Imagination at work. Ozgur Cosar, Specification Engineer Ryan Bergeron, Specification Engineer GE Technical Tuesday 30-Cycle ATS: Understanding Emergency System Applications

GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

  • Upload
    others

  • View
    10

  • Download
    0

Embed Size (px)

Citation preview

Page 1: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

Imagination at work

Ozgur Cosar Specification Engineer Ryan Bergeron Specification Engineer

GE Technical Tuesday 30-Cycle ATS Understanding Emergency System Applications

Agenda

NEC Articles ampSelective Coordination ATS testing Withstand Close Rating (WCR) Short Time Rating (STR) ATS selection criteria GErsquos ATS product portfolio GE Zenith 30 cycle ATS-ZT30

3

a) The ATS has to be able to transfer between two sources

b) The ATS must 1 Be able to withstand a fault and 2 Close-on a fault

Automatic Transfer Switch (ATS)

MDS WiYZTM NEC Mandates Selective Coordination

Article 70027 Emergency Systems

Article 70118 Legally Required Standby Systems

Article 70854 Critical Operations Power Systems

Article 51726 Healthcare Facilities

Article 62062 Elevators Dumbwaiters Escalators Moving Walks Wheelchair Lifts and Stairway Chairs Lifts

ldquoLocalization of an overcurrent condition to restrict outages to the circuit or

equipment affected accomplished by the choice of over current protective

devices and their ratings or settingsrdquo (NEC Article 100)

Source NEMA

P - 1

20A

200A

800A

400A

P - 2

OCPD Not affected

OCPD Opens

Unnecessary power

loss

Fault

P - 1

20A

200A

800A

400A

P - 2

Selectively Coordinated System For the full range of overcurrent possible at P -1 only the 20A OCPD opens

Not Selectively Coordinated System For some overcurrent possible at P -1 the 200A 400A amp 800A OCPDs opens when only the 20A OCPD should open

Power Distribution Equipment Power Distribution Equipment

What is Selective Coordination

Selective Coordination with ATS

A true selective coordination

design must ensure that every Over

Current Protective Device (OCPD)

has higher overcurrent rating and

a longer time-delay than the one

below it so that every fault will be

cleared by the OCPD immediately

ldquoupstreamrdquo of the fault

CL1

CL3 OCPD 7

CL2

Normal Source

OCPD 1

OCPD 2

OCPD 3

OCPD 8

OCPD 4 OCPD 5 OCPD 6

G

30-Cycle ATS

CL4 CL5

ATS must withstand the level of the short circuit fault current until the upstream overcurrent devices clear the fault by short time protection

Withstand Contacts must remain closed while current is applied for the prescribed time 1 ldquo3rdquo cycle-standard test 2 Short time ndash time defined by manufacturer -3 cyclelt Time le 30 cycle

Close on Contacts must close onto the prescribed fault current and remain closed for duration 1 ldquo3rdquo cycle 2 Short time ndash time defined by mfg - 3 cyclelt Time le 30 cycle

N E

X

ATS Testing

A typical ATS application

a) The ATS has to be able to transfer between two sources

b) The switch must also 1 Be able to withstand a fault and 2 Close-on a fault

Withstand and close rating (WCR) 1 Given in kA for a specific switch voltage upstream

overcurrent protection i A standard ATS is expecting short time protection

from the upstream overcurrent protective devices (OCPD) The ATS is expecting the clear time of the OCPD to be le 3 cycle

ii The Upstream overcurrent device can take many forms molded case circuit breaker insulated case circuit breaker LV power circuit breaker or fusible device

Withstand amp Close Rated ATS

UL Definition The maximum amount of fault current a switch can withstand at a specified voltage for a given amount of time and remain functional

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Short-Time Rated ATS

STR ATS vs WCR ATS

STR WCR

Withstand a Fault Event Yes Yes

Close-on to a Fault Event Yes Yes

Temperature Rise Test Yes No

Must be Functional after Fault Event on the tested contact

Yes No

Deliver 100 Power to Load after a Fault Event Yes No

Per UL 1008 standards

MDS WiYZTM Considerations

1 Short time pickup value (Amp)

2 Short time clear time

3 ST coordination between devices

4 Voltage amp fault current

5 The upstream device must clear a fault in a timeframe that is le the short time rating of the switch

a) 3 cycles=3x0016=0048s=48ms

b) 10 cycles =10x0016 = 016s=160ms

c) 18 cycles =18x0016 =0288s= 288ms

d) 30 cycles = 30x0016 = 048s=480ms

10 Cycle 18 Cycle or 30 Cycle ATS

N E

X

Instantaneous is either

bull Off ndash LVPCB

bull Set higher than available 3

phase bolted fault current

Typical 600AF 600AT MCCB adjustable inst max = 6072 Tracking ST (not adjustable)

Fixed ST delay clear range ~0192s to 046s = 12 to 29 cycles

~ 10 cycles- 016s but may not clear for faults below instantaneous pickup

~ 18 cycles=0288s

~ 30 cycles=048s

~ 3 cycleshellipfor purposes of conversation the inst PU is set above available fault current

Typical MCCB bull No adjustable ST pickup bull No adjustable ST delay

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

MDS WiYZTM

MCCB with independently adjustable

bull Short time pickup

bull Short time delay

bull Clear times range from ~ 4 to ~30+ cycles

~42 cycles

max

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

10 Cycle 18 Cycle or 30 Cycle ATS LVPCB Clearing with ST instantaneous turned off

MDS WiYZTM

Selective Coordination

Achieving selective coordination by the short time protection of an upstream breaker

The short time clearing time gt 3 cycle le 30 cycle

More Reliable Robust Switch

The short time test is the most stringent version amp ensures a more robust ATS is used in critical circuit applications

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Why use a 30 cycle ATS

Imagination at work

GE Zenith 30 Cycle ATS ZT30 Product Overview

End User

Eliminate Outages amp

Cost Optimization

Designer

Design to Codes amp Customer Options AHJ

Uphold Codes

Future Smart Grid

Total Cost Ownership w ATS

ZT30 Product Overview 30-Cycle ATS

Product Series Amperage Range Voltage Range

ZT30 1000A - 3000A 120V - 600V

Number of Poles Transition Type Enclosure Type Controller

3 4

bull Standard (Open)

bull Closed

bull Delayed

bull Bypass

bull NEMA 1

bull NEMA 3R

bull NEMA 4

bull NEMA 4X

bull NEMA 12

bull Open Style

bull MX350 bull MX250

Amperage Width Height Depth

1000

2000

3000

bull 365rdquo

bull 365rdquo

bull 365rdquo

bull 90rdquo

bull 90rdquo

bull 90rdquo

bull 235rdquo

bull 235rdquo

bull 385rdquo

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 2: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

Agenda

NEC Articles ampSelective Coordination ATS testing Withstand Close Rating (WCR) Short Time Rating (STR) ATS selection criteria GErsquos ATS product portfolio GE Zenith 30 cycle ATS-ZT30

3

a) The ATS has to be able to transfer between two sources

b) The ATS must 1 Be able to withstand a fault and 2 Close-on a fault

Automatic Transfer Switch (ATS)

MDS WiYZTM NEC Mandates Selective Coordination

Article 70027 Emergency Systems

Article 70118 Legally Required Standby Systems

Article 70854 Critical Operations Power Systems

Article 51726 Healthcare Facilities

Article 62062 Elevators Dumbwaiters Escalators Moving Walks Wheelchair Lifts and Stairway Chairs Lifts

ldquoLocalization of an overcurrent condition to restrict outages to the circuit or

equipment affected accomplished by the choice of over current protective

devices and their ratings or settingsrdquo (NEC Article 100)

Source NEMA

P - 1

20A

200A

800A

400A

P - 2

OCPD Not affected

OCPD Opens

Unnecessary power

loss

Fault

P - 1

20A

200A

800A

400A

P - 2

Selectively Coordinated System For the full range of overcurrent possible at P -1 only the 20A OCPD opens

Not Selectively Coordinated System For some overcurrent possible at P -1 the 200A 400A amp 800A OCPDs opens when only the 20A OCPD should open

