GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage Control Technical Conference 2/ GE WTG Dynamic Models Two classes of models: DFG and FC

GE Energy Voltage And Reactive Power Control - BPA.gov Business/TechnologyInnovation... · GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage

Embed Size (px)

Citation preview

Page 1: GE Energy Voltage And Reactive Power Control - BPA.gov Business/TechnologyInnovation... · GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage

GE Energy

Voltage And Reactive Power Control

Nicholas W. Miller

August 23, 2011BPA Voltage Control Technical Conference

2 /

GE WTG Dynamic Models

Two classes of models: DFG and FC

Page 2: GE Energy Voltage And Reactive Power Control - BPA.gov Business/TechnologyInnovation... · GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage

3

GE Energy

WTG Reactive Power Capability

• Full leading and lagging range over full power range

• Faster reactive response than synch. generator

• Capability of reactive compensation with no wind

• Behavior like a FACTS devices

4

GE Energy

Voltage at POI

Wind Plant Power Output

Voltage & Reactive Power ControlsActual measurements from a

162MW wind plant

Wind Plant Voltage

• Regulates Grid Voltage at Point of Interconnection

• Minimizes Grid Voltage Fluctuations Even Under Varying Wind Conditions

• Regulates Total Wind Plant Reactive Power through Control of Individual Turbines

Average Wind Speed

Voltage and Reactive Power RegulationLike A Conventional Power Plant…with FACTS speed

Page 3: GE Energy Voltage And Reactive Power Control - BPA.gov Business/TechnologyInnovation... · GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage

5

GE Energy

Tu

rbin

e k

VA

R

75

Time (seconds)

15000

1500

Tu

rbin

e k

VA

R

75

Time (seconds)

15000

1500

WindFREE Reactive Power

• Wind Turbine converter can deliver reactive power (kVAR) without wind (kW)

• Benefits weak grids and systems with high wind penetration

• Voltage support continues without active power generation…even following trips

Active

Power

(zero)

Reactive

Power

Field Test Results (2.5 unit)

Reactive Power - even without wind:A valuable option – An unreasonable requirement

6

GE Energy

The following 11 figures are from IEEE panel session paper:

“Validation of GE Wind Plant Models for System Planning

Simulations

Electric Machinery Committee

IEEE Power & Energy Society General Meeting

Jason MacDowell

Kara Clark

Nick Miller

Juan Sanchez-Gasca

July 25, 2011, IEEE General Power Meeting Detroit

Page 4: GE Energy Voltage And Reactive Power Control - BPA.gov Business/TechnologyInnovation... · GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage

7 /

High Side Bus (collector, e.g. 34.5kV) Terminal Bus

P gen

Q gen

Vreg bus Vterm

Project Substation

Unit Transformer

Point of Interconnection

(POI) Bus

Substation Transformer

CollectorEquivalentImpedance

GE 1.5 MW machines offered in a range of steady-state reactive power capabilities at their terminals. A common range:

• 0.90 pf overexcited (delivering 730 kVARs to the system)• 0.90 pf underexcited (drawing 730 kVARs from system)

Frequently provides +/- 0.95 pf at POI

The supervisory control will instruct individual machines to adjust their reactive power output in order to regulate system voltage; normally at the point-of-interconnection

Volt/Var Control for Application Studies

8 /

Vreg

Kiv

s+

Vref reg

1

1+ sTc

11+ sTr

Qord

-Kpv

1+ sTv

+

+

ΠΠΠΠVref qd

-

11+ sTlpqd

Kqd

QPOI

+

+

Qgen

Vref term

Vterm

KVi

s

XIQmax

Eq"cmd

XIQmin

KQi

s

-

-

+

Test

Signal

Slow Plant Level

Voltage Regulator

(WindCONTROL Emulation)

Fast Turbine Level

Voltage Regulator

Intermediate Turbine Level

Reactive Power Regulator

Verror

Vterm

IQcmd

Ipmx IPcmd

-Iqmn

Iqmx

to generator /

converter model

Converter

Current LimitP,Q priority flag

+

Doubly Fed

Full

Converter

to generator /

converter model

+

KVi

s

TestSignal

Vref qd

Pord

Vterm

Ipmx*

IPcmd

PelecPdbr

from wind

turbine model

from generator /

converter model

Dynamic Braking

Resistor to wind

turbine model

to generator /

converter model

Doubly

Fed

Full

Converter

* Ipmx is fixed for the doubly fed model, or calculated by the converter current limit

function for the full converter model.

