Advantages• Robust IP67 (NEMA Type4X) field enclosure.
It is so rugged, you can even stand on it!• Intrinsically Safe available - ATEX and IECEx
approval for gas and dust applications.• Programming can be done by your own crew, with
the sensible menu-driven structure, saving costand irritation. Know one, know them all!
• Very diverse mounting possibilities: walls, pipes,panels or directly onto outdoor sensors!
Features• Calculates compensated flow rate, total and
accumulated total.• Displays actual line pressure and temperature.• Selectable on-screen engineering units; volumetric
or mass.• 7 digit resettable total.• 11 digit accumulated total.• Explosion/flame proof available.• Full Modbus communication RS232/485/TTL.• Loop or battery powered, 8 - 24V AC/DC or
115 - 230V AC power supply.• LED backlight option.
Signal output• (0)4 - 20mA / 0 - 10V DC according to
compensated flow rate.• Scaled pulse output according to accumulated
total.
Signal inputFlow• Ability to process all types of flowmeter signals:
Reed-switch, NAMUR, NPN/PNP pulse, Sine wave(coil), Active pulse signals, (0)4 - 20mA, 0 - 10V DC.
Temperature• PT100 - 2 or 3 wire, (0)4 - 20mA, 0 - 10V DC.Pressure• (0)4 - 20mA, 0 - 10V DC.
Applications• The F-Series is your first and safest choice for field
mount indicators in safe and hazardous area applications. Especially in harsh weatherconditions like rain, snow, salty atmosphers andtemperatures between -40°C up to +80°C (-40°F up to 176°F).
• Applications where nett gas flow calculation atbase conditions is desired. For DIN panel mountindicators, check our D-Series.
FLOWCOMPUTER WITH TEMPERATURE AND PRESSURE
COMPENSATION FOR CORRECTED GAS VOLUME
DA
TAS
HE
ET
F12
6-E
G -
FLO
WC
OM
PU
TER
1
General informationIntroductionThe flowcomputer Model F126-EG has been
developed to calculate the gas volume at normal
conditions for generic products, in most cases at
0°C (32 °F) and 1.013 Bar. If desired, any other
temperature or pressure can be set. The corrected
volumetric flow is calculated using the equations
stored in the flowcomputer while a compressibility
factor can be set to approach a real gas behaviour.
DisplayThe display has large 17mm (0.67”) and 8mm
(0.31”) digits which can be set to show flow rate,
total, temperature and pressure. On-screen
engineering units are easily configured from a
comprehensive menu. The accumulated total can
register up to 11 digits and is backed-up in
EEPROM memory every minute.
ConfigurationAll configuration settings are accessed via a
simple operator menu which can be password
protected. Each setting is clearly indicated with an
alphanumerical description, which avoids
confusing abbreviations and baffling codes. Once
familiar with one F-series product, you will be able
to program all models in the series without a
manual. All settings are safely stored in EEPROM
memory in the event of sudden power failure.
Analog output signalThe calculated flow rate is re-transmitted with the
(0)4 - 20mA or 0 - 10V DC output signal. The
output signal is updated eight times per second
with a filter function being available to smoothen
out the signal if desired.
The output value is user defined in relation to the
flow rate, e.g. 4mA equals to 15Nm3/Hr and 20mA
equals to 2000Nm3/Hr. The output signal can be
passive, active or isolated where the passive
output type will loop power the F126-EG as well.
Pulse outputThe scaleable pulse output, reflects the counton the accumulated display. The pulse length isuser defined from 0.001 second up to 9.999seconds. The maximum output frequency is500Hz.The output signal can be passive NPN, activePNP or an isolated electro-mechanical relay.
Signal inputThe flowcomputer measures the uncorrected
volumetric flow, line temperature and pressure.
The F126-EG will accept most pulse and analog
input signals for flow. The analog flow input is
available with lineair and square root calculation
and even as 4 - 20mA input loop powered. For the
temperature measurement, 2 or 3 wire PT100
elements or sensors with a (0)4 - 20mA / 0 - 10V
DC output signal can be used, just as for the
pressure measurement.
CommunicationAll process data and settings can be read and
modified manually or through the Modbus
communication link (RS232 / RS485).
Full Modbus functionality remains available for the
Intrinsically Safe version (TTL).
Hazardous areasThis model has been ATEX and IECEx certified
Intrinsically Safe for gas and dust applications,
with an allowed ambient temperature of
-40°C to +70°C (-40°F to +158°F). A flame proof Ex d enclosure with ATEX certification is alsoavailable.
EnclosuresVarious types of enclosures can be selected,
all ATEX and IECEx approved. As standard the
F126-EG is supplied in a GRP panel mount
enclosure, which can be converted to an IP67 /
NEMA Type4X GRP field mount enclosure by the
addition of a back case. Most popular is our
rugged aluminum field mount enclosure with IP67
/ NEMA Type4X rating. Both European or U.S. cable
gland entry threads are available.
