Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
Installation and serviceinstructionsfor contractors
VIESMANN
Vitodens 050-WType BPJC, 6.5 to 35.0 kWWall mounted gas condensing boilerFor natural gas and LPG Gas Council no.: 47 819 31, 47 819 32
For applicability, see the last page
VITODENS 050-W
5513 085 GB 9/2014 Please keep safe.
2
Please follow these safety instructions closely to prevent accidents and mate-rial losses.
Safety instructions explained
DangerThis symbol warns against therisk of injury.
! Please noteThis symbol warns against therisk of material losses and envi-ronmental pollution.
NoteDetails identified by the word "Note" con-tain additional information.
Target group
These instructions are exclusively inten-ded for qualified contractors.■ Work on gas installations must only be
carried out by a registered gas fitter.■ Work on electrical equipment must
only be carried out by a qualified elec-trician.
■ The system must be commissioned bythe system installer or a qualified per-son authorised by the installer.
Regulations
Observe the following when working onthis system: ■ Statutory regulations regarding the
prevention of accidents■ Statutory regulations regarding envi-
ronmental protection
■ The Code of Practice of relevant tradeassociations
■ All current safety regulations asdefined by DIN, EN, DVGW, TRGI,TRF, VDE and all locally applicablestandards,Gas Safety (Installation & Use) Regu-lations the appropriate Building Regu-lationeither the Building regulations,theBuilding Regulation (Scotland),Building Regulations (Northern Ire-land), the Water Fittings Regulation orWater Bylaws in Scotland, the currentI.E.E. Wiring Regulations.
If you smell gas
DangerEscaping gas can lead to explo-sions which may result in seriousinjury.■ Do not smoke. Prevent naked
flames and sparks. Do notswitch lights or electrical appli-ances on or off.
■ Close the gas shut-off valve.■ Open windows and doors.■ Evacuate any people from the
danger zone.■ Notify your gas or electricity
supplier and your local heatingcontractor from outside thebuilding.
■ Shut off the electricity supply tothe building from a safe place(outside the building).
Safety instructions
Safety instructions
5513
085
GB
3
If you smell flue gas
DangerFlue gas can lead to life threat-ening poisoning.■ Shut down the heating system.■ Ventilate the installation site.■ Close all doors in the living
space.
Flue systems and combustion air
Ensure that flue systems are clear andcannot be sealed, for instance due toaccumulation of condensate or othercauses. Ensure a sufficient supply ofcombustion air.Instruct system users that subsequentmodifications to the building characteris-tics are not permissible (e.g. cable/pipe-work routing, cladding or partitions).
DangerLeaking or blocked flue systems,or an insufficient supply of com-bustion air can cause life threat-ening poisoning from carbonmonoxide in the flue gas.Ensure the flue system is inproper working order. Aperturesfor supplying combustion airmust be non-closable.
Extractors
Operating appliances that extract air tothe outside (cooker hoods, extractors, airconditioning units, etc.) can create neg-ative pressure. If the boiler is operated atthe same time, this can lead to reverseflow of the flue gas.
DangerThe simultaneous operation ofthe boiler and appliances thatextract air to the outside canresult in life threatening poison-ing due to reverse flow of the fluegas.Fit an interlock circuit or take suit-able steps to ensure a sufficientsupply of combustion air.
Working on the system
■ Where gas is used as the fuel, closethe main gas shut-off valve and safe-guard it against unintentional reopen-ing.
■ Isolate the system from the power sup-ply (e.g. by removing the separate fuseor by means of a mains isolator) andcheck that it is no longer 'live'.
■ Safeguard the system against recon-nection.
DangerHot surfaces can cause burns.■ Before maintenance or service
work, switch OFF the appli-ance and let it cool down.
■ Never touch hot surfaces onthe boiler, burner, flue systemor pipework.
! Please noteElectronic assemblies can bedamaged by electrostatic dis-charge.Before beginning work, touchearthed objects, such as heatingor water pipes, to discharge staticloads.
Safety instructions
Safety instructions (cont.)55
13 0
85 G
B
4
Repair work
! Please noteRepairing components that fulfil asafety function can compromisethe safe operation of the sys-tem.Faulty components must bereplaced with original Viessmannspare parts.
Auxiliary components, spare andwearing parts
! Please noteSpare and wearing parts thathave not been tested togetherwith the system can compromiseits function. Installing non-author-ised components and makingnon-approved modifications orconversions can compromisesafety and may invalidate thewarranty.For replacements, use only orig-inal spare parts supplied orapproved by Viessmann.
Safety instructions
Safety instructions (cont.)
5513
085
GB
5
Installation instructionsPreparing for installation................................................................................... 7
Installation sequenceMounting the boiler and making the connections................................................. 13Opening the programming unit............................................................................. 18Electrical connections........................................................................................... 19
Service instructionsCommissioning, inspection, maintenanceSteps - commissioning, inspection and maintenance.......................................... 22Further details regarding the individual steps....................................................... 23
TroubleshootingFunction sequence and possible faults................................................................ 45Fault display......................................................................................................... 46Repairs................................................................................................................. 50
Gas type conversionConverting from LPG to natural gas..................................................................... 60
Control unitFunctions and operating conditions in weather-compensated mode................... 62
DesignsConnection and wiring diagrams.......................................................................... 63
Parts listsOrdering parts...................................................................................................... 68Overview of assemblies....................................................................................... 69Casing assembly.................................................................................................. 70Heat cell assembly............................................................................................... 71Burner assembly.................................................................................................. 73Hydraulic assembly.............................................................................................. 75Grundfos hydraulic assembly............................................................................... 77Control unit assembly........................................................................................... 79Miscellaneous....................................................................................................... 80
Specification....................................................................................................... 81
CertificatesDeclaration of conformity...................................................................................... 82
Index
Index55
13 0
85 G
B
6
Keyword index.................................................................................................... 83
Index
Index (cont.)
5513
085
GB
7
Intended use
The appliance is only intended to beinstalled and operated in sealed unven-ted heating systems that comply withEN 12828, with due attention paid to theassociated installation, service andoperating instructions. It is only designedfor the heating of water that is of potablewater quality.
Intended use presupposes that a fixedinstallation in conjunction with permissi-ble, system-specific components hasbeen carried out.
Commercial or industrial usage for a pur-pose other than heating the building orDHW shall be deemed inappropriate.
Any usage beyond this must beapproved by the manufacturer in eachindividual case.
Incorrect usage or operation of the appli-ance (e.g. the appliance being openedby the system user) is prohibited and willresult in an exclusion of liability. Incorrectusage also occurs if the components inthe heating system are modified fromtheir intended use (e.g. if the flue gas andventilation air paths are sealed).
Product information
Vitodens 050-W, type BPJC
Preset for operation with natural gas.Conversion to LPG P requires a gas con-version kit.
Gas Council no.■ 29 kW combi: 47 819 31■ 35 kW combi: 47 819 32
Conversion for other countries
The Vitodens 050-W must only be deliv-ered to the countries specified on thetype plate. For deliveries to alternativecountries, an approved contractor mustarrange individual approval on his/herown initiative and in accordance with thelaw of the country in question.
Product description
The Vitodens 050-W is available as agas condensing combi boiler with inte-gral plate heat exchanger for DHW heat-ing. For the connection of heating circuitsand DHW line, see page 12 onwards.The Vitodens 050-W is set up for opera-tion with a constant boiler water temper-ature.The appliance is equipped with a sealedunvented hydraulic system with 2 con-nections for heating flow and return and2 connections for DHW heating.
