    Options for ABB drives, converters and inverters

    Users manualFDNA-01 DeviceNet adapter module

  • 7/28/2019 FDNA-01 1

    2/168

    List of related manuals

    See section Related manuals on page 16.

  • 7/28/2019 FDNA-01 1

    3/168

    6. Start-up

    Users manual

    FDNA-01 DeviceNet adapter module

    3AFE68573360 Rev EENEFFECTIVE: 2012-04-04

    2012 ABB OyAll Rights Reserved.

    1. Safety

    Table of contents

    4. Mechanical installation

    5. Electrical installation

  • 7/28/2019 FDNA-01 1

    4/168

  • 7/28/2019 FDNA-01 1

    5/168

    Table of contents 5

    Table of contents

    1. SafetyWhat this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    Use of warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    Safety in installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    2. About the manual

    What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    Applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    Target audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    Purpose of the manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    Related manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    Before you start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    Terms and abbreviations used in this manual . . . . . . . . . . . . . . 19

    General terms and abbreviations . . . . . . . . . . . . . . . . . . . . 19DeviceNet terms and abbreviations . . . . . . . . . . . . . . . . . . . 20

    3. Overview of the DeviceNet network and the FDNA-01

    module

    What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    DeviceNet network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    Example topology of the DeviceNet link . . . . . . . . . . . . . . . 24

    FDNA-01 DeviceNet adapter module . . . . . . . . . . . . . . . . . . . . 25

    Layout of the adapter module . . . . . . . . . . . . . . . . . . . . . . . 26

    4. Mechanical installation

    What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

    Delivery check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

    Mounting the adapter module . . . . . . . . . . . . . . . . . . . . . . . . . . 28

    5. Electrical installation

    What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

  • 7/28/2019 FDNA-01 1

    6/168

    6 Table of contents

    General cabling instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    Connecting the module to the DeviceNet network . . . . . . . . . . . 30

    Terminal block description . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    Connection examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    Switching on the bus termination . . . . . . . . . . . . . . . . . . . . . . . . 31

    6. Start-up

    What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

    Drive configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    DeviceNet connection configuration . . . . . . . . . . . . . . . . . . 34

    FDNA-01 configuration parameters group A (group 1) 35

    FDNA-01 configuration parameters group B (group 2) 47

    FDNA-01 configuration parameters group C (group 3) 48Control locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

    Starting up ACS355 drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

    Parameter setting examples ACS355 . . . . . . . . . . . . . . . . 50

    ABB Drives profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

    ODVA AC/DC drive profile . . . . . . . . . . . . . . . . . . . . . . . 52

    Starting up ACSM1 drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

    Parameter setting examples ACSM1 . . . . . . . . . . . . . . . . 55ABB Drives profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

    ODVA AC/DC drive profile . . . . . . . . . . . . . . . . . . . . . . . 57

    Starting up ACS850 and ACQ810 drives . . . . . . . . . . . . . . . . . . 59

    Parameter setting examples ACS850 and ACQ810 . . . . . 60

    ABB Drives profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

    ODVA AC/DC drive profile . . . . . . . . . . . . . . . . . . . . . . . 63

    Starting up ACS880 drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

    Parameter setting examples ACS880 . . . . . . . . . . . . . . . . 65

    ABB Drives profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

    ODVA AC/DC drive profile . . . . . . . . . . . . . . . . . . . . . . . 67

    Configuring the master station . . . . . . . . . . . . . . . . . . . . . . . . . . 70

    EDS files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

    Configuring an Allen-Bradley PLC . . . . . . . . . . . . . . . . . . 71

    7. Communication profilesWhat this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

  • 7/28/2019 FDNA-01 1

    7/168

    Table of contents 7

    Communication profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

    ODVA AC/DC drive profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

    ODVA output attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

    Run Forward & Run Reverse

    (Control supervisor object) . . . . . . . . . . . . . . . . . . . . . . . 80Fault Reset (Control supervisor object) . . . . . . . . . . . . . 80

    Net Ctrl (Control supervisor object) . . . . . . . . . . . . . . . . 80

    Net Ref (AC/DC drive object) . . . . . . . . . . . . . . . . . . . . . 80

    Speed Reference (AC/DC drive object) . . . . . . . . . . . . . 80

    Torque Reference (AC/DC drive object) . . . . . . . . . . . . 82

    ODVA input attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

    Faulted (Control supervisor object) . . . . . . . . . . . . . . . . 83

    Warning (Control supervisor object). . . . . . . . . . . . . . . . 83

    Running Forward (Control supervisor object) . . . . . . . . 83

    Running Reverse (Control supervisor object) . . . . . . . . 83

    Ready (Control supervisor object) . . . . . . . . . . . . . . . . . 83

    Ctrl From Net (Control supervisor object) . . . . . . . . . . . 83

    Ref From Net (AC/DC drive object) . . . . . . . . . . . . . . . . 83

    At Reference (AC/DC drive object) . . . . . . . . . . . . . . . . 84

    State (Control supervisor object) . . . . . . . . . . . . . . . . . . 84Speed Actual (AC/DC drive object) . . . . . . . . . . . . . . . . 86

