCTURE, CONDUIT,LIGHTS, ETC., ALLOWING SPACE FOR HANGERS, INSULATION, ETC.

DUCT SIZES SHOWN ARE INSIDE FREE AREA DIMENSIONS.

REFER TO ARCHITECTURAL DRAWINGS AND LIFE SAFETY PLANS FOR ALL RATED CONDITIONS.

MAINTAIN PROPER CLEARANCES PER ELECTRICAL CODE ON ALL VAV BOXES AND OTHER EQUIPMENT.COORDINATE WITH ALL TRADES TO ENSURE CLEARANCES ARE NOT OBSTRUCTED.

INSTALL ALL VAV BOXES BETWEEN 6 INCHES MINIMUM AND 24 INCHES MAXIMUM ABOVE CEILING.

FINAL LOCATION OF SPACE THERMOSTATS AND SENSORS SHALL BE APPROVED BY ARCHITECT.

INSTALL ALL WALL MOUNTED NON-ADJUSTABLE SENSORS AT 5'-0" FROM FINISHED FLOOR TO TOP OFSENSOR. ADJUSTABLE DEVICE SHALL BE INSTALLED 4'-0' ABOVE FINISHED FLOOR.

ALL ROUND BRANCH DUCTS TO DIFFUSERS SHALL MATCH NECK SIZES SHOWN ON SCHEDULE, UNLESSOTHERWISE NOTED.

ALL DIFFUSERS, GRILLES AND REGISTERS SHALL BE SIZED TO HAVE A MINIMUM FREE AREA OF 70% ANDMEET PERFORMANCE CRITERIA SCHEDULED.

PROVIDE A CONTINUOUS RETURN AIR PATH FROM SPACE CEILING RETURN PLENUMS TO THEIRASSOCIATED ROOFTOP UNIT. IN SPACES HAVING WALLS THAT ARE CONTINUOUS TO DECK, AND FORWHICH NO TRANSFER DUCT HAS BEEN INDICATED, PROVIDE SLEEVED WALL OPENING WITH TRANSFER"L" DUCT SIZED AT 500 FPM.

INDICATED MANUFACTURER'S ARE FOR BASIS OF DESIGN ONLY. ALTERNATE MANUFACTURER'S AREALLOWED AS APPROVED.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

A

100

RETURN/EXHAUST GRILLE

SUPPLY DIFFUSER

DUCTWORK WITH TRANSITION

RECTANGULAR DUCT ELBOW WITH TURNING VANES

ROUND OR RADIUS DUCT ELBOW

90º RECTANGULAR DUCT ELBOW - TURN UP

90º RECTANGULAR DUCT ELBOW - TURN DOWN

90º ROUND DUCT ELBOW - TURN UP

90º ROUND DUCT ELBOW - TURN DOWN

DIFFUSER, REGISTER, AND GRILLE CFM AS INDICATED

NEW WORK NOTE

VOLUME DAMPER

SMOKE DETECTOR LOCATIONSD

3/4" DOOR UNDERCUT

THERMOSTAT OR TEMPERATURE SENSORT

ROOF MOUNTED EXHAUST FAN

D DRAIN PIPING

ROUND DUCTø

DIRECTION OF AIR FLOW

LINEAR DIFFUSER

X

FLEXIBLE AIR DUCT

TRANSFER DUCT, SIZE AS INDICATED

AD DUCT ACCESS DOOR

NIGNELANOISS

E

FO

RP

RE

E

Lic. No. 023349

KEVIN D. ALLEN AI

NI

LTH OFV

IRG

COMMON

WEA

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 3

:10:0

0 P

M M-001

GE

NE

RA

L N

OT

ES

, LE

GE

ND

AN

DA

BB

RE

VIA

TIO

NS

AD

DIT

ION

TO

HIC

KO

RY

MID

DL

E S

CH

OO

L

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

JA

R

RC

P

MW

T

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

82

ABBREVIATIONSABBREVIATIONSGENERAL NOTESGENERAL NOTES LEGENDLEGEND

Page 2: GENERAL NOTES ABBREVIATIONS LEGEND · PDF filertu-x rooftop unit designation ... all round branch ducts to diffusers shall match neck sizes shown on schedule, ... meet performance

NIGNELANOISS

E

FO

RP

RE

E

Lic. No. 023349

KEVIN D. ALLEN AI

NI

LTH OFV

IRG

COMMON

WEA

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 3

:10:0

0 P

M M-002

ME

CH

AN

ICA

L S

CH

ED

ULE

SA

DD

ITIO

N T

O H

ICK

OR

Y M

IDD

LE

SC

HO

OL

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

JA

R

RC

P

MW

T

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

83

STYLEUNITNO.

HORIZONTAL DISCHARGE

CFM

400

CAPACITY(MBH)

11,200

KW

3.3

ELECTRIC HEATING COIL

V

277

PH

1

AMPS

11.9

SELECTION BASEDON "MARKEL"

GIG5103N

REMARKS

REMARKS:

UH-1

ELECTRIC UNIT HEATER SCHEDULE

PROVIDE WITH INTEGRAL THERMOSTAT AND FACTORY WIRED DISCONNECT SWITCH.

