Fike Agent Storage Containers

Embed Size (px)

Citation preview

  • 8/20/2019 Fike Agent Storage Containers

    1/38

    HFC-227EA AGENT STORAGE CONTAINERS

    DESCRIPTIONFike Series 70 Clean Agent Containers are used in fire extinguishing systems tostore the Clean Agent until a fire develops and the agent must be released. TheClean Agent is retained in the container by a valve assembly which contains afast-acting rupture disc. The disc will be ruptured, and the Clean Agent released,through the operation of an actuator by an electric signal that is automatically ormanually controlled. The valve is available in three sizes: 1" (25mm), 2 1/2"(65mm) and 3" (80mm). The 1" (25mm) valve is used on the 10 (4), 20 (8), 35(15), 60 (27), and 100 pound (44 L) containers; the 2 1/2" (65mm) valve is usedon the 125i (51 L) and 215i pound (90 L) containers; the 3" (80mm) valve is usedon the 215 (87), 375 (153), 650 (267) and 1000 pound (423 L) containers. After adischarge, the valve is field reconditioned by simply replacing three components.

    Fike Series 70 Clean Agent Containers have passed extensive testing by 

    Underwriters Laboratories and Factory Mutual and are used in installations where8 to 1045 pounds (3.5 to 474 kg) of HFC-227ea is required. To eliminate theneed for multiple containers, or using more Clean Agent than necessary, thesecontainers can be filled in 1 pound (0.5 kg) increments to their maximumcapacity.

    Each container for HFC-227ea Clean Agent Systems is super pressurized with dry nitrogen to 360 psig (25 bar), at 70° F (21° C), to provide a quick and effectivedischarge in 10 seconds or less.

    Fike Series 70 Clean Agent Containers are supplied with a pressure gauge thatpermits a quick, visual, inspection of container pressure. Optional items include aLiquid Level Indicator, and a Low Pressure Supervisory Switch. The Liquid Levelindicator provides the convenience of determining the container's agent weight

     without removing it from its installed location. The Low Pressure Supervisory Switch provides constant monitoring of the container's internal pressure and can be wired either normally opened or normally closed. In the event of a decrease incontainer internal pressure from 360 psig to 288 psig (24.8 bar to 18.8 bar), theSupervisory Switch normally opened/closed contacts will close/open. This willcause a supervisory trouble alarm at the system control panel.

    Fike Series 70 Clean Agent Containers are available for installation in the upright,inverted or horizontal positions, depending upon the user's particular needs and thetype and size container specified. The mounting location of the container is quiteflexible. It can be mounted at the exact point of discharge or at a remote locationby adding distribution piping from the container to the nozzle system. (Refer to theFike Design, Installation and Maintenance Manual - P/N 06-215).

     The operating temperature range is +32 to +130oF (0 to 54.4oC) in any 

    installation. If the Clean Agent reaches an internal temperature range of 160° to187° F (71.1°to 86.1°C), it will create a sufficient internal pressure to burst therupture disc and release the Clean Agent through the piping network.

    704 S. 10th Street · P.O. Box 610 · Blue Springs, Missouri 64013-0610 U.S.A. · (816) 229-3405 · (816) 229-4615 · www.fike.com

    APPROVALS

    • UL Listed, Ex4623

    • FM Approved 0Y4AB.AF (HFC-227ea)

    Series 70 Clean Agent Containers

    Form No. C.1.01.01-2

  • 8/20/2019 Fike Agent Storage Containers

    2/38

    "B"

    "A"

    Liquid Level Boss

    3" (80mm) Outlet1/2" (15mm)

    Electrical

    Connection

    "B"

    "A"

    Liquid Level Boss

    1" (25mm) Outlet

    1/2" (15mm)

    Electrical

    Connection

    "A"

    "B"

    Liquid Level Boss

    2-1/2" (65mm) Outlet1/2" (15mm)

    Electrical

    Connection

    DESCRIPTION (cont.)

    Reliability

    Fike Series 70 Clean Agent Containers are manufactured in strict accordance withDepartment of Transportation (DOT) regulations. The Fike Series 70 Clean Agent

    Containers have successfully passed testing by Factory Mutual and UnderwritersLaboratories, Inc. Before leaving the factory, each container must pass extensive leakagetesting, and pressure testing to 1000 psig (69 bar). The containers are constructed fromcarbon steel alloys and painted with a durable, baked enamel finish.

    InstallationFike Series 70 Clean Agent Containers are supplied with a mounting bracket that isdesigned to provide the most effective and versatile installation for that particularcontainer. The 10, 20 and 35 pound (4, 8 and 15 L) container brackets employ two U-bolts for securing the container to the bracket. The 60 pound (27 L) container is securedusing two quick connecting, over-center handle clamps. The 125i and 215i pound (51 and90 L) containers utilize an "L" shaped bracket for direct wall mounting or, with anoptional floor mounting kit, can be mounted on a floor in the "valve down" position. The100 pound (44 L) and 215 pound (87 L) through 1000 pound (423 L) containers are

    supplied with one or two U-shaped mounting brackets, depending upon container size,for mounting to a wall or other secure surface.

    Container Sizes and Dimensions: U.S. Standard and Metric

    Size-lb   10 20 35 60 100 125i 215i 215 375 650 100

    A(in)   7 7.25 7.25 10.75 10.75 20.00 24.00 20.00 20.00 24.00 24.00

    B(in)   14.12 21.50 32.50 28.00 38.75 20.25 23.75 28.87 42.50 48.75 70.00

    Size-L   4 8 15 27 44 51 90 87 153 267 423

    A(mm)   178 184 184 273 273 508 610 508 508 610 610

    B(mm)   359 546 826 711 984 515 605 733 1080 1237 1778

    U.S. SIZES & DIMENSIONS

    METRIC SIZES & DIMENSIONS

  • 8/20/2019 Fike Agent Storage Containers

    3/38

    AVAILABLE MODELS AND SPECIFICATIONS

    FIKE P/N SIZE (LB) VALVE (IN)EMPTY WT

    (LB)

    HFC-227ea

    AGENT FILL

    RANGE (LBS)

    VALVE

    POSITION

    DOT

    REGULATION

    70-108 10 1 15 8-10 horiz or upright 4BW500

    70-098 20 1 21 12-21 horiz or upright 4BW500

    70-089 35 1 32 22-38 horiz or upright 4BW500

    70-152 60 1 44 39-68 horiz or upright 4BW500

    70-153 100 1 61 63-108 upright 4BW500

    70-041 125i 2 ½ 180 73-126 inverted 4BA500

    70-077 215i 2 ½ 225 128-223 inverted 4BA500

    70-154 215 3 150 124-216 upright 4BW500

    70-155 375 3 218 217-378 upright 4BW500

    70-156 650 3 350 378-660 upright 4BW500

    70-157 1000 3 515 598-1045 upright 4BW500

    FIKE P/N SIZE (L)VALVE

    (MM)

    EMPTY WT

    (KG)

    HFC-227ea

    AGENT FILL

    RANGE (KG)

    VALVE

    POSITION

    DOT

    REGULATION

    70-108 4 25 7 4.0-4.5 horiz or upright 4BW50070-098 8 25 10 5.5-9.5 horiz or upright 4BW500

    70-089 15 25 15 10.0-17.0 horiz or upright 4BW500

    70-152 27 25 20 18.0-30.5 horiz or upright 4BW500

    70-153 44 25 28 28.5-48.5 upright 4BW500

    70-041 51 65 82 33.5-57.0 inverted 4BA500

    70-077 90 65 102 58.5-101.0 inverted 4BA500

    70-154 87 80 68 56.5-98.0 upright 4BW500

    70-155 153 80 99 98.5-171.5 upright 4BW500

    70-156 267 80 159 171.5-299.0 upright 4BW500

    70-157 423 80 234 271.5-474.0 upright 4BW500

    CLEAN AGENT STORAGE CONTAINER DATA - U.S. STANDARD

    CLEAN AGENT STORAGE CONTAINER DATA - METRIC

  • 8/20/2019 Fike Agent Storage Containers

    4/38

    Copyright © Fike Corporation All Rights Reserved.Form No. C.1.01.01-2 March, 2005 Specifications are subject to change without notice.