Plant and WTG Electrical Control

Page 5: GE Energy Voltage And Reactive Power Control - BPA.gov Business/TechnologyInnovation... · GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage

9 /

Vreg

Kiv

s+

Vref reg

1

1+ sTc

11+ sTr

Qord

-Kpv

1+ sTv

+

+

ΠΠΠΠVref qd

-

11+ sTlpqd

Kqd

QPOI

+

+

Qgen

Vref term

Vterm

KVi

s

XIQmax

Eq"cmd

XIQmin

KQi

s

-

-

+

Test

Signal

Slow Plant Level

Voltage Regulator

(WindCONTROL Emulation)

Fast Turbine Level

Voltage Regulator

Intermediate Turbine Level

Reactive Power Regulator

Verror

Vterm

IQcmd

Ipmx IPcmd

-Iqmn

Iqmx

to generator /

converter model

Converter

Current LimitP,Q priority flag

+

Doubly Fed

Full

Converter

to generator /

converter model

+

KVi

s

TestSignal

Vref qd

Pord

Vterm

Ipmx*

IPcmd

PelecPdbr

from wind

turbine model

from generator /

converter model

Dynamic Braking

Resistor to wind

turbine model

to generator /

converter model

Doubly

Fed

Full

Converter

* Ipmx is fixed for the doubly fed model, or calculated by the converter current limit

function for the full converter model.

Plant and WTG Electrical Control

10 /

Model Validation – Field Test Results

Page 6: GE Energy Voltage And Reactive Power Control - BPA.gov Business/TechnologyInnovation... · GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage

11 /

Volt/Var Control

Vreg

WindCONTROL Emulator

Kiv/s+

Vrfq

(vref)

1

1+ sTc

1

1+ sTr

Qmax

Qmin

1/fN Qord

s5

s4

s3

-Kpv

1+ sTv

s2

Qwv

+

+

Vqd

-

Vermx

Vermn

< Vfrz?

If yes, freeze

2 integrators

From Q Droop

Function

Slower Plant-Level Control

++

Qcmd

Qgen

Vref

Vmax

Vterm

KVi / s

XIQmax

Vmin

Eq"cmd

To Generator

Model

s0

s1

XIQmin

KQi / s

(efd)

--

+

( model[@index].sigval[0] )

Auxiliary Test Signal

Slower WTG Q Control Fast WTG V Control

12 /

Individual WTG Test

• Test fast response of individual turbine

• 3% positive step, slow reset

++

Qcmd

Qgen

Vref

Vmax

Vterm

KVi / s

XIQmax

Vmin

Eq"cmd

To Generator

Model

s0

s1

XIQmin

KQi / s

(efd)

--

+

( model[@index].sigval[0] )

Auxiliary Test Signal

Voltage Step Stimulus

Page 7: GE Energy Voltage And Reactive Power Control - BPA.gov Business/TechnologyInnovation... · GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage

13 /

Unit Internal Voltage Reference Step Test

0

400

800

1200

1600

0 10 20 30 40 50 60 70 80 90 100

Seconds (50ms sample)

kV

APwr

QPwrGrid

Q PSLF

WTG Reactive Power ResponseP

Q

Q - Model

Unit Internal Voltage Reference Step Test

Model replicates equipment response

Full response in ~200 ms

14 /

Unit Internal Voltage Reference Step Test

0

300

600

900

1200

1500

25 26 27 28 29 30 31 32 33 34 35

Seconds (50ms sample)

kV

A

Pwr

QPwrGrid

Q PSLF

Detail - WTG Reactive Power Response

P

Q

Q - Model

Full response in ~200 ms

Unit Internal Voltage Reference Step Test

10x expanded time scale

Page 8: GE Energy Voltage And Reactive Power Control - BPA.gov Business/TechnologyInnovation... · GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage

15 /

Plant Level Volt/Var Test

VPOI WindCONTROL

Qwtg

nQcmd

Vmeas

Imeas

VTerm

Shunt Bank(s):

Manually switched

for test stimulus

Pwtg

P PLANT

Q PLANT

Qcmd i

Switch Off 10 MVAr Shunt Capacitor

16 /

Model closely replicates field response

Field Test vs. Simulation – Reactive Power and Voltage

24650

24900

25150

25400

0 10 20 30 40

kV

Seconds

V POI - MODEL

V POI - TEST

V REFERENCE

-1000

1000

3000

5000

7000

9000

11000

0 10 20 30 40

kVAR

Seconds

Q_ACTUAL - TEST

Q POI- MODEL

Q_CMD - TESTQ ord - MODEL

Q_TURBINES - TEST

Q gen - MODELCap Bank

Switched Offline

Page 9: GE Energy Voltage And Reactive Power Control - BPA.gov Business/TechnologyInnovation... · GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage

17 /

Cap Switching Test vs. Model – (100 MW Plant)

0 1 2 3 4 5 6 7 8 9 10 Seconds

0.985

0.99

0.995

1

1.005

Vpoi (p

u)

W42: V POI (Blue = Measured Green = Simulated) [(W10)|overplot(W45)]

0 1 2 3 4 5 6 7 8 9 10 Seconds

-20

-10

0

10

Qcm

d (

MV

Ar)

W44: Qcmd POI (Blue = Measured Green = Simulated) [(W19)|overplot(W47*90.18)]

0 1 2 3 4 5 6 7 8 9 10 Seconds

-6

-3

0

3

6

9

Qpoi (M

VA

r)

W43: Q POI (Blue = Measured Green = Simulated) [(W14)|overplot(W46)]

POI Voltage Response

POI Q Response

Plant Qcmd

BLUE = MEASURED GREEN = SIMULATED

Very fast, if necessary

18 /

ConclusionVoltage and Reactive Control of GE Wind Plants:

• In many respects are more flexible and faster than conventional plants

• Flexibility means attention to basic planning and operation engineering needs to be applied

• Blind application of default control settings without consideration of local requirements has, upon occasion, caused problems

• Field tuning of plant supervisory control to be relatively slow (~30 seconds) has generally resulted in good grid performance; faster is possible, if necessary

• We have NEVER encountered a voltage/reactive issue than can’t be corrected

Page 10: GE Energy Voltage And Reactive Power Control - BPA.gov Business/TechnologyInnovation... · GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage

19 /

ConclusionThe GE wind models presented here are based on:

• Currently available design and test data

• Extensive engineering judgment

• The models represent actual equipment/plant behavior appropriate for bulk planning studies and have been validated via type and field tests.

These models are:

• Evolutionary and continuously updated as experience and test data are obtained

• Open and publicly available

• Able to be shared and distributed as required

Active Power Control

Nicholas W. Miller

August 23, 2011BPA Voltage Control Technical Conference

Page 11: GE Energy Voltage And Reactive Power Control - BPA.gov Business/TechnologyInnovation... · GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage

21

GE Energy

0

5000

10000

15000

20000

25000

30000

35000

4:30:00

AM

4:38:00

AM

4:46:00

AM

4:54:00

AM

5:02:00

AM

5:10:00

AM

5:18:00

AM

5:26:00

AM

5:34:00

AM

5:42:00

AM

5:50:00

AM

5:58:00

AM

6:06:00

AM

6:14:00

AM

6:22:00

AM

6:30:00

AM

Time

Pow

er

kW

0

5

10

15

20

Actual power

Wind speed

Curtailment and Ramp Rate Limits(Example 30 MW Plant)