Power Distribution Equipment Power Distribution Equipment

What is Selective Coordination

Selective Coordination with ATS

A true selective coordination

design must ensure that every Over

Current Protective Device (OCPD)

has higher overcurrent rating and

a longer time-delay than the one

below it so that every fault will be

cleared by the OCPD immediately

ldquoupstreamrdquo of the fault

CL1

CL3 OCPD 7

CL2

Normal Source

OCPD 1

OCPD 2

OCPD 3

OCPD 8

OCPD 4 OCPD 5 OCPD 6

G

30-Cycle ATS

CL4 CL5

ATS must withstand the level of the short circuit fault current until the upstream overcurrent devices clear the fault by short time protection

Withstand Contacts must remain closed while current is applied for the prescribed time 1 ldquo3rdquo cycle-standard test 2 Short time ndash time defined by manufacturer -3 cyclelt Time le 30 cycle

Close on Contacts must close onto the prescribed fault current and remain closed for duration 1 ldquo3rdquo cycle 2 Short time ndash time defined by mfg - 3 cyclelt Time le 30 cycle

N E

X

ATS Testing

A typical ATS application

a) The ATS has to be able to transfer between two sources

b) The switch must also 1 Be able to withstand a fault and 2 Close-on a fault

Withstand and close rating (WCR) 1 Given in kA for a specific switch voltage upstream

overcurrent protection i A standard ATS is expecting short time protection

from the upstream overcurrent protective devices (OCPD) The ATS is expecting the clear time of the OCPD to be le 3 cycle

ii The Upstream overcurrent device can take many forms molded case circuit breaker insulated case circuit breaker LV power circuit breaker or fusible device

Withstand amp Close Rated ATS

UL Definition The maximum amount of fault current a switch can withstand at a specified voltage for a given amount of time and remain functional

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Short-Time Rated ATS

STR ATS vs WCR ATS

STR WCR

Withstand a Fault Event Yes Yes

Close-on to a Fault Event Yes Yes

Temperature Rise Test Yes No

Must be Functional after Fault Event on the tested contact

Yes No

Deliver 100 Power to Load after a Fault Event Yes No

Per UL 1008 standards

MDS WiYZTM Considerations

1 Short time pickup value (Amp)

2 Short time clear time

3 ST coordination between devices

4 Voltage amp fault current

5 The upstream device must clear a fault in a timeframe that is le the short time rating of the switch

a) 3 cycles=3x0016=0048s=48ms

b) 10 cycles =10x0016 = 016s=160ms

c) 18 cycles =18x0016 =0288s= 288ms

d) 30 cycles = 30x0016 = 048s=480ms

10 Cycle 18 Cycle or 30 Cycle ATS

N E

X

Instantaneous is either

bull Off ndash LVPCB

bull Set higher than available 3

phase bolted fault current

Typical 600AF 600AT MCCB adjustable inst max = 6072 Tracking ST (not adjustable)

Fixed ST delay clear range ~0192s to 046s = 12 to 29 cycles

~ 10 cycles- 016s but may not clear for faults below instantaneous pickup

~ 18 cycles=0288s

~ 30 cycles=048s

~ 3 cycleshellipfor purposes of conversation the inst PU is set above available fault current

Typical MCCB bull No adjustable ST pickup bull No adjustable ST delay

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

MDS WiYZTM

MCCB with independently adjustable

bull Short time pickup

bull Short time delay

bull Clear times range from ~ 4 to ~30+ cycles

~42 cycles

max

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

10 Cycle 18 Cycle or 30 Cycle ATS LVPCB Clearing with ST instantaneous turned off

MDS WiYZTM

Selective Coordination

Achieving selective coordination by the short time protection of an upstream breaker

The short time clearing time gt 3 cycle le 30 cycle

More Reliable Robust Switch

The short time test is the most stringent version amp ensures a more robust ATS is used in critical circuit applications

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Why use a 30 cycle ATS

Imagination at work

GE Zenith 30 Cycle ATS ZT30 Product Overview

End User

Eliminate Outages amp

Cost Optimization

Designer

Design to Codes amp Customer Options AHJ

Uphold Codes

Future Smart Grid

Total Cost Ownership w ATS

ZT30 Product Overview 30-Cycle ATS

Product Series Amperage Range Voltage Range

ZT30 1000A - 3000A 120V - 600V

Number of Poles Transition Type Enclosure Type Controller

3 4

bull Standard (Open)

bull Closed

bull Delayed

bull Bypass

bull NEMA 1

bull NEMA 3R

bull NEMA 4

bull NEMA 4X

bull NEMA 12

bull Open Style

bull MX350 bull MX250

Amperage Width Height Depth

1000

2000

3000

bull 365rdquo

bull 365rdquo

bull 365rdquo

bull 90rdquo

bull 90rdquo

bull 90rdquo

bull 235rdquo

bull 235rdquo

bull 385rdquo

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 3: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

3

a) The ATS has to be able to transfer between two sources

b) The ATS must 1 Be able to withstand a fault and 2 Close-on a fault

Automatic Transfer Switch (ATS)

MDS WiYZTM NEC Mandates Selective Coordination

Article 70027 Emergency Systems

Article 70118 Legally Required Standby Systems

Article 70854 Critical Operations Power Systems

Article 51726 Healthcare Facilities

Article 62062 Elevators Dumbwaiters Escalators Moving Walks Wheelchair Lifts and Stairway Chairs Lifts

ldquoLocalization of an overcurrent condition to restrict outages to the circuit or

equipment affected accomplished by the choice of over current protective

devices and their ratings or settingsrdquo (NEC Article 100)

Source NEMA

P - 1

20A

200A

800A

400A

P - 2

OCPD Not affected

OCPD Opens

Unnecessary power

loss

Fault

P - 1

20A

200A

800A

400A

P - 2

Selectively Coordinated System For the full range of overcurrent possible at P -1 only the 20A OCPD opens

Not Selectively Coordinated System For some overcurrent possible at P -1 the 200A 400A amp 800A OCPDs opens when only the 20A OCPD should open

Power Distribution Equipment Power Distribution Equipment

What is Selective Coordination

Selective Coordination with ATS

A true selective coordination

design must ensure that every Over

Current Protective Device (OCPD)

has higher overcurrent rating and

a longer time-delay than the one

below it so that every fault will be

cleared by the OCPD immediately

ldquoupstreamrdquo of the fault

CL1

CL3 OCPD 7

CL2

Normal Source

OCPD 1

OCPD 2

OCPD 3

OCPD 8

OCPD 4 OCPD 5 OCPD 6

G

30-Cycle ATS

CL4 CL5

ATS must withstand the level of the short circuit fault current until the upstream overcurrent devices clear the fault by short time protection

Withstand Contacts must remain closed while current is applied for the prescribed time 1 ldquo3rdquo cycle-standard test 2 Short time ndash time defined by manufacturer -3 cyclelt Time le 30 cycle

Close on Contacts must close onto the prescribed fault current and remain closed for duration 1 ldquo3rdquo cycle 2 Short time ndash time defined by mfg - 3 cyclelt Time le 30 cycle

N E

X

ATS Testing

A typical ATS application

a) The ATS has to be able to transfer between two sources

b) The switch must also 1 Be able to withstand a fault and 2 Close-on a fault

Withstand and close rating (WCR) 1 Given in kA for a specific switch voltage upstream

overcurrent protection i A standard ATS is expecting short time protection

from the upstream overcurrent protective devices (OCPD) The ATS is expecting the clear time of the OCPD to be le 3 cycle

ii The Upstream overcurrent device can take many forms molded case circuit breaker insulated case circuit breaker LV power circuit breaker or fusible device

Withstand amp Close Rated ATS

UL Definition The maximum amount of fault current a switch can withstand at a specified voltage for a given amount of time and remain functional