Overview application F126-EG
Analog output Communication link
Flowmeterinput
Temperatureinput
Pressureinput
Pulse output
F126-EG2
Dimensions enclosuresAluminum & GRP panel mount enclosure
Aluminum & GRP field / wall mount enclosures
Terminal connections
Display example - 90 x 40mm (3.5” x 1.6”)
TA: (
0)4
- 20m
A*
TU: 0
- 10
V*
CB:
RS2
32
CH
: RS4
85 -
2 w
ire
AB
YZ
RX
DTX
D
CT:
TTL
Intri
nsic
ally
Saf
e
P: re
ed s
witc
h / N
PN
P: c
oil
P: n
amur
P: P
NP
A: (0
)4 -
20m
A
P: a
ctiv
e si
gnal
U: 0
- 10
V
-
0506
PULS
E O
UTP
UT
0102
POW
ER R
EQU
IREM
ENTS
00 -+
PD: 8
- 24
V AC
PD: 8
- 24
V D
C
PM: 1
15 -
230V
AC
PD -
XI: 1
6 - 3
0V D
C +-
+
0304
1011
FLO
WM
ETER
INPU
T
09
+
+ -+
+
+ +
AP: 4
- 20
mA
AA: 4
- 20
mA
AF: 4
- 20
mA
AU: 0
- 10
V
AI: 4
- 20
mA
AB: 0
- 20
mA
0708
ANAL
OG
OU
TPU
T
+II-
+I +U
I U
+II
+II-
+II
+I +U
1314
TEM
PER
ATU
RE
INPU
T /
PRES
SUR
E IN
PUT
1218
19
PRES
SUR
E IN
PUT
1715
16
+I +U
+ +
IA: (
0)4
- 20m
A (w
ith T
P)*
IU: 0
- 10
V (w
ith T
P)*
+I +U
+ +
2728
CO
MM
UN
ICAT
ION
2623
2425
2122
2029
3031
DTR
+12V
CI:
RS4
85 -
4 w
ire
AB
RX
DTX
DD
TR+1
2V
IA: (
0)4
- 20m
A (w
ith T
A/TU
)*
IU: 0
- 10
V (w
ith T
A/TU
)*
+I +U
IA: (
0)4
- 20m
A (w
ith T
A/TU
+PF/
PM)*
*
IU: 0
- 10
V (w
ith T
A/TU
+PF/
PM)*
*
+I +U
A - P
L: 4
- 20
mA
+I
PL: i
nput
loop
pow
ered
(term
inal
s G
ND
- 1
- 2 a
re n
ot a
vaila
ble)
AP: 8
- 30
V D
CO
utpu
t loo
p po
wer
ed
PB /
PC: b
atte
ry p
ower
edIn
tern
al lo
ng li
fe L
ithiu
m b
atte
ry
-+
PX: 8
- 30
V D
C
+
==
OT:
pas
sive
tran
s.
OA:
act
ive
24V
DC
OR
: mec
h. re
lay
+
Not
e: O
nly
avai
labl
e w
ith T
ype:
P
-+
ZB: B
ackl
ight
: 12
- 24V
DC
* N
ote:
If T
A / T
U is
use
d th
en IA
/ IU
use
term
inal
17
- 18.
If
TP
is u
sed
then
IA /
IU u
se te
rmin
al 1
2 - 1
3 - 1
4.**
Not
e: If
PF
/ PM
and
TA
/ TU
is u
sed
then
IA /
IU u
se te
rmin
al 1
7 on
ly.
-+
PF: 2
4V A
C
PF: 2
4V D
C
TP: P
T100
2-w
ire
TEM
PER
ATU
RE
INPU
T
+
TP: P
T100
3-w
ire
+
F126-EG 3
130 mm (5.12")
120
mm
(4.7
2")
31 mm(1.22")
29 mm(1.14")
115 (4.53")
98
(3.8
6")
panel cut-outHB & HC enclosures
75 mm (2.95")
130 mm (5.12")
112 mm (4.40")
60 m
m (2
.36"
)
120
mm
(4.7
2")
M20 x 1,5PG9 PG9
30mm 30mm
22,5
0mm
M20 x 1,5M16 x 1,5 M16 x 1,5
30mm 30mm
22,5
0mm
M20 x 1,5
22,5
0mm
M20 x 1,5 M20 x 1,5
25mm 25mm
22,5
0mm
1/2"NPT
0.9"
1/2"NPT1/2"NPT 1/2"NPT
1.18" 1.18"
0.9"
HA
HM
HN
HO
HD
HP
HE
HT
HF
HU
HG
HV
HH
6 x M12
12mm 12mm
24mm24mm36mm36mm
14m
m17
mm
Ø12
12mm 12mm
24mm24mm36mm36mm
14m
m17
mm
HK
22,5
0mm
30mm 30mm
Ø16 Ø16Ø20
HJ
22,5
0mm
(0.9
")30mm (1.18") 30mm (1.18")
Ø22 ( 7/8") Ø22 ( 7/8")Ø22 ( 7/8")
22,5
0mm
(0.9
")
Ø22 ( 7/8")
22,5
0mm
25mm 25mm
Ø20 Ø20
Aluminum GRP
Flat bottom, no holes available.
