GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
Genesis Compact (GC)Series Submittal DataModels GCH/V 018B - 060B
50Hz - R22English Language/SI Units
REVISION: 03/13/03
SERIES:HZ:UNIT OF MEAS:LANGUAGE:
GC - R2250SI
ENGLISH
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
MODEL DECODER
CGC
Model TypeGC = Genesis Compact Series
036 B 3 L BH
Configuration
SU
Controls
Cabinet Insulation3 = Standard Range4 = Standard Range, Mute
0 C
Future use0 = None
Rev:. 6/19/02 A
018, 024, 030, 036, 041, 042, 048, 060Size 041 available in vertical only
Voltage & RefrigerantV = 220-240/50/1 R22U = 380-420/50/3 R22
Unit Size, Nominal kbtuhH = Horizontal, V = Vertical
Water CoilC = CopperN = Cupro-Nickel
Standard
L = Left ReturnR = Right ReturnF = Front Return, vertical 018 - 030 only
T = Topflow, vertical onlyV = Topflow - High Static, vertical onlyB = Back Discharge, horiz. onlyS = Straight Discharge, horz. onlyY = Back Discharge - High Static, horz. onlyZ = Straight Discharge - High Static, horz. only
Supply Air Options
Return Air Options
Revision LevelA = Horizontal sizes 042 - 060B = Horziontal sizes 018 - 036
B = All Vertical sizes
C = CXM ControllerD = DXM Controller
L = CXM w/LonworksM = DXM w/Lonworks
F = CXM - CE MarkG = DXM - CE Mark
H = CXM w/Lonworks - CE MarkJ = DXM w/Lonworks - CE Mark
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
PERFORMANCE DATAARI/ASHRAE/ISO 13256-1
ARI/ASHRAE/ISO 13256-1Metric (SI) Units
ModelLiquidFlow
AirFlow Cooling 30°C EWT Heating 20°C EWT Cooling 15°C EWT Heating 10°C EWT Cooling 25°C EWT Heating 0°C EWT
(l/s) (l/s) CapacityWatts
EER(W/W)
CapacityWatts
COP(W/W)
CapacityWatts
EER(W/W)
CapacityWatts
COP(W/W)
CapacityWatts
EER(W/W)
CapacityWatts
COP(W/W)
GCV/H018 0.215 236 4,671 3.6 5,529 4.2
GCV/H024 0.284 319 6,119 3.9 7,381 5.0
GCV/H030 0.353 401 6,918 3.7 8,482 4.7
GCV/H036 0.429 472 8,842 3.5 11,458 4.5
GCV041 0.498 543 9,709 3.7 11,991 4.4
GCV/H042 0.505 566 10,513 3.8 13,187 4.5
GCV/H048 0.568 649 12,107 3.8 14,693 4.9
GCV/H060 0.713 779 14,786 3.9 18,714 4.5
Cooling capacities based upon 27°C DB, 19°C WB entering air temperature Rev.: 02/14/03 B
Heating capacities based upon 20°C DB, 15°C WB entering air temperatureAll air flow is rated on high speedAll ratings based upon operation at lower voltage of dual voltage rated models
ARI/ASHRAE/ISO 13256-1English (IP) Units
ModelLiquidFlow
AirFlow Cooling 86°F EWT Heating 68°F EWT Cooling 59°F EWT Heating 50°F EWT Cooling 77°F EWT Heating 32°F EWT
(gpm) (cfm) Capacity
BtuhEER
Btuh/W Capacity
Btuh COP CapacityBtuh
EERBtuh/W
CapacityBtuh COP Capacity
BtuhEER
Btuh/W Capacity
Btuh COP
GCV/H018 3.4 500 15,937 12.3 18,865 4.2
GCV/H024 4.5 676 20,878 13.3 25,184 5.0
GCV/H030 5.6 850 23,604 12.6 28,941 4.7
GCV/H036 6.8 1000 30,169 11.9 39,095 4.5
GCV041 7.9 1150 33,127 12.6 40,913 4.4
GCV/H042 8.0 1199 35,870 13.0 44,994 4.5
GCV/H048 9.0 1375 41,309 13.0 50,133 4.9
GCV/H060 11.3 1650 50,450 13.3 63,852 4.5
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature Rev.: 02/14/03 B
Heating capacities based upon 68°F DB, 59°F WB entering air temperatureAll air flow is rated on high speedAll ratings based upon operation at lower voltage of dual voltage rated models
cfm*0.472 = l/s
gpm*0.0631 = l/s
in wg*249 = pascals
ft of hd *2990 = pascals
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
PERFORMANCE DATAGCH/V 018B
236 l/s Nominal Airflow Performance capacities shown in kW
EWT °CWaterFlow WPD
COOLING - EAT 27/19°C HEATING - EAT 20°C
l/s kPA TCkW
SCkW
Sens/Tot Ratio
PowerkW
HRkW
EERW/W
HCkW
PowerkW
HEkW
LAT°C
COPW/W
0.146 14.4 5.1 4.0 0.78 1.12 6.2 4.55 5.1 1.26 3.8 37.9 4.05
15 0.215 21.0 5.3 4.1 0.77 1.05 6.4 5.05 5.3 1.29 4.0 38.6 4.11
0.283 29.2 5.4 4.1 0.76 1.02 6.4 5.29 5.4 1.30 4.1 39.0 4.15
0.146 14.0 4.9 3.9 0.80 1.19 6.1 4.12 5.4 1.30 4.1 39.0 4.15
20 0.215 20.2 5.1 4.0 0.78 1.12 6.2 4.55 5.6 1.32 4.3 39.7 4.24
0.283 28.5 5.2 4.0 0.77 1.09 6.3 4.77 5.7 1.33 4.4 40.0 4.29
0.146 13.6 4.7 3.8 0.81 1.27 6.0 3.70 5.8 1.34 4.5 40.4 4.33
25 0.215 19.6 4.9 3.9 0.80 1.20 6.1 4.08 6.0 1.37 4.6 41.1 4.38
0.283 27.7 5.0 3.9 0.78 1.18 6.2 4.24 6.1 1.38 4.7 41.4 4.42
0.146 13.2 4.4 3.6 0.82 1.34 5.7 3.28 6.1 1.37 4.7 41.4 4.45
30 0.215 19.1 4.6 3.7 0.80 1.29 5.9 3.57 6.3 1.40 4.9 42.1 4.50
0.283 27.0 4.7 3.8 0.81 1.26 6.0 3.73 6.3 1.41 4.9 42.1 4.47
0.146 12.8 4.0 3.3 0.83 1.41 5.4 2.84
35 0.215 18.5 4.3 3.5 0.81 1.36 5.7 3.16 Operation Not Recommended
0.283 26.3 4.4 3.6 0.82 1.33 5.7 3.31
Rev: 03/12/03 B
Interpolation is permissable, extrapolation is not.
All entering air conditions are 27 °C DB and 19°C WB in cooling and 20°C DB in heating.
All performance data is based upon the lower voltage of dual voltage rated units.
See Performance Correction Tables for operating conditions other than those listed above.
Data table does not reflect ISO pump or fan corrections.