1 2

1 PROVIDE HANGING BRACKET.2

MARK

A

GRILLE, REGISTER & DIFFUSER SCHEDULE

NECKSIZE

6"ø

FACESIZE

12" x 12"LOUVERED FACE ADJUSTABLE

CEILING DIFFUSER

DESCRIPTION

STEEL

MATERIAL

WHITE

FINISH

NO

VOLUMEDAMPER

SQUARE

SHAPE

0.1"

MAXIMUM P

25

MAXIMUMNC

SELECTIONBASED ON

"PRICE"

SCDA

REMARKS

B 8"ø 12" x 12" STEEL WHITE NO SQUARE 0.1" 25 SCDA

C 10"ø 24" x 24" STEEL WHITE NO SQUARE 0.1" 25 SCDA

D 12"ø 24" x 24" STEEL WHITE NO SQUARE 0.1" 25 SCDA

E 14"ø 24" x 24" STEEL WHITE NO SQUARE 0.1" 25 SCDA

F 16"ø 24" x 24" STEEL WHITE NO SQUARE 0.1" 25 SCDA

REMARKS: REFER TO ARCHITECT'S REFLECTED CEILING PLAN FOR CEILING TYPES. FOR ACOUSTICCEILING, PROVIDE WITH 24" x 24" PANEL SUITABLE FOR MOUNTING IN LAY-IN GRID. FORDRYWALL CEILING, PROVIDE WITH SMALL FACE AND SURFACE MOUNT FRAME.

PROVIDE 3-CONE CONFIGUARION.

LOUVERED FACE ADJUSTABLECEILING DIFFUSER

LOUVERED FACE ADJUSTABLECEILING DIFFUSER

LOUVERED FACE ADJUSTABLECEILING DIFFUSER

LOUVERED FACE ADJUSTABLECEILING DIFFUSER

LOUVERED FACE ADJUSTABLECEILING DIFFUSER

Z 8" x 8" 10" x 10" STEEL WHITE NO SQUARE 0.1" 25 530

Y 12" x 12" 14" x 14" STEEL WHITE NO SQUARE 0.1" 25 530

X 18" x 18" STEEL WHITE NO SQUARE 0.1" 25 53016" x 16"

W 24" x 24" STEEL WHITE NO SQUARE 0.1" 25 53022" x 22"

CEILING RETURN OR EXHAUST GRILLE45° DEFLECTION, 3/4" SPACING

PROVIDE 4-CONE CONFIGUARION.

CEILING RETURN OR EXHAUST GRILLE45° DEFLECTION, 3/4" SPACING

CEILING RETURN OR EXHAUST GRILLE45° DEFLECTION, 3/4" SPACING

CEILING RETURN OR EXHAUST GRILLE45° DEFLECTION, 3/4" SPACING

G 8"ø 48" x 4" ALUMINUM WHITE YES RECTANGULAR 0.1" 25 SDS100LINEAR DIFFUSER

1 2

1 2

1 3

1 3

1 3

1 3

1

1

1

1

1

2

3

1

4

PROVIDE 4-SLOT DIFFUSERAND PLENUM BOX.

4

UNITNO SUPPLY

CFMRPM

ESP(IN)

HP

SUPPLY FAN DATA EXHAUST FAN DATA

RPM HPESP(IN)

EXHAUSTCFM

ENERGY WHEEL SUPPLY AIR DATA

COOLING HEATING

OACFM

EAT LAT EAT LAT

DB(°F)

WB(°F)

DB(°F)

DB(°F)

DB(°F)

WB(°F)

WB(°F)

WB(°F)

APD(IN)

ENERGY WHEEL EXHAUST AIR DATA

COOLING HEATING

EACFM

EAT LAT EAT LAT

DB(°F)

WB(°F)

DB(°F)

DB(°F)

DB(°F)

WB(°F)

WB(°F)

WB(°F)

APD(IN)

ENERGY WHEELMOTOR DATA

HP V PH TOTAL(MBH)

SENS(MBH)

CAPACITY

DB(°F)

EAT

WB(°F)

DB(°F)

WB(°F)

LATNO. OFCOMP

INPUT(MBH)

OUTPUT(MBH)

EATDB(°F)

LATDB(°F)

DX COOLING COIL PERFORMANCE GAS HEATING COIL PERFORMANCE ELECTRICA DATA

V PH MOP

UNITWEIGHT

(LBS)

SELECTIONBASED ON"TRANE"

REMARKS

12,300RTU-8 1400 3.0 20 9,830 600 1.0 5 6485 95 78 80 68 15 12 54 42 76 65 91 75 68 50 25 210.21 6235 0.23 1/4 480 3 608 377 80 68 53 51 4 500 400 54 91 480 3 150 12,475 SFHLF554 1 2

REMARKS: PROVIDE UNIT WITH MERV 8 FILTERS.

