Hilti, Inc., 5400 South 122 nd East Avenue, Tulsa, OK 74121, (800) 879-8000 FIRESTOP SUBMITTAL PACKAGE ELECTRICAL Materials FS-ONE Intumesent Caulk CP 617 Putty Pads Thermafiber Safing Includes: Technical and Installation Data UL Certificate of Compliance LEED information MSDS UL Details Concrete Assemblies C-AJ-1184 – Max. 4" copper, steel conduit or EMT (Top or Underside) C-AJ 1226 – Max. 6" steel conduit or Max 4" EMT (optional sleeve) C-AJ-3095 - Cable bundles (various cables) - (optional sleeve) C-AJ-8099 - Multiple steel conduit or EMT and cable bundle Wood Floor Assemblies F-C-1009 - Max. 4" steel conduit or EMT (Chase wall required) F-C-3012 - Cable bundle (various cables) - (chase wall required) F-C-3044 - Cable bundle (various cables) - (chase wall optional) Gypsum Wall Assemblies W-L-1054 - Max. 6" copper, steel conduit, or max 4" EMT W-L-1243 - Max. 2" flexible aluminum or steel conduit W-L-1408 - Multiple steel conduit or EMT, Max 4", single row W-L-3065 - Cable bundles (various cables) - (optional sleeve) W-L-3071 - SER Cables Electrical Boxes Putty Pads Electrical Box Inserts

FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

  • Upload
    others

  • View
    28

  • Download
    1

Embed Size (px)

Citation preview

Page 1: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

Hilti, Inc., 5400 South 122nd

East Avenue, Tulsa, OK 74121, (800) 879-8000

FIRESTOP SUBMITTAL PACKAGE

ELECTRICAL

Materials

FS-ONE Intumesent CaulkCP 617 Putty PadsThermafiber Safing

Includes:Technical and Installation DataUL Certificate of Compliance

LEED informationMSDS

UL Details

Concrete Assemblies C-AJ-1184 – Max. 4" copper, steel conduit or EMT (Top or Underside)

C-AJ 1226 – Max. 6" steel conduit or Max 4" EMT (optional sleeve)

C-AJ-3095 - Cable bundles (various cables) - (optional sleeve)

C-AJ-8099 - Multiple steel conduit or EMT and cable bundle

Wood Floor Assemblies F-C-1009 - Max. 4" steel conduit or EMT (Chase wall required)

F-C-3012 - Cable bundle (various cables) - (chase wall required)

F-C-3044 - Cable bundle (various cables) - (chase wall optional)

Gypsum Wall Assemblies W-L-1054 - Max. 6" copper, steel conduit, or max 4" EMT

W-L-1243 - Max. 2" flexible aluminum or steel conduit

W-L-1408 - Multiple steel conduit or EMT, Max 4", single row

W-L-3065 - Cable bundles (various cables) - (optional sleeve)

W-L-3071 - SER Cables

Electrical BoxesPutty Pads

Electrical Box Inserts

Page 2: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

Product Information

Chap

ter

Tab

sC

hap

ter

Tab

sC

hap

ter

Tab

sC

hap

ter

Tab

sC

hap

ter

Tab

s

Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en español 1-800-879-5000 • Hilti Firestop Systems Guide 2007

Hilti. Outperform. Outlast.

sodfm,ev iJdjfiwhriuh. NöoWE

Z8Z23awöp3i4eß0288u27 uze

4i5kirdwiloi4jtf-öx-.vbvbvh, ireiv

u9+ß12oeoo

tlke0´9^)&(/R 84tc )v 6453

FS-ONEHigh Performance Intumescent Firestop Sealant

FS-ONE Technical DataChemical basis Water-based intumescent acrylic

dispersionColor RedApplication temperature 40°F to 104°F (5°C to 40°C) Skin forming time Approx. 20-30 min.Curing time Approx. 2 mm / 3 daysMovement capability Approx. 5%Expansion rate Up to 3-5 times (unrestricted): original volumeTemperature resistance (cured) –40°F to 212°F (–40°C to 100°C)Surface burning characteristics Flame Spread: 0(ASTM E 84-96) Smoke Development: 5Sound transmission classification 56 (Relates to specific construction)(ASTM E 90-99) ApprovalsCalifornia State Fire Marshal Listing No. 4485-1200:108City of New York MEA 326-96-M Vol. IVTested in accordance with • UL 1479

• ASTM E 814• ASTM E 84

At 73°F (23°C) and 50% relative humidity

FILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-PENETRATION

FIRESTOP SYSTEMSSEE UL FIRE RESISTANCE DIRECTORY

66Y7

FMAPPROVED

For Penetration Fire Stops. Consult the Factory Mutual Research Corporation Approval Guide.

R

C

LASSIFIED

FILL, VOID OR CAVITY MATERIALS CLASSIFIED BY

UNDERWRITERS LABORATORIES, INC. FOR USE IN TROUGH-PENETRATION

FIRESTOP SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY

66Y7

Product description• Intumescent (expands when exposed to fire) firestop sealant that

helps protect combustible and non-combustible penetrations forup to 4 hours fire rating

Product features• Smoke, gas and water resistant after material has cured

• Contains no halogen, solvents or asbestos

• High fire rating properties

• Water based, easy to clean

• Protects most typical firestop penetration applications

• Can be painted

• Single component systems available

• Meets LEED™ requirements for indoor environmental quality credit4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paintsand Coatings

Areas of application• Steel, copper and EMT pipes

• Insulated steel and copper pipes

• Cable bundles

• Closed or vented plastic pipes

• HVAC penetrations

For use with• Concrete, masonry, drywall and wood floor assemblies

• Wall and floor assemblies rated up to 4 hours

Examples• Sealing around plastic pipe penetrations in fire rated construction

• Sealing around combustible and non-combustible penetrations infire rated construction

1. Clean opening. 2. Pack mineral wool.(If required)

3. Apply FS-ONE. 4. Smooth FS-ONE.

5. Leave completedseal undisturbed for 48hours.

6. Fasten identificationplate (if required).

1. Clean opening. 2. Pack mineral wool.(If required)

3. Apply FS-ONE. 4. Smooth FS-ONE.

5. Leave completedseal undisturbed for 48hours.

6. Fastenidentification plate (ifrequired).

Firestop System

Notice • Before handling, read Material Safety DataSheet and

product label for safe usage and health information.

• Instructions below are general guidelines — alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information

Opening 1. Clean the opening. Surfaces to which FS-ONE will be

applied should be cleaned of loose debris, dirt, oil,moisture, frost and wax. Structures supportingpenetrating items must be installed in compliancewith local building and electrical standards.

