Advantages Robust IP67 (NEMA Type4X) field enclosure. It is so rugged, you can even stand on it! Intrinsically Safe available - ATEX and IECEx approval for gas and dust applications. Programming can be done by your own crew, with the sensible menu-driven structure, saving cost and irritation. Know one, know them all! Very diverse mounting possibilities: walls, pipes, panels or directly onto outdoor sensors! Features Calculates compensated flow rate, total and accumulated total. Displays actual line pressure and temperature. Selectable on-screen engineering units; volumetric or mass. 7 digit resettable total. 11 digit accumulated total. Explosion/flame proof available. Full Modbus communication RS232/485/TTL. Loop or battery powered, 8 - 24V AC/DC or 115 - 230V AC power supply. LED backlight option. Signal output (0)4 - 20mA / 0 - 10V DC according to compensated flow rate. Scaled pulse output according to accumulated total. Signal input Flow Ability to process all types of flowmeter signals: Reed-switch, NAMUR, NPN/PNP pulse, Sine wave (coil), Active pulse signals, (0)4 - 20mA, 0 - 10V DC. Temperature PT100 - 2 or 3 wire, (0)4 - 20mA, 0 - 10V DC. Pressure (0)4 - 20mA, 0 - 10V DC. Applications The F-Series is your first and safest choice for field mount indicators in safe and hazardous area applications. Especially in harsh weather conditions like rain, snow, salty atmosphers and temperatures between -40°C up to +80°C (-40°F up to 176°F). Applications where nett gas flow calculation at base conditions is desired. For DIN panel mount indicators, check our D-S eries . FLOWCOMPUTER WITH TEMPERATURE AND PRESSURE COMPENSATION FOR CORRECTED GAS VOLUME DATASHEET F126-EG - FLOWCOMPUTER 1

FLOWCOMPUTERGeneral information Introduction The flowcomputer Model F126-EG has been developed to calculate the gas volume at normal conditions for generic products, in most cases

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: FLOWCOMPUTERGeneral information Introduction The flowcomputer Model F126-EG has been developed to calculate the gas volume at normal conditions for generic products, in most cases

Advantages• Robust IP67 (NEMA Type4X) field enclosure.

It is so rugged, you can even stand on it!• Intrinsically Safe available - ATEX and IECEx

approval for gas and dust applications.• Programming can be done by your own crew, with

the sensible menu-driven structure, saving costand irritation. Know one, know them all!

• Very diverse mounting possibilities: walls, pipes,panels or directly onto outdoor sensors!

Features• Calculates compensated flow rate, total and

accumulated total.• Displays actual line pressure and temperature.• Selectable on-screen engineering units; volumetric

or mass.• 7 digit resettable total.• 11 digit accumulated total.• Explosion/flame proof available.• Full Modbus communication RS232/485/TTL.• Loop or battery powered, 8 - 24V AC/DC or

115 - 230V AC power supply.• LED backlight option.

Signal output• (0)4 - 20mA / 0 - 10V DC according to

compensated flow rate.• Scaled pulse output according to accumulated

total.

Signal inputFlow• Ability to process all types of flowmeter signals:

Reed-switch, NAMUR, NPN/PNP pulse, Sine wave(coil), Active pulse signals, (0)4 - 20mA, 0 - 10V DC.

Temperature• PT100 - 2 or 3 wire, (0)4 - 20mA, 0 - 10V DC.Pressure• (0)4 - 20mA, 0 - 10V DC.

Applications• The F-Series is your first and safest choice for field

mount indicators in safe and hazardous area applications. Especially in harsh weatherconditions like rain, snow, salty atmosphers andtemperatures between -40°C up to +80°C (-40°F up to 176°F).

• Applications where nett gas flow calculation atbase conditions is desired. For DIN panel mountindicators, check our D-Series.

FLOWCOMPUTER WITH TEMPERATURE AND PRESSURE

COMPENSATION FOR CORRECTED GAS VOLUME

DA

TAS

HE

ET

F12

6-E

G -

FLO

WC

OM

PU

TER

1

Page 2: FLOWCOMPUTERGeneral information Introduction The flowcomputer Model F126-EG has been developed to calculate the gas volume at normal conditions for generic products, in most cases

General informationIntroductionThe flowcomputer Model F126-EG has been

developed to calculate the gas volume at normal

conditions for generic products, in most cases at

0°C (32 °F) and 1.013 Bar. If desired, any other

temperature or pressure can be set. The corrected

volumetric flow is calculated using the equations

stored in the flowcomputer while a compressibility

factor can be set to approach a real gas behaviour.

DisplayThe display has large 17mm (0.67”) and 8mm

(0.31”) digits which can be set to show flow rate,

total, temperature and pressure. On-screen

engineering units are easily configured from a

comprehensive menu. The accumulated total can

register up to 11 digits and is backed-up in

EEPROM memory every minute.

ConfigurationAll configuration settings are accessed via a

simple operator menu which can be password

protected. Each setting is clearly indicated with an

alphanumerical description, which avoids

confusing abbreviations and baffling codes. Once

familiar with one F-series product, you will be able

to program all models in the series without a

manual. All settings are safely stored in EEPROM

memory in the event of sudden power failure.

Analog output signalThe calculated flow rate is re-transmitted with the

(0)4 - 20mA or 0 - 10V DC output signal. The

output signal is updated eight times per second

with a filter function being available to smoothen

out the signal if desired.

