Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
TM-851 0429.000
Fermilab,
ACCELERATOR DIVISION CAPACITOR STORED ENERGY DEVICES
J. Ryk
February 13, 1979
An attempt has been made to list all devices in the Accelerator
Division that use energy storage capacitors. Safety requirements
as stated by the National Electrical Code (NEC) are considered and
recommendations for safe practices are listed.
1. Code Requirements, NEC 1978, Article 460
1.1 Capacitors containing more than 3 gallons of flammable
liquid are to be stored in vaults or outdoor fenced
enclosures.
1.2 Capacitors are to be enclosed, located or guarded so
that accidental contact is not possible, unless the area
is only accessible to authorized and qualified persons.
1.3 Isolating means are required for capacitors that will be
removed from service. The isolation measure is to provide
a visible gap in the electrical circuit.
1.4
1.5
Overcurrent protection is required to detect and interrupt
fault current that is likely to cause dangerous pressure
within an individual capacitor.
Identification is required. Nameplate information to
include: manufacturer frequency KVAR or amperes number of phases amount of liquid flammable or non-flammable
TM-851 -2-
1.6 A means of discharge is required to reduce the residual
voltage to 50 volts or less:
within 5 minutes if initial voltage is over 600 volts
within 1 minute if initial voltage is less than 600 volts
2. Discharging Capacitor
The stored energy in a capacitor is W = %CV2=$QV with
C in farads
V in volts
Q in coulombs
W in Joules (Wattsec)
When a capacitor, initially charged to a voltage V,, is discharged
through a resistance R, the discharge current at first instance is
v, = -V,/R. Thereafter the current varies according to i = i. E -t/RC .
The charge on the capacitor decreases during discharge according to
q = QoE-t/RC, where Q. is the initial charge. The National Electric
Code states that the residual voltage is to be reduced to 50 volts
within 1 minute for V, < 600 volts and within 5 minutes for V, > 600
volts. Since V = Q/c, the voltage at discharge follows the same curve
as the charge, or v = V,E -t/RC . From this we can find the resistance
necessary to meet the code requirement for discharge time.
= E-t/RC In v t -= --
vO RC
In v, = t V RC
R=ElnV 0
TM-851 -3-
with t = 60 set for V < 600 volts 0
t = 300 see for V. > 600 volts
vO = peak operating voltage
v = 50 volts
If a capacitor bank already has a discharge resistor connected,
we can find the discharge time from:
t = RC In '0 v
All capacitor banks in the Accelerator Division have been listed
with their voltage, capacitance and stored energy. Values of dis-
charge resistance required per NEC are listed together with the dis-
charge times.
Warnings
1. In order to meet the NEC requirement for overcurrent protection
it is customary practice to use fuses to protect either individual
capacitor cases or complete capacitor banks. If a fuse blows
and the capacitor has internal discharge resistors, the
2.
capacitor will automatically discharge. If a fuse blows and
the capacitor has no internal discharge resistor, which is very
often the case, the capacitor will stay charged.
If a blown fuse is detected, always discharge the capacitor,
short it and ground it.
In general a capacitor does not return, on discharge, the full
amount of energy put into it. Some time after the discharge an
additional discharge may be obtained. This phenomenon is known
as dielectric absorption. Before working on a device with
capacitors, first discharge it, leave the discharge device on it,
short and ground the capacitors, Leave the capacitor shorted
and grounded during the complete servicing time.
TM-851
-4-
3. When storing and transporting capacitors, always have the
capacitors shorted.
4. An impulse discharge of % Joule causes muscular contraction.
An impulse discharge of 50 Joule is lethal (ref. 1).
5. If no good contact is made with the discharging device, it is
possible to create welding of the discharge device to the
stored energy device. See Appendix A.
6. Some capacitors are located in radiation areas, so radiation
rules need to be observed in addition to all other safety rules.
7. Many capacitors use askarel as the liquid dielectric. The
principal constituent of askarel is PCB (polychlorinated
biphenyl) a toxic substance with adverse ecological effects.
These capacitors should be marked with a sticker, indicating
that they contain PCB.
When a PCB filled capacitor fails, it has to be disposed of in
accordance with PCB disposal requirements.
8. Whenever a system has been subjected to a hi-pot test, it should
be treated as a charged capacitor. Proper discharge techniques
are to be followed prior to working on the system, see also
Appendix B.
TM-851
-5-
SAFETY
Capacitors are a potential shock hazard, explosion hazard,
fire hazard and toxicity (PCB) hazard.
Shock Hazard
1. Before working on capacitors, always remove power from the
capacitors by a visible disconnect.
2. After disconnecting the power, the capacitors still present a
potential shock hazard due to the fact that a charge may still
be existing. The capacitors should be discharged prior to
handling.