4 x M20 x 1.5
15mm 15mm
HZ
16m
m15
mm
38mm
1/2"NPT 1/2"NPT
1.18" 1.18"
0.9"
HL
Ø 7mm (0.27") Ø 7mm (0.27")
Typical wiring diagram F126-P-AP-CH-EG-IA-OT-(PX)-TA Typical wiring diagram F126-P-AI-CI-EG-IA-OA-PD-TA
0001
0910
1112
1413
1817
Common ground
Common ground
Common ground
Common ground
Signal
Supply *
Signal
Signal
TERMINAL CONNECTORSF100 - series
0708
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
2826
3130
29
+
-
Y
Common ground
Z
A
B
*Supply voltage: 1.2 / 3.2 / 8.2 / 12 / 24V DC to sensor
Analog output type AI: passive isolated 4 - 20mA
8 - 30V DC
indicator
Flowmeter input type: Ppulse
8 - 24V DC
+
-
Pressure inputtype IA:
(0)4 - 20mA
Power supply type PD: 8 - 24V AC / DC
Modbus communication type CI: RS485 - 4 wire
24V AC / DC POWER SUPPLY
Temperature inputtype TA:
(0)4 - 20mA
0605Common ground
Pulse output type OA:active 24V DC pulse
+
- e.g. counter123456
0910
1112
1413
Common ground
Common ground
Signal
Supply *
Signal
TERMINAL CONNECTORSF100 - series
0708
Common ground
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
2826
29
8 - 30V DC
+
-
A
Common ground
B
*Supply voltage: 1.2 / 3.2V DC to sensor
indicator
Modbus communication type CH: RS485 - 2 wire
Analog output type AP: passive 4 - 20mA (loop powered)
1817Common ground
Signal
Temperature inputtype TA:
(0)4 - 20mA
Flowmeter input type: Ppulse
OUTPUT LOOP POWERED
Pressure inputtype IA:
(0)4 - 20mA
Common ground 0001
0605Common ground
123456e.g. counter
Pulse output type OT:
passive transistor
Power supply type PX: 8 - 30V DC
(not used in this example)
F126-EG4
Typical wiring diagram F126-A-AA-CB-EG-IA-OX-PM-TP Typical wiring diagram F126-P-AI-CI-EG-IA-OR-PM-TA00
0102
TERMINAL CONNECTORSF100 - series
0708
Common ground
Common ground
Main supply
2827
2629
Common ground
RXD
TXD
Analog output type AA:active 4 - 20mAindicator
+
-
Modbus communication type CB: RS232
L1
NPower supply type PM:
115 - 230V AC
0910
1112
1413
Common ground
Common ground
Signal
Supply *
Signal
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
2221
20
Supply
Signal
Signal
Temperature input type TP:
PT100 3 - wire
DTR+12V
80 - 230V AC POWER SUPPLY
*Supply voltage: 3.2 / 8.2 / 12 / 24V DC to sensor
Flowmeter input type A:(0)4 - 20mA
Pressure input type IA:(0)4 - 20mA
0605
Note: Digital output not available with Type: A / U
0001
02
TERMINAL CONNECTORSF100 - series
L1
0708
Common ground
Main supply
26
8 - 30V DC
+
-
Common ground
N
e.g. indicator
Power supply type PM:115 - 230V AC
Analog output type AI:passive isolated 4 - 20mA
2831
3029
Y
Z
A
B
Modbus communication type CI: RS485 - 4 wire
115 - 230V AC POWER SUPPLY
*Supply voltage: 3.2 / 8.2 / 12 / 24V DC to sensor
0910
11
Common ground
Signal
Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Flowmeter input type: Ppulse
1214
13
Common ground
Signal
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Supply *
Temperature input type TA:
(0)4 - 20mA
17
Signal
Pressure inputtype IA:
(0)4 - 20mA
0605
e.g. counter123456
Pulse output type OR:mechanic relay
F126-EG 5
F126-EG6
Hazardous area applicationsThe F126-EG-XI has been certified accordingATEX and IECEx by DEKRA for use in IntrinsicallySafe applications with an ambient temperatureof -40°C to +70°C (-40°F to +158°F). • The ATEX markings for gas and dust
applications are:II 1 G Ex ia IIB/IIC T4 GaII 1 D Ex ia IIIC T100 °C Da.
