28
Operating and Installation Manual Fume hood monitor FM100

FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

  • Upload
    vannhan

  • View
    267

  • Download
    4

Embed Size (px)

Citation preview

Page 1: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

Operating and Installation Manual

Fume hood monitor FM100

Page 2: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

SCHNEIDER Elektronik GmbH Phone: +49 (0) 6171 / 88 479 - 0 Fax: +49 (0) 6171 / 88 479 - 99

Industriestraße 4 e-mail: [email protected] Steinbach • Germany www.schneider-elektronik.com

Page 3: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

1Operating Manual ● FM100

DECLARATION OF CONFORMITY

SCHNEIDER Elektronik GmbH hereby declares that the device:

FM100 FUME HOOD MONITOR complies with the basic requirements of the European Council Directive for electromagnetic compatibility (89/336/EEC) and the CE Marking Directive (93/68/EEC).

You may request a copy of the declaration of conformity at the address given below.

SCHNEIDER Elektronik GmbH Industriestraße 4 61449 Steinbach Tel.: +49 (0) 6171 / 88 479 - 0 Fax: +49 (0) 6171 / 88 479 - 99 e-mail: [email protected]

© Copyright 2008 SCHNEIDER Elektronik GmbH

61449 Steinbach ● GermanyTranslation, reproduction and other uses, etc. - in whole or in part - are only allowed with the explicit permission of Schneider Elektronik GmbH.

In the course of continuous product improvements we reserve the right to make technical and and design changes.

All rights reserved.

DECLARATION OF CONFORMITY

Page 4: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

2 Operating Manual ● FM100

Before installing and using the FM100 fume hood monitor, please read and follow this operating and installation manual carefully.

• Installation and wiring may only be done by qualifi ed specialists.• Check whether the operating voltage shown on the nameplate corresponds with the supply voltage at the site where the device will be installed.• During installation, wiring and operation, recognized technical precepts, particularly regulations regarding safety and accident prevention, must be followed.• The device should only be returned to the manfacturer for repair in the original box. • When you see the symbol CAUTION, we recommend that you pay careful attention to the explanatory text and notes.

• The electrical connection must be done by a qualifi ed electrician in accordance with the safety precautions.• The following rules and regulations must be followed: VDE guidelines Local power supplier regulations Manufacturer wiring instructions and terminal connection diagrams• Connect the FM100 fume hood controller to its own, separate circuit to pro tect against overload.• Do not do any electrical work on the device when the power supply is switched on.• Follow the safety regulations at all times: - Disconnect the FM100 fume hood monitor - Ensure that the controller cannot be switched on again - Ensure that the controller is voltage-free

• Do not use the FM100 device immediately after bringing it from an unheated room into a warm room. Condensation on the electronic circuits can lead to severe damage. The device reaches room temperature after approximately 2 hours.• Only place the device in a dry room on a fi rm, fl at surface (e.g, the roof of the fume hood) or screw it to the side wall of the fume hood.• Never pull the mains plug or disconnect the device from the power supply if objects or fl uids have permeated the device or if you notice a smell or smoke. Have the manufacturer check the device.• Never pull the mains plug or disconnect the device from the power supply if the case or lid of the device has to be opened.

• The FM100 fume hood controller is intended solely for controlling volume fl ows in fume hoods in accordance with EN 14175, Part 2.• Do not use the FM100 fume hood monitor in areas that are vulnerable to explosion.

SAFETY INSTRUCTIONS

1.0 SAFETY INSTRUCTIONS

ELECTRICAL CONNECTION

PROPER USE

OPERATING SAFETY

Page 5: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

3Operating Manual ● FM100

TABLE OF CONTENTS

PageDECLARATION OF CONFORMITY . . . . . . . . . . . . . . . . . . . 1

1.0 SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . 21.1 TABLE OF CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . 3

2.0 FUNCTIONAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . 42.1 FUNCTION DISPLAY PANEL . . . . . . . . . . . . . . . . . . . . . . 42.2 FUNCTIONAL DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . 52.3 PERFORMANCE FEATURES . . . . . . . . . . . . . . . . . . . . . . . . 52.4 CE NOTE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

3.0 SCOPE OF DELIVERY • INSTALLATION AND SETUP INSTRUCTIONS 64.0 TERMINAL DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75.0 INSTALLATION • THE FIRST FIVE STEPS. . . . . . . . . . . 8

5.1 STEP 1 • OPEN THE CASE COVER . . . . . . . . . . . . . . . 85.2 STEP 2 • CONNECT PVC HOSES TO THE SENSOR . . . . . . . . . . 85.3 STEP 3 • CONNECT THE FUNCTION DISPLAY . . . . . . . . 85.4 STEP 4 • CONNECT CURRENT AND LIGHTING . . . . . . . . . . . . . . . . . . . 95.5 STEP 5 • CONNECT EMERGENCY POWER PACK . . . . . . . . . . . . . . 9

6.0 INSTALLATION OF ADDITIONAL FUNCTIONS . . . . . . . . . . . . . . 106.1 CONNECTING THE MOTOR ON RECOGNITION. . . . . . . . . . . . . . 106.2 CONNECTING THE DIGITAL INPUTS . . . . . . . . . . . . . . . . . . 10

6.2.1 On/Off (In 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116.2.2 Daytime/night-time control (In 2). . . . . . . . . . . . . . . . . . . . 116.2.3 Sash > 50cm (In 3). . . . . . . . . . . . . . . . . . . . . . . . . 11

6.3 CONNECTING THE ANALOGUE OUTPUT. . . . . . . . . . . . . . . . . . . 126.4 CONNECTING THE ANALOGUE INPUT . . . . . . . . . . . . . . . . . 126.5 CONNECTING THE FLOW SENSOR . . . . . . . . . . . . . . . . . 136.6 CONNECTING THE RELAY OUTPUTS . . . . . . . . . . . . . . . . . . . 14

6.6.1 Light (K3) relay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146.6.2 Motor (K2) relay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146.6.3 Alarm (K1) relay. . . . . . . . . . . . . . . . . . . . . . . . . 14