    ARCHITECT AND ENGINEERING SPECIFICATIONS

     The Clean Agent shall be stored in Fike Series 70 Clean Agent Storage Containers. The containers shall be capable of being filled, in one-pound (0.5kg) increments, to their listed maximum capacity. The Clean Agent container shall be activated by asignal from the control panel which is processed by the Agent Release Module. This module shall store the power requiredto operate the actuator. The valve shall contain a scored, non-fragmenting, rupture disc to provide an immediate, total

    discharge of all the agent. HFC-227ea Clean Agent is stored in the container as a liquid, having a natural vapor pressure of 66 psig at 77°F (5 barg at 25°C). To aid in discharge, the container shall be super-pressurized to 360 psig at 70°F (25 bar at21.1°C) with dry nitrogen. Agent discharge shall be completed in 10 seconds or less.

    Clean Agent Storage Containers shall be actuated by an electrical signal that is automatically or manually controlled. Normaloperating temperature shall be +32 to +130°F (0 to 54.4°C) in any installation.

    Clean Agent Storage Containers shall be equipped with a pressure gauge to display internal pressure. This gauge shall be anintegral part of the container and color coded for fast referencing of pressure readings. A Low Pressure Supervisory Switchshall be made available as an option. A decrease in internal container pressure from 360 psig to 288 psig (24.8 bar to 18.8bar) shall cause the normally opened/closed Supervisory Switch contacts to close/open, indicating a trouble or supervisory condition at the control panel.

    Clean Agent Storage Containers shall be fastened to a wall, or other secure surface, using a mounting bracket that isdesigned for the most effective and versatile installation of each container.

  • 8/20/2019 Fike Agent Storage Containers

    5/38

    HFC-227EA PRE-ENGINEERED NOZZLES

    DESCRIPTIONNozzle

     The function of the Fike Nozzle in a fire suppression system, is to distribute theClean Agent in a uniform, predetermined pattern and concentration. The nozzlesare designed to complete the discharge of Clean Agent in 10 seconds or less

     when installed within the design limitations of the Fike Design Manual, P/N 06-202 or 06-215.

    Fike Nozzles are available in five sizes. Each nozzle comes in two configurationsof 180 and 360 degree distribution patterns.

    704 S. 10th Street · P.O. Box 610 · Blue Springs, Missouri 64013-0610 U.S.A. · (816) 229-3405 · (816) 229-4615 · www.fike.com

    Fike Pre-Engineered Nozzles

    360O PRE-ENGINEERED NOZZLES

    PART NUMBER DESCRIPTION

    80-052-0625 3/8" (10mm)

    80-052-0781 1/2" (15mm)

    80-1114 1" (25mm)

    80-1115 1-1/2" (40mm)

    80-1118 2" (50mm)

    180O PRE-ENGINEERED NOZZLES

    PART NUMBER DESCRIPTION

    80-1113 1" (25mm)80-1115 1-1/2" (40mm)

    80-1117 2" (50mm)

    Form No. C.1.02.01-3

    ARCHITECT AND ENGINEERING SPECIFICATIONS

     The Nozzle used to distribute the Clean Agent shall be a Fike Series 80. The nozzle shall be available in 3/8" (10 mm),1/2" (15mm), 1" (25mm), 1 1/2" (40mm) and 2" (50mm) sizes. Each nozzle is available in two styles: 180 and 360 degreedistribution patterns. The nozzle used shall be provided with internal pipe threads that correspond to the nozzle size. Thenozzle used shall be Underwriters Laboratories listed and Factory Mutual approved. (See diagrams on next page for nozzlesize/area coverage). The Fike Nozzle is provided with pipe threads that correspond to the nozzle size. With thisarrangement, the Fike Nozzle can be installed directly at the Clean Agent container or remotely, at the end of a dischargepiping system.

    .

    APPROVALS

    • UL Listed - Ex 4623

    • ULC Listed - CEx624

    • FM Approved - 0Y4A8.AF

  • 8/20/2019 Fike Agent Storage Containers

    6/38

    Copyright © Fike Corporation All Rights Reserved.Form No. C.1.02.01-3 March, 2005 Specifications are subject to change without notice.

    Nozzle Size and Area Coverage

     NOTES: 

    a. An allowable area of coverage includes any area where the maximum coverage from the nozzle ("R" dimension) is not exceeded.

    b. Nozzles should be located on center line of hazard area.

    c. When working with ceiling heights exceeding the values tabulated above, the hazard volume must be broken down into vertically stacked hazard volumes, with heights less than the maximums shown in the table. It is imperative that unusual applications of this nature be handled by experienced  people in the field, and in most cases, operational tests should be performed before the system is put into service.

    d. Dimensions and nozzle data shown are taken from the UL listed and FM approved Design, Installation & Maintenance Manual - P/N 06- 202 or 06-215.

    e. 180 and 360 degree nozzles may be placed a maximum of 1 foot (30.5cm) down from the ceiling, and 180 degree nozzles may be placed a maximum of 1 foot (30.5cm) from the wall.

    Nozzle Area Coverage

    Nozzle TypeRadius “R”

    Dimension (English)

    Radius “R”

    Dimension (Metric)

    Ceiling Height

    Range (English)

    Ceiling Height

    Range (Metric)

    180o 45'-8" 13.92m 12 in. to 16 ft. 0.3 to 4.88m

    360o 29'-8" 9.04m 12 in. to 16 ft. 0.3 to 4.88m

    R

    R

    180° Nozzle 360° Nozzle

  • 8/20/2019 Fike Agent Storage Containers

    7/38

    HFC-227EA CONTAINER ACCESSORIES

    DESCRIPTION

    Reload Kit HFC-227ea

    85-023 - 1" (25mm) Valve and 85-024 - 2 1/2" (65mm) Valve

     The Series 85 Reload Kits are designed to facilitate field reconditioning of thecomplete line of Fike Clean Agent Containers. The 1" (25mm) Reload Kit willservice the 10, 20, 35, 60 and 100 lb. (4, 8, 15, 27, 44 liter) Fike Containers. The2 1/2" (65mm) kit will service the Fike 125i and 215i lb. (51 & 90 liter)Containers. Generally, each kit consists of a rupture disc, a gas cartridge actuatorand actuator housing, pressure gauge, replacement core for the fill valve, O-ring,and a teflon ring.

    Reload Kit HFC-227ea85-025 - 3" (80mm) Valve

     The 3" (80mm) Reload Kit provides field reconditioning of the 215, 375, 650,and 1000 lb. (87, 153, 267, 423 liter) Containers. Each kit consists of a 3" (80mm)rupture disc valve assembly, gas cartridge actuator, "O"-rings, pressure gauge andreplacement core for the fill valve.

    Low Pressure Switch

    70-1121 - All Containers Over 10 lb. (4 liters)

    70-1650 - 10 lb. Container Only

     These devices monitor the pressure within the Clean Agent Container. Should

    loss of Agent or Nitrogen occur, the Pressure Switch's normal contacts willtransfer indicating a low pressure condition.

    Specifications

    • Temperature Limits: 32° to 120° F (0-48.9°C)

    • Enclosure Classification: NEMA 4

    • Contact Rating: Single pole, double throw; 5 amps resistive, 3 ampsinductive @ 30VDC

    • Body Material: Aluminum with irridite finish

    • Weight: 6.5 ounces• Pressure Connection: 1/8” NPT (6mm)

    • Electrical Connection: 1/2” NPT (15mm)

    • Pressure Setting: 288 psig (20 bar)(decreasing)

    704 S. 10th Street · P.O. Box 610 · Blue Springs, Missouri 64013-0610 U.S.A. · (816) 229-3405 · (816) 229-4615 · www.fike.com

    APPROVALS

    • UL Listed - Ex4623

    • FM Approved - 0Y4A8.AF

    Reload Kit (1” and 2 1/2”)

    Reload Kit (3”)

    Pressure Switch

    Form No. C.1.03.01-2

  • 8/20/2019 Fike Agent Storage Containers

    8/38

    Copyright © Fike Corporation All Rights Reserved.Form # C.1.03.01-2 March, 2005 Specifications are subject to change without notice.

    Victaulic Nipple and Coupling 

    Check Valve

    02-2980 - 1" Check Valve (25 mm)

    02-4158 - 2" Check Valve (40 mm)

    02-4157 - 3" Check Valve (80 mm)

     The Fike Check Valve prevents agent loss from the open end of a manifold and/orpiping system in the event that one or more containers are removed for servicing and the system is discharged. This applies to all manifold configurations including Main/Reserve Systems.

    Constructed of carbon steel, the Check Valve has a working pressure of 720 psig (4965 kPa) and has 1", 2" or 3" (25, 50 or 80 mm) female NPT threads.

    Equivalent Length Values:

    1" (25 mm) - 2 ft./0.61 m

    2" (50 mm) - 4 ft./1.22 m

    3" (80 mm) - 4 ft./1.22 m

    DESCRIPTION (CONT.)