• The IECEx markings for gas and dustapplications are: Ex ia IIC/IIB T4 Ga and Ex ia IIIC T100 °C Da.
It is allowed to connect up to six barriers inIIB/IIIC applications or one barrier in IICapplications. Consult the certificate for themaximum input and output values of thecircuits. Full functionality of the F126-EGremains available, including 4 - 20mA outputaccording to the flow rate and Modbuscommunication (type CT). Power supply typePD-XI offers a 8.2V sensor supply e.g. for oneNamur sensor and two analog sensors. An ATEX approved flame proof Ex d enclosure isavailable as well. Please contact your supplierfor further details.
Certificate of conformity KEMA 03ATEX1074 X• IECEx DEK 11.0042X
TERMINAL CONNECTORSF100-series
2221
20
Supply
Signal
Signal
Temperature input type TP:
PT100 3 - wire
HAZARDOUS AREA SAFE AREA
0910
1112
1413
Common ground
Common ground
Signal
Signal
Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
0708
Flow meter input type: Ppulse
Common ground
* Note sensor supply voltage: 1.2V DC for coil sensors or 3.2V DC for other pulse sensors.
Ci is negligiblysmall
+
-
Uo=max 30V
Io=max 100mA
Po=max 750mW
Ci is negligiblysmall
Pressure input type IA:(0)4 - 20mA
Analog output type AP:passive 4 - 20mA
(not used in this example).
Modbus communication type CT: TTLPossible for battery powered applications (not used in this example).
Please note: type AP may be used in combination with the battery (type PC), but only in IIB applications!
AP will power the unit (output loop powered); the battery will be disabled automatically till power
is disconnected).
REPEATERFor example
MTL 5541
0506
Common ground
Pulse output type OT: passive transistor
(not used in this example)
Note: above values are safety values.Consult the technical specification for operational values.
Configuration example IIB / IIIC and IIC - F126-P-(AP)-(CT)-EG-IA-(OT)-PC-TP-XI - Battery powered unit
Configuration example IIB / IIIC - F126-P-AP-CT-EG-IA-OT-(PX)-TP-XI - Output loop powered
TERMINAL CONNECTORSF100-series
2221
20
Supply
Signal
Signal
Temperature input type TP:
PT100 3 - wire
HAZARDOUS AREA SAFE AREA
1011
1214
13
Common ground
Common ground
Signal
Signal
Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Analog output type AP:passive 4 - 20mA (output loop powered)
RXD
Common ground
TXD
2826
29
Ci = 17nF
Flow meter input type: Ppulse
Common ground
DTR+12V
27
ISOLATOR:I.S. Certified Isolator
TTL to RS232 / RS422 / TTL
For example: MTL5051
+
-
POWER SUPPLYe.g. MTL 5525
and / or REPEATER
e.g. MTL 5541
Uo=max 30V
Io=max 100mA
Po=max 750mW
Uo=max 30V
Io=max 250mA
Po=max 850mW
+
-
e.g. indicator
e.g. PC
e.g. indicator
Modbus communication type CT: TTL
* Note sensor supply voltage: 1.2V DC for coil sensors or 3.2V DC for other pulse sensors.
Ci is negligiblysmall
+
-
Uo=max 30V
Io=max 100mA
Po=max 750mW
Ci is negligiblysmall
Pressure input type IA:(0)4 - 20mA
REPEATERFor example
MTL 5541
Common ground
123456e.g. counter
+
-
POWER SUPPLYe.g. MTL 5525
or SWITCH INTERFACE
e.g. MTL 5511
Uo=max 30V
Io=max 100mA
Po=max 750mWe.g. counter
123456Pulse output type OT:passive transistor
Ci is negligiblysmall
Note: above values are safety values.Consult the technical specification for operational values.
Common groundPX: Not used in this example
0907
0805
06
00
01
F126-EG 7
Configuration example IIB / IIIC and IIC - F126-A-AF-(CT)-EG-IA-OX-PD-TA-XI - Power requirement 16 - 30V DC
TERMINAL CONNECTORSF100-series
HAZARDOUS AREA SAFE AREA
Ci is negligibly small1817
Common ground
Common ground
Signal
TOTAL Co OF ALL CONNECTEDANALOG APPARATUS IN IICAPPLICATIONS MAY NOT
EXCEED 66nF MINUS 17nF(17nF IS USED BY THE ANALOG
OUTPUT SIGNAL TERMINAL 7 + 8).
Main supply
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Power supply type PD: 16 - 30V DC (please note: PD and battery supply (type PC) is NOT allowed in IIC applications).