The output value is user defined in relation to the

flow rate, e.g. 4mA equals to 15Nm3/Hr and 20mA

equals to 2000Nm3/Hr. The output signal can be

passive, active or isolated where the passive

output type will loop power the F126-EG as well.

Pulse outputThe scaleable pulse output, reflects the counton the accumulated display. The pulse length isuser defined from 0.001 second up to 9.999seconds. The maximum output frequency is500Hz.The output signal can be passive NPN, activePNP or an isolated electro-mechanical relay.

Signal inputThe flowcomputer measures the uncorrected

volumetric flow, line temperature and pressure.

The F126-EG will accept most pulse and analog

input signals for flow. The analog flow input is

available with lineair and square root calculation

and even as 4 - 20mA input loop powered. For the

temperature measurement, 2 or 3 wire PT100

elements or sensors with a (0)4 - 20mA / 0 - 10V

DC output signal can be used, just as for the

pressure measurement.

CommunicationAll process data and settings can be read and

modified manually or through the Modbus

communication link (RS232 / RS485).

Full Modbus functionality remains available for the

Intrinsically Safe version (TTL).

Hazardous areasThis model has been ATEX and IECEx certified

Intrinsically Safe for gas and dust applications,

with an allowed ambient temperature of

-40°C to +70°C (-40°F to +158°F). A flame proof Ex d enclosure with ATEX certification is alsoavailable.

EnclosuresVarious types of enclosures can be selected,

all ATEX and IECEx approved. As standard the

F126-EG is supplied in a GRP panel mount

enclosure, which can be converted to an IP67 /

NEMA Type4X GRP field mount enclosure by the

addition of a back case. Most popular is our

rugged aluminum field mount enclosure with IP67

/ NEMA Type4X rating. Both European or U.S. cable

gland entry threads are available.

Overview application F126-EG

Analog output Communication link

Flowmeterinput

Temperatureinput

Pressureinput

Pulse output

F126-EG2

Page 3: FLOWCOMPUTERGeneral information Introduction The flowcomputer Model F126-EG has been developed to calculate the gas volume at normal conditions for generic products, in most cases

Dimensions enclosuresAluminum & GRP panel mount enclosure

Aluminum & GRP field / wall mount enclosures

Terminal connections

Display example - 90 x 40mm (3.5” x 1.6”)

TA: (

0)4

- 20m

A*

TU: 0

- 10

V*

CB:

RS2

32

CH

: RS4

85 -

2 w

ire

AB

YZ

RX

DTX

D

CT:

TTL

Intri

nsic

ally

Saf

e

P: re

ed s

witc

h / N

PN

P: c

oil

P: n

amur

P: P

NP

A: (0

)4 -

20m

A

P: a

ctiv

e si

gnal

U: 0

- 10

V

-

0506

PULS

E O

UTP

UT

0102

POW

ER R

EQU

IREM

ENTS

00 -+

PD: 8

- 24

V AC

PD: 8

- 24

V D

C

PM: 1

15 -

230V

AC

PD -

XI: 1

6 - 3

0V D

C +-

+

0304

1011

FLO

WM

ETER

INPU

T

09

+

+ -+

+

+ +

AP: 4

- 20

mA

AA: 4

- 20

mA

AF: 4

- 20

mA

AU: 0

- 10

V

AI: 4

- 20

mA

AB: 0

- 20

mA

0708

ANAL

OG

OU

TPU

T

+II-

+I +U

I U

+II

+II-

+II

+I +U

1314

TEM

PER

ATU

RE

INPU

T /

PRES

SUR

E IN

PUT

1218

19

PRES

SUR

E IN

PUT

1715

16

+I +U

+ +

IA: (

0)4

- 20m

A (w

ith T

P)*

IU: 0

- 10

V (w

ith T

P)*

+I +U

+ +

2728

CO

MM

UN

ICAT

ION

2623

2425

2122

2029

3031

DTR

+12V

CI:

RS4

85 -

4 w

ire

AB

RX

DTX

DD

TR+1

2V

IA: (

0)4

- 20m

A (w

ith T

A/TU

)*

IU: 0

- 10

V (w

ith T

A/TU

)*

+I +U

IA: (

0)4

- 20m

A (w

ith T

A/TU

+PF/

PM)*

*

IU: 0

- 10

V (w

ith T

A/TU

+PF/

PM)*

*

+I +U

A - P

L: 4

- 20

mA

+I

PL: i

nput

loop

pow

ered

(term

inal

s G

ND

- 1

- 2 a

re n

ot a

vaila

ble)

AP: 8

- 30

V D

CO

utpu

t loo

p po

wer

ed

PB /

PC: b

atte

ry p

ower

edIn

tern

al lo

ng li

fe L

ithiu

m b

atte

ry

-+

PX: 8

- 30

V D

C

+

==

OT:

pas

sive

tran

s.

OA:

act

ive

24V

DC

OR

: mec

h. re

lay

+

Not

e: O

nly

avai

labl

e w

ith T

ype:

P

-+

ZB: B

ackl

ight

: 12

- 24V

DC

* N

ote:

If T

A / T

U is

use

d th

en IA

/ IU

use

term

inal

17

- 18.

If

TP

is u

sed

then

IA /

IU u

se te

rmin

al 1

2 - 1

3 - 1

4.**

Not

e: If

PF

/ PM

and

TA

/ TU

is u

sed

then

IA /

IU u

se te

rmin

al 1

7 on

ly.