Application of firestop sealant 2. Install the prescribed backfilling material type and

depth to obtain the desired rating (if required). Leavesufficient depth for applying FS-ONE.

3. Application of firestop sealant: Apply FS-ONE to therequired depth in order to obtain the desired fire rating.Make sure FS-ONE contacts all surfaces to providemaximum adhesion. For application of FS-ONE use astandard caulking gun, foil pack gun, bulk loader andbulk gun. With FS-ONE buckets, Graco type sealantpumps may be used. (Contact pump manufacturer forproper selection).

4. Smoothing of firestop sealant: To complete the seal,tool immediately to give a smooth appearance.Excess sealant, prior to curing, can be cleanedaway from adjacent surfaces and tools with water.

5. Leave completed seal undisturbed for 48 hours.

6. For maintenance reasons, a penetration seal couldbe permanently marked with an identification plate.In such a case, mark the identification plate andfasten it in a visible position next to the seal.

Not for use • High movement expansion joints

• Underwater

• On materials where oil, plasticizers or solvents maybleed i.e. impregnated wood, oil based seals, greenor partially vulcanized rubber

• In any penetration other than those specificallydescribed in this manual or the test reports

Storage • Store only in the original packaging in a location

protected from moisture at temperatures between 40°F (5°C) and 86°F (30°C)

• Observe expiration date on the packaging

Installation instructions for FS-ONE

Firestop System

Firestop System

CA

BLE

PIP

E

Page 3: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad
Page 4: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad
Page 5: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad
Page 6: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

Hilti, Inc. 5400 South 122nd East Avenue

Tulsa, OK 74146

1-800-879-8000 www.hilti.com

February 24, 2009 To Whom It May Concern: Re: Hilti FS-ONE Intumescent Firestop – LEED Info. The Hilti FS-ONE Intumescent Firestop is manufactured in Kaufering, Germany. The FS-ONE pail is made of polyethylene and can be completely recycled. There is no post-consumer or post-industrial content in FS-ONE and it cannot be recycled. The VOC content for FS-ONE is 75 grams/liter. FS-ONE is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal. Please feel free to contact me at (918) 872-3704 if you have questions. Sincerely, Jerry Metcalf MPH, CHMM Safety/Environmental Manager Hilti Inc (918) 872 3704 [email protected] Rev. Date: 2/24/09

Page 7: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

Product Information

Chap

ter

Tab

sC

hap

ter

Tab

sC

hap

ter

Tab

sC

hap

ter

Tab

sC

hap

ter

Tab

s

Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en español 1-800-879-5000 • Hilti Firestop Systems Guide 2007

Hilti. Outperform. Outlast.

Hilti FirestopSaving Livesthrough innovationand education

CP 617, CP 617L & CP 617XLFirestop Putty PadProduct description• A moldable firestop putty designed to help protect electrical outlet

boxes

Product features• Applied by hand

• Fast installation

Areas of application• Protection of electrical outlet boxes

For use with• Gypsum wall assemblies with wood or metal studs

Examples• Where two outlets are within a single stud/cavity or within 24"

(not back to back)

Installation instructions for CP 617

CP 617 Technical DataDimensions CP 617: 6" x 7" x 1/8"(15 x 18 x 0.3 cm)

CP 617L: 7" x 7" x 1/8" (18 x 18 x 0.3 cm)CP 617XL: 9" x 9" x 1/8" (23 x 23 x 0.3 cm)

Consistency Moldable puttyColor RedApplication temperature 40°F (5°C) to 95°F (35°C)Storage temperature 40°F (5°C) to 104°F (40°C)Cure Non-curingDensity 1.48 g/cm3

Intumescent activation Approx. 220°F to 250°F (104°C to 121°C)Volatile solvents NoneAsbestos fibers NoneSurface burning characteristics Flame Spread: 5(ASTM E 84-96) Smoke development: 5Sound transmission classification 55 (Relates to specific construction)(ASTM E 90-97) ApprovalsCalifornia State Fire Marshal Listing No. 4485-1200:129City of New York MEA-102-99-MTested in accordance with • UL 263

• ASTM E 84At 73°F (23°C) and 50% relative humidity

FMAPPROVED

For Penetration Fire Stops. Consult the Factory Mutual Research Corporation Approval Guide.

R

C

LASSIFIED

FILL, VOID OR CAVITY MATERIALS CLASSIFIED BY

UNDERWRITERS LABORATORIES, INC. FOR USE IN TROUGH-PENETRATION

FIRESTOP SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY

66Y7

WALL OPENING PROTECTIVE MATERIAL FIRE RESISTANCE CLASSIFICATION

SEE PRODUCT CATEGORY IN UL FIRE RESISTANCE DIRECTORY

66Y7

Notice • Before handling, read Material Safety DataSheet and

product label for safe usage and health information.

• Instructions below are general guidelines — alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information

Application of firestop putty1. Remove label from one side of pad. For a 1 to 2

hour fire rating, one CP 617 pad is required.Exposed side of pad is placed against box.

2. Adhere pad to side of the box, overlapping the studand all edges of the box. When drywall is installed:fix pad into gap between electrical box and gypsumboard slightly overlapping the inner wall boardsurface. When drywall will be installed later: overlapfront edge of electrical box so that CP 617 will becompressed around edges of box as gypsum boardis installed.

3. Reshape CP 617 to fit around conduit or cables.

4. Press CP 617 to all sides of electrical box. Trimexcess at corners and apply to conduit fittingsconnected to the box.

5. Remove other side of label. To help prevent passageof cold smoke, CP 617 may optionally be placedinto inside of electrical conduit fittings.

Not for use• In areas exposed to water

Storage• Store only in the original packaging in a location at

temperatures 40°F (5°C) to 104°F (40°C)

1. Remove label from oneside of CP 617

2. Adhere CP 617 toapplication

3. Reshape CP 617 to fitaround box

4. Press CP 617 to allsides of application

5. Remove other side oflabel

Page 8: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad
Page 9: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad
Page 10: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad
Page 11: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

THERMAFIBER® Safing Insulation is a mineral-wool-type insulation that resists temperatures up to 2,000 °F (1,093 °C), thus offering superior fire protection in a wide variety of fire-rated applications. It isa UL- and OPL-labeled product especially intended for tested UL and OPL Designs, as well as many otherfire- and smoke-tested assemblies. This product is noncombustible per Standard NFPA 220 when testedin accordance with ASTM E 136, and moisture-resistant, noncorrosive, nondeteriorating, mildew-proofand vermin-proof. It permits dry construction for all-year-round work. Also, THERMAFIBER SafingInsulation is available plain, or with scrim-reinforced foil facing (FSP) that serves as a vapor retarderand/or smoke barrier.