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
PERFORMANCE DATAGCH/V 024B
319 l/s Nominal Airflow Performance capacities shown in kW
EWT °CWaterFlow WPD
COOLING - EAT 27/19°C HEATING - EAT 20°C
l/s kPA TCkW
SCkW
Sens/TotRatio
PowerkW
HRkW
EERW/W
HCkW
PowerkW
HEkW
LAT°C
COPW/W
0.190 13.8 6.4 5.1 0.80 1.41 7.8 4.54 6.7 1.43 5.3 37.4 4.69
15 0.284 26.6 6.5 5.2 0.80 1.33 7.8 4.89 7.0 1.46 5.5 38.2 4.79
0.378 44.4 6.6 5.2 0.79 1.29 7.9 5.12 7.2 1.48 5.7 38.7 4.86
0.190 13.4 6.3 5.0 0.79 1.49 7.8 4.23 7.2 1.49 5.7 38.7 4.83
20 0.284 25.7 6.4 5.1 0.80 1.42 7.8 4.51 7.5 1.51 6.0 39.5 4.97
0.378 43.0 6.4 5.1 0.80 1.38 7.8 4.64 7.6 1.53 6.1 39.8 4.97
0.190 13.0 6.1 4.9 0.80 1.58 7.7 3.86 7.7 1.54 6.2 40.0 5.00
25 0.284 25.0 6.3 5.0 0.79 1.52 7.8 4.14 7.9 1.57 6.3 40.5 5.03
0.378 41.8 6.3 5.0 0.79 1.48 7.8 4.26 8.0 1.58 6.4 40.8 5.06
0.190 12.6 5.8 4.7 0.81 1.67 7.5 3.47 8.0 1.59 6.4 40.8 5.03
30 0.284 24.5 6.0 4.9 0.82 1.61 7.6 3.73 8.2 1.61 6.6 41.3 5.09
0.378 41.0 6.1 4.9 0.80 1.57 7.7 3.89 8.2 1.63 6.6 41.3 5.03
0.190 12.2 5.4 4.5 0.83 1.75 7.2 3.09
35 0.284 23.8 5.7 4.6 0.81 1.69 7.4 3.37 Operation Not Recommended
0.378 39.8 5.9 4.7 0.80 1.66 7.6 3.55
Rev: 03/12/03 B
Interpolation is permissable, extrapolation is not.
All entering air conditions are 27 °C DB and 19°C WB in cooling and 20°C DB in heating.
All performance data is based upon the lower voltage of dual voltage rated units.
See Performance Correction Tables for operating conditions other than those listed above.
Data table does not reflect ISO pump or fan corrections.
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
PERFORMANCE DATAGCH/V 030B
401 l/s Nominal Airflow Performance capacities shown in kW
EWT °CWaterFlow WPD
COOLING - EAT 27/19°C HEATING - EAT 20°C
l/s kPA TCkW
SCkW
Sens/TotRatio
PowerkW
HRkW
EERW/W
HCkW
PowerkW
HEkW
LAT°C
COPW/W
0.240 10.8 7.3 5.7 0.78 1.64 8.9 4.45 8.0 1.81 6.2 36.5 4.42
15 0.353 19.4 7.4 5.8 0.78 1.57 9.0 4.71 8.2 1.83 6.4 36.9 4.48
0.473 30.2 7.4 5.8 0.78 1.53 8.9 4.84 8.3 1.84 6.5 37.1 4.51
0.240 10.5 7.1 5.6 0.79 1.75 8.9 4.06 8.4 1.85 6.6 37.3 4.54
20 0.353 18.7 7.3 5.7 0.78 1.66 9.0 4.40 8.6 1.86 6.7 37.8 4.62
0.473 29.2 7.3 5.7 0.78 1.62 8.9 4.51 8.7 1.87 6.8 38.0 4.65
0.240 10.3 6.9 5.5 0.80 1.88 8.8 3.67 8.8 1.88 6.9 38.2 4.68
25 0.353 18.3 7.1 5.6 0.79 1.79 8.9 3.97 9.0 1.90 7.1 38.6 4.74
0.473 28.4 7.1 5.7 0.80 1.75 8.9 4.06 9.1 1.91 7.2 38.8 4.76
0.240 9.9 6.6 5.4 0.82 2.00 8.6 3.30 9.2 1.92 7.3 39.0 4.79
30 0.353 17.9 6.8 5.5 0.81 1.91 8.7 3.56 9.4 1.94 7.5 39.4 4.85
0.473 27.7 6.9 5.5 0.80 1.87 8.8 3.69 9.5 1.95 7.6 39.6 4.87
0.240 9.7 6.2 5.2 0.84 2.11 8.3 2.94
35 0.353 17.4 6.4 5.3 0.83 2.04 8.4 3.14 Operation Not Recommended
0.473 26.9 6.6 5.4 0.82 2.00 8.6 3.30
Rev: 03/12/03 B
Interpolation is permissable, extrapolation is not.
All entering air conditions are 27 °C DB and 19°C WB in cooling and 20°C DB in heating.
All performance data is based upon the lower voltage of dual voltage rated units.
See Performance Correction Tables for operating conditions other than those listed above.
Data table does not reflect ISO pump or fan corrections.
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
PERFORMANCE DATAGCH/V 036B
472 l/s Nominal Airflow Performance capacities shown in kW
EWT °CWaterFlow WPD
COOLING - EAT 27/19°C HEATING - EAT 20°C
l/s kPA TCkW
SCkW
Sens/TotRatio
PowerkW
HRkW
EERW/W
HCkW
PowerkW
HEkW
LAT°C
COPW/W
0.284 12.3 9.6 7.2 0.75 2.24 11.8 4.29 10.0 2.41 7.6 37.6 4.15
15 0.429 22.1 9.8 7.2 0.73 2.12 11.9 4.62 10.6 2.48 8.1 38.6 4.27
0.567 35.2 9.9 7.3 0.74 2.05 12.0 4.83 10.9 2.52 8.4 39.1 4.33
0.284 11.8 9.3 7.1 0.76 2.38 11.7 3.91 11.0 2.52 8.5 39.3 4.37
20 0.429 21.6 9.6 7.2 0.75 2.26 11.9 4.25 11.6 2.60 9.0 40.4 4.46
0.567 34.0 9.7 7.2 0.74 2.19 11.9 4.43 11.8 2.63 9.2 40.7 4.49
0.284 11.5 8.8 6.9 0.78 2.53 11.3 3.48 11.9 2.65 9.3 40.9 4.49
25 0.429 21.1 9.2 7.1 0.77 2.42 11.6 3.80 12.4 2.72 9.7 41.8 4.56
0.567 33.1 9.4 7.1 0.76 2.35 11.8 4.00 12.6 2.74 9.9 42.1 4.60
0.284 11.3 8.3 6.7 0.81 2.67 11.0 3.11 12.7 2.75 10.0 42.3 4.62
30 0.429 20.6 8.7 6.9 0.79 2.57 11.3 3.39 13.1 2.81 10.3 43.0 4.66
0.567 32.4 8.9 7.0 0.79 2.51 11.4 3.55 13.2 2.84 10.4 43.2 4.65
0.284 10.9 7.6 6.3 0.83 2.81 10.4 2.70
35 0.429 20.1 8.1 6.6 0.81 2.72 10.8 2.98 Operation Not Recommended
0.567 31.4 8.3 6.7 0.81 2.66 11.0 3.12
Rev: 03/12/03 B
Interpolation is permissable, extrapolation is not.
All entering air conditions are 27 °C DB and 19°C WB in cooling and 20°C DB in heating.
All performance data is based upon the lower voltage of dual voltage rated units.
See Performance Correction Tables for operating conditions other than those listed above.