Some systems have a mechanical automatic discharge system.
Some capacitors have internal discharge resistors.
Under no condition shall these discharge devices be considered
as adequate. As stated by NEMA Publication No. CP-1-1976, "The
use of a discharge device is intended to supplement rather than
to displace the short-circuiting of a capacitor unit before
handling".
3. After disconnecting the capacitor from the power source, wait
at least 5 minutes, then short and ground the capacitor equip-
ment and individual capacitors, using an insulated ground stick.
Shorting should be terminal to terminal and terminal to case.
Individual units should also be shorted because shorting of a
complete capacitor bank is ineffective in case of a fuse opera-
tion or other disconnection of an individual capacitor unit.
4. Ground sticks should have a discharge resistor so that initial
discharge of the capacitors is through a resistor (see attached
SKMS81375). The discharge resistance as required by the National
Electric Code requirements is listed for the different equipments.
TM-851
5.
6.
7.
-6-
Westinghouse, for their Wemcol impregnated capacitors (ref. 4)
suggests using a resistance in ohms about equal to the maximum
peak voltage that may have been on the capacitor. The resistor
should have a peak voltage capability greater than the maximum
peak voltage on the capacitor and an energy capability greater
than the energy stored in the capacitors.
After discharging the capacitors, a shorting connection should
be installed between the terminals and a ground connection should
be left on till all work on the equipment is completed.
If an insulated wire is used from ground stick to ground, it
should have clear insulation, so that wire continuity is visible.
Ground sticks should always be kept clean!
Explosion Hazard
Capacitors, fused or unfused, may rupture upon failure. They
may explode also during hi-pot tests; it is therefore important that
the capacitors are installed or shielded in such a way that personnel
are protected from exploding capacitors.
Sometimes capacitors show bulging due to internal pressure from
gassing. These capacitors should be disposed of. It is also recom:.
mended that the internal pressure be relieved before handling by
breaking off a bushing terminal with a long pole, or by puncturing
the case with a punch after covering the capacitor with a heavy cloth.
The puncture should be made where a minimum of fluid leakage will
occur. Provisions should be made to collect the drained fluid.
Avoid liquid contact with skin and eyes and avoid exposure to
fumes in an unventilated area.
TM-851
-7-
Fire Hazard
A fire
used in the
hazard exists where a flammable dielectric fluid is
capacitors. This should be stated on the nameplate.
The location of these type capacitors should be such that a possible
fire after capacitor failure and rupture can be contained in accord-
ance with the National Electric Code.
Conclusion
There are a large variety of devices with capacitive stored
energy in the Accelerator Division.
Many of the devices have automatic discharge equipment. There
are a variety of discharge and grounding sticks in use. The Safety
Department is in the process of procuring grounding sticks.
Due to the variety of the different systems, it is not possible
to treat each system alike. It is recommended that the persons
responsible for the different systems write their own safety discharge
and grounding procedures based upon the general recommendations as
listed in these guidelines. Several of the accelerator systems have
existing written procedures with pictorial guides. This would be a
good overall system, very valuable for training of new people.
JR/nep
TM-851 -8-
Appendix A
Welding of the grounding stick to the capacitor can occur
depending on capacitor energy. A large amount of stored energy should
be discharged using the proper discharge resistance and using positive
contact procedure. Intermittent contact will initiate welding.
The amount of energy needed to heat and weld 1 cc of copper
can be found as follows:
Copper: melting point = 1083 C
specific heat = .092 cal/g/oC at 20°C
Latent heat of fusion = 49 Cal/g
Density = .3223 lb/in3
The temperature rise to the melting temperature AT = 1083-20 = 1063°C.
To heat one gram of copper to melting temperature, it takes
. 092 x 1063 = 97.8 calories
To melt 1 gram of copper, takes 49 calories
To heat and melt 1 gram of copper it takes 146.8 calories.
One cubic inch of copper weighs .3223 pounds = .3223 x 453 = 146 grams 1 cm3 of weighs 146 copper
(2.54j3 = 8.9 grams.
To heat and melt 1 cm 3 of copper takes: 146.8 x 8.9 = 1308 calories.
1 Joule z .239 calories
In order to heat and melt 1 cc of copper, it will take - 1308 = 5473 . 239 joule:
A discharge of 5.5 kJ can cause melting of 1 cm' of copper, which would
mean welding of the grounding rod to the energy storage system. The
same calculations for steel show that 4.3 kJ is enough to heat and
weld 1 cc of steel.
TM-851
-9-
A typical weld with a spot diameter of .5 cm and a penetration of
one-fifth the spot diameter, corresponds to heating and melting of
. 040 cc. of metal.
The average cold resistance of a spot this size is .5 milliohm
(ref. 3).