THERMAFIBER Safing Insulation is compatible with both THERMAFIBER® Curtain Wall CW Insulations andTHERMAFIBER FIRESPAN™ Insulations.

THERMAFIBER Safing Insulation is a key element in a wide variety of fire-tested construction assemblies.It is used with THERMAFIBER Curtain Wall and FIRESPAN Insulations in applications to contain both fireand smoke to the area of origin. Especially for mid- and high-rise buildings, where fire and smoke mustbe prevented from spreading to the next floor. Since the floor assembly is typically fire-rated, one routefor the fire spread is through and up the exterior curtain wall system. THERMAFIBER Safing Insulation isalso used in conjunction with various sealants and caulks, in wall and floor penetration (poke-through)applications, head-of-wall construction joints, and other construction joints.

It is important to note that one of the most valuable yet misunderstood applications of THERMAFIBER Safing Insulation is its use in exterior curtain wall assemblies to safe-off the openingbetween concrete floor slabs and the curtain wall assemblies. Many people still believe the myth that allthermal insulations are the same when used in the curtain wall spandrel panels as long as THERMAFIBER Safing Insulation is used in the assembly. This is simply not true. Actual fire tests haveproven that low-melt-point insulations, such as glass fiber types, will disintegrate quickly once exposedto fire, leaving the curtain wall unprotected. Then, as the now-unprotected curtain wall disintegrates orfalls away, the safing insulation will no longer be supported, and the fire will spread to the floor(s) above.Effective perimeter fire containment can only be achieved when a fire-compatible product with the abilityto resist high temperatures (such as THERMAFIBER Curtain Wall Insulations or THERMAFIBERFIRESPAN Insulations) is used in conjunction with the THERMAFIBER Safing Insulation, acting together asa system. (See TF685, TF686 and TF871 for additional information).

In curtain wall fire-containment applications, THERMAFIBER Safing Insulation fills the void between theslab edge and the curtain wall insulation to contain fire. Foil-faced insulation impedes the passage ofsmoke and noxious gases. Install THERMAFIBER Safing Insulation, of proper width (2" to 8" max. opening), compression fit in safe-off area (foil side up, if required) between THERMAFIBER FIRESPAN orCW Curtain Wall Insulation and floor slabs, on safing "Z" clips spaced as required in the design (24" or12" o.c. maximum), leaving no voids. Compression fitting the safing insulation is critical to assuring atight seal. See specific test description for proper installation details. Install proper topping material,such as THERMAFIBER SMOKE SEAL Compound, or other approved smoke sealants as indicated in the spe-cific test description or architectural specification.

THERMAFIBER Safing Insulation provides a noncombustible, fire-resistant forming/packing material formany types of penetrations in walls and floor/ceilings. In all poke-through penetrations, clean substrateof dirt, dust, grease, oil, efflorescence, loose material or other matter. With a serrated knife, cut THERMAFIBER Safing Insulation slightly wider than the opening. Compress and tightly fit the minimumthickness and density of insulation required (per system specification) completely around penetrant. Forfloor slab openings, compress or install THERMAFIBER Safing Insulation according to details indicated inthe specific test description or architectural specification to seal completely around cables, ducts, pipingor other utilities.

THERMAFIBER Safing Insulation is also used as a forming material in head-of-wall, floor to floor, floor towall, and wall to wall construction joints. It is compressed and slid into joint openings to completely fillthe gap between the intersection of the walls, floor, etc.

THERMAFIBER® Safing Insulation

UL- and OPL-labeled* safing insulation for firestops and fire-containment systems • Firestop product for curtain wall fire and smoke containment systems, floor and wall penetrations,

head-of-wall, and other construction joint systems. • Fire resistant and noncombustible. • Economical; installs quickly and easily. • Aids sound control in many assemblies. • Available in unfaced felt (plain) or with a tough scrim-reinforced foil facing (FSP). • Durable; nondeteriorating and noncorrosive.

Description

Perimeter Fire Containment,Penetrations and Construction Joints

Installation Perimeter Installation

Penetration Application

Construction JointApplication

* UL is an abbreviation for Underwriters Laboratories Inc.; OPL is an abbreviation for Omega Point Laboratories, Inc.

Submittal Sheet07840

Page 12: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

Trademarks THERMAFIBER, FIRESPAN and THENAME IN MINERAL WOOL are trade-marks of Thermafiber Inc. SMOKESEAL is a trademark of United StatesGypsum Company.

NoteProducts described here may not beavailable in all geographic markets.Consult your local sales office or rep-resentative for information.

Notice THERMAFIBER INC. shall not beliable for incidental and consequentialdamages, directly or indirectlysustained, nor for any loss caused byapplication of these goods not inaccordance with current printedinstructions or for other than theintended use. THERMAFIBER’Sliability is expressly limited toreplacement of defective goods. Anyclaim shall be deemed waived unlessmade in writing within thirty (30)days from date it was or reasonablyshould have been discovered.

Safety First!Follow good safety and industrialhygiene practices while handling andinstalling products and systems.Take necessary precautions and wearthe appropriate personal protectiveequipment as needed. Read materialsafety data sheets and related litera-ture on products before specificationand/or installation.

Health AspectsInformation about health aspects ofusing THERMAFIBER® Curtain WallInsulation products are thoroughlyexplained in North AmericanInsulation ManufacturersAssociation’s (NAIMA) Health andSafety facts for rock and slag woolinsulation document #63. ContactThermafiber, Inc. for more details.

Product Designation Flame Spread Smoke Developed Safing, Regular (Unfaced) 0 0 Safing (Foil-Faced) 25 0 Products have a class A interior finish rating per NFPA 101, life safety code.

Product Actual Density Minimum ApplicationDesignation Density Tolerance-pcf(1) Thickness MethodSafing 4.0 -0.5 +1.0 1" safing clips and/or compression fitSafing 6.0 -0.75 +2.0 1-1/2" safing clips and/or compression fit Safing 8.0 -1.0 +2.0 1" safing clips and/or compression fit(1) On packaging weight basis.

THERMAFIBER Safing Insulation meets the following:

ASTM C 665 - Federal Specification HH-I-521F–Safing insulation as Types I and III, Class A, Category 1.

ASTM C 612-00 - Federal Specification HH-I-558B–Safing insulation as Types IA, IB and II.

ASTM E 136 - Rated noncombustible as defined by NFPA Standard 220 when tested according to ASTM E 136.

