51
Page 1 of 51 Document# 9001-0011 TROTTER CONTROLS, INC. Revision C, 6/1/2009 FORT WORTH, TX FRDS GENII Maintenance and Troubleshooting Manual __________________________________________________________________ Trotter Controls, Inc. Document# 9001-0011 Revision C, 6/1/2009 ____________________________________________________________________________________________________

FRDS GENII Maintenance and Troubleshooting Manual · 2015. 5. 23. · FRDS GENII FEATURES ... lets the pilot select the volume of agent released during a dump. This enables “split

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

  • Page 1 of 51 Document# 9001-0011 TROTTER CONTROLS, INC.

    Revision C, 6/1/2009 FORT WORTH, TX

    FRDS GENII Maintenance and Troubleshooting Manual __________________________________________________________________

    Trotter Controls, Inc. Document# 9001-0011

    Revision C, 6/1/2009

    ____________________________________________________________________________________________________

  • TROTTER CONTROLS, INC. Document# 9001-0011 Page 2 of 51

    FORT WORTH, TX Revision C, 6/1/2009

    Table of Contents REVISIONS ...............................................................................................................................................................................5

    OVERVIEW...............................................................................................................................................................................6

    INTRODUCTION ........................................................................................................................................................................6 FRDS GENII FEATURES..........................................................................................................................................................6

    Accurate and dependable coverage delivery......................................................................................................................6 Highly reliable specific purpose control system – Reliability FIRST.................................................................................7 Redundant Systems to Insure Door Opening......................................................................................................................7 Hydraulic system refinements ............................................................................................................................................7 Benefits...............................................................................................................................................................................8

    CONSTANT FLOW RATE VERSUS CONSTANT GATE ANGLE .....................................................................................................8 Constant Gate Angle Delivery Systems ..............................................................................................................................8 Constant Flow Rate Delivery Systems................................................................................................................................9

    SYSTEM DESCRIPTION ...........................................................................................................................................................10 MODES OF OPERATION ..........................................................................................................................................................12

    PILOT INTERFACE DETAILS ............................................................................................................................................13

    FOAM GALLONS DISPLAY ................................................................................................................................................14

    AUTO MODE OPERATION .................................................................................................................................................14

    SWITCH FUNCTIONS IN AUTO/TIMER MODE ......................................................................................................................14 DUAL ARMED LIGHT FUNCTIONALITY (AUTO/TIMER MODES) ..........................................................................................15

    TIMER MODE OPERATION ...............................................................................................................................................18

    SPECIAL USES OF PANEL SWITCHES (AUTO/TIMER MODES)...............................................................................20

    LAMP TEST switch ..........................................................................................................................................................20 NO switch .........................................................................................................................................................................20 RUN PUMP switch ..........................................................................................................................................................20

    SPECIAL MODES OF OPERATION (AUTO/TIMER) .....................................................................................................20

    FUEL FERRY MODE................................................................................................................................................................20 PILOT INTERFACE “MIRROR” MODE.......................................................................................................................................21

    Enabling/Disabling Mirror Mode ....................................................................................................................................21 Activating Mirror Mode ...................................................................................................................................................22 De-activating Mirror Mode..............................................................................................................................................22

    BRIGHTNESS ADJUST MODE ...................................................................................................................................................22 FOAM INJECTION ...................................................................................................................................................................22

    MANUAL MODE OPERATION...........................................................................................................................................23

    SALVO SYSTEM ACTIVATION .........................................................................................................................................23

    AUTOMATIC SALVO ACTIVATION ..........................................................................................................................................24 PILOT ACTIVATED SALVO......................................................................................................................................................24 AUTO SUPERVISOR ACTIVATED SALVO .................................................................................................................................24 MAN SYSTEM ACTIVATED SALVO ........................................................................................................................................25 RECOVERY FROM AN AUTOMATIC SALVO CONDITION ..........................................................................................................25

    SYSTEM TESTS .....................................................................................................................................................................26

    SYSTEM SELF DIAGNOSTIC TESTS – SYSTEST MENU .............................................................................................26

    PILOT (NO DOORS) – SYSTEM TEST ........................................................................................................................................27 PILOT (ALL) – SYSTEM TEST ................................................................................................................................................27 AUTO SALVO – SYSTEM TEST................................................................................................................................................28 MAN SALVO – SYSTEM TEST .................................................................................................................................................28

  • Page 3 of 51 Document# 9001-0011 TROTTER CONTROLS, INC.

    Revision C, 6/1/2009 FORT WORTH, TX

    MAINT SYSTEST – MAINTENANCE PERSONNEL – SYSTEM TEST............................................................................................28 SYSTEM TEST PERSISTENT ERRORS .......................................................................................................................................29

    Clearing Persistent SysTest Errors ..................................................................................................................................29 MENU SYSTEM.......................................................................................................................................................................30

    Main Menu...................................................................................................................................................................................... 30 Maint Menu .................................................................................................................................................................................... 30 Config Menu................................................................................................................................................................................... 31 SysTest Menu ................................................................................................................................................................................. 31 Error History................................................................................................................................................................................... 31 Digital Inputs .................................................................................................................................................................................. 32 Digital Input Map............................................................................................................................................................................ 32 Digital Outputs................................................................................................................................................................................ 33 Digital Output Map......................................................................................................................................................................... 33 Analog Inputs.................................................................................................................................................................................. 34 Analog Calibrate ............................................................................................................................................................................. 34 Err Msg Index/Counts..................................................................................................................................................................... 34 Clear Errors..................................................................................................................................................................................... 35 Clear Err Counts ............................................................................................................................................................................. 35 Clear ErrHistory.............................................................................................................................................................................. 35 System Reset................................................................................................................................................................................... 35 Save Memory.................................................................................................................................................................................. 35 Read EEprom.................................................................................................................................................................................. 36 Compare RAM/EE.......................................................................................................................................................................... 36 Logo/Version .................................................................................................................................................................................. 37 Leakage Table................................................................................................................................................................................. 38 System Operation Parameters (Tweak)........................................................................................................................................... 38

    ERROR OVERVIEW .................................................................................................................................................................40 Reduced Accuracy .......................................................................................................................................................................... 41

    Error Code Displayed: 112_Accuracy Loss.............................................................................................................................. 41 Reduced Redundancy (AUTO/TIMER mode only)........................................................................................................................ 42

    Error Code Displayed: 114_Redundancy Loss .......................................................................................................................... 42 Reduced Accuracy & Redundancy (AUTO/TIMER mode only).................................................................................................... 42

    Error Code Displayed: 113_Accur+Redun Loss....................................................................................................................... 42 Clearing Pump Errors ..................................................................................................................................................................... 42

    SETTING SYSTEM PREFERENCES ..................................................................................................................................43

    MAINTENANCE.....................................................................................................................................................................43

    FUSE, RELAY, & STATUS LED LOCATION AND FUNCTION ....................................................................................................43 PREVENTATIVE MAINTENANCE SCHEDULE ...........................................................................................................................48 CALIBRATION & SETUP .........................................................................................................................................................48 MANAGING MEMORY ............................................................................................................................................................49 UPDATING SYSTEM FIRMWARE .............................................................................................................................................49

    REFERENCE DOCUMENTS................................................................................................................................................50

    MANUALS ..............................................................................................................................................................................50 9001-0012 – FRDS GENII Operators Manual, Trotter Controls, Inc. .......................................................................................50

    TECHNICAL PUBLICATIONS & TEST SPECIFICATIONS ............................................................................................................50 TP-1000 – Constant Flow Rate Vs. Constant Gate Angle, Trotter Controls, Inc. ........................................................................50 TP-1002 – FRDS GENII System Description, Trotter Controls, Inc. .........................................................................................50 TS-0005 FRDS GENII Maintenance System Tests, Trotter Controls, Inc. ..................................................................................50