    Torque Actual (AC/DC drive object). . . . . . . . . . . . . . . . 87

    ABB Drives communication profile . . . . . . . . . . . . . . . . . . . . . . . 88

    Control word and Status word . . . . . . . . . . . . . . . . . . . . . . . 88

    Control word contents . . . . . . . . . . . . . . . . . . . . . . . . . . 88

    Status word contents . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

    State machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94

    Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94

    Actual values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95

    Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95

    8. Communication protocol

    What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97

    DeviceNet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97Object modeling and functional properties . . . . . . . . . . . . . . . . . 97

  • 7/28/2019 FDNA-01 1

    8/168

    8 Table of contents

    Assembly objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

    Basic speed control assembly . . . . . . . . . . . . . . . . . . . . . . . 98

    Basic speed control plus drive parameters assembly . . . . . 99

    Extended speed control assembly . . . . . . . . . . . . . . . . . . . 101

    Extended speed control plus drive parameters assembly . 102Basic speed and torque control assembly . . . . . . . . . . . . . 104

    Basic speed and torque control

    plus drive parameters assembly . . . . . . . . . . . . . . . . . . . . 105

    Extended speed and torque control assembly . . . . . . . . . . 108

    Extended speed and torque control

    plus drive parameters assembly . . . . . . . . . . . . . . . . . . . . 109

    ABB Drives profile with set speed assembly . . . . . . . . . . . 111

    ABB Drives profile with set speed

    plus drive parameters assembly . . . . . . . . . . . . . . . . . . . . 112

    ABB Drives profile with set speed and

    set torque assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115

    ABB Drives profile with set speed and set torque

    plus drive parameters assembly . . . . . . . . . . . . . . . . . . . . 116

    Transparent 16 with one assembly . . . . . . . . . . . . . . . . . . 118

    Transparent 16 with one assembly plus drive parameters 119Transparent 16 with two assembly . . . . . . . . . . . . . . . . . . 121

    Transparent 16 with two assembly plus drive parameters . 122

    Transparent 32 with one assembly . . . . . . . . . . . . . . . . . . 125

    Transparent 32 with one assembly plus drive parameters 126

    Transparent 32 with two assembly . . . . . . . . . . . . . . . . . . 128

    Transparent 32 with two assembly plus drive parameters . 130

    Class objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133Identity object, class 01h . . . . . . . . . . . . . . . . . . . . . . . . . . 134

    Class attributes (Instance #0). . . . . . . . . . . . . . . . . . . . 134

    Instance attributes (Instance #1) . . . . . . . . . . . . . . . . . 135

    Attribute explanations . . . . . . . . . . . . . . . . . . . . . . . . . . 135

    DeviceNet object, class 03h . . . . . . . . . . . . . . . . . . . . . . . . 137

    Class attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137

    Instance attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138

    Connection object, class 05h . . . . . . . . . . . . . . . . . . . . . . . 138

    Class attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139

  • 7/28/2019 FDNA-01 1

    9/168

    Table of contents 9

    Instance attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139

    Acknowledge handler object, class 2Bh . . . . . . . . . . . . . . 141

    Class attributes (Instance #0) . . . . . . . . . . . . . . . . . . . 141

    Instance attributes (Instance #1) . . . . . . . . . . . . . . . . . 141

    Motor data object, class 28h . . . . . . . . . . . . . . . . . . . . . . . 142Class attributes (Instance #0) . . . . . . . . . . . . . . . . . . . 142

    Instance attributes (Instance #1) . . . . . . . . . . . . . . . . . 143

    Control supervisor object, class 29h . . . . . . . . . . . . . . . . . 143

    Class attributes (Instance #0) . . . . . . . . . . . . . . . . . . . 144

    Instance attributes (Instance #1) . . . . . . . . . . . . . . . . . 144

    AC/DC-drive object, class 2Ah . . . . . . . . . . . . . . . . . . . . . 146

    Class attributes (Instance #0) . . . . . . . . . . . . . . . . . . . 146

    Instance attributes (Instance #1) . . . . . . . . . . . . . . . . . 146

    Drive parameter object, Class 90h . . . . . . . . . . . . . . . . . . 147

    Fieldbus configuration object 91h . . . . . . . . . . . . . . . . . . . 148

    Class attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148

    Instance #1: FDNA-01 configuration parameters

    group A (group 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148

    Instance #2: FDNA-01 configuration parameters

    group B (group 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151Instance #3: FDNA-01 configuration parameters

    group C (group 3). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152

    9. Diagnostics

    What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155

    LED indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156

    10. Technical dataWhat this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159

    FDNA-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160

    DeviceNet link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161

    11. Appendix A Varying the number of drive parame-

    ters

    What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163Modification of the EDS file . . . . . . . . . . . . . . . . . . . . . . . . . . . 163

