GE Power Switching & Controls
63 kA Power/Vac
Metalclad Switchgear
4.76 kV - 500 MVA8.25 kV - 900 MVA15.0 kV - 1500 MVA
An expanded offering fromGE PS&C Switchgear -exceeds the latest ANSI C37.06recommended ratings
Applications
Close/eliminate bus ties
Reduce/eliminate need forcurrent-limiting reactors orhigher impedance transformers
Simplify large motor startingrequirements
Provide protection for largergenerators and transformers
Retrofit/upgrade existingPower/Vac installations
7/30/2019 Ge Swgear Det-324
2/2
gGE Power Switching & Controls
General Electric Company510 East Agency RoadWest Burlington, IA 52655
DET-324
63 kA Rated Power/Vac
Metalclad Switchgear
Product Description 63kA rated, 1kV to 15kV
Available as new metalclad switchgear equipment
and retrofit/upgrade equipment for existingPower/Vac installations
Based on the ML-17 breaker mechanism which has
more than 25 years of excellent field experience
Manufactured by GE PS&C Switchgear Operation
in Burlington, Iowa qualified as an ISO-9002
manufacturer since 1992
UL and CSA listings available as an option
BenefitsEXPANDED RATINGS
Expanded metalclad switchgear ratings provide greaterdesign flexibility by permitting alternative choices for system
configuration, equipment type and protection.
EASY UPGRADES on EXISTING POWER/VAC
Retrofit upgrades on most existing Power/Vac can be achieved
without total system redesign; simply replace the breakers with
this higher rating and modify the bus bracing. The physical size
of this breaker is the same as that of other Power/Vac breakers.
ENHANCED RELIABILITY
System reliability is enhanced by allowing system sourcesto remain on-line, eliminating source transfers, optimizing
processes and accomodating increased short circuit ratings
from motors.
COST and SPACE SAVINGS
Total system cost savings - including equipment, space,
installation and operating losses - cost reductions are
achievable through the reduction/elimination of mutliple
bus ties, current limiting reactors, high impedance
transformers and complex motor starting schemes.
IMPROVING POWER QUALITY
By simplifying system design, installation and operation,this higher rating allows the user to achieve more
consistant power quality.
SAFE OPERATION
Vacuum interrupters are housed in insulated support
barriers, providing a greater degree of isolation between
phases. Vertical insulation prevents ready adherence of
contaminants, which can cause tracking and flashover.
Technical Data Summary
Nominal Voltage Range 4.16kV 7.2kV 13.8kVRated Maximum Voltage 4.76kV 8.25kV 15.0kV
Rated Short Circuit Current 63kA
Nominal MVA Class 500MVA 900MVA 1500MVA
Voltage Range Factor (K) 1.0
Frequency 50/60 Hz
Continuous Current
@ 60 Hz Amps 1200, 2000, 3000, 3500 or 4000
Low Frequency Withstand
1 Minute Dry 19kV 36kV 36kV
Impulse Voltage B.L.L. 60kV 95kV 95kV
Duty Cycle CO + 15s + CO
Interrupting Time 5 Cycles
Assymetry Factor (S) 1.1
Close and Latch Capability 170kA
3 sec. Short TimeCurrent Capability 63kA
Transient Recovery Voltage 8.9kV 15.5kV 28.2kV
Reclosing Time < 10 Cycles
Reclosing Duty Factor (R) 100%
# of Operation - No Load 10,000
# of Op. - Between Servicing 2,000
Spare Auxiliary Switch Contacts 2a, 3b
Operator Designation ML-17H
Control Voltage Close Coil
and Monitor 48V, 125V, 250V DC;
120V, 240V AC
Trip Coil 48V, 125V, 250V DC;
240V AC requires separate
capacitor trip unit