    ENGINEERING REPORTS .........................................................................................................................................................50 ER-0074 GENII FRDS System Operation Parameters, Trotter Controls, Inc. ............................................................................50 ER-0075 FRDS GENII System Error Codes and Resolution, Trotter Controls, Inc. ....................................................................50 ER-0077 Preventative Maintenance Schedule, Trotter Controls, Inc. ........................................................................................50

    PROCESS SPECIFICATIONS......................................................................................................................................................50 PS-0030 – FRDS GENII – Pressure Relief Valve Adjustment, Trotter Controls, Inc....................................................................50 PS-0031 Hopper Contents and Gatebox Sensor adjustment, Trotter Controls, Inc. .....................................................................50 PS-0032 Calibration Dumping Matrix, Trotter Controls, Inc. ..................................................................................................50

  • TROTTER CONTROLS, INC. Document# 9001-0011 Page 4 of 51

    FORT WORTH, TX Revision C, 6/1/2009

    PS-0033 – Hydraulic Flushing Procedure, Trotter Controls, Inc. .............................................................................................50 PS-0035 – FRDS GENII – Memory Management, Trotter Controls, Inc. ...................................................................................50

    PRODUCT DATASHEETS .........................................................................................................................................................50 DS-0001 Datasheet – Pilot Interface FRDS GENII, Trotter Controls, Inc. ................................................................................50 DS-0002 Datasheet – Relay Enclosure FRDS GENII, Trotter Controls, Inc. ..............................................................................50 DS-0003 Datasheet – Side Loader Gage FRDS GENII, Trotter Controls, Inc. ...........................................................................50

    DRAWINGS.............................................................................................................................................................................50 51625 SH.12 & 13 – Instrument Installation – Upper Panel (802F), Snow Engineering Co.........................................................50 52650 SH.1 – Instrument Installation – Upper Panel (1002F), Snow Engineering Co. ................................................................50 60513 - Assy – Gatebox Electrical, Snow Engineering Co. .............................................................................................................51 60441 SH.10 – Control System Wiring Schematic (802F), Snow Engineering Co. ......................................................................51 60441 SH.21 – Control System Wiring Schematic (1002F), Snow Engineering Co. ....................................................................51 61566 SH.1 – Installation - Relay Box – FRDS (1002F), Snow Engineering Co. ........................................................................51 61566 SH.2 – Installation - Relay Box – FRDS (802F), Snow Engineering Co. ..........................................................................51 61567 SH.1 - Installation - Multibox – FRDS (1002F), Snow Engineering Co............................................................................51 61567 SH.2 - Installation - Multibox – FRDS (802F), Snow Engineering Co. ............................................................................51 61572 SH.1 – Assy - Relay Box – FRDS (802F & 1002F), Snow Engineering Co. ......................................................................51 61574 - Cable Assy. – Valve to Multibox, , Snow Engineering Co. .................................................................................................51 61587 - Pilot Interface – GEN II FRDS", Snow Engineering Co. ..............................................................................................51 80442 SH.4 – Float Installation – Hopper (802F), Snow Engineering Co..................................................................................51 80493-1 - Assy - Gatebox Actuator, Snow Engineering Co. ............................................................................................................51 80504 SH. 10 - Hydraulic Schematic (802F), Snow Engineering Co. ........................................................................................51 80504 SH. 21- Hydraulic Schematic (1002F), Snow Engineering Co. .......................................................................................51 80577 SH.13 & 14 – Hydraulic System Installation (802F), Snow Engineering Co. ....................................................................51 80577 SH.21 & 22 – Hydraulic System Installation (1002F), Snow Engineering Co. ..................................................................51 80628 SH.2 – Installation – Hopper Fill Gauge (1002F), Snow Engineering Co. .......................................................................51 80628 SH.3 – Installation – Hopper Fill Gauge (802F), Snow Engineering Co. .........................................................................51 81424, Sheet 2 - Installation-Hydraulic Manifold-802, Snow Engineering Co.....................................................................................51 81759 - Fitting Assy, Hydraulic Tank, Snow Engineering Co. .........................................................................................................51 83222 SH.1 – Hydraulic Manifold Assy Fire Gate (802F), Snow Engineering Co................................................................................51 83222 SH.21 – Hydraulic Manifold Assy Fire Gate (1002F), Snow Engineering Co. ..................................................................51 83224 - Assy, Hydraulic Pump, Snow Engineering Co...................................................................................................................51 83230 - Filter Assy, Hydraulic System, Snow Engineering Co. ........................................................................................................51 83118 - Float Installation – Hopper (1002F), Snow Engineering Co.........................................................................................51 80493 SH.4 – Assembly – Gatebox Actuator (sensor assy) (802F), Snow Engineering Co. ..........................................................51 83056 SH.2 – Installation – Gatebox Actuator (sensor assy) (1002F) , Snow Engineering Co......................................................51

  • Page 5 of 51 Document# 9001-0011 TROTTER CONTROLS, INC.

    Revision C, 6/1/2009 FORT WORTH, TX

    Revisions

    Revision C: 6/1/2009

    € Added revisions section to track changes made

    € Updated AUTO/MAN cheat sheet photos € Added additional drawings to include references included in TC document

    ER-0077 € Added section for setting power on preferences for AUTO / TIMER mode

  • TROTTER CONTROLS, INC. Document# 9001-0011 Page 6 of 51

    FORT WORTH, TX Revision C, 6/1/2009

    Overview

    This document includes maintenance, troubleshooting, and other information in addition to

    items needed for basic operation of the system.

    A list of the reference documents used to support this manual is included at the end of the

    manual and in the table of contents.

    The reader is encouraged to refer to Trotter Controls Document# 9001-0012 for condensed

    FRDS system operation instructions.

    Introduction

    The Fire Retardant Delivery System or FRDS enhances the capability of the aircraft to fight

    grass fires and forest fires by providing computer control over the release of fire retardant

    agent from the hopper. The FRDS allows the pilot to select the most effective concentration

    or coverage of agent over the ground, which varies with the type and size of fire. It also

    lets the pilot select the volume of agent released during a dump. This enables “split load”

    operations.

    A second generation FRDS or GEN II system is now available and is being installed in AT-

    802/802A aircraft. The GEN II system is an advancement of the original GEN I FRDS and

    provides improved delivery accuracy, increased component reliability, and hydraulic system

    refinements.

    FRDS GENII Features

    Based on over 15 years of field experience with the first generation FRDS system, Air

    Tractor has developed a completely new FRDS system designed from the ground up for

    reliability, performance, and maintainability.

    The focus of the FRDS GENII ground up re-design was to eliminate failures due to vibration,

    humidity, and hydraulic system failures as well as the provide state of the art built in

    diagnostic features.

    Some of the enhancements over the first generation FRDS product are described below.

    Accurate and dependable coverage delivery

    � Improved flow control and gallonage delivered accuracy

    � Improved door speed

    � New advanced leakage compensation algorithms delivers ACCURATE split load

    operation

  • Page 7 of 51 Document# 9001-0011 TROTTER CONTROLS, INC.

    Revision C, 6/1/2009 FORT WORTH, TX

    Highly reliable specific purpose control system – Reliability

    FIRST

    � Hardened against vibration and humidity

    � Dual microprocessor (µP) and electro-mechanical backup automatic salvo systems

    o Redundant Automatic Salvo system ensures door opening

    � Fully sealed digital side loader displays sealed to IP67

    � New non-contact hopper contents sensor

    � New non-contact gatebox position sensor

    � Water proof connectors with IP67 rating

    � Pilot and Maintenance Friendly

    � “Black Box” or cable change out/swap program

    � Advanced Vacuum Fluorescent Text/Graphics Display

    � Built in system status, diagnostics & messaging

    o Stuck valve detection

    o Bad switch detection

    o Broken wire detection

    o Open or missing valve coil detection

    o Bad sensor detection

    o Blown fuse detection

    o Voltage monitoring

    o Built in test / diagnostics feature

    Redundant Systems to Insure Door Opening

    � Three independent systems are provided to ensure the doors open when

    expected.