PROVIDE WITH FACTORY MOUNTED AND WIRED VARIABLE FREQUENCYDRIVES FOR SUPPLY AND EXHAUST FANS.

1

2

PROVIDE WITH DOWN DISCHARGE CONFIGURATION.

PROVIDE UNIT WITH R-410A REFRIGERANT.

3

4

SEPARATE POWER FEED REQUIRED FOR ENERGY WHEEL.PROVIDE WITH SINGLE POINT POWER CONNECTION.

PROVIDE CONDENSATE PAN SWITCH AND ALARM.

5

SCCR(kA)

65

PACKAGED ROOFTOP AIR CONDITIONING UNIT SCHEDULE

FUEL TYPE

NATURAL GAS 3 4 5 6 7 8

6

PROVIDE FACTORY MOUNTED AIRFLOW MEASURING SENSORS FOR OUTDOOR AIR MEASUREMENT.

PROVIDE ISOLATION RAILS AND ACOUSTICAL PACKAGE BY MASON INDUSTRIES (NO SUBSTITUTIONS).REFER TO SPECIFICATION 230500.

7

8

TYPEUNITNO.

EF-23 POWER ROOF VENTILATOR

ARRANGEMENT

DOWNBLAST

WHEEL DRIVE

BELT

CFM

420

EXHAUST FAN SCHEDULE

ESP(IN.)

0.25

FAN RPM

1269

TIPSPEED(FPM)

3716 1/6

HP (W)

120

V

1

PH

MOTOR DATA CONTROLMETHOD

DDC

MAXSONES

6.6

SELECTIONBASED ON

"GREENHECK"

GB-081-6

REMARKS

BACKWARDS INCLINEDCENTRIFUGAL

REMARKS: PROVIDE INTEGRAL DISCONNECT SWITCH.

EF-24 690 0.35 1677 4912 1/4 11.1

EF-25 260 0.25 1416 4148 1/6 7.7

POWER ROOF VENTILATOR DOWNBLAST BELT 120 1 DDC GB-081-4BACKWARDS INCLINED

CENTRIFUGAL

POWER ROOF VENTILATOR DOWNBLAST BELT 120 1 DDC GB-071-6BACKWARDS INCLINED

CENTRIFUGAL

1

1

1

1

REFER TO SPECIFICATIONS FOR ADDITIONAL OPTIONS.2

2

2

2

UNITNO.

SERIES FAN POWERED VAV BOX SCHEDULE

INLET VALVE

MAXCFM

740

MINCFM

390

SIZE(IN.)

8"

CFM

0.35

FAN DATA

ESP(IN.)

20.5

MBH

ELECTRIC HEATING COIL DATA SELECTIONBASED ON"TRANE"

VSEF

REMARKS

REMARKS: PROVIDE WITH 1" FOIL FACED INSULATION.

PROVIDE WITH 2 STAGE CONTACTOR WITH PULSE WIDTH MODULATION.

480

VEAT(°F)

65.5

LAT(°F)

91.08-1 3

PH

715 375 8" 0.35 20.5 VSEF65.5 91.9

715 8" 0.35 20.5 VSEF65.5 91.9

710 8" 0.35 20.5 VSEF65.4 92.0

670 355 8" 0.35 20.5 VSEF65.5 93.7

730 385 8" 0.35 20.5 VSEF65.5 91.3

730 385 8" 0.35 20.5 VSEF65.5 91.3

400 210 8" 0.35 23.9 VSEF65.5 93.0

710 8" 0.35 20.5 VSEF65.5 92.1

740 390 8" 0.35 20.5 VSEF65.5 91.0

675 355 8" 0.35 20.5 VSEF65.5 93.5

670 355 8" 0.35 20.5 VSEF65.5 93.7

680 360 8" 0.35 20.5 VSEF65.5 93.3

600 320 8" 0.35 17.1 VSEF65.0 91.2

885 470 8" 0.35 27.3 VSEF65.5 94.0

400 210 8" 0.35 23.9 VSEF65.5 93.0

8-2

8-3

8-4

8-5

8-6

8-7

8-8

8-9

8-10

8-11

8-12

8-13

8-14

8-15

8-16

MOTOR DATA

V

277

HP

1/36.0

KW

6.0

6.0

6.0

6.0

6.0

6.0

7.0

6.0

6.0

6.0

6.0

6.0

5.0

8.0

7.0

SIZE

03SQ

03SQ

03SQ

03SQ

03SQ

03SQ

03SQ

03SQ

03SQ

03SQ

03SQ

03SQ

03SQ

02SQ

03SQ

03SQ

480 3 277 1/3

480 3 277 1/3

480 3 277 1/3

480 3 277 1/3

480 3 277 1/3

480 3 277 1/3

480 3 277 1/3

480 3 277 1/3

480 3 277 1/3

480 3 277 1/3

480 3 277 1/3

480 3 277 1/3

480 3 277 1/8

480 3 277 1/3

480 3 277 1/3

PROVIDE WITH ECM MOTOR.