Data table does not reflect ISO pump or fan corrections.
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
PERFORMANCE DATAGCV 041B
543 l/s Nominal Airflow Performance capacities shown in kW
EWT °CWaterFlow WPD
COOLING - EAT 27/19°C HEATING - EAT 20°C
l/s kPA TCkW
SCkW
Sens/TotRatio
PowerkW
HRkW
EERW/W
HCkW
PowerkW
HEkW
LAT°C
COPW/W
0.335 6.6 10.1 7.8 0.77 2.28 12.4 4.43 11.0 2.63 8.4 36.8 4.18
15 0.498 15.2 10.2 7.8 0.76 2.19 12.4 4.66 11.4 2.69 8.7 37.4 4.24
0.662 27.8 10.3 7.8 0.76 2.15 12.5 4.79 11.6 2.72 8.9 37.7 4.26
0.335 6.4 9.9 7.8 0.79 2.42 12.3 4.09 11.7 2.74 9.0 37.9 4.27
20 0.498 15.0 10.0 7.8 0.78 2.31 12.3 4.33 12.1 2.79 9.3 38.5 4.34
0.662 26.8 10.1 7.8 0.77 2.26 12.4 4.47 12.3 2.82 9.5 38.8 4.36
0.335 6.3 9.7 7.7 0.79 2.60 12.3 3.73 12.4 2.84 9.6 38.9 4.37
25 0.498 14.5 9.8 7.8 0.80 2.47 12.3 3.97 12.8 2.89 9.9 39.5 4.43
0.662 26.2 9.9 7.8 0.79 2.41 12.3 4.11 12.9 2.91 10.0 39.7 4.43
0.335 6.0 9.3 7.4 0.80 2.77 12.1 3.36 13.0 2.93 10.1 39.8 4.44
30 0.498 14.3 9.6 7.6 0.79 2.65 12.3 3.62 13.3 2.97 10.3 40.3 4.48
0.662 25.6 9.7 7.7 0.79 2.59 12.3 3.75 13.5 2.99 10.5 40.6 4.52
0.335 5.9 8.7 7.1 0.82 2.94 11.6 2.96
35 0.498 14.0 9.1 7.3 0.80 2.83 11.9 3.22 Operation Not Recommended
0.662 24.9 9.3 7.4 0.80 2.77 12.1 3.36
Rev: 03/12/03 B
Interpolation is permissable, extrapolation is not.
All entering air conditions are 27 °C DB and 19°C WB in cooling and 20°C DB in heating.
All performance data is based upon the lower voltage of dual voltage rated units.
See Performance Correction Tables for operating conditions other than those listed above.
Data table does not reflect ISO pump or fan corrections.
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
PERFORMANCE DATAGCH/V 042B
566 l/s Nominal Airflow Performance capacities shown in kW
EWT °CWaterFlow WPD
COOLING - EAT 27/19°C HEATING - EAT 20°C
l/s kPA TCkW
SCkW
Sens/TotRatio
PowerkW
HRkW
EERW/W
HCkW
PowerkW
HEkW
LAT°C
COPW/W
0.335 7.2 10.9 8.3 0.76 2.48 13.4 4.40 12.0 2.85 9.2 37.6 4.21
15 0.505 18.6 11.0 8.3 0.75 2.37 13.4 4.64 12.5 2.93 9.6 38.3 4.27
0.694 38.0 11.1 8.3 0.75 2.33 13.4 4.76 12.8 2.98 9.8 38.7 4.30
0.335 7.0 10.7 8.3 0.78 2.65 13.4 4.04 12.9 2.99 9.9 38.9 4.31
20 0.505 18.1 10.9 8.3 0.76 2.51 13.4 4.34 13.4 3.07 10.3 39.6 4.36
0.694 36.8 10.9 8.3 0.76 2.45 13.4 4.45 13.7 3.10 10.6 40.0 4.42
0.335 6.7 10.4 8.1 0.78 2.86 13.3 3.64 13.8 3.12 10.7 40.2 4.42
25 0.505 17.5 10.6 8.3 0.78 2.70 13.3 3.93 14.3 3.20 11.1 40.9 4.47
0.694 35.8 10.7 8.3 0.78 2.62 13.3 4.08 14.5 3.23 11.3 41.2 4.49
0.335 6.6 9.9 7.9 0.80 3.07 13.0 3.22 14.6 3.23 11.4 41.4 4.52
30 0.505 17.3 10.3 8.1 0.79 2.92 13.2 3.53 15.1 3.29 11.8 42.1 4.59
0.694 35.2 10.4 8.2 0.79 2.83 13.2 3.67 15.3 3.32 12.0 42.4 4.61
0.335 6.4 9.2 7.5 0.82 3.25 12.5 2.83
35 0.505 16.8 9.7 7.9 0.81 3.13 12.8 3.10 Operation Not Recommended
0.694 34.2 10.0 8.0 0.80 3.05 13.1 3.28
Rev: 03/12/03 B
Interpolation is permissable, extrapolation is not.
All entering air conditions are 27 °C DB and 19°C WB in cooling and 20°C DB in heating.
All performance data is based upon the lower voltage of dual voltage rated units.
See Performance Correction Tables for operating conditions other than those listed above.
Data table does not reflect ISO pump or fan corrections.
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
PERFORMANCE DATAGCH/V 048B
649 l/s Nominal Airflow Performance capacities shown in kW
EWT °CWaterFlow WPD
COOLING - EAT 27/19°C HEATING - EAT 20°C
l/s kPA TCkW
SCkW
Sens/TotRatio
PowerkW
HRkW
EERW/W
HCkW
PowerkW
HEkW
LAT°C
COPW/W
0.379 8.7 12.7 9.6 0.76 3.01 15.7 4.22 13.3 3.03 10.3 37.0 4.39
15 0.568 20.0 12.8 9.7 0.76 2.85 15.7 4.49 14.0 3.11 10.9 37.9 4.50
0.757 36.7 12.9 9.7 0.75 2.78 15.7 4.64 14.3 3.15 11.2 38.3 4.54
0.379 8.5 12.4 9.5 0.77 3.20 15.6 3.88 14.4 3.16 11.2 38.4 4.56
20 0.568 19.6 12.6 9.6 0.76 3.03 15.6 4.16 15.0 3.23 11.8 39.1 4.64
0.757 35.6 12.7 9.6 0.76 2.95 15.7 4.31 15.4 3.26 12.1 39.7 4.72
0.379 8.2 11.9 9.4 0.79 3.41 15.3 3.49 15.5 3.28 12.2 39.8 4.73
25 0.568 19.0 12.3 9.5 0.77 3.24 15.5 3.80 16.1 3.35 12.8 40.6 4.81
0.757 34.6 12.4 9.5 0.77 3.16 15.6 3.92 16.4 3.38 13.0 40.9 4.85
0.379 8.0 11.3 9.1 0.81 3.61 14.9 3.13 16.4 3.38 13.0 40.9 4.85
30 0.568 18.5 11.8 9.3 0.79 3.46 15.3 3.41 16.9 3.44 13.5 41.6 4.91
0.757 33.7 12.0 9.4 0.78 3.38 15.4 3.55 17.2 3.46 13.7 42.0 4.97
0.379 7.8 10.5 8.8 0.84 3.79 14.3 2.77
35 0.568 18.0 11.1 9.1 0.82 3.66 14.8 3.03 Operation Not Recommended
0.757 32.7 11.4 9.2 0.81 3.59 15.0 3.18
Rev: 03/12/03 B
Interpolation is permissable, extrapolation is not.