The following components are integra-ted into the hydraulic system:■ Circulation pump■ 3-way diverter valve
Preparing for installation
Preparing for installation55
13 0
85 G
B
Inst
alla
tion
8
■ Safety valve■ Diaphragm expansion vessel■ Plate heat exchanger for DHW heating
Connecting accessories
A time switch (accessories) can be con-nected to the control unit with a low volt-age supply.
Siting
Suitable siting locations include:■ Recreational rooms and other living
spaces■ Ancillary rooms without own ventila-
tion
■ Cupboards (open at the top)■ Recesses without compulsory clear-
ance towards combustible materials■ Attic rooms (pitched attics and long
panes) where the balanced flue can berouted directly through the roof
Since the flue pipe connection for room-sealed operation is surrounded by com-bustion air (coaxial pipe), no clearancestowards combustible materials need bemaintained. For further details, see thetechnical guide "Flue systems for theVitodens".The installation area must be safe fromthe risk of frost.
Operation of the Vitodens 050-W in wet rooms
Area 0
Area 1Are
a
2
Area 2
600
2250
The Vitodens is approved for installationin wet rooms (e.g. bathroom or showerrooms) (protection IP X4 D, splash-proof).
When installing the Vitodens in wetareas, observe the safety zones andminimum wall clearances according toVDE 0100 [or local regulations] (see also"Electrical safety zone"). The Vitodensmay be installed in area 1 if hosed water(e.g. from massage showers) is preven-ted.
Preparing for installation
Preparing for installation (cont.)
5513
085
GB
9
Electrical equipment in rooms containinga bathtub or a shower must be installedin such a way that users cannot beexposed to dangerous body currents.
VDE 0100 specifies that cables supply-ing permanently installed consumers inzones 1 and 2 should only be run verti-cally and routed into the equipment fromthe back.
Preparing for boiler installation
Dimensions and connections
41
5
250
400
58 58123123
BA C E
F
D
156350
125
867
6870
715
064
2
F
700
Shown without fittings
A Heating flow 7 22 mmB DHW 7 15 mmC Gas connection 7 22 mmD Cold water 7 15 mm
E Heating return 7 22 mmF Condensate drain / safety valve
drain: Plastic hose 7 22 mm
Preparing for installation
Preparing for installation (cont.)55
13 0
85 G
B
Inst
alla
tion
10
Minimum clearances
Maintain a clearance of 700 mm in frontof the Vitodens for maintenance purpo-ses. Maintenance clearances to the l.h.or r.h. side of the Vitodens are notrequired.
Preparing for installation
Preparing for installation (cont.)
5513
085
GB
11
Fitting the wall mounting bracket
250
A
Ø10 145
A Vitodens installation template
Preparing for installation
Preparing for installation (cont.)55
13 0
85 G
B
Inst
alla
tion
12
1. Position the supplied installation tem-plate on the wall.
2. Mark out the rawl plug holes.
3. Drill 7 10 mm holes for the rawl plugsand insert the rawl plugs supplied.
4. Fit wall mounting bracket with screwssupplied.
Fitting the pre-plumbing jig or mount-ing frame
Pre-plumbing jig or mountingframe installation instructions
Preparing the connections
! Please noteTo prevent appliance damage,connect all pipework free of loadand torque stress.
1. Prepare the water connections. Flushthe heating system.
2. Prepare the gas connection.
3. Prepare the electrical connections.■ The appliance is delivered fitted
with a 1.5 m long power cable:NYM-J 3 x 1.5 mm2
■ Accessory cables:NYM-O 2-core min. 0.5 mm2 or 2-core cable for LV
Installation in a cupboard
Any cupboard enclosing the appliancemust be designed and constructed spe-cifically for this purpose. An existing cup-board or closet may be used, provided itis modified accordingly. BS 7698:2000gives details of the essential design fea-tures for cupboards and closets, includ-ing airing cupboards. The Vitodensrange does not require the cupboard tobe ventilated.
Preparing for installation
Preparing for installation (cont.)
5513
085
GB
13
Removing the front panel and mounting the boiler
2x
2.
1.
3.
1. Undo the screws at the bottom of theboiler; do not remove completely.
2. Remove front panel.
3. Hook the boiler onto the wall mount-ing bracket.
Installation sequence
Mounting the boiler and making the connections55
13 0
85 G
B
Inst
alla
tion
14
Making the connections on the water side
A
¨
z z
B C D
A Heating flow G ¾B DHW G ½
C Cold water G ½D Heating return G ¾
1. Mount fittings with gaskets. 2. Install filling equipment on site. The filling equipment must meet theFittings Directive G24.2a.
Installation sequence
Mounting the boiler and making the connections (cont.)
5513
085
GB
15
Gas connection
A
¨
z z1. Fit the the gas shut-off valve with
bend to connection A.
2. Connect the gas supply to connectionA.
3. Carry out a tightness test.
NoteOnly use suitable and approved leakdetection agents (EN 14291) anddevices for the tightness test. Leakdetection agents with unsuitable con-stituents (e.g. nitrides, sulphides) cancause material damage.Remove leak detection agent resi-dues after testing.
Installation sequence
Mounting the boiler and making the connections (cont.)55
13 0
85 G
B
Inst
alla
tion
16
! Please noteExcessive test pressure willdamage the boiler and the gastrain. Max. test pressure 150 mbar(15 kPa). If a higher pressureis required for tightness tests,disconnect the boiler and thegas train from the main supplypipe (undo the fitting).
4. Purge the gas line.
Connecting the safety valve and condensate drain
A
■ The condensate pipe is connected tothe discharge pipe of the safety valve.The supplied condensate hose meetsthe temperature requirements forCE certification.
■ We recommend connecting the con-densate pipe to the internal domesticwaste water system, either directly orvia a tundish.
■ If the condensate pipe is routed out-side the building, use a pipe with min.7 30 mm and protect it from frost.Avoid long external pipe runs. Install atundish.
! Please noteA frozen condensate pipe canresult in faults and damage tothe boiler.Always protect condensatepipes against frost.
■ Observe local building regulations.Connect condensate pipe A to the pub-lic sewage system with a constant falland a pipe vent.Observe the local waste water regula-tions.
NoteFill the siphon with water before com-missioning.
Installation sequence
Mounting the boiler and making the connections (cont.)
5513
085
GB
17
Filling the siphon with water
Pour at least 0.3 l of water into the flueoutlet.
! Please noteDuring commissioning, flue gasmay escape from the condensatedrain.Always fill the siphon with waterbefore commissioning.
Balanced flue connection
Connect the balanced flue.During installation and positioning of theflue system, observe Part J of buildingregulations and BS 5440.
Flue system installation instruc-tions
Connecting several Vitodens 050-Wto a shared flue system
Adjust the burner setting of each con-nected boiler to match the flue system.See page 29.
Do not carry out commissioning untilthe following conditions are met:■ Free passage through the flue gas
pipes.■ Flue system with positive pressure is
gas-tight.
■ Apertures for ensuring sufficient com-bustion air supply are open and cannotbe closed off.
■ Applicable regulations on installingand commissioning flue systems havebeen followed.
Installation sequence
Mounting the boiler and making the connections (cont.)55
13 0
85 G
B
Inst
alla
tion
18
DangerLeaking or blocked flue systemsor an insufficient supply of com-bustion air cause life threateningpoisoning due to carbon monox-ide in the flue gas.
Ensure the flue system functionscorrectly. Apertures for combus-tion air supply must not be able tobe closed off.
Opening the programming unit
Only required if a wireless receiver ortime switch (accessories) is to be con-nected.
1.
3.
2. 2x
! Please noteElectronic assemblies can bedamaged by electrostatic dis-charge.Prior to commencing any work,touch earthed objects such asheating or water pipes to dis-charge static loads.
Installation sequence
Mounting the boiler and making the connections (cont.)