7.0 FUNCTION DISPLAY AND CONTROL PANEL . . . . . . . . . . . . . . . . . . . . . . 158.0 PROGRAMMING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . 169.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

9.1 ANNUAL FUME HOOD MAINTENANCE . . . . . . . . . . . . . . . . . . . 229.2 POWER PACK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

10.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 2211.0 TECHNICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . 23

11.1 DIMENSIONS CASE . . . . . . . . . . . . . . . . . . . . . . 2311.2 DATA VENTURI MEASURING TUBE . . . . . . . . . . . . . . . . . . . . . . 2411.3 DATA MEASURING TUBE . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

12.0 INDEX . . . . . . . . . . . . . . . . . . . . . . 25A1 APPENDIX A1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A1

TABLE OF CONTENTS 1.1

Page 6: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

4 Operating Manual ● FM100

FUNCTIONAL DESCRIPTION

2.0 FUNCTIONAL DESCRIPTION

oberer Grenzwert

unterer Grenzwert

time

Air

volu

me

or A

ir ve

loci

ty

Actual value

green red green yellow

Okay Alarm Okay Overshoot

2.1 FUNCTION DISPLAY AND CONTROL PANEL

For use as a monitoring and alarm system for exhaust air volume fl ows in various applications, such as fume hoods, safety cabinets and other extraction units.

Microprocessor controlled security system to monitor the containment-safe operating status of fume hoods. An acoustic and optical alarm is activated as soon as the exhaust air volume fl ow falls below the programmable thresholds. When the threshold is exceeded, only an optical alarm is signalled (yellow LED).

FM100 fulfi lls the standards DIN 12924, Part 1 and EN 14175, Part 2. That means security for the laboratory worker. FM100 is suitable for all types of fume hood, making it easy to implement new installations and retrofi t existing fume hoods.

A suitable measurement system is vital for precise and safe monitoring. For safe operation with the static differential pressure transmitter and reproducible and exact measurement results we recommend the SCHNEIDER measuring tube (suitable for retrofi tting) or the SCHNEIDER venturi measuring tube.

The function and control panel is available with its own case or as a built-in version in different variations. In addition to client-specifi c designs a wide range of different function displays are available (see the data sheet Standard function displays).

Basic functions:� Acoustic and optical alarm (LOW=red LED) for insuffi cient exhaust air or

excess supply air (when used for supply air monitoring)� Optical display (OK=green LED) for suffi cient exhaust/supply air� RESET button to acknowledge the acoustic alarm� Service plug for programming via the service module SVM100 or laptop

Addition optional functions:� Button VMAX only for SCHNEIDER fume hood controllers� Optical display (HIGH=yellow LED) for exceedance of the maximum

exhaust air� Yellow fl ashing LED as an optical alarm for the operating status “Sash > 50cm” � Status display VMIN for day/night display� Button Light ON/OFF (fume hood interior)� Button I/O for switching the control function ON or OFF

Function display type: 0010

Page 7: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

5Operating Manual ● FM100

FUNCTIONAL DESCRIPTION

The FM100 fume hood controller complies with the safety requirements of the EMC law and the CE Marking Directive and therefore disposes of a CE Mar-king.

FUNCTIONAL DIAGRAM 2.2

PERFORMANCEFEATURES

2.3

-

+

Supplyair

FM100

High

Okay

Low

Reset

Functionaldisplay

Monitoring according toEN 14175

Battery backup

F1 F2 F3

1 2 3

4 5 6

7 8 9

* 0 ,

ServicemoduleSVM-100

Laptopor alternate

Day/Night operation230 VAC Power

Digital In-/Outputs

Analogue Output

RS 232

Fume hoodmonitor

Fume hood

1

2

3

4

5

Venturi measuring tube

Static differential pressure transmitter

Air flow sensor

Digital In-/Outputs for special application

Analogue Output (0...10 VDC) for room group controller

21

3

4

5

Air volume displaym3

h6

6 Optional air volume (m3/h) or air flow (m/s) display

p

� Microprocessor controlled monitoring system� Integrated power supply 230V AC� All system data are saved mains voltage failure-safe in the EEPROM� Programming and retrieval of all system values via the service module

SVM100 or software PC2000� Monitoring of supply air and exhaust air systems � Static differential pressure transmitter with high long-term stability.

Measuring range: 6...240 (optional 20...800) pascal or face velocity (optional)

� Monitoring of fume hood operation to EN 14175, Part 2 with acoustic and optical alarm

� Optional monitoring of exceedance of a programmable volume fl ow with optical alarm

� Optical and optionally acoustic alarm for the operating status “Sash > 50cm”

� Programming of a second monitoring value (reduced volume fl ow/night-time operation

� Emergency power pack (optional) for mains voltage failure-safe operation� Integrated power pack charging connection � Suitable for all types of fume hood

CE NOTES 2.4

Page 8: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

6 Operating Manual ● FM100

DELIVERY AND INSTALLATION

3.0 SCOPE OF DELIVERY • INSTALLATION AND SETUP INSTRUCTIONS

SCOPE OF DELIVERY FM100 FUME HOOD MONITOR

The following components are included in the delivery of the FM100 fume hood monitor:

The following mounting methods are permissible for the FM100 fume hood monitor:

• Mounted level on the roof of the fume hood monitor (horizontal mounting position). Always with the lid facing upwards.• Screwed to the wall of the fume hood (vertical mounting position). Air connections at the side or facing downwards.

CAUTION! With all other mounting methods the output signal of the differential pressure transmitter changes.

In all events, after installation of the evaluation electronics and before initial operation, a zero-point calibration of the static differential pressure transmitter must be carried out .

Pos. Number Object1 1 Evaluation electronics in housing with sensor ( static dif-

ferential pressure transmitter) and integrated power pack (230V AC)

2 1 Function display and control panel with green and red light-emitting diodes (yellow LED and other functional elements optional), as well as an acoustic alarm with acknowledge-ment button

3 1 8-pole connection cable (3m, optionally 5m) 4 1 Optional accessories:

SCHNEIDER measuring device or venturi measuring tube

NOTE

The evaluation electronics with sensor must be mounted in such a way that vibrations cannot be transmitted to the housing.