-+

PF: 2

4V A

C

PF: 2

4V D

C

TP: P

T100

2-w

ire

TEM

PER

ATU

RE

INPU

T

+

TP: P

T100

3-w

ire

+

F126-EG 3

130 mm (5.12")

120

mm

(4.7

2")

31 mm(1.22")

29 mm(1.14")

115 (4.53")

98

(3.8

6")

panel cut-outHB & HC enclosures

75 mm (2.95")

130 mm (5.12")

112 mm (4.40")

60 m

m (2

.36"

)

120

mm

(4.7

2")

M20 x 1,5PG9 PG9

30mm 30mm

22,5

0mm

M20 x 1,5M16 x 1,5 M16 x 1,5

30mm 30mm

22,5

0mm

M20 x 1,5

22,5

0mm

M20 x 1,5 M20 x 1,5

25mm 25mm

22,5

0mm

1/2"NPT

0.9"

1/2"NPT1/2"NPT 1/2"NPT

1.18" 1.18"

0.9"

HA

HM

HN

HO

HD

HP

HE

HT

HF

HU

HG

HV

HH

6 x M12

12mm 12mm

24mm24mm36mm36mm

14m

m17

mm

Ø12

12mm 12mm

24mm24mm36mm36mm

14m

m17

mm

HK

22,5

0mm

30mm 30mm

Ø16 Ø16Ø20

HJ

22,5

0mm

(0.9

")30mm (1.18") 30mm (1.18")

Ø22 ( 7/8") Ø22 ( 7/8")Ø22 ( 7/8")

22,5

0mm

(0.9

")

Ø22 ( 7/8")

22,5

0mm

25mm 25mm

Ø20 Ø20

Aluminum GRP

Flat bottom, no holes available.

4 x M20 x 1.5

15mm 15mm

HZ

16m

m15

mm

38mm

1/2"NPT 1/2"NPT

1.18" 1.18"

0.9"

HL

Ø 7mm (0.27") Ø 7mm (0.27")

Page 4: FLOWCOMPUTERGeneral information Introduction The flowcomputer Model F126-EG has been developed to calculate the gas volume at normal conditions for generic products, in most cases

Typical wiring diagram F126-P-AP-CH-EG-IA-OT-(PX)-TA Typical wiring diagram F126-P-AI-CI-EG-IA-OA-PD-TA

0001

0910

1112

1413

1817

Common ground

Common ground

Common ground

Common ground

Signal

Supply *

Signal

Signal

TERMINAL CONNECTORSF100 - series

0708

Circ

uit d

epen

ds o

n ty

pe o

f sig

nal

Supply *

Circ

uit d

epen

ds o

n ty

pe o

f sig

nal

2826

3130

29

+

-

Y

Common ground

Z

A

B

*Supply voltage: 1.2 / 3.2 / 8.2 / 12 / 24V DC to sensor

Analog output type AI: passive isolated 4 - 20mA

8 - 30V DC

indicator

Flowmeter input type: Ppulse

8 - 24V DC

+

-

Pressure inputtype IA:

(0)4 - 20mA

Power supply type PD: 8 - 24V AC / DC

Modbus communication type CI: RS485 - 4 wire

24V AC / DC POWER SUPPLY

Temperature inputtype TA:

(0)4 - 20mA

0605Common ground

Pulse output type OA:active 24V DC pulse

+

- e.g. counter123456

0910

1112

1413

Common ground

Common ground

Signal

Supply *

Signal

TERMINAL CONNECTORSF100 - series

0708

Common ground

Circ

uit d

epen

ds o

n ty

pe o

f sig

nal

Supply *

Circ

uit d

epen

ds o

n ty

pe o

f sig

nal

2826

29

8 - 30V DC

+

-

A

Common ground

B

*Supply voltage: 1.2 / 3.2V DC to sensor

indicator

Modbus communication type CH: RS485 - 2 wire

Analog output type AP: passive 4 - 20mA (loop powered)

1817Common ground

Signal

Temperature inputtype TA:

(0)4 - 20mA

Flowmeter input type: Ppulse

OUTPUT LOOP POWERED

Pressure inputtype IA:

(0)4 - 20mA

Common ground 0001

0605Common ground

123456e.g. counter

Pulse output type OT:

passive transistor

Power supply type PX: 8 - 30V DC

(not used in this example)

F126-EG4

Page 5: FLOWCOMPUTERGeneral information Introduction The flowcomputer Model F126-EG has been developed to calculate the gas volume at normal conditions for generic products, in most cases

Typical wiring diagram F126-A-AA-CB-EG-IA-OX-PM-TP Typical wiring diagram F126-P-AI-CI-EG-IA-OR-PM-TA00

0102

TERMINAL CONNECTORSF100 - series

0708

Common ground

Common ground

Main supply

2827

2629

Common ground

RXD

TXD

Analog output type AA:active 4 - 20mAindicator

+

-

Modbus communication type CB: RS232

L1

NPower supply type PM:

115 - 230V AC

0910

1112

1413

Common ground

Common ground

Signal

Supply *

Signal

Circ

uit d

epen

ds o

n ty

pe o

f sig

nal

Supply *

Circ

uit d

epen

ds o

n ty

pe o

f sig

nal

2221

20

Supply

Signal

Signal

Temperature input type TP:

PT100 3 - wire

DTR+12V

80 - 230V AC POWER SUPPLY

*Supply voltage: 3.2 / 8.2 / 12 / 24V DC to sensor

Flowmeter input type A:(0)4 - 20mA

Pressure input type IA:(0)4 - 20mA

0605

Note: Digital output not available with Type: A / U

0001

02

TERMINAL CONNECTORSF100 - series

L1

0708

Common ground

Main supply

26

8 - 30V DC

+

-

Common ground

N

e.g. indicator

Power supply type PM:115 - 230V AC

Analog output type AI:passive isolated 4 - 20mA

2831

3029

Y

Z

A

B

Modbus communication type CI: RS485 - 4 wire

115 - 230V AC POWER SUPPLY

*Supply voltage: 3.2 / 8.2 / 12 / 24V DC to sensor

0910

11

Common ground

Signal

Supply *

Circ

uit d

epen

ds o

n ty

pe o

f sig

nal

Flowmeter input type: Ppulse

1214

13

Common ground

Signal

Circ

uit d

epen

ds o

n ty

pe o

f sig

nal

Supply *

Temperature input type TA:

(0)4 - 20mA

17

Signal

Pressure inputtype IA:

(0)4 - 20mA

0605

e.g. counter123456

Pulse output type OR:mechanic relay

F126-EG 5

Page 6: FLOWCOMPUTERGeneral information Introduction The flowcomputer Model F126-EG has been developed to calculate the gas volume at normal conditions for generic products, in most cases

F126-EG6

Hazardous area applicationsThe F126-EG-XI has been certified accordingATEX and IECEx by DEKRA for use in IntrinsicallySafe applications with an ambient temperatureof -40°C to +70°C (-40°F to +158°F). • The ATEX markings for gas and dust

applications are:II 1 G Ex ia IIB/IIC T4 GaII 1 D Ex ia IIIC T100 °C Da.

• The IECEx markings for gas and dustapplications are: Ex ia IIC/IIB T4 Ga and Ex ia IIIC T100 °C Da.

It is allowed to connect up to six barriers inIIB/IIIC applications or one barrier in IICapplications. Consult the certificate for themaximum input and output values of thecircuits. Full functionality of the F126-EGremains available, including 4 - 20mA outputaccording to the flow rate and Modbuscommunication (type CT). Power supply typePD-XI offers a 8.2V sensor supply e.g. for oneNamur sensor and two analog sensors. An ATEX approved flame proof Ex d enclosure isavailable as well. Please contact your supplierfor further details.

Certificate of conformity KEMA 03ATEX1074 X• IECEx DEK 11.0042X

TERMINAL CONNECTORSF100-series

2221

20

Supply

Signal

Signal

Temperature input type TP:

PT100 3 - wire

HAZARDOUS AREA SAFE AREA

0910

1112

1413

Common ground

Common ground

Signal

Signal

Supply *

Circ

uit d

epen

ds o

n ty

pe o

f sig

nal Supply *

Circ

uit d

epen

ds o

n ty

pe o

f sig

nal

0708

Flow meter input type: Ppulse

Common ground

* Note sensor supply voltage: 1.2V DC for coil sensors or 3.2V DC for other pulse sensors.

Ci is negligiblysmall

+

-

Uo=max 30V

Io=max 100mA

Po=max 750mW

Ci is negligiblysmall

Pressure input type IA:(0)4 - 20mA

Analog output type AP:passive 4 - 20mA

(not used in this example).

Modbus communication type CT: TTLPossible for battery powered applications (not used in this example).

Please note: type AP may be used in combination with the battery (type PC), but only in IIB applications!

AP will power the unit (output loop powered); the battery will be disabled automatically till power

is disconnected).

REPEATERFor example

MTL 5541

0506

Common ground

Pulse output type OT: passive transistor

(not used in this example)

Note: above values are safety values.Consult the technical specification for operational values.

Configuration example IIB / IIIC and IIC - F126-P-(AP)-(CT)-EG-IA-(OT)-PC-TP-XI - Battery powered unit

Page 7: FLOWCOMPUTERGeneral information Introduction The flowcomputer Model F126-EG has been developed to calculate the gas volume at normal conditions for generic products, in most cases

Configuration example IIB / IIIC - F126-P-AP-CT-EG-IA-OT-(PX)-TP-XI - Output loop powered

TERMINAL CONNECTORSF100-series

2221

20

Supply

Signal

Signal

Temperature input type TP:

PT100 3 - wire

HAZARDOUS AREA SAFE AREA

1011

1214

13

Common ground

Common ground

Signal

Signal

Supply *

Circ

uit d

epen

ds o

n ty

pe o

f sig

nal Supply *

Circ

uit d

epen

ds o

n ty

pe o

f sig

nal

Analog output type AP:passive 4 - 20mA (output loop powered)

RXD

Common ground

TXD

2826

29

Ci = 17nF

Flow meter input type: Ppulse

Common ground

DTR+12V

27

ISOLATOR:I.S. Certified Isolator

TTL to RS232 / RS422 / TTL

For example: MTL5051

+

-

POWER SUPPLYe.g. MTL 5525

and / or REPEATER

e.g. MTL 5541

Uo=max 30V

Io=max 100mA

Po=max 750mW

Uo=max 30V

Io=max 250mA

Po=max 850mW

+

-

e.g. indicator

e.g. PC

e.g. indicator

Modbus communication type CT: TTL

* Note sensor supply voltage: 1.2V DC for coil sensors or 3.2V DC for other pulse sensors.