RXD
Common ground
TXD
2826
29
Ci = 17nF
Analog output type AF:passive floating 4 - 20mA
1011
1214
13
Common ground
Common ground
Signal
Signal
Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Ci is negligiblysmall
Flow meter input type: A(0)4 - 20mA
Ci is negligiblysmall
Temperature input type: TA(0)4 - 20mA
Modbus communication type CT: TTLPlease note: communciation type CT is not allowed in IIC applications.
DTR+12V
27
Pressure input type IA:
(0)4 - 20mA
ISOLATOR:I.S. Certified Isolator
TTL to RS232 / RS422 / TTL
For example: MTL5051
Uo=max 30V
Io=max 250mA
Po=max 850mW
+
-
POWER SUPPLY
For example MTL 5525
Uo=max 30V
Io=max 100mA
Po=max 750mW
+
-
e.g. PC
e.g. indicator
* Note power supply type PD: the supply voltage to pulse sensors is maximum 8.7V (Uo=max 8.7V Io=max 25mA Po=max 150mW) and to analog sensors as connected to terminal 1 (internally linked).
0209
0708
0
001
Note: above values are safety values.Consult the technical specification for operational values.
* Note: Communication only allowed when configured as IIB / IIIC.
Note: Digital output not available with Type: A / U
F126-EG8
Configuration example IIB / IIIC - F126-A-AF-CT-EG-IA-OX-(PC)-(PD)-TA-XI - Power requirement 16 - 30V DC or battery powered
TERMINAL CONNECTORSF100-series
HAZARDOUS AREA SAFE AREA
Ci = 17nF
Ci is negligibly small
1011
1214
1318
17
Common ground
Common ground
Common ground
Common ground
Signal
Signal
Signal
Supply *
Main supply
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Power supply type PD: 16 - 30V DC
Analog output type AF:passive floating 4 - 20mA
RXD
Common ground
TXD
2826
29
DTR+12V
27
Pressure input type IA:(0)4 - 20mA
+
-
ISOLATOR:I.S. Certified Isolator
TTL to RS232 / RS422 / TTL
For example: MTL5051
+
-
POWER SUPPLYe.g. MTL 5525
and / or REPEATER
e.g. MTL 5541
Uo=max 30V
Io=max 100mA
Po=max 750mW
Uo=max 30V
Io=max 250mA
Po=max 850mW
Uo=max 30V
Io=max 100mA
Po=max 750mW
+
-
Uo=max 30V
Io=max 100mA
Po=max 750mW
+
-
POWER SUPPLY
For example MTL 5525
Uo=max 30V
Io=max 100mA
Po=max 750mW
+
-
Uo=max 30V
Io=max 100mA
Po=max 750mW
+
-
e.g. indicator
e.g. PC
e.g. indicator
Modbus communication type CT: TTL
Due to analog output type AF, the unit has to be powered with battery type PC or with external power supply type PD.
Ci is negligiblysmall
Ci is negligiblysmall
* Note power supply type PD: the supply voltage to pulse sensors is maximum 8.7V (Uo=max 8.7V Io=max 25mA Po=max 150mW) and to analog sensors as connected to terminal 1 (internally linked).
Temperature input type TA:(0)4 - 20mA
Flow meter input type A:(0)4 - 20mA
Note: above values are safety values.Consult the technical specification for operational values.
Note: above values are safety values.Consult the technical specification for operational values.
0209
0708
0
001
REPEATERFor example
MTL 5541
REPEATERFor example
MTL 5541
REPEATERFor example
MTL 5541
Note: Digital output not available with Type: A / U
F126-EG 9
Technical specificationGeneralDisplayType High intensity reflective numeric and
alphanumeric LCD, UV-resistant.Dimensions 90 x 40mm (3.5” x 1.6”).Digits Seven 17mm (0.67") and eleven 8mm (0.31") digits.
Various symbols and measuring units.Refresh rate User definable: fast, 1sec , 3sec, 15sec, 30sec, off.Option ZB Transflective LCD with white LED-backlight.
Good readings in full sunlight and darkness. Note ZB Only available for safe area applications.
Ambient temperatureSafe areas -40°C to +80°C (-40°F to +176°F).Intrinsically Safe -40°C to +70°C (-40°F to +158°F).
Power requirementsType AP Analog output loop powerd, 8 - 30V DC.
Power consumption max 0.5 Watt.Type PB Long life Lithium battery - life-time depends upon
settings and configuration - up to 5 years.(requires PD, PL or PX)
Type PC Intrinsically Safe long life lithium battery - life-time depends upon settings and configuration - up to 5 years. (requires XI and PD or PX)
Type PD 8 - 24V AC / DC ± 10%. Power consumption max. 10 Watt. Intrinsically Safe: 16 - 30V DC; power consumption max. 0.75 Watt.
