Module Type Controller SRZ IMS01T12-E1 Thank you for purchasing this RKC product. In order to achieve maximum performance and ensure proper operation of your new instrum ent, carefully read all the instructions in this manual. Please place this manual in a convenient location for easy reference. 1. PLC COMMUNICATION DATA TRANSFER The data transmitted between the PLC and the Z-TIO-C/D module is compiled in the PLC communication data map. In the PLC communi cation data map the communication data is classified into system data, monitor groups, and setting groups. System data Request item number, Request commands, Setting group communication state, etc. Monitor group Measured value (PV), Comprehensive event state, etc. Setting group PID/AT transfer, Set value (SV), etc. PLC PLC register Z-TIO-C/D module 1 Z-TIO-C/D module 2 For the communication data, see 2. PLC COMMUNICATION DATA MAP . 1.1 Data Transfer Type Data transfer between PLC and Z-TIO-C/D m odule are executed by the request item number and the request command. Request item number This command sets the communication data of th e setting group that is transferred. Set transfer of all communication data of t he setting group, or transfer by one data item. Data transfer are executed by request command. Setting range: 0 or 1 to 64 (Item number) When set to 0, all communication dat a of the setting group is transferred. When set to a number from 1 to 64 (item number), only the set communication data item is transferred (t ransfer by one data item). For the item number 1 to 64, see “ Table 2: Setting item selection (Communication data of setting group) of Z-TIO PLC Communication Quick Instruction Manual [PART1: Preparation] (IMS01T11-E ). Note that communication data that is not selected (set to binary: 0) in setting item selection of the PLC communication environment is not transferred. Request command For the request command, both “setting request bi t” and “monitor request bit” are available. Setting request bit (PLC Z-TIO-C/D module) This command requests that the Z-TIO- C/D module read the communication data of the setting group on the PLC side. [Processing] (1) Just when “1 (decimal numbers: 1)” is se t to the setting request bit, the Z-TIO-C/D module starts reading the data from the PLC side. (2) The setting group communication data set in “Request item number” is transferred from the PCL to the Z-TIO-C/D module. (3) After data transmission is complet ed, the setting request bit becomes “0.” Monitor request bit (PLC Z-TIO-C/D module) This command requests that the Z-TIO-C/D module write the communication data of the setting group on the PLC side. [Processing] (1) Just when “1 (decimal numbers: 2)” is set to the monitor request bit, the Z-TIO-C/D starts writing the dat a to the PLC side. (2) The setting group communication data set in “request item number” is transferred from the Z-TIO-C/D module to the PLC. (3) After data transmission is completed, the monitor request bit becomes “0.” When setting both the setting request bit and the monitor request bit to “1,” set the bits simultaneously. If se t separately, the bit set later may be disregarded. Monitor group The monitor group communication data is always transferred as monitor item data between the PLC and the Z-TIO-C/D module rega rdless of the request command setting. 1.2 Data Transfer Procedures Change each set value of Z-TIO-C/D m odule from the PLC after the initial settings are made. If each set value of Z-TIO-C/D module is changed from the PLC without setting the initial values, it is re-written to “0” with each set value of the PLC at that time set to “0.” Initial setting Data setting When the setting group communication data is transferred from PLC to the Z-TIO-C/D module. Data processing precautions The data type is treated as binary data with a sign and without a decimal point. For this reason, carefully express and set the data. (Excluding the bit data) 2. PLC COMMUNICATION DATA MAP The data that can be communicated by the PL C and Z-TIO-C/D module is compiled in the PLC communication data map. The data map indi cated in this manual is the data map of factory set value. The data map ca n be changed using the PLC communication environment items below. Register type Setting item register bias Register start number (High-order 4-bit) Monitor item selection Register start number(Low-order 16-bit) Setting item selection Monitor item register bias Slave register bias For the PLC communication environment item, see Z-TIO PLC Communication Quick Instruction Manual [PAR T1: Preparation] (IMS01T11-E ). For communication data not described in this manual, see the SRZ Instruction Manual [PLC Communication] (IMS01T13-E ). 2.1 Explanation of Data Map Items Name: Name of communication data Register address: A register address of communication data in PLC communication (MITSUBISHI MELSEC series) Structure: C: Data for each channel M: Data for each module Attribute: RO: Read only data (PLC Z-TIO-C/D module) R/W: Read and Write data (PLC Z-TIO-C/D module) Data range and Number of data: Data range: Read or write range of communication data Number of data: This is the maximum number per communication data that can be handl ed by one Z-TIO-C/D module. (Numerical value in the [ ] at the lower right) The total number of communication data is 150 items. Factory set value: Factory set value of communication data 2.2 Data Map The data map register address is the addre ss when the following items are used at their factory set values. Register start number (Low-order 16-bit): 1000 ) r e t s i g e r D ( 0 : e p y t r e t s i g e R Monitor item register bias: 10 Setting item register bias: 0 Monitor item selection: 33535 Setting item selection: ch1: 62427 3 8 5 5 1 : 2 h c 2 1 5 : 3 h c 2 1 5 : 4 h c Z-TIO-C/D module 1 Z-TIO-C/D module 2 System data: D01000 to D01009 System data: D01150 to D01159 Monitor group: D01010 to D01049 Monitor group: D01160 to D01199 Setting