5513
085
GB
19
B
C
4 3 2 1A
OT+OT-
A Terminals on underside of appli-ance
B Outside temperature sensorC Vitotrol 100 or on-site room temper-
ature controller with LV switchingcontact and low transition resist-anceRemove jumper when connecting.
Separate installation instruc-tions
Note: the terminal C is not suitablefor 230V room thermostats.
Information on connectingaccessoriesWhen connecting accessoriesobserve the separate installationinstructions provided with them.
Installation sequence
Electrical connections55
13 0
85 G
B
Inst
alla
tion
20
Outside temperature sensor (accessories)
1. Fit outside temperature sensor.
Installation site:■ North or north-westerly wall, 2 to
2.5 m above ground level; in multistorey buildings, in the upper half ofthe 2nd floor
■ Not above windows, doors or vents■ Not immediately below balconies
or gutters■ Never render over■ Connection:
2-core lead, length up to 35 m witha cross-section of 1.5 mm2
2. Connect the outside temperaturesensor across terminals 3 and 4(underside of appliance).
Power supply
Connect the power cable to the buildingmains.
Regulations and Directives
DangerIncorrectly executed electricalinstallations can result in injuriesfrom electrical current and inappliance damage.
Connect the power supply andimplement all safety measures(e.g. RCD circuit) in accordancewith the following regulations:■ IEC 60364-4-41■ VDE regulations■ Connection requirements
specified by your local powersupply utility
Install an isolator in the power cable toprovide omnipolar separation from themains for all active conductors, corre-sponding to overvoltage category III(3 mm) for full isolation. This isolatormust be fitted in the permanent electricalinstallation in line with installationrequirements.Protect the power cable with an external3 A fuse to BS 1362.
DangerIncorrect core allocation canresult in serious injury and dam-age to the appliance.Take care not to interchangewires "L1" and "N".
Installation sequence
Electrical connections (cont.)
5513
085
GB
21
DangerIf system components are notearthed, serious injury from elec-tric current can result if an elec-trical fault occurs.
Connect the appliance and pipe-work to the equipotential bondingof the building in question.
Routing the connecting cables
! Please noteConnecting cables will be dam-aged if they touch hot compo-nents. When routing and securingcables/leads on site, ensure thatthe maximum permissible tem-perature for these cables/leads isnot exceeded.
Installation sequence
Electrical connections (cont.)55
13 0
85 G
B
Inst
alla
tion
22
For further information regarding the individual steps, see the page indicated
Commissioning steps
Inspection steps
Maintenance steps Page
• • • 1. Filling the heating system.............................................. 23• • • 2. Converting to operation with LPG................................ 25• • • 3. Checking the static and supply pressure..................... 25• 4. Reducing the max. heating output................................ 27• 5. Matching the burner output to the flue system........... 28• 6. Burner adjustment when connecting multiple flues to
a flue system................................................................... 29
• 7. Checking the CO2 content............................................. 33• • 8. Burner removal .............................................................. 36• • 9. Checking the burner gasket and burner gauze
assembly......................................................................... 36
• • 10. Checking and adjusting the electrode.......................... 38• • 11. Cleaning the heat exchanger......................................... 39• • 12. Checking the condensate drain and cleaning the
siphon.............................................................................. 40
• • 13. Installing the burner ...................................................... 41• • 14. Checking the diaphragm expansion vessel and
system pressure............................................................. 42
• • • 15. Checking all connections on the heating water sideand DHW side for leaks
• • • 16. Checking firm seating of electrical connections • • • 17. Checking all gas equipment for tightness at operating
pressure .......................................................................... 42
• • 18. Fitting the front panel..................................................... 43• 19. Instructing the system user........................................... 44
Commissioning, inspection, maintenance
Steps - commissioning, inspection and maintenance
5513
085
GB
23
Filling the heating system
! Please noteUnsuitable fill water increasesthe level of deposits and corro-sion and may lead to boiler dam-age.■ Flush the heating system thor-
oughly before filling.■ Only fill with water of potable
quality.
■ Fill water with a hardnessabove 300 ppm must be soft-ened.
■ Antifreeze suitable for heatingsystems can be added to the fillwater.
1. Close the gas shut-off valve.
2. Switch ON the power supply at ON/OFF switch A.
3. Activate the filling function.1. Press MODE and simultane-
ously and hold for approx. 3 s."SERV" is displayed and "0"flashes.
2. Use / to set "I"3. OK to confirm.
The filling function is enabled.
NoteThis function terminates automati-cally after 30 min or when the ON/OFF switch is switched off.
Commissioning, inspection, maintenance
Further details regarding the individual steps55
13 0
85 G
B
Serv
ice
24
B C
A 4. Open shut-off valves B and C.
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)
5513
085
GB
25
5. Fill and vent the heating system usingthe on-site valve. System pressure0.8 to 1.2 bar (0.08 to 0.1 MPa). The system can be filled using a sep-arate filling point fitted at a convenientposition on the heating circuit. Theconnection must be removed whenfilling is complete. Where local WaterAuthority regulation does not allowtemporary connection, a sealed sys-tem filler pump with break tank mustbe used. The heating system will notbe filled automatically from thedomestic hot water side. Alternativemethods for filling sealed systems aregiven in BS 5449.
Converting to operation with LPG
In the delivered condition, the boiler isset up for operation with natural gas. Foroperation with LPG, change the gas noz-zle and switch to the correct gas type inthe control unit.
Separate installation instructions
Conversion from LPG to natural gas, seepage 60.
Checking the static and supply pressure
DangerCO formation as a result of incor-rect burner adjustment can haveserious health implications.Carry out a CO test before andafter work on gas appliances.
Operation with LPGPurge the LPG tank twice during com-missioning or replacement. Vent the tankand gas connection line thoroughly afterpurging.
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)55
13 0
85 G
B
Serv
ice
26
A
Gas train viewed from behind
1. Close the gas shut-off valve.
2. Undo screw A inside test connector"IN" on the gas train, but do notremove it. Connect the pressuregauge.
3. Open the gas shut-off valve.
4. Check the static pressure.Set value: max. 57.5 mbar(5.75 kPa)
5. Start the boiler.
NoteDuring commissioning, the boiler canenter a fault state because of airlocksin the gas line. After approx. 5 s,press Reset to reset the burner (seepage 49).
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)
5513
085
GB
27
6. Check the supply (flow) pressure.
Set value:■ Natural gas: 20 mbar (2.0 kPa)■ LPG: 37 mbar (3.7 kPa)
NoteUse a suitable measuring instrumentwith a resolution of at least 0.1 mbar(0.01 kPa) to check the supply pres-sure.
7. Proceed as indicated in the followingtable.
8. Shut down the boiler, close the gasshut-off valve, remove the pressuregauge and close test nipple A withthe screw.
9. Open the gas shut-off valve and startthe appliance.
DangerGas escaping from the testconnector leads to a risk ofexplosion.Check gas tightness at testconnector A.
Supply pressure (flow pressure) ProcedureFor natural gas For LPGBelow 17.4 mbar(1.74 kPa)
Below 25 mbar(2.5 kPa)
Do not commission the boiler. Notify yourgas supply utility or LPG supplier.
17.4 to 25 mbar(1.74 to 2.5 kPa)
25 to 47 mbar(2.5 to 4.7 kPa)
Start the boiler.
Above 25 mbar(2.5 kPa)
Above 47 mbar(4.7 kPa)
Install a separate gas pressure governorupstream of the system and regulate theflow pressure to 20 mbar (2.0 kPa) fornatural gas or 37 mbar (3.7 kPa) for LPG.Notify your gas supply utility or LPG sup-plier.