Ramp rate limit enforced

when curtailment is

released

Curtailed to 10

MW: regulation is

very tight

22

GE Energy

Over-Frequency Droop Response

2% Frequency Increase

50% Power Reduction

Po

we

r (k

W)

Fre

qu

en

cy (

Hz)

Function is Grid Friendly with Little Opportunity Cost: A Reasonable Request

Initial Steady-State Conditions:

• 25% power reduction for 1% frequency increase

Test:

• 2% frequency ramp-up @ 0.125 Hz/sec

• 50% reduction in plant watts with 2% over-frequency

Equivalent Under-frequency Function has High Opportunity Cost: To Be Used Sparingly

Page 12: GE Energy Voltage And Reactive Power Control - BPA.gov Business/TechnologyInnovation... · GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage

23

GE Energy

Why Inertial Response: System Needs

• Increasing Dependence on Wind Power

– Large Grids with Significant Penetration of Wind Power

• Modern variable speed wind turbine-generators do not contribute to system inertia

• System inertia declines as wind generation displaces synchronous generators (which are de-committed)

• Result is deeper frequency excursions for system disturbances

• Increased risk of

– Under-frequency load shedding (UFLS)

– Cascading outages

Inertial response enabled by power electronics enables CONTROLLED performance

(not just Park’s equations!)

24

GE Energy

How does it work? Electrical Torque, Te

Mechanical Torque, Tm

• In steady-state, torques must be balanced

• When electrical torque is greater than mechanical torque, the rotation slows extracting stored inertial energy from the rotating mass

WindINERTIAtm uses controls to increase electric power during the initial stages of a significant downward frequency

event

Electrical power delivered to gridis completely controlled by power electronics

P statorF stator

P convF network

Page 13: GE Energy Voltage And Reactive Power Control - BPA.gov Business/TechnologyInnovation... · GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage

25

GE Energy

Objectives and Constraints on Inertial Controls

• Target incremental energy similar to that provided by a synchronous turbine-generator with inertia (H constant) of 3.5 pu-sec.

• Focus on functional behavior and grid response

– do not try to exactly replicate synchronous machine behavior

• Not possible to increase wind speed

• Slowing wind turbine reduces aerodynamic lift

– must avoid stall

• Must respect WTG component ratings

– mechanical loading

– converter and generator electrical ratings

• Must respect other controls

– turbulence management

– drive-train and tower loads management

26

GE Energy

Field Tests Results:

Test count:

8 m/s - 19 tests

10 m/s – 19 tests

14 m/s – 52 tests

0

300

600

900

1200

1500

1800

0 10 20 30 40 50 60 70 80

Time (Seconds)

Po

wer

(kW

)

8 m/s Avg Meas 10 m/s Avg Meas 14 m/s Avg Meas

Page 14: GE Energy Voltage And Reactive Power Control - BPA.gov Business/TechnologyInnovation... · GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage

27

GE Energy

59.4

59.5

59.6

59.7

59.8

59.9

60

60.1

0 5 10 15 20 25 30 35 40

Time (seconds)

Fre

qu

en

cy

(H

z)

No Wind

20% Wind

20% Wind with WindINERTIA

28,000

29,000

30,000

31,000

32,000

33,000

0 5 10 15 20 25 30 35 40

Time (seconds)

Po

we

r (M

W)

20% Wind

20% Wind with WindINERTIA

Inertial response reduces

and delays minimum

frequency

Margin above UFLS

increases by about

40mHz

Response in this case is

overly aggressive:

Inertia is now another

control variable that

can be tuned.