ASTM E 814 or UL 1479 - Safing insulation used in conjunction with SMOKE SEAL Compound, or other approved material in through - penetration firestop systems.

UL 2079 - Safing insulation used in conjunction with various sealants and caulks in construction jointsystems.

ASTM C 553 - THERMAFIBER Insulations absorb less than 1% moisture by weight and volume.

Safing insulation products are approved by: New York City Board of Standards & Appeals– 39-74-SM &MEA 209-82-M, Vol. II.

THERMAFIBER blankets are a mineral fiber material manufactured from blast furnace slag, a by-product ofiron ore reduction, and naturally occurring rock. THERMAFIBER blankets contain greater than 80% post-industrial recycle content. This product contains No Asbestos.

System performance following substitution of materials or compromise in assembly design cannot becertified and may result in failure of fire performance under certain conditions. Products and systemsprovided by Thermafiber Inc. are warranted to be free from defects in material workmanship. ContactThermafiber Inc. for complete warranty details.

Store in a cool, dry place.

Surface BurningCharacteristics (According to ASTM E 84)

Product Density

Standards Compliance

Composition andMaterials

Warranty

Storage

Submittal Approvals:

Product Data

Job Name

Contractor Date

INC

3711 West Mill Street Wabash, IN 46992-8687 1-888-TFIBER1 (834-2371)www.thermafiber.com

TF612/Rev 11/06Copyright 2004, Thermafiber Inc. Printed in U.S.A.

Technical Data

MMAADDEE IINN UUSSAATTHHEERRMMAAFFIIBBEERR MMAADDEE FFRROOMM

RREECCYYCCLLEEDD MMAATTEERRIIAALLSS

For the most up-to-date technical data, please refer to our website at www.thermafiber.com

Page 13: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

Material Safety Data Sheet

MSDS No.: 270Revision No.: 003Revision Date: 06/18/03Page: 1 of 2

Product name: Mineral woolDescription: Synthetic vitreous fiber

Supplier: Hilti, Inc. P.O. Box 21148, Tulsa, OK 74121

Emergency # (Chem-Trec.): 1 800 424 9300 (USA, PR, Virgin Islands, Canada); 001 703 527 3887 (other countries)

INGREDIENTS AND EXPOSURE LIMITS

Ingredients: CAS Number: P EL: TLV: STEL:

Slag wool fiber 65997-17-3 NE 1 fiber / cc NE

Phenolic resin 09003-35-4 NE NE NE

Polyvinyl alcohol 09002-89-5 NE NE NE

Abbreviations: PEL = OSHA Permissible Exposure Limit. TLV = ACGIH Threshold Limit Value. STEL = Short Term Exposure Limit. NE = None Established.NA = Not Applicable.

PHYSICAL DATA

Appearance: 2’ x 4’ x 4” sheets. Odor: Negligible.

Boiling Point: Not applicable. Vapor Pressure: Not applicable.

Melting Point: Approx. 2400° F VOC Content: Not applicable.

Evaporation Rate: Not applicable. Solubility in Water: Insoluble.

pH: Not applicable. Specific Gravity: Not determined.

FIRE AND EXPLOSION HAZARD DATA

Flash Point: Not applicable. Flammable Limits: Not applicable.

Extinguishing Media: As appropriate for surrounding fire; material does not burn.

Special Fire Fighting Procedures: Soak cartons to help prevent the spread of fire. Use a self-contained breathing apparatus when fighting firesinvolving chemicals.

Unusual Fire and Explosion Hazards: None known.

REACTIVITY DATA

Stability: Stable. Hazardous Polymerization: Will not occur.

Incompatibility: Strong acids.

Hazardous Decomposition Products: Thermal decomposition products can be formed at temperatures exceeding 2000° F. Thermal decompositioncan yield CO and CO2.

Conditions to Avoid: None known.

HEALTH HAZARD DATA

Known Hazards: Acute: Eye, skin and respiratory irritation. Chronic: Respiratory impairment.

Routes of Exposure: Inhalation, Dermal.

Signs and Symptoms of Exposure: Eyes: Mechanical irritation. Skin: Itching, irritation. Inhalation: Nose, throat and upper respiratory tractirritation.

Carcinogenicity: Slag wool has been classified by the IARC as Group 3 – Unclassifiable as to Carcinogenicity in Humans.

Medical Conditions Eye, skin, and respiratory conditions.Aggravated by Exposure:

INTR

ODUC

TION

APPL

ICAT

IONS

/ PR

ODUC

TSSY

STEM

DET

AILS

ESTI

MAT

ING

TABL

ES /

TEC

H DA

TA

Saving Lives through innovation & education ❘ Hilti Firestop Guide 2005–2006 ❘ 1-800-879-8000 ❘ www.us.hilti.com480

W3321_12_TablesTech_TP_70.qxd 3/23/05 7:56 AM Page 480

Page 14: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

Material Safety Data SheetINTRODUCTION

APPLICATIONS / PRODUCTSSYSTEM

DETAILSESTIM

ATING TABLES / TECH DATA

Saving Lives through innovation & education ❘ Hilti Firestop Guide 2005–2006 ❘ 1-800-879-8000 ❘ www.us.hilti.com 481

MSDS No.: 270Revision No.: 003Revision Date: 06/18/03Page: 2 of 2

EMERGENCY AND FIRST AID PROCEDURES

Eyes: Flush with plenty of water while holding eyelids apart. Avoid rubbing the eyes as mechanical abrasions canoccur. Call a physician if symptoms persist.

Skin: Wash with soap and water. Launder clothing before reuse.

Inhalation: Move to fresh air.

Ingestion: No ill effects expected.

Other: Referral to a physician is recommended if there is any question about the seriousness of the injury/exposure.

CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT

Ventilation: General (natural or mechanically induced fresh air movements).

Eye Protection: Safety goggles recommended to prevent particulates from irritating the eyes.

Skin Protection: Cloth gloves and long sleeves to protect skin from irritating fibers.

Respiratory Protection: Use local exhaust and/or a NIOSH-approved dust respirator when air movement is inadequate to control dusts / fibers below recommended exposure levels.

PRECAUTIONS FOR SAFE HANDLING AND USE

Handling and Storing Precautions: Avoid generating dusts. Local exhaust may be required to control dusts if power tools are used for cutting /trimming. Wear appropriate personal protective equipment. Store away from moisture; keep dry.

Spill Procedures: Not applicable.

REGULATORY INFORMATION

Hazard Communication: This MSDS has been prepared in accordance with the federal OSHA Hazard Communication Standard 29 CFR1910.1200.

HMIS Codes: Health 1, Flammability 0, Reactivity 0, PPE B (Gloves, Goggles)

DOT Shipping Name: Not regulated.

