Core Identification
ALSECURE ® NX 400
Design
Marking
5. ArmourSingle layer of galvanizedsteel wires
6. Outer sheathHalogen free polyolefinColour: black
Applications
Max core temperature: 90 °C
Type Approval Certificates
StandardsBS 7846 - F2BS 6387 Cat. CWZ
0.6/1 kV
Fire safety circuits for controlsystems and large powertransmission (water pump,hydrant, air fans....) withenhanced mechanical protection
BASEC: British Approval Service for Cables
LPCB : Loss PreventionCertification Board
3 cores: brown - black - grey4 cores: blue - brown - black - grey
1. ConductorBare copper stranded class 2BS 6360/IEC 60228
2. Mica tape(s)
3. InsulationSpecial XLPE(cross linked polyethylene)
4. Inner sheathHalogen free polyolefin (over optional filler and bindertapes(s))
1
2
3
6
BrCl
Fl EMI-20 °C + 70 °CNo corrosivity
IEC 60754-2No toxicityHalogen free
IEC 60754-1Low smoke
IEC 61034Fire retardant
IEC 60332-3
1
British StandardFire Resistant Cables
5
4
BS7846-F2
WHITE PRINT:ALSECURE NX400 size CU/MT/XLPE/EB/SWA/LSHF year xxxxM Batch No.xxxx
EMBOSSING 1:)( BS7846 - F2 ELECTRIC CABLE - 600/1000V BASEC LPCB 582B/01
EMBOSSING 2:Cu XLPE size year
Fire resistantBS 6387 CWZIEC 60331-21
All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexansare indicicative only and shall not be binding on Nexans or treated as constituting a representation on the part of Nexans.
snaxeN - 80 02
© th gi ryp oC
ALSECURE® NX 400
2
131 1.65
162 1.15
197 0.87
251 0.60
304 0.45
353 0.37
406 0.30
463 0.26
546 0.21
628 0.185
728 0.17
3 x 25* 21.0 27.5 1 960
3 x 35* 23.0 30.0 2 380
3 x 50** 24.0 30.5 2 770
3 x 70** 27.0 34.0 3 550
3 x 95** 30.5 39.0 4 780
3 x 120** 34.0 42.0 5 720
3 x 150** 37.0 46.5 7 100
3 x 185** 41.5 51.0 8 490
3 x 240** 46.0 56.5 10 620
3 x 300** 51.0 61.5 12 740
3 x 400** 57.0 68.0 15 810
Cables(mm2)
Current rating(A)
Weightapprox.(kg/km)
Outer diameter (approx.)
Min. (mm) Max. (mm)
Voltage drop(V/A x km)
AC 3 cores loaded
* circular stranded conductors (class 2)** shaped stranded conductors (class 2)
(1) to be doubled during laying operations
R= 6 x outer diam. max. for circular conductors(1)
= 8 x outer diam. max. for shaped conductors(1)
Current rating general conditionsThe data are indicated for continuous duty operation and apply to:• maximum conductor temperature = 90 °C• nominal frequencies = 50 or 60 Hz• one cable in free air (on perforated trays)• ambient temperature = 30 °CData recording from BS 7671 (1992) table 4 E 4
Voltage dropThe data are based on Cos ϕ = 1and in accordance with BS 7671 (1992)
For other laying conditions, refer to the above standard.
131 1.65
162 1.15
197 0.87
251 0.60
304 0.45
353 0.37
406 0.30
463 0.26
546 0.21
628 0.185
728 0.17
4 x 25* 22.5 32.0 2 320
4 x 35* 25.0 32.0 2 870
4 x 50** 27.0 34.0 3 450
4 x 70** 31.0 39.5 4 800
4 x 95** 34.5 43.0 5 980
4 x 120** 38.5 48.5 7 690
4 x 150** 43.0 52.5 8 900
4 x 185** 48.0 58.0 10 8004 x 240** 54.0 64.5 13 600
4 x 300** 59.0 70.0 16 500
4 x 400** 66.5 79.0 21 800