Type PF 24V AC / DC ± 10%. Power consumption max. 15 Watt.Type PL Input loop powered from sensor signal 4 - 20mA
(type “A”) - requires types AI and OT (not Xi).Type PM 115 - 230V AC ± 10%. Power consumption max. 15 Watt.Type PX 8 - 30V DC. Power consumption max. 0.5 Watt. Type ZB 12 - 24V DC ± 10%. Power consumption max. 1 Watt.
Note PB/PF/PM Not available Intrinsically Safe.Note PF/PM The total consumption of the sensors and outputs
may not exceed 400mA @ 24V.Note For Intrinsically Safe applications, consult the safety
values in the certificate.
Sensor excitationType PB/PC/PX 3V DC for pulse signals and 1.2V DC for coil pick-up.
Note This is not a real sensor supply. Only suitable for sensors with a very low power consumption like coils(sine wave) and reed-switches.
Type PD 1.2 / 3 / 8.2 / 12 / 24V DC - max. 50mA @ 24V DC.Type PD-XI 1.2 / 3 / 8.2V DC - max. 7mA @ 8.2V DC and mains
power supply voltage (as connected to terminal 1).Note In case PD-XI and signal A or U: the sensor supply
voltage is according to the power supply voltage connected to terminal 1. The sensor supply of the second analog input is fixed 8.2V DC.
Type PF / PM 1.2 / 3 / 8.2 / 12 / 24V DC - max. 400mA @ 24V DC.
Terminal connectionsType Removable plug-in terminal strip.
Wire max. 1.5mm2 and 2.5mm2.
Data protectionType EEPROM backup of all settings. Backup of running
totals every minute. Data retention at least 10 years.Password Configuration settings can be password protected.
Directives & StandardsEMC Directive 2014/30/EU, FCC 47 CFR part 15.Low voltage Directive 2014/35/EURoHS Directive 2011/65/EUATEX / IECEx Directive 2014/34/EU, IEC 600079-0, IEC 60079-11.IP & NEMA EN 60529 & NEMA 250
EnclosureGeneralWindow Polycarbonate window.Sealing Silicone.Control keys Three industrial micro-switch keys. UV-resistant
silicone keypad.
Aluminum wall / field mount enclosuresGeneral Die-cast aluminum wall/field mount enclosure IP67 /
NEMA Type4X with 2-component UV-resistant coating.Dimensions 130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.Weight 1100 gr.
Type HA Cable entry: 2 x PG9 and 1 x M20. Type HL Cable entry: 2 x 1/2" NPT.Type HM Cable entry: 2 x M16 and 1 x M20. Type HN Cable entry: 1 x M20. Type HO Cable entry: 2 x M20. Type HP Cable entry: 6 x M12. Type HT Cable entry: 1 x 1/2" NPT.Type HU Cable entry: 3 x 1/2" NPT.Type HV Cable entry: 4 x M20. Type HZ Cable entry: no holes.
GRP wall / field mount enclosuresGeneral GRP wall/field mount enclosure IP67 / NEMA Type4X,
UV-resistant and flame retardant. Dimensions 130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.Weight 600 gr.
Type HD Cable entry: no holes.Type HE Cable entry: 2 x Ø 16mm and 1 x Ø 20mm.Type HF Cable entry: 1 x Ø 22mm (7/8").Type HG Cable entry: 2 x Ø 20mm. Type HH Cable entry: 6 x Ø 12mm. Type HJ Cable entry: 3 x Ø 22mm (7/8"). Type HK Flat bottom, cable entry: no holes.
Panel mount enclosuresDimensions 130 x 120 x 60mm (5.12" x 4.72" x 2.36") - W x H x D.Panel cut-out 115 x 98mm (4.53" x 3.86") L x H.
Type HB Die-cast alu. panel mount enclosure IP65 / NEMA Type4X.
Weight 600 gr.Type HC GRP panel mount enclosure IP65 / NEMA Type4X,
UV-resistant and flame retardant.Weight 450 gr.
Hazardous areaIntrinsically Safe (Type XI)ATEX II 1 G Ex ia IIB/IIC T4 Ga.certification II 1 D Ex ia IIIC T100 °C Da.IECEx Ex ia IIC/IIB T4 Ga.certification Ex ia IIIC T100 °C Da.Ambient Ta -40°C to +70°C (-40°F to +158°F).
Explosion proof (Type XF)ATEX certification II 2 G / Ex d IIB T5 Gb.
II 2 D / Ex t IIIB T100 °C Db.Type XF Dimensions of enclosure: 300 x 250 x 200mm
(11.8" x 9.9" x 7.9") L x H x D.Weight Appr. 15kg.Note IECEx available on request.
