Client Name : BASF India Limited Project Name : Project GIR Project Number: G3IR
Specification G3IR-1050-65-SP-9031 Date 18-Jul-12
Page 1 of 12
66 kV Instrument Transformer
G3IR-1050-65-SP-9031_R0 Page 1 of 12
Project Document No: G3IR-1050-65-SP-9031
Unit: General Discipline: Electrical Document Type: Specification
Document Title: SPECIFICATION FOR 66 kV INSTRUMENT TRANSFORMER
1 30-Jul-12 Issued for Design HS NG VP
0 18-Jul-12 Issued for RFQ HS NG VP
Fluor BASF Revision Date Purpose Prepared By Checked By
Approved By
ISSUED FOR DESIGN08 Aug 2012
Client Name : BASF India Limited Project Name : Project GIR Project Number: G3IR
Specification G3IR-1050-65-SP-9031 Date 18-Jul-12
Page 2 of 12
66 kV Instrument Transformer
G3IR-1050-65-SP-9031_R0 Page 2 of 12
Record of Revisions
This specification has been revised as indicated below and described in the revision record on the following page. Please destroy all previous revisions.
Revision
No. Date Description
0 18-Jul-12 Issued for Design (RFQ)
1 30-Jul-12 Issued for Design
Client Name : BASF India Limited Project Name : Project GIR Project Number: G3IR
Specification G3IR-1050-65-SP-9031 Date 18-Jul-12
Page 3 of 12
66 kV Instrument Transformer
G3IR-1050-65-SP-9031_R0 Page 3 of 12
TABLE OF CONTENTS
1.0 GENERAL.................................................................................................................................................. 4
1.1 SCOPE....................................................................................................................................................... 4
1.2 REFERENCES........................................................................................................................................... 4
1.3 SERVICE CONDITION .............................................................................................................................. 5
2.0 TECHNICAL REQUIREMENTS ................................................................................................................ 5
2.1 GENERAL.................................................................................................................................................. 5
2.2 CURRENT TRANSFORMERS (CTs)........................................................................................................ 6
2.3 VOLTAGE TRANSFORMERS (VTs) ........................................................................................................ 7
2.4 MARSHALLING BOX................................................................................................................................ 8
3.0 INSPECTION AND TESTS........................................................................................................................ 8
3.1 66kV VOLTAGE TRANSFORMER ........................................................................................................... 8
3.2 66 kV Current Transformer...................................................................................................................... 9
4.0 SPARE PARTS.......................................................................................................................................... 9
5.0 FITTINGS AND ACCESSORIES............................................................................................................... 9
6.0 SUPPORT STRUCTURE......................................................................................................................... 10
7.0 DRAWINGS AND DOCUMENTS ............................................................................................................ 10
ANNEXURE-A
(SPECIAL REQUIREMENTS FOR DGVCL METERING INSTRUMENT TRANSFORMERS) ........................ 11
Client Name : BASF India Limited Project Name : Project GIR Project Number: G3IR
Specification G3IR-1050-65-SP-9031 Date 18-Jul-12
Page 4 of 12
66 kV Instrument Transformer
G3IR-1050-65-SP-9031_R0 Page 4 of 12
1.0 GENERAL
1.1 SCOPE
1.1.1 This specification is intended to cover design, engineering, procurement,
manufacture, inspection and testing at manufacturer’s works, packing, loading,
forwarding, transport and delivery to site, erection / installation, testing and
commissioning at site of isolator suitable for current and voltage transformers for
outdoor use.
1.1.2 For specific requirements of tariff metering VT and CT, please refer to Annexure-A
for details. Whatever arrangements / modifications required to be done to meet
the requirements mentioned in the annexure shall be responsibility of supplier.
1.1.3 It is not the intent to specify completely herein all details of design and
construction of the equipment. However, all components shall conform in all
respects to high standards of design engineering, materials of construction,
workmanship and shall also be in line with the current practice for reliable and
efficient functioning of the equipment and be capable of performing in continuous
commercial operation in a manner acceptable to the Owner.