  • 7/28/2019 FDNA-01 1

    10/168

    10 Table of contents

    Further information

    Product and service inquiries . . . . . . . . . . . . . . . . . . . . . . . . . . 167

    Product training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167

    Providing feedback on ABB Drives manuals . . . . . . . . . . . . . . 167

    Document library on the Internet . . . . . . . . . . . . . . . . . . . . . . . 167

  • 7/28/2019 FDNA-01 1

    11/168

    Safety 11

    1Safety

    What this chapter contains

    The chapter presents the warning symbols used in this manual andthe safety instructions which you must follow when installing anoptional module into a drive, converter or inverter. If ignored,physical injury or death may follow, or damage may occur to theequipment. Read this chapter before you start the installation.

  • 7/28/2019 FDNA-01 1

    12/168

    12 Safety

    Use of warnings

    Warnings caution you about conditions which can result in seriousinjury or death and/or damage to the equipment and advise on howto avoid the danger. The following warning symbols are used in

    this manual:

    Electricity warning warns of hazards from electricity

    which can cause physical injury and/or damage to the

    equipment.

    General warning warns about conditions, other than

    those caused by electricity, which can result in physical

    injury and/or damage to the equipment.

  • 7/28/2019 FDNA-01 1

    13/168

    Safety 13

    Safety in installation

    These warnings are intended for all who install an optional moduleinto a drive, converter or inverter.

    WARNING! Ignoring the following instructions can cause

    physical injury or death, or damage to the equipment.

    Only qualified electricians are allowed to install and maintainthe drive, converter or inverter!

    Disconnect the drive, converter or inverter into which themodule will be installed from all possible power sources. After

    disconnecting, always wait for 5 minutes to let the intermediate

    circuit capacitors discharge before you proceed.

    Do not work on the control cables when power is applied to theexternal control circuits of the drive, converter or inverter.

    Externally supplied control circuits may carry dangerous

    voltage.

  • 7/28/2019 FDNA-01 1

    14/168

    14 Safety

  • 7/28/2019 FDNA-01 1

    15/168

    About the manual 15

    2About the manual

    What this chapter contains

    This chapter introduces this manual.

    Applicability

    This manual applies to the FDNA-01 DeviceNet adapter module

    (+K451), SW version 0.223 or later.

    Compatibility

    The FDNA-01 DeviceNet adapter module is compatible with thefollowing drives:

    ACS355

    ACSM1

    ACS850

    ACQ810

    ACS880.

    The FDNA-01 DeviceNet adapter module is compatible with allmaster stations that support the DeviceNet protocol.

  • 7/28/2019 FDNA-01 1

    16/168

    16 About the manual

    Target audience

    The reader is expected to have a basic knowledge of fieldbusinterface, electrical fundamentals, electrical wiring practices andhow to operate the drive.

    Purpose of the manual

    The manual provides information on installing, commissioning andusing an FDNA-01 DeviceNet adapter module.

    Related manuals

    The related manuals are listed below.

    Code (English)

    Drive users manuals

    ACS355 drives (0.3722 kW,0.530 hp) users manual

    3AUA0000066143

    Drive hardware manuals andguides

    ACSM1-204 regen supply modules(5.3 to 61 kW) hardware manual 3AUA0000053713

    ACSM1-04 drive modules (0.75 to45 kW) hardware manual

    3AFE68797543

    ACSM1-04 drive modules (55 to 110kW) hardware manual

    3AFE68912130

    ACSM1-04Lx liquid-cooled drivemodules (55 to 160 kW) hardwaremanual

    3AUA0000022083

    ACS850-04 (0.3745 kW)

    hardware manual

    3AUA0000045496

    ACS850-04 (55160 kW, 75200hp) hardware manual

    3AUA0000045487

    ACS850-04 (200500 kW,250600 hp) hardware manual

    3AUA0000026234

    ACQ810-04 drive modules(0.3745 kW, 0.560 hp) hardwaremanual

    3AUA0000055160

    ACQ810-04 drive modules (55 to

    160 kW, 75 to 200 hp) hardwaremanual

    3AUA0000055161

    http://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000066143&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000053713&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE68797543&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE68912130&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000022083&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000045496&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000045487&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000026234&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000055160&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000055161&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000055161&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000055160&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000026234&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000045487&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000045496&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000022083&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE68912130&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE68797543&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000053713&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000066143&LanguageCode=en&DocumentPartId=1&Action=Launch
  • 7/28/2019 FDNA-01 1

    17/168

    About the manual 17

    You can find manuals and other product documents in PDF formaton the Internet. See section Document library on the Internetonthe inside of the back cover. For manuals not available in theDocument library, contact your local ABB representative.