group: D01050 to D01149 Setting group: D01200 to D01299 Data map of Z-TIO-C/D module 1 Name Register address Structure Attribute Data range and Number of data Factory set value System communication state D01000 M RO Bit data b0: Data collection condition b1 to b15: Unused Data 0: Before data collection is completed 1: Data collection is completed [Decimal number: 0, 1] ] 1 [ Z-TIO normal communication flag D01001 M RO 0/1 transfer (For communication checking) “0” and “1” are repeated for each communication period. ] 1 [ D01002 RO Internal processing Do not use the register address ] 1 [ D01003 RO Internal processing Do not use the register address ] 1 [ PLC communication error code D01004 M RO Bit data b0: PLC register read/write error b1: Slave communication timeout b2: Unused b3: Unused b4: Master communication timeout b5 to b15: Unused Data 0: OFF 1: ON [Decimal number: 0 to 31] [1] Z-TIO module recognition flag D01005 M RO Bit data b0: Z-TIO module 1 b1: Z-TIO module 2 b2: Z-TIO module 3 b3: Z-TIO module 4 b4: Z-TIO module 5 b5: Z-TIO module 6 b6: Z-TIO module 7 b7: Z-TIO module 8 b8: Z-TIO module 9 b9: Z-TIO module 10 b10: Z-TIO module 11 b11: Z-TIO module 12 b12: Z-TIO module 13 b13: Z-TIO module 14 b14: Z-TIO module 15 b15: Z-TIO module 16 Data 0: No module exists 1: Module exists [Decimal number: 0 to 65535] [1] D01006 Internal processing Do not use the register address ] 1 [ Request item number D01007 M R/W 0 or 1 to 64 0: Transfer all communication data of the setting group. * 1 to 64: Transfer only the communication data of the selected item number. * ] 1 [ 0 Request command D01008 M R/W Bit data b0: Setting request bit b1: Monitor request bit Data 0: OFF 1: ON [Decimal number: 0 to 3] ] 1 [ 0 Setting group communication state D01009 M RO Bit data b0: Setting error bit b1: Setting completed bit b2: Monitor completed bit Data 0: OFF 1: ON [Decimal number: 0 to 7] ] 1 [ * Note that communication data that is not selected (set to binary: 0) in setting item selection of the PLC communication environment is not transferred. 0000000000000000 bit 15 bit 0 Request command: bit 1: Monitor request bit bit 0: Setting request bit Turn on the power of the Z-TIO-C/D module, and the PLC. When the PLC communication start time (factory setting: 5 seconds) elapses, writing of the system data begins. When the monitor request bit (bit 1) of request command of the PLC register is set to “1 (Decimal: 2),” th e Z-TIO-C/D module begins writing the setting group to th e PLC. During data write: Treat the data of all items as inconsistent during the data write. If the monitor request bit (bit 1) of the request command of the PLC register is “0,” this indicates that writing of dat a to the PLC is finished. After the system data is written, the Z-TIO-C/D modul e begins writing the communication data of the monito r group to the PLC. When monitor group writing starts, “system communication state” changes to “1.” When the system communication condition becomes “1, PLC communication can be performed. Because all communication data of the setting group i s written to the PLC, the request item number of the PL C register is set to “0.” When writing is finished, the Z-TIO-C/D module writes th e communication state of the setting group to the monito r completed bit (bit 2) of the setting group communication state of the PLC. System communication state = 1? YES NO Start Turn on power of each instrument Set “1 (Decimal: 2)” to the monitor request bit (bit 1). Monitor request bit (bit 1) = 0? YES NO End Set “0” to the request item number. Monitor completed bit (bit 2) of the setting group communication state = 1 (Decimal: 4) Setting request bit (bit 0) = 0? If the setting request bit (bit 0) of the request command o f the PLC register is “0,” this indicates that reading of data from the PLC is finished. NO YES When the monitor request bit (bit 1) of request command of the PLC register is set to “1 (Decimal: 2),” th e Z-TIO-C/D module begins writing the setting group to th e PLC. If the monitor request bit (bit 1) of the request command of the PLC register is “0,” this indicates that writing o f data to the PLC is finished. NO YES End Set “1 (Decimal: 2)” to the monitor request bit (bit 1). A Set “0” to the request item number. [Confirmation of setting data] The request item number of the PLC register is set to “0” fo r verification of the data read from the PCL by the Z-TIO-C/D module. During data write: Treat the data of all items as inconsistent during the data write. Monitor completed bit (bit 2) of the setting group communication state = 1 (Decimal: 4) When writing is finished, the Z-TIO-C/D module write s the communication state of the setting group to th e monitor completed bit (bit 2) of the setting grou p communication state of the PLC. Monitor request bit (bit 1) = 0? 0000000000000011 bit 15 bit 0 Request command: bit 1: Monitor request bit bit 0: Setting request bit (Decimal numbers: 3) Set the setting group communication data values in the register (memory) on the PLC side. Set “1” to the setting request bit (bit 0). When the setting request bit (bit 0) of request command of the PLC register is set to “1,” the Z-TIO-C/D modul e begins reading the data set in the PLC register (memory). During data read: Treat the data of all items as inconsistent during the data read. Start A Set “0” to the request item number. [Data setting] Set “0” to the request item number of PLC register. Setting completed bit (bit 1) of the setting group communication state = 1 (Decimal: 2) When reading of the data ends, the Z-TIO-C/D modul e writes the setting group communication state to th e setting completed bit (bit 1) of PLC setting grou p communication state. All Rights Reserved, Copyright 2006, RKC INSTRUMENT INC. Z - TIO PLC Communication Quick Instruction Manual [PART2: Operation] Temperature Control Module [for PLC Communication] (800) 576 - 6308 www.rkc-usa.com Distributed By Inc, RKC