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Short-Time Rated ATS

STR ATS vs WCR ATS

STR WCR

Withstand a Fault Event Yes Yes

Close-on to a Fault Event Yes Yes

Temperature Rise Test Yes No

Must be Functional after Fault Event on the tested contact

Yes No

Deliver 100 Power to Load after a Fault Event Yes No

Per UL 1008 standards

MDS WiYZTM Considerations

1 Short time pickup value (Amp)

2 Short time clear time

3 ST coordination between devices

4 Voltage amp fault current

5 The upstream device must clear a fault in a timeframe that is le the short time rating of the switch

a) 3 cycles=3x0016=0048s=48ms

b) 10 cycles =10x0016 = 016s=160ms

c) 18 cycles =18x0016 =0288s= 288ms

d) 30 cycles = 30x0016 = 048s=480ms

10 Cycle 18 Cycle or 30 Cycle ATS

N E

X

Instantaneous is either

bull Off ndash LVPCB

bull Set higher than available 3

phase bolted fault current

Typical 600AF 600AT MCCB adjustable inst max = 6072 Tracking ST (not adjustable)

Fixed ST delay clear range ~0192s to 046s = 12 to 29 cycles

~ 10 cycles- 016s but may not clear for faults below instantaneous pickup

~ 18 cycles=0288s

~ 30 cycles=048s

~ 3 cycleshellipfor purposes of conversation the inst PU is set above available fault current

Typical MCCB bull No adjustable ST pickup bull No adjustable ST delay

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

MDS WiYZTM

MCCB with independently adjustable

bull Short time pickup

bull Short time delay

bull Clear times range from ~ 4 to ~30+ cycles

~42 cycles

max

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

10 Cycle 18 Cycle or 30 Cycle ATS LVPCB Clearing with ST instantaneous turned off

MDS WiYZTM

Selective Coordination

Achieving selective coordination by the short time protection of an upstream breaker

The short time clearing time gt 3 cycle le 30 cycle

More Reliable Robust Switch

The short time test is the most stringent version amp ensures a more robust ATS is used in critical circuit applications

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Why use a 30 cycle ATS

Imagination at work

GE Zenith 30 Cycle ATS ZT30 Product Overview

End User

Eliminate Outages amp

Cost Optimization

Designer

Design to Codes amp Customer Options AHJ

Uphold Codes

Future Smart Grid

Total Cost Ownership w ATS

ZT30 Product Overview 30-Cycle ATS

Product Series Amperage Range Voltage Range

ZT30 1000A - 3000A 120V - 600V

Number of Poles Transition Type Enclosure Type Controller

3 4

bull Standard (Open)

bull Closed

bull Delayed

bull Bypass

bull NEMA 1

bull NEMA 3R

bull NEMA 4

bull NEMA 4X

bull NEMA 12

bull Open Style

bull MX350 bull MX250

Amperage Width Height Depth

1000

2000

3000

bull 365rdquo

bull 365rdquo

bull 365rdquo

bull 90rdquo

bull 90rdquo

bull 90rdquo

bull 235rdquo

bull 235rdquo

bull 385rdquo

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 4: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

MDS WiYZTM NEC Mandates Selective Coordination

Article 70027 Emergency Systems

Article 70118 Legally Required Standby Systems

Article 70854 Critical Operations Power Systems

Article 51726 Healthcare Facilities

Article 62062 Elevators Dumbwaiters Escalators Moving Walks Wheelchair Lifts and Stairway Chairs Lifts

ldquoLocalization of an overcurrent condition to restrict outages to the circuit or

equipment affected accomplished by the choice of over current protective

devices and their ratings or settingsrdquo (NEC Article 100)

Source NEMA

P - 1

20A

200A

800A

400A

P - 2

OCPD Not affected

OCPD Opens

Unnecessary power

loss

Fault

P - 1

20A

200A

800A

400A

P - 2

Selectively Coordinated System For the full range of overcurrent possible at P -1 only the 20A OCPD opens

Not Selectively Coordinated System For some overcurrent possible at P -1 the 200A 400A amp 800A OCPDs opens when only the 20A OCPD should open

Power Distribution Equipment Power Distribution Equipment

What is Selective Coordination

Selective Coordination with ATS

A true selective coordination

design must ensure that every Over

Current Protective Device (OCPD)

has higher overcurrent rating and

a longer time-delay than the one

below it so that every fault will be

cleared by the OCPD immediately

ldquoupstreamrdquo of the fault

CL1

CL3 OCPD 7

CL2

Normal Source

OCPD 1

OCPD 2

OCPD 3

OCPD 8

OCPD 4 OCPD 5 OCPD 6

G

30-Cycle ATS

CL4 CL5

ATS must withstand the level of the short circuit fault current until the upstream overcurrent devices clear the fault by short time protection

Withstand Contacts must remain closed while current is applied for the prescribed time 1 ldquo3rdquo cycle-standard test 2 Short time ndash time defined by manufacturer -3 cyclelt Time le 30 cycle

Close on Contacts must close onto the prescribed fault current and remain closed for duration 1 ldquo3rdquo cycle 2 Short time ndash time defined by mfg - 3 cyclelt Time le 30 cycle

N E

X

ATS Testing

A typical ATS application

a) The ATS has to be able to transfer between two sources

b) The switch must also 1 Be able to withstand a fault and 2 Close-on a fault

Withstand and close rating (WCR) 1 Given in kA for a specific switch voltage upstream

overcurrent protection i A standard ATS is expecting short time protection

from the upstream overcurrent protective devices (OCPD) The ATS is expecting the clear time of the OCPD to be le 3 cycle

ii The Upstream overcurrent device can take many forms molded case circuit breaker insulated case circuit breaker LV power circuit breaker or fusible device

Withstand amp Close Rated ATS

UL Definition The maximum amount of fault current a switch can withstand at a specified voltage for a given amount of time and remain functional

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Short-Time Rated ATS

STR ATS vs WCR ATS

STR WCR

Withstand a Fault Event Yes Yes

Close-on to a Fault Event Yes Yes

Temperature Rise Test Yes No

Must be Functional after Fault Event on the tested contact

Yes No

Deliver 100 Power to Load after a Fault Event Yes No

Per UL 1008 standards

MDS WiYZTM Considerations

1 Short time pickup value (Amp)

2 Short time clear time

3 ST coordination between devices

4 Voltage amp fault current

5 The upstream device must clear a fault in a timeframe that is le the short time rating of the switch

a) 3 cycles=3x0016=0048s=48ms

b) 10 cycles =10x0016 = 016s=160ms

c) 18 cycles =18x0016 =0288s= 288ms

d) 30 cycles = 30x0016 = 048s=480ms

10 Cycle 18 Cycle or 30 Cycle ATS

N E

X

Instantaneous is either

bull Off ndash LVPCB

bull Set higher than available 3

phase bolted fault current

Typical 600AF 600AT MCCB adjustable inst max = 6072 Tracking ST (not adjustable)

Fixed ST delay clear range ~0192s to 046s = 12 to 29 cycles

~ 10 cycles- 016s but may not clear for faults below instantaneous pickup

~ 18 cycles=0288s

~ 30 cycles=048s

~ 3 cycleshellipfor purposes of conversation the inst PU is set above available fault current

Typical MCCB bull No adjustable ST pickup bull No adjustable ST delay

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

MDS WiYZTM

MCCB with independently adjustable

bull Short time pickup

bull Short time delay

bull Clear times range from ~ 4 to ~30+ cycles

~42 cycles

max

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

10 Cycle 18 Cycle or 30 Cycle ATS LVPCB Clearing with ST instantaneous turned off

MDS WiYZTM

Selective Coordination

Achieving selective coordination by the short time protection of an upstream breaker

The short time clearing time gt 3 cycle le 30 cycle

More Reliable Robust Switch

The short time test is the most stringent version amp ensures a more robust ATS is used in critical circuit applications

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Why use a 30 cycle ATS

Imagination at work

GE Zenith 30 Cycle ATS ZT30 Product Overview

End User

Eliminate Outages amp

Cost Optimization

Designer

Design to Codes amp Customer Options AHJ

Uphold Codes

Future Smart Grid

Total Cost Ownership w ATS

ZT30 Product Overview 30-Cycle ATS

Product Series Amperage Range Voltage Range

ZT30 1000A - 3000A 120V - 600V

Number of Poles Transition Type Enclosure Type Controller

3 4

bull Standard (Open)

bull Closed

bull Delayed

bull Bypass

bull NEMA 1

bull NEMA 3R

bull NEMA 4

bull NEMA 4X

bull NEMA 12

bull Open Style

bull MX350 bull MX250

Amperage Width Height Depth

1000

2000

3000

bull 365rdquo

bull 365rdquo

bull 365rdquo

bull 90rdquo

bull 90rdquo

bull 90rdquo

bull 235rdquo

bull 235rdquo

bull 385rdquo

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 5: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

ldquoLocalization of an overcurrent condition to restrict outages to the circuit or

equipment affected accomplished by the choice of over current protective

devices and their ratings or settingsrdquo (NEC Article 100)