Reducing the max. heating output
The maximum heating output can bereduced in 25 % increments according tosystem requirements.
1. Press MODE and simultaneouslyfor 3 s."SERV" is displayed and "I"flashes.
2. Use / to select "2" and confirm withOK."00" flashes on the display (corre-sponds to 100 % burner output).
3. Use / to select the required burneroutput and confirm with OK.
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)55
13 0
85 G
B
Serv
ice
28
4. Press MODE and simultaneouslyfor 3 s.Service mode is terminated. Servicemode also terminates automaticallyafter 30 min.
5. Start the boiler.
6. Check the selected burner output bymeasuring the gas throughput at ahigh heating output.
Matching the burner output to the flue system
To match the burner output to the sys-tem's flue pipe length, a correction factorcan be set.
NoteObserve max. flue pipe lengths in thepricelist. If the max. flue pipe lengths inthe pricelist are exceeded, a calculatedperformance verification is required.
1. Press MODE and simultaneouslyfor 3 s."SERV" is displayed and "I"flashes.
2. Use / to select "3" and confirm withOK."0" flashes on the display.
3. Look up the required correction factorrelevant to the length of the flue in thetables below.
4. Use / to set the required correctionfactor and confirm with OK.
5. Press MODE and simultaneouslyfor 3 s.Service mode is terminated. Servicemode also terminates automaticallyafter 30 min.
Open flue operation 7 60 mmCorrection fac-tor
0 1 2 3 4 5 6
Rated heatingoutput (kW)
Flue length (m)
24 ≤ 8 > 8 ≤15
Do not adjust
33 ≤ 8 > 8 ≤14
> 14 ≤19
> 19 ≤25
Do not adjust
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)
5513
085
GB
29
Room sealed operation 7 60 mm coaxialCorrection fac-tor
0 1 2 3 4 5 6
Rated heatingoutput (kW)
Flue length (m)
24 ≤ 4 > 4 ≤ 8 > 8 ≤12
> 12 ≤15
Do not adjust
33 ≤ 4 > 4 ≤ 7 > 7 ≤11
> 11 ≤20
Do not adjust
Burner adjustment when connecting multiple flues to a flue sys-tem
When connecting several Vitodens 050-W to a shared flue system: Adjust the burner setting of each con-nected boiler by a correction factor tomatch the flue system.
System conditions:■ Shared flue in shaft 7 100 mm■ Balanced flue from boiler to shaft
7 80/125 mm■ Minimum shaft cross-section
– Square 175 x 175 mm– Round 7 195 mm
■ Height between floors min. 2.5 m■ Max. 4 boilers with the same rated
heating output connected to the fluesystem
1. Press MODE and simultaneouslyfor 3 s."SERV" is displayed and "I"flashes.
2. Use / to select "4" and confirm withOK."0" flashes on the display.
3. Look up the required correction factorrelevant to the flue system require-ments in the tables below.
4. Use / to set the required correctionfactor and confirm with OK.
5. Press MODE and simultaneouslyfor 3 s.Service mode is terminated. Servicemode also terminates automaticallyafter 30 min.
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)55
13 0
85 G
B
Serv
ice
30
One boiler per floor
Rated heating output 24 kWNumber of boilers 2 3 4Correction factor (setting value) Flue length a (m)01 ≤ 212 > 21 ≤ 25 ≤ 19 ≤ 133 – > 19 ≤ 25 > 13 ≤ 174 – – > 17 ≤ 215 – – –6 – – –
Rated heating output 33 kWNumber of boilers 2 3 4Correction factor (setting value) Flue length a (m)01 ≤ 122 > 12 ≤ 25 ≤ 173 – ≤ 164 – > 16 ≤ 20 ≤ 145 – > 20 ≤ 25 > 14 ≤ 166 – – > 16 ≤ 18
NoteThe correction factor changes the mod-ulating range of the boiler.
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)
5513
085
GB
31
3 m
a
2.5
m
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)55
13 0
85 G
B
Serv
ice
32
Two boilers per floor
Rated heating output 24 kWNumber of boilers 2 4Correction factor (setting value) Flue length a (m)01 ≤15 ≤52 – > 5 ≤ 93 – > 9 ≤ 144 – > 14 ≤ 155 – –6 – –
Rated heating output 33 kWNumber of boilers 2 4Correction factor (setting value) Flue length a (m)01 ≤ 92 > 9 ≤ 15 ≤ 63 – > 6 ≤ 84 – > 8 ≤ 105 – > 10 ≤ 136 – > 13 ≤ 15
NoteThe correction factor changes the mod-ulating range of the boiler.
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)
5513
085
GB
33
3 m
0.3
m2.
2 m
a
Checking the CO2 content
The Vitodens 050-W is factory-set fornatural gas. During commissioning ormaintenance, the CO2 and CO have tobe measured at the boiler flue adaptortest port to check the flue integrity. Sub-ject to the Wobbe index, the CO2 contentfluctuates between 7.5 % and 10.5 %. ACO level of up to 500 ppm during start-up is acceptable.
We recommend measuring O2 as thevalue is unmistakable regarding lambda(air/gas). The O2-content fluctuatesbetween 7.5 % and 2.2 %. The CO/CO2ratio has to be less than 0.004.If the actual CO2 or O2 and CO valuesdeviate from the stated range, check thebalanced flue systems for leaks. If theflue installation is OK, change the gasvalve.
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)55
13 0
85 G
B
Serv
ice
34
NoteOperate the appliance with uncontami-nated combustion air to prevent operat-ing faults and damage.
A
1. Connect a flue gas analyser at fluegas port A on the boiler flue con-nection.
2. Start the boiler and check for leaks.
DangerEscaping gas leads to a risk ofexplosion.Check all gas equipment fortightness.
3. To check the CO2 content the burneroutput can be set manually.1. Press MODE.2. / until "SERV" is displayed.3. OK to confirm.
"OFF" appears on the display.4. Use / to select the burner output:
Value shown on display
Burner out-put
_ 20 20 %_ _ 40 40 %_ _ _ 60 60 %_ _ _ _ 80 80 %_ _ _ _ _ 00 100 %
5. Confirm your settings with OK.
NoteThis function terminates automati-cally after 30 min, alternatively use / to set the burner output to "OFF"
after checking.
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)
5513
085
GB
35
4. Set the higher heating output andcheck the CO2 content.Subject to gas type, the CO2 contentmust be within the following range.See table.
Gas type CO2 contentin %
E or H (G20) 7.5 – 10.5P (G31) 10.0 – 12.0
5. Set the lower heating output andcheck the CO2 content.The CO2 content must be between0.3 and 0.9 % below the value for theupper heating output.
6. ■ If the CO2 content is within thegiven range, continue with point 8.
■ If the CO2 content is outside thegiven range, check the balancedflue system for tightness; remedyany leaks.Replace gas train if required.
7. Re-check the CO2 content for theupper and lower heating output.
8. Shut the boiler down, remove the fluegas analyser and close flue gas portA.
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)55
13 0
85 G
B
Serv
ice
36
Burner removal
AB
C
D
E
F
4xG
1. Switch ON/OFF switch to OFF.
2. Shut off the gas supply.
3. Pull the power cables off fan motorA, gas train B, ignition unit C andelectrodes D.
4. Pull venturi extension E off the fan.
5. Undo gas supply pipe fitting F.
6. Undo 4 screws G and remove theburner.
! Please notePrevent damage. Never rest the burner on theburner gauze assembly.
Checking the burner gasket and burner gauze assembly
Check burner gasket A for damage andreplace if required.
Replace the burner gauze assembly if itis damaged.