[for PLC Communication] Z-TIO PLC Communication Quick … · 2010-07-22 · (800) 576 - 6308 Module Type Controller SRZ T IMS01T12-E1 Thank you for purchasing this RKC product. In

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: [for PLC Communication] Z-TIO PLC Communication Quick … · 2010-07-22 · (800) 576 - 6308 Module Type Controller SRZ T IMS01T12-E1 Thank you for purchasing this RKC product. In

Module Type Controller SRZ

IMS01T12-E1

Thank you for purchasing this RKC product. In order to achieve maximum performance and ensure proper operation of your new instrum ent, carefully read all the instructions in this manual. Please place this manual in a convenient location for easy reference.

1. PLC COMMUNICATION DATA TRANSFER The data transmitted between the PLC and the Z-TIO-C/D module is compiled in the PLC communication data map. In the PLC communi cation data map the communication data is classied into system data, monitor groups, and setting groups.

System data Request item number, Request commands, Setting group communication state, etc.

Monitor group Measured value (PV), Comprehensive event state, etc.

Setting group PID/AT transfer, Set value (SV), etc.

PLC

PLC register

Z-TIO-C/D module 1

Z-TIO-C/D module 2

For the communication data, see 2. PLC COMMUNICATION DATA MAP .

1.1 Data Transfer Type Data transfer between PLC and Z-TIO-C/D m odule are executed by the request item number and the request command.

Request item number This command sets the communication data of th e setting group that is transferred. Set transfer of all communication data of t he setting group, or transfer by one data item. Data transfer are executed by request command.

Setting range: 0 or 1 to 64 (Item number) • When set to 0, all communication dat a of the setting group is transferred. • When set to a number from 1 to 64 (item number), only the set communication

data item is transferred (t ransfer by one data item).

For the item number 1 to 64, see “ Table 2: Setting item selection (Communication data of setting group) ” of Z-TIO PLC Communication Quick Instruction Manual [PART1: Preparation] (IMS01T11-E ).

Note that communication data that is not selected (set to binary: 0) in setting item selection of the PLC communication environment is not transferred.

Request command

For the request command, both “setting request bi t” and “monitor request bit” are available.

• Setting request bit (PLC → Z-TIO-C/D module) This command requests that the Z-TIO- C/D module read the communication data of the setting group on the PLC side. [Processing] (1) Just when “1 (decimal numbers: 1)” is se t to the setting request bit, the Z-TIO-C/D

module starts reading the data from the PLC side. (2) The setting group communication data set in “Request item number” is transferred

from the PCL to the Z-TIO-C/D module. (3) After data transmission is complet ed, the setting request bit becomes “0.”

• Monitor request bit (PLC ← Z-TIO-C/D module)

This command requests that the Z-TIO-C/D module write the communication data of the setting group on the PLC side.

[Processing] (1) Just when “1 (decimal numbers: 2)” is set to the monitor request bit, the Z-TIO-C/D

starts writing the dat a to the PLC side. (2) The setting group communication data set in “request item number” is transferred

from the Z-TIO-C/D module to the PLC. (3) After data transmission is completed, the monitor request bit becomes “0.”

When setting both the setting request bit and the monitor request bit to “1,” set the bits simultaneously. If se t separately, the bit set later may be disregarded.

Monitor group The monitor group communication data is always transferred as monitor item data between the PLC and the Z-TIO-C/D module rega rdless of the request command setting.

