FusionModule800Smart Small Data Center Solution
02 Preface
03 Huawei Solution Overview
07 Customer Benefits
14 System Parameters
15 Key Components
17 Typical Configurations
18 Global Services & Applications
Contents
01 FusionModule800Smart Small Data Center Solution
Preface
Does your small data center look like this?
• Long delivery period and different appearances due to separately purchased components and onsite installation
• Difficult O&M with disunified monitoring platforms • Low integration and large footprint • High power consumption of constant-frequency air conditioners without contained aisles • Serious condensation due to poor temperature and humidity control • Frequent fire accidents due to lack of battery overheat protection
Do you want to deploy a small data center like this?
02
FusionModule800 integrates the power distribution, UPS , monitoring, cooling, and cabinet system. The converged cabinet integrates the PDU, UPS, rack air conditioner,
and monitoring system, saving the installation space.
The IT cabinet can be flexibly extended on both sides of it. A single module supports a maximum of eight cabinets, at most 12 kW IT load, and up to 6 kW/R power density. The module has a single-row 250 mm cold aisle containment.
Layout (cold aisle)
Huawei Solution Overview
03 FusionModule800Smart Small Data Center Solution
• Small data center, branch data center, reconstructed data center, or data center with capacity expansion
• Indoor data center
• Tier I or tier II construction level
Application Scenarios01
Finance (branches and large banking outlets), government, education, healthcare, public security, transportation, energy, small-and medium-sized enterprises, retail merchandising and carriers (business hall), etc.
Applicable Industry02
04
Indicator module
PDU module
ECC800 monitoring module
Air conditioner indoor unit
UPS
Camera
10 inch screen
Glass door
Aisle
System Architecture03
Core Subsystem04UPS system
• Rack-mounted • 10kVA • 20kVA
Power distribution system
• Rack power distribution module • Indicator module • rPDU
Refrigerating system
• Variable-frequency air conditioner • Rack-mounted • Low-load dehumidification
Huawei Solution Overview
05 FusionModule800Smart Small Data Center Solution
Indicator module
PDU module
ECC800 monitoring module
Air conditioner indoor unit
UPS
Camera
10 inch screen
Glass door
Aisle
Cabinet system
• 19-inch standard cabinet • Contained aisle • Glass door • 250 mm single-row aisle
Cabling system
• Power cable tray • Signal cable tray
Lightning protection system
• Class C surge arrester for the entire system
• Class D surge arrester for the UPS
• Class D surge arrester for the air conditioner
Monitoring system
• Monitoring module • 10-inch screen display • SMS alarms • Camera • Door access control
system
• Temperature, humidity, and smoke sensors
• Door status sensor • Water leakage sensor • Intelligent battery
management
06
Quick installation and fast service launch
Fast Delivery01
Features and Values • Factory-installation and factory-commissioning of the PDU, UPS, air conditioner, monitoring system, and aisle • Pre-fabrication of cables • Pre-filling of refrigerant, free of welding for the connection between the air conditioner indoor and outdoor
units • Only four hours required for onsite installation of a smart module with three cabinets, saving the installation
cost and reducing the service online time
① The product is prefabricated, pre-installed, and pre-commissioned in the factory.
② You simply need to combine the cabinets and connect some cables and air conditioner pipes on site.
③ The installation is complete.
Customer Benefits Simple, Efficient, Reliable
07 FusionModule800Smart Small Data Center Solution
Remote web UI monitoring, mobile phone app O&M, local 10-inch screen display, and centralized management of multiple sites
Intelligent O&M02
Features and Values • The ECC800 monitoring module monitors the UPS, air conditioner, temperature and humidity sensor, water
sensor, door status sensor, and smoke sensor of the system in real time, ensuring a reliable infrastructure environment for IT equipment.
• The 10-inch local large screen LCD user-friendly interface communicates with the ECC800 over the wireless network and displays various operating parameters of the system in real time.
• SMS alarms ensure that the O&M personnel is notified of the alarm information in time. • The entire power and environment system can be accessed by logging in to the ECC800 monitoring module
over the remote web UI of a single module, implementing remote O&M.