740

715

715

710

670

730

730

800

710

740

675

670

680

600

885

800

200 105 4" 0.35 5.1 VSEF65.5 85.78-17 1.502SQ 480 3 277 1/8200

665 350 8" 0.35 15.4 VSEF65.5 86.88-18 4.502SQ 480 3 277 1/8665

665 350 8" 0.35 15.4 VSEF65.5 86.88-19 4.502SQ 480 3 277 1/8665

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1

2

3

375

375

375

STYLEUNITNO.

VERTICAL DISCHARGE -RECESSED

CFM

250

CAPACITY(MBH)

10,239

KW

5

ELECTRIC HEATING COIL

V

277

PH

3

AMPS

7.8

SELECTION BASEDON "MARKEL"

633D05

REMARKS

REMARKS:

CUH-1

CABINET UNIT HEATER SCHEDULE

PROVIDE WITH FACTORY WIRED DISCONNECT SWITCH.

CUH-2

UNIT HEATER SHALL BE CONTROLLED THROUGH THE DDC.

VERTICAL DISCHARGE -RECESSED 250 10,239 5 277 633D05

CUH-3HORIZONTAL DISCHARGE -

DUCTED 250 10,239 5 277 633D05

1 2

1 2

2

1

1 2

3 7.8

3 7.8

UNITNO.

IU-1

SPLIT SYSTEM AIR CONDITIONING UNIT SCHEDULE

CFM

320

DB (°F)

80.0

WB (°F)

67.0

EAT SELECTION BASEDON "MITSUBISHI"

PKA-A12HA6

MCA

1

FLA

0.33

ELECTRICAL

VOLTS

208

PH

1

COOLING(MBH)

12.0

INDOOR UNITNOMINALCAPACITY

UNITNO.

OU-1

DB (°F)

95.0

WB (°F)

78.0

EAT SELECTION BASEDON "MITSUBISHI"

PUY-A12NHA6

MCA

13

MOP

15

ELECTRICAL

VOLTS

208

PH

1

OPERATINGWEIGHT (LBS)

82

REMARKS

OUTDOOR UNIT

REMARKS: WALL MOUNTED INDOOR UNIT, COOLING ONLY.

MOUNT INDOOR UNIT 7'-4" AFF TO BOTTOM OF UNIT.

PROVIDE WITH WALL MOUNTED WIRED CONTROLLER.

PROVIDE WITH CONDENSATE PUMP "LITTLEGIANT" MODEL EC-OP-K OR EQUAL.

PROVIDE INDOOR UNIT WITH 14/3 CONDUCTOR AND 3-POLEDISCONNECT SWITCH BY UNIT MANUFACTURER.

POWER & CONTROL WIRING TO INDOOR UNIT SHALL BE SERVED FROMOUTDOOR UNIT. WIRING BETWEEN UNITS BY DIV 23.

1 2 3 4 5 6

1

2

3

4

5

6

Page 3: GENERAL NOTES ABBREVIATIONS LEGEND · PDF filertu-x rooftop unit designation ... all round branch ducts to diffusers shall match neck sizes shown on schedule, ... meet performance

VAV-8-1

VAV-8-2

CUH-1

VAV-8-3

VAV-8-5

VAV-8-9

109

105

104

103

102

123

106

108

107B

T

T

T

T

T

VAV-8-4

VAV-8-8

EF-24 ONROOF

14"/14"

12"/12" 10"/10"

B

185 B

185

B

185

B

185

12"ø

16"/14"

A

100

B

180

B

175

B

180

B

180

B

175

B

180

B

180

B

180

B

175

B

175

B

180

B

180

B

175

B

175

B

180

B

180

2

2

2

2

2

2

2

12"/12"

10"/10"

12"/12"

10"/10"

12"/12" 10"/10"

14"/14"

14"/14"

14"/14"

14"/14"10"/10"

12"ø

12"ø

W

W

W

W

G

100

G

100 10"/8"

8"ø

8"ø

1

Y

200

Z

70

B

140

12"/10"

10"/8"

6"/6"

8"/8"

W

420

W

B

185

B

185

B

18514"/14"

CUH-3

A

100

T

T

CUH-3

G

105

G

250

10"/8"

10"/8"

W

T

C

225

16"/14"

14"/14"AREA A

AREA B

12"ø

12"ø

12"ø

12"ø

EXISTINGBUILDING

NEWADDITION

8"ø

W

AD

T CUH-1

12"/12"

10"/10"

NIGNELANOISS

E

FO

RP

RE

E

Lic. No. 023349

KEVIN D. ALLEN AI

NI

LTH OFV

IRG

COMMON

WEA

0' 1' 5' 10' 20'1/8" = 1'-0"

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

GRAPHIC SCALE

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 3

:10:5

0 P

M M-101

FLO

OR

PLA

N -

AR

EA

A -

ME

CH

AN

ICA

LA

DD

ITIO

N T

O H

ICK

OR

Y M

IDD

LE

SC

HO

OL

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

JA

R

RC

P

MW

T

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

84

1/8" = 1'-0"

FLOOR PLAN - AREA A - MECHANICALFLOOR PLAN - AREA A - MECHANICALKEY PLAN

N.T.S.

