    GE Power Switching & Controls

    63 kA Power/Vac

    Metalclad Switchgear

    4.76 kV - 500 MVA8.25 kV - 900 MVA15.0 kV - 1500 MVA

    An expanded offering fromGE PS&C Switchgear -exceeds the latest ANSI C37.06recommended ratings

    Applications

    Close/eliminate bus ties

    Reduce/eliminate need forcurrent-limiting reactors orhigher impedance transformers

    Simplify large motor startingrequirements

    Provide protection for largergenerators and transformers

    Retrofit/upgrade existingPower/Vac installations

  • 7/30/2019 Ge Swgear Det-324

    2/2

    gGE Power Switching & Controls

    General Electric Company510 East Agency RoadWest Burlington, IA 52655

    DET-324

    63 kA Rated Power/Vac

    Metalclad Switchgear

    Product Description 63kA rated, 1kV to 15kV

    Available as new metalclad switchgear equipment

    and retrofit/upgrade equipment for existingPower/Vac installations

    Based on the ML-17 breaker mechanism which has

    more than 25 years of excellent field experience

    Manufactured by GE PS&C Switchgear Operation

    in Burlington, Iowa qualified as an ISO-9002

    manufacturer since 1992

    UL and CSA listings available as an option

    BenefitsEXPANDED RATINGS

    Expanded metalclad switchgear ratings provide greaterdesign flexibility by permitting alternative choices for system

    configuration, equipment type and protection.

    EASY UPGRADES on EXISTING POWER/VAC

    Retrofit upgrades on most existing Power/Vac can be achieved

    without total system redesign; simply replace the breakers with

    this higher rating and modify the bus bracing. The physical size

    of this breaker is the same as that of other Power/Vac breakers.

    ENHANCED RELIABILITY

    System reliability is enhanced by allowing system sourcesto remain on-line, eliminating source transfers, optimizing

    processes and accomodating increased short circuit ratings

    from motors.

    COST and SPACE SAVINGS

    Total system cost savings - including equipment, space,

    installation and operating losses - cost reductions are

    achievable through the reduction/elimination of mutliple

    bus ties, current limiting reactors, high impedance

    transformers and complex motor starting schemes.

    IMPROVING POWER QUALITY

    By simplifying system design, installation and operation,this higher rating allows the user to achieve more

    consistant power quality.

    SAFE OPERATION

    Vacuum interrupters are housed in insulated support

    barriers, providing a greater degree of isolation between

    phases. Vertical insulation prevents ready adherence of

    contaminants, which can cause tracking and flashover.

    Technical Data Summary

    Nominal Voltage Range 4.16kV 7.2kV 13.8kVRated Maximum Voltage 4.76kV 8.25kV 15.0kV

    Rated Short Circuit Current 63kA

    Nominal MVA Class 500MVA 900MVA 1500MVA

    Voltage Range Factor (K) 1.0

    Frequency 50/60 Hz

    Continuous Current

    @ 60 Hz Amps 1200, 2000, 3000, 3500 or 4000

    Low Frequency Withstand

    1 Minute Dry 19kV 36kV 36kV

    Impulse Voltage B.L.L. 60kV 95kV 95kV

    Duty Cycle CO + 15s + CO

    Interrupting Time 5 Cycles

    Assymetry Factor (S) 1.1

    Close and Latch Capability 170kA

    3 sec. Short TimeCurrent Capability 63kA

    Transient Recovery Voltage 8.9kV 15.5kV 28.2kV

    Reclosing Time < 10 Cycles

    Reclosing Duty Factor (R) 100%

    # of Operation - No Load 10,000

    # of Op. - Between Servicing 2,000

    Spare Auxiliary Switch Contacts 2a, 3b

    Operator Designation ML-17H

    Control Voltage Close Coil

    and Monitor 48V, 125V, 250V DC;

    120V, 240V AC

    Trip Coil 48V, 125V, 250V DC;

    240V AC requires separate

    capacitor trip unit