    Before you start

    It is assumed that the drive is installed and ready to operate beforeyou start the installation of the adapter module.

    In addition to conventional installation tools, have the drivemanuals available during the installation as they contain importantinformation not included in this manual. The drive manuals arereferred to at various points of this manual.

    ACQ810-04 drive modules(200400 kW, 250600 hp)hardware manual

    3AUA0000055155

    ACS880-01 (0.55 to 250 kW, 0.75 to

    350 hp) hardware manual

    3AUA0000078093

    Drive firmware manuals andguides

    ACSM1 motion control programfirmware manual

    3AFE68848270

    ACSM1 speed and torque controlprogram firmware manual

    3AFE68848261

    ACSM1 regen supply control

    program firmware manual

    3AUA0000052174

    ACS850 standard control programfirmware manual

    3AUA0000045497

    ACQ810 standard pump controlprogram firmware manual

    3AUA0000055144

    ACS880 primary control programfirmware manual

    3AUA0000085967

    Option manuals and guides

    FDNA-01 DeviceNet adapter moduleusers manual

    3AFE68573360

    Code (English)

    http://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000055155&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000078093&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE68848270&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE68848261&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000052174&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000045497&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000055144&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000085967&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE685733601&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE685733601&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000085967&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000055144&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000045497&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000052174&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE68848261&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE68848270&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000078093&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000055155&LanguageCode=en&DocumentPartId=1&Action=Launch
  • 7/28/2019 FDNA-01 1

    18/168

    18 About the manual

    Contents

    The manual consists of the following chapters:

    Safetypresents the safety instructions which you must followwhen installing a fieldbus adapter module.

    About the manualintroduces this manual.

    Overview of the DeviceNet network and the FDNA-01 modulecontains a short description of the DeviceNet network and the

    adapter module.

    Mechanical installation contains a delivery checklist andinstructions on mounting the adapter module.

    Electrical installation contains cabling and bus terminationinstructions and instructions on connecting the module to the

    DeviceNet network.

    Start-up presents the steps to take during the start-up of thedrive with the adapter module and gives examples of

    configuring the master system.

    Communication profiles describes the communication profiles

    used in the communication between the DeviceNet network,the adapter module and the drive.

    Communication protocoldescribes the DeviceNetcommunication protocol for the adapter module and the

    configuration of the scanner.

    Diagnostics explains how to trace faults with the status LEDson the adapter module.

    Technical data contains the technical data of the adaptermodule and the DeviceNet link.

    Appendix A Varying the number of drive parametersdescribes how to reduce the number of drive parameter

    members in FDNA-01 assemblies by modifying the EDS file.

  • 7/28/2019 FDNA-01 1

    19/168

    About the manual 19

    Terms and abbreviations used in this manual

    General terms and abbreviations

    Term Explanation

    Command word See Control word.

    Communication module Communication module is a name for a device(eg, a fieldbus adapter) through which the driveis connected to an external communicationnetwork (eg, a fieldbus). The communicationwith the module is activated with a driveparameter.

    Control word 16-bit or 32-bit word from master to slave withbit-coded control signals (sometimes called theCommand word).

    DCU profile Drive Control Unit profile, native profile used inthe ACS350 and ACS355 drives

    DTC Direct Torque Control is a motor control methodfor AC drives. DTC allows accurate control ofboth motor speed and torque without pulseencoder feedback from the motor shaft.

    FBA profile Fieldbus Adapter profile, native profile used inthe ACQ810, ACS850 and ACSM1 drives

    FDNA-01 DeviceNetadapter module

    One of the optional fieldbus adapter modulesavailable for ABB drives. FDNA-01 is a devicethrough which an ABB drive is connected to aDeviceNet serial communication bus.

    LSW Least significant word

    MSW Most significant word

    Parameter An operating instruction for the drive.Parameters can be read and programmed withthe drive control panel, drive PC tools orthrough the adapter module.

    Profile Adaptation of the protocol for certain applicationfield, for example, drives.

    In this manual, drive-internal profiles (eg, DCU

    or FBA) are called native profiles.

    RFG Ramp Function Generator

  • 7/28/2019 FDNA-01 1

    20/168

    20 About the manual

    DeviceNet terms and abbreviations

    Status word 16-bit or 32-bit word from slave to master withbit-coded status messages

    Term Explanation

    Change of State/CyclicMessage

    Change of State/Cyclic Message is transmittedby either the master or the slave. A Change ofState/Cyclic Message is directed towards asingle specific node (point-to-point). AnAcknowledge Message may be returned in

    response to this message.CIP Common Industrial Protocol (CIP) is an

    industrial protocol for industrial automationapplications. It is managed by ODVA.

