    Technical data (at 73F(23 C )and 50% relative humidity)Chemical basis Water-based intumescent

    acrylic dispersionDensity: Approx. 1.5 g/cm3

    Colour: RedWorking time: Approx. 20-30 minCuring time: Approx. 2mm / 3 daysShore A Hardness: Approx. 35Movement capability: Max. 10%

    Intumescent Activation: Approx. 482F (250C)Expansion rate (unrestricted): Approx. 4 times original volumeTemperature resistance (cured): 40F to 212F (40C to 100C)

    Application temperature: 41F to 104F (5C to 40CSurface burning characteristics Flame Spread: 0(ASTM E 84-96): Smoke Development: 5Sound transmission classification (ASTM E 90-99): 56Shelf life at 25C(77F) and store at dry place: 9 months

    Approvals:ICBO (International Conference of Building Officials) Report No. 5071California State Fire Marshal: Listing No. 4485-1200:108City of New York: MEA 326-96-MTested in accordance with: UL 1497

    ASTM E 814 ASTM E 84

    Packaging contents Ordering designation Colour Item no.

    Intumescent firestop mastic 5gallon(19 liter) FS-ONE, pail Red 259578

    Internationally tested and approved

    FS ONEHigh Performance Intumescent firestop sealant

    Product descriptionIntumescent (expands when exposed to fire) firestop sealant thathelps protect combustible and non-combustible penetrations forup to 4 hours fire rating.

    Product features

    Smoke, gas and water resistant after material has cured.Contains no halogen, solvents or asbestos.High fire rating properties.Water based, easy to clean.

    Areas of application*Insulated and non-insulated steel, cast iron, steel conduit, copperand EMT pipes.Cable trays and cable bundles. (various cables)Closed or vented plastic p ipes. (PVC, CPVC, ABS)HVAC penetrations. (Insulated and non-insulated metal dusts)Electrical busways.

    For use with*Concrete, masonry, gypsum, drywall and wood floor assemblies.Wall and floor assemblies rated up to 4 hours.

    Example*Sealing around cable bundles in fire rated construction.

    Sealing around combustible and non-combustible penetrationsin fire rated construction.

    FS-ONEHigh Performance intumescent firestop sealant

    System advantages / Customer Benefits

    Protects most typical firestop penetration applicationsEasy to work with and fast clean upCan be painted

    Age tested for 30 yearsSingle component system availableMeet LEED requirements for indoor environmental quality credit 4.1 LowEmiting Materials, Sealants and Adhesive and 4.2 Paints and Coatings

    OpeningClean the opening. Surfaces to which FS-ONE will beapplied should be cleaned of loose debris, dirt, oil ,moisture, frost and wax. Structures supporting penetratingitems must be installed in compliance with local buildingand electrical standards.

    Application of firestop sealantInstall the prescribed backfilling material type and depthto obtain the desired rating (if required). Leave sufficientdepth for applying FS-ONE.

    Appli cat ion of fir est op seala nt: Apply FS- ONE to therequired depth in order to obtain the desired fire rating.Make sure FS-ONE contact all surfaces to providemaximum adhesion. For application of FS-ONE use astandard caulking gun, foil pack gun, bulk loader and bulk gun. With FS-ONE buckets, Graco type sealant pumps may

    be use. (Contact pump manufacturer for proper selection).

    Smoothing of firestop sealant: To complete the seal, toolimmediately to give a smooth appearance. Excess sealant,prior to curing, can be cleaned away from adjacentsurfaces and tools with water.

    Leave completed seal undisturbed for 48 hours.

    For maintenance reasons, a penetration seal could bepermanently marked with an identification plate. In such acase, mark the identification plate fasten it in a visibleposition next to the seal.

    Notice about approvalsCheck that the penetration has been sealed according tothe specified drawing in the UL Fire Resistance Directoryor Hilti Firestop Manual. For further advice, please contactHilti customer service. Refer to Hilti product literature andUL fire resistance directory for specific application details.

    Not for use...High movement expansion jointsUnderwaterOn materials where oil, Plasticizers or solvents may bleedi.e. impregnated wood, oil based seals, green or partiallyvulcanized rubberIn any penetration other than those specifically describedin this manual or the text reports

    Safety precautionsBefore handling, read the product and Material Safety

    Data Sheet for detailed use and health informationKeep out of reach of childrenWear suitable gloves and eye protection

    StorageStore only in the original packaging in a location protectedfrom moisture at temperatures between 41F (5C) and86F (30C)Observe expiration date on the packaging

    Installation instructions for FS-ONE