FusionModule800Smart Small Data Center Solution

Page 2: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

02 Preface

03 Huawei Solution Overview

07 Customer Benefits

14 System Parameters

15 Key Components

17 Typical Configurations

18 Global Services & Applications

Contents

01 FusionModule800Smart Small Data Center Solution

Page 3: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

Preface

Does your small data center look like this?

• Long delivery period and different appearances due to separately purchased components and onsite installation

• Difficult O&M with disunified monitoring platforms • Low integration and large footprint • High power consumption of constant-frequency air conditioners without contained aisles • Serious condensation due to poor temperature and humidity control • Frequent fire accidents due to lack of battery overheat protection

Do you want to deploy a small data center like this?

02

Page 4: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

FusionModule800 integrates the power distribution, UPS , monitoring, cooling, and cabinet system. The converged cabinet integrates the PDU, UPS, rack air conditioner,

and monitoring system, saving the installation space.

The IT cabinet can be flexibly extended on both sides of it. A single module supports a maximum of eight cabinets, at most 12 kW IT load, and up to 6 kW/R power density. The module has a single-row 250 mm cold aisle containment.

Layout (cold aisle)

Huawei Solution Overview

03 FusionModule800Smart Small Data Center Solution

Page 5: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

• Small data center, branch data center, reconstructed data center, or data center with capacity expansion

• Indoor data center

• Tier I or tier II construction level

Application Scenarios01

Finance (branches and large banking outlets), government, education, healthcare, public security, transportation, energy, small-and medium-sized enterprises, retail merchandising and carriers (business hall), etc.

Applicable Industry02

04

Page 6: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

Indicator module

PDU module

ECC800 monitoring module

Air conditioner indoor unit

UPS

Camera

10 inch screen

Glass door

Aisle

System Architecture03

Core Subsystem04UPS system

• Rack-mounted • 10kVA • 20kVA

Power distribution system

• Rack power distribution module • Indicator module • rPDU

Refrigerating system

• Variable-frequency air conditioner • Rack-mounted • Low-load dehumidification

Huawei Solution Overview

05 FusionModule800Smart Small Data Center Solution

Page 7: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

Indicator module

PDU module

ECC800 monitoring module

Air conditioner indoor unit

UPS

Camera

10 inch screen

Glass door

Aisle

Cabinet system

• 19-inch standard cabinet • Contained aisle • Glass door • 250 mm single-row aisle

Cabling system

• Power cable tray • Signal cable tray

Lightning protection system

• Class C surge arrester for the entire system

• Class D surge arrester for the UPS

• Class D surge arrester for the air conditioner

Monitoring system

• Monitoring module • 10-inch screen display • SMS alarms • Camera • Door access control

system

• Temperature, humidity, and smoke sensors

• Door status sensor • Water leakage sensor • Intelligent battery

management

06

Page 8: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

Quick installation and fast service launch

Fast Delivery01

Features and Values • Factory-installation and factory-commissioning of the PDU, UPS, air conditioner, monitoring system, and aisle • Pre-fabrication of cables • Pre-filling of refrigerant, free of welding for the connection between the air conditioner indoor and outdoor

units • Only four hours required for onsite installation of a smart module with three cabinets, saving the installation

cost and reducing the service online time

① The product is prefabricated, pre-installed, and pre-commissioned in the factory.

② You simply need to combine the cabinets and connect some cables and air conditioner pipes on site.

③ The installation is complete.

Customer Benefits Simple, Efficient, Reliable

07 FusionModule800Smart Small Data Center Solution

Page 9: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

Remote web UI monitoring, mobile phone app O&M, local 10-inch screen display, and centralized management of multiple sites

Intelligent O&M02

Features and Values • The ECC800 monitoring module monitors the UPS, air conditioner, temperature and humidity sensor, water

sensor, door status sensor, and smoke sensor of the system in real time, ensuring a reliable infrastructure environment for IT equipment.

• The 10-inch local large screen LCD user-friendly interface communicates with the ECC800 over the wireless network and displays various operating parameters of the system in real time.

• SMS alarms ensure that the O&M personnel is notified of the alarm information in time. • The entire power and environment system can be accessed by logging in to the ECC800 monitoring module

over the remote web UI of a single module, implementing remote O&M.