IATA / ICAO Shipping Name: Not regulated.

TSCA Inventory Status: Chemical components listed on TSCA inventory.

SARA Title III, Section 313: This product does not contain any toxic chemicals which are subject to reporting under Section 313 of SARATitle III (40 CFR Part 372).

EPA Waste Code(s): Not regulated by EPA as a hazardous waste.

Waste Disposal Methods: Consult with regulatory agencies or your corporate personnel for disposal methods that comply with local,state, and federal safety, health and environmental regulations.

CONTACTS

Customer Service: 1 800 879 8000 Technical Service: 1 800 879 8000

Health / Safety: 1 800 879 6000 Jerry Metcalf (x6704)

Emergency # (Chem-Trec): 1 800 424 9300 (USA, PR, Virgin Islands, Canada); 001 703 527 3887 (other countries)

The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee or warranty of any kindexpressed or implied is made with respect to the information provided.

W3321_12_TablesTech_TP_70.qxd 3/22/05 3:36 PM Page 481

Page 15: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad
Page 16: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

Hilti, Inc. 5400 South 122nd East Avenue

Tulsa, OK 74146

1-800-879-8000 www.hilti.com

February 24, 2009 To Whom It May Concern: Re: Hilti Mineral Wool-LEED Info. The Hilti Mineral Wool is manufactured in Waubash Indiana. There is no post-consumer or post-industrial content in Hilti Mineral Wool. There is no detectable VOC content in this product. Hilti Mineral Wool is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal. Please feel free to contact me at (918) 872-3704 if you have questions. Sincerely, Jerry Metcalf MPH, CHMM Safety/Environmental Manager Hilti Inc. 918 872 3704 [email protected] Rev. Date: 2/24/09

Page 17: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad
Page 18: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

System No. C-AJ-1226

SECTION A-A

CAJ 1

226

A

Reproduced by HILTI, Inc. Courtesy ofUnderwriters Laboratories, Inc.

June 27, 2007

F Rating — 3 HrT Rating — 0 Hr

L Rating At Ambient — Less Than 1 CFM/Sq FtL Rating At 400 F — 4 CFM/Sq Ft

C US

CL

ASS I F IED

1. Floor or Wall Assembly — Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Wall may also be constructed of anyUL Classified Concrete Blocks*. Max diam of opening is 32 in.

2. Metallic Sleeve — (Optional) Nom 32 in. diam (or smaller) Schedule 40 (or heavier) steel sleeve cast or grouted into floor or wall assembly, flushwith floor or wall surfaces or extending a max of 3 in. above floor or beyond both surfaces of wall.

2A. Sheet Metal Sleeve — (Optional) Max 6 in. diam, min 26 ga galv steel provided with a 26 ga galv steel square flange spot welded to the sleeveat approx mid-height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. larger than the sleeve diam. The sleeve is to be cast inplace and may extend a max of 4 in. below the bottom of the deck and a max of 1 in. above the top surface of the concrete floor.

2B. Sheet Metal Sleeve — (Optional) - Max 12 in. diam, min 24 ga galv steel provided with a 24 ga galv steel square flange spot welded to thesleeve at approx mid-height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. larger than the sleeve diam. The sleeve is to becast in place and may extend a max of 4 in. below the bottom of the deck and a max of 1 in. above the top surface of the concrete floor.

3. Through-Penetrant — One metallic pipe, tube or conduit to be installed either concentrically or eccentrically within the firestop system. Theannular space between penetrant and periphery of opening shall be min 0 in. (point contact) to max 1-7/8 in. Penetrant may be installed withcontinuous point contact. Penetrant to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallicpenetrants may be used:

A. Steel Pipe — Nom 30 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.B. Iron Pipe — Nom 30 in. diam (or smaller) cast or ductile iron pipe.C. Copper Pipe — Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe.D. Copper Tubing — Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.E. Conduit — Nom 6 in. diam (or smaller) steel conduit.F. Conduit — Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT).

4. Firestop System — The firestop system shall consist of the following:A. Packing Material — Min 4 in. thickness of min 4 pcf mineral wool batt insulation firmly packed into opening as a permanent form. Packing

material to be recessed from top surface of floor or sleeve or from both surfaces of wall or sleeve as required to accommodate the requiredthickness of fill material.

B. Fill, Void or Cavity Material* — Sealant — Min 1/4 in. thickness of fill material applied within the annulus, flush with top surface of floor orsleeve or with both surfaces of wall or sleeve. At the point or continuous contact locations between penetrant and concrete or sleeve, a min1/4 in. diam bead of fill material shall be applied at the concrete or sleeve/ pipe penetrant interface on the top surface of floor and on bothsurfaces of wall.HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant

*Bearing the UL Classification Mark

A

2

34B

3

14B

4A

Page 19: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

System No. C-AJ-3095

CAJ 3

095

Page: 1 of 2

1. Floor or Wall Assembly — Min 2-1/2 in. (64 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600 2400 kg/m3) concrete floor ormin 3 in. (76 mm) thick reinforced lightweight or normal weight concrete wall. Wall may also be constructed of any UL Classified Concrete Blocks*.Max diam of opening is 6 in. (152 mm).See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.

2. Sleeve — (Optional) — Nom 6 in. (152 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe cast or grouted into floor or wall assembly, flushwith floor or wall surfaces or extending a max 3 in. (76 mm) above the floor or both surfaces of the wall. If the steel sleeve extends above the flooror both surfaces of the wall, the T Rating of the firestop system is 0 Hr.

3. Cables — Aggregate cross-sectional area of cables in opening to be min 25 percent to max 45 percent of the aggregate cross-sectional area ofthe opening. Cables to be rigidly supported on both sides of floor or wall assembly. Any combination of the following types and sizes of metallicconductor or fiber optic cable may be used:

A. Max 500 kcmil single copper connector power cable with thermoplastic insulation and polyvinyl chloride (PVC) jacket. When single copperconductor power cable is used, T Rating is 0 hr.

B. Max 350 kcmil single conductor power cables with either aluminum or copper conductors and cross-linked polyethylene (XPLE) insulation.When single aluminum conductor power cable is used, T Rating is 0 hr. When single copper conductor power cable is used, T Rating is 1/2 hr.

C. Max 300 pair No. 24 AWG copper conductor telecommunication cables with polyvinyl chloride (PVC) insulation and jacket material. Whentelecommunication cable is used, T Rating is 0 hr.

D. Max three copper connector No. 6 AWG cable with polyvinyl chloride (PVC) insulation and jacket material. When multi-connector powercable is used, T Rating is 0 hr.