    EDS File Electronic Data Sheet (EDS) file identifies theproperties of the device to the DeviceNetScanner. Each type of drive and applicationprogram requires its own EDS file.

    Input In the ODVA DeviceNet specification the wordinput is used to describe data flow from adevice (such as FDNA-01) to the network.

    I/O assembly selection Smart networked devices (like FDNA-01) canproduce and/or consume more than one I/Ovalue. Typically, they produce and/or consumeone or more I/O value, as well as status anddiagnostic information. Each piece of datacommunicated by a device is represented by an

    attribute of one of the devices internal objects.Communicating multiple pieces of data(attributes) across a single I/O connectionrequires that the attributes be grouped orassembled together into a single block.

    MAC ID Every node on DeviceNet network has to havea unique identifier. This node number is calledMAC ID (Media Access Control Identifier).

    Term Explanation

  • 7/28/2019 FDNA-01 1

    21/168

    About the manual 21

    ODVA ODVA stands for Open DeviceNet Vendor Association. ODVA is an independentorganization that promotes interoperativity

    between different manufacturers DeviceNetproducts. ABB is an Associate Member atODVA.

    Output In the ODVA DeviceNet specification the wordoutput is used to describe data flow from thenetwork into a device (such as FDNA-01).

    Poll Message Most DeviceNet Scanners as well as the FDNA-01 module support two different data services.These are Poll and Change of State/Cyclicmessages.

    The Poll Command is an I/O Message that istransmitted by the master. A Poll Command isdirected towards a single, specific slave (point-to-point, FDNA-01 always acts as a slave). Amaster must transmit a separate Poll CommandMessage for each of its slaves that is to bepolled. The Poll Response is an I/O Messagethat a slave transmits back to the master when

    the Poll Command is received.

    Scanlist DeviceNet Scanner communicates with theDeviceNet slaves in a user-defined order. Thisorder of communication is the scanlist. Thescanlist contains a complete list of the slavenodes and the order in which the slaves areaccessed.

    Term Explanation

  • 7/28/2019 FDNA-01 1

    22/168

    22 About the manual

  • 7/28/2019 FDNA-01 1

    23/168

    Overview of the DeviceNet network and the FDNA-01 module 23

    3Overview of the DeviceNetnetwork and the FDNA-01module

    What this chapter contains

    This chapter contains a short description of the DeviceNet network

    and the FDNA-01 DeviceNet adapter module.

    DeviceNet network

    The DeviceNet network has a linear bus topology. Terminatingresistors are required on each end of the trunk line. Drop lines aslong as 6 metres (20 feet) each are permitted, allowing one ormore nodes to be attached. DeviceNet allows branching structuresonly on drop lines.

    The maximum length of the trunk cable depends on the data rateand on the type of the cable used (see chapterTechnical data).

  • 7/28/2019 FDNA-01 1

    24/168

    24 Overview of the DeviceNet network and the FDNA-01 module

    Example topology of the DeviceNet link

    An example of an allowable topology is shown below.

    Node

    Node

    Node

    Node

    Node

    Tap

    Tap

    TapTap

    Node

    Node

    Node

    Node

    Node

    Node

    Trunk line

    Terminating

    Resistor

    Drop line

  • 7/28/2019 FDNA-01 1

    25/168

    Overview of the DeviceNet network and the FDNA-01 module 25

    FDNA-01 DeviceNet adapter module

    The FDNA-01 DeviceNet Adapter module is an optional device forABB drives. It enables the connection of the drive to a DeviceNetnetwork. The drive is considered a slave in the DeviceNet network.

    Through the adapter module you can:

    give control commands to the drive (for example, Start, Stop,Run enable)

    feed a motor speed or torque reference to the drive

    give the actual value or reference of the process to the PIDcontroller of the drive

    read status information and actual values from the drive change drive parameter values

    reset a drive fault.

    The adapter module acts as a class 2 slave only with predefinedmaster-slave connection set services. These include the explicitmessaging, the poll-response service and the change of state/cyclic service. The DeviceNet commands and services supportedby the adapter module are described in chapterCommunication

    protocol.

    The adapter module is mounted into an option slot on the motorcontrol board of the drive. See the drive manuals for the moduleplacement options.

  • 7/28/2019 FDNA-01 1

    26/168

    26 Overview of the DeviceNet network and the FDNA-01 module

    Layout of the adapter module

    Diagnostic LEDs(see chapterDiagnostics)

    Bus connector X1

    (see chapterElectricalinstallation)Mounting screw

  • 7/28/2019 FDNA-01 1

    27/168

    Mechanical installation 27

    4Mechanical installation

    What this chapter contains

    This chapter contains a delivery checklist and instructions onmounting the adapter module.

