Upload
others
View
6
Download
0
Embed Size (px)
Citation preview
A Mitigation Strategy to Address Voltage Flicker
due to the Cloud Cover Effect
Soonwook Hong
Solectria Renewables
1
2
High Penetration Scenario Example:
1.7 MW site in Cedarville NJ
4.7 miles from substation 12kV feeder, 6MW mid-day load
Concerns of local overvoltage
Utility has closed circuit for more PV
0.5 MW1.7 MW
Courtesy of Pepco Holdings
3
Overvoltage Concerns
3.0% of points
exceed +5% limit
Courtesy of Pepco Holdings
4
Mitigating overvoltage issue with Power Factor control
< 0.1% of points
exceed 5% limit
• Feeder could be reopened for PV after PF adjustment to 0.97
• “Flicker” Mitigation (cloud induced voltage transients)
Courtesy of Pepco Holdings
5
Overvoltage Issues
Utility concerns
• Feeder voltage can exceed the ANSI 84.1 Guideline
• The number of operations of tap changer, regulators and cap banks
increases with voltage fluctuation
• Conservation voltage reduction will not work well with DGs
Site/Project owner concerns
• Projects can be denied by utilities due to the overvoltage concerns.
• Due to the high AC voltage, inverters trip with the overvoltage protection.
6
Topics
� How voltage changes with DG generation?
� How power factor control contribute to regulate the feeder voltage?
� More considerations to enhance the power factor control
� Benefits and applications of XR Compensation (power factor control)
7
Voltage rise of PV plant
8
Voltage profile with irradiation changes
1.01
1.015
1.02
1.025
1.03
1.035
1.04
1.045
1.05
5:27 8:19 11:12 14:05 16:58 19:51
Feeder Voltage
9
Line Impedance Z = 0.1pu
Line Impedance Z = 0.2pu
• Low Impedance feeder experiences less voltage rise
• With a fixed impedance, high X/R ratio feeder experiences less voltage rise
Voltage rise with different feeder characteristics
10
How power factor control regulates voltage?
(XR Compensation)
• If the X/R ratio of the feeder is known, the required power factor can
be calculated.
• Slight overcompensation can be expected with the high generation
level
11
800
806 808 812 814
810
802 850
818
824 826
816
820
822
828 830 854 856
852
832
888 890
838
862
840
836860834
842
844
846
848
864
858
PV
Simulation with IEEE 34 Node Test Feeder
Regulator
Load
12
XR Compensation (Power Factor Control)
Sunny Day Cloudy Day
0
10
20
30
40
No PV Generation Mode PF Control
0
10
20
30
40
No PV Generation Mode PF Control
Number of operations of the regulator at 850
1.01
1.015
1.02
1.025
1.03
1.035
1.04
1.045
1.05
5:27 8:19 11:12 14:05 16:58 19:51
With No PV
Generation mode
PF Control 1.01
1.015
1.02
1.025
1.03
1.035
1.04
1.045
1.05
5:27 8:19 11:12 14:05 16:58 19:51
With No PV
Generation mode
PF Control
13
PF = 1 PF = 0.949 PF = 0.976
Compensation of “Over-Compensation”
Error is caused by using approximation! (usually not significant though)
Corrected power factor can be accurately calculated with feeder impedance (Z and X/R)
14
Line Impedance Z = 0.2pu
• High X/R ratio requires smaller power factor angle, thus low reactive power
• The control is more effective with high X/R ratio
• For low X/R ratio feeder, adding reactor can be considered to increase energy harvest
Voltage Compensation with different X/R ratio
PF = cos(39°°°°)
Q = 0.777pu
PF = cos(12.7°°°°)
Q = 0.976
PF = cos (5.5°°°°)
Q = 0.995
15
Typical X/R ratio of distribution feeders
The required power factor is usually higher than 0.95 when a PV plant
includes a MV transformer and larger than 1MVA.
16
Generation Reduction with Power Factor Control (0.97)
0%
20%
40%
60%
80%
100%
97%0.4%
Gen
era
ted
Po
wer
time
Generation Profile on a sunny day
Still, 99.6% generation is expected with the power factor control.
Without it, the grid connection might not be possible!
17
Uniqueness of the XR Compensation
XR Compensation Other regulation scheme
Reduce feeder overvoltage Regulate feeder voltage
(both over and under voltage)
Controlled by DG generation
(self induced overvoltage)Controlled by voltage variations
due to load, generation and fault
DG plant voltage compensation Distribution line voltage regulation
18
XR Compensation Advantages
� Regulates the self-induced voltage fluctuation issue
� Steady state as well as dynamic voltage regulation
� Autonomous function without need for communication
� 0.4% generation reduction when pf = 0.97 on sunny days
� Overcompensation can be compensated properly
� Low X/R ratio feeder can use series inductor to effectively use power
factor control (or high impedance transformer)