This weld would be accomplished with an energy .04 x 5473 = 220 Joules.
If this energy is discharged in .l second, the average power would
be 2200 Joules per second or 2200 watts. From P = i2R = 'g we find
that the welding current will be G3 = 2080 amps at a voltage
of 1 volt across the weld.
TM-851 -lO-
Appendix B
Capacitance of Cables
The capacitance of a one-conductor shielded cable is given
by the formula C = 7.35(SIC) log ;
where C = capacitance of the cable in picofarads per foot
SIC = dielectric constant of the insulation
D = diameter over the insulation
d = diameter under the insulation
typical values of SIC
polyvinyl chloride (PVC) 5.0 - 8.0
butyl and EP insulation 3.5
polyethylene insulation 2.3
cross-linked polyethylene 3.5 - 6.0
A typical example is our 13.8 KV feeder cable, 750 MCM with
cross-linked polyethylene insulation.
Typical length is % circumference of the main ring, or
10600 feet
D = 1.45"
d = 1.1"
c = 7.35 x 5 = 306 pf/ft
for 10,600 ft., C = 3.27nf
At the typical test voltage of 29 KVDC, the feeder has a stored
energy of 1362 Joules.
To discharge the feeder in accordance with the National Electric Code
to 50 volts in 5 minutes, requires a discharge resistor of 15 MQ.
TM-851 -ll-
DEVICES WITH CAPACITIVE ENERGY STORAGE
MAIN RING
DEVICE
CAPACITANCE PEAK STORED NEC NEC C VOLTAGE ENERGY Required Required
V gv 2 Discharge Discharge Resistance Time t
IJf VOLTS JOULES KS2 Set REMARKS
RF Anode Supplies 45
RF UC 4 Modulators amp .1
Cap. Tree per phase 2940
C48 Kicker .080
B24 Pulsed Quad 240
E48 Pinger 240
C34 Pulsed Quad 240
A34 Pulser 240
F13 Pulsed Quad 240
RF Test Station 11
Harmonic Filter 25
Power Supplies Passive Filter 200
$I Power Supplies Active Filter 690000
A, Power
Supplies (2) 88800
34,000 26010 1022
480 .46 6631 30,000 45 470,000
12,000 212000 18.6
200 KV 400 493000
2000 480 340
2000 480 340
2000 480 340
2000 480 340
2000 480 340
35000 6700 4160
8000 800 2364
1000
40
150
100 500
552 60 ex. 50R disch. res.
999 60 60 ex. 3352 disch. res.
300
60 300
300
300
300
300
300
300
300
300
300
oil filled
300
TM-851
DEVICE
200 MeV Chopper
Sl and S2 Pulsed Power Supplies
Electrostatic Injection Infl ector
ORBUMP Supply H+
ORBUMP Supply H-
Hor & Vert Notch Power SUPPlY
Bex Back
GMPS Circuit Cap, Each Girder
GMPS Filters
East and West RF Anode Supplies
RF ac-
-12-
DEVICES WITH CAPACITIVE ENERGY STORAGE
CAPACITANCE C
uf
.17
PEAK STORED VOLTAGE ENERGY
V 1-,cv 2
VOLTS JOULES
1000000 850
NEC NEC Required Required Discharge Discharge Resistor R Time t
KS-2 Set
232000 300
1200 1.300 1014 76 300
.04 70000 98 1035000 300
2400 2250 6075 33 300
1100 3500 6738 64 400
.34 32000 174 137000 300
1660 350 102 19 60
8300 1000 4150 12
2800 1000 1400 36
45
4
34000 26010 1022
480 .46 6631 30000 45 470000
60000 135 564000 60000 270 282000
300
300
300
3:;
300 300
300
300 300
300
300
Modulators output- .l
MK 90 cable .075 internal .15
MP 01 Pulsed Septum 2400
MKS Ol/ cable .075 MKS-02 internal ..15
RF Test Station 11
MP-70 2400
BOOSTER
1500 2700 37
50000 94 579000 50000 198 289500
3500 6700 4160
1500 2700 37
REMARKS ex. 1000 KS2 disch. res.
ex. 75 KS2 disch. res.
ex 100 KS2 disch. res.
ex. 100 KR disch. res.