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)
5513
085
GB
37
A
C
D
E
B
1. Remove electrode B.
2. Undo the 2 Torx screws and removethermal insulation ring C.
3. Undo the 2 Torx screws and removeburner gauze assembly D with gas-ket E.
4. Insert and secure a new burnergauze assembly D with new gasketE.
! Please noteTighten screws just enough to ensure the components donot suffer damage and willfunction correctly.
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)55
13 0
85 G
B
Serv
ice
38
5. Refit thermal insulation ring C.
! Please noteTighten screws just enough to ensure the components donot suffer damage and willfunction correctly.
6. Refit electrode B.
! Please noteTighten screws just enough to ensure the components donot suffer damage and willfunction correctly.
Checking and adjusting the electrode8+
2
4+0,5
1. Check the electrode for wear andcontamination.
2. Clean the electrode with a smallbrush (not with a wire brush) or emerypaper.
3. Check the electrode gaps. If the gapsare not as specified or the electrodeis damaged, replace electrode andgasket and realign the electrode.Tighten the fixing screws for the elec-trode.
! Please noteTighten screws just enough to ensure the components donot suffer damage and willfunction correctly.
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)
5513
085
GB
39
Cleaning the heat exchanger
! Please noteDo not damage the surfaces ofthe heat exchanger that comeinto contact with hot gas. This canlead to corrosion damage. Never use brushes to clean theheat exchanger.Brushing can cause deposits tobecome lodged in the gapsbetween the coils.
NoteDiscolouration on the heat exchangersurface is a normal sign of use. It has nobearing on the function and service lifeof the heat exchanger.The use of chemical cleaning agents isnot required.
A
1. Use a vacuum cleaner to removecombustion residues from heatingsurface A of the heat exchanger.
2. Flush heating surface A withwater.
3. Check condensate drain and cleansiphon. See the following chapter.
4. Flush the heating surface again withwater (the siphon is also filled withwater in the process).
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)55
13 0
85 G
B
Serv
ice
40
Checking the condensate drain and cleaning the siphon
C
B
A
1. Unclip burner control unit A andremove. Protect against escapingcondensate.
2. Pull siphon B upwards out of thedrain connection.
3. Detach supply hose C from siphonB.
4. Clean siphon B.
5. Reconnect supply hose C.
6. Refit siphon B to the drain connec-tion.
7. Install burner control unit A. Checkplugs for correct seating.
8. Fill siphon B with water. For this,pour approx. 0.3 l of water into thecombustion chamber.
9. Check that condensate can drainfreely and that the connections aretight.
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)
5513
085
GB
41
Installing the burner
A
B
C
DE
F
4x
G
1. Fit burner and tighten 4 screws Adiagonally.
! Please noteTighten screws just enough to ensure the components donot suffer damage and willfunction correctly.
2. Insert new gasket and tighten the fit-ting on gas supply pipe B.
3. Attach venturi extension C to thefan.
4. Fit the power cables for fan motorD, gas train E, ignition unit F andelectrodes G.
5. Reopen gas supply and switch onpower supply.
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)55
13 0
85 G
B
Serv
ice
42
6. Check the gas connections forleaks.
DangerEscaping gas leads to a risk ofexplosion.Check the fitting for gas tight-ness.
! Please noteThe use of leak detectionspray can result in faulty oper-ation. Leak detection spray must notcome into contact with electri-cal contacts or seal the dia-phragm opening on the gasvalve.
Checking the diaphragm expansion vessel and system pressure
NoteThe expansion vessel can lose some ofits charge pressure after some time inuse. When the boiler heats up, the pres-sure gauge will indicate a higher pres-sure of 2 or 3 bar (0.2 or 0.3 MPa). Thesafety valve can respond and dischargeexcess pressure.For this reason, check the expansionvessel pre-charge pressure annually.
Check whether the installed expansionvessel is adequate for the system watervolume (GB only).Carry out this test on a cold system.
1. Drain the system until the pressuregauge shows "0".Alternatively, close the cap valve onthe expansion vessel and reduce thepressure until the pressure gaugeindicates "0".
2. If the pre-charge pressure of theexpansion vessel is lower than thestatic system pressure, top up withnitrogen until the pre-charge pres-sure is 0.1 to 0.2 bar (10 to 20 kPa)higher than the static system pres-sure.
3. Top up with water until the chargepressure of the cooled system is atleast 1.0 bar (0.1 MPa), and is 0.1 to0.2 bar (10 to 20 kPa) higher than thepre-charge pressure of the expan-sion vessel. Permiss. operating pressure: 3 bar(0.3 MPa)
Checking all gas equipment for tightness at operating pressure
DangerEscaping gas leads to a risk ofexplosion.Check all gas equipment for tight-ness.
! Please noteThe use of leak detection spraycan result in faulty operation.
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)
5513
085
GB
43
Leak detection spray must notcome into contact with electricalcontacts or seal the diaphragmopening on the gas valve.
Fitting the front panel
2x
2.
1.
1. Hook the front panel into place. 2. Tighten screws on the underside.
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)55
13 0
85 G
B
Serv
ice
44
Instructing the system user
The system installer should hand theoperating instructions to the system userand instruct the user in operating thesystem.
Commissioning, inspection, maintenance
Further details regarding the individual steps (cont.)
5513
085
GB
45
Display Action Control unit issues
a heat demand No Increase set value
and ensure heat isdrawn off
Yes
Fan starts No After approx. 1 minfault F9
Check the fan, fanconnecting cables,power at the fanand fan control
Yes
Ignition No Fault F4 Check the ignitionmodule connec-tion
Yes
Gas train opens No Fault F4 Check the gastrain (control volt-age 230 V) andgas supply pres-sure
Yes
Ionisation currentbuilds (greaterthan 2 µA)Symbol A
No Fault F4 Check the ionisa-tion current andelectrode adjust-ment, check thecondensate drainand the gas line forairlocks.
Troubleshooting
Function sequence and possible faults55
13 0
85 G
B
Serv
ice
46
Yes
Burner in opera-tion
No Stops below the setboiler water tem-perature and re-starts immediately
Check the flue sys-tem for tightness(flue gas recircula-tion); check thegas flow pressure
Fault display
Example
Display■ Faults with lower priority:
Fault code (e.g. "51") is displayed per-manently and fault symbol " " flashes
■ Faults with higher priority:Fault code (e.g. "F2") flashes and faultsymbol " " flashes
For an explanation of the fault codes,see the following table.
Displayedfault code
System characteris-tics
Cause Measures
10 Constant mode Short circuit, out-side temperaturesensor
Check the outside tem-perature sensor and lead(see page 51).
18 Constant mode Lead break, out-side temperaturesensor
Check the outside tem-perature sensor and lead(see page 51).
30 Burner blocked Short circuit, boilerwater temperaturesensor
Check boiler water tem-perature sensor (seepage 52).
38 Burner blocked Lead break, boilerwater temperaturesensor
Check boiler water tem-perature sensor (seepage 52).
51 No DHW heating Short circuit, outlettemperature sen-sor
Check sensor (seepage 54).
Troubleshooting
Function sequence and possible faults (cont.)
5513
085
GB
47
Displayedfault code
System characteris-tics
Cause Measures
52 Burner blocked Short circuit, flowsensor
Check connections andlead; replace sensor if re-quired.
59 No DHW heating Lead break, outlettemperature sen-sor
Check sensor (seepage 54).
5 A Burner blocked Lead break, flowsensor
Check connections andlead; replace sensor if re-quired.
A9 Control mode withoutOpenTherm influ-ence
Communication er-ror, OpenThermdevice
Check connections andlead; replace OpenThermif required.
b0 Burner blocked Short circuit, fluegas temperaturesensor
Check sensor (seepage 55).
b8 Burner blocked Lead break, fluegas temperaturesensor
Check sensor (seepage 55).