    WARNING! Follow the safety instructions given in thismanual and the drive documentation.

    Delivery check

    The option package for the adapter module contains:

    DeviceNet adapter module, type FDNA-01 this manual.

  • 7/28/2019 FDNA-01 1

    28/168

    28 Mechanical installation

    Mounting the adapter module

    The adapter module is to be inserted into its specific position in thedrive. The module is held in place with plastic pins and one screw.The screw also provides the electrical connection between the

    module and drive frame for cable shield termination.When the module is installed, the signal and power connection tothe drive is made through a 20-pin connector. (All drives do not useall the available signals so the connector on the drive may havefewer pins.)

    Mounting procedure:

    1. Insert the module carefully into its position on the drive.

    2. Fasten the screw.

    Note: It is essential to install the screw properly to fulfill the EMCrequirements and to ensure the proper operation of the module.

    For more information on mounting, see the drive manuals.

  • 7/28/2019 FDNA-01 1

    29/168

    Electrical installation 29

    5Electrical installation

    What this chapter contains

    This chapter contains:

    general cabling instructions

    instructions on connecting the module to the DeviceNetnetwork

    instructions on switching on the bus termination.

    WARNING! Before installation, switch off the drive power

    supply. Wait five minutes to ensure that the capacitor bank

    of the drive is discharged. Switch off all dangerous

    voltages connected from external control circuits to the inputs and

    outputs of the drive.

    General cabling instructions

    Arrange the bus cables as far away from the motor cables aspossible.

    Avoid parallel runs. Use bushings at cable entries.

  • 7/28/2019 FDNA-01 1

    30/168

    30 Electrical installation

    Connecting the module to the DeviceNet network

    Connect the bus cable to terminal block X1 on the adapter module.

    Terminal block description

    Connection examples

    5-pin micro-style connector:

    5-pin mini-style connector:

    X1 Description

    1 V- Network power supply ground (0V DC)

    2 CAN_L CAN_L bus line

    3 SHLD Network cable shield

    4 CAN_H CAN_H bus line

    5 V+ Network power supply source (24V DC)

    5

    3

    Male micro-style

    SHLDCAN_L

    CAN_H

    V- 12

    3

    4

    connector

    4

    1 2

    X1

    0 V+24 V

    Networkpower supply

    4

    5

    3

    12

    FDNA

    5V+

    V+

    32

    Male mini-style

    4

    5

    3

    12connector

    4

    5 1

    0 V+24 V

    Networkpower supply

    SHLDCAN_L

    CAN_H

    V- 12

    3

    4

    X1FDNA

    5

  • 7/28/2019 FDNA-01 1

    31/168

    Electrical installation 31

    Standard open-style screw connector:

    Switching on the bus termination

    The adapter module does not provide bus termination. TheDeviceNet network should be terminated at both ends of the trunkcable with a 121 ohm, W, 1% metal film resistor. Connect theresistor between the two signal wires (CAN_H, CAN_L) on theDeviceNet cable, as shown in the figure below.

    Further information on the DeviceNet protocol is available atwww.odva.org.

    4

    3

    2

    1

    5

    SHLDCAN_L

    CAN_H

    V-1

    2

    3

    4

    X1FDNA

    5V+

    0 V+24 VNetwork

    power supply

    Node 1 Node n

    121

    CAN_H

    CAN_L

    Scanner

    1211%

    Metal Film1/4 W

    1%Metal Film

    1/4 W

    http://www.odva.org/http://www.odva.org/http://www.odva.org/
  • 7/28/2019 FDNA-01 1

    32/168

    32 Electrical installation

  • 7/28/2019 FDNA-01 1

    33/168

    Start-up 33

    6Start-up

    What this chapter contains

    This chapter contains:

    information on configuring the drive for operation with theadapter module

    drive-specific instructions on starting up the drive with the

    adapter module examples of configuring the master station for communication

    with the adapter module.

    WARNING! Follow the safety instructions given in this

    manual and the drive documentation.

  • 7/28/2019 FDNA-01 1

    34/168

    34 Start-up

    Drive configuration

    The following information applies to all drive types compatible withthe adapter module, unless otherwise stated.

    DeviceNet connection configuration

    After the adapter module has been mechanically and electricallyinstalled according to the instructions in chapters Mechanicalinstallation and Electrical installation, the drive must be preparedfor communication with the module.

    The detailed procedure of activating the module for DeviceNetcommunication with the drive depends on the drive type. Normally,a parameter must be adjusted to activate the communication. Seethe drive-specific start-up procedures starting on page 49.

    Once communication between the drive and the adapter modulehas been established, several configuration parameters are copiedto the drive. These parameters are shown in the tables below andmust be checked first and adjusted where necessary.