Source NEMA

P - 1

20A

200A

800A

400A

P - 2

OCPD Not affected

OCPD Opens

Unnecessary power

loss

Fault

P - 1

20A

200A

800A

400A

P - 2

Selectively Coordinated System For the full range of overcurrent possible at P -1 only the 20A OCPD opens

Not Selectively Coordinated System For some overcurrent possible at P -1 the 200A 400A amp 800A OCPDs opens when only the 20A OCPD should open

Power Distribution Equipment Power Distribution Equipment

What is Selective Coordination

Selective Coordination with ATS

A true selective coordination

design must ensure that every Over

Current Protective Device (OCPD)

has higher overcurrent rating and

a longer time-delay than the one

below it so that every fault will be

cleared by the OCPD immediately

ldquoupstreamrdquo of the fault

CL1

CL3 OCPD 7

CL2

Normal Source

OCPD 1

OCPD 2

OCPD 3

OCPD 8

OCPD 4 OCPD 5 OCPD 6

G

30-Cycle ATS

CL4 CL5

ATS must withstand the level of the short circuit fault current until the upstream overcurrent devices clear the fault by short time protection

Withstand Contacts must remain closed while current is applied for the prescribed time 1 ldquo3rdquo cycle-standard test 2 Short time ndash time defined by manufacturer -3 cyclelt Time le 30 cycle

Close on Contacts must close onto the prescribed fault current and remain closed for duration 1 ldquo3rdquo cycle 2 Short time ndash time defined by mfg - 3 cyclelt Time le 30 cycle

N E

X

ATS Testing

A typical ATS application

a) The ATS has to be able to transfer between two sources

b) The switch must also 1 Be able to withstand a fault and 2 Close-on a fault

Withstand and close rating (WCR) 1 Given in kA for a specific switch voltage upstream

overcurrent protection i A standard ATS is expecting short time protection

from the upstream overcurrent protective devices (OCPD) The ATS is expecting the clear time of the OCPD to be le 3 cycle

ii The Upstream overcurrent device can take many forms molded case circuit breaker insulated case circuit breaker LV power circuit breaker or fusible device

Withstand amp Close Rated ATS

UL Definition The maximum amount of fault current a switch can withstand at a specified voltage for a given amount of time and remain functional

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Short-Time Rated ATS

STR ATS vs WCR ATS

STR WCR

Withstand a Fault Event Yes Yes

Close-on to a Fault Event Yes Yes

Temperature Rise Test Yes No

Must be Functional after Fault Event on the tested contact

Yes No

Deliver 100 Power to Load after a Fault Event Yes No

Per UL 1008 standards

MDS WiYZTM Considerations

1 Short time pickup value (Amp)

2 Short time clear time

3 ST coordination between devices

4 Voltage amp fault current

5 The upstream device must clear a fault in a timeframe that is le the short time rating of the switch

a) 3 cycles=3x0016=0048s=48ms

b) 10 cycles =10x0016 = 016s=160ms

c) 18 cycles =18x0016 =0288s= 288ms

d) 30 cycles = 30x0016 = 048s=480ms

10 Cycle 18 Cycle or 30 Cycle ATS

N E

X

Instantaneous is either

bull Off ndash LVPCB

bull Set higher than available 3

phase bolted fault current

Typical 600AF 600AT MCCB adjustable inst max = 6072 Tracking ST (not adjustable)

Fixed ST delay clear range ~0192s to 046s = 12 to 29 cycles

~ 10 cycles- 016s but may not clear for faults below instantaneous pickup

~ 18 cycles=0288s

~ 30 cycles=048s

~ 3 cycleshellipfor purposes of conversation the inst PU is set above available fault current

Typical MCCB bull No adjustable ST pickup bull No adjustable ST delay

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

MDS WiYZTM

MCCB with independently adjustable

bull Short time pickup

bull Short time delay

bull Clear times range from ~ 4 to ~30+ cycles

~42 cycles

max

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

10 Cycle 18 Cycle or 30 Cycle ATS LVPCB Clearing with ST instantaneous turned off

MDS WiYZTM

Selective Coordination

Achieving selective coordination by the short time protection of an upstream breaker

The short time clearing time gt 3 cycle le 30 cycle

More Reliable Robust Switch

The short time test is the most stringent version amp ensures a more robust ATS is used in critical circuit applications

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Why use a 30 cycle ATS

Imagination at work

GE Zenith 30 Cycle ATS ZT30 Product Overview

End User

Eliminate Outages amp

Cost Optimization

Designer

Design to Codes amp Customer Options AHJ

Uphold Codes

Future Smart Grid

Total Cost Ownership w ATS

ZT30 Product Overview 30-Cycle ATS

Product Series Amperage Range Voltage Range

ZT30 1000A - 3000A 120V - 600V

Number of Poles Transition Type Enclosure Type Controller

3 4

bull Standard (Open)

bull Closed

bull Delayed

bull Bypass

bull NEMA 1

bull NEMA 3R

bull NEMA 4

bull NEMA 4X

bull NEMA 12

bull Open Style

bull MX350 bull MX250

Amperage Width Height Depth

1000

2000

3000

bull 365rdquo

bull 365rdquo

bull 365rdquo

bull 90rdquo

bull 90rdquo

bull 90rdquo

bull 235rdquo

bull 235rdquo

bull 385rdquo

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 6: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

Selective Coordination with ATS

A true selective coordination

design must ensure that every Over

Current Protective Device (OCPD)

has higher overcurrent rating and

a longer time-delay than the one

below it so that every fault will be

cleared by the OCPD immediately

ldquoupstreamrdquo of the fault

CL1

CL3 OCPD 7

CL2

Normal Source

OCPD 1

OCPD 2

OCPD 3

OCPD 8

OCPD 4 OCPD 5 OCPD 6

G

30-Cycle ATS

CL4 CL5

ATS must withstand the level of the short circuit fault current until the upstream overcurrent devices clear the fault by short time protection

Withstand Contacts must remain closed while current is applied for the prescribed time 1 ldquo3rdquo cycle-standard test 2 Short time ndash time defined by manufacturer -3 cyclelt Time le 30 cycle

Close on Contacts must close onto the prescribed fault current and remain closed for duration 1 ldquo3rdquo cycle 2 Short time ndash time defined by mfg - 3 cyclelt Time le 30 cycle

N E

X

ATS Testing

A typical ATS application

a) The ATS has to be able to transfer between two sources

b) The switch must also 1 Be able to withstand a fault and 2 Close-on a fault

Withstand and close rating (WCR) 1 Given in kA for a specific switch voltage upstream

overcurrent protection i A standard ATS is expecting short time protection

from the upstream overcurrent protective devices (OCPD) The ATS is expecting the clear time of the OCPD to be le 3 cycle

ii The Upstream overcurrent device can take many forms molded case circuit breaker insulated case circuit breaker LV power circuit breaker or fusible device

Withstand amp Close Rated ATS

UL Definition The maximum amount of fault current a switch can withstand at a specified voltage for a given amount of time and remain functional

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Short-Time Rated ATS

STR ATS vs WCR ATS

STR WCR

Withstand a Fault Event Yes Yes

Close-on to a Fault Event Yes Yes

Temperature Rise Test Yes No

Must be Functional after Fault Event on the tested contact

Yes No

Deliver 100 Power to Load after a Fault Event Yes No

Per UL 1008 standards

MDS WiYZTM Considerations

1 Short time pickup value (Amp)

2 Short time clear time

3 ST coordination between devices

4 Voltage amp fault current

5 The upstream device must clear a fault in a timeframe that is le the short time rating of the switch

a) 3 cycles=3x0016=0048s=48ms

b) 10 cycles =10x0016 = 016s=160ms

c) 18 cycles =18x0016 =0288s= 288ms

d) 30 cycles = 30x0016 = 048s=480ms

10 Cycle 18 Cycle or 30 Cycle ATS

N E

X

Instantaneous is either

bull Off ndash LVPCB

bull Set higher than available 3

phase bolted fault current

Typical 600AF 600AT MCCB adjustable inst max = 6072 Tracking ST (not adjustable)