During installation and operation it is essential to ensure that no shavings, dirt or contaminants get into the static differential pressure sensor.

13

2

DN

4

Page 9: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

7Operating Manual ● FM100

TERMINAL DIAGRAM

X 5

Monitoringaccordingto EN 14175

TRANSFORMER

PRIM: 230 VAC, 50/60Hz

SEK I: 9 V~/5 VA

FAZ 1

FAZ 2

Battery backup

EARTH

+ (red)

X1

X 9

JP1Serial

Parallel

FUME HOOD MONITOR

FM100Date:15. December 2005

Rev.:0.2

Terminal diagram

according to EN 14175

Laptop

-+

Supply air

Fume hood

F1 F2 F3

1 2 3

4 5 6

7 8 9

* 0 ,

ServicemoduleSVM-100

FLOW SENSOR(optional)

High

Okay

Low

Reset

STATIC DIFFERENTIAL PRESSURETRANSMITTERMeasuring range: 5...240 Pa

- (black)

1

X8

3

2

N

LN

LN

K3L

COM

NO

NC

Operation

FaultFAULTK1: max. 3A/250V AC

NO

COM

MOTOR ONVENTILATOR ON/OFFK2: max. 3A/250V AC

LIGHT FUME HOODON/OFFK3: max. 12A/250V AC

FUNCTIONALDISPLAYstandard orcustomer version

In2In1 JP2

Run

On/Off

In 3

In 2

In 1

GND0...5/10V DCGND2...10V DC

Day/Nightmonitoring

LED-Sashposition >50cm

X 4

X 6

X 7

X10

ANALOGUE INPUT0...5/10V DC, 1mA

DIGITAL INPUTSMax. cable length <5m

ANALOGUE OUTPUT2...10V DC, 10mA

Exhaust air actual value

MAKE SURE TOUSE THE RIGHTFUSES

+ = overpressure

- = underpressure

NC

K1

K2

LN

EARTH

X2

X3

Measuring tube

TERMINAL DIAGRAM 4.0

Page 10: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

8 Operating Manual ● FM100

INSTALLATION

5.0 INSTALLATION • THE FIRST FIVE STEPS

Unscrew the two screws on the case cover and lift the cover upwards to remove it.

For proper installation you need a suitable damming body such as a measuring device with connection nipples (outer Ø 6mm) and two suffi ciently long PVC hoses (inner Ø 6mm).

1. Fit the venturi measuring tube or measuring device into the exhaust pipe.

2. Attach one PVC hose to the positive connector (+ = red) of the differential pressure transmitter and the other end of the hose to the connection nipple (+) on the measuring device. Attach the second PVC hose to the negative connector (- = blue) of the differential pressure transmitter and connect the other end of the tube to the connection nipple (-) on the measuring device.

The PVC hoses must be leak-proof and must not be bent or buckled.

1. Attach the function display and control unit in an easily visible position on the front side of the fume hood.

2. Attach the connection cable (3m, optionally 5m) to the side of the case and to the function display panel. A maximum of two function display panels can be connected (suitable for pass-through fume hoods).

3. Check that jumper JP1 has the correct function display type.

JP1 Serial plug: complex function displays, e.g. Type: 0010

JP1 Parallel plug: simple function displays, e.g. Type: 0060 Please refer to the datasheet Function displays standard for details.

STEP 15.1 OPEN THE CASE

COVER

STEP 25.2 CONNECT PVC HOSES

TO THE SENSOR

STEP 35.3 CONNECTING THE

FUNCTION DISPLAY

FAZ 1

-+

Supplyair

Fume hood

Exh

aust

air

STATIC DIFFERENTIAL PRESSURETRANSMITTERMeasuring range: 5...240 Pa

CP

U

+ -

X8

2021

22

In2In1 JP2

X 7

X10

+ = overpressure

- = underpressure

Measuring tube

X 5

Monitoring acc. toEN 14175

FAZ 1

FAZ 2

JP1Serial

Parallel

Laptop

-+

Supplyair

Fume hood

Exh

aust

air

F1 F2 F3

1 2 3

4 5 6

7 8 9

* 0 ,

Service moduleSVM-100

high

okay

low

Reset

STATIC DIFFERENTIAL PRESSURETRANSMITTERMeasuring range: 5...240 Pa

CPU

+ -

X8

1617

1819

2021

22

CONTROLPANELStandard orcustomized

In2In1 JP2

X 6

X 7

X10

+ = overpressure

- = underpressure

Measuring tube

Page 11: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

9Operating Manual ● FM100

The electrical connection must be carried out by a qualifi ed electrician and safety regulations and the VDE guidelines must be followed.

The power feed-in generates the supply voltage for the control electronics. Check whether the operating voltage shown on the nameplate corresponds with the supply voltage at the site where the device will be installed.

Important!It is essential to ensure that PHASE, ZERO and EARTH are connected correctly!Ensure proper protection against short circuiting!

Follow the safety regulations at all times: - Disconnect the FM100 fume hood monitor - Ensure that the controller cannot be switched on again - Ensure that the controller is voltage-free - Connect the mains connector (230 VAC) with a 3x1,5mm² cable

If supplied, connect the emergency power pack. The red wire is connected to the positive pole (+) and the blue (black) wire to the negative pole (-).

According to the standard EN 14175 an emergency power pack is no longer compulsory.

In the case of a mains voltage failure the emergency power pack provides the supply voltage for the fume hood controller. A mains voltage failure alarm is signalled (red fl ashing LED and acoustic alarm). This alarm cannot be acknow-ledged. With a 6V/1.2 Ah emergency power pack the FM100 mains voltage failure alarm remains active for at least 4 hours (provided that regular annual maintenance is carried out on the power pack).

Important! When connecting the emergency power pack it is essential to ensure that the polarity (+) and (-) is correct!

The components required for basic functioning have now been connected. If no further additional functions or relay outputs are needed, you can now move on to the programming instructions (Chapter 8.0).

The terminal connections for the additional functions and relay outputs are described from Chapter 6 onwards.

