18
Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway Fred Hervey

Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test

Fire Endurance Testing of Floor Truss Assemblies

Prepared by:

Joe Treadway

Fred Hervey

Page 2: Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test

ASTM E119 – Standard Test Methods for Fire Tests of Building Construction and Materials

ASTM E119 prescribes a standard fire exposure of controlled extent and severity.

Performance is defined as the period of resistance to standard exposure before the first critical point in behavior (conditionsof acceptance)is observed.

Conditions of acceptance for floor systems include:• Sustained applied load during classification period• No passage of flame or hot gasses• Maximum and average temperatures of the unexposed side of

the specimen• Maximum and average temperatures of the steel joists

Page 3: Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test

•Two tests conducted in Toronto at ULCAugust 7, 2004 - 35 ft. Restrained Assembly

August 11, 2004 - 35 ft. Unrestrained Assembly

•Two tests conducted in Northbrook at ULIAugust 19, 2004 - 18 ft. Restrained Assembly

August 25, 2004 - 18 ft. Restrained Assembly (1/2 in. fireproofing)

Testing Summary

Page 4: Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test

WTC Floor Assembly

Page 5: Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test

Test Restraint Conditions

Restrained Test Condition Unrestrained Test Condition

Reaction FrameFloor Slab

Gap

Reaction FrameFloor Slab

Page 6: Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test

Effect of Restraint Against Thermal Expansion

Heated floor assembly wants to expandIf thermal expansion is restrained, forces will developFloor assembly is subjected to fire conditions

Floor Asse

mbly

Span

Furnace

Page 7: Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test

Design and Fabrication of Test Assemblies

Page 8: Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test

Preparation of Test Assemblies

Page 9: Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test

Instrumentation

Each Assembly Contained:

• 159 Thermocouples–44 on Each Main Truss

–~ 6 miles of thermocouple wire

• 2 Plate TC’s, 2 Radiometers, 2 Asp. TC’s

• 15 Deflection Measurements–9 on Unexposed Surface

–6 on Bottom Chords

Page 10: Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test

UL - Northbrook Furnace

Page 11: Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test

UL - Northbrook Furnace with Test Specimen

Page 12: Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test

Loading of Test Assembly - Northbrook

Hydraulic Actuators

Concrete Block

Water-filled Containers

Page 13: Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test
Page 14: Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test
Page 15: Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test

Post Test Observations Test No. 3

Page 16: Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test

Post-Test Observations – Steel Truss Behavior

Page 17: Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test

Post Test Observations - Slab Deflections

Test 1 - before

Test 1 - after

Page 18: Fire Endurance Testing of Floor Truss Assemblies Prepared ...Fire Endurance Testing of Floor Truss Assemblies Prepared by: Joe Treadway ... Testing Summary. WTC Floor Assembly. Test

Fire Resistance Ratings

Times to Reach End-Point Criteria (min) Standard Fire Test Rating

Temperature onUnexposed Surface Steel Temperatures ASTM

E 119-61 ASTM E 119-00

Average(Ambient+250ºF)

Maximum(Ambient+325ºF)

Average(1100ºF)

Maxi-mum

(1300ºF)

Rating(hr)

Restr-ained

Rating(hr)

Unrestr-ained

Rating(hr)

1 35 ft, restrained,¾ in fireproofing --- 111 66 62 (3) 116(1) 1½ 1½ 1

2 35 ft, unrestrained,¾ in fireproofing --- --- 76 62 (3) 146(2) 2 --- 2

3 17 ft, restrained,¾ in fireproofing 180 157 86 76 (3) 210(2) 2 2 1

417 ft, restrained,

½ in fireproofing --- 58 66 58 (3) 120(1) ¾ ¾ ¾

Failure to

Support Load

TestTermin-

ated(min)

Test Description

___________________________________________________(1) Imminent collapse(2) Vertical displacement exceeded capability to measure accurately(3) Did not occur