Fixed ST delay clear range ~0192s to 046s = 12 to 29 cycles

~ 10 cycles- 016s but may not clear for faults below instantaneous pickup

~ 18 cycles=0288s

~ 30 cycles=048s

~ 3 cycleshellipfor purposes of conversation the inst PU is set above available fault current

Typical MCCB bull No adjustable ST pickup bull No adjustable ST delay

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

MDS WiYZTM

MCCB with independently adjustable

bull Short time pickup

bull Short time delay

bull Clear times range from ~ 4 to ~30+ cycles

~42 cycles

max

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

10 Cycle 18 Cycle or 30 Cycle ATS LVPCB Clearing with ST instantaneous turned off

MDS WiYZTM

Selective Coordination

Achieving selective coordination by the short time protection of an upstream breaker

The short time clearing time gt 3 cycle le 30 cycle

More Reliable Robust Switch

The short time test is the most stringent version amp ensures a more robust ATS is used in critical circuit applications

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Why use a 30 cycle ATS

Imagination at work

GE Zenith 30 Cycle ATS ZT30 Product Overview

End User

Eliminate Outages amp

Cost Optimization

Designer

Design to Codes amp Customer Options AHJ

Uphold Codes

Future Smart Grid

Total Cost Ownership w ATS

ZT30 Product Overview 30-Cycle ATS

Product Series Amperage Range Voltage Range

ZT30 1000A - 3000A 120V - 600V

Number of Poles Transition Type Enclosure Type Controller

3 4

bull Standard (Open)

bull Closed

bull Delayed

bull Bypass

bull NEMA 1

bull NEMA 3R

bull NEMA 4

bull NEMA 4X

bull NEMA 12

bull Open Style

bull MX350 bull MX250

Amperage Width Height Depth

1000

2000

3000

bull 365rdquo

bull 365rdquo

bull 365rdquo

bull 90rdquo

bull 90rdquo

bull 90rdquo

bull 235rdquo

bull 235rdquo

bull 385rdquo

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 7: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

Withstand Contacts must remain closed while current is applied for the prescribed time 1 ldquo3rdquo cycle-standard test 2 Short time ndash time defined by manufacturer -3 cyclelt Time le 30 cycle

Close on Contacts must close onto the prescribed fault current and remain closed for duration 1 ldquo3rdquo cycle 2 Short time ndash time defined by mfg - 3 cyclelt Time le 30 cycle

N E

X

ATS Testing

A typical ATS application

a) The ATS has to be able to transfer between two sources

b) The switch must also 1 Be able to withstand a fault and 2 Close-on a fault

Withstand and close rating (WCR) 1 Given in kA for a specific switch voltage upstream

overcurrent protection i A standard ATS is expecting short time protection

from the upstream overcurrent protective devices (OCPD) The ATS is expecting the clear time of the OCPD to be le 3 cycle

ii The Upstream overcurrent device can take many forms molded case circuit breaker insulated case circuit breaker LV power circuit breaker or fusible device

Withstand amp Close Rated ATS

UL Definition The maximum amount of fault current a switch can withstand at a specified voltage for a given amount of time and remain functional

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Short-Time Rated ATS

STR ATS vs WCR ATS

STR WCR

Withstand a Fault Event Yes Yes

Close-on to a Fault Event Yes Yes

Temperature Rise Test Yes No

Must be Functional after Fault Event on the tested contact

Yes No

Deliver 100 Power to Load after a Fault Event Yes No

Per UL 1008 standards

MDS WiYZTM Considerations

1 Short time pickup value (Amp)

2 Short time clear time

3 ST coordination between devices

4 Voltage amp fault current

5 The upstream device must clear a fault in a timeframe that is le the short time rating of the switch

a) 3 cycles=3x0016=0048s=48ms

b) 10 cycles =10x0016 = 016s=160ms

c) 18 cycles =18x0016 =0288s= 288ms

d) 30 cycles = 30x0016 = 048s=480ms

10 Cycle 18 Cycle or 30 Cycle ATS

N E

X

Instantaneous is either

bull Off ndash LVPCB

bull Set higher than available 3

phase bolted fault current

Typical 600AF 600AT MCCB adjustable inst max = 6072 Tracking ST (not adjustable)

Fixed ST delay clear range ~0192s to 046s = 12 to 29 cycles

~ 10 cycles- 016s but may not clear for faults below instantaneous pickup

~ 18 cycles=0288s

~ 30 cycles=048s

~ 3 cycleshellipfor purposes of conversation the inst PU is set above available fault current

Typical MCCB bull No adjustable ST pickup bull No adjustable ST delay

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

MDS WiYZTM

MCCB with independently adjustable

bull Short time pickup

bull Short time delay

bull Clear times range from ~ 4 to ~30+ cycles

~42 cycles

max

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

10 Cycle 18 Cycle or 30 Cycle ATS LVPCB Clearing with ST instantaneous turned off

MDS WiYZTM

Selective Coordination

Achieving selective coordination by the short time protection of an upstream breaker

The short time clearing time gt 3 cycle le 30 cycle

More Reliable Robust Switch

The short time test is the most stringent version amp ensures a more robust ATS is used in critical circuit applications

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Why use a 30 cycle ATS

Imagination at work

GE Zenith 30 Cycle ATS ZT30 Product Overview

End User

Eliminate Outages amp

Cost Optimization

Designer

Design to Codes amp Customer Options AHJ

Uphold Codes

Future Smart Grid

Total Cost Ownership w ATS

ZT30 Product Overview 30-Cycle ATS

Product Series Amperage Range Voltage Range

ZT30 1000A - 3000A 120V - 600V

Number of Poles Transition Type Enclosure Type Controller

3 4

bull Standard (Open)

bull Closed

bull Delayed

bull Bypass

bull NEMA 1

bull NEMA 3R

bull NEMA 4

bull NEMA 4X

bull NEMA 12

bull Open Style

bull MX350 bull MX250

Amperage Width Height Depth

1000

2000

3000

bull 365rdquo

bull 365rdquo

bull 365rdquo

bull 90rdquo

bull 90rdquo

bull 90rdquo

bull 235rdquo

bull 235rdquo

bull 385rdquo

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 8: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

A typical ATS application

a) The ATS has to be able to transfer between two sources

b) The switch must also 1 Be able to withstand a fault and 2 Close-on a fault

Withstand and close rating (WCR) 1 Given in kA for a specific switch voltage upstream

overcurrent protection i A standard ATS is expecting short time protection

from the upstream overcurrent protective devices (OCPD) The ATS is expecting the clear time of the OCPD to be le 3 cycle

ii The Upstream overcurrent device can take many forms molded case circuit breaker insulated case circuit breaker LV power circuit breaker or fusible device

Withstand amp Close Rated ATS

UL Definition The maximum amount of fault current a switch can withstand at a specified voltage for a given amount of time and remain functional

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Short-Time Rated ATS

STR ATS vs WCR ATS

STR WCR

Withstand a Fault Event Yes Yes

Close-on to a Fault Event Yes Yes

Temperature Rise Test Yes No

Must be Functional after Fault Event on the tested contact

Yes No

Deliver 100 Power to Load after a Fault Event Yes No

Per UL 1008 standards

MDS WiYZTM Considerations

1 Short time pickup value (Amp)

2 Short time clear time

3 ST coordination between devices

4 Voltage amp fault current

5 The upstream device must clear a fault in a timeframe that is le the short time rating of the switch

a) 3 cycles=3x0016=0048s=48ms

b) 10 cycles =10x0016 = 016s=160ms

c) 18 cycles =18x0016 =0288s= 288ms

d) 30 cycles = 30x0016 = 048s=480ms

10 Cycle 18 Cycle or 30 Cycle ATS

N E

X

Instantaneous is either

bull Off ndash LVPCB

bull Set higher than available 3

phase bolted fault current

Typical 600AF 600AT MCCB adjustable inst max = 6072 Tracking ST (not adjustable)