1.2 Data Transfer Procedures Change each set value of Z-TIO-C/D m odule from the PLC after the initial settings are made. If each set value of Z-TIO-C/D module is changed from the PLC without setting the initial values, it is re-written to “0” with each set value of the PLC at that time set to “0.”

Initial setting

Data setting When the setting group communication data is transferred from PLC to the Z-TIO-C/D module.

Data processing precautions The data type is treated as binary data with a sign and without a decimal point. For this reason, carefully express and set the data. (Excluding the bit data)

2. PLC COMMUNICATION DATA MAP The data that can be communicated by the PL C and Z-TIO-C/D module is compiled in the PLC communication data map. The data map indi cated in this manual is the data map of factory set value. The data map ca n be changed using the PLC communication environment items below.

• Register type • Setting item register bias • Register start number (High-order 4-bit) • Monitor item selection • Register start number(Low-order 16-bit) • Setting item selection • Monitor item register bias • Slave register bias

For the PLC communication environment item, see Z-TIO PLC Communication Quick Instruction Manual [PAR T1: Preparation] (IMS01T11-E ).

For communication data not described in this manual, see the SRZ Instruction Manual [PLC Communication] (IMS01T13-E ).

2.1 Explanation of Data Map Items Name: Name of communication data

Register address: A register address of communication data in PLC communication (MITSUBISHI MELSEC series)

Structure: C: Data for each channel M: Data for each module

Attribute: RO: Read only data (PLC ← Z-TIO-C/D module) R/W: Read and Write data (PLC ↔ Z-TIO-C/D module)

Data range and Number of data: Data range: Read or write range of communication data Number of data: This is the maximum number per communication data that can be handl ed by one Z-TIO-C/D module. (Numerical value in the [ ] at the lower right) The total number of communication data is 150 items.

Factory set value: Factory set value of communication data

2.2 Data Map The data map register address is the addre ss when the following items are used at their factory set values.

Register start number (Low-order 16-bit): 1000 )retsiger D( 0 :epyt retsigeR

Monitor item register bias: 10 Setting item register bias: 0 Monitor item selection: 33535 Setting item selection: ch1: 62427

38551 :2hc 215 :3hc 215 :4hc

Z-TIO-C/D module 1 Z-TIO-C/D module 2 System data: D01000 to D01009 System data: D01150 to D01159 Monitor group: D01010 to D01049 Monitor group: D01160 to D01199 Setting group: D01050 to D01149 Setting group: D01200 to D01299 Data map of Z-TIO-C/D module 1

Name Register address

Structure AttributeData range and Number of data

Factory set value

System communication state

D01000 M RO Bit data b0: Data collection condition b1 to b15: Unused

Data 0: Before data collection is

completed 1: Data collection is completed

[Decimal number: 0, 1] ]1[

Z-TIO normal communication ag

D01001 M RO 0/1 transfer (For communication checking) “0” and “1” are repeated for each communication period.

]1[

D01002 RO Internal processing Do not use the register address

]1[

D01003 RO Internal processing Do not use the register address

]1[

PLC communication error code

D01004 M RO Bit data b0: PLC register read/write errorb1: Slave communication timeoutb2: Unused b3: Unused b4: Master communication

timeout b5 to b15: Unused

Data 0: OFF 1: ON [Decimal number: 0 to 31]

[1]

Z-TIO module recognition ag

D01005 M RO Bit data b0: Z-TIO module 1 b1: Z-TIO module 2 b2: Z-TIO module 3 b3: Z-TIO module 4 b4: Z-TIO module 5 b5: Z-TIO module 6 b6: Z-TIO module 7 b7: Z-TIO module 8 b8: Z-TIO module 9 b9: Z-TIO module 10 b10: Z-TIO module 11 b11: Z-TIO module 12 b12: Z-TIO module 13 b13: Z-TIO module 14 b14: Z-TIO module 15 b15: Z-TIO module 16

Data 0: No module exists 1: Module exists [Decimal number: 0 to 65535]

[1]

D01006 Internal processing Do not use the register address

]1[

Request item number D01007 M R/W 0 or 1 to 64

0: Transfer all communication data of the setting group. *

1 to 64: Transfer only the communication data of the selected item number. *

]1[

0

Request command D01008 M R/W Bit data b0: Setting request bit b1: Monitor request bit

Data 0: OFF 1: ON [Decimal number: 0 to 3]

]1[

0

Setting group communication state

D01009 M RO Bit data b0: Setting error bit b1: Setting completed bit b2: Monitor completed bit

Data 0: OFF 1: ON [Decimal number: 0 to 7]

]1[

* Note that communication data that is not selected (set to binary: 0) in setting item selection of the PLC communication environment is not transferred.

0000000000000000

bit 15 bit 0

Request command:

bit 1: Monitor request bit bit 0: Setting request bit

Turn on the power of the Z-TIO-C/D module, and the PLC.When the PLC communication start time (factory setting: 5 seconds) elapses, writing of the system data begins.