E. Max 7/C copper conductor No. 12 AWG multiconductor power and control cables with PVC or cross-linked polyethylene (XLPE) insulationand PVC jacket. When multiconductor power and control cable is used, T Rating is 3/4 hr.

F. Multiple fiber optical communication cables jacketed with PVC and having a max outside diam of 1/2 in. When fiber optic cable is used, TRating is 3/4 hr.

G. Max 3/C copper conductor No. 12 AWG with Bare aluminum ground, polyvinyl chloride (PVC) insulated steel, Metal-clad cable+. When MCcable is used, T Rating is 0 hr.AFC CABLE SYSTEMS INC

H. Max 3/C with ground 2/0 AWG copper conductor SER cable with cross-linked polyethylene (XLPE) insulation and polyvinyl chloride (PVC)jacket. When SER cable is used, T Rating is 0 hr.

Reproduced by HILTI, Inc. Courtesy ofUnderwriters Laboratories, Inc.

May 29, 2008

F Rating - 3 HrT Ratings - 0, 1/2 and 3/4 Hr (See Item 3)

C US

CL

ASS IF IED

SECTION A-A

A

A

53

1

242

3 5

Page 20: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

Page: 2 of 2

I. Max RG/U coaxial cable with polyethylene (PE) insulation and polyvinyl chloride (PVC) jacket having a max outside diameter of ½ in. Whencoaxial cable is used, T Rating is 0 hr.

J. Fire Resistive Cables* - Max 1-1/4 in. (32 mm) diam single conductor or multi conductor Type MI cable. A min 1/8 in. (3 mm) separation shallbe maintained between MI cables and any other type of cable. When Fire Resistive Cables *are used, T Rating is 0 hr.

K. Through Penetrating Product* — Any Cables, Metal-Clad Cable+ or Armored Cable+ currently Classified under the Through PenetratingProducts category.See Through Penetrating Product (XHLY) category in the Fire Resistance Directory for names of manufacturers.

4. Packing Material — Min 2 in. (51 mm) thickness of min 4.0 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a permanentform. Packing material to be recessed 1/2 in. (13 mm) from top surface of floor or from both surfaces of wall as required to accommodate the fillmaterial. If the steel sleeve (Item 2) extends above the top of the floor, the packing material shall be flush with the bottom surface of the floor.

5. Fill, Void or Cavity Material* — Sealant — Min 1/2 in. (13 mm) thickness of fill material applied within the annulus, flush with top surface of floor orwith both surfaces of wall.HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant.

*Bearing the UL Classification Mark+Bearing the UL Listing Mark

C US

CL

ASS IF IEDReproduced by HILTI, Inc. Courtesy ofUnderwriters Laboratories, Inc.

May 29, 2008

System No. C-AJ-3095

CAJ 3

095

F Rating - 3 HrT Ratings - 0, 1/2 and 3/4 Hr (See Item 3)

Page 21: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

System No. C-AJ-8099

SECTION A-A

CAJ 8

099

Page: 1 of 2

1. Floor or Wall Assembly — Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete flooror min 5 in. (127 mm) reinforced lightweight or normal weight concrete wall. Wall may also be constructed of any UL Classified Concrete Blocks*.Floor may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow core Precast Concrete Units*. Max area of square, rectangularor circular opening is 192 sq in. (1239 cm2) with max dimension of 24 in. (61 cm). When Precast Concrete Unit floors are used, max area ofsquare, rectangular or circular opening is 49 sq in. (316 cm2) with max dimension of 7 in. (17.8 cm).See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers.

2. Through-Penetrant — One or more pipes or tubes to be installed within the opening. The total number of through-penetrants is dependent on thesize of the opening and types and sizes of the penetrants. Any combination of the penetrants described below may be used provided that thefollowing parameters relative to the annular spaces and the spacings between the pipes are maintained. The separation between cable bundle,tubes and insulated tubes shall be a min 1/2 in. (13 mm) to max 3-1/8 in. (79 mm). The annular space between penetrants and the periphery ofopening shall be a min 1/2 in. (13 mm) to max 5 in. 127 mm). Pipes or tubes to be rigidly supported on both sides of floor or wall assembly. Thefollowing types and sizes of metallic pipes or tubes may be used.

A. Copper Tubing — Nom 3 in. (76 mm) diam (or smaller) Type L (or heavier) copper tube.B. Copper Pipe — Nom 3 in. (76 mm) diam (or smaller) Regular (or heavier) copper pipe.C. Steel Pipe — Nom 3 in. (76 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.D. Iron Pipe — Nom 3 in. (76 mm) diam (or smaller) cast or ductile iron pipe.E. Conduit — Nom 3 in. (76 mm) diam (or smaller) electric metallic tubing (EMT) or steel conduit.F. Flexible Steel Conduit+ — Nom 1 in. (25 mm) diameter (or smaller) flexible steel conduit.

See Flexible Metal Conduit (DXUZ) category in the Electrical Construction Material Directory for names of manufacturers.G. Through Penetrating Product* — Flexible Metal Piping — The following types of steel flexible metal gas piping may be used:

1.) Nom 2 in. (51 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides offloor or wall assembly.

OMEGA FLEX INC2.) Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of

floor or wall assembly.GASTITE, DIV OF TITEFLEX3.) Nom 2 in. (51 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of

floor or wall assembly.WARD MFG INCThe hourly T Rating is 3/4 hr when a pipe or tube with fiber-glass insulation is used, or 0 hr when a pipe or tube, a pipe or tube with AB/PVC

insulation or a cable bundle is used. T he T Rating is 0 hr when metallic penetrants without pipe insulation are used.

A

Reproduced by HILTI, Inc. Courtesy ofUnderwriters Laboratories, Inc.

August 03, 2007

F Rating — 3 HrT Ratings — 0 and 3/4 Hr (See Item 2)

A

C US

CL

ASS IF IED2

3A

3B

4

5B

2

5B

5A

1

Page 22: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

Page: 2 of 2

3. Pipe Insulation — (Optional)—The following types of pipe insulation may be used with metallic penetrants (Items 2A, 2B, 2C, 2D and 2F):A. Pipe Covering* — Nom 1 in. (25 mm) thick (or thinner) hollow cylindrical heavy density (min 3.5 pcf or 56 kg/m3) glass fiber units jacketed

on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied self-sealing lap tape. Transversejoints secured with metal fasteners or with butt tape supplied with the product.

See Pipe and Equipment Covering - Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipecovering material meeting the above specifications and bearing the UL Classifica tion Marking with a Flame Spread Index of 25 or less anda Smoke Developed Index of 50 or less may be used.