1 Remote monitoring of a single module

ECC800

Water sensor

Smoke detector

Mobile phone

Cabinet door status sensor

Temperature sensor

Independent deployment AI/DI unit

AI/DI

AI/DI

UPS2000-G

RS485FE

VCN500 Camera

BIM

CIM

WiFi

NetCol5000-A011 air conditioner

Access actuator

RF_Z

RF_Z

NetCol5000-A011 air conditioner

SPD

Smart ETH gateway

Smart ETH gateway

Internet

PAD

08

Page 10: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

2 Centralized monitoring and unified management of multiple modules

DC

DC

DC

DC

DC

Centralized management

Large screen display

DC

Mobile app

Customer Benefits Simple, Efficient, Reliable

Features and Values • If there are multiple sites, the Huawei NetEco intelligent NMS can be used to implement centralized monitoring and

unified management of multiple modules. • The unique GIS map mode highlights the faulty sites, enabling quick location of the alarm site by using the GIS map. • Support for integration by a third-party NMS (including but not limited to eSight) allows unified network

management with the IT/IP equipment. • Mobile phone app O&M makes it possible to monitor the power and environment system of the equipment room

in real time any time and anywhere, implementing unattended operation. • The equipment room view management, alarm management, permission and security management, report

management, capacity management, and asset management functions are available.

09 FusionModule800Smart Small Data Center Solution

Page 11: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

Features and Values • The all-in-one design integrates the UPS, PDU, monitoring system, and air conditioner in one cabinet. • Compared with the in-row air conditioner or traditional refrigerating solution, the air conditioner

redundancy solution saves the installation space of at least two cabinets.

High integration, saving the installation space

Smaller required floor space01

UPS

ECC800

Air conditioner indoor unit

Power distribution module

Indicator module

Converged cabinet

Only 4.05 m2 for the smart module 3IT cabinets At least 10 m2 for 3IT cabinets of the traditional small data center

VS

Customer Benefits Simple, Efficient, Reliable

10

Page 12: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

Features and Values • The all-in-one cabinet with the contained aisle effectively separates the hot and cold airflow.

• The use of the advanced CFD head simulation design optimizes the air transmission performance and prevents hotspots in the aisle, creating a highly efficient energy conservation effect.

• Combined with the PUE (Beijing) as low as 1.37, the contained aisle and DC inverter compressor air conditioner save the energy by more than 40% compared with the traditional solution.

Contained aisle and DC inverter compressor, featuring high energy efficiency

High energy efficiency02

① CFD simulation of the traditional small data center without the contained aisle – mixed cold and hot airflow and low cooling efficiency

② CFD simulation of the smart module with the contained aisle – isolated hot and cold airflow and maximized cooling efficiency

Remarks: $8,338 electricity expense is saved every year compared with the traditional solution (10 kW IT load, 2.1 PUE)

Customer Benefits Simple, Efficient, Reliable

11 FusionModule800Smart Small Data Center Solution

Page 13: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

Features and Values

• Intelligent (low-load) dehumidificationThe air conditioner can switch between low-load dehumidification, dehumidification, and cooling automatically based on the humidity and temperature of the equipment room.

• Expanded cooling operation scopeThe cooling system runs with the minimum of 10% IT load, which is the lowest in the industry.

• Reduced costThe high-humidity issue of the traditional equipment room is resolved by adding dehumidifiers in the micro-module. The costs are high and the O&M is complex.

• Energy conservationThe Huawei patent technology does not require additional heat compensation by enabling electric auxiliary heat during the low-load dehumidification process.

Low-load dehumidification, intelligent dehumidification

Condensation-free design01

Customer Benefits Simple, Efficient, Reliable

12

Page 14: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

Battery SOC/SOH, intelligent shutdown upon overheat

Wireless battery monitoring02

iBAT iBOX

wifi

ECC800 monitoring module

Battery overheatBattery overvoltage

Increase of internal resistance

Customer Benefits Simple, Highly Efficient, Reliable

Features and Values

• Active O&M management without human inspection • Online real-time monitoring of core parameters such as the battery temperature by the UPS. When

overtemperature occurs, the UPS automatically shut down the battery string to eliminate fire risks. • Real-time detection of the voltage, temperature, current, and internal resistance of a single battery and

full monitoring of core parameters without periodic measurement of battery parameters • Automatic test of battery performance, battery SOC and SOH monitoring by using the proprietary

algorithm, and early-warning of battery failure

• Wireless transmission and simple deployment • Wireless communication between iBat and iBox and flexible networking without complex cabling,

reducing the deployment time by 50% • Powerful networking functions. One iBox can connect to 300 iBats, saving the investment.