Inertial Response from Wind Generation

Minimum frequency ~12% better

Governor response

better (more headroom)

Controlled inertial power

Inertial energy

recovery

The following 4 figures are fully discussed in

IEEE paper: “Frequency Responsive Wind Plant

Controls: Impacts on Grid Performance

N.W. Miller, K. Clark, M. Shao, GE Energy, IEEE

General Power Meeting 2011, Detroit

28

GE Energy

59.4

59.5

59.6

59.7

59.8

59.9

60

60.1

0 5 10 15 20 25 30 35 40

Time (seconds)

Fre

qu

en

cy (

Hz)

20% Wind with WindINERTIA

20% Wind with Tuned WindINERTIA

28,000

29,000

30,000

31,000

32,000

33,000

0 5 10 15 20 25 30 35 40

Time (seconds)

Po

we

r (M

W)

20% Wind with WindINERTIA

20% Wind with Tuned WindINERTIA

Tuning inertial response

further improves

frequency nadir and

reduces impact of

recovery energy

Margin above UFLS

increases by about

80mHz

(i.e. case without wind is

about 20% worse than

with wind)

Tuning Inertial Response from Wind

Minimum frequency ~20% better

Tuned inertial response

Inertial energy recovery

moderated

Page 15: GE Energy Voltage And Reactive Power Control - BPA.gov Business/TechnologyInnovation... · GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage

29

GE Energy

28,000

29,000

30,000

31,000

32,000

33,000

0 5 10 15 20 25 30 35 40

Time (seconds)

Pow

er

(MW

)

20% Wind

20% Wind with Tuned WindINERTIA

20% Wind with WindINERTIA, Different Operating Point

59.4

59.5

59.6

59.7

59.8

59.9

60

60.1

0 5 10 15 20 25 30 35 40

Time (seconds)

Fre

quency (

Hz)

No Wind

20% Wind

20% Wind with Tuned WindINERTIA

20% Wind with WindINERTIA, Different Operating Point

Same initial loadflow

condition: fewer WTGs

producing the same MW

at higher wind speed

When wind speed is high,

system response is

superior throughout

Frequency Nadir/Margin to

UFLS improved by

~80mHz

Impact of Operating Point on Inertial Response

No energy recovery when wind speed greater than rated

30

GE Energy

Frequency Response Curve

0

0.2

0.4

0.6

0.8

1

1.2

0.95 0.96 0.97 0.98 0.99 1 1.01 1.02 1.03 1.04 1.05 1.06 1.07

Frequency (pu)

Active

Po

we

r O

utp

ut

(pu

)

Point

A

(Fa,Pa)

Point B

(Fb,Pbc) Point C

(Fc,Pbc)

Point D

(Fd,Pd)

From PSLF manual

WTGs reduce power very effectively.

Symmetric droops aren’t required.

Genesis of present defaults is for systems with deeper frequency nadirs… may not

be adequate for North American grids.

36mHz DB and 5% droop is present NERC guideline.

All parameters can be set/customized. Is easy

to selectively enable/disable all

frequency sensitive controls. 2 sets of

parameters allowed: SOP in Ireland.

Page 16: GE Energy Voltage And Reactive Power Control - BPA.gov Business/TechnologyInnovation... · GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage

31 /

Turbine and Turbine Control

PitchCompensation

Power Response

Rate Limit

Torque

ControlPitch

Actuator

Pitch

Control

Wind

Power

Model

Pmech ωωωωWind

Speed

θθθθ

ωωωωrotor

+

+

+

+

ωωωω

Pelec

Rotor

Model

Pdbr

from electrical

control model

+ +

TerminalBus

Frequency

Pset

Pord

Speed Reference

Function

ωωωωref

Power

Control

Active Power

Control (optional)

from generator /

converter model

to electrical

control model

1.

WindINERTIA

Control

(optional)

+

+

Doubly

Fed

FullConverter

0

-

ωωωωerr

θθθθcmdx

-

default

APC on

0.

default

WI on

GE Energy

Thanks

Page 17: GE Energy Voltage And Reactive Power Control - BPA.gov Business/TechnologyInnovation... · GE Energy Voltage And Reactive Power Control Nicholas W. Miller August 23, 2011 BPA Voltage

GE Energy

For more information or to contact us please visitwww.ge-energy.com/ease

Nicholas W. Miller

[email protected]

For more information or to contact us please visitwww.ge-energy.com/ease

Nicholas W. Miller

[email protected]