1.1.4 Supplier is required to carefully examine and understand the specifications and
seek clarifications, if required, to ensure that he has understood the specifications
as intended by the Owner. In the absence of any specific clarifications made by
the Owner during bidding stage, the interpretation of Owner shall be final. The
Supplier’s offer should not carry any sections like clarifications, interpretations
and/or assumptions. All such points are required to be clarified during bidding
stage.
1.2 REFERENCES
1.2.1 The instrument transformers and the associated equipment shall conform to the
latest editions of following standards issued by BIS (Bureau of Indian Standards)
and IEC unless otherwise specified. Each publication shall be the latest revision
and addendum in effect on the date this specification is issued for Purchase,
unless noted otherwise. Except as modified by the requirements specified herein
or the details of the drawings, as a minimum, work included in this specification
shall conform to the applicable provisions of these publications:
Client Name : BASF India Limited Project Name : Project GIR Project Number: G3IR
Specification G3IR-1050-65-SP-9031 Date 18-Jul-12
Page 5 of 12
66 kV Instrument Transformer
G3IR-1050-65-SP-9031_R0 Page 5 of 12
S.No. Description IS/IEC
1 Specification for current transformer IS-2705 (Part I to V)
2 Application guide for current transformer. IS-4201
3 High voltage porcelain bushings IS-2099
4 Hollow insulator for use in electrical equipment IS-5621
5 Specification for Voltage transformer. IS-3156 (Part I to IV)
6 Application guide for voltage transformer. IS-4146
7 Specification of electric power connectors IS-5561
8 PVC insulated cables up to & including 1100 volts.
IS-1554
1.2.2 In case of any contradiction between various referred standards/specification/data
sheets and statutory regulations, it shall be brought to the notice of Client for
resolution. Generally the following order of priority shall govern,
Statutory regulations
BASF Guidlines
Data Sheets
This specification
Codes and standards
1.3 SERVICE CONDITION
1.3.1 The instrument transformers shall, in all respects, be suitable for operation under
the service conditions stated in the RFQ.
1.3.2 The instrument transformers shall be fully stabilized thermally to give a life
expectancy of twenty five (25) years under site conditions and take care of effect
of direct solar radiation. Periodic maintenance interval shall be greater than 5
years.
2.0 TECHNICAL REQUIREMENTS
2.1 GENERAL
2.1.1 The instrument transformers shall be hermetically sealed units. The instrument
transformers shall be provided with filling and drain plugs.
Client Name : BASF India Limited Project Name : Project GIR Project Number: G3IR
Specification G3IR-1050-65-SP-9031 Date 18-Jul-12
Page 6 of 12
66 kV Instrument Transformer
G3IR-1050-65-SP-9031_R0 Page 6 of 12
2.1.2 The instrument transformers i.e. current and voltage transformers shall be single
phase transformer units and shall be supplied with a common marshalling box for
a set of three single phase units.
2.1.3 Polarity marks shall indelibly be marked on each instrument transformer and at
the lead terminals at the associated terminal block.
2.1.4 The parameters for the CT's and VT's are given in the following clauses shall be
reviewed during detailed engineering based on the burden and other calculations
to be furnished by the Bidder during detailed engineering.
2.2 CURRENT TRANSFORMERS (CTs)
2.2.1 The CTs shall be capable of withstanding the dynamic & thermal stresses and
short circuit current at 31.5 kA for 1 sec.
2.2.2 The CTs shall have single primary of bar type with following requirements:
The secondary shall be totally encased in metallic shielding providing a
uniform equi-potential surface for even electric field distribution.
The upper part of insulation assembly sealing on primary bar shall be
properly secured to avoid any damage during transportation due to
relative movement between insulation assembly and top dome.
The insulator shall be one piece without any metallic flange joint.