     Victaulic Nipple and Coupling

    02-1388 - 2 1/2” (65mm) Victaulic Nipple

    02-1376 - 2 1/2” (65mm) Victaulic Coupling 

    02-2106 - 3” (80mm) Victaulic Nipple

    02-1987 - 3” (80mm) Victaulic Coupling

     The purpose of the 2 1/2" (65 mm) and 3" (80 mm) victaulic nipple and coupling is to connect the 2" (55 mm) or 3" (80 mm) check valve(s) and/or system piping tothe 2 1/2" (65 mm) or 3" (80 mm) container valve. The coupling is rated at 1000psi (6895 kPa) working pressure and contains a Buna "N" gasket. The nipple is Sch.40 pipe, has 2 1/2" (65 mm) or 3" (80 mm) NPT male thread at one end and a 21/2" (65 mm) or 3" (80 mm) Victaulic groove on the opposite end.

    Check Valve

  • 8/20/2019 Fike Agent Storage Containers

    9/38

    AGENT RELEASE MODULE

    DESCRIPTION

     The Agent Release Module (ARM III), Fike P/N 10-1832, in conjunction with aFike Control Panel, allows the electrical actuators used with Fike Clean Agentcontainers to be wired in parallel. This configuration substantially increases theoverall reliability of the Clean Agent releasing circuit. With series-wired actuatorcircuits, a problem in a single actuator will incapacitate the entire system. Utilizing parallel-wired actuators, that same incident would incapacitate only that individualClean Agent container; all others would still be active.

     The Agent Release Module (ARM III) is compatible with either Class A or ClassB wiring. When an ARM III is used in a Class A wiring configuration, theresulting system is the most reliable available for today's Fire Protection.

    Installation

     The Fike Agent Release Module (ARM III) is mounted in the lower right corner of a 4 11/16" (11.9 cm) square box which connects to the actuator boss on the Clean Agent container. The ARM III is a solid-state circuit board and contains a terminalstrip for the connections of field wiring and actuator leads. The module is alsoequipped with a polarity diode that illuminates if the field wiring has been installed with reversed polarity. Special care should be taken to assure proper polarity.

    ARCHITECT AND ENGINEERING SPECIFICATIONS

    Each Clean Agent container shall be provided with a Fike P/N 10-1832 AgentRelease Module (ARM III) to allow all electrical actuators to be connected inparallel. Series-wired actuators are not acceptable. The ARM III shall be locatedat each container and shall be securely mounted in the lower right hand corner of a 4 11/16" (11.9cm) square electrical box, with cover. All wiring to the Clean Agent container and the actuator leads shall connect to a terminal strip located onthe ARM III.

    704 S. 10th Street · P.O. Box 610 · Blue Springs, Missouri 64013-0610 U.S.A. · (816) 229-3405 · (816) 229-4615 · www.fike.com

    APPROVALS

    • UL Listed - S3217

    • FM Approved

    • Cheetah: 0B4A6.AY

    • Rhino: 0Y4A4.AY 

    • SHP Pro: 0Z8A0.AY 

    Fike Agent Release Module

    Form No. C.1.04.01-2

      10-1832 ARM

    1.5K EOL

    + - R B Y G - +

      10-1832 ARM

    + - R B Y G - +TO CONTROL PANEL

    Maximum of 6 ARMs

    WIRING DIAGRAM

  • 8/20/2019 Fike Agent Storage Containers

    10/38

    Copyright © Fike Corporation All Rights Reserved.Form No. C.1.04.01-2 March, 2005 Specifications are subject to change without notice.

    This page intentionally left blank.

  • 8/20/2019 Fike Agent Storage Containers

    11/38

    HFC-227EA LIQUID LEVEL INDICATOR

    DESCRIPTION The Fike 70-1353 series Liquid Level Indicator is asimple manually operated device which provides ameans to determine the Clean Agent liquid level in

     vertically mounted agent storage containers. Once theliquid level is determined, it can then be convertedinto pounds (kilograms) of Clean Agent present in theagent storage container. (Refer to Fike HFC-227eaInstruction Manual for Liquid Level Indicator (LLi),P/N 06-107.)

    Operation

     A magnet equipped float moves with the liquid level along the unit stem. Levelreadout is obtained by simply removing the protective cap and pulling out a

    calibrated tape until magnetic interlock with the float is felt. With the tape in thisposition, the reading is obtained at the point where the tape emerges from theunit housing.

     When the liquid level is determined, the reading is then located on a chart and thecorresponding Clean Agent weight is read. Accurate readings can be obtainedover a +40 to +90oF (+4.4 to +32.2oC) temperature range.

    Features

    • Reduced maintenance time - the weight of the agent in storage containers canbe determined in a fraction of the time it would take to remove and weighthem.

    • Continuous fire protection - use of the liquid level indicator does not requireshutting down the Clean Agent System, thus affording uninterrupted fire

    protection.• Field installation capability - the indicator can easily be installed in the field

    using a single wrench, as long as the container is empty and is equipped with amounting boss.

    • Compact - when not in use, the unit requires no more space than that requiredby the container.

    • Flexibility - the flexible tape design allows the unit to be used in tight spacesthat would otherwise hinder the use of a rigid indicator "stick".

    • Availability - units are available for Fike container sizes of 100 lb. (44 liter)through 1000 lb. (423 liter) in both the modular and central storage typedesigns.

    Construction

     The Fike 70-1353 series Liquid Level Indicator housing and stem assembly isconstructed of brass. The flexible indicator tape is constructed of steel with ayellow mylar coating. The indicator tape is calibrated in inches and centimeters.

     The unit housing provides straight mounting threads with a static O-ring seal. The float is constructed of a special ECCO material for high pressure service. The cellular construction of the ECCO material allows the float to be solid and isnot susceptible to water-logging, as hollow floats are if they develop a leak. Theunit is provided with a plastic protective cap.

    704 S. 10th Street · P.O. Box 610 · Blue Springs, Missouri 64013-0610 U.S.A. · (816) 229-3405 · (816) 229-4615 · www.fike.com

    APPROVALS

    • UL Ex4623

    • FM 3002238

    • USCG 162.161/2/0

    Liquid Level Indicator 

    Form No. C.1.05.01-2

    MAGNETIC

    FLOAT

    LIQUID LEVEL

    UNIT STEM

    LLi BOSS

    READ HERE

    INDICATOR TAPE

  • 8/20/2019 Fike Agent Storage Containers

    12/38

    Copyright © Fike Corporation All Rights Reserved.Form No. C.1.05.01-2 March, 2005 Specifications are subject to change without notice.

    ARCHITECT AND ENGINEERING SPECIFICATIONS

     Agent storage containers of 100 lb. (44 liter) capacity or more shall be provided with a reliable means, other than weighing,of determining the agent weight within the storage container during normal routine service.

     The device used shall be a Fike 70-1353-xx series Liquid Level Indicator and shall not require any additional space when thecontainer is installed.

    Use of the indicator shall not require the Clean Agent System to be shut down, thus allowing uninterrupted fire protectionduring service intervals. Level indicators which are not factory installed shall be capable of being retrofitted in the field,

     with a single standard wrench, when the container is removed for recharge.

     The level indicator tape shall be flexible to allow use in confined spaces. The unit housing shall be constructed of brass with straight mounting threads and a static O-ring seal. The float shall be of solid construction to eliminate the possibility of water logging to which hollow floats are susceptible. The float shall be equipped with a magnet which provides for apositive feel when the magnetic interlock is reached between the float and indicating tape.

     When the level reading is obtained, the agent weight can be determined through the use of the chart or graph found in the

    Liquid Level Indicator Manual (P/N: 06-107). Accurate readings shall be capable of being obtained over a +40oF (+4.4oC)to 90oF (+32.2oC) temperature range.