Ci is negligiblysmall

+

-

Uo=max 30V

Io=max 100mA

Po=max 750mW

Ci is negligiblysmall

Pressure input type IA:(0)4 - 20mA

REPEATERFor example

MTL 5541

Common ground

123456e.g. counter

+

-

POWER SUPPLYe.g. MTL 5525

or SWITCH INTERFACE

e.g. MTL 5511

Uo=max 30V

Io=max 100mA

Po=max 750mWe.g. counter

123456Pulse output type OT:passive transistor

Ci is negligiblysmall

Note: above values are safety values.Consult the technical specification for operational values.

Common groundPX: Not used in this example

0907

0805

06

00

01

F126-EG 7

Page 8: FLOWCOMPUTERGeneral information Introduction The flowcomputer Model F126-EG has been developed to calculate the gas volume at normal conditions for generic products, in most cases

Configuration example IIB / IIIC and IIC - F126-A-AF-(CT)-EG-IA-OX-PD-TA-XI - Power requirement 16 - 30V DC

TERMINAL CONNECTORSF100-series

HAZARDOUS AREA SAFE AREA

Ci is negligibly small1817

Common ground

Common ground

Signal

TOTAL Co OF ALL CONNECTEDANALOG APPARATUS IN IICAPPLICATIONS MAY NOT

EXCEED 66nF MINUS 17nF(17nF IS USED BY THE ANALOG

OUTPUT SIGNAL TERMINAL 7 + 8).

Main supply

Circ

uit d

epen

ds o

n ty

pe o

f sig

nal

Power supply type PD: 16 - 30V DC (please note: PD and battery supply (type PC) is NOT allowed in IIC applications).

RXD

Common ground

TXD

2826

29

Ci = 17nF

Analog output type AF:passive floating 4 - 20mA

1011

1214

13

Common ground

Common ground

Signal

Signal

Supply *

Circ

uit d

epen

ds o

n ty

pe o

f sig

nal Supply *

Circ

uit d

epen

ds o

n ty

pe o

f sig

nal

Ci is negligiblysmall

Flow meter input type: A(0)4 - 20mA

Ci is negligiblysmall

Temperature input type: TA(0)4 - 20mA

Modbus communication type CT: TTLPlease note: communciation type CT is not allowed in IIC applications.

DTR+12V

27

Pressure input type IA:

(0)4 - 20mA

ISOLATOR:I.S. Certified Isolator

TTL to RS232 / RS422 / TTL

For example: MTL5051

Uo=max 30V

Io=max 250mA

Po=max 850mW

+

-

POWER SUPPLY

For example MTL 5525

Uo=max 30V

Io=max 100mA

Po=max 750mW

+

-

e.g. PC

e.g. indicator

* Note power supply type PD: the supply voltage to pulse sensors is maximum 8.7V (Uo=max 8.7V Io=max 25mA Po=max 150mW) and to analog sensors as connected to terminal 1 (internally linked).

0209

0708

0

001

Note: above values are safety values.Consult the technical specification for operational values.

* Note: Communication only allowed when configured as IIB / IIIC.

Note: Digital output not available with Type: A / U

F126-EG8

Page 9: FLOWCOMPUTERGeneral information Introduction The flowcomputer Model F126-EG has been developed to calculate the gas volume at normal conditions for generic products, in most cases

Configuration example IIB / IIIC - F126-A-AF-CT-EG-IA-OX-(PC)-(PD)-TA-XI - Power requirement 16 - 30V DC or battery powered

TERMINAL CONNECTORSF100-series

HAZARDOUS AREA SAFE AREA

Ci = 17nF

Ci is negligibly small

1011

1214

1318

17

Common ground

Common ground

Common ground

Common ground

Signal

Signal

Signal

Supply *

Main supply

Circ

uit d

epen

ds o

n ty

pe o

f sig

nal

Circ

uit d

epen

ds o

n ty

pe o

f sig

nal

Supply *

Circ

uit d

epen

ds o

n ty

pe o

f sig

nal

Power supply type PD: 16 - 30V DC

Analog output type AF:passive floating 4 - 20mA

RXD

Common ground

TXD

2826

29

DTR+12V

27

Pressure input type IA:(0)4 - 20mA

+

-

ISOLATOR:I.S. Certified Isolator

TTL to RS232 / RS422 / TTL

For example: MTL5051

+

-

POWER SUPPLYe.g. MTL 5525

and / or REPEATER

e.g. MTL 5541

Uo=max 30V

Io=max 100mA

Po=max 750mW

Uo=max 30V

Io=max 250mA

Po=max 850mW

Uo=max 30V

Io=max 100mA

Po=max 750mW

+

-

Uo=max 30V

Io=max 100mA

Po=max 750mW

+

-

POWER SUPPLY

For example MTL 5525

Uo=max 30V

Io=max 100mA

Po=max 750mW

+

-

Uo=max 30V

Io=max 100mA

Po=max 750mW

+

-

e.g. indicator

e.g. PC

e.g. indicator

Modbus communication type CT: TTL

Due to analog output type AF, the unit has to be powered with battery type PC or with external power supply type PD.

Ci is negligiblysmall

Ci is negligiblysmall

* Note power supply type PD: the supply voltage to pulse sensors is maximum 8.7V (Uo=max 8.7V Io=max 25mA Po=max 150mW) and to analog sensors as connected to terminal 1 (internally linked).