E3 Burner in a faultstate
Fault in safetychain
Check the temperaturelimiter and connecting ca-bles (see page 53).
E5 Burner blocked Internal fault Check the ionisation elec-trode and connecting ca-bles.
F0 Burner blocked Internal fault Replace control unit.F1 Burner in a fault
stateMax. flue gas tem-perature exceeded
Check heating system filllevel. Check circulationpump. Vent the system.
F2 Burner in a faultstate
Temperature limit-er has responded
Check heating system filllevel. Check circulationpump. Vent the system.Check the temperaturelimiter and connecting ca-bles (see page 53). Press "Reset" (seepage 49).
Troubleshooting
Fault display (cont.)55
13 0
85 G
B
Serv
ice
48
Displayedfault code
System characteris-tics
Cause Measures
F3 Burner in a faultstate
Flame signal is al-ready present atburner start
Check ionisation elec-trode and connecting ca-ble. Press "Reset" (seepage 49).
F4 Burner in a faultstate
No flame signal de-tected
Check the ignition/ionisa-tion electrode and con-necting cables, check thegas pressure, check thegas train, ignition, ignitionmodule and condensatedrain.Press "Reset" (seepage 49).
F8 Burner in a faultstate
Fuel valve closestoo late
Check gas train. Checkboth control paths.Press "Reset" (seepage 49).
F9 Burner in a faultstate
Fan speed too lowduring burner start
Check fan, fan connectingcables and power supply;check fan control.Press "Reset" (seepage 49).
FA Burner in a faultstate
Fan idle state notreached
Check fan, fan connectingcables and power supply;check fan control.Press "Reset" (seepage 49).
FC Burner blocked Electrical fan con-trol (control unit)faulty
Check fan connecting ca-ble; replace if required, orreplace control unit.
Troubleshooting
Fault display (cont.)
5513
085
GB
49
Displayedfault code
System characteris-tics
Cause Measures
Fd Burner blocked Fault, burner con-trol unit
Check ignition electrodesand connecting cables.Check whether a stronginterference (EMC) fieldexists near the appliance.
Press "Reset" (seepage 49).Replace control unit iffault persists.
FF Burner blocked Fault, burner con-trol unit
Check ignition electrodesand connecting cables.Check whether a stronginterference (EMC) fieldexists near the appliance.
Press "Reset" (seepage 49).Replace control unit iffault persists.
––– Burner blocked Communication er-ror between burnercontrol unit andprogramming unit
Check connecting cable.Press "Reset" (seepage 49).Replace burner controlunit or programming unit ifthe fault persists.
Reset (reset burner control unit)
À and ¿: press simultaneously.The display shows –––.If the fault has been remedied "¨" dis-appears and the default display or a fur-ther fault are shown.
Scanning the programming unit soft-ware version
À and : press simultaneously.
Troubleshooting
Fault display (cont.)55
13 0
85 G
B
Serv
ice
50
Removing the front panel
2x
1.
2.
1. Undo screws at the bottom of theboiler; do not remove completely.
2. Remove front panel.
Troubleshooting
Repairs
5513
085
GB
51
Outside temperature sensor
4 3 2 1
OT+OT-
A
1. Disconnect the leads of outside tem-perature sensor A.
100
10
-20 -10 0 10 20 30Temperature in °C
68
20
406080
200
Res
ista
nce
in k
Ω
Sensor type: NTC 10 kΩ
2. Check the sensor resistance andcompare it with the curve.
3. In the event of severe deviationreplace the sensor.
Troubleshooting
Repairs (cont.)55
13 0
85 G
B
Serv
ice
52
Boiler water temperature sensor
A
1. Pull out the leads on boiler water tem-perature sensor A and check theresistance.
10
1
10 30 50 70 90 110Temperature in °C
0.40.60.8
2
468
20
Res
ista
nce
in k
Ω
Sensor type: NTC 10 kΩ
2. Check the sensor resistance andcompare it with the curve.
3. In the case of severe deviation, drainthe boiler on the heating water sideand replace the sensor.
DangerThe boiler water temperaturesensor is in direct contact withthe heating water (risk ofscalding).Drain the boiler before replac-ing the sensor.
Troubleshooting
Repairs (cont.)
5513
085
GB
53
Checking the temperature limiter
A
If the burner control unit cannot be resetafter a fault shutdown although the boilerwater temperature is below approx.95 °C, check the temperature limiter.
1. Pull out the leads of temperature lim-iter A.
2. Check the continuity of the tempera-ture limiter with a multimeter.
3. Remove the faulty temperature lim-iter.
4. Install a new temperature limiter.
5. Reset by pressing "Reset" on thecontrol unit to (see page 49).
Troubleshooting
Repairs (cont.)55
13 0
85 G
B
Serv
ice
54
Checking the outlet temperature sensor
A
1. Pull out the leads on outlet tempera-ture sensor A.
2. Check the sensor resistance andcompare it with the curve.
10
1
10 30 50 70 90 110Temperature in °C
0.40.60.8
2
468
20
Res
ista
nce
in k
Ω
Sensor type: NTC 10 kΩ
3. In the event of severe deviationreplace the sensor.
NoteWater may leak out when replacingthe outlet temperature sensor. Shutoff the cold water supply. Drain theDHW line and the plate heatexchanger (on the DHW side).
Troubleshooting
Repairs (cont.)
5513
085
GB
55
Checking the flue gas temperature sensor
A
1. Pull out the leads on flue gas temper-ature sensor A.
2. Check the sensor resistance andcompare it with the curve.
10
1
10 30 50 70 90 110Temperature in °C
0.40.60.8
2
468
20
Res
ista
nce
in k
Ω
Sensor type: NTC 10 kΩ
3. In the event of severe deviationreplace the sensor.
Troubleshooting
Repairs (cont.)55
13 0
85 G
B
Serv
ice
56
Replacing the flow limiter
B
A
C
1. Drain the boiler on the DHW side.
2. Pull off spring clip B.
3. Remove flow sensor A.
4. Remove faulty flow limiter C.
5. Check fitted strainer for dirt/contami-nation. Clean strainer if required.
6. Select new flow limiter C from thetable below.
Serial no.(type plate)
Flowratel/min
Colour
7537906 10 lightblue
7537947 14 lightpink
7. Insert new flow limiter C.
8. Mount flow sensor A with new gas-kets.
Troubleshooting
Repairs (cont.)
5513
085
GB
57
Replacing the flow sensor
B
E
CA
D 01. Drain the boiler on the DHW side.
02. Pull the leads off faulty flow sensorA.
03. Pull off spring clip B.
04. Remove enclosure C with flowsensor A.
05. Pull off spring clip D and removefaulty flow sensor A.
06. Select new flow limiter E from thetable on page 56.
07. Insert new flow limiter E.
08. Fit new flow sensor A with newgaskets in enclosure C. Insertspring clip D.
09. Insert spring clip B.
10. Attach leads.
Troubleshooting
Repairs (cont.)55
13 0
85 G
B
Serv
ice
58
Checking or replacing the plate heat exchanger
A
B
C D
EF
C Heating water returnD Heating water flow
E DHWF Cold water
1. Shut off and drain the boiler on theheating water and the DHW side.
2. Undo screw A on the plate heatexchanger and remove plate heatexchanger B with gaskets.
NoteDuring and after removal, smallamounts of water may trickle from theplate heat exchanger.
Troubleshooting
Repairs (cont.)
5513
085
GB
59
3. Check the connections on the DHWside for scaling; clean or replace theplate heat exchanger if required.
4. Check the connections on the heat-ing water side for contamination;clean or replace the plate heatexchanger if required.