B. Tube Insulation-Plastics+++ — Nom 3/4 in. (19 mm) thick (or thinner) acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foamfurnished in the form of tubing.See Plastics+++ (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any RecognizedComponent tube insulation material meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may beused.

4. Cables — Max 2 in. (51 mm) diam tight bundle of cables installed within the opening and rigidly supported on both sides of floor or wall assembly.The space between the cables and periphery of the opening shall range from min 2 in. (51 mm) to max 4 in. (102 mm). Any combination of thefollowing types and sizes of metallic conductor of fiber optic cable may be used:

A. Max 500 kcmil single copper connector power cable with thermoplastic insulation and polyvinyl chloride (PVC) jacket.B. Max 300 pair No. 24 AWG copper conductor telecommunication cables with PVC insulation and jacket material.C. Max 7/C copper conductor No. 12 AWG multiconductor power and control cables with PVC or cross-linked polyethylene (XLPE) insulation

and PVC jacket.D. Multiple fiber optical communication cables jacketed with PVC and having a max outside diam of 1/2 in.E. Max 3/C copper conductor No. 12 AWG with bare aluminum ground, PVC insulated steel Metal-Clad cable.

5. Firestop System — The firestop system shall consist of the following:A. Packing Material — Min 4 in. (102 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a

permanent form. Packing material to be recessed from top surface of floor or both surfaces of wall to accommodate the required thicknessof fill material. When Precast Concrete Unit floors are used, packing material shall be installed at a thickness equal to the thickness of thefloor minus 1/2 in. (13 mm), flush with bottom surface of floor.

B. Fill Void or Cavity Materials* - Sealant — Min 1/2 in. (51 mm) thickness of fill material applied within the annulus, flush with top surface offloor or with both surfaces of wall.HILTI CONSTRUCTION CHEMICALS, DIV OFHILTI INC — FS-ONE Sealant+++Bearing the UL Recognized Component Marking*Bearing the UL Classification Mark+Bearing the UL Listing Mark

C US

CL

ASS IF IED

System No. C-AJ-8099

CAJ 8

099

Reproduced by HILTI, Inc. Courtesy ofUnderwriters Laboratories, Inc.

August 03, 2007

F Rating — 3 HrT Ratings — 0 and 3/4 Hr (See Item 2)

Page 23: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad
Page 24: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad
Page 25: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad
Page 26: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

Sheet Drawing No.HILTI, Inc.

Tulsa, Oklahoma USA (918) 252-6000Date

Scale

FRONT VIEWA

A

SECTION A-A

NOTES : 1. MAXIMUM DIAMETER OF OPENING : A. 32-1/4" FOR STEEL STUD WALLS. B. 14-1/2" FOR WOOD STUD WALLS.

2. ANNULAR SPACE = MINIMUM 0", MAXIMUM 2-1/4". 3. PIPE MAY BE INSTALLED WITH CONTINUOUS POINT OF CONTACT. 4. PIPE MAY BE INSTALLED AT AN ANGLE NOT GREATER THAN 45°

FROM PERPENDICULAR.

1. GYPSUM WALL ASSEMBLY (UL/ULC CLASSIFIED U300 OR U400 SERIES) (1-HR. OR 2-HR. FIRE-RATING) (2-HR. SHOWN).

2. (NOT SHOWN). WOOD STUDS TO CONSIST OF NOMINAL 2" x 4" LUMBER. STEEL STUDS TO BE MINIMUM 2-1/2" WIDE.

3. PENETRATING ITEM TO BE ONE OF THE FOLLOWING : A. MAXIMUM 30" DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER). B. MAXIMUM 30" DIAMETER CAST IRON PIPE. C. MAXIMUM 6" NOMINAL DIAMETER COPPER PIPE. D. MAXIMUM 6" NOMINAL DIAMETER STEEL CONDUIT. E. MAXIMUM 4" NOMINAL DIAMETER EMT.

4. MINIMUM 5/8" DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT. 5. MINIMUM 1/2" BEAD HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT AT POINT OF CONTACT.

WL1054q

1 of 1

7/32" = 1"

Nov. 6, 2002

UL/cUL SYSTEM NO. W-L-1054

F-RATING = 1-HR. OR 2-HR. T-RATING = 0-HR.

L-RATING AT AMBIENT = LESS THAN 1 CFM/SQ. FT. L-RATING AT 400°F = 4 CFM/SQ. FT.

WL1

054q

.1106

02

1

3

2

4

5

Page 27: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad
Page 28: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad
Page 29: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad
Page 30: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad
Page 31: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

Sheet Drawing No.HILTI, Inc.

Tulsa, Oklahoma USA (918) 252-6000Date

Scale

FRONT VIEW

A

A

SECTION A-A

WL3071e

1 of 1

3/16" = 1"

SEPT. 16, 1999

UL/cUL SYSTEM NO. WL3071

F RATING = 1-HR. OR 2-HR.T RATING = 1/4 HR. OR 3/4 HR.

L RATING AT AMBIENT = LESS THAN 1 CFM/SQ. FT.L RATING AT 400° F = 4 CFM/SQ. FT.

WL3

071e

.0916

99

1. GYPSUM WALL ASSEMBLY (UL/ULC CLASSIFIED U300 OR U400 SERIES) (1-HR. OR 2-HR. FIRE-RATING) (2-HR. SHOWN).

2. MAXIMUM 3/C (+ GRND) NO. 2/0 AWG ALUMINUM OR COPPER SER CABLE WITH PVC INSULATION (MAX. QTY. = 2).

3. HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT: A. MINIMUM 5/8" DEPTH, FOR A 1-HR. FIRE-RATING. B. MINIMUM 1-1/4" DEPTH, FOR A 2-HR. FIRE-RATING.

NOTES : 1. MAXIMUM DIAMETER OF OPENING = 3". 2. ANNULAR SPACE = MINIMUM 1/2", MAXIMUM 1-1/2".

1

2

3

Page 32: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

Page: 1 of 2

CP61

7 / C

P617

L

Wall Opening Protective Materials (CLIV)

CP 617 Firestop Putty Pads, for use with max 4 by 4 in. flush device UL Listed Metallic Outlet Boxes installed with steel cover plates in 1 and 2 hr. fire rated gypsum wallboard wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed as specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Min 1/8 in. thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the side of the outlet box against the stud) and completely seal against the stud within the stud cavity. When moldable putty pad outlet box protective material is used on boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back to back.