All entering air conditions are 27 °C DB and 19°C WB in cooling and 20°C DB in heating.
All performance data is based upon the lower voltage of dual voltage rated units.
See Performance Correction Tables for operating conditions other than those listed above.
Data table does not reflect ISO pump or fan corrections.
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
PERFORMANCE DATAGCH/V 060B
779 l/s Nominal Airflow Performance capacities shown in kW
EWT °CWaterFlow WPD
COOLING - EAT 27/19°C HEATING - EAT 20°C
l/s kPA TCkW
SCkW
Sens/TotRatio
PowerkW
HRkW
EERW/W
HCkW
PowerkW
HEkW
LAT°C
COPW/W
0.474 30.3 15.3 11.3 0.74 3.58 18.9 4.27 16.1 4.11 12.0 37.1 3.92
15 0.713 52.3 15.4 11.6 0.75 3.42 18.8 4.50 17.3 4.23 13.1 38.4 4.09
0.946 79.7 15.5 11.6 0.75 3.34 18.8 4.64 17.8 4.30 13.5 38.9 4.14
0.474 29.3 14.9 11.5 0.77 3.78 18.7 3.94 18.1 4.32 13.8 39.3 4.19
20 0.713 50.9 15.2 11.6 0.76 3.61 18.8 4.21 19.2 4.44 14.8 40.4 4.32
0.946 77.1 15.3 11.6 0.76 3.53 18.8 4.33 19.8 4.50 15.3 41.1 4.40
0.474 28.4 14.5 11.4 0.79 4.04 18.5 3.59 20.0 4.53 15.5 41.3 4.42
25 0.713 49.5 14.8 11.5 0.78 3.85 18.7 3.84 21.0 4.64 16.4 42.3 4.53
0.946 75.2 15.0 11.6 0.77 3.76 18.8 3.99 21.5 4.69 16.8 42.9 4.58
0.474 27.8 13.9 11.2 0.81 4.32 18.2 3.22 21.6 4.71 16.9 43.0 4.59
30 0.713 48.3 14.3 11.4 0.80 4.11 18.4 3.48 22.4 4.79 17.6 43.8 4.68
0.946 73.3 14.5 11.5 0.79 4.01 18.5 3.62 22.8 4.83 18.0 44.3 4.72
0.474 26.9 13.1 10.9 0.83 4.63 17.7 2.83
35 0.713 47.0 13.7 11.2 0.82 4.41 18.1 3.11 Operation Not Recommended
0.946 71.2 14.0 11.3 0.81 4.30 18.3 3.26
Rev: 03/12/03 B
Interpolation is permissable, extrapolation is not.
All entering air conditions are 27 °C DB and 19°C WB in cooling and 20°C DB in heating.
All performance data is based upon the lower voltage of dual voltage rated units.
See Performance Correction Tables for operating conditions other than those listed above.
Data table does not reflect ISO pump or fan corrections.
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
PERFORMANCE DATACORRECTION TABLES
Air Flow Correction Table
Entering Air Correction Table
Airflow
% ofNominal Htg Cap Power Heat of
Ext Total Cap Sens Cap Power Heat of Rej
75% 0.966 1.051 0.939 0.970 0.899 0.953 0.967
81% 0.976 1.037 0.956 0.979 0.924 0.966 0.976
88% 0.985 1.023 0.973 0.987 0.949 0.979 0.985
94% 0.993 1.012 0.987 0.994 0.975 0.990 0.993
100% 1.000 1.000 1.000 1.000 1.000 1.000 1.000
106% 1.006 0.991 1.010 1.005 1.026 1.008 1.005
113% 1.011 0.982 1.020 1.009 1.051 1.016 1.010
119% 1.014 0.975 1.027 1.011 1.077 1.022 1.013
125% 1.017 0.968 1.033 1.013 1.102 1.027 1.016
Rev: 06/12/01 B
Heating Cooling
Heating Corrections Cooling Corrections
Sens Clg Cap Multiplier - Entering DB °FEnt Air DB
°CHtg Cap Power Heat of
ExtEnt AirWB °C
Total ClgCap 21 23 25 27 29.5 32 35
Power Heat ofRej
15 1.026 0.935 1.054 15 0.855 0.810 0.948 1.095 1.190 * * * 0.983 0.880
17 1.016 0.962 1.032 17 0.928 0.681 0.836 0.983 1.095 * * * 0.989 0.939
20 1.000 1.000 1.000 19 1.000 0.552 0.707 0.853 1.000 1.147 * * 1.000 1.000
22 0.984 1.025 0.972 21 1.059 0.052 0.422 0.690 0.853 1.026 1.164 1.328 1.006 1.049
24 0.969 1.050 0.944 23 1.105 0.371 0.664 0.845 1.017 1.207 1.006 1.086
26 0.953 1.072 0.917 25 1.125 0.233 0.586 0.776 0.966 1.155 1.008 1.103
Rev: 08/08/02 B
* Sensible capacity equals total capacity
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
BLOWER PERFORMANCE DATA
Airflow in l/s with dry coil and clean air filter.
Model Rated Min Fan
l/s l/s Speed 0 25 50 75 100 125 150 175 200 225 250 275 300 325
HI 297 274 255 222 165
H/V 018 236 175 MED 302 288 269 245 222 170
LOW 288 274 255 236 175
HI 378 345 283 241
H/V 024 319 235 MED 439 420 392 359 326 274 222
LOW 378 363 340 321 245 236
HI 505 463 420 378 312
H/V 030 401 305 MED 543 510 467 425 382 316
LOW 514 491 448 411 312
HI 609 585 543 500 453 368
H/V 036 472 355 MED 500 486 463 439 406 340
LOW 467 453 430 411 411
HI 534 517 500 470 431 397 342
V041 543 378 MED 487 474 461 440 406 371
LOW 418 406 397 380 359
HI 694 670 647 618 585 548 505 467
H/V 042 566 425 MED 647 628 604 581 548 519 486 439
LOW 505 500 496 486 467
HI 812 765 713 632 543
H/V 048 649 495 MED 807 769 741 694 609
LOW 784 765 746 732 694 642 590
HI 953 949 935 902 873 854 831 798 760 703
H/V 060 779 590 MED 902 887 864 840 821 793 774 741 703 637
LOW 826 817 802 788 769 741 708 670 604
Gray areas denote ESP where operation is not recommended Rev.: 08/09/02 B
Units factory shipped on medium speed. Other speeds require field selection.
All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 200V for 200-220V units.
All units ARI/ISO/ASHRAE 13256-1 rated on high fan speed.
For wet coil performance first calculate the face velocity of the air coil (Face Velocity [mpm] = Airflow [l/s]/1000 / Face Area [m2]).
Then for velocities of 61 m per min reduce the static capability by 7.5 Pa, 91 m per min by 20 Pa, 121 m per min by 30 Pa.
and 150 m per min by 40 Pa.