1 Remote monitoring of a single module
ECC800
Water sensor
Smoke detector
Mobile phone
Cabinet door status sensor
Temperature sensor
Independent deployment AI/DI unit
AI/DI
AI/DI
UPS2000-G
RS485FE
VCN500 Camera
BIM
CIM
WiFi
NetCol5000-A011 air conditioner
Access actuator
RF_Z
RF_Z
NetCol5000-A011 air conditioner
SPD
Smart ETH gateway
Smart ETH gateway
…
Internet
PAD
08
2 Centralized monitoring and unified management of multiple modules
DC
DC
DC
DC
DC
Centralized management
Large screen display
DC
Mobile app
Customer Benefits Simple, Efficient, Reliable
Features and Values • If there are multiple sites, the Huawei NetEco intelligent NMS can be used to implement centralized monitoring and
unified management of multiple modules. • The unique GIS map mode highlights the faulty sites, enabling quick location of the alarm site by using the GIS map. • Support for integration by a third-party NMS (including but not limited to eSight) allows unified network
management with the IT/IP equipment. • Mobile phone app O&M makes it possible to monitor the power and environment system of the equipment room
in real time any time and anywhere, implementing unattended operation. • The equipment room view management, alarm management, permission and security management, report
management, capacity management, and asset management functions are available.
09 FusionModule800Smart Small Data Center Solution
Features and Values • The all-in-one design integrates the UPS, PDU, monitoring system, and air conditioner in one cabinet. • Compared with the in-row air conditioner or traditional refrigerating solution, the air conditioner
redundancy solution saves the installation space of at least two cabinets.
High integration, saving the installation space
Smaller required floor space01
UPS
ECC800
Air conditioner indoor unit
Power distribution module
Indicator module
Converged cabinet
Only 4.05 m2 for the smart module 3IT cabinets At least 10 m2 for 3IT cabinets of the traditional small data center
VS
Customer Benefits Simple, Efficient, Reliable
10
Features and Values • The all-in-one cabinet with the contained aisle effectively separates the hot and cold airflow.
• The use of the advanced CFD head simulation design optimizes the air transmission performance and prevents hotspots in the aisle, creating a highly efficient energy conservation effect.
• Combined with the PUE (Beijing) as low as 1.37, the contained aisle and DC inverter compressor air conditioner save the energy by more than 40% compared with the traditional solution.
Contained aisle and DC inverter compressor, featuring high energy efficiency
High energy efficiency02
① CFD simulation of the traditional small data center without the contained aisle – mixed cold and hot airflow and low cooling efficiency
② CFD simulation of the smart module with the contained aisle – isolated hot and cold airflow and maximized cooling efficiency
Remarks: $8,338 electricity expense is saved every year compared with the traditional solution (10 kW IT load, 2.1 PUE)
Customer Benefits Simple, Efficient, Reliable
11 FusionModule800Smart Small Data Center Solution
Features and Values
• Intelligent (low-load) dehumidificationThe air conditioner can switch between low-load dehumidification, dehumidification, and cooling automatically based on the humidity and temperature of the equipment room.
• Expanded cooling operation scopeThe cooling system runs with the minimum of 10% IT load, which is the lowest in the industry.
• Reduced costThe high-humidity issue of the traditional equipment room is resolved by adding dehumidifiers in the micro-module. The costs are high and the O&M is complex.
• Energy conservationThe Huawei patent technology does not require additional heat compensation by enabling electric auxiliary heat during the low-load dehumidification process.
Low-load dehumidification, intelligent dehumidification
Condensation-free design01
Customer Benefits Simple, Efficient, Reliable
12
Battery SOC/SOH, intelligent shutdown upon overheat
Wireless battery monitoring02
iBAT iBOX
wifi
ECC800 monitoring module
Battery overheatBattery overvoltage
Increase of internal resistance
Customer Benefits Simple, Highly Efficient, Reliable
Features and Values
• Active O&M management without human inspection • Online real-time monitoring of core parameters such as the battery temperature by the UPS. When
overtemperature occurs, the UPS automatically shut down the battery string to eliminate fire risks. • Real-time detection of the voltage, temperature, current, and internal resistance of a single battery and
full monitoring of core parameters without periodic measurement of battery parameters • Automatic test of battery performance, battery SOC and SOH monitoring by using the proprietary
algorithm, and early-warning of battery failure
• Wireless transmission and simple deployment • Wireless communication between iBat and iBox and flexible networking without complex cabling,
reducing the deployment time by 50% • Powerful networking functions. One iBox can connect to 300 iBats, saving the investment.