CP 617 Firestop Putty Pads, for use with max 4-11/16 by 4-11/16 in., or max 4-3/8 by 4-7/8 in., flush device UL Listed Metallic Outlet Boxes installed with steel cover plates for use in 1 hr fire rated V446 gypsum board/steel stud or U341 gypsum board/wood stud Wall and Partition Design No. in the Fire Resistance Directory. When U341 wall design is used, wall shall be sheathed with 5/8 in. gypsum board, and glass or mineral fiber batt insulation shall be installed in stud cavities in accordance with U341 design. Min 1/8 in. thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the side of the outlet box against the stud) and to completely seal against the box within the stud cavity. When moldable putty pad outlet box protective material is used on boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. and the boxes may be installed back-to-back.

CP 617 Firestop Putty Pads , for use with max 4-11/16 by 4-11/16 in. flush device UL Listed Metallic Outlet Boxes installed with steel cover plates for use in 1 and 2 hr fire rated gypsum board wall assemblies framed with min 3-1/2 in. deep steel studs and constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Min 0.8 pcf density fiberglass batt insulation is to be installed within the wall cavity required for 1 hr fire rated gypsum board wall assemblies and optional in 2 hr fire rated gypsum wallboard assemblies. Min 1/8 in. thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the side of the outlet box against the stud) and to completely seal against the box within the stud cavity. When moldable putty pad outlet box protective material is used on boxes on both sides of wall as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back-to-back.

Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.

April 18, 2007

as Tested to ANSI/UL 2631 or 2 Hr Rating

C US

CL

ASS I F IED1 or 2 Hr Gypsum Wall

Assembly (2 Hr Shown)

Power Cable

1/8" thick CP617/CP617L/CP617XL Firestop Putty Pad

Wood Stud or Steel Stud (Not Shown)

UL Listed Non-Metallic Outlet Box (Refer to UL listing) Or UL Listed Metallic Outlet Box (Refer to UL listing)

Page 33: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad

Page: 2 of 2

CP61

7 / C

P617

L

CP 617 Firestop Putty Pads, for use with max 4 by 3-3/4 by 3 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Carlon Electrical Products, made from polyvinyl chloride, and bearing a 2 hr rating under the "Outlet Boxes and Fittings Classification for Fire Resistance" category in the Fire Resistance Directory. Putty pads and boxes for use in 1 and 2 hr fire rated gypsum wallboard assemblies, framed with min 3-1/2 in. deep wood studs and constructed as specified in the individual U300 Series Wall and Partition Designs in the Fire Resistance Directory. Outlet box secured to wood stud by means of two nailing tabs supplied with the outlet box. Min 1/8 in. thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the side of the outlet box against the stud) including the nailing tab and completely seal against the stud within the stud cavity. Outlet boxes installed with steel or plastic cover plates. When moldable putty pad outlet box protective material is used on boxes on both sides of wall as directed, the horizontal separation between boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back to back .

CP 617 Firestop Putty Pads, for use with max 4 by 4 by 2-7/8 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Carlon Electrical Products, made from polyvinyl chloride, and bearing a 2 hr rating under the "Outlet Boxes and Fittings Classification for Fire Resistance" category in the Fire Resistance Directory. Putty pads and boxes for use in the 1 hr fire rated V446 gypsum board/steel stud or U341 gypsum board/wood stud Wall and Partition Design in the Fire Resistance Directory. When U341 wall design is used, wall shall be sheathed with 5/8 in. gypsum board, and glass or mineral fiber batt insulation shall be installed in stud cavities in accordance with U341 design. Outlet box secured to steel stud by means of fastening tab supplied with the outlet box. Min 1/8 in. thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the side of the outlet box against the stud) including the tab and completely seal against the stud within the stud cavity. Outlet boxes installed with steel or plastic cover plates. When moldable putty pad outlet box protective material is used on boxes on both sides of wall as directed, the horizontal separation between boxes on opposite sides of the wall may be less than 24 in. and the boxes may be installed back to back.

CP 617 Firestop Putty Pads, for use with max 2-1/4 by 3-3/4 by 2-3/4 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Pass and Seymore, Inc., and bearing a 2 hr rating under the "Outlet Boxes and Fittings Classification for Fire Resistance" category in the Fire Resistance Directory. Putty pads and boxes for use in 1 and 2 hr fire rated gypsum wallboard assemblies, framed with min 3-1/2 in. deep wood studs and constructed as specified in the individual U300 Series Wall and Partition Designs in the Fire Resistance Directory. Outlet box secured to wood stud by means of two nailing tabs supplied with the outlet box. Min 1/8 in. thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the side of the outlet box against the stud) including the nailing tab and completely seal against the stud within the stud cavity. Outlet boxes installed with steel or plastic cover plates. When moldable putty pad outlet box protective material is used on boxes on both sides of wall as directed, the horizontal separation between boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back to back .

CP 617 Firestop Putty Pads, for use with max 4 by 3-3/4 by 3 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Allied Molded Products, Inc., made from fiber reinforced thermoplastic and bearing a 2 hr rating under the "Outlet Boxes and Fittings Classification for Fire Resistance" category in the Fire Resistance Directory. Putty pads and boxes for use in 1 hr fire rated gypsum wallboard assemblies, framed with min 3-1/2 in. deep wood studs and constructed as specified in the individual U300 Series Wall and Partition Designs in the Fire Resistance Directory. Outlet box secured to wood stud by means of two nailing tabs supplied with the outlet box. Min 1/8 in. thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the side of the outlet box against the stud) including the nailing tab and completely seal against the stud within the stud cavity. Outlet boxes installed with plastic cover plates. When moldable putty pad outlet box protective material is used on boxes on both sides of wall as directed, the horizontal separation between boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are not installed back to back.

CP 617 Firestop Putty Pads , for use with max 4 by 4 in. by 1-½ in. deep flush device UL Listed Metallic Outlet Boxes installed with steel cover plates in 1 hr. fire rated gypsum wallboard wall assemblies framed with min 3-1/2 in. deep wood or steel studs and constructed as specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the Fire Resistance Directory. Min 1/8 in. thick moldable putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the side of the outlet box against the stud) and completely seal against the stud within the stud cavity. The boxes are installed back to back with 5 in. by 4 in. UL Classified fire block, FS 657 or CP 657 installed in the cavity between the two boxes.

C US

CL

ASS IF IED

Wall Opening Protective Materials (CLIV)as Tested to ANSI/UL 263

1 or 2 Hr Rating

Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc.

April 18, 2007

Page 34: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad
Page 35: FIRESTOP SUBMITTAL PACKAGE...for complete installation information Application of firestop putty 1. Remove label from one side of pad. For a 1 to 2 hour fire rating, one CP 617 pad