A

NEW WORK NOTES

NO. DESCRIPTION

1 ROUTE 14"x14" DUCT UP TO EF-24 ON ROOF.

2 MAINTAIN MANUFACTURER'S RECOMMENDED SERVICEAREA FOR ALL VAV TERMINAL UNITS. COORDINATECLEARANCE REQUIREMENTS WITH OTHER TRADES.REFER TO VAV BOX INSTALLATION DETAIL ON DRAWINGM-301.

Page 4: GENERAL NOTES ABBREVIATIONS LEGEND · PDF filertu-x rooftop unit designation ... all round branch ducts to diffusers shall match neck sizes shown on schedule, ... meet performance

VAV-8-10

VAV-8-6

VAV-8-7

VAV-8-11

VAV-8-13

VAV-8-12

VAV-8-14

VAV-8-15

CUH-2

123

122

119

118

116

115

114

124

117

113

112

111B

120

107B

RTU-8ON ROOF

EF-23 ONROOF

T

T

T

T

T

T

T

UH-1

EF-25 ONROOF

VAV-8-16

T

VAV-8-18

VAV-8-19

6

6

SD

SD

55

46"/22"

46"/22"52"/30" UP

C

225

C

220

C

220

C

220

B

150

B

150B

150

B

150

B

170

B

170

B

170

B

170

B

170

B

170

B

170

B

165

B

185

C

225

C

220

B

180

B

180

B

185

B

185

B

180

B

185

B

185

B

180

C

225

C

220

C

225

A

100

A

100

G

100

G

100

2

2

2

2

2

2

2

2

2

2

2

T

W

14"/12"

10"/12"

16"/12"

14"/14"

12"/12"

10"/10"

W

14"/14"

14"/14"

12"/12"

10"/10"

10"/10"

12"/12"

W

W

8"ø

8"ø

10"/8"

10"/10"

12"/12"

10"/12"

W

14"/14"

14"/14"

12"/12"

10"/10"10"/10"

12"/12"

W

W

G

105

G

105

G

105

G

105

G

105

G

105

G

105

G

105

8"ø

8"ø

10"ø

10"ø

10"ø

10"ø

8"ø

8"ø

10"/12" Z

12"/12"

10"/10"10"/10"

12"/12"

14"/14"

16"/14"

B

140

Z

130

Z

130 Z

420

12"/10"

IU-1

2

VAV-8-17

B

200

10"/8"

8"/8"

Z

OU-1ON ROOF

1/4" RL,1/2" RG UP

8"ø

T

AREA A

AREA B

EX

IST

ING

BU

ILD

ING

NE

WA

DD

ITIO

N

W

8"ø

12"ø16"/14"

12"ø

12"ø12"ø

12"ø

12"ø12"ø

12"ø

12"ø

12"ø

12"ø

AD

T

CUH-2

12"ø

16"/14"

16"/14"

12

12

W

W

16"/14"

13

W

12

1

M-302

2

M-302

12"ø

8"/8"

NIGNELANOISS

E

FO

RP

RE

E

Lic. No. 023349

KEVIN D. ALLEN AI

NI

LTH OFV

IRG

COMMON

WEA

0' 1' 5' 10' 20'1/8" = 1'-0"

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

GRAPHIC SCALE

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 3

:11:0

1 P

M M-102

FLO

OR

PLA

N -

AR

EA

B -

ME

CH

AN

ICA

LA

DD

ITIO

N T

O H

ICK

OR

Y M

IDD

LE

SC

HO

OL

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

JA

R

RC

P

MW

T

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

85

1/8" = 1'-0"

FLOOR PLAN - AREA B - MECHANICALFLOOR PLAN - AREA B - MECHANICAL

KEY PLANN.T.S.

B

NEW WORK NOTES

NO. DESCRIPTION

2 MAINTAIN MANUFACTURER'S RECOMMENDED SERVICEAREA FOR ALL VAV TERMINAL UNITS. COORDINATECLEARANCE REQUIREMENTS WITH OTHER TRADES.REFER TO VAV BOX INSTALLATION DETAIL ON DRAWINGM-301.

5 DUCT MOUNTED SMOKE DETECTOR FURNISHED BYDIVISION 26, INSTALLED BY DIVISION 23. INTERLOCKSMOKE DETECTORS WITH FIRE ALARM SYSTEM INACCORDANCE WITH SECTION 606.4.1 OF VIRGINIAMECHANICAL CODE. REFER TO ELECTRICAL DRAWINGSFOR ADDITIONAL INFORMATION.