    AVAILABLE MODELS

    INDICATOR P/N DIMENSION “L” CONTAINER SIZE CONTAINER P/N

    70-1353-22 22” (381 mm) 100 lb (44 liter) 70-153

    70-1353-11 11” (278 mm) 125i lb (51 liter) 70-041

    70-1353-15 15” (381 mm) 215 lb (87 liter) 70-154/S70-154

    70-1353-15 15” (381 mm) 215i lb (90 liter) 70-077

    70-1353-24 24” (610 mm) 375 lb (153 liter) 70-155 / S70-155

    70-1353-38 38” (965 mm) 650 lb “short” (267 liter “short”) 70-156 / S70-156

    70-1353-44 44” (1118 mm) 1000 lb (423 liter) 70-157 / S70-157

    "L"

    Float

    Inspection

    Tag

    Cap

    Measuring

    Tape

  • 8/20/2019 Fike Agent Storage Containers

    13/38

    INTERFACE FIRING MODULE

    DESCRIPTION

     The Interface Firing Module (IFM), Fike P/N 10-2136, is designed to allow an

    existing control panel (approved for releasing service) to connect with a Fike Clean Agent system. The IFM is designed to operate from any of three different inputsignals from a listed control panel:

    Dry Contact A dry contact closure from a releasing circuit of a UL listed control panel willcause the IFM to enter the release state after the contacts are closed for a minimumof 1.1 seconds. When using dry contact output, all interface wiring must be in thesame room, within 20' of the panel, and in EMT or conduit.

    Polarity Reversal A polarity reversal circuit input (full reversal required) from a releasing circuit of aUL listed releasing control panel will cause the IFM to enter the release state afterthe polarity signal is reversed for at least 1.1 seconds. The listed releasing controlpanel supervises this circuit by allowing current to flow in one direction during 

    normal operation and the reverse direction during the discharge state. When theIFM enters a trouble state, and immediately after power-up, the IFM opens thepolarity reversal circuit to signal a trouble condition at the control panel. Thepolarity reversal circuit can be wired for Class A or Class B operation. If wired forClass B operation, the EOL resistor must be installed across terminals 5 and 8.(Value determined by specific panel manufacturer.)

    Series Firing A series firing circuit from a compatible control panel which is UL listed forreleasing operation will cause the IFM to enter the release state after a sufficiently large current is passed through the circuit for at least 1.1 seconds. The panelsupervises the circuit by passing a lesser current level through the circuit. When theIFM enters a trouble state, and immediately after power-up, the IFM opens theseries firing circuit to signal a trouble condition on the control panel.

     The IFM is provided with an agent release circuit that is capable of connecting  with up to 20 Containers/Agent Release Modules (ARM III, Fike P/N 10-1832).It also supervises the integrity of the ARM circuit via Class B wiring by utilizing a1.5K ohm end-of-line device connected at the ARM.

    Upon activation of any one of the three types of inputs for a period of at least 1.1seconds, the IFM will energize the ARM III module(s), which in turn fires theactuator(s) to release the agent.

     The programmable output contact is a form A dry contact which can be set viaDIP switches for NO or NC operation. It also can be programmed for activationupon trouble or system alarm.

     The IFM is a power limited device which requires 24VDC input power from theexisting control panel.

     This module is designed to electrically isolate the input circuits from the output

    circuits to provide flexibility.

    INSTALLATION

     The IFM is housed in an enclosure (4" x 3" x 1.5") (10.2 x 7.6 x 3.8 cm). Thishousing can be mounted in the control panel or a separate enclosure. An optionalmetal enclosure (10" x 6" x 2.5") (25.4 x 15.2 x 6.4 cm) with cover is offered; P/N10-2137.

     All wiring shall be with conductors approved for use in this application. The IFMincludes a removable terminal strip that can accommodate wiring sizes from 18 to14 AWG.

    704 S. 10th Street · P.O. Box 610 · Blue Springs, Missouri 64013-0610 U.S.A. · (816) 229-3405 · (816) 229-4615 · www.fike.com

    APPROVALS

    • UL/cUL Listed - S5566

    Interface Firing Module

    Form No. C.1.06.01-2

  • 8/20/2019 Fike Agent Storage Containers

    14/38

    Copyright © Fike Corporation All Rights Reserved.Form No. C.1.06.01-2 March, 2005 Specifications are subject to change without notice.

    STANDARD FEATURES/SPECIFICATIONS

    • Interfaces with existing approved releasing control panels

    • Operates from any one of three differentinputs

    • Connects up to 20 Agent Release Modules(ARMs)

    • Supervises the ARM circuit

    • Has test mode

    • Provides programmable output contact

    • Operating Voltage: 21-27 VDC

    • Current:- Normal 45 mA Max.- Release 70 mA Max.- Trouble 150 mA Max.

    Inputs

    • Polarity Reversal Input

    - Maximum supervision voltage 30 VDC- Maximum release voltage 30 VDC- Minimum release voltage 12 VDC- Minimum release current required 5 mA

    • Series Firing Input- Maximum supervision current 3.0 mA- Minimum release current 8.0 mA- Maximum release voltage 25.5 VDC

    - Minimum release voltage 20.7 VDC- Typical input impedance 1.5K ohm

    • Dry Contact Input- Maximum Voltage across contact 30 VDC- Maximum Current through contact 50 mA

    Outputs

    • Dry Contact Output Rating - Maximum voltage 30 VDC- Maximum current 1.0 A

    • ARM Circuit rating - Maximum Agent Release Modules 20

    WIRING DIAGRAM

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    P/N 10-1832

    (ARM III)

    MODULE

    RELEASE

     AGENT

    GCA

    1.5K OHM

    2 WATT

    UP TO 20 AGENT RELEASEMODULES PER CIRCUIT

    EXTERNAL EOL

    +

    -

    +

    -

    DRY CONTACT INPUT

     AGENT RELEASE

    POLARITY REVERSALCIRCUIT

    SERIES FIRING CIRCUIT

    DRY CONTACTOUTPUT

    POWER INPUT

    MODULE

    UL Listed Control Panel Approved For Releasing Service

    CIRCUIT

    (POLARITY SHOWN IN

    DISCHARGE CONDITION)

    24VDC 0.2 AMP

    Use one of three outputs Contact Monitor Circuit

    (for release or trouble

    feedback)

    INTERFACE FIRING

    24 VDC Power 

    -

    +

    8

    7

    6

    5

    4

    3

    2

    1

    RED

    BLU

    YEL

    GRN

     AGENT

    RELEASE

    MODULE

    (ARM III)

    P/N 10-1832

    +

    -

    1

    2

    3

    4

    5

    6

    7

    8

    +

    -

    GRN

    YEL

    BLU

    RED

    GCA

    -

    +

    -

    +

  • 8/20/2019 Fike Agent Storage Containers

    15/38

    HFC-227EA

    APPLICATION/DESCRIPTION

    HFC-227ea provides superior fire protection in a wide range of applications fromsensitive electrical equipment to industrial applications using flammable liquids.HFC-227ea is ideal for applications where clean-up of other media presents aproblem, where weight versus suppression potential is a factor, where anelectrically non-conductive medium is needed and where people compatibility isan overriding factor. When environmental impact is a consideration, HFC-227eais particularly useful. It has zero ozone-depleting potential, low global warming potential and a short atmospheric lifetime. These characteristics make it suitablenot only for new installations using Fike’s total flooding systems, but also forHalon 1301 replacement applications.

    HFC-227ea is an odorless, colorless, liquefied compressed gas. (See PhysicalProperties Table for additional information). It is stored as a liquid and dispensed

    into the hazard as a colorless, electrically non-conductive vapor that is clear anddoes not obscure vision. It leaves no residue and has acceptable toxicity for use inoccupied spaces at design concentration. HFC-227ea extinguishes a fire by acombination of chemical and physical mechanisms. HFC-227ea does not displaceoxygen and therefore is safe for use in occupied spaces without fear of oxygendeprivation.

    Performance

    HFC-227ea is an effective fire extinguishing agent that can be used on many typesof fires. It is effective for many surface fires, such as flammable liquids, and mostsolid combustible materials.

    On a weight-of-agent basis, HFC-227ea is a very effective gaseous extinguishing agent. The HFC-227ea extinguishing concentration for normal Class Acombustibles is 6.25 - 7% by volume. The minimum design concentration fortotal flood applications should be in accordance with NFPA 2001.

    Specifications

    HFC-227ea is manufactured to these specifications:• Mole%: 99.0 Minimum• Acidity, ppm by weight: 3.0 Maximum• Water content, % by weight: 0.001 Maximum• Non-volatile residues, gram/100mL: 0.05 Maximum

     Toxicity

     The toxicology of HFC-227ea compares favorably with other suppression agents. The LC50 of HFC-227ea is greater than 800,000 ppm. HFC-227ea has beenevaluated for cardiac sensitization via test protocols approved by the United

    States Environmental Protection Agency. Test results show that cardiac toleranceto HFC-227ea is higher than that of other suppression agents and is acceptablefor safe use in occupied spaces. HFC-227ea will decompose to form halogenacids when exposed to open flames. The formation of these acids is minimizedby using Fike early warning detection systems and proper system installation. When properly applied and installed, the generation of these by-products of HFC-227ea should be minimal.