oil filled
oil filled
TM-851
-13-
DEVICES WITH CAPACITIVE.ENERGY STORAGE
SWITCHYARD
DEVICE
MK-120
CAPACITIVE PEAK STORED NEC Required NEC C VOLTAGE ENERGY Discharge Required
V J-;cv 2 Resistor Discharge (max) R
Ilf Time (max)
VOLTS JOULES K1;2 t (set) REMARKS
240 2000 480 340 300
MV-T90 inv 970 415 84 29 60
MVT-101 inv 970 415 84 29 60
MVT-120 inv 970 415 84 29 300
PVT-80 240 2000 480 339 300
PVT-91 240 2000 480 339 300
PVT-101 240 2000 480 339 300
PVT-103 240 2000 480 339 300
Pos. Pulse 480 2000 960 169 300
Ang. Pulse 480 2000 960 169 300
EXT 60800 400 4864 .475 60
TM-851 -14-
DEVICES WITH CAPACITIVE ENERGY STORAGE
LINAC
CAPACITANCE PEAK STORED NEC NEC C VOLTAGE ENERGY Required Required
V gv* Discharge Discharge Resistor Time
(max) hod DEVICE
PA bias SUPP’iY
220
VOLTS JOULES ‘KG iec REMARKS r\nrr ex. disch. resistor
Modulators plate- 100
4616 Anode driver 24 SUPPlY screen 40
7651 Anode Supply 40
Quad Cl-C4 2200 Supplies Cll-C22 240
2700 6500
800 2100
340 600
mu 140 KQ 300 ex. disch. res
200 KQ
Both Haeflies
HV PS Cap Bank
PFN Power Bank
PFN Turn-Off SUPPlY
Ion Pump Power Supply
Varian p.s. for ion pump
Triplet p.s.
Chopper U.V.
H- Extractor
Hf Extractor .048 12000 .24
HV p.s. (anode supply)
Arc modulator
Cup pulser
.005 750000 1406 6240MS2 300
30.8 52000 41640 1402 300 aut gnd 2.5m to Ofi
1000 600 180 24 60
20 2000 4066
2 5000 25 32600
.5 10000 25
360000 40 288
.27 30000 122
.a 30000 45
113MS1
we
174MR
469MR
1100MQ 300
8 8000 256
3900 300 176
900 600 162 27 1800 300 81 19
20000 4800 3500 245
3000 180
800 704 800 77
2086 1765
1832
4:;
300 aut gnd 1KR to OR 300 aut gnd 25Ks2
300 aut gnd 25KsZ
300 aut gnd 1OOQ 600 aut gnd 100R
300
300
300
60
300
300
300
300 300
ex. 10MM disch. res.
ex. 4R disch. res.
aut gnd 4000Mn to Or;2
ex. 27OKs2 disch res +2.5MR solenoid
ex. 333MR disch res safety ckt 1OMQ
ex. 3Om disch res
ex. 47Kr;2 disch res ex. 47m disch res
TM-851
REFERENCES
-15-
1.
2.
3.
4.
5.
6.
7.
ZGS Safety Information - December 10, 1964.
National Electric Code - 1978.
Welding for Engineers, J. Wiley.
Westinghouse Publication I.L. 39-311-1A.
NEMA CP-1, 1976.
Ten Commandments of Electronic Safety.
Okonite Bulletin 721.1.
JR/nep
-16- TM-851
W&inghouse Electric Corporation /GwuAL GEOUx/p/M~ t$5&Ge 0 w
TITLE
DIV & PLANT LOCATION- DAD--BLOOMINGTON. IND. U.S.A
ELECTR I C SHOCK, SEVERlTY FACTORS ~
-. TM-851
The severity of the shock received when a person becomes part of an electrical circuit is affected by three primary factors. These factors are:
(1) The rate of flow of current through the body, measured in milliamperes;
(2) The path of current through the body; and (3) The length of time the body is in the circuit.
Other factors which may affect the degree of shock are: the frequency of the current, phase of the heart cycle when shock occurs, and the physical and psychological condition of the person. The following are measurements of injury related to current for the case of 60 cycle, 120 volt alternating current.
Less than l/2 milliampere -- No sensation. l/2 to 2 -- Threshold of perception. 2to 10 -- Muscular cant raction
(mild to strong). 5 to 25 -- Painful shock, inability to
let go. Over 25 -- Violent muscular contraction. 50 to 100 -- Ventricular fibrillation. Over 100 -- Paralysis of breathing.
Direct Current Voltage 60 milliamperes -- Muscular contraction. 500 milliamperes -- Lethal.
Impulse Discharge l/4 joule -- Muscular contraction. 50 joule -- Lethal.
Over 100, 000 cycles there is no sensation to shock but strong possibility of burns.
In estimating possible body current, assume a 500 ohm body resistance between major extremities. This low figure might be attained when the skin is initially injured by shock from voltages as low as 50 Volts or from damp contact conditions.
Example: 50 Volts A. C. divided by body resistance of 500 ohms, equals 100 milliamperes, which is lethal if through body.
Ref: LOS Almos, Electrical Safety Guide; Safety In Industry, Bulletin No. 216
DATE December 16, 1964 PAGE 1 OF I