The lowest part of insulation assembly shall be properly secured to avoid
any risk of damage due to transportation stresses.
2.2.3 The core lamination shall be of cold rolled grain oriented silicon steel or other
equivalent alloys. The cores shall produce undistorted secondary current under
transient conditions at all ratios with specified parameters.
2.2.4 CT shall be oil-filled, self cooled, hermetically sealed type. CT shall be provided
with oil level gauge and pressure relief device. An inert gas cushion shall be
maintained on top of the oil.
2.2.5 CT shall be single phase unit, designed for upright mounting on steel structure
and furnished complete with anchoring hardware. Insulator shall be wet process
porcelain, brown glazed and free from imperfections. All metal parts and
hardware shall be hot dip galvanised.
Client Name : BASF India Limited Project Name : Project GIR Project Number: G3IR
Specification G3IR-1050-65-SP-9031 Date 18-Jul-12
Page 7 of 12
66 kV Instrument Transformer
G3IR-1050-65-SP-9031_R0 Page 7 of 12
2.2.6 Different ratios (if applicable) shall be achieved by secondary taps only, and
primary reconnections shall not be accepted.
2.2.7 The guaranteed burdens and accuracy class are to be intended as simultaneous
for all cores.
2.2.8 The secondary terminals shall be terminated on stud type non-disconnecting
terminal blocks inside the terminal box of degree of protection IP: 55 at the bottom
of CT. The terminal box should be weather proof and dust-tight, complete with
gasketed front access cover and removable gland plate at bottom for cable entry
2.2.9 The CTs shall have provision for taking oil samples from bottom of CT without
exposure to atmosphere to carry out dissolved gas analysis periodically.
Contractor shall give his recommendations for such analysis, i.e. frequency of
test, norms of acceptance, quantity of oil to be withdrawn, and treatment of CT.
2.2.10 The winding shall be suitable for simultaneous 100% full load continuous rating.
The winding shall be capable of desired output as per specified limit.
2.2.11 Rating of the CT shall be as per the single line diagram attached with the RFQ.
Supplier to submit the VA burden calculation report for owner’s approval.
2.3 VOLTAGE TRANSFORMERS (VTs)
2.3.1 The VT shall be capable of withstanding the dynamic and thermal stresses of
short circuit current of 31.5 KA for 1 sec. without any damage or deterioration.
There shall be no radio interference when the equipment is operated at maximum
service voltage. The safety clearances of all live parts of the equipment shall be
as per relevant standards.
2.3.2 VT shall be oil-filled, self cooled, hermetically sealed type. VT shall be provided
with oil level gauge and pressure relief device. An inert gas cushion shall be
maintained on top of the oil.
2.3.3 VT shall be single phase unit, designed for upright mounting on steel structure
and furnished complete with anchoring hardware. Insulator shall be wet process
porcelain, brown glazed and free from imperfections. All metal parts and
hardware shall be hot dip galvanised.
2.3.4 The maximum temperature in any part of the equipment at specified rating shall
not exceed the permissible limits as stipulated in the relevant standards.
Client Name : BASF India Limited Project Name : Project GIR Project Number: G3IR
Specification G3IR-1050-65-SP-9031 Date 18-Jul-12
Page 8 of 12
66 kV Instrument Transformer
G3IR-1050-65-SP-9031_R0 Page 8 of 12
2.3.5 Rating of the VT shall be as per the single line diagram attached with the RFQ.
Supplier to submit the VA burden calculation report for owner’s approval.
2.4 MARSHALLING BOX
2.4.1 The wiring diagram for the interconnection of three phase instrument transformer
shall be pasted inside the box in such a manner so that it is visible and it does not
deteriorate with time.
2.4.2 Terminal blocks in the marshaling box shall have facility for star/delta formation,
short circuiting and grounding of secondary terminals. The box shall have enough
terminals to wire all control circuits plus 20 spare terminals.