Fixed ST delay clear range ~0192s to 046s = 12 to 29 cycles

~ 10 cycles- 016s but may not clear for faults below instantaneous pickup

~ 18 cycles=0288s

~ 30 cycles=048s

~ 3 cycleshellipfor purposes of conversation the inst PU is set above available fault current

Typical MCCB bull No adjustable ST pickup bull No adjustable ST delay

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

MDS WiYZTM

MCCB with independently adjustable

bull Short time pickup

bull Short time delay

bull Clear times range from ~ 4 to ~30+ cycles

~42 cycles

max

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

10 Cycle 18 Cycle or 30 Cycle ATS LVPCB Clearing with ST instantaneous turned off

MDS WiYZTM

Selective Coordination

Achieving selective coordination by the short time protection of an upstream breaker

The short time clearing time gt 3 cycle le 30 cycle

More Reliable Robust Switch

The short time test is the most stringent version amp ensures a more robust ATS is used in critical circuit applications

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Why use a 30 cycle ATS

Imagination at work

GE Zenith 30 Cycle ATS ZT30 Product Overview

End User

Eliminate Outages amp

Cost Optimization

Designer

Design to Codes amp Customer Options AHJ

Uphold Codes

Future Smart Grid

Total Cost Ownership w ATS

ZT30 Product Overview 30-Cycle ATS

Product Series Amperage Range Voltage Range

ZT30 1000A - 3000A 120V - 600V

Number of Poles Transition Type Enclosure Type Controller

3 4

bull Standard (Open)

bull Closed

bull Delayed

bull Bypass

bull NEMA 1

bull NEMA 3R

bull NEMA 4

bull NEMA 4X

bull NEMA 12

bull Open Style

bull MX350 bull MX250

Amperage Width Height Depth

1000

2000

3000

bull 365rdquo

bull 365rdquo

bull 365rdquo

bull 90rdquo

bull 90rdquo

bull 90rdquo

bull 235rdquo

bull 235rdquo

bull 385rdquo

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 9: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

UL Definition The maximum amount of fault current a switch can withstand at a specified voltage for a given amount of time and remain functional

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Short-Time Rated ATS

STR ATS vs WCR ATS

STR WCR

Withstand a Fault Event Yes Yes

Close-on to a Fault Event Yes Yes

Temperature Rise Test Yes No

Must be Functional after Fault Event on the tested contact

Yes No

Deliver 100 Power to Load after a Fault Event Yes No

Per UL 1008 standards

MDS WiYZTM Considerations

1 Short time pickup value (Amp)

2 Short time clear time

3 ST coordination between devices

4 Voltage amp fault current

5 The upstream device must clear a fault in a timeframe that is le the short time rating of the switch

a) 3 cycles=3x0016=0048s=48ms

b) 10 cycles =10x0016 = 016s=160ms

c) 18 cycles =18x0016 =0288s= 288ms

d) 30 cycles = 30x0016 = 048s=480ms

10 Cycle 18 Cycle or 30 Cycle ATS

N E

X

Instantaneous is either

bull Off ndash LVPCB

bull Set higher than available 3

phase bolted fault current

Typical 600AF 600AT MCCB adjustable inst max = 6072 Tracking ST (not adjustable)

Fixed ST delay clear range ~0192s to 046s = 12 to 29 cycles

~ 10 cycles- 016s but may not clear for faults below instantaneous pickup

~ 18 cycles=0288s

~ 30 cycles=048s

~ 3 cycleshellipfor purposes of conversation the inst PU is set above available fault current

Typical MCCB bull No adjustable ST pickup bull No adjustable ST delay

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

MDS WiYZTM

MCCB with independently adjustable

bull Short time pickup

bull Short time delay

bull Clear times range from ~ 4 to ~30+ cycles

~42 cycles

max

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

10 Cycle 18 Cycle or 30 Cycle ATS LVPCB Clearing with ST instantaneous turned off

MDS WiYZTM

Selective Coordination

Achieving selective coordination by the short time protection of an upstream breaker

The short time clearing time gt 3 cycle le 30 cycle

More Reliable Robust Switch

The short time test is the most stringent version amp ensures a more robust ATS is used in critical circuit applications

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Why use a 30 cycle ATS

Imagination at work

GE Zenith 30 Cycle ATS ZT30 Product Overview

End User

Eliminate Outages amp

Cost Optimization

Designer

Design to Codes amp Customer Options AHJ

Uphold Codes

Future Smart Grid

Total Cost Ownership w ATS

ZT30 Product Overview 30-Cycle ATS

Product Series Amperage Range Voltage Range

ZT30 1000A - 3000A 120V - 600V

Number of Poles Transition Type Enclosure Type Controller

3 4

bull Standard (Open)

bull Closed

bull Delayed

bull Bypass

bull NEMA 1

bull NEMA 3R

bull NEMA 4

bull NEMA 4X

bull NEMA 12

bull Open Style

bull MX350 bull MX250

Amperage Width Height Depth

1000

2000

3000

bull 365rdquo

bull 365rdquo

bull 365rdquo

bull 90rdquo

bull 90rdquo

bull 90rdquo

bull 235rdquo

bull 235rdquo

bull 385rdquo

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 10: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

STR ATS vs WCR ATS

STR WCR

Withstand a Fault Event Yes Yes

Close-on to a Fault Event Yes Yes

Temperature Rise Test Yes No

Must be Functional after Fault Event on the tested contact

Yes No

Deliver 100 Power to Load after a Fault Event Yes No

Per UL 1008 standards

MDS WiYZTM Considerations

1 Short time pickup value (Amp)

2 Short time clear time

3 ST coordination between devices

4 Voltage amp fault current

5 The upstream device must clear a fault in a timeframe that is le the short time rating of the switch

a) 3 cycles=3x0016=0048s=48ms

b) 10 cycles =10x0016 = 016s=160ms

c) 18 cycles =18x0016 =0288s= 288ms

d) 30 cycles = 30x0016 = 048s=480ms

10 Cycle 18 Cycle or 30 Cycle ATS

N E

X

Instantaneous is either

bull Off ndash LVPCB

bull Set higher than available 3

phase bolted fault current

Typical 600AF 600AT MCCB adjustable inst max = 6072 Tracking ST (not adjustable)

Fixed ST delay clear range ~0192s to 046s = 12 to 29 cycles

~ 10 cycles- 016s but may not clear for faults below instantaneous pickup

~ 18 cycles=0288s

~ 30 cycles=048s

~ 3 cycleshellipfor purposes of conversation the inst PU is set above available fault current

Typical MCCB bull No adjustable ST pickup bull No adjustable ST delay

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

MDS WiYZTM

MCCB with independently adjustable

bull Short time pickup

bull Short time delay

bull Clear times range from ~ 4 to ~30+ cycles

~42 cycles

max

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

10 Cycle 18 Cycle or 30 Cycle ATS LVPCB Clearing with ST instantaneous turned off

MDS WiYZTM

Selective Coordination

Achieving selective coordination by the short time protection of an upstream breaker

The short time clearing time gt 3 cycle le 30 cycle

More Reliable Robust Switch

The short time test is the most stringent version amp ensures a more robust ATS is used in critical circuit applications

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Why use a 30 cycle ATS

Imagination at work

GE Zenith 30 Cycle ATS ZT30 Product Overview

End User

Eliminate Outages amp

Cost Optimization

Designer

Design to Codes amp Customer Options AHJ

Uphold Codes

Future Smart Grid

Total Cost Ownership w ATS

ZT30 Product Overview 30-Cycle ATS

Product Series Amperage Range Voltage Range

ZT30 1000A - 3000A 120V - 600V

Number of Poles Transition Type Enclosure Type Controller

3 4

bull Standard (Open)

bull Closed

bull Delayed

bull Bypass

bull NEMA 1

bull NEMA 3R

bull NEMA 4

bull NEMA 4X

bull NEMA 12

bull Open Style

bull MX350 bull MX250

Amperage Width Height Depth

1000

2000

3000

bull 365rdquo

bull 365rdquo

bull 365rdquo

bull 90rdquo

bull 90rdquo

bull 90rdquo

bull 235rdquo

bull 235rdquo

bull 385rdquo

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 11: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