13 FusionModule800Smart Small Data Center Solution
System Parameters
Overall Solution
Maximum IT power consumption 6 kW a 12 kW
Maximum number of cabinets in a singlesmart module
6 8
IT cabinet quantity 0-4 (including 0-1 network cabinet) 0-6 (0-1 network cabinet)
Contained aisle Cold aisle
Maximum power density of a singlecabinet
6 kW
Battery deployment mode Battery pack/Battery cabinet/Battery rack
Power backup time 15 min/30 min
Installation mode Concrete floor or raised floor
Power system 380/400/415 V AC, 50/60 Hz, 3Ph+N+PE
System protection level IP20
Operating temperature -10℃ to +55℃
Cooling System
Power supply type Mains supplies power
Air conditioner configuration 1+0, 1+1, 2+0, 2+1
Power Supply and Distribution System
Power input Single input
Power input switch capacity 63 A
UPS capacity 10 kVA 20 kVA
UPS configuration N, N+1 (N = 1)
AC SPD In 20 kA, Imax 40 kA, 8/20 μs
Maintenance bypass Standard configuration
Monitoring system
Monitoring systemMobile phone APP, SMS alarm, Web access, centralized management for multiple DCs
10 inched Pad Standard
Water sensor Optional
Smoke sensor Standard
Door status sensor Optional
Door access control system Optional (2 most)
Temperature and humidity sensor Standard
Local mobile app Standard (ECC APP)
Remote mobile app Optional (NetEco APP)
SMS alarm Standard
Camera (4 most)Optional, camera of module (1 most)
Optional, room camera (4 most)
Remarks:
a. The recommended IT load for smart module is 3 kW–12 kW. If the IT power is less than 3 kW, FusionModule500 is recommended.
14
Key Components
1 Rack UPS
2 Power Distribution Module
Type Parameter 10 kVA 20 kVA
Input parameter
Rated input voltage 380/400/415 V AC, 50/60 Hz, 3Ph+N+PE
Input voltage range 138–485 V AC, 50/60 Hz, 3Ph+N+PE
Input frequency range 40–70 Hz
Output parameter
Rated voltage220/230/240 V AC, 50/60 Hz,1Ph+N+PE
380/400/415 V AC, 50/60 Hz, 3Ph+N+PE
Power factor 0.9
Maximum efficiency 94.50% 95%
Overload capability105% ≤ Load < 125%, bypass in 5 min;125% ≤ Load < 150%, bypass in 1 min;Load ≥ 150%, bypass in 0.1s
Structural parameters
Installation mode Rack-mounted
Surge protectionThe AC input end meets requirements of class D surgeprotection (differential/common mode 5 kA, 8/20 μs)
Environment parameter
Communication Dry contact/USB/Modbus/SNMP
Operating temperature 0–40℃
Relative humidity 0%–95% RH, no condensation
Maximum altitude < 1000 m (derating for 1000–4000 m)
Storage and transportation temperature
–40℃ to +70℃
Operating temperature 0–40℃
Height 2 U 3 U
Noise < 55 dB < 58 dB
Certification CE, CB, RoHS, TLC, CQC, REACH, WEEE
Honor One of the first Energy Start certified products in the industry, ECA
10kVA
20kVA
Indicator module
Height: 1 U
Power distribution module
Height: 6 U
Output loop: 14
Main switch: 63 A
Corresponding UPS: 10 kVA
Typical configuration: BC12
Power distribution module
Height: 6 U
Output loop: 14
Main switch: 63 A
Corresponding UPS: 20 kVA
Typical configuration: BC13/14
Power distribution module
Height: 3 U
Output loop: 4
Main switch: 63 A
Corresponding UPS: 10 kVA
Typical configuration: BC11
15 FusionModule800Smart Small Data Center Solution
3 Rack-mounted Air Conditioner
Parameter SpecificationsOperating temperature of theoutdoor unit
–10℃ to +55℃
Height difference between indoor and outdoor units
20 m at most when the outdoor unit is installed higher than theindoor unit
5 m at most when the indoor unit is installed higher than theoutdoor unit
Maximum equivalent length of one-way pipe
≤ 60 m
Water drainage4 m at most for the distance between the up drainage on thewater pump and the floor on which the cabinet is installed
Pipe and cable routing Top or bottom routing
Certification REACH, RoHS, CE, SASO
Item Indoor Unit (Cooling System)Power system 220/230/240 V AC, 50/60 Hz, 1Ph+N+PE
Maximum current 17.3 A
Cooling mode Air-cooled (horizontal air flow)
Refrigerant R410A
Cooling capacity 11 kW b
Fan type EC fan
Maximum airflow 2600 m3/h
Condensate pump Yes