External Static Pressure (Pa)
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
PHYSICAL DATA
y
Model H/V 018 H/V 024 H/V 030 H/V 036 V041 H/V 042 H/V 048 H/V 060
Compressor (1 each) Recip Recip Recip Recip Recip Recip Recip Scroll
Factory R22 Charge Vertical, oz [kg] 26 [0.74] 38 [1.08] 37 [1.05] 42 [1.19] 50 [1.42] 51 [1.45] 66 [1.87] 74 [2.10]
Factory R22 Charge Horizontal - oz. [kg] 25 [0.71] 38 [1.08] 37 [1.05] 41 [1.16] 50 [1.42] 51 [1.45] 66 [1.87] 74 [2.10]
PSC Fan Motor & Blower
Fan Motor Type/Speeds PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3
Fan Motor - hp [W] 1/6 [124] 1/4 [187] 3/4 [560] 1/2 [373] 3/4 [560] 3/4 [560] 3/4 [560] 1 [746]
Blower Wheel Size (Dia x W) - in. [cm] 8 x 7[20.3x17.8]
9 x 7[22.9x17.8]
9 x 7[22.9x17.8] 9 x 8 [22.9x20.3] 9 x 8 [22.9x20.3] 9 x 8 [22.9x20.3] 10 x 10
[25.4x25.4] 11 x 10 [27.9x25.4]
Water Connection Size
FPT - American Std Pipe thread - in. [mm] 1/2 [12.7] 3/4 [19.1] 3/4 [19.1] 3/4 [19.1] 3/4 [19.1] 3/4 [19.1] 1 [25.4] 1 [25.4]
Horizontal
Air Coil Dimensions (H x W) - in. [cm] 16 x 22[40.6x55.9]
16 x 22[40.6x55.9]
16 x 22[40.6x55.9]
20 x 25[50.8x63.5] - 20 x 25
[50.8x63.5]20 x 35
[50.8x88.9] 20 x 35 [50.8x88.9]
Air Coil Total Face Area - ft2 [m2] 2.44 [0.227] 2.44 [0.227] 2.44 [0.227] 3.47 [0.323] - 3.47 [0.323] 4.86 [0.452] 4.86 [0.452]
Air Coil Tube Diam - in. [mm] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] - 3/8 [9.5] 3/8 [9.5] 3/8 [9.5]
Air Coil Distance between fins, in. [mm] 0.083 [2.1] 0.083 [2.1] 0.083 [2.1] 0.077 [2.0] - 0.083 [2.1] 0.083 [2.1] 0.083 [2.1]
Air Coil Number of rows 2 3 3 2 - 3 3 3
Filter Standard - 1" [25.4mm] Throwaway -in. [cm] 16 x 25 16 x 25 16 x 25 1 - 20x28 or
2 - 20x14 - 1 - 20x28 or2 - 20x14
1 - 20x24 &1 - 20x14
1 - 20x24 &1 - 20x14
[40.6x63.5] [40.6x63.5] [40.6x63.5] [1 - 50.8x71.1 or2 - 50.8x35.6] - [1 - 50.8x71.1 or 2
- 50.8x35.6][1 - 50.8x61.0 & 1 -
50.8x35.6][1 - 50.8x61.0 &
1 - 50.8x35.6]
Vertical
Air Coil Dimensions (H x W) - in. [cm] 20 x 17.25[50.8x43.8]
20 x 17.25[50.8x43.8]
20 x 17.25[50.8x43.8]
24 x 21.75[61.0x55.2]
20 x 17.25[50.8x43.8]
24 x 21.75[61.0x55.2]
24 x 28.25[61.0x71.8]
24 x 28.25[61.0x71.8]
Air Coil Total Face Area - ft2 [m2] 2.40 [0.223] 2.40 [0.223] 2.40 [0.223] 3.62 [0.337] 2.40 [0.223] 3.62 [0.337] 4.71 [0.438] 4.71 [0.438]
Air Coil Tube Diam - in. [mm] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5]
Air Coil Distance between fins, in. [mm] 0.083 [2.1] 0.083 [2.1] 0.083 [2.1] 0.077 [2.0] 0.091 [2.3] 0.083 [2.1] 0.083 [2.1] 0.083 [2.1]
Air Coil Number of rows 2 3 3 2 4 3 3 3
Filter Standard - 1" [25.4mm] Throwaway -in. [cm] 20 x 20 20 x 20 20 x 20 24 x 24 20 x 20 24 x 24 1 - 14x24 &
1 - 18x241 - 14x24 &
1 - 18x24
[50.8x50.8] [50.8x50.8] [50.8x50.8] [61.0x61.0] [50.8x50.8] [61.0x61.0] [1 - 35.6x61.0 &1 - 45.7x61.0]
[1 - 35.6x61.0 &1 - 45.7x61.0]
Weight - Operating - lbs. [kg] 181 [82.1] 189 [85.7] 197 [89.4] 203 [92.1] 207 [93.9] 218 [98.9] 263 [119.2] 278 [126.1]
Weight - Packaged - lbs. [kg] 186 [84.4] 194 [88.0] 202 [91.6] 209 [94.8] 212 [96.2] 224 [101.6] 270 [119.3] 285 [129.3]
Notes: Rev.: 07/18/02 B
"-" Data not available at time of printing
All units have grommet compressor mountings,and 1/2" & 3/4" electrical knockouts.
Check serial plate for refrigerant type (R22).
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
HORIZONTAL DIMENSIONALDATA
F
Right Return Straight Discharge
Front
L N
O
M
LegendCAP=Control Access PanelCSP=Compressor Service PanelBSP=Blower Service PanelASP=Alternate Service Panel
Right Return
Front
StraightDischarge
CSP
BackDischarge
Condensate3 / 4” FPT
3.3
0.7
Front-View
E D
KJ 2
1
1.1
A
CAP
BSP
Right Return Right View -Air Coil Opening
Air Coil
C
TS
B
ASP R
Q
Front
L
N O
M
Left Return Straight Discharge
Front
BSP
LEFT RETURN RIGHT RETURN
Air Coil
CSP
Front
Left Return Left View -Air Coil Opening
1.75
C
T
R
QS
B
Unit Hanger Detail
U
V
Fro
nt
WModel U V W018-030 43.1 22.2 18.0036-042 47.1 22.2 18.0048-060 54.1 26.2 22.0
Right Return Back Discharge
A
Air
Coi
l Sid
e
C
PN
O
M
ASP CSP
BSP
2’ ServiceAccess
Front
Left Return
0.7
3.3
CSP
Condensate3 / 4” FPT
ASP
2’ ServiceAccess
Air
Coi
l Sid
e
M
A
C
Left Return Back Discharge
NO
P
BSP
Rev.: 08/09/01 B
BlowerOutlet
BlowerOutlet
BlowerOutlet
BlowerOutlet
Optional 2’ServiceAccess
Optional 2’ServiceAccess
G
H
Power Supply3 / 4” Knockout
1 / 2”Knockout
Low Voltage1 / 2” Knockout
3StraightDischarge
BackDischarge
Overall CabinetWater Connections Electrical Knockouts
Return ConnectionHorizontal 1 - In 2 - Out H J K using return air opening
Model A B C D E F G 1/2" cond 1/2" cond 3/4" cond L M N O P Q R S T
Width Depth Height LowVoltage
LowVoltage
PowerSupply
SupplyHeight
SupplyDepth
ReturnDepth
ReturnHeight
018-030 in. 20.1 43.1 17.1 15.3 2.4 1.9 2.1 12.1 9.1 6.1 2.6 13.3 9.9 4.1 1.3 23.0 15.0 1.1 1.0
cm. 51.1 109.5 43.4 38.9 6.1 4.9 5.3 30.8 23.2 15.6 6.6 33.8 25.1 10.5 3.3 58.4 38.1 2.8 2.5
036-042 in. 20.1 47.1 21.1 18.8 2.2 4.7 1.2 16.1 13.1 10.1 2.5 16.1 11.0 3.0 2.5 25.9 19.0 1.1 1.0
cm. 51.1 119.6 53.6 47.6 5.5 11.9 3.0 41.0 33.3 25.7 6.3 40.9 27.9 7.7 6.4 65.8 48.3 2.8 2.5
048 in. 24.1 54.1 21.1 19.4 5.9 4.3 2.3 16.1 13.1 10.1 3.7 16.1 13.7 4.1 1.3 35.9 19.0 1.1 1.0