6 PROVIDE 1"x1" WIRE MESH WITH FLANGED FRAMEASSEMBLY.

12 PROVIDE DUCT LINER FOR INDICATED DUCTWORK.

13 REFER TO PLUMBING DRAWINGS FOR CONDENSATEPIPING TIE-IN.

Page 5: GENERAL NOTES ABBREVIATIONS LEGEND · PDF filertu-x rooftop unit designation ... all round branch ducts to diffusers shall match neck sizes shown on schedule, ... meet performance

RTU-8

EF-25

EF-24

EF-23

7

7

7

11

9

10 8

D 1 1/2"

"SMART BOX" PIPE PORTAL.REFER TO DRAWING M-301FOR DETAIL.

OU-1

1/4" RL,1/2" RG DN

CURB RAIL. REFERTO DRAWING A-501FOR DETAIL.

REFER TO PLUMBINGDRAWINGS FOR GASPIPING TO RTU-8.

NIGNELANOISS

E

FO

RP

RE

E

Lic. No. 023349

KEVIN D. ALLEN AI

NI

LTH OFV

IRG

COMMON

WEA

01/16" = 1'-0"

5' 10' 20' 40'

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

GRAPHIC SCALE

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 3

:11:0

7 P

M M-121

OV

ER

ALL R

OO

F P

LA

N -

ME

CH

AN

ICA

LA

DD

ITIO

N T

O H

ICK

OR

Y M

IDD

LE

SC

HO

OL

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

JA

R

RC

P

MW

T

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

86

1/16" = 1'-0"

OVERALL ROOF PLAN - MECHANICALOVERALL ROOF PLAN - MECHANICAL

NEW WORK NOTES

NO. DESCRIPTION

7 REFER TO ROOF EXHAUST FAN DETAIL ON DRAWINGM-301.

8 REFER TO ROOFTOP MOUNTING DETAIL ON DRAWINGM-301.

9 REFER TO PIPE SUPPORT DETAIL ON DRAWING M-301.

10 REFER TO CONDENSATE DRAIN TRAP DETAIL ONDRAWING M-301.

11 RUN CONDENSATE DRAIN TO GUTTER/ROOF DRAIN. DONOT DISCHARGE INTO OVERFLOW ROOF DRAIN.

Page 6: GENERAL NOTES ABBREVIATIONS LEGEND · PDF filertu-x rooftop unit designation ... all round branch ducts to diffusers shall match neck sizes shown on schedule, ... meet performance

"J"SLOPE

"L"

"H"

NOTES:

1.

2.

"H" = (1" FOR EACH 1" OF MAXIMUM NEGATIVE STATIC PRESSURE) + 1"

"J" = HALF OF "H"

3. "L" = "H" + "J" + PIPE DIAMETER + INSULATION

4. SIZE TRAP IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.

DRAIN

CLEANOUT (TYP)

RUN AS INDICATED

COILDRAIN PAN

UNIONS (TYP)

MOTOR OUT OF AIRSTREAM

FACTORY WIRING FROM MOTOR TO DISCONNECT

BIRDSCREEN

FLASHING AND COUNTERFLASHING, REFER TO ARCHITECTURAL DRAWINGS FOR DETAILS

ROOF, REFER TO ARCHITECTURAL DRAWINGS

BACKDRAFT DAMPER

FACTORY INSTALLEDDISCONNECT SWITCH

ROOF CURB BYFAN MANUFACTURER

CONDUIT AND WIRINGINSIDE ROOF CURB

DUCT - SEEPLAN FOR SIZE

1-3/4" FOAM

2" ALUMINUM CHANNELMOUNTED ABOVE THESPRING ISOLATION

REFER TO ARCHITECTURALAND STRUCTURAL DRAWINGSFOR ROOF WORK REQUIRED

ROOFTOP UNIT

2" (2.8 LBS/CUBIC FEET)ACOUSTICAL BATTINSULATION

2 LAYERS (5/8") GYPSUM BOARD

MASON INDUSTRIESMODEL CMAB ISOLATIONRAIL SYSTEM

FLEXIBLE EPDM CONNECTION

WOOD NAILER

FACTORY FURNISHED ROOF CURB

2" WIDE DUCT HANGER

PREINSULATED FLEXIBLE DUCT

FLEXIBLE DUCT SECURED WITH MECHANICALBAND CLAMPS, SEE SPECIFICATIONS FORACCEPTABLE MATERIALS (TYP)

USE FOIL BACKED TAPE TOTRANSITION TO FLEXIBLE DUCTINSULATION (TYP ALL FLEXIBLE DUCTS)

INSULATION OVERLAPPINGDIFFUSER COLLAR

FINISHED CEILING SUPPORT

SUPPLY AIR DIFFUSER FACE

1 DIA.

MINIMUM 2 DIAMETERS OF STRAIGHT DUCT ORPROVIDE EQUALIZING GRID AT DIFFUSER

OFFSET NO GREATER THAN D/8WHEN FLEXIBLE RISER IS USED

RECTANGULAR TO ROUNDEXPANDED SIDE TAKE-OFF WITHDAMPER IN BRANCH. EXTERNALINSULATION ON SHEET METAL.