INSTALLATION

STEP 4CONNECT POWER

AND LIGHTING5.4

X 5

TRANSFORMATOR

PRIM: 230 VAC, 50/60Hz

SEC I: 9 V~/5 VA

FAZ 1

FAZ 2

EARTH

+ (red)

X1

X 9

JP1Serial

Parallel

CPU

- (black)

1

X8

3

2

N

LN

FEED

-IN P

OW

ERVO

LTA

GE

230V

AC

, 50/

60H

z

K3L

LIGHT FUME HOODON/OFFK3: max. 12A/250V AC

89

710

1112

Run

X 4

X 6

X 7

LOAD MUST BEFUSED ACC. TORULES

K1

K2

LN

EARTH

X2

X3

STEP 5 CONNECT EMERGENCY

POWER PACK5.5

Page 12: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

10 Operating Manual ● FM100

INSTALLATION • DIGITAL INPUTS • ADDITIONAL FUNCTIONS

6.0 INSTALLATION OF ADDITIONAL FUNCTIONS

X 5

TRANSFORMATOR

PRIM: 230 VAC, 50/60Hz

SEC I: 9 V~/5 VA

FAZ 1

FAZ 2

EARTH

+ (red)

X1

JP1Serial

Parallel

- (black)

1

X8

3

2

N

MO

TOR

-ON

-REC

OG

NIT

ION

Feed

bac

k si

gnal

exh

aust

fan=

On

230V

AC

, opt

iona

l 24V

AC

/DC

LN

K3

89

710

1112

X 4

X 6

X 7

K1

K2

L

X2

X3

The motor on recognition function can be activated or deactivated via the ser-vice module SVM100 or laptop (see Chapter 8.0 Programming instructions).

When the motor on recognition is activated (= On) terminal block X2 is checked to see whether the exhaust fan is switched on (230V AC on terminal X2.2 and X2.3). When the exhaust fan is switched on the FM100 fume hood controller is ready for use and controls the safe exhaust air volume fl ow for the fume hood that is connected to it.

When the exhaust fan is switched off (no current on terminal connector X2.2 and X2.3) the FM100 controller is deactivated (red LED is on, the acoustic alarm and and all other LEDs are off), i.e. an optical alarm is only signalled when the exhaust fan is switched off (=without current).

The mains voltage (230V AC) of the corresponding exhaust fan can be directly connected to terminal X2.2 and X2.3.

Important!It is essential to ensure that PHASE and ZERO are connected correctly!Ensure proper protection against short circuiting!

Optionally terminal input X2.2 and X2.3 is also available for a voltage of 24V AC (please request this on your order).

The following additional functions can be implemented with the digital inputs on terminal block X9.

The digital inputs In 1, In 2 and In 3 have no galvanic separation. Activation is done directly via potential-free contacts.

With activation via potential-free contacts the maximum cable length is limited to 5m. The current per input is ≤ 2mA (bei 5V DC).

6.1 CONNECTING THE MOTOR ONRECOGNITION

6.2 CONNECTING THE DIGITAL INPUTS

X 9

1516

1314

1718

1920

2122

In2In1 JP2

Run

On/Off

In 3

In 2

In 1

MonitoringDay/Night

LED-Sashposition >50cm

X10

DIGITAL INPUTSMax. cable length <5m

Page 13: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

11Operating Manual ● FM100

On/Off (In 1) 6.2.1

INSTALLATION • DIGITAL INPUTS • ADDITIONAL FUNCTIONS

Switches the FM100 fume hood controller ON and OFF via terminal X9.17 and X9.18. When the FM100 is switched on, the relay K2 Motor on/off is activated.

When the contact is open the FM100 fume hood controller is switched on, while a closed contact switches the device off (relay K2 Motor on/off drops out). This relay serves as feedback to a building services management system (BSM) or for direct activation of an exhaust fan (via a contactor).

Daytime/night-time switching of the control setpoints via terminal X9.15 and X9.16. The Day and Night control setpoint is programmed via the service modu-le SVM100 or laptop (see Chapter 8.0 Programming instructions).

The Day setpoint controls safe exhaust air volume fl ow during daytime opera-tion, while the fume hood‘s Night setpoint controls the fume hood during night-time operation (reduced operation). That means that during reduced operation an alarm is only signalled when the reduced exhaust air volume fl ow falls below the Night setpoint.

When the contact is open the FM100 fume hood monitor is in Day setpoint con-trol mode, while a closed contact switches the device to Night setpoint control mode.

A relay as feedback for the building management system (BMS) is only supplied with the FM500 model.

According to EN 14175 fume hood sashes must be equipped with a mechanical lock at a sash opening of 50cm. If the sash is opened more than 50cm, the me-chanical lock must be released. In accordance with this standard, a fl ashing LED on the function display signals the condition „Sash opening > 50cm“ (alarm).

When the contact on terminal X9.13 and X9.14 is open (switch type=normally closed contact) or shut (switch type=normally open contact) the LED „Close sash“ fl ashes on the function display.

The switch type (normally closed contact or normally open contact), the acoustic alarm delay time as well as an acoustic alarm in addition to the optical alarm can be programmed via the service module SVM100 (see Programming instructions, steps 8.9, 8.10 and 8.11).

Daytime/night-time control (In 2) 6.2.2

Sash >50cm (In 3) 6.2.3

Page 14: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

12 Operating Manual ● FM100

INSTALLATION • ANALOGUE OUTPUT • ANALOGUE INPUT • ADDITIONAL FUNCTIONS

6.3 CONNECTING THE ANALOGUE OUTPUT

X 9

1516

1314

1718

1920

2122

In2In1 JP2

Run

GND0...10V DC

X10

ANALOGUE OUTPUT0...10V DC, 10mA

Actual value

The analogue output (terminal X9.21 = GND and X9.22 = 2...10V DC) provides the exhaust air actual value as a voltage signal 2...10V DC. The voltage range 2...10V DC corresponds to an exhaust air volume fl ow of 0...2000m³/h.

Room monitoring and control can be achieved using the exhaust air actual value signal. The maximum output current is 10mA.

The analogue input on terminals X9.19 (GND) and X9.20 (0...5/10V DC) is free and reserved for special functions.

Combined supply air and exhaust air control can be achieved with this input, for example. The maximum input current is 1mA.