cm. 61.2 137.4 53.6 49.2 14.9 11.0 5.8 41.0 33.3 25.7 9.5 41.0 34.8 10.3 3.2 91.2 48.3 2.8 2.5
060 in. 24.1 54.1 21.1 19.4 5.9 4.3 2.3 16.1 13.1 10.1 1.7 18.1 13.7 4.1 1.3 35.9 19.0 1.1 1.0
cm. 61.2 137.4 53.6 49.2 14.9 11.0 5.8 41.0 33.3 25.7 4.4 46.0 34.8 10.3 3.2 91.2 48.3 2.8 2.5
Condensate is 3/4" FPT copper. Rev.: 08/09/01 B
Horizontal unit shipped with filter bracket only. This bracket should be removed for return duct connection.Hanger kit is factory installed
Verify high static option discharge connection dimensions with ClimateMaster
duct flange (± 0.10 in)
Discharge Connections
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
VERTICAL DIMENSIONAL DATA
Access Panels
Top View-Left ReturnTop View-Right Return
U
RSIsometric
View
Left Return Left View- Air Coil Opening
T
CPower Supply
3/4” (19.1 mm) HVKnockout
Low Voltage1/2” (12.7 mm) LV
KnockoutLow Voltage
1/2” (12.7 mm) LVKnockout
Condensate 3/4”(19.1 mm) FPT
Front-View
K
1.00 [25.4 mm]
F
JH
D
L
Air Coil
Field InstalledDischarge Flange
FrontBack
U
R S
T
C
BackFront
Right Return Right View- Air Coil Opening
BSP
CAP
Standard Filter Bracket
ASP
Air Coil
Front
P N
O
Q
Fro
nt
2’ (61cm)Service
Access *Left Rtn(Right RtnOpposite
Side)
NB
P
A
O
M
2’ (61cm)Service
3
2
1
E
I
G
LegendCAP=Control Access PanelCSP=Compressor Service PanelBSP=Blower Service PanelASP=Alternate Service Panel
CSP
CAP
CSPCSP
CSP
Air Coil
Air Coil SideAir Coil Side
Rev.: 05/07/02 B
* Note: Shaded areas are recommended service areas, not required.
BSP
Vertical Overall CabinetWater Connections Electrical Knockouts
Discharge Connection Return Connection
Upflow 1 2 Water J K L using return air opening
Model A B C D E F G H I FPT 1/2" cond 1/2" cond 3/4" cond M N O P Q R S T U
Width Depth HeightSize
LowVoltage
LowVoltage
PowerSupply
SupplyWidth
SupplyDepth
ReturnDepth
ReturnHeight
018-030 in. 21.5 21.5 39.0 1.8 3.8 15.2 3.6 8.1 2.3 3/4" 4.1 7.1 10.1 6.4 3.8 14.0 14.0 5.3 2.3 18.3 20.2 0.7
cm. 54.6 54.6 99.1 4.5 9.7 38.6 9.1 20.6 5.8 1.9 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.6 5.8 46.5 51.3 1.9
036 & 042 in. 21.5 26.0 44.0 2.0 3.7 16.2 2.6 10.4 2.3 3/4" 4.1 7.1 10.1 6.4 3.8 14.0 14.0 5.1 2.3 22.8 24.2 0.7
cm. 54.6 66.0 111.8 5.1 9.4 41.1 6.6 26.4 5.8 1.9 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.1 5.8 57.9 61.4 1.9
041 in. 21.5 21.5 39.0 1.7 3.6 16.4 2.6 8.1 2.3 3/4" 4.1 7.1 10.1 6.4 3.8 14.0 14.0 5.3 2.3 18.3 20.2 0.7
cm. 54.6 54.6 99.1 4.4 9.1 41.7 6.6 20.6 5.8 1.9 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.6 5.8 46.5 51.3 1.9
048-060 in. 24.0 32.5 46.0 1.8 5.9 16.7 2.3 10.1 2.3 1" 4.1 7.1 10.1 6.9 7.3 16.0 18.0 5.1 2.3 29.3 24.2 0.7
cm. 61.0 82.6 116.8 4.5 14.9 42.4 5.8 25.7 5.8 2.5 10.5 18.1 25.7 17.4 18.4 40.6 45.7 13.1 5.8 74.4 61.4 1.9
Rev.: 05/13/02 B
Condensate is 3/4" ( 19.1 mm) FPTFilter bracket extending from unit 2.5" (6.4 cm). This bracket should be removed when connecting return duct.Discharge flange field installed
duct flange installed (±0.10 in)
In Out
3
Condensate
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
UNIT ELECTRICAL DATA
Voltage Rated Voltage Compressor Fan Total Min Max
Model Code Voltage Min/Max Motor Unit Circ Fuse/
Qty RLA LRA FLA FLA Amp HACR
V/H018 V 220-240/50/1 197/254 1 8.1 44.0 0.86 8.9 11.0 15
V/H024 V 220-240/50/1 197/254 1 9.1 55.0 1.30 10.4 12.7 20
U 380-420/50/3 342/462 1 3.5 25.0 0.76 4.2 5.1 15
V/H030 V 220-240/50/1 197/254 1 10.0 58.0 2.70 12.7 15.2 25
U 380-420/50/3 342/462 1 3.6 28.0 1.70 5.3 6.2 15
V/H036 V 220-240/50/1 197/254 1 14.4 83.0 2.00 16.4 20.0 30
U 380-420/50/3 342/462 1 4.9 33.0 1.24 6.1 7.4 15
V041 U 380-420/50/3 342/462 1 4.3 40.0 1.70 6.0 7.1 15
V/H042 U 380-420/50/3 342/462 1 5.3 42.0 1.70 7.0 8.3 15
V/H048 U 380-420/50/3 342/462 1 5.7 42.0 1.80 7.5 8.9 15
V/H060 U 380-420/50/3 342/462 1 7.4 59.6 2.50 9.9 11.8 15
HACR circuit breaker in USA only Rev:. 06/22/02 BAll fuses Class RK-5
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
TYPICAL WIRING DIAGRAMSINGLE PHASE WIRING DIAGRAMGC UNITS WITHCXM CONTROLLER
GC, GR, GSH/V006-070 Commercial with CXM208-230/60/1, 265/60/1 & 220-240/50/1 96B0006N01 Rev H 6/8/01
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
TYPICAL WIRING DIAGRAMTHREE PHASE WIRING DIAGRAMGC UNITS WITHCXM CONTROLLER(460/575 Volt)
GC, GR, GSH/V024-070 Commercial with CXM460/60/3, 575/60/3, & 380-420/60/3 96B0008N01 Rev. F 5/7/01
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
TYPICAL WIRING DIAGRAMSINGLE PHASE WIRING DIAGRAMGC UNITS WITHDXM CONTROLLER
GC, GR, GSH/V006-070 Commercial with DXM208-230/60/1, 265/60/1 & 220-240/50/1 96B0006N02 Rev. F 6/8/01
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
TYPICAL WIRING DIAGRAMTHREE PHASE WIRING DIAGRAMGC UNITS WITH DXM CONTROLLER (460/575 volt)
GC, GR, GSH/V024-070 Commercial with DXM460/60/3, 575/60/3, & 380-420/60/3 96B0008N02 Rev. E 5/7/01
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
GeneralFurnish and install ClimateMaster Water Source Heat Pumps, as indicated on the plans. Equipment shall be completely assembled, piped and internally wired.Capacities and characteristics as listed in the schedule and the specifications that follow.
