Upload
usama-ahmed
View
215
Download
1
Embed Size (px)
DESCRIPTION
Harmonics caused by furnaces of induction and arc type
Citation preview
EE 545 Power System Quality Usama Ahmed 2015-MS-EE-16
Page 1 of 8
ARC FURNACES
Input voltage and current waveform to an arc furnace during the melting phase of the technological cycle
of arc furnace:
The associated harmonic spectrum and the total harmonic distortion (THD):
In the phase of the electric arc stable burning that appears towards the final of the heats making, is found
that the distortion that appear in the currents and voltages wave forms (figure(a) voltage and figure(b)
current) are more reduced. In this phase, the amplitude of the three phase currents and voltages are closer
as value, fact which shows that the load impedance is more balanced:
EE 545 Power System Quality Usama Ahmed 2015-MS-EE-16
Page 2 of 8
The associated harmonic spectrum and the total harmonic distortion (THD):
INDUCTION FURNACES
The results obtained in the harmonic distortion analysis of voltage and current at the connection point of
the induction furnace are shown below. The THD value corresponding to the current is 4.47% while the
voltage THD is 1.04%. The highest harmonics are the 11th (550 Hz) and the 13th (650 Hz) and they are repeated
at the 23rd (1150 Hz) and the 25th (1250 Hz).
EE 545 Power System Quality Usama Ahmed 2015-MS-EE-16
Page 3 of 8
Voltage Harmonics and
THD
Current Harmonics and
THD
EE 545 Power System Quality Usama Ahmed 2015-MS-EE-16
Page 4 of 8
APPLICATION OF POWER FACTOR CORRECTION CAPACITORS
The figures below show the time domain voltage and currents wave forms and the frequency domain
harmonic spectrums without the application of capacitors:
Without adding capacitor banks for power factor correction, there would be no harmonic resonance
problems associated with the furnace operation. The addition of capacitors may cause system
capacitor resonance, this is illustrated in the figure below:
EE 545 Power System Quality Usama Ahmed 2015-MS-EE-16
Page 5 of 8
Thus there is the possibility of severe harmonic distortion in case of applying capacitor banks alone
without series tuned rector. Therefore using capacitors banks in harmonics environment should be
accomplished with through analysis prior to installation.
APPLICATION OF A SERIES INDUCTOR
The effect of introducing a series inductor to load current in comparison to no compensation is as follows:
EE 545 Power System Quality Usama Ahmed 2015-MS-EE-16
Page 6 of 8
Amplitudes of some of the noticeable harmonic components are as follows:
THE EFFECT OF HARMONICS ON TRANSFORMER
The effects of harmonics on transformers are quite self-evident, the harmonics will not only cause extra
loading on the transformer but will also result in the reduction of its overall useful life.
Application of non-sinusoidal excitation voltages to transformers increases the iron losses in the magnetic
core of the transformer in much the same way as in a motor. A more serious effect of harmonic loads
served by transformers is due to an increase in winding eddy current losses. Eddy currents are circulating
currents in the conductors induced by the sweeping action of the leakage magnetic field on the
conductors. Eddy current concentrations are higher at the ends of the transformer windings due to the
crowding effect of the leakage magnetic fields at the coil extremities. The eddy current losses increase as
the square of the current in the conductor and the square of its frequency. The increase in transformer
eddy current loss due to harmonics has a significant effect on the operating temperature of the
transformer. Transformers that are required to supply power to nonlinear loads must be derated based on
the percentages of harmonic components in the load current and the rated winding eddy current loss.
One method of determining the capability of transformers to handle harmonic loads is by k factor ratings.
The k factor is equal to the sum of the square of the harmonic currents multiplied by the square of the
frequencies.
EE 545 Power System Quality Usama Ahmed 2015-MS-EE-16
Page 7 of 8
The figures below illustrate the predicted top oil and hot spot temperatures, respectively at different
harmonic cases. In the first case study, no harmonics are assumed to be present. The harmonics assumed
for the second case include major harmonics 5th, 7th, 11th, 13th, 17th, 19th, 23th and 25th with total
harmonic distortion (THD) 10%. The third case is with THD 22% and the same order harmonics. The
increase in top oil temperature for the second and third case is 2C and 8C, respectively compared with
no harmonics. The hot spot temperature of the HV winding shows an increase of more than 20C for the
third case.
Although the hot spot temperature has increased the loss of life factor above 1 .1 pu, it returns to normal
loss of life at the end of the load cycle as shown in the last figure.
EE 545 Power System Quality Usama Ahmed 2015-MS-EE-16
Page 8 of 8
REFRENCES
[1] Power Quality Impacts of an Electric Arc Furnace and Its Compensation Journal of Electrical
Engineering & Technology, Vol. 1, No. 2, pp. 153~160, 2006
[2] Investigation and Mitigation of Harmonics from Electric Arc Furnaces Proceedings of the 1999 IEEE
Canadian Conference on Electrical and Computer Engineering Shaw Conference Center, Edmonton,
Alberta, Canada May 9-12 1999
[3] Harmonic distortion in a steel plant with induction furnaces I. Zamora1, I. Albizu2, A. J. Mazon, K. J.
Sagastabeitia, E. Fernandez Department of Electrical Engineering University of the Basque Country
Alda. Urquijo s/n, 48013 Bilbao (Spain)
[4] Horia Andrei, Costin Cepisca and Sorin Grigorescu (2011). Power Quality and Electrical Arc
Furnaces, Power Quality, Mr Andreas Eberhard (Ed.)
[5] The Effect of Harmonic Distortion on a Three phase Transformer Losses Canadian Journal on
Electrical and Electronics Engineering Vol. 3, No. 5, May 2012
[6] Effect of Harmonics on Transformers Loss of life Conference Record of the 2006 IEEE International
Symposium on Electrical Insulation
[7] IEEE Std. 519-1992, IEEE Recommended Practices and Requirements for Harmonic Control in
Electrical Power Systems, April 1993.