6.4 CONNECTING THE ANALOGUE INPUT

X 9

1516

1314

1718

1920

2122

In2In1 JP2

Run

GND0...5/10V DC

X10

ANALOGUE INPUT0...5/10V DC, 1mA

Page 15: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

13Operating Manual ● FM100

INSTALLATION • AIR FLOW SENSOR

CONNECTING THEFLOW SENSOR

6.5

The air fl ow sensor measures the fl ow velocity in the fume hood. The FM100 fume hood controller has two different monitoring op-tions:

1. Monitoring of safe exhaust air volume fl ow2. Monitoring of safe fl ow velocity

The static differential pressure transmitter and the necessary measuring system is not required if the fl ow sensor is used. Low fl ow velocities of 0,3 m/s can be monitored, whereby this system is very vulnerable to disturbance variables, i.e. air turbulence, the type of fume hood, the installation point of the fl ow sensor and air temperature changes may distort the measuring result.

A considerably more robust and accurate measuring method is a static differential pressure transmitter with a suitable measuring system. The disturbance variables mentioned above have no infl u-ence on the result of the volume fl ow measurement. This method is therefore well established for measuring low volume fl ows (=low fl ow velocities).

X 5

FAZ 1

FAZ 2

X1

JP1Serial

Parallel

Supplyair

Fume hood

Exh

aust

air

AIR FLOW SENSOR

1

X8

3

2

N

K3

89

710

1112

X 4

X 6

X 7

K1

K2

L

X2

X3

Page 16: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

14 Operating Manual ● FM100

INSTALLATION • RELAY OUTPUTS

6.6 CONNECTING THERELAY OUTPUTS

The complete system is populated with max. 3 relays. The potential-free relay outputs are for malfunction notifi cation and feedback to the building services management system. The maximum ohmic contact load of the relay Light K3 is 12 A (230V AC), which means that it is also suitable for controlling fl uorescent tubes. The maximum ohmic contact load of the relay K1 and K2 ist 3 A (230V AC).

Important! Ensure that connected consumer loads are properly protected against short circuiting!

The meaning of the relay outputs K1 to K3 is as follows:

The Light relay (K3) is activated when the Light on/off button on the function dis-play and control panel is pressed and is inactiveted when the button is pressed again. With this relay the lighting in the fume hood is switched on and off. The phase is switched from terminal X1.1 to X3.L via the relay contact K3 and may be a separate mains from the power line (3 phases). When the phase is the same, terminal X1.L is bridged to X1.1.

The fl uorescent light is connected to terminal X3.L (phase L), X3.N (neutral) and X3.earth.

The Motor on/off relay K2 is activated when the FM100 fume hood controller is switched on. This may be done by pressing the I/O (in/out) button (if this function is enabled) on the function display and control panel or via the remote activa-tion input X9.17 and X9.18 (see digital inputs). The digital in/out output has a higher priority than the button and overrides it. This relay switches the exhaust fan on or off and also serves as feedback for the building management system (BMS).

In the case of a fault alarm, the Alarm relay (K1) drops out and thus signals the malfunction status. Malfunctions may be, for example, insuffi cient exhaust air volume, mains voltage failure and internal errors.

X 5

FAZ 1

FAZ 2

EARTH

+ (rot)

X1

JP1Serial

Parallel

- (black)

1

X8

3

2

N

LN

230V

AC

, 50/

60H

z

LN

K3L

COM

NO

NCOKAY

FAULTFAULT ALARMK1: max. 3A/250V AC

NO

COM

MOTOR ONMOTOR ON/OFFK2: max. 3A/250V AC

LIGHT FUME HOODON/OFFK3: max. 12A/250V AC

89

710

1112

X 4

X 6

X 7

LOAD MUST BEFUSED ACC. TORULES!

NC

K1

K2

LN

EARTH

X2

X3

FEED

-IN P

OW

ERVO

LTA

GE

MO

TOR

-ON

-REC

OG

NIT

ION

Feed

bac

k si

gnal

exh

aust

fan=

On

230V

AC

, opt

iona

l 24V

AC

/DC

6.6.1 CONNECTING THE LIGHT RELAY (K3)

6.6.2 CONNECTING THE MOTOR ON RELAY (K2)

6.6.3 CONNECTING THE ALARM RELAY (K1)

Page 17: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

15Operating Manual ● FM100

FUNCTION DISPLAY AND CONTROL PANEL

FUNCTION DISPLAY AND CONTROL PANEL 7.0

This yellow and lights cess exhafl ow.

This green the normal i.e. the fumting with sair volume flfore within a

This red Lsignal a mthe fume hwith insuffi volume fl ownot contamacoustic aladue to insuair volume flnowledged Reset buttalarm cannledged and off when sair volume fl

The service plug has an RS 232 interface. The service module SVM100 or a laptopcan be connected here.

X button is only ac-during fume hood During fume hood monitoring it has no

RESET button thealarm (malfunction nsuffi cient exhaust me fl ow) can be edged. The optical annot be acknow-nd is only switched

n suffi cient exhaust me fl ow is available.

ow LED fl ashes ton optical alarm when is opened >50cm.D indicates to the t safest operation is d when the sash is

ton VMIN can only ated on the FM500 This button has no

function on the FM100 mo-del. The yellow status LEDlights up to show the night-time reduction status when the terminals Day/night con-trol X9.15 and X9.16 are activated. FM100 monitors the Night setpoint (reduced operation).

With the LIGHT button theinterior lighting of the fumehood can be switched on and off.

With the I/O button monito-ring can be switched on or off. The green LED lights upto signal that the controller is switched on.

In some cases client-specifi c function and display panels require a different arrangement of the elements on the function display and control panel than the universal function display panel shown here. However, the operation and meaning of the functions is exactly the same and can therefore be compared with the universal function display panel. With complex function display panels like the one shown here, the jumper JP1 must be plugged to serial, while with simple function display panels (two LEDs, a Reset button and a service plug) the jumper JP1 must be plugged to parallel.

Status display mains voltage failure:In the case of a mains voltage failure the red LED fl ashes briefl y once every 2 s. Simultaneously the acoustic alarm is signalled. Mains voltage failure is also signalled when the device is switched off, but in this case without an acoustic alarm. The following LEDs are off: green LED (OK), yellow LED (ex-cess), yellow LED (close sash). The Alarm relay (K4) drops out.