Horizontal/Vertical Water Source Heat Pumps:Units shall be supplied completely factory built and capable of operation with an entering water temperature range from 60° to 95°F (15.6° to 35.0°C) asstandard. Equivalent units from other manufacturers can be proposed provided approval to bid is given 10 days prior to bid closing. All equipment listed in thissection must be rated and certified in accordance with ARI/ISO/ASHRAE, NRTL, CSA or optional CE Mark. The units shall have ARI/ISO, NRTL, CSA oroptional CE Mark labels. All units shall be factory run tested under normal operating conditions at nominal water flow rates. This testing shall generate a reportcard to be shipped with each unit stating performance in both heating and cooling modes. Serial numbers will be recorded by factory and furnished tocontractor for ease of unit warranty status. Units tested without water flow ARE NOT acceptable.
Basic ConstructionHorizontal Units shall have one of the following air flow arrangements: Right-Discharge/Left-Inlet; Left-Discharge/Right-Inlet; Back-Discharge/Left-Inlet; orBack-Discharge/Right-Inlet as shown on the plans. Units must have the ability to be field convertible from side to back or back to side discharge with noadditional parts or unit structure modification. Units will have factory installed hanger brackets and isolation grommets.
Vertical Units shall have one of the following air flow arrangements: Right-Return/Top-Discharge or Left-Return/Top-Discharge as shown on the plans. Unitswill have factory-installed internal condensate trap.
If units with these arrangements ARE NOT used, the contractor is responsible for any extra costs incurred by other trades. All units must have a minimum oftwo access panels for serviceability of compressor compartment. If other arrangements make servicing difficult, the contractor must provide access panelsand clear routes to ease service. Architect must approve any changes in layout.
The horizontal heat pumps shall be fabricated from heavy gauge galvanized sheet metal. All interior surfaces shall be lined with 1/2 inch thick (12mm), 1-1/2lb/ft3 (24kg/m3) density acoustic type glass fiber insulation. All fiberglass shall be coated and have exposed edges tucked under flanges to prevent theintroduction of glass fibers into the air stream. All insulation must meet NFPA 90A.
The vertical heat pumps shall be fabricated from heavy gauge galvanized sheet metal. All interior surfaces shall be lined with 1/2 inch thick (12mm), 1-1/2 lb/ft3 (24kg/m3) density acoustic type glass fiber insulation. All fiberglass shall be coated and have exposed edges tucked under flanges to prevent theintroduction of glass fibers into the air stream. All insulation must meet NFPA 90A. All vertical heat pumps shall have a powder coat paint finish. The colorshall be polar ice.
Option: Mute package shall consist of sound attenuating materials that are strategically applied to the cabinet, and will consist of 1" (25.4mm) fiberglassinsulation that is specifically selected to focus on Noise Reduction at the lower 125 and 250 Hz frequencies. All surfaces that normally have 0.5" (12.7mm)insulation would be substituted the noise dampening 1" (25.4mm) insulation.
All units must have an insulated panel separating the fan compartment from the compressor compartment. Units with the compressor in the air streamARE NOT acceptable. Units shall have a factory installed 1 inch wide filter bracket for filter removal from either side. Units shall have a 1 inch (25.4mm)thick throwaway type glass fiber filter. The contractor shall purchase one spare set of filters and replace factory shipped filters on completion of start-up.Filters shall be standard sizes. If units utilize non-standard filter sizes then the contractor shall provide 12 spare filters for each unit.
Option: Contractor shall install 2 inch (50.8mm) filter brackets and 2 inch (50.8mm) glass fiber throwaway filters on all units.
Cabinets shall have separate openings and knockouts for entrance of line voltage and low voltage control wiring. Supply and return water connections shall becopper FPT fittings. All water connections and electrical knockouts must be in the compressor compartment corner post as to not interfere with theserviceability of unit. Contractor shall be responsible for any extra costs involved in the installation of units that do not have this feature. Contractor must ensurethat units can be easily removed for servicing and coordinate locations of electrical conduit and lights with the electrical contractor.
Fan and Motor AssemblyUnits rated 60,000 BTUH and under shall have a direct-drive centrifugal fan. The fan motor shall be 3-speed (2 speed 575V), permanently lubricated, PSCtype with internal thermal overload protection. Blower shall have inlet rings to allow removal of wheel and motor from one side without removing housing. Unitssupplied without permanently lubricated motors must provide external oilers for easy service. The fan motor shall be isolated from the fan housing by torsionallyflexible isolation grommets. The fan and motor assembly must be capable of overcoming the external static pressures as shown on the schedule. CFM/Staticpressure rating of the unit shall be based on a dry coil and a clean filter in place.
Option: High static motors available for sizes 018 through 060 (except GCV041).
Refrigerant CircuitUnits shall have a sealed refrigerant circuit including a high efficient rotary or reciprocating compressor designed for heat pump operation, a capillary tubeassembly for refrigerant metering, an enhanced aluminum lanced fin and rifled copper tube refrigerant to air heat exchanger, a reversing valve, a coaxial (tubein tube) refrigerant to water heat exchanger, and safety controls including a high pressure switch, a low pressure sensor, and a low water temperature sensor.
GENESIS COMPACT (GC) SERIESENGINEERING GUIDESPECIFICATIONSRevision: 08/08/02 B
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
Access fittings shall be factory installed on high and low pressure refrigerant lines to facilitate field service. Activation of any safety device shall preventcompressor operation via a lockout device. The lockout shall be reset at the thermostat or at the contractor supplied disconnect switch. Units which may bereset only at the disconnect switch only SHALL NOT be acceptable.
Hermetic reciprocating compressors shall be internally sprung. The compressor will be mounted on external computer selected isolating grommets. Theexternal grommets will be secured to a heavy gauge compressor plate that has rubber grommet isolation from the cabinet base, which provides multiplelevels of isolation. Compressor shall have thermal overload protection and be located in an insulated compartment away from air stream to minimize soundtransmission. Refrigerant to air heat exchangers shall utilize enhanced lanced aluminum fins and rifled copper tube construction rated to withstand 450PSIG (3108 kPa) refrigerant working pressure. Refrigerant to water heat exchangers shall be of copper inner water tube and steel refrigerant outer tubedesign, rated to withstand 450 PSIG (3108 kPa) working refrigerant pressure and 450 PSIG (3108 kPa) working water pressure. Plate to plate heatexchangers ARE NOT acceptable.Reversing valves shall be four-way solenoid activated refrigerant valves which shall fail to heating operation should the solenoid fail to function. If the reversingvalve solenoid fails to cooling, a low temperature thermostat must be provided to prevent over-cooling an already cold room.
Option: The unit will be supplied with cupro-nickel coaxial water to refrigerant heat exchangers.