When the monitor request bit (bit 1) of request commandof the PLC register is set to “1 (Decimal: 2),” th eZ-TIO-C/D module begins writing the setting group to th ePLC.

During data write: Treat the data of all items as inconsistent during the data write.

If the monitor request bit (bit 1) of the request commandof the PLC register is “0,” this indicates that writing of dat ato the PLC is nished.

After the system data is written, the Z-TIO-C/D modul ebegins writing the communication data of the monito rgroup to the PLC. When monitor group writing starts,“system communication state” changes to “1.” When the system communication condition becomes “1, ”PLC communication can be performed.

Because all communication data of the setting group i swritten to the PLC, the request item number of the PL Cregister is set to “0.”

When writing is nished, the Z-TIO-C/D module writes th ecommunication state of the setting group to the monito rcompleted bit (bit 2) of the setting group communicationstate of the PLC.

System communication state = 1?

YES

NO

Start

Turn on power of each instrument

Set “1 (Decimal: 2)” to the monitor request bit (bit 1).

Monitor request bit (bit 1) = 0?

YES

NO

End

Set “0” to the request item number.

Monitor completed bit (bit 2) of the setting group communication state = 1 (Decimal: 4)

Setting request bit(bit 0) = 0?

If the setting request bit (bit 0) of the request command o fthe PLC register is “0,” this indicates that reading of datafrom the PLC is nished.

NO

YES

When the monitor request bit (bit 1) of request commandof the PLC register is set to “1 (Decimal: 2),” th eZ-TIO-C/D module begins writing the setting group to th ePLC.

If the monitor request bit (bit 1) of the request commandof the PLC register is “0,” this indicates that writing o fdata to the PLC is nished.

NO

YES

End

Set “1 (Decimal: 2)” to the monitor request bit (bit 1).

A

Set “0” to the request item number.

[Conrmation of setting data] The request item number of the PLC register is set to “0” fo rverication of the data read from the PCL by the Z-TIO-C/Dmodule.

During data write: Treat the data of all items as inconsistent during the data write.

Monitor completed bit (bit 2) of the setting group communication state = 1 (Decimal: 4)

When writing is nished, the Z-TIO-C/D module write sthe communication state of the setting group to th emonitor completed bit (bit 2) of the setting grou pcommunication state of the PLC.

Monitor request bit(bit 1) = 0?

0000000000000011

bit 15 bit 0

Request command:

bit 1: Monitor request bit bit 0: Setting request bit

(Decimal numbers: 3)

Set the setting group communication data values in the register (memory) on the PLC side.

Set “1” to the setting request bit (bit 0).

When the setting request bit (bit 0) of request commandof the PLC register is set to “1,” the Z-TIO-C/D modul ebegins reading the data set in the PLC register (memory).

During data read: Treat the data of all items as inconsistent during the data read.

Start

A

Set “0” to the request item number.

[Data setting] Set “0” to the request item number of PLC register.

Setting completed bit (bit 1) of the setting group communication state = 1 (Decimal: 2)

When reading of the data ends, the Z-TIO-C/D modul ewrites the setting group communication state to th esetting completed bit (bit 1) of PLC setting grou pcommunication state.

All Rights Reserved, Copyright 2006, RKC INSTRUMENT INC.

Z-TIO PLC Communication Quick Instruction Manual [PART2: Operation]

Temperature Control Module [for PLC Communication]

(800) 576 - 6308www.rkc-usa.comDistributed By Inc,

RKC

Page 2: [for PLC Communication] Z-TIO PLC Communication Quick … · 2010-07-22 · (800) 576 - 6308 Module Type Controller SRZ T IMS01T12-E1 Thank you for purchasing this RKC product. In

® RKC INSTRUMENT INC.

The first edition: SEP. 2006 [IMQ00]

HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 JAPAN PHONE: 03-3751-9799 (+81 3 3751 9799) E-mail: [email protected] FAX: 03-3751-8585 (+81 3 3751 8585) SEP. 2006

Modbus is a registered trademark of Schneider Electric.The name of each programmable controller (PLC) means the products of each manufacturer. Company names and product names used in this manual are the trademarks or registeredtrademarks of the respective companies.

Name Register

address Structure Attribute Data range and Number of data

Factory set value

Measured value (PV) D01010 to D01013

C RO Input scale low to Input scale high [4]

Comprehensive event state

D01014 to D01017

C RO Bit data b0: Event 1 state b1: Event 2 state b2: Event 3 state b3: Event 4 state b4: Heater break alarm state b5: Temperature rise completion b6: Burnout b7 to b15: Unused

Data 0: OFF 1: ON [Decimal number: 0 to 127] [4]

Operation mode state monitor

D01018 to D01021

C RO Bit data b0: 1: Control STOP b1: 1: Control RUN b2: 1: Manual mode (Including Remote mode and Manual mode) b3: 1: Remote mode b4 to b15: Unused