    Note: Not all drives display descriptive names for the configurationparameters. To help you identify the parameters in different drives,the names displayed by each drive are given in grey boxes in thetables.

    Note: The new settings take effect only when the adapter moduleis powered up the next time or when the fieldbus adapter refreshparameter is activated.

    Note: If communication between the adapter module andDeviceNet master is established, changes to the configurationparameters can be done also throughFieldbus configuration object91h.

  • 7/28/2019 FDNA-01 1

    35/168

    Start-up 35

    FDNA-01 configuration parameters group A (group 1)

    Note: The actual parameter group number depends on the drivetype. Group A (group 1) corresponds to:

    parameter group 51 in ACS355, ACSM1, ACS850 and

    ACQ810

    parameter group 51 in ACS880 if the adapter is installed asfieldbus adapter A or group 54 if the adapter is installed as

    fieldbus adapter B.

    No. Name/Value Description Default

    01 FBA TYPE Read-only. Shows the fieldbus adapter type asdetected by the drive. Value cannot be adjusted

    by the user.If the value is 0 = None, the communicationbetween the drive and the module has not beenestablished.

    1 = Devi-ceNet

    02 MAC ID Defines the MAC ID number for the drive theadapter module is connected to. Each deviceon the DeviceNet network must have a uniqueMAC ID number.

    63

    ACS355:FB PAR 2

    ACSM1:FBA PAR2

    ACS850/ACQ810:FBA par2

    ACS880:MAC ID

    063 MAC ID

    03 BAUD RATE Read-only. Indicates the detectedcommunication speed in kbit/s.

    0 = 125kbit/s

    ACS355:FB PAR 3

    ACSM1:FBA PAR3

    ACS850/ACQ810:FBA par3

    ACS880:Baud rate

    0 = 125 kbit/s Communication speed is 125 kbit/s.

    1 = 250 kbit/s Communication speed is 250 kbit/s.

    2 = 500 kbit/s Communication speed is 500 kbit/s.

  • 7/28/2019 FDNA-01 1

    36/168

    36 Start-up

    04 DRIVE PROFILE Defines the communication used between themodule and the drive (not fieldbus and module).If a drive supports more than one drive profile,this parameter is used to select the preferred

    profile. Presently, to use the ODVA and ABBDrives profiles, the drive must support a nativeprofile (eg, DCU or FBA). Transparent16 andTransparent32 profiles may be used with anydrive profile.

    0 =Nativeprof

    ACS355:FB PAR 4

    ACSM1:FBA PAR4

    ACS850/ACQ810:FBA par4

    ACS880:Drive profile

    0 = Native prof Native profile of the drive selected

    05 ODVA STOPFUNC

    Used with the ODVA AC/DC drive profile.Determines how the motor is stopped when a

    stop command is received via DeviceNet.

    0 = Rampstop

    ACS355:FB PAR 5

    ACSM1:FBA PAR5

    ACS850/ACQ810:FBA par5

    ACS880:ODVA stop func

    0 = Ramp stop Motor decelerates along the active decelerationramp.

    1 = Coast stop Motor comes to a stop by coasting.

    No. Name/Value Description Default

  • 7/28/2019 FDNA-01 1

    37/168

    Start-up 37

    06 OUTPUTINSTANCE

    Configures the output assembly instances usedby the adapter module. Tables below list thesupported assemblies and allowedcombinations. For the descriptions of the

    assembly instances, see sectionAssemblyobjects on page 98.

    20

    ACS355:FB PAR 6

    ACSM1:FBA PAR6

    ACS850/ACQ810:FBA par6

    ACS880:Output instance

    No. Name/Value Description Default

    Name Outputinstance

    Inputinstance

    Defaultinput

    size(bytes)

    Profile

    Basic speed control 20 70 4 ODVA AC/DC drive

    Extended speedcontrol

    21 71 4 ODVA AC/DC drive

    Basic speed andtorque control

    22 72 6 ODVA AC/DC drive

    Extended speed andtorque control

    23 73 6 ODVA AC/DC drive

    Basic speed controlplus drive parameters

    120 170 24 ODVA AC/DC drive

    Extended speedcontrol plus driveparameters

    121 171 24 ODVA AC/DC drive

    Basic speed andtorque control plusdrive parameters

    122 172 26 ODVA AC/DC drive

    Extended speed andtorque control plusdrive parameters

    123 173 26 ODVA AC/DC drive

    ABB Drives profilewith set speed

    801 851 4 ABB Drives

    ABB Drives profilewith set speed andset torque

    802 852 6 ABB Drives

    (continued)

  • 7/28/2019 FDNA-01 1

    38/168

    38 Start-up

    No. Name/Value Description Default

    Name Outputinstance

    Inputinstance

    Defaultinputsize

    (bytes)

    Profile

    (continued)