Drain PanThe drain pan shall be constructed to inhibit corrosion and fully insulated. Drain outlet shall be located on pan as to allow complete and unobstructed drainageof condensate. The unit as standard will be supplied with solid-state electronic condensate overflow protection. Mechanical float switches WILL NOT beaccepted.
ElectricalA control box shall be located within the unit compressor compartment and shall contain a 50VA transformer, 24 Volt activated, 2 or 3 pole compressorcontactor, terminal block for thermostat wiring and solid-state controller for complete unit operation. Electro-mechanical operation WILL NOT be accepted.Units shall be name-plated for use with time delay fuses or HACR circuit breakers. Unit controls shall be 24 Volt and provide heating or cooling as required bythe remote thermostat/sensor.Option: CE Mark Construction: To include power connection block, compressor grounding, fully insulated terminals and CE listed electrical components.
Solid-State Control SystemUnits shall have a solid-state control system (CXM). The control shall interface with a heat pump (Y,O) wall thermostat, mechanical or electronic. The controlsystem microprocessor board shall be specifically designed to protect against building electrical system noise contamination, EMI, and RFI interference. Thecontrol system shall have the following features:a. Anti-short cycle time delay on compressor operation, time delay shall be 5 minutes minimum.b. Random start on power up mode.c. Low voltage protection.d High voltage protection.e. Unit shutdown on high or low refrigerant pressures.f. Unit shutdown on low water temperature.g. Water coil low temperature cutout (selectable for water or anti-freeze).h. Condensate overflow shutdown.i. Option to reset unit at thermostat or disconnect. Fault type shall be retained in memory if reset at thermostat.j. Automatic intelligent reset. Unit shall automatically reset 5 minutes after trip if the fault has cleared. Should a fault re-occur 3 times sequentially then
permanent lockout will occur.k. Ability to defeat time delays for servicing.l. Light emitting diodes (LED) to indicate high pressure, low pressure, low voltage, high voltage, low water temperature cut-out, condensate overflow and
control status.m. The low pressure switch SHALL NOT be monitored for the first 120 seconds after a compressor start command to prevent nuisance safety trips.n. Remote fault type indication at thermostat.o. Selectable 24V or pilot duty dry contact alarm output.p. 24V output to cycle a motorized water valve with compressor contactor.
Option: Enhanced control features (DXM)Control shall have all the features of the CXM control with the following additional features:a. A removable thermostat connector.b. Random start on return from night setback.c. Minimized reversing valve operation for extended life and quiet operation.d. Night setback control from low temperature thermostat, with 2-hour override initiated by a momentary signal from the thermostat.e. Dry contact night setback output for digital night setback thermostats.f. Ability to work with heat/cool (Y, W) thermostats.
GENESIS COMPACT (GC) SERIESENGINEERING GUIDESPECIFICATIONS (cont.)Revision: 06/03/02 B
GC Submittal DataContractor: P.O.:
Engineer:
Project Name: Unit Tag:
ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be asdescribed herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and otherinformation contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster's opinion or commendation of its products.The latest version of this document is available at www.climatemaster.com.
Page ______ of ______Rev.: 03/13/03
*LC279*LC279
g. Ability to work with heat pump thermostats using O or B reversing valve control.h. Single grounded wire to initiate night setback, or emergency shutdown.i. Boilerless system control can switch automatically to electric heat at low loop water temperature.j. Control board shall allow up to 3 units to be operated from one thermostat without any auxiliary controls.k. A relay to operate an external damper. The control to be such that the damper WILL NOT open until 30 minutes after the unit comes back from
unoccupied mode.l. Fan speed selection at thermostat.m. A relay to restart a central pump or control a 24V motorized water valve.n. Intelligent fan speed selection based upon thermostat demand and/or dehumidistat signal.
Option: LonWorks Control SystemUnits shall have all the features listed above and the control board will be supplied with a LonWorks interface board. This will permit all units to be daisy chainconnected by a 2-wire twisted pair shielded cable. The following points must be available at a central or remote computer location:a. space temperature.b. leaving water temperature.c. discharge air temperature.d. command of space temperature setpoint.e. cooling status.f. heating status.g. fan “ON/AUTO” position of space thermostat as specified above.h. unoccupied/occupied command.i. compressor shutdown (load shedding) command.j. emergency shutdown command.k. cooling command.l. heating command.m. fan “ON/AUTO” command.
Field Installed Options
Hose KitsAll units 120,000 BTUH (35 kW) and below shall be connected with hoses. The hoses shall be 2 feet (0.6m) long, braided stainless steel; fire rated hosescomplete with adapters. Only fire rated hoses will be accepted.
Thermostats
Electromechanical ThermostatsThermostats shall be single-stage manual change-over with HEAT-OFF-COOL system switch and fan ON-AUTO switch.
Electronic ThermostatsThermostat shall be single-stage, manual changeover with HEAT-OFF-COOL system switch and fan ON-AUTO switch. Thermostat shall have a LCD displaywith temperature and setpoint indication selectable for °F or °C. Thermostat shall only require 4 wires for connection.
Thermostat shall be single-stage, manual or automatic changeover with HEAT-OFF-COOL-AUTO system settings and fan ON-AUTO settings. Thermostatshall have a back-lit LCD display with temperature, setpoints, mode, and status indication. The temperature indication shall be selectable for °F or °C. ASystem Test feature shall be provided to simplify troubleshooting. The thermostat shall provide permanent memory of setpoints without batteries. A fault LEDshall be provided. Thermostat shall provide optional extended end of cycle fan operation, outdoor air temperature display, heating setpoint range limit, coolingsetpoint range limit, and temperaturedisplay offset.
Thermostat shall be multi-stage (3H/2C), manual or automatic change over with HEAT-OFF-COOL-AUTO system settings and fan ON-AUTO settings.Thermostat shall have an LCD display with temperature, set-points, mode, and status indication. The temperature indication shall be selectable for °F or °C. ASystem Test feature shall be provided to simplify troubleshooting. The thermostat shall provide permanent memory of setpoints without batteries. A fault LEDshall be provided. Thermostat shall provide optional extended end of cycle fan operation, heating setpoint range limit, cooling setpoint range limit, temperaturedisplay offset, temperature display disable, keypad lockout, dead-band range setting, and inter-stage differential settings. Thermostat shall provide capability toaverage from 1 to 9 remote sensors. Thermostat shall switch to selectable unoccupied setpoints upon signal from DXM control within unit. The thermostat shallrevert to occupied setpoints when the Override key is pressed.
Thermostat shall be 7 day programmable, multi-stage (3H/2C), manual or automatic change over with HEAT-OFF-COOL-AUTO system settings and fan ON-AUTO settings. Thermostat shall have an LCD display with temperature, set-points, mode, and status indication. The temperature indication shall be selectablefor °F or °C. A System Test feature shall be provided to simplify troubleshooting. The thermostat shall provide permanent memory of setpoints and programwithout batteries. A fault LED shall be provided. Thermostat shall provide optional extended end of cycle fan operation, heating setpoint range limit, cooling set-point range limit, temperature display offset, temperature display disable, keypad lockout, dead-band range setting, and inter-stage differential settings.Thermostat shall provide capability to average from 1 to 9 remote sensors.
GENESIS COMPACT (GC) SERIESENGINEERING GUIDESPECIFICATIONS (cont.)Revision: 06/03/02 B