3.0 INSPECTION AND TESTS
The current and voltage transformers shall confirm to type tests and shall be subjected to routine
and type tests in accordance with the relevant IEC/IS. Following is the list of tests (not limited to)
which vendor shall be perform:
3.1 66kV VOLTAGE TRANSFORMER
3.1.1 Type test reports for the following tests shall be submitted for EHV Voltage
Transformer
Temperature rise test
Chopped impulse test
EMC radio Interference Voltage tests, if applicable
Short Circuit Withstand Capability test
Lightning impulse test
Wet test
3.1.2 Routine Tests: The following Routine test shall be conducted under this contract :
Capacitance and tan d measurement at power-frequency
Power Frequency withstand test
Measurement of Partial discharges
Verification of terminal markings
Power-frequency withstand test on the L.V terminal
Client Name : BASF India Limited Project Name : Project GIR Project Number: G3IR
Specification G3IR-1050-65-SP-9031 Date 18-Jul-12
Page 9 of 12
66 kV Instrument Transformer
G3IR-1050-65-SP-9031_R0 Page 9 of 12
3.2 66 kV Current Transformer
3.2.1 Type test reports for the following tests shall be submitted for EHV Current
Transformer
Temperature rise test
Short time current test
Switching impulse voltage test
Lightning impulse test
Wet test for outdoor type transformers
Radio interference voltage measurement
3.2.2 Routine Tests: The following Routine test shall be conducted under this Contract:
Power Frequency withstand test on primary winding
Power Frequency withstand test on secondary winding
Power Frequency withstand test between sections
Measurement of Partial discharges
Verification of terminal markings
Accuracy Check (Determination of errors)
Ratio Test
4.0 SPARE PARTS
Bidder shall submit list of spares recommended by him for satisfactory operation of the circuit
breakers for first two (2) years and rate for each spare shall also be quoted. The owner shall
decide the actual quantity of spare parts to be ordered on the basis of the prices of the spare
parts, quoted by the bidder.
5.0 FITTINGS AND ACCESSORIES
a) Each CT shall be furnished complete with the accessories as listed below:
1. Base frame with anchoring bolts, nuts etc. for fixing the equipment on to structure.
2. Two grounding pads with bolts and spring washers.
3. Lifting Lugs.
Client Name : BASF India Limited Project Name : Project GIR Project Number: G3IR
Specification G3IR-1050-65-SP-9031 Date 18-Jul-12 Page 10 of 12
66 kV Instrument Transformer
G3IR-1050-65-SP-9031_R0 Page 10 of 12
4. Clamp type bimetallic terminal connectors.
5. Weather-proof secondary terminal box with set of terminals.
6. Grading ring, if necessary.
7. Oil level gauge and pressure relief device.
8. Oil sampling valve.
9. Spark gap arrangement
10. Nitrogen sealing hole cover
11. Other standard accessories which are not specifically mentioned but are required
with current transformers of such type and rating for efficient and trouble-free
operation and make the installation complete.
b) Each VT shall be furnished complete with the accessories as listed below :
1. Base frame with anchoring bolts, nuts etc. for fixing the equipment on to structure.
2. Two grounding pads with bolts and spring washers.
3. Lifting Lugs.
4. Clamp type bimetallic terminal connectors.
5. Weather-proof secondary terminal box with set of terminals and 3 nos. HRC
fuses.
6. Grading ring, if necessary.
7. Oil level gauge and pressure relief device.
8. Other standard accessories which are not specifically mentioned but are required
with voltage transformers of such type and rating for efficient and trouble-free
operation and make the installation complete.
6.0 SUPPORT STRUCTURE
For steel support structure specification, refer Doc. No. G3IR-1050-65-SP-9042 attached with
RFQ.
7.0 DRAWINGS AND DOCUMENTS
The Vendor shall furnish drawings in accordance with SDDC form, enclosed with the Bid.