    Hydraulic system refinements

    � Hydraulic pump package – Highly

    reliable

    o Dual head 93% efficient

    hydraulic pump

    o Lower electrical current

    requirements than GENI systems

    o Heavy duty DC motor

    o Inlet filter on pump eliminates

    contaminates

    o Tested for over 10,000 flight

    hours in a 160F controlled

    environment with no failure

    � No servo valve – three low cost, dirt tolerant directional valves are used.

    � Three valves offer three levels of redundancy when opening doors

    � Independent pressure switch (electro-mechanical system) and pressure

    sensor (µP system) are used to control the pump for added mission

    reliability

  • TROTTER CONTROLS, INC. Document# 9001-0011 Page 8 of 51

    FORT WORTH, TX Revision C, 6/1/2009

    Constant Gate Angle Vs. Constant Flow Control (Coverage Level 2.0)

    0.00

    0.50

    1.00

    1.50

    2.00

    2.50

    3.00

    3.50

    4.00

    0.0 100.0 200.0 300.0 400.0 500.0 600.0

    Ground Line (feet)

    Co

    ve

    rag

    e L

    ev

    el

    (ga

    ls/1

    00

    SF

    T)

    Constant Gate Angle Constant Flow Control

    Benefits

    � System is highly reliable

    � System is highly repeatable

    � System offers three modes of operation

    � System has three levels of redundancy on door opening command

    � System is very easy to install and set up

    � System is easy to operate

    � Lower cost of ownership

    � System is self diagnosing

    � “Black Box” swap out

    � Minimal training required for troubleshooting and maintenance

    Constant Flow Rate Versus Constant Gate Angle

    The flow rate of retardant from the hoppers has been shown to be proportional to

    the coverage level seen on the ground pattern. It follows that the primary goal of

    the retardant delivery system is to maintain a constant flow rate from the hoppers

    throughout the delivery.

    Constant angle and constant flow delivery operation are briefly discussed in the

    following sections.

    Trotter Controls Document# TP-1000 (included in the reference materials) provides

    details regarding the clear advantages of constant flow (coverage) retardant delivery

    as opposed to the less accurate constant gate angle delivery method used on less

    sophisticated systems.

    Constant Gate Angle Delivery Systems

    Some retardant delivery systems open the gatebox doors to a fixed angle throughout

    the delivery then close when a preset amount of time has elapsed. These systems

    allow split load operation and a coarse method of delivering the retardant at different

    flow rates.

    Constant gate angle systems are simple to design and construct since the only

    requirement is to open the door to a

    fixed angle for a given amount of

    time. This method is inexpensive to

    engineer and produce but does not

    have the ability to accurately control

    the flow rate produced by the system

    as the level of liquid retardant and

    acceleration forces on the aircraft

    vary during the delivery process.

    Typically one timer is used to control

    how wide the doors open (a crude coverage control), and another timer is used to

    control how long the doors remain open (controls the amount of retardant

    delivered).

  • Page 9 of 51 Document# 9001-0011 TROTTER CONTROLS, INC.

    Revision C, 6/1/2009 FORT WORTH, TX

    Constant gate angle systems will produce a ground pattern that is too heavy at the

    onset of retardant delivery and is too light at the end of the delivery.

    These systems do not use retardant nearly as effectively as constant flow rate

    delivery systems.

    When the MODE switch is set to TIMER, the FRDS GENII system offers constant gate

    angle. The main advantage of this mode is that almost no sensors are using during

    TIMER mode operation thus allowing FRDS operation in the event of a hardware

    failure that prevents operation in AUTO mode.

    Constant Flow Rate Delivery Systems

    Constant flow rate delivery systems are more expensive to design and construct

    since the system must monitor various parameters during the retardant delivery and

    control the gatebox doors in a way to maintain constant flow rate.

    These systems control the position of the gatebox doors to effectively maintain

    constant flow rate during retardant delivery operations.

    Constant flow rate delivery systems will produce a superior ground pattern that is

    consistent throughout the delivery. These systems optimize the use of retardant

    during delivery operations and assure that the correct coverage level is maintained

    until just before the retardant tanks are empty.

    The FRDS GENII system operates in constant flow mode when the mode switch is in

    the AUTO position.

    Trotter Controls Document# TP-1000 shows that the constant gate angle system’s

    (CGA) retardant utilization efficiency is only 65% as efficient as the more

    sophisticated constant flow rate delivery system for a 2.0 coverage delivery. At a

    coverage level of 0.5, the constant gate angle system is only 53.6% as efficient as

    the constant flow system.

    The bottom line is that the constant flow system will deliver longer ground line for a

    given amount of retardant delivered.

    CONSTANT FLOW = MAXIMUM GROUND LINE PER GALLON OF RETARDANT

    Utilization of constant flow rate delivery systems drastically improves the ability of a

    given aircraft and pilot to suppress fires due to the constant coverage delivered and

    longer ground lines that can be produced with a given amount of available retardant.

  • TROTTER CONTROLS, INC. Document# 9001-0011 Page 10 of 51

    FORT WORTH, TX Revision C, 6/1/2009

    System Description

    The FRDS GENII system is comprised of the basic primary elements:

    � A hydraulic actuator to open and close the gatebox doors used to meter

    retardant flow rate.

    � Hydraulic valves to control the flow of oil to and from the actuator.

    � Sensors to sense various parameters needed by the control system.

    � A relay enclosure to provide high power relays and drivers needed to operate

    the hydraulic valves and provide various voltages. This enclosure also houses

    a redundant electro-mechanical system.

    � A pilot interface containing a graphic/text display, switches, accelerometers,

    and the primary microprocessor used to control the system. This is the

    primary interface for the pilot to control and interact with the system.

    The reader is encouraged to refer to Trotter Controls Document#TP-1002 for a

    detailed description of the system. The electrical schematic (Snow Engineering

    drawing 60441) and the hydraulic schematic (Snow Engineering Drawing 80504)

    provide specific details on the how the system is connected.

    The FRDS GENII operators manual (Trotter Controls Document #9001-0012)

    provides an abreviated description and operation details from the pilot’s perspective.

    An overview of the system is shown in Figure 1.

  • Page 11 of 51 Document# 9001-0011 TROTTER CONTROLS, INC.

    Revision C, 6/1/2009 FORT WORTH, TX

    Figure 1 ~ FRDS GENII system overview.

  • TROTTER CONTROLS, INC. Document# 9001-0011 Page 12 of 51

    FORT WORTH, TX Revision C, 6/1/2009

    Modes of Operation

    There are several modes of operation for the FRDS GENII system. The operation mode is

    selected using the MODE switch on the pilot interface. There is a hydraulic power switch

    (HYD PWR) and a separate mode switch with three positions (AUTO, TIMER, MAN).

    The various operation modes for the system are listed below.

    � Automatic Mode (AUTO) – In this mode, the microprocessor controlled primary

    system automatically controls the flow rate and quantity delivered using various

    sensors and valves.

    � Timer Mode (TIMER) – In this mode, two timers and minimal sensors and valves are

    used to control the doors. One timer adjusts how long the doors move towards the

    open position (adjusts door angle) and a second timer adjusts how long the doors

    remain in a fixed position before closing. The doors are maintained in fixed position

    throughout the delivery.

    � Manual Mode (MAN) – In this mode, the backup manual system (separate from the

    primary AUTO system) opens and closes the gatebox doors using simple directional

    valves. The flow rate and quantity captured are not controlled. This mode is used to

    manually operate the gatebox doors and as a backup system for the AUTO system.

    The doors are opened to full open or full closed in this mode using directional control

    valves.

    The operation mode is selected using the MODE switch on the pilot interface. The various

    modes for the system are shown below.

  • Page 13 of 51 Document# 9001-0011 TROTTER CONTROLS, INC.

    Revision C, 6/1/2009 FORT WORTH, TX

    Table 1 ~ FRDS Operation Modes during normal operation.