10
Signal inputsFlowmeterType P Coil / sine wave (HI: 20mVpp or LO: 80mVpp -
sensitivity selectable), NPN/PNP, open collector, reed-switch, Namur, active pulse signals 8 - 12 and 24V DC.
Frequency Minimum 0Hz - maximum 7kHz for total and flow rate. Maximum frequency depends on signal type and internal low-pass filter. E.g. reed switch with low-pass filter: max. frequency 120Hz.
K-Factor 0.000010 - 9,999,999 with variable decimal position.Low-pass filter Available for all pulse signals.Option ZF coil sensitivity 10mVpp.
Type A (0)4 - 20mA. Analog input signal can be scaled to anydesired range within 0 - 20mA.
Type U 0 - 10V DC. Analog input signal can be scaled to any desired range within 0 - 10V DC.
Accuracy Resolution: 14 bit. Error < 0.025mA / ± 0.125% FS. Low level cut-off programmable.
Span 0.000010 - 9,999,999 with variable decimal position.Update time Four times per second.Voltage drop Type A: 2.5V @ 20mA.Load impedance Type U: 3kOhm.Relationship Linear and square root calculation.Note For signal type A and U: external power to sensor is
required; e.g. type PD.
TemperatureAccuracy Resolution: 14 bit. Error < 0.025mA / ± 0.125% FS.
Low level cut-off programmable.Update time Four times per second.Type TA (0)4 - 20mA. Analog input signal can be scaled to
any desired range within 0 - 20mA.Span 0.000010 - 9,999,999 K with variable decimal position.Offset 0.00 - 99,999.99 K.Voltage drop 2.5V @ 20mA.
Type TP 2 or 3 wire PT100.Range -100°C to +200°C (-148°F to 392°F).
Accuracy 3°C (5.4°F).Option ZV Range: -200°C to +800°C (-328°F to 1832°F).
Accuracy 3°C (5.4°F).Type TU 0 - 10V DC. Analog input signal can be scaled to
any desired range within 0 - 10V DC.Span 0.000010 - 9,999,999 K with variable decimal position.Offset 0.00 - 99,999.99 K.Load impedance 3kOhm.
Note 1 For signal TA and TU: power supply to temperature sensor is required; e.g. PD.
PressureAccuracy Resolution: 14 bit. Error < 0.025mA / ± 0.125% FS.
Low level cut-off programmable.Update time Four times per second.Type IA (0)4 - 20mA. Analog input signal can be scaled to any
desired range within 0 - 20mA.Span 0.000010 - 9,999,999 with variable decimal position.Offset 0.000 - 9,999.999.Voltage drop 2.5V @ 20mA.
Type IU 0 - 10V DC. Analog input signal can be scaled to any desired range within 0 - 10V DC.
Span 0.000010 - 9,999,999 with variable decimal position.Load impedance 3kOhm.Note For signal type IA and IU: external power to sensor
required; e.g. PD.
OperationalFlow equationsType EG Corrected gas volume.
Normal press. Default: 1.013 bar.Normal temp. Default: 273.15K (0°C / 32°F)
Operator functionsDisplayed • Compensated flow rate.functions • Compensated total and accumulated total.
• Actual line temperature / pressure.• Reset total by pressing the CLEAR-key twice.
TotalDigits 7 digits.Units L, m3, GAL, USGAL, kg, lb, bbl, no unit.Decimals 0 - 1 - 2 or 3. Note Total can be reset to zero.
Accumulated totalDigits 11 digits.Units / decimals According to selection for total.Note Can not be reset to zero.
Flow rateDigits 7 digits.Units mL, L, m3, Gallons, kg, Ton, lb, bl, cf, RND, ft3, scf,
Nm3, Nl, igal - no units.Decimals 0 - 1 - 2 or 3.Time units /sec - /min - /hr - /day.
Line temperatureDigits 6 digits.Units °C, °F or K.Decimals 1.
Line pressureDigits 6 digits.Units mbar, bar, PSI, no-unit.Decimals 1.
Signal outputsDigital outputFunction Pulse output - transmitting accumulated total.Frequency Max. 500Hz. Pulse length user definable between
0.001 second up to 9.999 seconds.Type OA One active 24V DC transistor output (PNP);
max. 50mA per output (requires P + PD, PF, PM or PX).Type OR One electro-mechanical relay output - isolated;
max. switch power 230V AC (N.O.) - 0.5A per relay (requires P + PF or PM).
Type OT One passive transistor output (NPN) - not isolated. Max. 50V DC - 300mA per output. (requires P)
Analog outputFunction Transmitting compensated flow rate.Accuracy 10 bit. Error < 0.05%. Analog output signal can be
scaled to any desired range.Update time Eight times per second.Type AA Active 4 - 20mA output (requires PD, PF, PM or PX).Type AB Active 0 - 20mA output (requires PD, PF, PM or PX).Type AF Passive floating 4 - 20mA output (requires XI + PD or PX).