Temperature input type TA:(0)4 - 20mA

Flow meter input type A:(0)4 - 20mA

Note: above values are safety values.Consult the technical specification for operational values.

Note: above values are safety values.Consult the technical specification for operational values.

0209

0708

0

001

REPEATERFor example

MTL 5541

REPEATERFor example

MTL 5541

REPEATERFor example

MTL 5541

Note: Digital output not available with Type: A / U

F126-EG 9

Page 10: FLOWCOMPUTERGeneral information Introduction The flowcomputer Model F126-EG has been developed to calculate the gas volume at normal conditions for generic products, in most cases

Technical specificationGeneralDisplayType High intensity reflective numeric and

alphanumeric LCD, UV-resistant.Dimensions 90 x 40mm (3.5” x 1.6”).Digits Seven 17mm (0.67") and eleven 8mm (0.31") digits.

Various symbols and measuring units.Refresh rate User definable: fast, 1sec , 3sec, 15sec, 30sec, off.Option ZB Transflective LCD with white LED-backlight.

Good readings in full sunlight and darkness. Note ZB Only available for safe area applications.

Ambient temperatureSafe areas -40°C to +80°C (-40°F to +176°F).Intrinsically Safe -40°C to +70°C (-40°F to +158°F).

Power requirementsType AP Analog output loop powerd, 8 - 30V DC.

Power consumption max 0.5 Watt.Type PB Long life Lithium battery - life-time depends upon

settings and configuration - up to 5 years.(requires PD, PL or PX)

Type PC Intrinsically Safe long life lithium battery - life-time depends upon settings and configuration - up to 5 years. (requires XI and PD or PX)

Type PD 8 - 24V AC / DC ± 10%. Power consumption max. 10 Watt. Intrinsically Safe: 16 - 30V DC; power consumption max. 0.75 Watt.

Type PF 24V AC / DC ± 10%. Power consumption max. 15 Watt.Type PL Input loop powered from sensor signal 4 - 20mA

(type “A”) - requires types AI and OT (not Xi).Type PM 115 - 230V AC ± 10%. Power consumption max. 15 Watt.Type PX 8 - 30V DC. Power consumption max. 0.5 Watt. Type ZB 12 - 24V DC ± 10%. Power consumption max. 1 Watt.

Note PB/PF/PM Not available Intrinsically Safe.Note PF/PM The total consumption of the sensors and outputs

may not exceed 400mA @ 24V.Note For Intrinsically Safe applications, consult the safety

values in the certificate.

Sensor excitationType PB/PC/PX 3V DC for pulse signals and 1.2V DC for coil pick-up.

Note This is not a real sensor supply. Only suitable for sensors with a very low power consumption like coils(sine wave) and reed-switches.

Type PD 1.2 / 3 / 8.2 / 12 / 24V DC - max. 50mA @ 24V DC.Type PD-XI 1.2 / 3 / 8.2V DC - max. 7mA @ 8.2V DC and mains

power supply voltage (as connected to terminal 1).Note In case PD-XI and signal A or U: the sensor supply

voltage is according to the power supply voltage connected to terminal 1. The sensor supply of the second analog input is fixed 8.2V DC.

Type PF / PM 1.2 / 3 / 8.2 / 12 / 24V DC - max. 400mA @ 24V DC.

Terminal connectionsType Removable plug-in terminal strip.

Wire max. 1.5mm2 and 2.5mm2.

Data protectionType EEPROM backup of all settings. Backup of running

totals every minute. Data retention at least 10 years.Password Configuration settings can be password protected.

Directives & StandardsEMC Directive 2014/30/EU, FCC 47 CFR part 15.Low voltage Directive 2014/35/EURoHS Directive 2011/65/EUATEX / IECEx Directive 2014/34/EU, IEC 600079-0, IEC 60079-11.IP & NEMA EN 60529 & NEMA 250

EnclosureGeneralWindow Polycarbonate window.Sealing Silicone.Control keys Three industrial micro-switch keys. UV-resistant

silicone keypad.

Aluminum wall / field mount enclosuresGeneral Die-cast aluminum wall/field mount enclosure IP67 /

NEMA Type4X with 2-component UV-resistant coating.Dimensions 130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.Weight 1100 gr.

Type HA Cable entry: 2 x PG9 and 1 x M20. Type HL Cable entry: 2 x 1/2" NPT.Type HM Cable entry: 2 x M16 and 1 x M20. Type HN Cable entry: 1 x M20. Type HO Cable entry: 2 x M20. Type HP Cable entry: 6 x M12. Type HT Cable entry: 1 x 1/2" NPT.Type HU Cable entry: 3 x 1/2" NPT.Type HV Cable entry: 4 x M20. Type HZ Cable entry: no holes.

GRP wall / field mount enclosuresGeneral GRP wall/field mount enclosure IP67 / NEMA Type4X,

UV-resistant and flame retardant. Dimensions 130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.Weight 600 gr.

Type HD Cable entry: no holes.Type HE Cable entry: 2 x Ø 16mm and 1 x Ø 20mm.Type HF Cable entry: 1 x Ø 22mm (7/8").Type HG Cable entry: 2 x Ø 20mm. Type HH Cable entry: 6 x Ø 12mm. Type HJ Cable entry: 3 x Ø 22mm (7/8"). Type HK Flat bottom, cable entry: no holes.

Panel mount enclosuresDimensions 130 x 120 x 60mm (5.12" x 4.72" x 2.36") - W x H x D.Panel cut-out 115 x 98mm (4.53" x 3.86") L x H.