Data 0: OFF 1: ON [Decimal number: 0 to 15] [4]

Error code * D01022 to D01025

M RO 1: Adjustment data error 2: Data back-up error 4: A/D conversion error 32: Logic output data error [4]

Manipulated output value (MV) monitor [heat-side] ♣

D01026 to D01029

C RO PID control or heat/cool PID control: −5.0 to +105.0 %

Position proportioning control with feedback resistance (FBR) input: 0.0 to 100.0 % [4]

Manipulated output value (MV) monitor [cool-side] ♣

D01030 to D01033

C RO −5.0 to +105.0 %

[4]

Current transformer (CT) input value monitor

D01034 to D01037

C RO CTL-6-P-N: 0.0 to 30.0A CTL-12-S56-10L-N: 0.0 to 100.0 A

[4]

Set value (SV) monitor

D01038 to D01041

C RO Setting limiter (low) to Setting limiter (high) [4]

Output state monitor * D01042 to D01045

M RO Bit data b0: OUT1 b1: OUT2 b2: OUT3 b3: OUT4 b4~b15: Unused

Data 0: OFF 1: ON [Decimal number: 0 to 15] [4]

Memory area number monitor

D01046 to D01049

C RO 1 to 8 [4]

PID/AT transfer D01050 to D01053

C R/W 0: PID control 1: Autotuning (AT)

[4]

0

Auto/Manual transfer D01054 to D01057

C R/W 0: Auto mode 1: Manual mode [4]

0

RUN/STOP transfer * D01058 to D01061

M R/W 0: STOP (Control stop) 1: RUN (Control start) [4]

0

Memory area transfer

D01062 to D01065

C R/W 1 to 8 [4]

1

Event 1 set value (EV1)

D01066 to D01069

C R/W Deviation action, Deviation action between channels, Temperature rise completion range 1:

50

Event 2 set value (EV2)

D01070 to D01073

C R/W −Input span to +Input span Process action, SV action: Input scale low to

50

Event 3 set value (EV3)

D01074 to D01077

C R/W Input scale high MV action: −5.0 to +105.0 %

50

Event 4 set value (EV4)

D01078 to D01081

C R/W 1 When temperature rise completion is selected at Event 3 action type.

[Each 4]

50

Set value (SV)

D01082 to D01085

C R/W Setting limiter (low) to Setting limiter (high) [4]

TC/RTD: 0 °C [°F]

V/I: 0.0 %

Proportional band [heat-side] ♣

D01086 to D01089

C R/W TC/RTD inputs: 0 (0.0) to Input span (Unit: °C [°F])

Voltage (V)/current (I) inputs: 0.0 to 1000.0 % of Input span

0 (0.0): ON/OFF action [4]

TC/RTD: 30 V/I: 30.0

* Occupies four PLC registers, however, the actual number of data items is 1 (data units are modules), and thus only the data of CH1 is effective.

♣ When heat/cool control or position proportioning control is performed, there will be communication data (indicated by ♣ in the name column) for which the 2nd channel and 4th channel will be invalid. [Read is possible (0 is shown), but the result of Write is disregarded.]

Parameters which can be used in multi-memory area function

Name Register

address Structure Attribute Data range and Number of data

Factory set value

Integral time [heat-side] ♣

D01090 to D01093

C R/W PID control or heat/cool PID control:0 to 3600 seconds or 0.0 to 1999.9 seconds (0, 0.0: PD action)

Position proportioning control: 1 to 3600 seconds or 0.1 to 1999.9 seconds

[4]

240

Derivative time [heat-side] ♣

D01094 to D01097

C R/W 0 to 3600 seconds or 0.0 to 1999.9 seconds (0, 0.0: PI action) [4]

60

Control response parameter ♣

D01098 to D01101

C R/W 0: Slow 1: Medium 2: Fast P or PD action: 2 (Fast) fixed

[4]

PID control, Position proportioning control: 0 Heat/cool PID control: 2

Proportional band [cool-side] ♣

D01102 to D01105

C R/W TC/RTD inputs: 1 (0.1) to Input span (Unit: °C [°F])

Voltage (V)/current (I) inputs: 0.1 to 1000.0 % of Input span

[4]

TC/RTD: 30V/I: 30.0

Integral time [cool-side] ♣

D01106 to D01109

C R/W 0 to 3600 seconds or 0.0 to 1999.9 seconds (0, 0.0: PD action) [4]

240

Derivative time [cool-side] ♣

D01110 to D01113

C R/W 0 to 3600 seconds or 0.0 to 1999.9 seconds (0, 0.0: PI action) [4]

60

Overlap/Deadband ♣

D01114 to D01117

C R/W TC/RTD inputs: −Input span to +Input span (Unit:°C [°F])

Voltage (V)/current (I) inputs: −100.0 to +100.0 % of Input span

[4]

0

Setting change rate limiter (up)