    Power

    Sw

    Armed

    Sw

    Mode

    Sw

    System State / Mode

    OFF X X Display Active, No pressure available to hydraulics, no pressure in

    system

    ON OFF X Display active, pressure available to hydraulics, no power available to

    valves to cause actuator motion, pressing fire switch has no effect

    ON ON AUTO Automatic control, power to hydraulics, depressing fire switch initiates

    delivery

    € Constant flow rate

    € Microprocessor Auto Salvo and Electro-mechanical Auto Salvo

    Active

    € The gatebox door position is controlled in a way to maintain

    constant retardant flow rate during delivery

    € Pump is controlled by the primary auto system and hydraulic

    pressure sensor

    ON ON TIMER Timer based control of doors, power to hydraulics, depressing fire

    switch initiates delivery

    € Microprocessor Auto Salvo and Electro-Mechanical Auto Salvo

    Active

    € Timer settings control the gatebox door position during delivery

    € Pump is controlled by the primary auto system and hydraulic

    pressure sensor

    € No sensors except pressure sensor required for operation

    € The AUTO SALVO system uses the gate open sensors

    ON ON MAN Electro-mechanical control, power to hydraulics, depressing fire switch

    initiates delivery

    € Electro-Mechanical Auto Salvo Active Only

    € Pressure Switch Controls Pump

    € Doors @ full open or full close only

    € Gatebox door position is not automatically controlled by the

    system during delivery

    € Pump is controlled by a pressure switch and relay. Pump

    operation cannot be disabled by the system in the event of an

    error in this mode.

    € The AUTO SALVO systems are not active = NO

    REDUNDANCY

    Pilot Interface Details

    The pilot interface is comprised of graphics / text display and various switches used by the

    pilot or maintenance crew to control system operation.

  • TROTTER CONTROLS, INC. Document# 9001-0011 Page 14 of 51

    FORT WORTH, TX Revision C, 6/1/2009

    Foam gallons display

    The pilot interface displays the current gallons left in the foam reservoir. The gallons

    displayed can range from 3 to 18 gallons. Due to the mechanical limitations of the foam

    tank sensor, 3 gallons is the minimum that can be displayed.

    Auto Mode Operation The functionality of the switches when the system is in AUTO or TIMER mode is summarized below.

    Switch Functions In AUTO/TIMER Mode

    Table 2 ~ Pilot interface switch functions when in AUTO/Timer mode.

    Parameter Device

    Type

    Action Comments

    Mode Switch Auto, Timer, Man

    Switch

    Set Mode to AUTO Changes the operation

    mode. When set to AUTO,

    primary microprocessor has

    control.

    Hyd Power Switch Turns on hydraulic

    power

    Energize EDUMP valves,

    BLEED valve, pressurizes

    hydraulic system

    Fire switch Switch – 1NO, 1NC Open the doors when

    pressed (if armed),

    Close doors when

    released

    Located on flight stick

    Armed Sw Switch Arms hydraulic

    system directional

    valves (hardware),

    turn armed lamp on if

    real time diagnostics

    is OK

    Display Armed & Ready on

    Status, Light LED if all is

    ready

    Open Door Sw Switch Open the doors at

    1/8 speed, opening

    door

    Open doors manually using

    the primary AUTO system

    Close Door Sw Switch Close the doors at

    1/8 speed, closing

    door

    Close doors manually using

    the primary AUTO system

    Run Pump Sw Switch Turn on pump

    output, running

    pump

    Run the pump using the

    primary AUTO system.

    Clears any detected pump

    errors.

    Test Lamps Sw Switch Test all lamps that

    can be tested (see

    LAMP TEST switch on

    page 20)

    This switch will not function

    if the I2C serial diagnostics

    bus is not active.

  • Page 15 of 51 Document# 9001-0011 TROTTER CONTROLS, INC.

    Revision C, 6/1/2009 FORT WORTH, TX

    Parameter Device

    Type

    Action Comments

    Yes Sw / No Sw Switch Not used for normal

    operation

    Used for menu selection of

    item in the maintenance

    and configuration menus

    Foam / Menu Switch Used to inject foam

    with the optional

    foam injection pump

    Pressing Foam from the

    main AUTO or TIMER menu

    displays the FOAM

    INJECTION menu. Pressing

    MENU will display the

    various maintenance and

    configuration menus.

    Coverage Level

    (Delivery Parameter)

    GENII – Data Wheel

    The coverage level in

    gallons per 100

    square feet

    AUTO MODE: Set the

    retardant flow rate desired

    TIMER MODE: Set time for

    doors to move towards

    open

    Gals to Dump

    (Delivery Parameter)

    GENII – Data Wheel

    Pilot, 200, 250, 300,

    350, 400, 450, 500,

    500, 550, 600, 650,

    700, 750, ALL

    AUTO MODE: Set the

    number of gallons to

    release

    TIMER MODE: Set time for

    doors to remain open

    Dual Armed Light Functionality (AUTO/TIMER Modes)

    On GENII systems, two ARM indicator lights are provided. One ARM light indicates that the

    microprocessor controlled AUTO system is armed while the second ARM light indicates that the

    back-up electro-mechanical system is armed. Both ARM lights on indicates that both the primary

    and backup manual system are armed and ready. GENII systems take any errors detected into

    account before turning the AUTO armed LED on. The possible states of the GENII armed indicators

    and their meanings are shown in the table below.

  • TROTTER CONTROLS, INC. Document# 9001-0011 Page 16 of 51

    FORT WORTH, TX Revision C, 6/1/2009

    Table 3 ~ GENII Dual Armed Indicator Meaning (AUTO/TIMER modes)

    MAN ARMED

    LED

    AUTO ARMED

    LED

    Indicated ARMED Status

    ON ON FULL REDUNDANCY: The backup manual system is armed

    and the primary AUTO system is armed. No errors are

    detected for the AUTO system.

    ON ON FLASHING REDUCED REDUNDANCY: The backup manual system is

    armed and the primary AUTO system is armed. Errors are

    detected for the AUTO system. The auto system may have

    reduced accuracy or reduced redundancy. See status

    message at the bottom of the alpha-numeric display.

    OFF ON NO REDUNDANCY: The backup manual system is not

    armed and the primary AUTO system is armed. This

    condition cannot exist unless there is a hardware problem

    with the manual system.

    OFF ON FLASHING NO REDUNDANCY: The backup manual system is not

    armed and the primary AUTO system is armed but has

    detected errors. This condition cannot exist unless there is

    a hardware problem with the manual system. The AUTO

    system should operate properly. However, there is

    no redundancy should the AUTO system fail.

    ON OFF NO REDUNDANCY: The backup manual system is armed.

    The primary AUTO system is not armed. This condition

    normally exists when the Pilot Interface MODE switch is set

    to MAN. The AUTO system may or many not operate

    properly. The system has reduced or no redundancy.

    The pilot interface and its functionality when operated in AUTO mode are shown in Figure 2.

  • Page 17 of 51 Document# 9001-0011 TROTTER CONTROLS, INC.

    Revision C, 6/1/2009 FORT WORTH, TX

    Figure 2 ~ Pilot interface function when operated in AUTO mode (main AUTO menu shown).

  • TROTTER CONTROLS, INC. Document# 9001-0011 Page 18 of 51

    FORT WORTH, TX Revision C, 6/1/2009

    Timer Mode Operation GENII systems also have a timer mode that allows operation of the system using minimal sensors

    and valves. This mode is provided to allow operation in the event of a sensor or other hardware

    failure that would prevent the AUTO mode from functioning properly. Trial and error adjustments

    of the timer settings are required to provide the desired operation of the gatebox doors.

    Note that timer mode provides constant door angle control similar to less capable systems

    available on the market.

    Timer mode is not recommended as the default operation mode since the quality of the ground

    pattern and retardant usage is not as desirable as the pattern produced by the system when

    operated in AUTO mode.

    Timer mode operation is summarized below:

    € To enter Timer Mode, set the MODE switch on the GENII pilot interface to TIMER.