Type HB Die-cast alu. panel mount enclosure IP65 / NEMA Type4X.

Weight 600 gr.Type HC GRP panel mount enclosure IP65 / NEMA Type4X,

UV-resistant and flame retardant.Weight 450 gr.

Hazardous areaIntrinsically Safe (Type XI)ATEX II 1 G Ex ia IIB/IIC T4 Ga.certification II 1 D Ex ia IIIC T100 °C Da.IECEx Ex ia IIC/IIB T4 Ga.certification Ex ia IIIC T100 °C Da.Ambient Ta -40°C to +70°C (-40°F to +158°F).

Explosion proof (Type XF)ATEX certification II 2 G / Ex d IIB T5 Gb.

II 2 D / Ex t IIIB T100 °C Db.Type XF Dimensions of enclosure: 300 x 250 x 200mm

(11.8" x 9.9" x 7.9") L x H x D.Weight Appr. 15kg.Note IECEx available on request.

10

Page 11: FLOWCOMPUTERGeneral information Introduction The flowcomputer Model F126-EG has been developed to calculate the gas volume at normal conditions for generic products, in most cases

Signal inputsFlowmeterType P Coil / sine wave (HI: 20mVpp or LO: 80mVpp -

sensitivity selectable), NPN/PNP, open collector, reed-switch, Namur, active pulse signals 8 - 12 and 24V DC.

Frequency Minimum 0Hz - maximum 7kHz for total and flow rate. Maximum frequency depends on signal type and internal low-pass filter. E.g. reed switch with low-pass filter: max. frequency 120Hz.

K-Factor 0.000010 - 9,999,999 with variable decimal position.Low-pass filter Available for all pulse signals.Option ZF coil sensitivity 10mVpp.

Type A (0)4 - 20mA. Analog input signal can be scaled to anydesired range within 0 - 20mA.

Type U 0 - 10V DC. Analog input signal can be scaled to any desired range within 0 - 10V DC.

Accuracy Resolution: 14 bit. Error < 0.025mA / ± 0.125% FS. Low level cut-off programmable.

Span 0.000010 - 9,999,999 with variable decimal position.Update time Four times per second.Voltage drop Type A: 2.5V @ 20mA.Load impedance Type U: 3kOhm.Relationship Linear and square root calculation.Note For signal type A and U: external power to sensor is

required; e.g. type PD.

TemperatureAccuracy Resolution: 14 bit. Error < 0.025mA / ± 0.125% FS.

Low level cut-off programmable.Update time Four times per second.Type TA (0)4 - 20mA. Analog input signal can be scaled to

any desired range within 0 - 20mA.Span 0.000010 - 9,999,999 K with variable decimal position.Offset 0.00 - 99,999.99 K.Voltage drop 2.5V @ 20mA.

Type TP 2 or 3 wire PT100.Range -100°C to +200°C (-148°F to 392°F).

Accuracy 3°C (5.4°F).Option ZV Range: -200°C to +800°C (-328°F to 1832°F).

Accuracy 3°C (5.4°F).Type TU 0 - 10V DC. Analog input signal can be scaled to

any desired range within 0 - 10V DC.Span 0.000010 - 9,999,999 K with variable decimal position.Offset 0.00 - 99,999.99 K.Load impedance 3kOhm.

Note 1 For signal TA and TU: power supply to temperature sensor is required; e.g. PD.

PressureAccuracy Resolution: 14 bit. Error < 0.025mA / ± 0.125% FS.

Low level cut-off programmable.Update time Four times per second.Type IA (0)4 - 20mA. Analog input signal can be scaled to any

desired range within 0 - 20mA.Span 0.000010 - 9,999,999 with variable decimal position.Offset 0.000 - 9,999.999.Voltage drop 2.5V @ 20mA.

Type IU 0 - 10V DC. Analog input signal can be scaled to any desired range within 0 - 10V DC.

Span 0.000010 - 9,999,999 with variable decimal position.Load impedance 3kOhm.Note For signal type IA and IU: external power to sensor

required; e.g. PD.

OperationalFlow equationsType EG Corrected gas volume.

Normal press. Default: 1.013 bar.Normal temp. Default: 273.15K (0°C / 32°F)

Operator functionsDisplayed • Compensated flow rate.functions • Compensated total and accumulated total.

• Actual line temperature / pressure.• Reset total by pressing the CLEAR-key twice.

TotalDigits 7 digits.Units L, m3, GAL, USGAL, kg, lb, bbl, no unit.Decimals 0 - 1 - 2 or 3. Note Total can be reset to zero.

Accumulated totalDigits 11 digits.Units / decimals According to selection for total.Note Can not be reset to zero.

Flow rateDigits 7 digits.Units mL, L, m3, Gallons, kg, Ton, lb, bl, cf, RND, ft3, scf,

Nm3, Nl, igal - no units.Decimals 0 - 1 - 2 or 3.Time units /sec - /min - /hr - /day.

Line temperatureDigits 6 digits.Units °C, °F or K.Decimals 1.

Line pressureDigits 6 digits.Units mbar, bar, PSI, no-unit.Decimals 1.

Signal outputsDigital outputFunction Pulse output - transmitting accumulated total.Frequency Max. 500Hz. Pulse length user definable between

0.001 second up to 9.999 seconds.Type OA One active 24V DC transistor output (PNP);

max. 50mA per output (requires P + PD, PF, PM or PX).Type OR One electro-mechanical relay output - isolated;

max. switch power 230V AC (N.O.) - 0.5A per relay (requires P + PF or PM).