    704 S. 10th Street · P.O. Box 610 · Blue Springs, Missouri 64013-0610 U.S.A. · (816) 229-3405 · (816) 229-4615 · www.fike.com

    APPROVALS

    HFC-227ea complies with NFPAStandard 2001 - current edition. FikeHFC-227ea systems are UL listedand FM approved for Clean AgentFire Suppression Systems.

    • UL Listed Ex 4623

    • FM Approved 0Y4A8.AF

    • USCG 162.161/2/0

    Form No. C.1.07.01-2

  • 8/20/2019 Fike Agent Storage Containers

    16/38

    Copyright © Fike Corporation All Rights Reserved.Form No. C.1.07.01-2 March, 2005 Specifications are subject to change without notice.

    PHYSICAL PROPERTIES

    • Chemical Name: Heptafluoropropane (CF3CHFCF3 )

    • Molecular Weight: 170.03

    • Boiling Point @ 760 mm Hg: 2.55oF (-16.4oC)

    • Freezing Point : -204oF (-131.1oC)

    • Critical Temperature: 215oF (101.7oC)

    • Critical Pressure (psia): 422 psia (2912 kPa)

    • Critical Volume (ft3/lbm) (cc/mole): 0.0258 (274)

    • Critical Density (lbm/ft3): 38.8 (621 kg/m3 )

    • Specific Heat, Liquid (BTU/lb-Fo ) @ 77oF (25oC): 0.283 (1.184 kj/kg/oC)

    • Specific Heat, Vapor (BTU/lb-oF) @ constant pressure of 1 ATM @ 77oF (25oC):0.1932 (0.808 kj/kg/oC)

    • Heat of Vaporization (BTU/lb) at Boiling Point: 57.0 (132.6 kj/kg)

    • Thermal Conductivity (BTU/h ftoF) of Liquid @ 77oF (25oC): 0.040 (0.069 w/moC)

    • Viscosity, Liquid (lb/ft hr) @ 77oF (25oC): 0.443 (0.184 centipoise)

    • Vapor Pressure (psia) @ 77

    o

    F (25

    o

    C): 66.4 (457.7 kPa)• Ozone Depletion Potential: 0

    • Estimated Atmospheric Lifetime (years): 31-42

    • LC50 (Rats; 4hrs - ppm): >800,000

  • 8/20/2019 Fike Agent Storage Containers

    17/38

    HFC-227EA ENGINEERED NOZZLES

    DESCRIPTION The function of the Fike Engineered Discharge Nozzle in a fire extinguishing system is to distribute the Clean Agent in a uniform, predetermined pattern andconcentration. The nozzles are designed to complete the discharge of Clean

     Agent in 10 seconds or less when installed within the design limitations of theFike Design, Installation and Maintenance Manual, P/N 06-202 or 06-215 and theFike Flow Calculation computer program.

    Fike Engineered Discharge Nozzles are available in sizes of 3/8" (10mm)through 2" (50mm). Each nozzle is available in 180 and 360 degree dischargepatterns.

     The Discharge Nozzle size refers to the size of Schedule 40 or 80 steel pipe to which it can be connected. The nozzle discharge orifices are drilled perpendicular

    to the center line of the threads. The nozzles are mounted to allow the agent tobe discharged on a horizontal axis.

    Nozzle orifices are available in a wide range of sizes to provide accurate Clean Agent flow results. All nozzles have been tested for their ability to discharge theClean Agent under extreme conditions.

    Nozzle orifice drilling must be done at the Fike factory, or other UL listed nozzledrill station, only after "As-Built" calculations of the installed piping system(s)have been performed, using the Fike Flow Calculation computer program.

     The Fike Discharge Nozzle used shall be Factory Mutual (FM) approved andUnderwriters Laboratories (UL) listed.

    704 S. 10th Street · P.O. Box 610 · Blue Springs, Missouri 64013-0610 U.S.A. · (816) 229-3405 · (816) 229-0314 · www.fike.com

    Fike Engineered Nozzles

    APPROVALS

    • UL Listed - Ex4623

    • ULC Listed - CEx1136

    • FM Approved - 0Y4A8.AF

    Form No. C.1.08.01-2

    ARCHITECT AND ENGINEERING SPECIFICATIONS

     The nozzle used to disperse Clean Agent shall be a Fike Series 80. The nozzle shall be available in 3/8" (10mm) thru 2"(50mm) sizes. Each size shall be available in both 180 and 360 degree dispersion patterns. The nozzle used shall have pipethreads that correspond to the nozzle size. All nozzles shall have an orifice size determined by a UL listed and FMapproved flow calculation program. All nozzle orifice drilling shall be performed by the manufacturer or a UL listed nozzledrilling facility.

  • 8/20/2019 Fike Agent Storage Containers

    18/38

    Copyright © Fike Corporation All Rights Reserved.Form No. C.1.08.01-2 March, 2004 Specifications are subject to change without notice.

    Nozzle Size and Area Coverage

     NOTES: 

    a. The maximum allowable area of coverage includes any area within the radius distance from the nozzle ("R" dimension) to the most extreme wall or corner.

    b. Nozzles should be located on center line of hazard area.

    c. When working with ceiling heights exceeding the values tabulated above, the hazard volume must be broken down into vertically stacked hazard volumes, with heights less than the maximums shown in the table.

    It is imperative that unusual applications of this nature be handled by experienced design engineers and, in most cases, operational tests should be 

     performed before the system is put into service.d. Dimensions and nozzle data shown are taken from the UL listed and FM approved Design, Installation & Maintenance Manual -

    P/N 06-202 or 06-215.

    e. 180 and 360 degree nozzles may be placed a maximum of 1 foot (30.5cm) down from the ceiling, and 180 degree nozzles may be placed a maximum of 1 foot (30.5cm) from the wall.

     f. Nozzle threading is NPT.

    NOZZLE SIZE 180O NOZZLE 360O NOZZLE

    (NPT) (mm) PART NUMBER PART NUMBER

    3/8" (10) 80-060 80-052

    1/2" (15) 80-061 80-053

    3/4" (20) 80-062 80-054

    1" (25) 80-063 80-0551 1/4" (32) 80-064 80-056

    1 1/2" (40) 80-065 80-057

    2" (50) 80-066 80-058

    180° Nozzle 360° Nozzle

    R

    R

    Nozzle Area Coverage

    Nozzle Type“R”

    Dimension

    Ceiling Height

    Range

    180 Degree 45’ - 8” (13.92)1.0 to 16.0

    (0.3 to 4.9)

    360 Degree 29’ - 8” (9.04)1.0 to 16.0

    (0.3 to 4.9)

  • 8/20/2019 Fike Agent Storage Containers

    19/38

    HFC-227EA INSTRUCTIONAL SIGNS

    APPLICATIONInstructional signs must be supplied in order to provide a system in which thefunction of all devices is easy to understand. Fike offers several different standardsigns that comply with NFPA and other industry requirements. All signs aredurable plastic and backed with a strong adhesive for easy installation. Signs aretypically installed at all entrances (CAUTION - Room Protected By HFC-227ea)and near any device for which the extra explanation is helpful. Custom signs areavailable upon special request.

    System “Release” Sign/Manual Release Station 02-10137

     The purpose of the System "Release" Sign is to identify the manual release stationas the place where the HFC-227ea System can be manually discharged. It alsominimizes the possibility of the manual station being mistaken for a fire alarmdevice. The sign is 4" x 2.25" x 1/16" (102 x 57 x 1.6mm) and is constructed of 

    red plastic with white lettering. The System "Release" Sign should normally belocated under each HFC-227ea manual release station for quick positiveidentification.

    Upon Device Activation "Do Not Enter” Sign 02-10138

     The purpose of the System Discharge Sign is to explain the presence of an alarmin the event of a HFC-227ea System discharge. The sign is 9" x 6" x 1/16" (229 x152 x 1.6mm) and is constructed of white plastic with black lettering. The SystemDischarge Sign is located next to or under an audible or visual alarm outside of the protected space entrance(s). This sign, together with the alarm device(s) willalert personnel when HFC-227ea agent has discharged and allow them to takeappropriate actions.

    Caution “Do Not Enter” Sign 02-10139

     The purpose of the Caution Sign is to alert personnel that the room is protectedby an HFC-227ea System and that all doors should be kept closed in the event of fire. The sign is 10" x 13" x 1/16" (254 x 330 x 1.6mm) and constructed of yellow plastic with black lettering. The Caution Sign should normally be locatedon the entrance door(s) leading into any room where HFC-227ea protection isbeing provided.