MDS WiYZTM Considerations

1 Short time pickup value (Amp)

2 Short time clear time

3 ST coordination between devices

4 Voltage amp fault current

5 The upstream device must clear a fault in a timeframe that is le the short time rating of the switch

a) 3 cycles=3x0016=0048s=48ms

b) 10 cycles =10x0016 = 016s=160ms

c) 18 cycles =18x0016 =0288s= 288ms

d) 30 cycles = 30x0016 = 048s=480ms

10 Cycle 18 Cycle or 30 Cycle ATS

N E

X

Instantaneous is either

bull Off ndash LVPCB

bull Set higher than available 3

phase bolted fault current

Typical 600AF 600AT MCCB adjustable inst max = 6072 Tracking ST (not adjustable)

Fixed ST delay clear range ~0192s to 046s = 12 to 29 cycles

~ 10 cycles- 016s but may not clear for faults below instantaneous pickup

~ 18 cycles=0288s

~ 30 cycles=048s

~ 3 cycleshellipfor purposes of conversation the inst PU is set above available fault current

Typical MCCB bull No adjustable ST pickup bull No adjustable ST delay

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

MDS WiYZTM

MCCB with independently adjustable

bull Short time pickup

bull Short time delay

bull Clear times range from ~ 4 to ~30+ cycles

~42 cycles

max

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

10 Cycle 18 Cycle or 30 Cycle ATS LVPCB Clearing with ST instantaneous turned off

MDS WiYZTM

Selective Coordination

Achieving selective coordination by the short time protection of an upstream breaker

The short time clearing time gt 3 cycle le 30 cycle

More Reliable Robust Switch

The short time test is the most stringent version amp ensures a more robust ATS is used in critical circuit applications

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Why use a 30 cycle ATS

Imagination at work

GE Zenith 30 Cycle ATS ZT30 Product Overview

End User

Eliminate Outages amp

Cost Optimization

Designer

Design to Codes amp Customer Options AHJ

Uphold Codes

Future Smart Grid

Total Cost Ownership w ATS

ZT30 Product Overview 30-Cycle ATS

Product Series Amperage Range Voltage Range

ZT30 1000A - 3000A 120V - 600V

Number of Poles Transition Type Enclosure Type Controller

3 4

bull Standard (Open)

bull Closed

bull Delayed

bull Bypass

bull NEMA 1

bull NEMA 3R

bull NEMA 4

bull NEMA 4X

bull NEMA 12

bull Open Style

bull MX350 bull MX250

Amperage Width Height Depth

1000

2000

3000

bull 365rdquo

bull 365rdquo

bull 365rdquo

bull 90rdquo

bull 90rdquo

bull 90rdquo

bull 235rdquo

bull 235rdquo

bull 385rdquo

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 12: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

Typical 600AF 600AT MCCB adjustable inst max = 6072 Tracking ST (not adjustable)

Fixed ST delay clear range ~0192s to 046s = 12 to 29 cycles

~ 10 cycles- 016s but may not clear for faults below instantaneous pickup

~ 18 cycles=0288s

~ 30 cycles=048s

~ 3 cycleshellipfor purposes of conversation the inst PU is set above available fault current

Typical MCCB bull No adjustable ST pickup bull No adjustable ST delay

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

MDS WiYZTM

MCCB with independently adjustable

bull Short time pickup

bull Short time delay

bull Clear times range from ~ 4 to ~30+ cycles

~42 cycles

max

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

10 Cycle 18 Cycle or 30 Cycle ATS LVPCB Clearing with ST instantaneous turned off

MDS WiYZTM

Selective Coordination

Achieving selective coordination by the short time protection of an upstream breaker

The short time clearing time gt 3 cycle le 30 cycle

More Reliable Robust Switch

The short time test is the most stringent version amp ensures a more robust ATS is used in critical circuit applications

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Why use a 30 cycle ATS

Imagination at work

GE Zenith 30 Cycle ATS ZT30 Product Overview

End User

Eliminate Outages amp

Cost Optimization

Designer

Design to Codes amp Customer Options AHJ

Uphold Codes

Future Smart Grid

Total Cost Ownership w ATS

ZT30 Product Overview 30-Cycle ATS

Product Series Amperage Range Voltage Range

ZT30 1000A - 3000A 120V - 600V

Number of Poles Transition Type Enclosure Type Controller

3 4

bull Standard (Open)

bull Closed

bull Delayed

bull Bypass

bull NEMA 1

bull NEMA 3R

bull NEMA 4

bull NEMA 4X

bull NEMA 12

bull Open Style

bull MX350 bull MX250

Amperage Width Height Depth

1000

2000

3000

bull 365rdquo

bull 365rdquo

bull 365rdquo

bull 90rdquo

bull 90rdquo

bull 90rdquo

bull 235rdquo

bull 235rdquo

bull 385rdquo

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 13: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

MDS WiYZTM

MCCB with independently adjustable

bull Short time pickup

bull Short time delay

bull Clear times range from ~ 4 to ~30+ cycles

~42 cycles

max

10 Cycle 18 Cycle or 30 Cycle ATS MCCB Clearing with ST band inst set gt available fault current

10 Cycle 18 Cycle or 30 Cycle ATS LVPCB Clearing with ST instantaneous turned off

MDS WiYZTM

Selective Coordination

Achieving selective coordination by the short time protection of an upstream breaker

The short time clearing time gt 3 cycle le 30 cycle

More Reliable Robust Switch

The short time test is the most stringent version amp ensures a more robust ATS is used in critical circuit applications

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Why use a 30 cycle ATS

Imagination at work

GE Zenith 30 Cycle ATS ZT30 Product Overview

End User

Eliminate Outages amp

Cost Optimization

Designer

Design to Codes amp Customer Options AHJ

Uphold Codes

Future Smart Grid

Total Cost Ownership w ATS

ZT30 Product Overview 30-Cycle ATS

Product Series Amperage Range Voltage Range

ZT30 1000A - 3000A 120V - 600V

Number of Poles Transition Type Enclosure Type Controller

3 4

bull Standard (Open)

bull Closed

bull Delayed

bull Bypass

bull NEMA 1

bull NEMA 3R

bull NEMA 4

bull NEMA 4X

bull NEMA 12

bull Open Style

bull MX350 bull MX250

Amperage Width Height Depth

1000

2000

3000

bull 365rdquo

bull 365rdquo

bull 365rdquo

bull 90rdquo

bull 90rdquo

bull 90rdquo

bull 235rdquo

bull 235rdquo

bull 385rdquo

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 14: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

10 Cycle 18 Cycle or 30 Cycle ATS LVPCB Clearing with ST instantaneous turned off

MDS WiYZTM

Selective Coordination

Achieving selective coordination by the short time protection of an upstream breaker

The short time clearing time gt 3 cycle le 30 cycle

More Reliable Robust Switch

The short time test is the most stringent version amp ensures a more robust ATS is used in critical circuit applications

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Why use a 30 cycle ATS

Imagination at work

GE Zenith 30 Cycle ATS ZT30 Product Overview

End User

Eliminate Outages amp

Cost Optimization

Designer

Design to Codes amp Customer Options AHJ

Uphold Codes

Future Smart Grid

Total Cost Ownership w ATS

ZT30 Product Overview 30-Cycle ATS

Product Series Amperage Range Voltage Range

ZT30 1000A - 3000A 120V - 600V

Number of Poles Transition Type Enclosure Type Controller

3 4

bull Standard (Open)

bull Closed

bull Delayed

bull Bypass

bull NEMA 1

bull NEMA 3R

bull NEMA 4

bull NEMA 4X

bull NEMA 12

bull Open Style

bull MX350 bull MX250

Amperage Width Height Depth

1000

2000

3000

bull 365rdquo

bull 365rdquo

bull 365rdquo

bull 90rdquo

bull 90rdquo

bull 90rdquo

bull 235rdquo

bull 235rdquo

bull 385rdquo

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 15: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

MDS WiYZTM

Selective Coordination

Achieving selective coordination by the short time protection of an upstream breaker