    € Use the selector knob to adjust the timer value in the COVERAGE window to control how

    long the doors will slew towards the open position before stopping. This adjustment

    controls the fixed gate angle used. Larger timer settings will result in a larger fixed door

    opening.

    € Use the selector knob to adjust the timer value in the GALS TO DUMP window to control

    how long the doors remain open before closing. This adjustment controls how much

    retardant is delivered. If PILOT is selected for this parameter, the doors will close as soon

    as the “FIRE” button is released during a delivery.

    System drops and operation are identical for AUTO and TIMER (GENII only) mode except that the

    retardant flow rate is not actively controlled in TIMER mode since the doors open to a fixed angle

    and remain at this angle until they are closed.

    The functionality of the pilot interfaces and switches when the system is operated in TIMER mode

    are summarized in Figure 3 on the next page.

  • Page 19 of 51 Document# 9001-0011 TROTTER CONTROLS, INC.

    Revision C, 6/1/2009 FORT WORTH, TX

    Figure 3 ~ Pilot Interface Functionality when operated in TIMER mode (main timer menu shown).

  • TROTTER CONTROLS, INC. Document# 9001-0011 Page 20 of 51

    FORT WORTH, TX Revision C, 6/1/2009

    Special Uses of Panel Switches (AUTO/TIMER MODES) The panel switches are, for the most part, self-explanatory, and are described in detail in the AUTO

    MODE and TIMER MODE operation sections. However, some of the panel switches have special

    uses described below.

    LAMP TEST switch

    This switch tests the built-in panel indicator LEDs, with the EXCEPTION of the LEDs labeled “GATE

    CLOSED” (two LEDs), “MAN SALVO”, and the left MAN “ARMED” LED. These LEDs are always

    controlled by hardware and do not respond to the software controlled LAMP TEST function. The

    remaining LEDs will respond to the LAMP TEST switch.

    NO switch

    While in most menus and sub-menus, the NO switch can be used to immediately exit the menu

    system and return to the main system display.

    During system startup, holding the NO switch down will start the system with FACTORY VALUES

    after a warning message is displayed. Note, the system will not operate properly using the factory

    default leakage and analog calibration values. This option is provided as an intermediate step

    required to recover specific calibration data for your aircraft in the event of a memory problem.

    While either an AUTO dump or TIMER dump is in progress, pressing the NO switch will ABORT the

    dump and immediately close the gate doors.

    RUN PUMP switch

    Depressing this switch momentarily will clear ANY active errors except for errors 021 and 105

    reported by the system diagnostics performed by the pilot (SysTest, See System Tests on page

    26), including errors that may have shut down the hydraulic pump. Note that even though all

    errors are cleared, the fact that these errors have occurred are still indicated in both the Error

    History table and the Error Counts table.

    € Pressing the Run Pump clears all current errors except for error 021 and 105.

    € Current hardware errors will return once they are detected again by the system.

    € Errors 021 and 105 detected during SysTest will persist even if power is removed from the

    unit until the appropriate SysTest has been successfully performed to clear the error(s) (See

    System Tests on page 26).

    Special Modes of Operation (AUTO/TIMER)

    Fuel Ferry Mode This special mode of operation allows the airplane to be flown with the gate actuator hydraulically

    locked in the closed position to ferry fuel in the hopper for long non-stop over-water flights. It can

    also be used to ferry water or retardant to distant fires with the hydraulic pump remaining off to

    preserve battery power, and insure that the gate doors are in a fail-safe mode and will not open. In

    this mode, although the system is hydraulically locked, the hydraulic pump will remain off to

    preserve battery power, and hydraulic pressure will NOT be maintained.

  • Page 21 of 51 Document# 9001-0011 TROTTER CONTROLS, INC.

    Revision C, 6/1/2009 FORT WORTH, TX

    To enter this mode, perform the following steps:

    � From the main AUTO or TIMER display press

    the NO/MENU switch.

    � The menu shown to the right should be

    displayed.

    � Use the selector knob to highlight FUEL FERRY

    � Press the selector knob to enter FUEL FERRY

    mode

    � Turn the ARMED switch to the OFF position

    � Turn the HYD POWER switch to the ON position

    o The gate doors are now hydraulically locked and pump operation is disabled.

    � This mode can be exited ONLY by switching “HYD POWER OFF TO EXIT”.

    o No other switches or controls are operational to eliminate accidental exit from this

    mode. The HYD POWER switch is a safety-locking switch and must be pulled out to

    unlock it before it can be switched to the OFF position.

    NOTE: The MAN SALVO button is active in this mode. Depressing the MAN SALVO button

    regardless of ARMED or POWER switch setting will cause the pump to operate and the

    gatebox doors to open slowly.

    Pilot Interface “Mirror” mode A special mode has been incorporated to allow the same graphics and text displayed to the pilot to

    be displayed or “mirrored” on the remote side loader gauges as well as any remote gages present

    in the cockpit. This feature allows a remote display to be mounted in the rear cockpit for pilot

    training purposes (or a more visible location in the front cockpit) and is useful during maintenance

    of the system.

    “Mirror” mode allows any remote display connected to the system (such as the remote hopper

    gauges) to be used to display identical information as on the Pilot Interface display. For example,

    you could monitor operation from just about anywhere as seen in the photo below.

    The remote side loader gages display the same information as any “remote” displays

    located in the cockpit. Be sure to set the MODE switch to MANUAL when loading the

    system with retardant so that the side loaders display hopper gallons to ground

    personnel.

    Enabling/Disabling Mirror

    Mode

    To enable mirror mode functionality, set the value of

    system parameter (tweak) 94 to the value of 255 (the

    default factory value).

    To disable mirror mode functionality, set the value of

    system parameter (tweak) 94 to the value of 0.

    Refer to Trotter Controls Engineering Report 0074 for

    details on how to edit system operation parameters.

  • TROTTER CONTROLS, INC. Document# 9001-0011 Page 22 of 51

    FORT WORTH, TX Revision C, 6/1/2009

    Activating Mirror Mode

    If the mirror mode system parameter has been enabled using system parameter 94 (the default),

    and the MODE switch is in either AUTO or TIMER mode, mirror mode is activated.

    In this mode, the hopper gauge (which normally shows gallons in hopper) will “mirror” the same

    information as displayed on the main Pilot Interface display when the system is in AUTO or TIMER

    mode.

    When the mode switch is set to MANUAL mode, the hopper contents are displayed on the remote

    displays present in the cockpit and on the side loaders.

    De-activating Mirror Mode

    Placing the MODE switch in the MAN position will return the hopper gauge to its normal function.

    Any remote displays (cockpit or side loader) will display the gallons of retardant present in the

    hoppers.

    Brightness Adjust mode

    When the main display is visible in AUTO or TIMER mode, Pressing and holding the selector knob

    will enter Brightness Adjust mode.

    Brightness values may range from 1 (dimmest) through 8 (brightest). Setting a value of zero will

    allow the brightness to “auto-adjust” based on ambient light at the Pilot Interface. The brightness

    setting controls both the display of the Pilot Interface (and any “mirrored” displays) as well as the

    brightness of any dimmable display lamps/LEDs on the Pilot Interface.

    Foam Injection This feature (if installed) allows the operator to inject foam from the foam dispenser into the main

    retardant hopper. This feature is selected by pressing “FOAM/YES” from the main AUTO or TIMER

    screen.

    � Press the “FOAM/YES” from the main AUTO or TIMER screen.

    � Turn “Hyd Power” switch on.

    o Note that the Hydraulic Pump cannot operate

    during operation in this mode.

    � Use the twist knob to select the number of seconds

    (from 0 to 120) to run the injection pump.

    � Press “YES” to operate the injection pump for the

    specified amount of time.

    � The timer value can be changed at any time, or the

    “NO” switch can be used to turn off the pump.

    o A countdown timer at the bottom of the screen shows the number of seconds

    remaining for the injection cycle, while the number displayed at the lower right

    indicates the gallons remaining in the foam tank.