Client Name : BASF India Limited Project Name : Project GIR Project Number: G3IR
Specification G3IR-1050-65-SP-9031 Date 18-Jul-12 Page 11 of 12
66 kV Instrument Transformer
G3IR-1050-65-SP-9031_R0 Page 11 of 12
ANNEXURE-A
SPECIAL REQUIREMENTS FOR DGVCL METERING INSTRUMENT TRANSFORMERS
1. The DGVCL metering shall be located in the switchyard nearest to CTs and EMPTs in the
Weatherproof MMB / SMC box with adequate sealing arrangement.
2. All the CTs and EMPTs must be provided with Stainless Steel Bellows & No Noitrogen gas
filling or Rubber Gasket will be acceptable in case of 66 kV class of voltage.
3. For multi ratio CTs:
(i) The selection of ratio must be provided only on secondary of the CTs.
(ii) The value of ISF shall have to be certified for each ratio of the metering core.
4. The copy of all the type test certificates in respect of sample CT and EMPT as per specified
under CI. No. 9.1 .1 of IS-2705 (Part-I) for CTs and CI No. 9.1.1 of IS-3156 (Part-I) of similar
class of accuracy, similar design, rating and technical specification conducted on proto type
sample by the supplier at any Govt. or Govt. approved test house (not later than (FIVE years
before the HME of submission of certificates), shall have to be submitted at DGVCL Corporate
office for necessary approval before procurement / placement of procurement orders. Failing
to submit the above Type test certificates any subsequences arise after placement of order /
procurement without the approval, shall have to be borne by the supplier.
5. All the CTs produced and to be installed / used for tariff metering purpose shall have to be got
tested at ERDA-Vadodara for all routine tests, as specified under CI. No. 9.1.2 of IS-2705
(Part-1), including the test of ISF as per CI. No. 7.1.2 of IS-2705 (Part-2). The original copy
with one zerox copy of ERDA Routine Test Certificates along with the ERDA test certificate for
ISF test shall have to be submitted at DGVCL Corporate Office for final approval before actual
commissioning of the CTs at connection site. Also the copy of OGA drawing, Name plate
drawing and the secondary terminals drawings of the above CTs shall have to be submitted
along with the ERDA test certificates in case of CTs & supplier's Acceptable test certificates
(witnessed by GETCO officer) in case of EMPTs for final approval.
6. The supplier shall have to arrange routine testing of all EMPTs at manufacturer's works as
specified under CI . No. 9.1.2 of IS-3156 (Part-1). The acceptance tests will be witnessed by
concern GETCO officer at supplier's works . The accuracy test on PT shall not be conducted
with simultaneous burden of all cores, instead the tariff metering core shall be tested
separately for 10 VA and 2.5 VA burden i.e. as per CI. NO. 5 of IS-3156 (Part-II). The original
Client Name : BASF India Limited Project Name : Project GIR Project Number: G3IR
Specification G3IR-1050-65-SP-9031 Date 18-Jul-12 Page 12 of 12
66 kV Instrument Transformer
G3IR-1050-65-SP-9031_R0 Page 12 of 12
copy with one zerox copy of supplier's Acceptance test certificates (witnessed and signed by
GETCO officer) shall have to be submitted for final approval before actual commissioning of
the same. the supplier shall also have to submit copy of OGA drawing, Name plate drawing
and secondary terminal/ box drawing for necessary approval along with the Acceptance tests
certificates .
7. Supplier shall have to intimate SE (TR) of concern GETCO circle, seven days in advance for
deputation of concerned Engineer for witnessing the Acceptance tests at their supplier works.
8. Supplier shall have to obtain necessary approval from the GETCO Corporate office in respect
of 66 KV SLD, its protection system , PLCC / VHF system and 66 KV Switch Yard and also
necessary approval from the Chief Electricity Commissioner of E&P Dept., GOG before actual
commissioning of the switch yard.