CEILING HANGERWIRE TO STRUCTURE

36"CLEARANCE

MEDIUM PRESSURE FLEXIBLEDUCTWORK (MAX. 3'-0" LONG)

STRAIGHT RUN DUCT CONNECTIONDIMENSION PER MANUFACTURER'SRECOMMENDATION

ELECTRIC REHEAT COIL

FLEXIBLE CONNECTOR

48" MIN, TO FIRST BRANCH

DIFFUSER

FLEXIBLE DUCT(MAX. 5'-0" LONG)

LOW VELOCITYDUCTWORK

MAINTAIN NOTEDCLEARANCES FROM ALLHORIZONTAL AND VERTICALOBSTRUCTIONS (TYP)

VAV BOX, HANG FROM BUILDINGSTRUCTURE WITH THREADEDRODS AND VIBRATION ISOLATORS

VD

SINGLE WALLRECTANGULAR DUCTWORK

MEDIUM PRESSUREDUCTWORK

ELECTRICAL ENCLOSURE

ELECTRICAL ENCLOSURES

36" CLEARANCE

FILTER

ISOLATOR

BOLT SLOTTED END OFFLAT PAR TO CURB,DO NOT OVER TIGHTEN.BAR MUST BE ALLOWEDTO MOVE WITH UNIT.

3/4" THICK NEOPRENEVIBRATION ISOLATIONPADS (TYPICAL)QUANTITY AS RECOMMENDEDBY PAD MANUFACTURER

STEEL STRUCTURE, REFER TOSTRUCTURAL DRAWINGS

BASE PLATE

BOLT FLAT BAR TO UNIT BASE RAIL

1/4" GALVANIZED FLAT STEEL BAR

1" LONG SLOT

AIR-COOLED CONDENSING UNIT

ATTACH CONDENSING UNIT TO RAILS

COUNTER FLASHING, REFER TOARCHITECTURAL DRAWINGS

FLASHING, REFER TOARCHITECTURAL DRAWINGS

ROOFING

PREFABRICATED GALVANIZEDSTEEL EQUIPMENT RAILSWELDED SEAMS

BASE FLASHING, REFER TOARCHITECTURAL DRAWINGS.

INSUL METAL CURB W/2" DECK FLANGE.

SECURE BASE FLASH TO TOP OF CURBAND CNTR FLASH W/ BOX HOUSING.

NUMBER AND SIZE OF PIPE SEALS PERMECH AND ELEC REQUIREMENTS.

LID & HOUSING FABRICATED FROM14 GA POWDER COATED ALUMINUM.

NOTE:PIPE CHASE HOUSING AS MANUFACTUREDBY ALTA PRODUCTS LLC. COORD W/MECHANICAL PLANS FOR LOCATIONS.

WATERPROOF GFI ELECTRIC OUTLET. (TYP.)

NIGNELANOISS

E

FO

RP

RE

E

Lic. No. 023349

KEVIN D. ALLEN AI

NI

LTH OFV

IRG

COMMON

WEA

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 3

:11:0

7 P

M M-301

ME

CH

AN

ICA

L D

ET

AIL

SA

DD

ITIO

N T

O H

ICK

OR

Y M

IDD

LE

SC

HO

OL

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

JA

R

RC

P

MW

T

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

87

NOT TO SCALE

COIL CONDENSATE TRAP DETAILCOIL CONDENSATE TRAP DETAIL

NOT TO SCALE

ROOF EXHAUST FAN DETAILROOF EXHAUST FAN DETAILNOT TO SCALE

SECTION - ROOFTOP UNIT MOUNTING DETAIL SECTION - ROOFTOP UNIT MOUNTING DETAIL

NOT TO SCALE

TYPICAL CEILING DIFFUSER INSTALLATION DETAILTYPICAL CEILING DIFFUSER INSTALLATION DETAIL

NOT TO SCALE

TYPICAL SERIES FAN POWERED VAV BOX(WITH ELECTRIC REHEAT COIL) INSTALLATION DETAILTYPICAL SERIES FAN POWERED VAV BOX(WITH ELECTRIC REHEAT COIL) INSTALLATION DETAIL

(NEGATIVE PRESSURE)

NOTE: DIRECT DRIVE SIMILAR

NOT TO SCALE

AIR COOLED CONDENSING UNIT SUPPORT DETAILAIR COOLED CONDENSING UNIT SUPPORT DETAILNOT TO SCALE

"SMART BOX" PIPE PORTAL DETAIL"SMART BOX" PIPE PORTAL DETAIL

Page 7: GENERAL NOTES ABBREVIATIONS LEGEND · PDF filertu-x rooftop unit designation ... all round branch ducts to diffusers shall match neck sizes shown on schedule, ... meet performance

90° RADIUS ELBOWS OFFSETS

BRANCH TAKEOFFS 90° TEES

MORE USE VANED ELBOW.