    � Pushing the selector knob exits this screen, turning off the injection pump if it was currently

    on. At exit, the Hydraulic Pump will again be enabled unless the “Hyd Power” switch is first

    turned off.

  • Page 23 of 51 Document# 9001-0011 TROTTER CONTROLS, INC.

    Revision C, 6/1/2009 FORT WORTH, TX

    Manual Mode Operation The operations of the various switches on the panel are summarized in the table below.

    Table 4 ~ Switch functionality in manual mode.

    Parameter Device Type Action Comments

    Mode Switch

    (MAN)

    Auto, Timer, EM

    Switch

    Set Mode to MAN When the switch is set to MAN,

    the electro-mechanical

    relay/timer system has control.

    NO REDUNDANCY IN MAN

    MODE.

    Hyd Power Switch Turns on hydraulic power Energize EDUMP valves, BLEED

    valve, pressurize hydraulic

    system

    Fire switch Switch – 1NO,

    1NC

    Open the doors when

    pressed, Close doors when

    released

    Located on flight stick

    Armed Sw Switch Arms hydraulic system

    directional valves (hardware),

    turn armed lamp on if real

    time diagnostics OK

    AUTO armed is not active when

    in MAN mode (NO

    REDUNDANCY IN MAN

    MODE)

    Open Door

    Sw

    Switch Open the doors at 1/8 speed, Open doors manually using the

    secondary electro-mechanical

    system

    Close Door

    Sw

    Switch Close the doors at 1/8 speed, Close doors manually using the

    secondary electro-mechanical

    system

    Run Pump Sw Switch Active switch to manually

    turn on the pump

    Run the pump using the

    secondary electro-mechanical

    system

    Note that the system hardware is not able to turn the pump off when in manual (MAN) mode in the

    event of a detected pump error. The pilot should monitor the RUN PUMP LED and make sure the

    system has sufficient oil before using manual mode since the automatic pump error detection used

    to detect errors is not active when operated in MAN mode.

    Salvo System Activation GENII FRDS systems incorporate an automatic salvo backup system. The function of this sub-

    system is to open the doors in the event that the primary (AUTO) system is unable to open the

    doors due to a hardware or software error.

    GENII systems provide two independent automatic salvo systems (one system is controlled by an

    independent supervisor microprocessor (AUTO SALVO) while the second system is controlled by

    relays and hardware timers only (MAN SALVO)).

    The two independent automatic salvo systems are only active in AUTO or TIMER modes of

    operation. The function of these systems is to monitor whether or not the primary AUTO/TIMER

    system opened the gatebox doors as expected when the system is armed and the “FIRE” button is

    depressed.

  • TROTTER CONTROLS, INC. Document# 9001-0011 Page 24 of 51

    FORT WORTH, TX Revision C, 6/1/2009

    Automatic Salvo Activation If the doors do not open as expected in AUTO or TIMER mode when the system is “ARMED”,

    hydraulic power is present, and the “FIRE” button is depressed, the system will perform the

    following actions:

    � Open the gatebox doors using a directional valve

    o The AUTO SALVO microprocessor system uses valve 2 on the hydraulic manifold

    o The MAN SALVO electro-mechanical system uses valve 3 on the hydraulic manifold

    � Run the pump for a specified time interval

    � Illuminate the AUTO SALVO or MAN SALVO LED to indicate which of the two independent

    auto salvo systems has been activated.

    o Note that normally the AUTO SALVO system is activated first.

    o The MAN SALVO system is activated only if the AUTO SALVO system was unable to

    open the doors for some reason within the specified amount of time.

    See the sections below for more information regarding the AUTO SALVO and MAN SALVO system

    operation.

    Pilot Activated Salvo

    The manual salve system can be activated using the red MAN SALVO button regardless of the pilot

    interface switch settings. On GENII systems, this button is located adjacent to the power quadrant

    on the L/H side of the cockpit.

    o This RED button overrides the power, mode, and arm switches to open the gatebox doors.

    If no hydraulic pressure is present in the system (system power is off), the doors will open

    slowly as the pump delivers flow to open them.

    o To open the doors using the MAN SALVO button, depress the red “SALVO” button. This will

    run the pump, open the doors, then leave the doors in the open state after a timeout

    period. The pump will run until a pressure of 3000 PSI is reached, then it will turn off

    automatically.

    o This latching button disables auto and manual operation when activated (pressed in).

    ����Caution: Never press this button unless you intend for the gatebox doors to open and

    you have verified that all personnel are clear of the gatebox doors.

    ����Always deactivate the MAN SALVO button to resume normal system operation. The

    button should be in the extended position for normal operation.

    Auto Supervisor Activated Salvo No pilot action is required for this event to occur. The microprocessor controlled AUTO SALVO

    system monitors the doors to make sure they open when expected. If the doors do not open

    within 0.8 seconds after the fire switch has been pressed, the system will take over, isolate the

    primary system and attempt to open the gatebox doors.

  • Page 25 of 51 Document# 9001-0011 TROTTER CONTROLS, INC.

    Revision C, 6/1/2009 FORT WORTH, TX

    � Pre-conditions: MODE=AUTO or TIMER, HYD PWR=ON, ARMED=ON

    � Activation Condition: If “FIRE” button is depressed and the gatebox doors do not open

    within 0.8 seconds, an AUTO SALVO condition is triggered.

    o If the AUTO SALVO system has been activated, this means that primary system

    (AUTO or TIMER mode) failed to open the doors.

    � The AUTO SALVO LED will be illuminated when this system is activated.

    � Valve 2 (middle directional valve) on the hydraulic manifold is used to open the doors.

    � The pump is operated for 20 seconds, then is turned off.

    � The gatebox doors will remain open until the salvo condition is cleared.

    MAN System Activated Salvo No pilot action is required for this event to occur. The electro-mechanical MAN SALVO system

    monitors the doors to make sure they open when expected. If the doors do not open within 1.2

    seconds after the “FIRE” switch has been pressed (this is 0.4 seconds after the AUTO SALVO

    system would have tried to open the doors), the system will take over, isolate the primary system

    and attempt to open the gatebox doors.

    � Pre-conditions: MODE=AUTO or TIMER, HYD PWR=ON, ARMED=ON

    � Activation Condition: If “FIRE” button is depressed and the gatebox doors do not open

    within 1.2 seconds, a MAN SALVO condition is triggered.

    � This MAN SALVO system is activated 0.4 seconds after the AUTO supervisor is activated.

    o If the MAN SALVO system has been activated, this means that the AUTO SALVO

    system failed to open the doors.

    � The MAN SALVO LED will be illuminated when this system is activated.

    � Valve 2 (middle directional valve) on the hydraulic manifold is used to open the doors.

    � The pump operates until a pressure of 3000 PSI is reached and runs as required to maintain

    hydraulic pressure. It’s operation is controlled via a relay and a pressure switch.

    � The doors will remain open until the salvo condition is cleared.

    Recovery from an Automatic Salvo Condition To reset the system after a AUTO or MAN SALVO event, the error must be cleared. To clear the

    error on GENII systems perform the following actions:

    � Turn the ARM switch to the “OFF” position.

    � Turn the POWER switch to the “OFF” position.

    � The condition should be cleared and the MAN SALVO button should not be illuminated.

    � Turn the POWER switch to the “ON” position and operate the system as required.

    If MAN SALVO is still displayed after performing the steps above, check the following:

    � Verify that all breakers are pushed in are not tripped.

    � Verify that the MAN SALVO red button is not pressed in.

    � Verify that the relay enclosure is connected properly and receiving power as expected. MAN

    SALVO is displayed anytime the relay enclosure is not receiving power as expected and the

    pilot interface is active.