Status display night-time reduction:The night-time reduction display depends on the type of function display:� Function display and control panel with LED VMIN

When the night-time reduction is activated via the digital input Day/night or the Motor on signal: LED VMIN = static on.� Function display and cotnrol panel without an integrated LED VMIN

The red LED (underrun) fl ashes.In both cases the green LED (OK) is off. The Alarm relay (K3) only drops out if the underrun value for night-time opera-tion is not reached.

Page 18: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

16 Operating Manual ● FM100

PROGRAMMING INSTRUCTIONS

8.0 PROGRAMMING INSTRUCTIONS

8.1 Select function display type

Menu item in the service module

Type selection(see Overview func-

tion display type)

FAZ-Type Type xxxENT

-+

ENT

Programming of project-specifi c data is done via the service module SVM100 or PC. Plug the service module data cable into the service plug of the function display and plug in the service module mains plug. The fume hood controller power supply must also be switched on.

After selecting the FM product from the main menu with the F1 button on the service module, the following settings are available for selection:

When steps 1 to 11 have been programmed and checked, the FM100 fume hood monitor is ready for use. All settings are saved mains voltage failure-safe.

The programming instructions described here are for the service module SVM100. If programming of the FM100 fume hood monitor is carried out via PC/laptop and the SCHNEIDER software PC-2000 the settings and their explanations are identical.

The programming options of the service module SVM100 are clearly structured. The buttons needed are described be-low.

STEP SETTINGS VIA THE SERVICE MODULE8.1 Select function display type8.2 Pressure sensor zero-point calibration8.3 Shield factor of the measuring system and fume hood type8.4 Enter setpoints8.5 Set alarm delay time8.6 Set piezo duration8.7 Set motor on recognition (optional)8.8 Alarm delay after start-up8.9 Defi ne switch type „Sash > 50cm“8.10 Piezo „Sash > 50cm“ on/off8.11 Set delay time „Sash > 50cm“

Several FAZ types are available for selection (see appendix: Function display type selection). The type selection is a pre-programmed factory setting and refers to the model of the function display and control panel. Please check whether the correct FAZ type is programmed for the function display type that you use.

+

-

ENT

F1

Selects the previous menu item

SPACE

The red button function is selected by pressing the SHIFT key and the desired key together.

Selects the next menu item

Menu item selection, entry confirmation and selectionof the previous (sub-) menu item

F1...F10 Selection of a sub-menu item

Value selection or value increment

Value selection or value decrement

Cancellation of zero-point calibration

Page 19: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

17Operating Manual ● FM100

PROGRAMMING INSTRUCTIONS

8.2 Zero-point calibration of the pressure sensor

Menu item in the service module

Zero point sensor

SPACE

ENT

SPACE = Cancel

ENTER = Zero point sensor

The static differential pressure transmitter is position-dependent, so calibration may only be carried out in its fi nal moun-ting position (vertical sensor or horizontal sensor).

CAUTION! Detach both measuring hoses if zero-point calibration is to be performed.

Press the SPACE key to cancel the zero-point calibration and the ENTER key to carry out the zero-point calibration.

8.3 Shield factor of the measuring system and fume hood type

Menu item in the service module

Setting range

The shield factor is necessary to calculate the exhaust air volume fl ow (actual value). This actual value is constantly compared with the programmed setpoints. If the setpoints are exceeded or underrun, an alarm or warning message is signalled. Selection of the correct shield factor is very important for the effi cient functioning of the FM100 fume hood mo-nitor.

The following table illustrates the relationship between the Venturi measuring tube from SCHNEIDER the nominal diame-ter (DN), the C-value (C), the shield factor (B) and the overall length (L).

Shield factor 10 to 250ENT

-+

ENT

C-value=C, Shield factor=B, Overall length=L [mm]Measuring system DN160 DN200 DN250 DN315

C B L C B L C B L C B LSCHNEIDER venturi measuring tube 40 32 190 61 49 210 92 73 230 148 118 600

The C-value of the measuring tube MT depend on fume hood type and must be calculatet once for each type (e.g. 1200, 1500, 1800) by reference measuring (e.g. Venturi measuring tube) according to formula on page 18.

The shield factor must be programmed. It is calculated on the basis of the C value (C) of the measuring system used, whereby: B = C • 0,8

Page 20: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

18 Operating Manual ● FM100

Setpoint cbm/h Minimum day F1

Maximum day F2

Minimum night F3

F1

F2

F3

0 to 2500

0 to 2500

0 to 2500

0 to 2500Maximum night F4 F4

ENT

+

ENT

-

ENT

8.4 Enter setpoints for the volume fl ows

Menu item in theservice module

Submenu items Settings [m3/h]

+ Connection

- Connection

p Differential pressure

Measuring tube+

-

Flow hood with measuring tube

Using a SCHNEIDER measuring tube, determination of the volume fl ow and measuring accuracy can be considerably improved. The differential pressure will be measured room pressure independend on the masuring tube. The static differential pressure transmitter is connected to the (+) connector and the (-) connector of the measuring tube.

Depending on the model and the connection diameter (DN), each type of fume hood also has a specifi c shield factor (C value). This can easily be calculated using the measuring reports that are available for each fume hood type.

Calulation formula:

Assumption:Air density ς = 1.2 kg/m³

The shield factor required for fume hood control is calculated as follows:

B = C 0,8

Sample calculation:

From your test report you establish that the fume hood has a static pressure loss of 42 pascal (pa) at a volume fl ow of 480 m³/h.

Thus C is calculated as:

and the shield factor S:

Set the calculated value of 59 for this type of fume hood.

480C = = 74

42

B = 74 0,8 = 59

Enter the underrun value (Minimum day F1) and, if necessary, the exceedance value (Maximum day F2) for daytime operation in m³/h. To monitor in night-time reduction mode (reduced operation = non-working time) enter the appropriate underrun (Minimum night F3) or exceedance (Maximum night F4) value for reduced operation as well.