5. Install in reverse order using newgaskets.
NoteDuring installation, ensure the fixingholes are aligned and the gaskets arepositioned correctly. Mount the plateheat exchanger with the correct ori-entation.
Checking the fuse
F4
1. Switch off the power supply.
2. Open the control unit enclosure.
3. Check fuse F4.
Troubleshooting
Repairs (cont.)55
13 0
85 G
B
Serv
ice
60
Removing the gas restrictor
C
B
D
AF
E
1. Pull out power cable from gas trainA.
2. Undo union nut B and remove gasgasket.
3. Undo 2 screws C and remove gastrain A.
4. Remove gasket D from gas trainA.
5. Remove gas restrictor E from gas-ket D.
6. Insert gasket D in gas train A.
7. Fit gas train A with new gas gasketF.
! Please noteTighten screws just enough to ensure the components donot suffer damage and willfunction correctly.
8. Remove or void gas type sticker onthe top of the boiler (next to the typeplate).
Gas type conversion
Converting from LPG to natural gas
5513
085
GB
61
9. Start the boiler and check for leaks.
DangerEscaping gas leads to a risk ofexplosion.Check all gas equipment fortightness.
! Please noteThe use of leak detectionspray can result in faulty oper-ation. Leak detection spray must notcome into contact with electri-cal contacts or seal the dia-phragm opening on the gasvalve.
Changing the gas type at the control unit
1. Switch ON the ON/OFF switch.
2. Press MODE and simultaneouslyfor 3 s."SERV" is displayed and "I"flashes.
3. Use / to select "5" and confirm withOK."1" flashes on the display.
4. Use / to select "0" and confirm withOK.The burner has been switched tooperation with natural gas.
5. Press MODE and simultaneouslyfor 3 s.Service mode is terminated. Servicemode also terminates automaticallyafter 30 min.
6. Switch the ON/OFF switch OFF andON again.The selected gas type is now ena-bled.
Checking the CO2 content
See page 33.
Gas type conversion
Converting from LPG to natural gas (cont.)55
13 0
85 G
B
Serv
ice
62
If an outside temperature sensor is con-nected to the control unit, the boilerwater temperature is regulated subject tothe outside temperature.In line with the selected heating curve, aboiler water temperature is set for thecurrent outside temperature.
The heating curve is set at the controlunit as a code. In the delivered condition,the heating curve with code 20 is set.
Operating instructions
Heating curve for weather-compensated operation
20
30
40
50
60
70
80
90
Boile
r wat
er te
mpe
ratu
re in
°C
20 15 10 5 0 -5 -10 -15 -20
5
wP
qT
qP
eT wTeP
Outside temperature in °C
X Code for selected heating curve
Frost protection function
The frost protection function requires anoutside temperature sensor to be con-nected. The frost protection functionbecomes active at outside temperaturesof < 5 °C. The burner starts and the boilerwater temperature is held at 20 °C.
Control unit
Functions and operating conditions in weather-compensated mode
5513
085
GB
63
Overview
A
A Power supplyA1 Main PCB in control unit enclosure
on side panel
A3 Programming unitS1 ON/OFF switchX ... Electrical interface
Designs
Connection and wiring diagrams55
13 0
85 G
B
Serv
ice
64
Programming unit
A
D
C
B
E
F
A Power supply
Designs
Connection and wiring diagrams (cont.)
5513
085
GB
65
B Gas pressure switch (accesso-ries)
C Outside temperature sensor(accessories)
D Room temperature controller(accessories)
E Time switch or wireless receiver(accessories)
F Jumper, remove when connectingroom temperature controller
A1 Main PCBA3 Programming unitS1 ON/OFF switchX ... Electrical interface
Designs
Connection and wiring diagrams (cont.)55
13 0
85 G
B
Serv
ice
66
Control unit
D
C
A
B
A Programming unit connection B Flow sensor
Designs
Connection and wiring diagrams (cont.)
5513
085
GB
67
C Diverter valve stepper motorD Ionisation electrodeA1 Main PCBA2 Power supply unitA3 Programming unitPWM Circulation pump switchingX ... Electrical interface§ Boiler water temperature sensor$ Outlet temperature sensor
aG Flue gas temperature sensorsÖ Circulation pump 230 V~dG Gas solenoid valvefÖ Power supplyfJ Temperature limitergF Ignitiona-Ö Fan motor 230 V~a-ÖA Fan control
Designs
Connection and wiring diagrams (cont.)55
13 0
85 G
B
Serv
ice
68
The following information is required:■ Serial no. (see type plate A)■ Assembly (from this parts list)■ Position number of the individual part
within the assembly (from this partslist)
Standard parts are available from yourlocal supplier.
Parts lists
Ordering parts
5513
085
GB
69
A
B C
D E
F
A Type plateB Casing assemblyC Heat cell assembly
D Hydraulic assemblyE Control unit assemblyF Miscellaneous
Parts lists
Overview of assemblies55
13 0
85 G
B
Serv
ice
70
Pos. Component0001 Front panel0002 Profiled seal0003 Viessmann logo0004 Wall mounting bracket
00020003
0003
0001
0002
0004
Parts lists
Casing assembly
5513
085
GB
71
Pos. Component0001 Gasket DN 600002 Boiler flue connection0003 Boiler flue connection plug0004 Flue gasket0005 Flue gas temperature sensor0006 Heat exchanger0007 Condensate hose0008 Splash siphon0009 Tee connector 7 190010 Gas connection0011 Gasket A 17 x 24 x 2 (5 pce)0012 Burner0013 Thermal insulation block0014 Heat exchanger mounting (set)0015 O-ring 20.63 x 2.62 (5 pce)0016 Corrugated hose 19 x 155 with ferrule/bend0017 Corrugated hose 19 x 500 with ferrule0018 Ignition transformer
Parts lists
Heat cell assembly55
13 0
85 G
B
Serv
ice
72
0008
0007
0018
0004001300140015
0006
00010003
0011
0017
0016
0009
0013
0012
0010
0011
0015
0004
00030014
0014
0014
0002
00010005
Parts lists
Heat cell assembly (cont.)
5513
085
GB
73
Pos. Component0001 Burner gasket 7 1870002 Thermal insulation ring0003 Cylinder burner gauze assembly0004 Burner gauze assembly gasket0005 Burner door0006 Gasket, ionisation electrode (5 pce)0007 Ignition/ionisation electrode0008 Burner door flange gasket0009 Radial fan NRG 1180010 Gas valve GB-ND 055 E010011 Venturi extension0012 Gasket set G20/G310013 Conversion kit G20/G31
Parts lists
Burner assembly55
13 0
85 G
B
Serv
ice
74
0004
0003 0002 00010004
0006
0001000400060008
00080012
0012
0012
0010
0013 0011
0011
0009
0008
0007 0006 0005
0012
Parts lists
Burner assembly (cont.)
5513
085
GB
75
Pos. Component0001 Diaphragm expansion vessel CRI 80002 DEV pad0003 Gasket A 10 x 15 x 1.5 (5 pce)0004 DEV connection line G 3/80005 Connection elbow HR brass0006 Profile hose HR 0007 Spring clip DN 25 (5 pce)0008 Clip 7 10 (5 pce)0009 Clip 7 80010 O-ring 20.63 x 2.62 (5 pce)0011 Temperature sensor0012 Circular seal washer 8 x 2 (5 pce)0013 Profile hose HF0014 Pressure gauge0015 Thermal circuit breaker0016 Connection elbow HF0017 Grundfos hydraulics0018 Spring clip DN 30
Parts lists
Hydraulic assembly55
13 0
85 G
B
Serv
ice
76
0009
0010
0010
0015
0016
0009
0007
0008
0008
0007001000150007
001800070018
00070010
0009
0002
0003
0018
0006
00070005
0004
0003
0001
0012
0011
0013
0018
0017
0014
0012
Parts lists
Hydraulic assembly (cont.)