  • TROTTER CONTROLS, INC. Document# 9001-0011 Page 26 of 51

    FORT WORTH, TX Revision C, 6/1/2009

    System Tests

    The FRDS system passively monitors many parameters any time the HYD POWER switch is set to

    the ON position and the mode is set to AUTO or TIMER. However, some items are only tested

    when the pilot initiates a SysTest menu item, since outputs and valves must be activated to fully

    test the system. The self test feature incorporated in the unit is able to detect the following

    problems:

    � Stuck valves

    � Incorrectly wired valves (in most cases)

    � Burned out wires

    � Burned out coils

    � Problems with the pump or accumulator

    � Faulty or improperly adjusted sensors

    � Improper manifold orifice installation

    � Damaged or non-operational pilot interface switches

    � Other errors

    We recommend that the following tests be performed by the pilot on a regular basis as shown

    below to ensure that the system is operating as expected:

    Table 5 ~ Recommended Pilot Initiated System Test Schedule.

    System Test Type Recommended

    Test Interval

    Comments

    Pilot (no doors) Daily Test can be performed with hoppers fully

    loaded

    Pilot (ALL) Weekly Hoppers must be empty for this test

    Auto Salvo Weekly Hoppers must be empty for this test

    Man Salvo Weekly Hoppers must be empty for this test

    Maint SysTest As required Hoppers must be empty for this test

    System Self Diagnostic Tests – SysTest Menu To enter the SysTest menu, perform the following steps:

    � From the main AUTO or TIMER menu press the

    NO/MENU switch.

    � The menu shown below should be displayed.

    � Use the selector wheel to highlight SysTest

    � Press the selector wheel to enter SysTest mode

    � Use the selector wheel to select the test to be

    performed

    � Follow instructions on the screen

    NOTE: The red MAN SALVO button is active in this mode. Depressing the MAN SALVO button will

    cause the pump to operate and the doors to open slowly.

  • Page 27 of 51 Document# 9001-0011 TROTTER CONTROLS, INC.

    Revision C, 6/1/2009 FORT WORTH, TX

    The SysTest submenu contains the following five menu items:

    • Pilot (no doors) – Testing with no gatebox door movement allowed

    • Pilot (ALL) – Comprehensive tests with gatebox door movement allowed

    • Auto Salvo – Test the microprocessor controlled AUTO SALVO system

    • Man Salvo – Test the electro-mechanical MAN SALVO system

    • Maint SysTest – Same as Pilot(ALL) with PASS/FAIL and diagnostics reports displayed

    Note that it is necessary to scroll the menu using the data

    wheel to display all of the items shown above, since only

    four items can be displayed at one time on the four line

    display.

    The individual submenu items are fully described in the

    following sections.

    Pilot (no doors) – System Test

    This submenu item allows the pilot to quickly test system components that DO NOT result in the

    gate doors being operated. This set of tests is useful when there are contents in the hopper that

    should not be released. The total time of this set of tests requires about 45 seconds. The tests are

    performed without the need for operator intervention unless any of the tests fail, in which case an

    error indicator remains on the screen until cleared by the pilot. The set of tests that are performed

    are:

    • Switch Test (optional) – Pilot must cycle all switches during this test, then press the data

    wheel in once all “illuminated blocks” indicating the switch positions are not illuminated to

    continue to the next test (See Trotter Controls Document# TS-0005 for more information on

    the switch test)

    • Valve Mon1 Mon2 Test – Are the valves connected, OK, and is wiring OK.

    • Hyd Pump pressure limit test

    • Bleed / Edump Pass Fail test

    Pilot (ALL) – System Test

    CAUTION: The gatebox doors are operated during this test. Verify that all ground

    personnel are clear before selecting this test.

    This submenu item allows the pilot to quickly test ALL system components, including those that

    result in the gate doors being opened. This set of tests is useful when the hopper is empty. The

    total time of this set of tests requires about 2 minutes.

    The tests performed are almost identical to the comprehensive maintenance system tests described

    below except that no status is displayed to the pilot unless a failure is detected. Trotter Controls

    Document# TS-0005 has a detailed description of the items that are tested.

    The tests are performed without the need for operator intervention unless any of the tests fail, in

    which case an error indicator remains on the screen until cleared by the pilot. The set of tests that

    are performed are:

  • TROTTER CONTROLS, INC. Document# 9001-0011 Page 28 of 51

    FORT WORTH, TX Revision C, 6/1/2009

    • Switch Test (optional) – Pilot must cycle all switches during this test, then press the data

    wheel in once all “illuminated blocks” indicating the switch positions are not illuminated to

    continue to the next test (See Trotter Controls Document# TS-0005 for more information on

    the switch test)

    • Valve Mon1 Mon2 Test – Are the valves connected, OK, and is wiring OK.

    • Valve Wiring Test – Do valves function as expected. Are they connected properly?

    • Gate prox switch test – Verify that the door home sensors function properly.

    • Hyd Pump pressure limit test – Verify that the hydraulic pump and sensor are OK.

    • Bleed / Edump Pass Fail test – Verify that the bleed and EDUMP valves function properly.

    • Gate Angle voltage Test – Verify that the gatebox angle sensor functions properly.

    Auto Salvo – System Test

    CAUTION: The gatebox doors are operated during this test. Verify that all

    ground personnel are clear before selecting this test.

    This submenu item allows the pilot to test the primary microprocessor controlled automatic salvo

    system (Auto Salvo) for ensuring that a dump occurs when the pilot requests one. This test should

    be performed only when the hopper is empty. After starting this test, the operator is instructed to

    press the DUMP (fire) switch. The primary system will inhibit dumping and the redundant system

    should then initiate an AUTO SALVO. The display should read AUTO SALVO (in large text). Turn

    the ARMED switch off to terminate this test after a salvo has occurred.

    Man Salvo – System Test

    CAUTION: The gatebox doors are operated during this test. Verify that all

    ground personnel are clear before selecting this test.

    This submenu item allows the pilot to test the secondary electro-mechanical automatic salvo

    system (Man Salvo) for ensuring that a dump occurs when the pilot requests one. This test should

    be performed only when the hopper is empty. After starting this test, the operator is instructed to

    press the DUMP (fire) switch. The primary system and first redundant system will inhibit dumping

    and the second redundant system should then initiate a MAN SALVO. The display should read MAN

    SALVO (in large text). Turn the ARMED switch off to terminate this test after a salvo has occurred.

    Maint SysTest – Maintenance Personnel – System Test

    CAUTION: The gatebox doors are operated during this test. Verify that all

    ground personnel are clear before selecting this test.

    This submenu item allows maintenance personnel to test any or all system components. Unlike the

    Pilot(no doors) and Pilot(ALL) tests, these tests require the operator to acknowledge the result of

    each test, whether the test passes or fails. The operator may choose which tests to perform and

    which tests to skip. The set of tests that may be performed are:

  • Page 29 of 51 Document# 9001-0011 TROTTER CONTROLS, INC.

    Revision C, 6/1/2009 FORT WORTH, TX

    • Switch Test – Pilot must cycle all switches during this test, then press the data wheel in

    once all “illuminated blocks” indicating the switch positions are not illuminated to continue

    to the next test (See Trotter Controls Document# TS-0005 for more information on the

    switch test)

    • Valve Mon1 Mon2 Test

    • Valve Wiring Test

    • Gate prox switch test

    • Hyd Pump pressure limit test

    • Bleed / Edump Pass Fail test

    • Hyd Pump rate & Bleed/eDump Test

    • Continuous Hyd System Flush

    • Gate Angle voltage Test

    All of the tests performed in any of the SysTest menu choices are described in detail in a separate

    document, Trotter Controls Document# TS-0005.

    System Test Persistent Errors

    The FRDS computer saves the results of the system tests to EEPROM so that an error is indicated

    anytime the system has failed to pass SysTest as expected. This feature has been added to alert

    the pilot that the system previously failed during the pilot initiated system test (SysTest) of the

    controls and hydraulics hardware. These errors can only be reset by successfully performing the

    system tests for the system hardware.

    Two error conditions can be detected and will persist even if power is removed from the system

    until the hardware is able to pass the system tests.

    � "021_Panel Switch Err" - The switch test failed or was aborted by the pilot during the

    current or previous SysTest.