The short time clearing time gt 3 cycle le 30 cycle

More Reliable Robust Switch

The short time test is the most stringent version amp ensures a more robust ATS is used in critical circuit applications

To attain UL Short-Time Rating a transfer switch must undergo and pass

Withstand and Close Test

Temperature Test

Repeated Withstand Test

Why use a 30 cycle ATS

Imagination at work

GE Zenith 30 Cycle ATS ZT30 Product Overview

End User

Eliminate Outages amp

Cost Optimization

Designer

Design to Codes amp Customer Options AHJ

Uphold Codes

Future Smart Grid

Total Cost Ownership w ATS

ZT30 Product Overview 30-Cycle ATS

Product Series Amperage Range Voltage Range

ZT30 1000A - 3000A 120V - 600V

Number of Poles Transition Type Enclosure Type Controller

3 4

bull Standard (Open)

bull Closed

bull Delayed

bull Bypass

bull NEMA 1

bull NEMA 3R

bull NEMA 4

bull NEMA 4X

bull NEMA 12

bull Open Style

bull MX350 bull MX250

Amperage Width Height Depth

1000

2000

3000

bull 365rdquo

bull 365rdquo

bull 365rdquo

bull 90rdquo

bull 90rdquo

bull 90rdquo

bull 235rdquo

bull 235rdquo

bull 385rdquo

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 16: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

Imagination at work

GE Zenith 30 Cycle ATS ZT30 Product Overview

End User

Eliminate Outages amp

Cost Optimization

Designer

Design to Codes amp Customer Options AHJ

Uphold Codes

Future Smart Grid

Total Cost Ownership w ATS

ZT30 Product Overview 30-Cycle ATS

Product Series Amperage Range Voltage Range

ZT30 1000A - 3000A 120V - 600V

Number of Poles Transition Type Enclosure Type Controller

3 4

bull Standard (Open)

bull Closed

bull Delayed

bull Bypass

bull NEMA 1

bull NEMA 3R

bull NEMA 4

bull NEMA 4X

bull NEMA 12

bull Open Style

bull MX350 bull MX250

Amperage Width Height Depth

1000

2000

3000

bull 365rdquo

bull 365rdquo

bull 365rdquo

bull 90rdquo

bull 90rdquo

bull 90rdquo

bull 235rdquo

bull 235rdquo

bull 385rdquo

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 17: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

End User

Eliminate Outages amp

Cost Optimization

Designer

Design to Codes amp Customer Options AHJ

Uphold Codes

Future Smart Grid

Total Cost Ownership w ATS

ZT30 Product Overview 30-Cycle ATS

Product Series Amperage Range Voltage Range

ZT30 1000A - 3000A 120V - 600V

Number of Poles Transition Type Enclosure Type Controller

3 4

bull Standard (Open)

bull Closed

bull Delayed

bull Bypass

bull NEMA 1

bull NEMA 3R

bull NEMA 4

bull NEMA 4X

bull NEMA 12

bull Open Style

bull MX350 bull MX250

Amperage Width Height Depth

1000

2000

3000

bull 365rdquo

bull 365rdquo

bull 365rdquo

bull 90rdquo

bull 90rdquo

bull 90rdquo

bull 235rdquo

bull 235rdquo

bull 385rdquo

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 18: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

ZT30 Product Overview 30-Cycle ATS

Product Series Amperage Range Voltage Range

ZT30 1000A - 3000A 120V - 600V

Number of Poles Transition Type Enclosure Type Controller

3 4

bull Standard (Open)

bull Closed

bull Delayed

bull Bypass

bull NEMA 1

bull NEMA 3R

bull NEMA 4

bull NEMA 4X

bull NEMA 12

bull Open Style

bull MX350 bull MX250

Amperage Width Height Depth

1000

2000

3000

bull 365rdquo

bull 365rdquo

bull 365rdquo

bull 90rdquo

bull 90rdquo

bull 90rdquo

bull 235rdquo

bull 235rdquo

bull 385rdquo

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 19: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

Features Short Time Rating

85kA 30 Cycle (05s)

100kA 3 cycle

Withstand and Close-on Rating

100kA 3 Cycle

200kA with Current Limiting Fuse Class L

Supplies 100 rated power to loads after overcurrent event

Transfer Time

Standard (Open) Transition ~ 30ms to 70ms

Delayed Transition ~ 80ms (Customer Programmable Time

Delay Setting)

Closed Transition Less than 100ms parallel

Certifications ULcUL rated up to 600V at 5060Hz Seismic Qualified to IBC-2009 amp IEEE 693-2005 OSHPD

ZT30 Product Overview

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 20: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

30-Cycle ATS UL 1008 testedlabeled bull Industry-leading 30-cycle UL short-time rating for withstand

and close-on for maximized system availability

bull Allows for true short-time selective coordination system design

Key Benefits

bullReliability Performance

bullSafety

bullEase of Use Maintenance

bullSpace Optimization Flexibility

ZT30 Meets New Expectations

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 21: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

Reliability Performance Industry-leading durability and fault tolerance

bull Maximizes system uptimereliability

Withstands and closes on a fault

Supplies 100 rated power to loads after overcurrent event

85 kA Short-Time Rating (05s)

ZT30 Product Highlights

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 22: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

Safety Manual Quick Make Quick Break ZT30 ATS enables operators to perform manual

transfers with the door closed

Manual transfers can be performed on a fully loaded switch (just as fast as electric transfer)

Allows operators to put switch in open position (load disconnected from both source) when performing manual operation for added safety

ZT30 Product Highlights

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 23: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

Safety Optional ldquoShutter Systemrdquo Adds another layer of protection

during maintenance

ZT30 Product Highlights

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 24: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

Ease of Use Flexibility Centralized Terminal Connection

bull Multi-tap transformer enables operation on a wide range of

system voltages

bull Centralized location for customer connections

ZT30 Product Highlights

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 25: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

Ease of Use Maintenance Mechanical Position Indicators enable personnel to quickly

determine switch position

ZT30 Product Highlights

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 26: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

Ease of Use Maintenance Plug amp Play Interchangeable Source Cable Kit

bull Enables installers to quickly reconfigure the designation of

Source 1 and Source 2 lugs without any physical reconfiguration

ZT30 Product Highlights

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 27: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

Space Optimization Flexibility Small Footprint Panel Removal TopBottom Cable Entry

bull Removable panels provide for space optimization and easy

maintenance access

bull Bypass-Isolation Transfer Switch

ZT30 Product Highlights

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 28: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

MX 250

Voltage amp Frequency Sensing

Synchro-Scope

Voltage Imbalance Detection

Phase Rotation Check

Communications

MX 250 Processor Highlights

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 29: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

Power Quality Metering

Event Recording

Networking

MX 350 Processor Highlights

MX 350

Facility Integration and Diagnostic Reporting

Advanced User Interface amp Controls

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 30: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

MX 350 Processor Details

Microprocessor Input Controls Q2 Remote Test

Q3 Remote inhibit transfer to Source 2

Q7 Remote inhibit transfer to Source 1

R15D Load shed

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 31: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

Internal Components

ZT30 Thermal amp Electromagnetic Capabilities

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 32: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

GE ZT30 Summary 1) Meets UL Safety Standard

1) Withstand a 30-cycle short circuit fault

2) Reliability

1) Withstand a 30-cycle short circuit fault

2) Closing onto another 30-cycle short circuit fault

3) Smaller Footprint

ZT30 Product Conclusion

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 33: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

References and Contact Info GE Critical Power website

httpwwwgeindustrialcomproductscritical-power GE ZT30-30 Cycle ATS website

httpwwwgeindustrialcomproductsautomatic-transfer-switcheszt30-series-30-cycle-critical-applications

GE ZT30-30 Cycle ATS publication httpappsgeindustrialcompublibrarycheckoutDEA-

571TNR=Brochures7CDEA-

5717CPDFampfilename=2417_GE_ZT30_ATbrochure_NoCrop-TBpdf

Contact Information OzgurCosargecom RyanBergerongecom

Questions

Page 34: GE Technical Tuesday 30-Cycle ATS: Understanding Emergency ... · Selective Coordination: Achieving selective coordination by the short time protection of an upstream breaker The

Questions