    Upon Device Activation "Exit" Sign 02-10105

     The purpose of the System Discharge Sign is to explain the presence of an alarmin the event of an HFC-227ea System discharge. The sign is 9" x 6'' x 1/16" (229x 152 x 1.6mm) and is constructed of white plastic with black lettering. TheSystem Discharge Sign is located next to or under an audible or visual alarminside of the protected space. This sign, together with the alarm device, will alertpersonnel when HFC-227ea agent has been discharged and allow them to take

    appropriate action.System Abort "Push and Hold" Sign 02-10106

     The purpose of this System Abort Sign is to identify the presence of the HFC-227ea System Abort Station. The sign is 4" x 2.25" x 1/16" (102 x 57 x 1.6mm)and is constructed of red plastic with white lettering. The System Abort Station isdesigned to provide a manual means by which the HFC-227ea system actuationcircuit may be interrupted. The System Abort Sign should be located next to eachHFC-227ea Abort Station for quick positive identification.

    704 S. 10th Street · P.O. Box 610 · Blue Springs, Missouri 64013-0610 U.S.A. · (816) 229-3405 · (816) 229-4615 · www.fike.com

    Form No. C.1.10.01-3

    HFC-227ea

    EXTINGUISHING

    SYSTEM RELEASE

    HFC-227ea EXTINGUISHING

    SYSTEM DISCHARGE ALARM

    IF ACTIVE

    DO NOT ENTER AREA

    THIS AREA IS PROTECTED BYA

    HFC-227ea EXTINGUISHING SYSTEM

    DO NOT ENTER AREA DURINGOR AFTER DISCHARGE

    KEEP DOOR CLOSED AT ALL TIMES

    HFC-227ea EXTINGUISHING

    SYSTEM ALARM

    IF ACTIVE

    EXIT AREA IMMEDIATELY

    HFC-227ea

    EXTINGUISHING

    SYSTEM ABORT

    PUSH AND HOLD

  • 8/20/2019 Fike Agent Storage Containers

    20/38

    Copyright © Fike Corporation All Rights Reserved.Form No. C.1.10.01-3 March, 2005 Specifications are subject to change without notice.

    APPLICATION (Cont.)

    System "Main/Reserve" Sign 02-10107

     The purpose of Main/Reserve Sign is to identify the presence of the HFC-227ea

    Main/Reserve Switch Station. The sign is 4” x 2.25” x 1/16" (102 x 57 x 1.6mm)and is constructed of red plastic with white lettering. The Main/Reserve Signshould be located under the Main/Reserve Switch for positive identification. AMain/Reserve Switch is used with systems that incorporate main and reserve (back up) HFC-227ea Agent storage.

    Release Pending Sign 02-10268

     The purpose of the Release Pending Sign is to explain the presence of an alarm inthe event of an impending HFC-227ea System discharge. The sign is 7” x 4.25” x1/16" (178 x 108 x 1.6mm) and is constructed of red plastic with white lettering.

     The Release Pending Sign is located next to an audible or visual alarm inside of theprotected space. This sign, together with the alarm device, will alert personnel of aforthcoming HFC-227ea Agent discharge and allow them to take appropriate action.

    HFC-227ea

    EXTINGUISHINGSYSTEM

    MAIN / RESERVE

    HFC-227ea

    RELEASE

    PENDING WHENDEVICE IS ACTIVE

    EXIT AREA

  • 8/20/2019 Fike Agent Storage Containers

    21/38

    GAS CARTRIDGE ACTUATOR

    DESCRIPTION

     The Gas Cartridge Actuator (GCA), Fike P/N 70-1651, provides the necessary pressure to fully open all Fike's Clean Agent containers utilizing a Fike fast acting rupture disc assembly. The GCA consists of a stainless steel body containing twosets of bridge wires and a charge of smokeless powder. Operation of the GCAoccurs when an electric current is sent through the bridge wires causing thesmokeless powder to ignite. This generates the necessary pressure to open therupture disc and discharge the agent in the Clean Agent container.

     The GCA is not an explosive device and cannot be used as a detonator.Operating time for the GCA is 10 milliseconds. Operating temperature range forthe GCA is +32o to +130oF. (0o to +54.4oC) for HFC-227ea systems. ForECARO-25 systems, the maximum operating temperature is 120oF (49oC).

     The GCA is designed to operate in all Fike Clean Agent system containers with1" and 2 1/2" valves and also containers with 3" valves with single disc packs. This device is designed to operate by two methods of actuation:

    1. Electrical input from a Fike Control Unit or Interface Firing Module (IFM)and through an Agent Release Module (ARM).

    2. Input from an (optional) independent Fike Manual Actuator.

    Installation

     The GCA has two sets of threads; the 3/8-24 UNF-20 thread is used to installthe GCA in either 1 or 2 1/2" (25 or 65mm) valved containers and the 7/16-20UNF-24 thread is used to install the GCA in the 3" (80mm) valved containers, without modification to the valve assemblies.

    It should be noted that for retrofit systems, the junction box for the ARM/GCA

    may need to be longer and/or larger than was required for the ARM/detonatordevice.

    Shelf Life

     The GCA is a sealed device utilizing a glass seal and epoxy plug on the wire endand a mylar seal on the discharge end. This extends the actuator's continuousservice and shelf life to 10 years before it requires replacement.

    Shipping Classification

     The GCA will not detonate any explosive materials or products. It has a U.S.Department of Transportation classification of:

    - Class: 1.4- Compatibility Group: "S"- Shipping Number: UN0323

     This classification allows this device to be shipped on any type of carrier(excluding ocean containers) such as commercial airlines, as well as all forms of land carriers without special handling permits and/or licensing.

    704 S. 10th Street · P.O. Box 610 · Blue Springs, Missouri 64013-0610 U.S.A. · (816) 229-3405 · (816) 229-4615 · www.fike.com

    Gas Cartridge Actuator 

    APPROVALS

    • UL Listed - Ex 4623• FM Approved:

    • HFC-227EA: 0Y4A8.AF

    • ECARO-25 TM: 3014476

    Form No. C.1.26.01-2

  • 8/20/2019 Fike Agent Storage Containers

    22/38

    Copyright © Fike Corporation All Rights Reserved.Form No. C.1.26.01-2 March, 2005 Specifications are subject to change without notice.

    GAS CARTRIDGE ACTUATOR DETAILS

    .75" Hex

    40" (1016mm) Ref. 3.5" (89mm)

    Epoxy Plug3/8-24 UNF-2A Thread

    for 1" (25mm) &

    2-1/2" (65mm) ValvesSST Body

    7/16-20 UNF-2A Thread

    for 3" (80mm) Valves

    #22 AWG Solid Copper 

    PVC Insulated Wires

     ARM Wires (Red/Blue)

    Manual Actuator Wires

    (Yellow/Green)

    YEL

    GRN

    REDBLUE

    Fike

    Control

    Panel

     ARM

    GCA

    Manual Actuator 

    GAS CARTRIDGE ACTUATOR DETAILS

  • 8/20/2019 Fike Agent Storage Containers

    23/38

  • 8/20/2019 Fike Agent Storage Containers

    24/38

  • 8/20/2019 Fike Agent Storage Containers

    25/38

  • 8/20/2019 Fike Agent Storage Containers

    26/38

    The MSDS format adheres to U.S. standards and regulatory

    requirements and may not meet regulatory requirements in

    other countries.

    This information is based upon technical information

    believed to be reliable. It is subject to revision as

    additional knowledge and experience are gained.

    FE-227

      6160FR Revised 22-SEP-2000 Printed 30-MAR-2001

    CHEMICAL PRODUCT/COMPANY IDENTIFICATION

      Material Identification

      FE-227 is a registered trademark of DuPont.

      CAS Number : 431-89-0

      Formula : CF3 CHF CF3

      Molecular Weight : 170.04

      CAS Name : Propane, 1,1,1,2,3,3,3-Heptafluoro-

      Tradenames and Synonyms

      HFA 227ea

      FC-227ea

      Dymel 227 ea/p

      2-Hydroperfluoropropane

      Propane, 1,1,1,2,3,3,3-Heptafluoro-

      HFC-227ea

      2-Hydroheptafluoropropane

      FM-200(tm) Great Lakes Chemical Corp.