Type OT One passive transistor output (NPN) - not isolated. Max. 50V DC - 300mA per output. (requires P)

Analog outputFunction Transmitting compensated flow rate.Accuracy 10 bit. Error < 0.05%. Analog output signal can be

scaled to any desired range.Update time Eight times per second.Type AA Active 4 - 20mA output (requires PD, PF, PM or PX).Type AB Active 0 - 20mA output (requires PD, PF, PM or PX).Type AF Passive floating 4 - 20mA output (requires XI + PD or PX).

Type AI Passive galvanically isolated 4 - 20mA output - also available for battery powered models.

Type AP Passive 4 - 20mA output - not isolated. Unit will beloop powered.

Type AU Active 0 - 10V DC output (requires PD, PF, PM or PX).

Communication optionFunction Reading display information, reading / writing all

configuration settings.Protocol Modbus RTU.Speed 1200 - 2400 - 4800 - 9600 baud.Addressing Maximum 255 addresses.Type CB RS232Type CH RS485 2-wire Type CI RS485 4-wireType CT TTL Intrinsically Safe. Formula Qnormal = Q x ( P ) x ( Tnormal ) x ( Cnormal )Pnormal T C .

11

Page 12: FLOWCOMPUTERGeneral information Introduction The flowcomputer Model F126-EG has been developed to calculate the gas volume at normal conditions for generic products, in most cases

Copy

righ

t: F

luid

wel

l bv

- 201

7 - F

126E

G-D

ATA-

EN-V

1704

Ordering information - Standard configuration: F126-P-AP-CX-EG-HC-IA-OT-PX-TA-XX-ZX.Ordering information: F126 -_ -A _ -C _ -EG -H _ -I _ -OT -P _ -T _ -X _ -Z _Flowmeter input signalA (0)4 - 20mA input. (Digital ouput is pending)P Pulse input: coil, npn, pnp, namur, reed-switch.U 0 - 10V DC input. (Digital ouput is pending)Analog output signalAA Active 4 - 20mA output - requires PD, PF, PM or PX.AB Active 0 - 20mA output - requires PD, PF, PM or PX.AF I.S. floating 4 - 20mA output - requires XI + PD or PX.AI Isolated 4 - 20mA output.AP Passive 4 - 20mA output, loop powered unit.AU Active 0 - 10V DC output - requires PD, PF, PM or PX.CommunicationCB Communication RS232 - Modbus RTU.CH Communication RS485 - 2wire - Modbus RTU.CI Communication RS485 - 4 wire - Modbus RTU.CT Intrinsically Safe TTL - Modbus RTU.CX No communication.Flow equationsEG Corrected gas volume.Panel mount enclosures - IP65 / NEMA Type4XHB Aluminum enclosure.HC GRP enclosure.GRP field / wall mount enclosures - IP67 / NEMA Type4XHD Cable entry: no holes.HE Cable entry: 2 x Ø 16mm & 1 x Ø 20mm.HF Cable entry: 1 x Ø 22mm (7/8”).HG Cable entry: 2 x Ø 20mm.HH Cable entry: 6 x Ø 12mm.HJ Cable entry: 3 x Ø 22mm (7/8”).HK Flat bottom, cable entry: no holes.Aluminum field / wall mount enclosures - IP67 / NEMA Type4XHA Cable entry: 2 x PG9 + 1 x M20.HL Cable entry: 2 x 1/2”NPT.HM Cable entry: 2 x M16 + 1 x M20.HN Cable entry: 1 x M20.HO Cable entry: 2 x M20.HP Cable entry: 6 x M12.HT Cable entry: 1 x 1/2”NPT.HU Cable entry: 3 x 1/2”NPT.HV Cable entry: 4 x M20.HZ Cable entry: no holes.Pressure input signalIA (0)4 - 20mA input.IU 0 - 10V DC input.Digital output signalsOA One active transistor outputs - requires P and PD, PF, PM or PX.OR One mechanical relay outputs - requires P and PF or PM.OT One passive transistor outputs - standard configuration. rreeqquuiirreess PP Power requirementsPD 8 - 24V AC/DC + sensor supply - with XI: 16 - 30V DC.PF 24V AC/DC + sensor supply.PL Input loop powered from sensor signal type “A” - requires AI (not XI).PM 115 - 230V AC + sensor supply.PX Basic power supply 8 - 30V DC (no real sensor supply).Additional battery supply (optional)PB Lithium battery powered - requires PD, PL or PX.PC Lithium battery powered - Intrinsically Safe - requires XI, and PD or PX.Temperature input signalTA (0)4 - 20mA input.TP PT100 input.TU 0 - 10V DC input.Hazardous areaXI Intrinsically Safe, according ATEX and IECEx.XF Ex d enclosure - 3 keys according ATEX.XX Safe area only.Other optionsZB Backlight.ZF Coil input 10mVpp.ZV PRTD-range -200°C / +800°C.ZX No options.

The bold marked text contains the standard configuration. / Available Intrinsically Safe.

12

Specifications are subject to change without notice.

Fluidwell bvP.O. Box 65460 AA - Veghel - The NetherlandsTelephone: +31 (0)413 343 786Telefax: +31 (0)413 363 443email: [email protected] Internet: www.fluidwell.com