Type AI Passive galvanically isolated 4 - 20mA output - also available for battery powered models.
Type AP Passive 4 - 20mA output - not isolated. Unit will beloop powered.
Type AU Active 0 - 10V DC output (requires PD, PF, PM or PX).
Communication optionFunction Reading display information, reading / writing all
configuration settings.Protocol Modbus RTU.Speed 1200 - 2400 - 4800 - 9600 baud.Addressing Maximum 255 addresses.Type CB RS232Type CH RS485 2-wire Type CI RS485 4-wireType CT TTL Intrinsically Safe. Formula Qnormal = Q x ( P ) x ( Tnormal ) x ( Cnormal )Pnormal T C .
11
Copy
righ
t: F
luid
wel
l bv
- 201
7 - F
126E
G-D
ATA-
EN-V
1704
Ordering information - Standard configuration: F126-P-AP-CX-EG-HC-IA-OT-PX-TA-XX-ZX.Ordering information: F126 -_ -A _ -C _ -EG -H _ -I _ -OT -P _ -T _ -X _ -Z _Flowmeter input signalA (0)4 - 20mA input. (Digital ouput is pending)P Pulse input: coil, npn, pnp, namur, reed-switch.U 0 - 10V DC input. (Digital ouput is pending)Analog output signalAA Active 4 - 20mA output - requires PD, PF, PM or PX.AB Active 0 - 20mA output - requires PD, PF, PM or PX.AF I.S. floating 4 - 20mA output - requires XI + PD or PX.AI Isolated 4 - 20mA output.AP Passive 4 - 20mA output, loop powered unit.AU Active 0 - 10V DC output - requires PD, PF, PM or PX.CommunicationCB Communication RS232 - Modbus RTU.CH Communication RS485 - 2wire - Modbus RTU.CI Communication RS485 - 4 wire - Modbus RTU.CT Intrinsically Safe TTL - Modbus RTU.CX No communication.Flow equationsEG Corrected gas volume.Panel mount enclosures - IP65 / NEMA Type4XHB Aluminum enclosure.HC GRP enclosure.GRP field / wall mount enclosures - IP67 / NEMA Type4XHD Cable entry: no holes.HE Cable entry: 2 x Ø 16mm & 1 x Ø 20mm.HF Cable entry: 1 x Ø 22mm (7/8”).HG Cable entry: 2 x Ø 20mm.HH Cable entry: 6 x Ø 12mm.HJ Cable entry: 3 x Ø 22mm (7/8”).HK Flat bottom, cable entry: no holes.Aluminum field / wall mount enclosures - IP67 / NEMA Type4XHA Cable entry: 2 x PG9 + 1 x M20.HL Cable entry: 2 x 1/2”NPT.HM Cable entry: 2 x M16 + 1 x M20.HN Cable entry: 1 x M20.HO Cable entry: 2 x M20.HP Cable entry: 6 x M12.HT Cable entry: 1 x 1/2”NPT.HU Cable entry: 3 x 1/2”NPT.HV Cable entry: 4 x M20.HZ Cable entry: no holes.Pressure input signalIA (0)4 - 20mA input.IU 0 - 10V DC input.Digital output signalsOA One active transistor outputs - requires P and PD, PF, PM or PX.OR One mechanical relay outputs - requires P and PF or PM.OT One passive transistor outputs - standard configuration. rreeqquuiirreess PP Power requirementsPD 8 - 24V AC/DC + sensor supply - with XI: 16 - 30V DC.PF 24V AC/DC + sensor supply.PL Input loop powered from sensor signal type “A” - requires AI (not XI).PM 115 - 230V AC + sensor supply.PX Basic power supply 8 - 30V DC (no real sensor supply).Additional battery supply (optional)PB Lithium battery powered - requires PD, PL or PX.PC Lithium battery powered - Intrinsically Safe - requires XI, and PD or PX.Temperature input signalTA (0)4 - 20mA input.TP PT100 input.TU 0 - 10V DC input.Hazardous areaXI Intrinsically Safe, according ATEX and IECEx.XF Ex d enclosure - 3 keys according ATEX.XX Safe area only.Other optionsZB Backlight.ZF Coil input 10mVpp.ZV PRTD-range -200°C / +800°C.ZX No options.
The bold marked text contains the standard configuration. / Available Intrinsically Safe.
12
Specifications are subject to change without notice.
Fluidwell bvP.O. Box 65460 AA - Veghel - The NetherlandsTelephone: +31 (0)413 343 786Telefax: +31 (0)413 363 443email: [email protected] Internet: www.fluidwell.com