D01118 to D01121

C R/W 0 (0.0) to Input span/unit time 0 (0.0): Unused

0 (0.0)

Setting change rate limiter (down)

D01122 to D01125

C R/W Unit time: 60 seconds (factory set value)

[4]

0 (0.0)

Heater break alarm (HBA) set value

D01126 to D01129

C R/W When CT is CTL-6-P-N: 0.0 to 30.0 A (0.0: Not used) When CT is CTL-12-S56-10L-N: 0.0 to 100.0 A (0.0: Not used)

[4]

0.0

Heater break determination point

D01130 to D01133

C R/W 0.0 to 100.0 % of HBA set value (0.0: Heater break determination is invalid)

[4]

30.0

Heater melting determination point

D01134 to D01137

C R/W 0.0 to 100.0 % of HBA set value (0.0: Heater melting determination is invalid)

[4]

30.0

PV bias D01138 to D01141

C R/W −Input span to +Input span [4]

0

Manual manipulated output value ♣

D01142 to D01145

C R/W PID control: Output limiter (low) to

Output limiter (high) Heat/cool PID control: −Cool-side output limiter (high) to

+Heat-side output limiter (high)Position proportioning control (with FBR input): Output limiter (low) to

Output limiter (high) Position proportioning control (without FBR input): 0: Close-side output OFF,

Open-side output OFF 1: Close-side output ON,

Open-side output OFF 2: Close-side output OFF,

Open-side output ON [4]

0.0

Operation mode D01146 to D01149

C R/W 0: Unused 1: Monitor 2: Monitor + Event function 3: Control [4]

3

* Occupies four PLC registers, however, the actual number of data items is 1 (data units are modules), and thus only the data of CH1 is effective.

♣ When heat/cool control or position proportioning control is performed, there will be communication data (indicated by ♣ in the name column) for which the 2nd channel and 4th channel will be invalid. [Read is possible (0 is shown), but the result of Write is disregarded.]

Parameters which can be used in multi-memory area function

Data map of Z-TIO-C/D module 2

Name Registeraddress Structure Attribute Data range and

Number of data Factory

set value System communication state

D01150 M RO Same as Z-TIO-C/D module 1

Z-TIO normal communication flag

D01151 M RO Same as Z-TIO-C/D module 1

D01152 RO Same as Z-TIO-C/D module 1 D01153 RO Same as Z-TIO-C/D module 1

PLC communicationerror code

D01154 M RO Same as Z-TIO-C/D module 1

Z-TIO module recognition flag

D01155 M RO Same as Z-TIO-C/D module 1

D01156 Same as Z-TIO-C/D module 1 Request item number D01157 M R/W Same as Z-TIO-C/D module 1 0 Request command D01158 M R/W Same as Z-TIO-C/D module 1 0 Setting group communication state

D01159 M RO Same as Z-TIO-C/D module 1

Measured value (PV) D01160 toD01163

C RO Same as Z-TIO-C/D module 1

Comprehensive event state

D01164 toD01167

C RO Same as Z-TIO-C/D module 1

Operation mode state monitor

D01168 toD01171

C RO Same as Z-TIO-C/D module 1

Error code D01172 toD01175

M RO Same as Z-TIO-C/D module 1

Manipulated output value (MV) monitor [heat-side]

D01176 toD01179

C RO Same as Z-TIO-C/D module 1

Manipulated output value (MV) monitor [cool-side]

D01180 toD01183

C RO Same as Z-TIO-C/D module 1

Current transformer (CT) input value monitor

D01184 toD01187

C RO Same as Z-TIO-C/D module 1

Set value (SV) monitor

D01188 toD01191

C RO Same as Z-TIO-C/D module 1

Output state monitor D01192 toD01195

M RO Same as Z-TIO-C/D module 1

Memory area number monitor

D01196 toD01199

C RO Same as Z-TIO-C/D module 1

PID/AT transfer D01200 toD01203

C R/W Same as Z-TIO-C/D module 1 0

Auto/Manual transfer D01204 toD01207

C R/W Same as Z-TIO-C/D module 1 0

RUN/STOP transfer D01208 toD01211

M R/W Same as Z-TIO-C/D module 1 0

Memory area transfer

D01212 toD01215

C R/W Same as Z-TIO-C/D module 1 1

Event 1 set value (EV1)

D01216 toD01219

C R/W Same as Z-TIO-C/D module 1 50

Event 2 set value (EV2)

D01220 toD01223

C R/W Same as Z-TIO-C/D module 1 50

Event 3 set value (EV3)

D01224 toD01227

C R/W Same as Z-TIO-C/D module 1 50

Event 4 set value (EV4)

D01228 toD01231

C R/W Same as Z-TIO-C/D module 1 50

Set value (SV) D01232 toD01235

C R/W Same as Z-TIO-C/D module 1 TC/RTD: 0 °C [°F]

V/I: 0.0 % Proportional band [heat-side]