13 FusionModule800Smart Small Data Center Solution

Page 15: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

System Parameters

Overall Solution

Maximum IT power consumption 6 kW a 12 kW

Maximum number of cabinets in a singlesmart module

6 8

IT cabinet quantity 0-4 (including 0-1 network cabinet) 0-6 (0-1 network cabinet)

Contained aisle Cold aisle

Maximum power density of a singlecabinet

6 kW

Battery deployment mode Battery pack/Battery cabinet/Battery rack

Power backup time 15 min/30 min

Installation mode Concrete floor or raised floor

Power system 380/400/415 V AC, 50/60 Hz, 3Ph+N+PE

System protection level IP20

Operating temperature -10℃ to +55℃

Cooling System

Power supply type Mains supplies power

Air conditioner configuration 1+0, 1+1, 2+0, 2+1

Power Supply and Distribution System

Power input Single input

Power input switch capacity 63 A

UPS capacity 10 kVA 20 kVA

UPS configuration N, N+1 (N = 1)

AC SPD In 20 kA, Imax 40 kA, 8/20 μs

Maintenance bypass Standard configuration

Monitoring system

Monitoring systemMobile phone APP, SMS alarm, Web access, centralized management for multiple DCs

10 inched Pad Standard

Water sensor Optional

Smoke sensor Standard

Door status sensor Optional

Door access control system Optional (2 most)

Temperature and humidity sensor Standard

Local mobile app Standard (ECC APP)

Remote mobile app Optional (NetEco APP)

SMS alarm Standard

Camera (4 most)Optional, camera of module (1 most)

Optional, room camera (4 most)

Remarks:

a. The recommended IT load for smart module is 3 kW–12 kW. If the IT power is less than 3 kW, FusionModule500 is recommended.

14

Page 16: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

Key Components

1 Rack UPS

2 Power Distribution Module

Type Parameter 10 kVA 20 kVA

Input parameter

Rated input voltage 380/400/415 V AC, 50/60 Hz, 3Ph+N+PE

Input voltage range 138–485 V AC, 50/60 Hz, 3Ph+N+PE

Input frequency range 40–70 Hz

Output parameter

Rated voltage220/230/240 V AC, 50/60 Hz,1Ph+N+PE

380/400/415 V AC, 50/60 Hz, 3Ph+N+PE

Power factor 0.9

Maximum efficiency 94.50% 95%

Overload capability105% ≤ Load < 125%, bypass in 5 min;125% ≤ Load < 150%, bypass in 1 min;Load ≥ 150%, bypass in 0.1s

Structural parameters

Installation mode Rack-mounted

Surge protectionThe AC input end meets requirements of class D surgeprotection (differential/common mode 5 kA, 8/20 μs)

Environment parameter

Communication Dry contact/USB/Modbus/SNMP

Operating temperature 0–40℃

Relative humidity 0%–95% RH, no condensation

Maximum altitude < 1000 m (derating for 1000–4000 m)

Storage and transportation temperature

–40℃ to +70℃

Operating temperature 0–40℃

Height 2 U 3 U

Noise < 55 dB < 58 dB

Certification CE, CB, RoHS, TLC, CQC, REACH, WEEE

Honor One of the first Energy Start certified products in the industry, ECA

10kVA

20kVA

Indicator module

Height: 1 U

Power distribution module

Height: 6 U

Output loop: 14

Main switch: 63 A

Corresponding UPS: 10 kVA

Typical configuration: BC12

Power distribution module

Height: 6 U

Output loop: 14

Main switch: 63 A

Corresponding UPS: 20 kVA

Typical configuration: BC13/14

Power distribution module

Height: 3 U

Output loop: 4

Main switch: 63 A

Corresponding UPS: 10 kVA

Typical configuration: BC11

15 FusionModule800Smart Small Data Center Solution

Page 17: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

3 Rack-mounted Air Conditioner

Parameter SpecificationsOperating temperature of theoutdoor unit

–10℃ to +55℃

Height difference between indoor and outdoor units

20 m at most when the outdoor unit is installed higher than theindoor unit

5 m at most when the indoor unit is installed higher than theoutdoor unit

Maximum equivalent length of one-way pipe

≤ 60 m

Water drainage4 m at most for the distance between the up drainage on thewater pump and the floor on which the cabinet is installed

Pipe and cable routing Top or bottom routing

Certification REACH, RoHS, CE, SASO

Item Indoor Unit (Cooling System)Power system 220/230/240 V AC, 50/60 Hz, 1Ph+N+PE

Maximum current 17.3 A

Cooling mode Air-cooled (horizontal air flow)

