29
FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR

FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR

Embed Size (px)

Citation preview

Page 1: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR

FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR

Page 2: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR
Page 3: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR
Page 4: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR
Page 5: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR

James Watt’s steam governor

Page 6: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR

Watt’s fly ball governor

Page 7: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR

Watt’s fly ball governor

This photograph shows a flyball governor used on a steam engine in a cotton factory near Manchesterin the United Kingdom.

Of course, Manchester was at the centre of the industrial revolution. Actually, this cotton factory is still running today.

Page 8: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR

Watt’s fly ball governor

This flyball governor is in the same cotton factory in Manchester.However, this particular governor was used to regulate the speed of a water wheel driven by the flow of the river. The governor is quite large as can be gauged by the outlineof the door frame behind the governor.

Page 9: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR

SteamEngine

ActualSpeed

DesiredSpeed

SteamSupply

Fly-BallGovernor

Deviation

MachineOperator

MachineUse

Negative(Balancing)Feedback

Sensor Actuator

Controller

Feedback Loop

Steam Engine Speed Control

Page 10: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR
Page 11: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR
Page 12: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR
Page 13: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR
Page 14: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR
Page 15: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR
Page 16: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR
Page 17: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR
Page 18: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR
Page 19: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR
Page 20: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR
Page 21: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR
Page 22: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR
Page 23: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR

• Governors. To provide an equitable and

coordinated system response to load/generation imbalances, governor droop shall be set at 5%.

• Governors shall not be operated with excessive deadbands, and governors shall not be blocked unless required by regulator mandates

Page 24: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR

• Assume that all generators on a power grid are operating in the droop mode with the same 4 percent speed regulation.

• Assume also that one of the generators is rated at 50 megawatts (call it Unit #1) and is synchronized on a grid whose total generating capacity is 8000 megawatts.

• The speed governor for Unit #1 will take 50 ÷ 8000 or .625% of any load demand changes that should occur.

• For example, assume that Unit #1 is currently generating 37 MW.

• If the grid is operating at 60.00 Hz and an increase in demand of 5 MW occurs, Unit #1 will increase its power output by: (.00625)(5) = .03125 MW. Unit #1 will then be generating 37.03125 MW.

Page 25: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR

• The other generators, with their own 4 % droop characteristic, will share proportionally the remainder of the load change (that is, 5 MW minus.03125 = 4.96875).

• In the above example, something happens to grid frequency as well.

• Assume that the frequency is 60.00 Hz when the additional load of 5 MW came on the grid.

• In this example, the system frequency would droop the following amount:

60.00 - [(.04) (60) (5) ÷ 8000] = 60.00 - .0015 = 59.9985 Hz If the operator increases the setpoint on Unit #1 as the other governor setpoints remain steady, the frequency will return to 60.00 Hz and all of the new load of 5 MW will be transferred to Unit #1.

Page 26: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR

Droop Setting Determines Response

• 5% Droop: 100% change in generator output for a 5% change in Frequency or Speed.– A 5% change in frequency, 60 Hz x 0.05 = 3 Hz or

for a 2 pole generator, 3600 rpm x 0.05 = 180 rpm.• 4% Droop: 100% change in generator output for a 4%

change in Frequency or Speed.– A 4% change in frequency, 60 Hz x 0.04 = 2.4 Hz or

for a 2 pole generator, 3600 rpm x 0.04 = 144 rpm.• 4% Droop setting is more sensitive (responsive) than

the 5% Droop setting.

Page 27: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR

Example of Expected Response

• 150 MW unit at 5% Droop– 150 / 3 Hz = 50.00 MW/Hz or in tenths of Hz, 5.00

MW/0.1 Hz– Frequency change from 60.05 to 59.95 should

result in the generator increasing output 5.0 MW’s• 150 MW unit at 4% Droop

– 150 / 2.4 Hz = 62.50 MW/Hz or in tenths of Hz, 6.25 MW/0.1 Hz

– Frequency change from 60.05 to 59.95 should result in the generator increasing output 6.25 MW’s

Page 28: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR

Expected Governor Response

• 5 % Droop:– Unit Net Capability/30 = MW/0.10 Hz

• 4 % Droop:– Unit Net Capability/24 = MW/0.10 Hz

Page 29: FREQUENCY-POWER CHARACTERISTICS OF SYNCHRONOUS GENERATOR

Droop Mode Versus Isochronous Mode • Droop Mode: It is the mode of operation in which the

machine will react to the load variation by changing its speed. It is utilized when multiple machine run in parallel so that load is shared between the machines. For this sharing to be equal the machine need to have same droop characteristic. Typically if a machine has droop of 4% it means for a change of 1% in rated speed the machine takes 25% of its rated load. This is also referred to as load control mode of operation.

• Isochronous Mode: In this mode the machine is not affected by  load and regardless of load it will maintain the frequency. This mode is also referred to as frequency control mode of operation. In case of systems not connected to grid it is required to run at least one machine in this mode so as to take care of the load variation.