PROGRAMMING INSTRUCTIONS

VC =

p

C = Shield factor (C-value)

V = Air volume flow [m3/h]

P = Differential pressure [pa]

Page 21: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

19Operating Manual ● FM100

8.5 Set the alarm delay time

Menu item in the service module

Settings [s]

Delay time 1 to 240ENT

-+

ENT

The alarm delay time defi nes how long the predefi ned setpoint must be underrun or exceeded before an alarm or warning is signalled. The delay time is entered in seconds.

PROGRAMMING INSTRUCTIONS

8.6 Set the duration of the acoustic alarm

Menu item in the service module

Submenu item Settings [s]

Piezo setting Piezo duration F1 F1 10 to 900ENT

+

ENT

-

ENT

The piezo duration defi nes how long an acoustic is signalled before it is automatically acknowledged. This is entered in units of 10 seconds.

When an acoustic alarm is signalled, either it switches off automatically after the predefi ned piezo duration (automatic alarm acknowledgement) or it can be switched off manually (manual acknowledgement) by pressing the acknowledge-ment button (Reset). Setting 900 suppresses automatic acknowledgement and allows only manual acknowledgement.

8.7 Set the motor on recognition

Menu item in the service module

Setting range

Motor-On On/OffENT

-+

ENT

The Motor on recognition is used to recognize and analyze various operating modes of the fume hood controller. Motor on recognition OFF The control function is always active. An alarm (optical and acoustic) is signalled when the ventilation system is shut down. Motor on recognition ON The control system is only active when the Motor on signal (230V AC, optio- nally 24V AC) is connected to terminal X2.2 and X2.3 (ventilation system is switched on). If a Motor on signal is not present, only an optical and not an acoustic alarm is signalled (ventilation system is switched off).

Page 22: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

20 Operating Manual ● FM100

PROGRAMMING INSTRUCTIONS

8.8 Alarm delay after start-up

Menu item in service module

Setting [s]

Delay start 5 to 120ENT

-+

ENT

After start-up, the red LED (underrun) always lights up fi rst. When the volume of air reaches or exceeds the underrun threshold, the green LED lights up and the red LED goes out. During the predetermined alarm delay time the malfunc-tion relay K1 does not drop out even if the volume of air is too low. It is only activated after the predetermined time (5 to 120s).

This is true for all for methods of switching on and over: � Connection of the supply voltage � Button On/Off � Signal Motor on � Switch to Day/night

This function does not generate an alarm for example, if the exhaust fan is switched on but only reaches its full volume fl ow rate after a specifi c period of time. The alarm delay time after start-up is entered in seconds.

8.9 Defi ne the switch type „Sash > 50cm“

Menu item in theservice module

Type selection

Switch type NC/NOENT

-+

ENT

The switch type on terminal X7.13 and X7.14 is defi ned as a normally closed contact (NC) or a normally open contact (NO).

According to EN 14175 fume hood sashes must be equipped with a mechanical lock at a sash opening of 50cm. If the sash is opened more than 50cm the mechanical lock must be released. In accordance with this standard, a fl ashing LED on the function display signals the condition „Sash > 50cm“ (alarm).

When the contact on terminal X9.13 and X9.14 is open (switch type=normally closed contact) or shut (switch type=normally open contact) the LED „Close sash“ fl ashes on the function display.

Page 23: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

21Operating Manual ● FM100

PROGRAMMING INSTRUCTIONS

8.10 Set the piezo Sash > 50cm on/off

Menu item in theservice module

Setting

Piezo sash On/OffENT

-+

ENT

For a sash opening > 50cm an acoustic alarm (=On) can be programmed in addition to the optical alarm.

8.11 Set the delay time Sash > 50cm

Menu item in the service module

Settings [min]

Delay time 1 to 240ENT

-+

ENT

The delay time defi nes how long the contact on terminal X9.13 und X9.14 must be open (switch type=normally closed contact, NC) or shut (normally open contact, NO) before an acoustic alarm (see 8.10 Piezo sash) is signalled. The delay time is entered in minutes.

The optical alarm is signalled directly without delay.

Page 24: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

22 Operating Manual ● FM100

MAINTENANCE • TROUBLESHOOTING

The FM100 fume hood monitor requires no special maintenance.

However, you must ensure that the PVC measuring hoses are not damaged or buckled and that they are securely attached to the measuring system and the sensor.

Annual fume hood maintenance must include a function test that signals the acoustic and optional alarm (detach the measuring hoses). Following zero-point calibration of the differential pressure transmitter (only to be carried out when the measuring hoses are detached), see Chapter 8.2, the setpoints must be checked via the service module or laptop. Finally, select the menu item Actual value in the SVM100 service module and compare the exhaust air actual value (reattach the measuring hoses fi rst) with a redundant measuring value (hot-wire or vane anemometer).

The 6V/1.2 Ah power pack must undergo maintenance checks at regular inter-vals and must be exchanged after a maximum of fi ve years. The FM100 fume hood monitor has an integrated power pack charging connection.

PROBLEM CAUSE

LEDs do not light up.Power supply not connected or faulty. Check the cable connection between the function display panel and the sensor box.

LEDs fl ashing.Wrong setting for FAZ display type.Jumper JP1 function display parallel/serial incorrectly connected or not connec-ted at all.Check the cable connection between the function display panel and the sensor box.

Actual value (via service module) is not identical with the externally measured actual value.

Carry out or repeat the zero-point calibration (see Chapter 8.2).Check the shield factor (see Chapter 8.3).Check that the PVC measuring hoses are fi rmly attached (measuring system and differential pressure transmitter) and are not bent or buckled.Check the data cable connection between the service module and the function display panel.

Function display is not working properly (LED always red).

Check whether the Motor on recognition is activated. (=On).If Motor on recognition = On. Check whether current is not connected to the Motor on terminal or is faulty.Check the Minimum day and Minimum night setpoints.

Function display is not working properly (LED always green).

Check the Minimum day and Minimum night setpoints.

Function display is not working properly (LED always yellow).

Check the setpoints Maximum day and Maximum night.

The red and green LEDs are fl as-hing alternately.

The differential pressure transmitter or the fl ow sensor is faulty.

Use the following table to analyze problems and their possible causes and to correct them.