Refrigerant R410A

Cooling capacity 11 kW b

Fan type EC fan

Maximum airflow 2600 m3/h

Condensate pump Yes

Dimensions (W×D×H) 442 mm x 800 mm x 468 mm

Net weight / Gross weight 60 kg / 79 kg

Protection level IP20

Installation mode Rack-mounted

Item Outdoor UnitMaximum operating current 30 A

Fan quantity 2

Dimensions (W×D×H) 1327mm×966mm×320mm

Net weight / Gross weight 101kg / 114kg

Protection level IPX4

Front of the air conditioner indoor unit

4 ECC800 Collector Parameter Specifications

FE port WAN_1–2, LAN_1–2

DO output dry contact DO_1–2

AI/DI port AI/DI_1–6/12 V

RS485 port COM1–4/12 V

USB port Wi-Fi module access port

3G/4G antenna port SMS alarm antenna access port

Software Embedded software for web UI monitoring

Rear of the air conditioner indoor unit

Front of the air conditioner outdoor unit

b. The 11kW cooling capacity of the air conditioner is obtained when the indoor dry bulb temperature is 37.8℃, and the outdoor dry bulb temperature is 35℃.

Rated cooling capacity in the nameplate. T1/T3:8kW/7.2kW (T1: indoor dry bulb temperature 27 ℃, outdoor dry bulb temperature 35 ℃; T3: indoor dry bulb temperature 29℃, outdoor dry bulb temperature 46 ℃ )

16

Page 18: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

Typical Configurations

Total IT load ≤ 6kW 6kW<IT ≤ 12kW

Typical configuration BC11C BC12 BC13C BC14d

Aisle containment Cold

UPS (kVA) 10 10+10 20+20 20+20

Air conditioner (Heating and humidifying)

1+0 1+1 2+0 2+1

Input power Single

rPDU 1 2 2 2

UPS outputs 4 14 14 14

Remarks:

c: BC11 and BC13 are only applicable to Tier 1 construction level for enterprises;

d: BC14 includes two cabinets, two heating and humidifying air conditioners are in the converged cabinet. One cooling only air conditioner is in the other cabinets.

BC11

BC13

BC12

BC14

IT load ≤ 6kW

6kW<IT load ≤ 12kW

17 FusionModule800Smart Small Data Center Solution

Page 19: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

Global Services & Applications

Huawei has full-time data center infrastructure service engineers in regions around the globe to provide globalized professional services and fast response. Huawei offers customized services based on the demand of the customer. Currently Huawei provides the following services:

Global Services01

The smart module has been deployed in over 30 countries around

the world with more than 500 deployed modules.

Typical Customers02

• 140+ national delivery management organizations

• 129+ national spare part centers

• 300+ regional warehouses

• 22,000+ service personnel

• 24 x 7 service

24 x 7 remote support service

NM commissioning

service

Active prevention service

(preventive inspection)

Hardware support service

(installation)

Onsite support service

(supervision)

Customer support service (maintenance)

Finance • Ireland Branch of Bank of China • Italy Branch of Bank of

Communications • Orient Finance Holdings (Hong Kong) • Bank of Guiyang

Public Security • Tiantan Police Station • Turkish National Police

Education • Spanish University

Healthcare • Suzhou Institute of Cardiovascular

Health

Government • Xuchang government cloud • Huizhou municipal office, SAT • South Africa COT

18

Page 20: FusionModule800 - datacentrehardware.com€¦ · Sm oke detector Mobile phone Cabinet door status sensor Temperature sensor Independent deployment AI/DI unit AI/DI AI/DI UPS2 0-G

Copyright © Huawei Technologies Co., Ltd. 2017. All rights reserved.

No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd.

General Disclaimer

The information in this document may contain predictive statements including,

without limitation, statements regarding the future financial and operating results,

future product portfolio, new technology, etc. There are a number of factors

that could cause actual results and developments to differ materially from those

expressed or implied in the predictive statements. Therefore, such information

is provided for reference purpose only and constitutes neither an offer nor an

acceptance. Huawei may change the information at any time without notice.

Trademark Notice

, HUAWEI, and are trademarks or registered trademarks of Huawei Technologies Co., Ltd.

Other trademarks, product, service and company names mentioned are the property of their respective owners.

HUAWEI TECHNOLOGIES CO., LTD.

Huawei Industrial Base

Bantian Longgang

Shenzhen 518129, P.R. China

Tel: +86-755-28780808

Version No.: M3-040174-20170511-E-3.0

www.huawei.com