      Heptafluoropropane

      Company Identification

      MANUFACTURER/DISTRIBUTOR

      DuPont

      Fluoroproducts

      1007 Market Street

      Wilmington, DE 19898

  • 8/20/2019 Fike Agent Storage Containers

    27/38

      PHONE NUMBERS

      Product Information : 1-800-441-7515

      Transport Emergency : CHEMTREC 1-800-424-9300

      Medical Emergency : 1-800-441-3637

    COMPOSITION/INFORMATION ON INGREDIENTS

      Components

      Material CAS Number %

      1,1,1,2,3,3,3-Heptafluoropropane 431-89-0 99+

    HAZARDS IDENTIFICATION

      Potential Health Effects

      Symptoms similar to oxygen deprivation (headache, nausea,

      dizziness or loss of consciousness) may result from

      overexposure by inhalation. Gross overexposure by

      inhalation may cause irregular pulse, heart palpitations

      and potentially fatal cardiac sensitization. Cold, white or

      discolored skin or in severe cases blistering, can be a sign

      of frostbite caused by cold liquids or gases.

      Eyes: Direct eye contact with the liquid or cold gas can

      cause chilling or possibly frostbite of exposed tissues.

      Skin: Direct skin contact with the liquid or cold gas can  cause chilling or possibly frostbite of exposed tissues.

      Ingestion: Not expected to be a hazard in normal industrial

      use.

      Inhalation: Inhalation of high concentrations can be

      harmful or fatal due to oxygen deprivation and/or heart

      irregularities (arrhythmias). Misuse of product by

      deliberately inhaling high concentrations of this gas could

      cause death without warning.

      Medical Conditions Aggravated by Exposure: Persons with

      pre-existing cardiac, respiratory or central nervous system

      disorders may be more susceptible to effects of an

      overexposure.

      Notice to Physicians: Overexposure to this material may

      make the heart more susceptible to arrhythmias.

      Catecholamines such as adrenaline and other compounds having

      similar effects should be reserved for emergencies and then

      used only with special caution.

  • 8/20/2019 Fike Agent Storage Containers

    28/38

      Vapors are heavier than air and pose a hazard of suffocation

      if trapped in enclosed or low places.

      Carcinogenicity Information

      None of the components present in this material at concentrations

      equal to or greater than 0.1% are listed by IARC, NTP, OSHA or ACGIH

      as a carcinogen.

    FIRST AID MEASURES

      First Aid

      INHALATION

      If inhaled, immediately remove to fresh air. If not breathing,

      give artificial respiration. If breathing is difficult, give  oxygen. Call a physician.

      SKIN CONTACT

      Treat for frostbite if necessary by gently warming affected area.

      EYE CONTACT

      In case of contact, immediately flush eyes with plenty of water

      for at least 15 minutes. Call a physician.

      INGESTION

      Ingestion is not considered a potential route of exposure.

    FIRE FIGHTING MEASURES

      Flammable Properties

      1,1,1,2,3,3,3-Heptafluoropropane is not flammable, however

      in the presence of a flame or ignition source it may

      decompose to form toxic hydrogen fluoride or carbonyl

      fluoride.

      Non-flammable.

      Extinguishing Media

      Use media appropriate for surrounding material.

      Fire Fighting Instructions

  • 8/20/2019 Fike Agent Storage Containers

    29/38

      Self-contained breathing apparatus (SCBA) may be required if

      cylinders rupture or release under fire conditions.

      Keep cylinders cool with water spray applied from a safe

      distance.

     ACCIDENTAL RELEASE MEASURES

      Safeguards (Personnel)

      NOTE: Review FIRE FIGHTING MEASURES and HANDLING (PERSONNEL)

      sections before proceeding with clean-up. Use appropriate

      PERSONAL PROTECTIVE EQUIPMENT during clean-up.

      Evacuate personnel, thoroughly ventilate area, use self-contained

      breathing apparatus. Keep upwind of leak - evacuate until gas has

      dispersed.

      Initial Containment

      Use forced ventilation to disperse vapors.

    HANDLING AND STORAGE

      Handling (Personnel)

      Do not breathe gas. Avoid contact with eyes, skin, or clothing.

      Wash thoroughly after handling. Wash clothing after use.

      Storage

      Store in a well ventilated place. Store in a cool, dry place.

      Keep container tightly closed.

    EXPOSURE CONTROLS/PERSONAL PROTECTION

      Engineering Controls

      Use only with adequate ventilation. Keep container tightly closed.

      Personal Protective Equipment

      EYE/FACE PROTECTION

      Wear safety glasses or coverall chemical splash goggles.

      RESPIRATORS

  • 8/20/2019 Fike Agent Storage Containers

    30/38

      Wear NIOSH approved respiratory protection, as appropriate.

      PROTECTIVE CLOTHING

      Where there is potential for skin contact have available and wear

      as appropriate impervious gloves, apron, pants, and jacket.

      Exposure Guidelines

      Exposure Limits

      FE-227

      AEL * (DuPont) : 1000 ppm, 8 & 12 Hr. TWA

      * AEL is DuPont's Acceptable Exposure Limit. Where governmentally

      imposed occupational exposure limits which are lower than the AEL

      are in effect, such limits shall take precedence.

    PHYSICAL AND CHEMICAL PROPERTIES

      Physical Data

      Boiling Point : -15.6 C (3.9 F)

      Melting Point : -133 C (-207 F)

      Vapor Pressure : 66.69 psia @ 25 C (77 F) (460.06 kPa)

      Liquid Density : 1.386 g/cm3 @ 25 C (77 F) (86.53 lb/ft3)

      Critical temperature : 101.6 C (214.9 F)

      Critical pressure : 424.7 psia (2930 kPa)

      Odor : Slight Ethereal

      Form : Liquified Gas

    STABILITY AND REACTIVITY

      Chemical Stability

      Stable at normal temperatures and storage conditions.

      Avoid sources of heat or open flame.

      Incompatibility with Other Materials

      Incompatible with strong reducing agents such as alkali

      metals (e.g., sodium, potassium), alkali-earth metals (e.g.,

      magnesium, calcium), and powdered aluminum or zinc.

      Decomposition

      Decomposes by reaction with high temperature (open flames,

      glowing metal surfaces, etc.) forming hydrofluoric acid,

      carbonyl fluorides, carbon monoxide and carbon dioxide.

  • 8/20/2019 Fike Agent Storage Containers

    31/38

      Polymerization

      Polymerization will not occur.

    TOXICOLOGICAL INFORMATION

      Animal Data

      Groups of six rats were exposed for four hours to 25,000 or

      53,000 ppm of FC-227ea. No deaths occurred. Signs of

      toxicity during exposure included irregular breathing,

      slight lacrimation and red ears. No toxic signs were seen

      post exposure.

      Animal studies have found the rat four hour LC50 to be

      >788,696 ppm (80%), the highest level tested. A cardiac

      sensitization study in dogs found the No Observable Adverse

      Effect Level (NOAEL) to be 9.0%. The Lowest Observable  Adverse Effect Level (LOAEL) for this study was reported to

      be 10.5%. A 90 day inhalation study did not find any

      exposure related effects at 105,000 ppm (10.5% vol./vol.),

      the highest level tested.

      Tests have shown that this material does not cause genetic

      damage in bacterial and mammalian cell cultures. When

      evaluated by an in-vivo mouse micronucleus assay, no

      increase in micronuclei was observed.

    DISPOSAL CONSIDERATIONS

      Waste Disposal

      Treatment, storage, transportation, and disposal must be in

      accordance with applicable Federal, State/Provincial, and Local

      regulations. Incinerate material in accordance with Federal,

      State/Provincial and Local requirements.

    TRANSPORTATION INFORMATION

      Shipping Information

      DOT

      Proper Shipping Name : Heptafluoropropane

      Hazard Class : 2.2

      I.D. No. (UN/NA) : UN 3296

      DOT Label(s) : Nonflammable Gas

  • 8/20/2019 Fike Agent Storage Containers

    32/38

    REGULATORY INFORMATION

      U.S. Federal Regulations

      TSCA Inventory Status : Listed.

      TITLE III HAZARD CLASSIFICATIONS SECTIONS 311, 312

      Acute : Yes

      Chronic : No

      Fire : No

      Reactivity : No

      Pressure : No

    OTHER INFORMATION

      NFPA, NPCA-HMIS

      NFPA Rating

      Health : 1

      Flammability : 0

      Reactivity : 1

      NPCA-HMIS Rating

      Health : 1

      Flammability : 0

      Reactivity : 0

      Personal Protection rating to be supplied by user depending on use

      conditions.

      Additional Information

      Some of the health and toxicity information was provided

      from a Great Lakes Chemical Corporation MSDS.