Dimensions (W×D×H) 442 mm x 800 mm x 468 mm
Net weight / Gross weight 60 kg / 79 kg
Protection level IP20
Installation mode Rack-mounted
Item Outdoor UnitMaximum operating current 30 A
Fan quantity 2
Dimensions (W×D×H) 1327mm×966mm×320mm
Net weight / Gross weight 101kg / 114kg
Protection level IPX4
Front of the air conditioner indoor unit
4 ECC800 Collector Parameter Specifications
FE port WAN_1–2, LAN_1–2
DO output dry contact DO_1–2
AI/DI port AI/DI_1–6/12 V
RS485 port COM1–4/12 V
USB port Wi-Fi module access port
3G/4G antenna port SMS alarm antenna access port
Software Embedded software for web UI monitoring
Rear of the air conditioner indoor unit
Front of the air conditioner outdoor unit
b. The 11kW cooling capacity of the air conditioner is obtained when the indoor dry bulb temperature is 37.8℃, and the outdoor dry bulb temperature is 35℃.
Rated cooling capacity in the nameplate. T1/T3:8kW/7.2kW (T1: indoor dry bulb temperature 27 ℃, outdoor dry bulb temperature 35 ℃; T3: indoor dry bulb temperature 29℃, outdoor dry bulb temperature 46 ℃ )
16
Typical Configurations
Total IT load ≤ 6kW 6kW<IT ≤ 12kW
Typical configuration BC11C BC12 BC13C BC14d
Aisle containment Cold
UPS (kVA) 10 10+10 20+20 20+20
Air conditioner (Heating and humidifying)
1+0 1+1 2+0 2+1
Input power Single
rPDU 1 2 2 2
UPS outputs 4 14 14 14
Remarks:
c: BC11 and BC13 are only applicable to Tier 1 construction level for enterprises;
d: BC14 includes two cabinets, two heating and humidifying air conditioners are in the converged cabinet. One cooling only air conditioner is in the other cabinets.
BC11
BC13
BC12
BC14
IT load ≤ 6kW
6kW<IT load ≤ 12kW
17 FusionModule800Smart Small Data Center Solution
Global Services & Applications
Huawei has full-time data center infrastructure service engineers in regions around the globe to provide globalized professional services and fast response. Huawei offers customized services based on the demand of the customer. Currently Huawei provides the following services:
Global Services01
The smart module has been deployed in over 30 countries around
the world with more than 500 deployed modules.
Typical Customers02
• 140+ national delivery management organizations
• 129+ national spare part centers
• 300+ regional warehouses
• 22,000+ service personnel
• 24 x 7 service
24 x 7 remote support service
NM commissioning
service
Active prevention service
(preventive inspection)
Hardware support service
(installation)
Onsite support service
(supervision)
Customer support service (maintenance)
Finance • Ireland Branch of Bank of China • Italy Branch of Bank of
Communications • Orient Finance Holdings (Hong Kong) • Bank of Guiyang
Public Security • Tiantan Police Station • Turkish National Police
Education • Spanish University
Healthcare • Suzhou Institute of Cardiovascular
Health
Government • Xuchang government cloud • Huizhou municipal office, SAT • South Africa COT
18
Copyright © Huawei Technologies Co., Ltd. 2017. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd.
General Disclaimer
The information in this document may contain predictive statements including,
without limitation, statements regarding the future financial and operating results,
future product portfolio, new technology, etc. There are a number of factors
that could cause actual results and developments to differ materially from those
expressed or implied in the predictive statements. Therefore, such information
is provided for reference purpose only and constitutes neither an offer nor an
acceptance. Huawei may change the information at any time without notice.
Trademark Notice
, HUAWEI, and are trademarks or registered trademarks of Huawei Technologies Co., Ltd.
Other trademarks, product, service and company names mentioned are the property of their respective owners.
HUAWEI TECHNOLOGIES CO., LTD.
Huawei Industrial Base
Bantian Longgang
Shenzhen 518129, P.R. China
Tel: +86-755-28780808
Version No.: M3-040174-20170511-E-3.0
www.huawei.com