9.0 MAINTENANCE

9.1 ANNUAL FUME HOODMAINTENANCE

9.2 POWER PACK

10.0 TROUBLESHOOTING

Page 25: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

23Operating Manual ● FM100

167

185 92

+

-

Static differentialpressure transmitter

+ = overpressure - = underpressure

Cable entry pointand pull relief

Caseearthing

Case FM100Top view

Case FM100Side view

TECHNICAL DATA • DIMENSIONS

TECHNICAL DATA 11.0

DIMENSIONSCASE

11.1

� GeneralNominal voltage 230 V AC/50/60Hz/+-15%Max. charging rate 200 mAMax. power input 10 VAReactivation time 600msOperating temperature 0 OC bis +55 OCHumidity max. 80 % relative, non-

condensing

� CaseProtection type IP 20Material Sheet steelColour white, RAL 9002Dimensions (LxWxH) (185 x 167 x 92) mmWeight approx. 1.4 kgTerminals Screw terminal 1.5 mm2

caged spring terminal 1.5 mm2

� Relay outputsNumber 1 relay (K3)Contact type normally open contactMax. switching voltage 250 V ACMax. continuous current 12 ANumber 2 relays (K1, K2)Contact type changeover contactMax. switching voltage 250 V ACMax. continuous current 3 A

� Digital inputsNumber 3 inputs, 5 V DC/2 mAActivation potential-free contact, maxi-

mum cable length < 5 m

� Analogue outputExhaust air actual value 0(2)...10VDC, 10 mA

� Analogue inputSetpoint value 0(2)...5/10VDC, 1 mA

� Differential pressure transmitterMeasuring principle staticPressure range 6...240 pascal

20...640 pascal optionalResponse time <10 msOverpressure max. 500 mbar

� Optional measuring systemMaterial Polypropylene (PPs)Measuring system Measuring device or venturi

measuring tube

Page 26: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

24 Operating Manual ● FM100

DN

Measuring device with integrated venturi measuring tube, model: PPs, Socket/socket

Nominal dia-meter [mm]

Socket/socketlength[mm]

Flange/fl angelength[mm]

VMIN

[m3/h]VMAX

[m3/h]C value Shield factor

S

DN 160 190 160 100 480 40 32DN 200 210 160 180 800 61 49DN 250 230 180 250 1200 92 73DN 315 600 500 400 1950 148 118

TECHNICAL DATA • MEASURING SYSTEM

11.2 DATA VENTURI MEASURING TUBE

11.3 DATA MEASURING TUBE

Available lengths [mm]160, 200, 250315, 400, 500600, 700, 800

The C-value of the measuring tube MT depend on fume hood type and must be calculatet once for each type (e.g. 1200, 1500, 1800) by reference measuring (e.g. Venturi measuring tube) according to formula on page 18.

The shield factor must be programmed. It is calculated on the basis of the C value (C) of the measuring system used, whereby:

B = C • 0,8

Page 27: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

25Operating Manual ● FM100

INDEX

INDEX 12.0

A

Alarm delay time after start-up 16, 20Alarm delay time, setting 16, 19ANNUAL MAINTENANCE 22Attachment A1

C

CASE COVER, OPENING 8CE NOTE 5CONNECTION ANALOGUE INPUT 12CONNECTION ANALOGUE OUTPUT 12Connection cable 6CONNECTION DIGITAL INPUT 10CONNECTION FLOW SENSOR 13CONNECTION FUNCTION DISPLAY 8CONNECTION MAGNETIC VALVE 12CONNECTION MOTOR ON RECOGNITION 10CONNECTION RELAY ALARM (K1) 14CONNECTION RELAY LIGHT (K§) 14CONNECTION RELAY MOTOR (K2) 14CONNECTION RELAY OUTPUTS 14CONNECTION SUPPLY VOLTAGE ANALOGUE INPUT 12

D

DATA MEASURING TUBE 24DATA VENTURI MEASURING TUBE 24Day/night (In 2) 11Declaration of conformity 1Delay time „Sash > 50cm“, setting 16, 21Differential pressure transmitter 6DIMENSIONS CASE 23Duration of the acoustic alarm, setting 16, 19

E

Electrical connection 2EMERGENCY POWER PACK 9Errors, overview 22

F

FUNCTIONAL DESCRIPTION 4FUNCTIONAL DIAGRAM 5FUNCTION DISPLAY PANEL 4, 15

I

INSTALLATION AND SETUP INSTRUCTIONS 6INSTALLATION OF ADDITIONAL FUNCTIONS 10INSTALLATION • THE FIRST FIVE STEPS 8

M

MAINS CONNECTION 9MAINTENANCE 22Motor on recognition, setting 16, 19

O

On/off (In 1) 11

P

PERFORMANCE FEATURES 5Piezo duration, setting 16, 19Piezo Sash > 50cm“, setting 16, 20POWER PACK 22PROGRAMMING INSTRUCTIONS 16PVC HOSES, ATTACHING TO THE SENSOR 8

R

RELAY OUTPUTS 14

S

Safety instructions 2SAMPLE CALCULATION 18Sash >50cm (In 3) 11SCOPE OF DELIVERY 6Selection of the function display type 16Setpoint specifi cation 16Setpoint specifi cation of volume fl ows 16, 18Shield factor of the measuring system or fume hood type 16, 17Static differential pressure transmitter 6Switch type „Sash > 50cm“, setting 16, 20

T

TABLE OF CONTENTS 3TECHNICAL DATA 23TERMINAL DIAGRAM 7TROUBLESHOOTING 22

Z

Zero-point calibration of the pressure sensor 16, 17

Page 28: FM100 Operating manual - Schneider Elektronik · Before installing and using the FM100 fume hood monitor, ... to the explanatory text and notes. ... F1 F2 F3 12 3 45 6 78 9 *0 , Servicemodule

26 Operating Manual ● FM100

SCHNEIDER Elektronik GmbH Phone: +49 (0) 6171 / 88 479 - 0 Fax: +49 (0) 6171 / 88 479 - 99

Industriestraße 4 e-mail: [email protected] Steinbach • Germany www.schneider-elektronik.com