      ----------------------------------------------------------------------

      The data in this Material Safety Data Sheet relates only to the

      specific material designated herein and does not relate to use in

      combination with any other material or in any process.

      Responsibility for MSDS : MSDS Coordinator

      > : DuPont Fluoroproducts  Address : Wilmington, DE 19898

      Telephone : (800) 441-7515

      End of MSDS

  • 8/20/2019 Fike Agent Storage Containers

    33/38

    T HE MO ST TR US TED

    F I RE S UP PR ES SI O N S YS

    ON THE MARKET

    C L E A N A G E N T F I R E S U P P R E S S I O NC L E A N A G E N T F I R E S U P P R E S S I O N

    CLEAN AGENT

    FIRE SUPPRESSION

    WITH

  • 8/20/2019 Fike Agent Storage Containers

    34/38

    C LE AN A GE NT F IR E P RO TE CT IO N I S

    BEST F OR EL ECTR ON IC S AN D HI GH

    VAL UE ASSETS

    Water-based fire suppression systems (i.e. sprinklers), are designed to

    protect people and structures. But, when it comes to protecting high

    value machinery, computers and other electronic equipment, water ca

    be more damaging than the fire itself!

    Gaseous chemical suppression systems (clean agent systems) have been

    used for more than 40 years to protect electronics and other valuables tha

    are susceptible to the damaging effects of water-based suppression

    systems. Fike’s Clean Agent Systems are superior to water and dry chemic

    in virtually every way:

    Imagine your company’s valuable data, equipment and systems lost to f

    It happens every day somewhere in the world. And it’s devastating. Eveone day lost to fire-related downtime can mean lost revenues, custome

    and profits.

    You can’t afford equipment being inoperable ... service interruptions to

    customers ... or being unable to produce valuable data, documents and

    resources. You must protect your employees, your business and most

    importantly, your customers.

    CONSIDER THE FIKE CLEAN AGENT FIRE SUPPRESSION SYSTE

    IT’S TIME TO THINK

    THE UNTHINKABLE.

    WATER AND ELECTRONICS –

    A BAD COMBINATION

    • Clean agents are not electrically conductive, and donot damage electronics — water is a conductor and

    ruins electronics!

    • Clean agents are safe for people.

    • Clean agents leave no residue and require no clean-up.

    • Because they act quickly, clean agents greatly reduce the

    amount of smoke and soot damage caused by a fire.

    • Clean agents provide three-dimensional suppression,

    extinguishing fires that water may not reach.

    FM-200

    Save lives

    Protect high-value equipment,

    assets and irreplaceables

    from damage

    Minimize business interruption

    due to fire

    Minimize downtime after fire

    Prevent residue and clean-up

    after fire

    Minimize floor space requirements

    The superior design features and

    exceptional performance of Fike’s

    Clean Agent Fire SuppressionSystem using DuPont™ FM-200®

    help you:

    C L E A N A G E N T F I R E S U P P R E S S I O N

  • 8/20/2019 Fike Agent Storage Containers

    35/38

    WHY FM-200?

    Fike’s Clean Agent System extinguishes a fire quickly by

    discharging in 10 seconds – or less! The system removes

    heat and breaks up the fire at the molecular level. FM-200

    discharges as gas, leaves no residue and doesn’t require costly

    clean-up, unlike sprinklers and other systems.

    And with Fike’s patented valve system, we offer greater

    coverage – faster and more effectively — than any other

    option. This means minimal damages and interruptions

    for your business.

    FM-200 is a widely accepted replacement for Halon 1301.

    FM-200 is people-friendly... won’t obscure vision in a

    fire... and Fike’S Clean Agent System using FM-200  takes

    up less floor space than other systems. In addition, the U.S.Environmental Protection Agency named it a non-ozone

    depleting agent for fire extinguishing systems installed in

    occupied spaces.

    HE MOST TRUSTED FIRE SUPPRESSION SYSTEM ON THE MARKETHE MOST TRUSTED FIRE SUPPRESSION SYSTEM ON THE MARKET

    For speed in suppressing fires, reducing

    damages, saving on floor space and allowing visibility, Fike is the clear choice.

    FIKE’S CLEAN AGENT SYSTEM WITH

    FM-200 PROVIDES OPTIMUM FIRE

    DAMAGE PROTECTION FOR CRITICAL

    ASSETS IN NUMEROUS APPLICATION

    • Telecommunications facilities

    • Control rooms

    • Computer rooms

    • Data processing equipment

    • Marine shipboard systems

    • Record and archive storage

    • Museums

    • Universities

    • Pharmaceutical and medical fac

    • Industrial applications

    PROTECTS YOUR PEOPLE, ASSETS AND BUSINESS

    C L E A N A G E N T F I R E S U P P R E S S I O N

  • 8/20/2019 Fike Agent Storage Containers

    36/38

    WHY FIKE?

    W W W . F I K E . C O M

    FIKE – THE FIRST CHOICE FOR KEY ASSET PROTECTION SINCE 1945

    We manufacture the finest 

    products possible, your orders are filled quickly and you enjoy 

    24-hour technical support.

    Our on-site manufacturing

    and testing provides the

    highest quality protection.

    THE FIKE DIFFERENCE

    Fike is the industry standard for performance...

    unsurpassed for detection technology... and our 

    rupture valve unleashes protection the fastest.

    We have more Clean Agent

    experience than any other

    company. Fike authorized

    distributors are trained expertsin Clean Agent Suppression 

    Systems and can handle all your 

    needs quickly and efficiently.

    You can’t afford a major – or even

    minor – interruption due to fire. In

    fire situations, every second counts.

    In fact, downtime often outweighs

    the loss of equipment and structures.For this reason, companies large and

    small count on Fike.

    We manufacture most of what we

    sell. As a result, you’ll benefit from

    Fike’s higher quality control with

    both equipment and personnel ...

    a greater capacity to meet your

    demands quickly ... and shorter

    lead times between your order

    and the system’s installation.

    Innovation is another key. At Fike,

    we built our name on research,

    development and testing of systems.

    “Good enough” is never good

    enough. We were the first company

    to offer an independent laboratory

    approvedFM-200 system.

    C L E A N A G E N T F I R E S U P P R E S S I O N

  • 8/20/2019 Fike Agent Storage Containers

    37/38

    ADVANCED DETECTION SYSTEMSFIKE LEADS THE WAY WITH CHEETAH Xi®.  Our intelligent Cheetah Xi system performs operations with

    speed, intelligence and flexibility. Fike can help you design the ideal fire protection, detection and

    control system for your facility.

    O NE PAN EL F IT S AL L Y OU R N EE DS F OR L IF E SAF ET Y AN D F IRE P RO TE CT IO N

    C L E A N A G E N T F I R E S U P P R E S S I O N

  • 8/20/2019 Fike Agent Storage Containers

    38/38

    E - m a i l : f p s s a l e s @ f i k e . c o m

    Fike and Fike Corporation, CheetahXi are trademarks or registered trademarks of 

    Fike Corporation VESDA is a registered trademark of Xtralis DuPont and FM 200

    F I K E G L O B A L M A N U F A C T U R I N G , S A L E S A N D S E R V I

    AMERICAS

    FIKE CORPORATIONBlue Springs, MOUSATel: +1-816-229-3405Email: [email protected]

    FIKE LATINA LTDA

    Jundiai, BrazilTel: +55-11-4525-5900Email: [email protected]

    EUROPE

    FIKE PROTECTION SYSTEMS, LTD.Guildford, SurreyUnited KingdomTel: +44-01-483-457-584Email: [email protected]

    ASIAFIKE ASIA PACIFIC SDN BHDSelangor Darul Ehsan, MalaysiaTel: +60-3-7859-1462Email: [email protected]

    EXPERIENCED: We’ve worked in the

    ire protection business since 1960.

    FOCUSED: We specialize in Life Safety

    Products, as well as Facility and Asset

    Protection Products.

    VERSATILE: We design, manufacture,

    distribute and maintain our products.

    GLOBAL: We have clients, manufacturing

    acilities, sales outlets and maintenance

    ompanies around the world.

    NNOVATIVE: In 1994, we became

    he first manufacturer to bring a

    UL-listed and FM-approved, clean agent

    ire-suppression system to market,

    eplacing Halon.

    EARTH-FRIENDLY: We pioneered the

    development of clean agent systems

    nd we continue to develop other

    nvironmentally safe alternatives such

    s our superior inert gas system.

    COMPREHENSIVE: Fike has a worldwide

    etwork of experienced distributors

    ach with a staff of factory trained

    echnicians to meet your installation

    nd service requirements.