Foul Condensate7

Embed Size (px)

Citation preview

  • 8/12/2019 Foul Condensate7

    1/2

    PLUMBING INDUSTRY COMMISSION

    Technical SolutionsTechnical SolutionsTechnical Solutions

    Page 1 of 2

    Continued over.../

    Current as atAugust 2003

    7 : MECHANICAL SERVICES

    Condensate drainage for air conditioning systems

    Condensate drainage using a self sealing device

    Note this technical solution is in addition to previously published technical solutionsrelating to split system installation and condensate drainage methods and may also beused for applications such as high efciency ducted heaters and evaporative coolers.

    40mm upvc pipe

    40mm upvc pipe

    Flow

    Flow

    Adaptor

    Adaptor

    Fig. 1 Self sealing device

    Fig. 2 Via a discharge pipe beneath a sink, trough or vanity basin

    A self sealing device is, in effect, awaterless trap which is designed to closeafter waste discharge and prevent theadmittance of foul air into the building.It offers the advantage, in the case ofcondensate drainage, of continuing toprevent foul air entry during times oflittle or no ow when a conventionalwater trap seal may evaporate.

    The device is designed for 40mmupvc pipe and can be installed in thevertical or on grade position but must

    be within a building, accessible and outof direct sunlight. An adaptor tting(available from the manufacturer, orregular ttings) may be required for theupstream end of the valve to providefor the connection of 40mm pipe or atundish. (See g.1 opposite.)

    Permitted locations

    1(a) Via the discharge pipe beneath asink, trough or vanity basin.

    A junction and device is installedby the sanitary plumberin the verticalsection of discharge pipe (50mm or40mm) below the trap seal of the xtureand the self sealing device is installed inthe vertical position as high as is practicalto the underside of the benchtop. Thedischarge pipe, device and condensatedrain must be adequately supported. Atundish is required on the top of thedevice to provide a physical air gap(20mm) in the condensate drain. (See

    g. 2 opposite.)

    Airgap

    Self sealingdevice50mm or 40mm

    fixture dischargepipe

    Drain

    40mmdischarge

    pipe

  • 8/12/2019 Foul Condensate7

    2/2

    PLUMBING INDUSTRY COMMISSION

    Technical SolutionsTechnical SolutionsTechnical Solutions

    Page 2 of 2

    Current as atAugust 2003

    7 : MECHANICAL SERVICES

    Condensate drainage for air conditioning systemsCont.

    Permitted locations cont.

    40mmdischargepipe

    Vent

    Ceiling space

    Tundish

    Self sealing device

    Air gap

    Drain from air conditioning unit

    1(b) Via a dishwasher connection point on aDN 50mm xture trap

    Fig. 4 To a vent in a ceiling space vertical position

    40mmdischargepipe

    Vent

    Ceiling space

    Tundish

    Self sealing device

    Air gap

    Drain from air conditioning unit

    Fig. 5 To a vent in a ceiling space on grade

    Alternatively the drain may discharge

    to the dishwasher connection point ona 50mm xture trap using appropriateexible hose and ttings providing all theconditions described in 1(a) can be met.(See g. 3 opposite.)

    2. Waste or vent in a roof / ceiling space.

    The condensate drainage from an airconditioning or heating appliance maybe discharged to a vent pipe via a selfsealing device located in a ceiling or roofspace. The junction and device is to be

    installed by the sanitary plumberandmust be supported in accordance with AS3500. It is preferable for the device to beinstalled in the vertical position with an airgap provided over a tundish. (See g. 4opposite.)

    If it is not practical to install the devicein the vertical position, it is acceptable inan on-grade position as long as a tundishincorporating an air gap is provided. (Seeg. 5 below, opposite.)

    In the case of ceiling space

    installations, test the system under fulloperating conditions to ensure there is nosplashing or spillage from the tundish onto the ceiling.

    Airgap

    Self sealing

    device

    Flexible hose50mmfixture dischargepipe

    Drain

    Dishwasher connection

    50mm fixture trap

    Fig. 3 Dishwasher connection point on a DN 50mm xture trap