X OR Y LESS THAN 12"

VD

VD

X OR W LESS THAN 12"

VDVD

VD

VD

VDVDVD

X

2

1

21

1

11

R

2

1

1

2

1

2

2

21

1

2

1R = W + W

R = (W + W )/2

2

1

20° MAX.

W

WW

W

WW

WY

R = X+Y

R = (X+Y)/2R = D

R

RR

Y

X

D

D

R

RR

RX

W

R = X+Y

R = (X+Y)/2

R = W

PREFERRED OFFSET

FULL RADIUS WHERE POSSIBLE

FOR D OF 12" OR

D LESS THAN 12"

NOTE: ABOVE APPLY TO SUPPLY AND RETURN

X Y

YX

20° MAX.

RETURN ONLY

20° MAX.

FROM RECTANGULAR MAIN

ROUND DUCT TAKEOFF

1.5 D

D

DC MORE THAN 12"

ACFM

CC

FM

BCFMY

A

C CFMCFM

x Y = X

XC

FM

CFM

CFM

CFMCFM

YC

x Y = X

C LESS THAN 12"

A

C

SD

AB

TRANSITIONS

BRANCHES TAPS 90° RADIUS ELBOWS

OFFSET

S2

CONCENTRIC TRANSITION

ECCENTRIC TRANSITION

SPECIFIED

L, O, AND TD MUST BE

S1, S2 = 0

Y- BRANCH

W4 = W3 = W1

S1, S3, S4 = 0

H1

L MUST BE SPECIFIED

LOLOSS TAP

L

W3

L MUST BE SPECIFIED

∅ IF ∅ = 45°

S3 = 0

∅ = 45°

L

H3

H3

S1, S2 > 2"

∅ = 1° TO 90°

RADIUS ELBOW

S1, S2 = 0

∅ = 1° TO 90°

R = W1

.50"∅

W3

S3

∅.50"

H1

S2

H1

S2

W1

S1

R

S1 W1

W3

H1

S3

R = W1

R

S2

RADIUS OFFSET

ANGLED TAP

L = 2W1

S1, S2 = 0

H1

WITH TURNING VANES

MITERED ELBOW

S1

W1

O

H2

H2

H1

O

S1

L

W1

S4

S1W1

R

W4

S1, S2 = 0TD = 0.5(W1-W2)

O = 0.5(W1-W2)

O

S2

S1

L TD

W2

TO

W1

W2

DUCTWORK CONSTRUCTION REQUIREMENTS

NOTES:

1. CONSTRUCT ALL DUCTWORK IN ACCORDANCE WITH "SMACNA" HVAC DUCTCONSTRUCTION STANDARDS.

2. ALL MEDIUM PRESSURE DUCTWORK SHALL BE LEAK TESTED (DALT) AS SPECIFIED.

SYSTEM PRESSURE CLASS SEAL CLASS

+1.5" WG

-1.0" WG

-1.0" WG

RETURN AIR

EXHAUST AIR

CLASS B

CLASS B

CLASS B

+2.5" WG CLASS ASUPPLY AIR

SUPPLY AIR

TRANSFER AIR N/A NOT REQUIRED

RTU-8

16"/14"

46"/22"

14"/16" 14"/16"

12"ø 12"ø

52"/30"

30"/50"8"ø8"ø

RTU-8

8"ø

16"/14" 22"/46"22"/46"

30"/52"

NIGNELANOISS

E

FO

RP

RE

E

Lic. No. 023349

KEVIN D. ALLEN AI

NI

LTH OFV

IRG

COMMON

WEA

SHEET NO.

JO

B N

O.:

SC

ALE

:

DA

TE

:

AP

PR

OV

ED

:

CH

EC

KE

D:

DR

AW

N:

AS

NO

TE

D

RE

VIS

ION

S:

SHT. OF

THOMPSONConsulting Engineers

22 ENTERPRISE PARKWAY

TELEPHONE: (757) 599-4415PROJECT NUMBER: 17041

FAX: (757) 599-4113

HAMPTON, VA 23666

104

03-07-18

3/6

/2018 3

:11:1

2 P

M M-302

ME

CH

AN

ICA

L D

ET

AIL

S A

ND

SE

CT

ION

SA

DD

ITIO

N T

O H

ICK

OR

Y M

IDD

LE

SC

HO

OL

1997 H

AW

K B

LV

D, C

HE

SA

PE

AK

E V

A 23322

JA

R

RC

P

MW

T

03/0

7/1

8

17005

100%

FIN

AL S

UB

MIT

TA

L

88

NOT TO SCALE

LOW VELOCITY DUCTWORK DETAILSLOW VELOCITY DUCTWORK DETAILSNOT TO SCALE

MEDIUM PRESSURE SINGLE-WALL RECTANGULAR DUCTWORK DETAILSMEDIUM PRESSURE SINGLE-WALL RECTANGULAR DUCTWORK DETAILS

1/4" = 1'-0"

SECTION 1SECTION 1 1/4" = 1'-0"

SECTION 2SECTION 21M-102

2M-102