    � "105_Systest Err" - Some hardware item failed during the current or previous SysTest.

    Error number 021 indicates that either a panel switch error had occurred during SysTest, or that

    the operator had aborted the panel switch test without successfully completing the test by testing

    all possible switch positions.

    Error number 105 indicates that some error had occurred during a previous run of SysTest, and a

    successful run of SysTest had not been completed since the error occurred.

    Clearing Persistent SysTest Errors

    While the RUN PUMP switch and the "Clear Errors" menu item of the “Maint” menu can be used to

    “clear all errors”, these will NOT clear the persistent errors 021 and 105. These errors can only be

    cleared by successfully running a SysTest procedure.

  • TROTTER CONTROLS, INC. Document# 9001-0011 Page 30 of 51

    FORT WORTH, TX Revision C, 6/1/2009

    To clear error “021_Panel Switch Err”, perform either “PILOT (no doors)”, “PILOT (ALL)”, or “Maint

    SysTest”.

    o Make sure to cycle all switches during the switch test per Trotter Controls

    Document# TS-0005.

    o Do not press the data wheel to exit the switch test until all of the switches have been

    properly cycled and the “illuminated block” indicators for each switch position have

    gone out as each switch is actuated.

    o The error is automatically cleared once the switch test has been properly performed

    with no detected failures.

    To clear error "105_Systest Err”, perform the PILOT (ALL) system test.

    o Perform the “PILOT (ALL)” system tests per Trotter Controls Document# TS-0005.

    o Do not exit the test or abort during the test sequence.

    o The error is automatically cleared once the SysTest has been performed and the

    hardware is verified to operate properly.

    o Note that performing a “Maint SysTest” or a “Pilot (no doors)” SysTest WILL NOT

    clear error 105. A successful PILOT (ALL) test is the only way to clear this error.

    Maint SysTest can be utilized to diagnose the cause of the system failure but will not

    clear the persistent error.

    Menu System

    The menu system is a multi-level set of menus that is initiated by pressing the “NO/MENU” switch

    from the main AUTO or TIMER screen. Rotate the selector knob to the desired option and press the

    selector knob to select that option. To exit any menu, press the NO switch, which results in

    returning to the main AUTO or TIMER screen. Some menus have an “EXIT” option which will return

    to the previous (higher level) menu.

    Main Menu

    The Main menu contains the following menu items:

    • Maint – Maintenance Functions

    • Config – Set the aircraft configuration

    • SysTest – Perform hardware diagnostics

    • Fuel Ferry – Special mode for ferry operations

    • ErrorHistory – Display of logged errors

    • Exit – Exits the current screen

    Maint Menu

    This menu item opens a “Maintenance” submenu which contains the following menu items:

    • Tweak Parameters – Adjust system operation parameters - See Trotter Controls

    Document ER-0074 for details.

    • Digital Inputs – View the various inputs from switches and sensors in the system

  • Page 31 of 51 Document# 9001-0011 TROTTER CONTROLS, INC.

    Revision C, 6/1/2009 FORT WORTH, TX

    • Digital Input Map – View a map of all inputs simultaneously

    • Digital Outputs – View and/or force selected outputs

    • Digital Output Map – View a map of all outputs simultaneously

    • Analog Inputs – View the various voltages from sensors monitored by the system

    • Analog Calibrate – Calibrate the system A/D converters (factory use only)

    • Err Msg Index/Counts – Show a listing of all errors that can occur

    • Clear Errors – Clear active errors but don’t clear the count of errors that have occurred

    • Clear Err Counts – Clear the counts for the number of times a given error has occurred.

    This clears the counts for all error counters.

    • Clear ErrHistory – Clear the error history buffer

    • System Reset – Restart/Re-boot the primary microprocessor

    • Save Memory – Save memory to the internal and/or external data memory

    • Read EEprom – Read the leakage data and other information from the external memory

    • Compare RAM/EE – Display the differences in active parameters and the EEPROM memory

    • Logo/Version – Display the Air Tractor Logo and software version installed

    • Leakage Table – Display the tank leakage calibration factors

    • Exit – Exit the menu

    Config Menu

    This menu item opens a “Configuration” submenu which contains the following menu items:

    • Aircraft – Select the aircraft type and hardware configuration

    • Learn – Set learning mode for dump pit calibration. Refer to PS-0032

    • H/Ware – Future Use - Hardware configuration options.

    • Exit – Exit the menu

    SysTest Menu

    This menu item opens a “SysTest” submenu. This menu selection is used to select the various

    diagnostics self tests that can be performed by the system. The system test features are described

    in System Test section of this document.

    Error History

    From the Main menu, select “Error History”. This display shows any errors that have occurred in

    chronological order. Errors displayed include those encountered during the current run, as well as

    those that have occurred during previous runs of the system. A “system reset” entry (code 001)

    separates the current run errors from those of previous runs. The most recent error is at position

    number 1 of the error history table, with the oldest error at position number 50. The position of

    the entry at the beginning of the current run is indicated by “(1st boot entry)”. Errors at positions

    lower than this entry (through position number 1) have occurred during the current run of the

    system. Errors at positions higher than this entry (through position number 50) have occurred

    during prior runs of the system.

  • TROTTER CONTROLS, INC. Document# 9001-0011 Page 32 of 51

    FORT WORTH, TX Revision C, 6/1/2009

    Digital Inputs

    This menu option allows maintenance personnel to view the values of various digital inputs to the

    system. Each input is listed with its hardware pin designator and preceded with its current value,

    either “ON” (in highlighted text) or “OFF” (in normal text). The sequence number of the input is

    displayed in highlighted text. The sequence number ranges from 0 to 81 and is associated with the

    “Digital Input Map” display (described next). Panel switches appear at the beginning of the digital

    input display to facilitate easy testing.

    Note: “Digital Inputs” mode is the ONLY mode (other than Pilot Assisted Test – SysTest) in which

    an AUTO dump is INHIBITED. In all other modes, if the system is “ARMED” and “Hyd Power” is on

    and the Fire switch is pressed, an auto dump will be performed. “Digital Inputs” mode will inhibit

    an auto dump if the MODE switch is in either the “AUTO” or the “TIMER” position. Note that simply

    inhibiting an auto dump will NOT prevent a dump from happening; because if an auto dump DOES

    NOT occur, one of two backup systems (AUTO SALVO or MAN SALVO) will take control and open

    the gate doors.

    Digital Input Map

    This menu option allows maintenance personnel to view the values of all digital inputs to the

    system on a single screen. Since there are 21 characters per line and four lines per screen, up to

    84 inputs may be viewed at once. Digital inputs are numbered from 0 to 83, and are listed

    sequentially on the display with 0 to 20 on the top line, 21 to 41 on the second line, 42 to 62 on

    the third line, and 63 to 83 on the bottom line. To

    facilitate ease of reading the display, a digit

    (0,1,2,3,4,5,6,7,8) is displayed every 10 positions

    to indicate positions 0,10,20,30,40,50,60,70, and

    80. A slash mark “/” is displayed every 5 positions

    at position 5,15,25,35, etc. Positions that

    correspond to an input value of “ON” will contain a

    block character. Positions that correspond to an input value of “OFF” will NOT contain a block

    character. The sample display below shows all inputs “OFF” except for inputs numbered 1, 10, 13,

    15, 31, 33, 77, 79, 80, and 81.

    To facilitate easier reading of the display when many “ON” states (block characters) exist, when a

    block character is present at a position that is a multiple of five (0,5,10,15,20,etc.), a narrow block

    character is used instead of the full-sized block character. Note that the first 11 digital input values

    (positions 0 to 10) represent the current state of the Pilot Interface panel switches, as viewed from

    left to right. A complete list of the digital input numbers can be viewed in the “Digital Inputs”

    display.

  • Page 33 of 51 Document# 9001-0011 TROTTER CONTROLS, INC.

    Revision C, 6/1/2009 FORT WORTH, TX

    Digital Outputs

    This menu option allows maintenance personnel to view