D01236 toD01239

C R/W Same as Z-TIO-C/D module 1 TC/RTD: 30 V/I: 30.0

Integral time [heat-side]

D01240 toD01243

C R/W Same as Z-TIO-C/D module 1 240

Derivative time [heat-side]

D01244 toD01247

C R/W Same as Z-TIO-C/D module 1 60

Control response parameter

D01248 toD01251

C R/W Same as Z-TIO-C/D module 1 PID control, Position proportioning control: 0 Heat/cool PID control: 2

Proportional band [cool-side]

D01252 toD01255

C R/W Same as Z-TIO-C/D module 1 TC/RTD: 30 V/I: 30.0

Integral time [cool-side]

D01256 toD01259

C R/W Same as Z-TIO-C/D module 1 240

Derivative time [cool-side]

D01260 toD01263

C R/W Same as Z-TIO-C/D module 1 60

Overlap/Deadband

D01264 toD01267

C R/W Same as Z-TIO-C/D module 1 0

Setting change rate limiter (up)

D01268 toD01271

C R/W Same as Z-TIO-C/D module 1 0 (0.0)

Setting change rate limiter (down)

D01272 toD01275

C R/W Same as Z-TIO-C/D module 1 0 (0.0)

Heater break alarm (HBA) set value

D01276 toD01279

C R/W Same as Z-TIO-C/D module 1 0.0

Heater break determination point

D01280 toD01283

C R/W Same as Z-TIO-C/D module 1 30.0

Heater melting determination point

D01284 toD01287

C R/W Same as Z-TIO-C/D module 1 30.0

PV bias D01288 toD01291

C R/W Same as Z-TIO-C/D module 1 0

Manual manipulated output value

D01292 toD01295

C R/W Same as Z-TIO-C/D module 1 0.0

Operation mode D01296 toD01299

C R/W Same as Z-TIO-C/D module 1 3

3. COMMUNICATION SPECIFICATIONS PLC communication

Interface: Base on RS-485, EIA standard Protocol: MITSUBISHI MELSEC series special protocol (type 4)

− A compatible, 1C frame, ACPU common command (WR/WW) (A series, FX2N/FX2NC series or FX3U/FX3UC series)

− A compatible, 1C frame, AnA/AnUCPU common command (QR/QW) D register, R register, W register

QnA compatible, 3C frame, command (0401/1401) Only ZR register

(AnA/AnU/QnA series, Q series) Synchronous method: Start/stop synchronous type Communication speed: 4800 bps, 9600 bps, 19200 bps, 38400 bps Data bit configuration: Start bit: 1

Data bit: 7 or 8 Parity bit: Without, Odd or Even Stop bit: 1

Maximum connections: 16 Z-TIO-C/D modules per communication port of PLC The maximum number of SRZ modules (including other function modules) on the same communication line is 31.

Usable PLC type: MITSUBISHI MELSEC series − Computer link unit

AJ71UC24、A1SJ71UC24-R4、A1SJ71C24-R4, etc. The unit which AnA/AnUCPU common command (type 4) can use.

− Serial communication unit AJ71QC24N, A1SJ71QC24N, QJ71C24, etc. The unit which AnA/AnUCPU common command (type 4) can use.

− Adapter FX0N-485ADP, FX2NC-485ADP, FX3U-485ADP

− Expanded function board FX2N-485BD, FX3U-485-BD

Interval time: 0 to 250 ms Host communication

Interface: Base on RS-485, EIA standard Protocol: RKC communication (Based on ANSI X3.28 subcategory 2.5 B1)

Modbus-RTU Connection method: 2-wire system, half-duplex multi-drop connection Synchronous method: Start/stop synchronous type Communication speed: 4800 bps, 9600 bps, 19200 bps, 38400 bps Data bit configuration: Start bit: 1

Data bit: RKC communication: 7 or 8 Modbus: 8 Parity bit: RKC communication: Without or 1 (Odd or Even) Modbus: Without Stop bit: 1

Protocol: RKC communication (Based on ANSI X3.28 subcategory 2.5 B1) Modbus-RTU (Selectable)

Error control: RKC communication: Vertical parity, Horizontal parity Modbus: CRC-16

Termination resistor: Externally terminal connected (example: 120 Ω 1/2W) Interval time: 0 to 250 ms Maximum connections: Up to 16 Z-TIO-C/D modules The maximum number of SRZ modules (including other function

modules) on the same communication line is 31. Loader communication

Interface: Connection with a loader communication cable for our USB converter COM-K (sold separately).

Synchronous method: Start/stop synchronous type Communication speed: 38400 bps Data bit configuration: Start bit: 1

Data bit: 8 Parity bit: Without Stop bit: 1 Data bit configuration is fixed to the above value. Module address is fixed at 0.

Protocol: ANSI X3.28 subcategory 2.5, B1 Maximum connections: 1 point