5513
085
GB
77
Pos. Component0001 Flow casing EU10002 Temperature sensor0003 Expansion tank0004 O-ring 19.8 x 3.6 (5 pce)0005 O-ring 16 x 3 (5 pce)0006 Clip 7 8 narrow (5 pce)0008 Plate heat exchanger0009 Circulation pump motor0010 Return casing0011 Flow limiter0012 Stepper motor0015 Air vent valve0018 Flow sensor0019 Clip 7 80020 Clip 7 160022 Connection elbow0023 Air box floor0025 Dummy adaptor, time switch0028 Gasket set, plate heat exchanger0030 Tee connector 7 19
Parts lists
Grundfos hydraulic assembly55
13 0
85 G
B
Serv
ice
78
0019
0028 0028
0028 0005
0015
00020004000500060028
0011
00040005001100120015001800200028
0010
0022
0022
0022
0004
0010
0010
0006
0002
00030001
00050004
0011
0018
0008
0009
0025
0023
0020
0022
0012
0015
0030
Parts lists
Grundfos hydraulic assembly (cont.)
5513
085
GB
79
Pos. Component0001 Programming unit0002 Burner control unit0003 Cable harness X1/X17/stepper motor0004 Cable harness 100/35/54/ion0005 Cable harness, connecting cable X21/GFA/programming unit0006 Outside temperature sensor lead0007 Connecting cable, heating circuit pump 200008 PWM BUS0009 Power cable
0001
0002
0003
0005
0004
0009000800070006
Parts lists
Control unit assembly55
13 0
85 G
B
Serv
ice
80
Pos. Component0001 Touch-up spray paint, Vitowhite, 150 ml can0002 Touch-up paint stick, Vitowhite0003 Special grease0004 Operating instructions0005 Installation and service instructions
0004
0005
0003
0002
0001
Parts lists
Miscellaneous
5513
085
GB
81
Rated voltage: 230 V~Rated frequency: 50 HzRated current: 2.0 A~Safety category: IIP rating: IP X4D to EN 60529
Permissible ambient temperature ■ During operation: -5 to +40 °C■ During storage
and transport: -35 to +65 °C
Temperature limitersetting: 100 °C (fixed)Backup fuse (powersupply): 3 A
Gas boiler, category II 2H3PRated heating output range in heating mode TF/TR 50/30 °C kW 6.5 – 24 8.8 – 33TF/TR 80/60 °C kW 5.9 – 21.9 8.0 – 30.1Rated heating output rangefor DHW heating kW 5.9 – 29 8.0 – 35
Rated heat input range kW 6.1 – 22.4 8.2 – 30.9Connection values *1Relative to the max. load with:
- Natural gas H m3/h 2.37 3.28- LPG P kg/h 1.71 2.36Power consumption (max.) W 118 142DHW heating Permiss. operating pressure bar 10 10 MPa 1.0 1.0Min. operating pressure, cold water bar 1 1 MPa 0.1 0.1Rated water volumeat ΔT 30 K(according to EN 13203)
l/min 13.8 16.7
Set flow rate (max.) l/min 10 14Min. flow rate l/min 2.1 2.1Product ID CE-0085CP0029
*1 The connection values are only for reference (e.g. in the gas contract application)or for a supplementary, rough estimate to check the volumetric settings. Due to thefactory settings, the gas pressure must not be altered from these values. Refer-ence: 15 °C, 1013 mbar (101.3 kPa).
Specification
Specification55
13 0
85 G
B
Serv
ice
82
Declaration of Conformity for the Vitodens 050-W
We, Viessmann Werke GmbH & Co KG, D-35107 Allendorf, confirm as sole respon-sible body that the product Vitodens 050-W complies with the following standards:
EN 297 EN 55 014-2EN 483 EN 60 335–1EN 625 EN 60 335-2-102EN 677 EN 61 000-3-2EN 806 EN 61 000-3-3EN 12 897 EN 62 233EN 55 014–1
In accordance with the following Directives, this product is designated with_-0085:
92/42/EEC 2006/95/EC2004/108/EC 2009/142/EC
This product complies with the requirements of the Efficiency Directive (92/42/EEC) for condensing boilers.
Allendorf, 01 February 2014 Viessmann Werke GmbH & Co KG
Authorised signatory Manfred Sommer
Certificates
Declaration of conformity
5513
085
GB
83
BBoiler water temperature sensor .......52Burner gasket.....................................36Burner gauze assembly.....................36Burner removal..................................36
CCleaning the combustion chamber....39Cleaning the heat exchanger.............39Commissioning..................................23Condensate........................................16Condensate drain.........................16, 40Connection diagram...........................63– Control unit.....................................66– Programming unit...........................64Connections.......................................14Connections on the water side...........14
DDeclaration of Conformity..................82
EElectrical connections........................19
FFault code..........................................46Fault display.......................................46Filling function....................................23Flow limiter.........................................56Flow sensor........................................57Flue gas temperature sensor.............55Flue pipe............................................17Frost limit...........................................62Frost protection..................................62Function sequence.............................45Fuse...................................................59
GGas connection..................................15Gas supply pressure..........................27
Gas train ...........................................26Gas type conversion..........................60– LPG................................................25– Natural gas.....................................60
HHeating curve.....................................62
IIgnition...............................................38Ignition electrode................................38Installing the burner...........................41Ionisation electrode............................38
MMatching output to flue system..........28Max. heating output...........................27Multiple flue system connection.........29
OOpening the programming unit..........18Outlet temperature sensor.................54Output adjustment– Multiple connection.........................29Outside temperature sensor........20, 51
PPlate heat exchanger.........................58Power supply.....................................20
RReducing the heating output..............27Reset..................................................49
SSafety chain ......................................53Safety valve.......................................16Siphon .........................................17, 40Software version................................49Specification ......................................81Static pressure...................................26Supply pressure.................................25
Keyword index
Keyword index55
13 0
85 G
B
84
System filling................................23, 25System pressure................................25
TTemperature limiter............................53Troubleshooting.................................50
VVentilation air pipe.............................17
WWall mounting....................................11Weather-compensated mode.............62
Applicability
These service instructions relate to appliances with the following serial num-bers (see type plate):7537906 7537947
Viessmann LimitedHortonwood 30, TelfordShropshire, TF1 7YP, GBTelephone: +44 1952 675000Fax: +44 1952 675040E-mail: [email protected]
Viessmann Werke GmbH&Co KGD-35107 AllendorfTelephone: +49 6452 70-0Fax: +49 6452 70-2780www.viessmann.com
5513
085
GB
Sub
ject
to te
chni
cal m
odifi
catio
ns.
Keyword index
Keyword index (cont.)
Installation and service instructionsVitodens 050-WSafety instructionsIndexPreparing for installationInstallation sequenceMounting the boiler and making the connectionsOpening the programming unitElectrical connections
Commissioning, inspection, maintenanceSteps - commissioning, inspection and maintenanceFurther details regarding the individual steps
TroubleshootingFunction sequence and possible faultsFault displayRepairs
Gas type conversionConverting from LPG to natural gas
Control unitFunctions and operating conditions in weather-compensated mode
DesignsConnection and wiring diagrams
Parts listsOrdering partsOverview of assembliesCasing assemblyHeat cell assemblyBurner assemblyHydraulic assemblyGrundfos hydraulic assemblyControl unit assemblyMiscellaneous
SpecificationCertificatesDeclaration of conformity
Keyword index