Upload
chandushar1604
View
220
Download
0
Embed Size (px)
Citation preview
Understanding basic principles o ow calculations
V alve size often is described by the
nominal size of the end connec-
tions, but a more important
measure is the ow that the valve can
provide. And determining ow through
a valve can be simple. Using the princi-
ples of ow calculations, some basic
formulas, and the effects of specic
gravity and temperature, ow can be
estimated well enough to select a valve
size easily and without complicated
calculations
Flow calculation principlesThe principles of ow calculations are
illustrated by the common orice ow
meter (see Figure 1). We need to know
only the size and shape of the orice,
the diameter of the pipe and the uid
density. With that information, we can
calculate the ow rate for any value of
pressure drop across the orice (the
difference between inlet and outlet
pressures).
For a valve, we also need to know the
pressure drop and the uid density. But in addi-
tion to the dimensions of pipe diameter and
orice size, we need to know all the valve passage
dimensions and all the changes in size and direc-
tion of ow through the valve.
However, rather than doing complex calcula-
tions, we use the valve ow coefcient, which
combines the effects of all the ow restrictions in
the valve into a single number (see Figure 2).
Valve manufacturers determine the valve ow
coefcient by testing the valve with water at
several ow rates, using a standard test method2
developed by the Instrument Society of America
for control valves and now used widely for all
valves.
John Baxter and Ulrich Koch Swagelok Company
Flow tests are done in a straight piping system
of the same size as the valve, so that the effects
of ttings and piping size changes are not
included (see Figure 3).
Liquid owSince liquids are
i n c o m p r e s s i b l e
uids, their ow
rate depends only
on the difference
between the inlet
and outlet pres-
sures (∆p, pressure
drop). The ow is
www.digitalrefning.com/article/1000088 March 2008
1
Figure 1
Figure 2
Equation 1
the same whether the system pressure is low or
high, so long as the difference between the inlet
and outlet pressures is the same. Equation 1
shows the relationship.
The water ow graphs show water ow as a
function of pressure drop for a range of C v
values.
2 March 2008 www.digitalrefning.com/article/1000088
Gas owGas ow calculations are
slightly more complex
because gases are
compressible uids whose
density changes with pres-
sure. In addition, there
are two conditions that
must be considered: low
pressure drop ow and
high pressure drop ow.
Equation 2 applies when
the low pressure drop ow
outlet pressure ( p2) is
greater than one half of
the inlet pressure ( p1):
The low pressure drop air ow graphs show
low pressure drop air ow for a valve with a C v
of 1.0, given as a function of inlet pressure ( p1)
for a range of pressure drop (∆p) values.
When outlet pressure ( p2) is less than half of
inlet pressure ( p1), high pressure drop, any
further decrease in outlet pressure does not
increase the ow because the gas has reached
sonic velocity at the orice and it cannot break
that “sound barrier”.
Equation 3 for high pressure drop ow is
simpler because it depends only on inlet pres-
sure and temperature, valve ow coefcient and
specic gravity of the gas:
Figure 3
The basic orifce meter illustrates the dier-ence between high and low pressure drop owconditions.
In low pressure drop ow, when outlet pres-sure ( p
2 ) is greater than hal o inlet pressure
( p1 ), outlet pressure restricts ow through the
orifce: as outlet pressure decreases, owincreases and so does the velocity o the gasleaving the orifce.
When outlet pressure decreases to hal o inlet pressure, the gas leaves the orifce at thevelocity o sound. The gas cannot exceed thevelocity o sound, so this becomes the maxi-mum ow rate. The maximum ow rate is alsoknown as choked ow or critical ow.
Any urther decrease in outlet pressure doesnot increase ow, even i the outlet pressureis reduced to zero. Consequently, high pres-sure drop ow only depends on inlet pressureand not outlet pressure.
Low and high pressure drop gas ow
The high-pressure drop air
ow graphs show high pres-
sure drop air ow as a function
of inlet pressure for a range of
ow coefcients.
Eects o specifc gravity The ow equations include the
variables liquid specic gravity
(G f ) and gas specic gravity
(G g), which are the density of
the uid compared to the
density of water (for liquids)
or air (for gases).
However, specic gravity is
not accounted for in the
graphs, so a correction factor
must be applied, which
includes the square root of G.
Taking the square root reduces
the effect and brings the value
much closer to that of water or
air, 1.0.
For example, the specic
gravity of sulphuric acid is
80% higher than that of water,
yet it changes ow by just 34%.
The specic gravity of ether is
26% lower than that of water,
yet it changes ow by only
14%.
Figure 4 shows how taking
the square root of specic
gravity diminishes the signi-
cance on liquid ow. Only if
the specic gravity of the liquid
is very low or very high will
the ow change by more than
10% from that of water.
The effect of specic gravity
on gases is similar. For
www.digitalrefning.com/article/1000088 March 2008
3
Low pressure drop air ow graphs
Flow tet are
doe a traght
ppg ytem of
the ame ze a
the valve
example, the specic gravity of
hydrogen is 93% lower than
that of air, but it changes ow
by just 74%. Carbon dioxide
has a specic gravity 53%
higher than that of air, yet it
changes ow by only 24%. Only
gases with very low or very high
specic gravity change the ow
by more than 10% from that of
air.
Figure 5 shows how the effect
of specic gravity on gas ow is
reduced by use of the square
root.
Eects o temperatureTemperature usually is ignored
in liquid ow calculations
because its effect is too small.
Temperature has a greater
effect on gas ow calculations,
because gas volume expands
with higher temperature and
contracts with lower tempera-
ture. But similar to specic
gravity, temperature affects
ow by only a square root
factor. For systems that operate
between -40°F (-40°C) and
+212°F (+100°C), the correc-
tion factor is only +12 to -11%.
Figure 6 shows the effect of
temperature on volumetric ow
over a broad range of tempera-
tures. The plus or minus 10%
range covers the usual operat-
ing temperatures of most
common applications.
Temperature
uually gored
lqud ow
calculato
becaue t effect
too mall
High pressure drop air ow graphs
4 March 2008 www.digitalrefning.com/article/1000088
Cited reerences
1 ISA S75.01, Flow Equations or Sizing Control
Valves, Standards and Recommended Practices or
Instrumentation and Control, 10th ed, Vol 2, 1989.
2 ISA S75.02, Control Valve Capacity Test Procedure,
Standards and Recommended Practices or
Instrumentation and Control, 10th ed, Vol 2, 1989.
Other reerences
1 Driskell L, Control Valve Selection and Sizing, ISA,
1983.
2 Hutchinson J W, ISA Handbook of Control Valves,
2nd ed, ISA, 1976.
3 Chemical Engineers’ Handbook , 4th ed, Perry R H,
Chilton C H, Kirkpatrick S D, Ed, McGraw-Hill, New
York.
4 Instrument Engineers’ Handbook , revised ed,
Lipták B G, Venczel K, Ed, Chilton, Radnor, PA.
5 Piping Handbook , 5th ed, King R C, Ed, McGraw-Hill, New York.
6 Standard Handbook for Mechanical Engineers, 7th ed,
Baumeister T, Marks L S, Ed, McGraw-Hill, New York.
Figure 4
Figure 5 Figure 6
www.digitalrefning.com/article/1000088 March 2008 5
Links
More artcle from: swagelo Compay
More artcle from the followg categore:
Deg, Egeerg & Cotructo
Hydroproceg Water/Watewater Maagemet
safety, Health, Evromet ad Qualty