    ABB Drives profilewith set speed plusdrive parameters

    901 951 24 ABB Drives

    ABB Drives profilewith set speed andset torque plus driveparameters

    902 952 26 ABB Drives

    ABB Drives profile

    with set speed plusdrive parameters

    901 951 24 ABB Drives

    Transparent16 withone

    811 861 4 Transparent16

    Transparent16 withtwo

    812 862 6 Transparent16

    Transparent16 withone plus driveparameters

    911 961 24 Transparent16

    Transparent16 withtwo plus driveparameters

    912 962 26 Transparent16

    Transparent32 withone

    821 871 8 Transparent32

    Transparent32 withtwo

    822 872 12 Transparent32

    Transparent32 withone plus driveparameters

    921 971 28 Transparent32

    Transparent32 withtwo plus driveparameters

    922 972 32 Transparent32

  • 7/28/2019 FDNA-01 1

    39/168

    Start-up 39

    Note: With ACSM1, ACQ810, ACS850 and ACS880, when using the ODVAAC/DC drive or ABB Drives profile, make sure that drive parameter 50.04 FBAREF MODESEL is set to SPEED. With ACSM1, ACS850 and ACS880, makesure that 50.05 FBA REF2 MODESEL is set to TORQUE.

    For alternative values, see columnOutputinstance in the table describing parameter06OUTPUT INSTANCE.

    07 OUTPUT NUMPARS

    Some assembly instances support transferringdrive parameter values between the I/Oscanner and drive. Parameters 07OUTPUTNUM PARSand 09INPUT NUM PARS specifyhow many drive parameter values should be

    included in the respective assembly instance.Changing the numbers of the drive parametersto values other than the defaults also changesthe lengths of the associated assemblyinstances. This requires manual changes toeither the EDS file or I/O scanner configuration.Before changing these parameters, consult

    Appendix A Varying the number of driveparameters.Note: This parameter is only used when the

    output assembly instance is 120, 121, 122, 123,901, 902, 911, 912, 921, 922. It must always beset to the default, 10, except as described in

    Appendix A Varying the number of driveparameters

    10

    ACS355:FB PAR 7

    ACSM1:FBA PAR7

    ACS850/ACQ810:FBA par7

    ACS880:Output num pars

    110 Number or drive parameter values to beincluded in the assembly instance

    No. Name/Value Description Default

    Input

    ODVA

    (70-73; 170-173)

    ABB DRIVES

    (851-852; 951-952

    TRANSPARENT16

    (861-862; 961-962)

    TRANSPARENT32

    (871-872; 971-972)

    Output

    ODVA

    (20-23; 120-123)x

    ABB DRIVES

    (801-802; 901-902)x

    TRANSPARENT16

    (811-812; 911-912)x

    TRANSPARENT32

    (821-822; 921-922)

    x

  • 7/28/2019 FDNA-01 1

    40/168

    40 Start-up

    08 INPUT INSTANCE Configures the input assembly instances usedby the adapter module. See parameter06OUTPUT INSTANCE.

    70

    ACS355:FB PAR 9

    ACSM1:FBA PAR9

    ACS850/ACQ810:FBA par9

    ACS880:Input instance

    For alternative values, see parameter06OUTPUT INSTANCE.

    09 INPUT NUM

    PARS

    See parameter07OUTPUT NUM PARS.

    Note: This parameter is only used when theinput assembly instance is 170, 171, 172, 173,951, 952, 961, 962, 971, 972. It must always beset to the default, 10, except as described in

    Appendix A Varying the number of driveparameters.

    10

    ACS355:FB PAR 9

    ACSM1:FBA PAR9

    ACS850/ACQ810:FBA par9

    ACS880:Input num pars

    110 Number or drive parameter values to beincluded in the assembly instance

    No. Name/Value Description Default

  • 7/28/2019 FDNA-01 1

    41/168

    Start-up 41

    10 ODVA SPEEDSCALE

    Defines the speed scale in the ODVA AC/DCdrive profile. Units of reference and actualspeeds for the ODVA AC/DC drive profile aregiven by the formula below. No effect on the

    ABB Drives profiles.Note: While a wide range of resolutions may beconfigured, the actual performance is limited tothe performance capabilities of the drive.

    Speed unit = RPM X 2(-1 X ODVA speed scale value)

    128

    ACS355:FB PAR 10

    ACSM1:FBA PAR10

    ACS850/ACQ810:FBA par10

    ACS880:ODVA speed scale

    Table below shows how the values of driveparameter ODVA SPEED SCALE correspondto the ODVA Speed Scale units.

    123133 Speed scale value of the drive parameter

    No. Name/Value Description Default

    ODVA speed scale value1) Speed scale value ofdrive parameter2)

    Unit

    -5 123 32 RPM

    -4 124 16 RPM

    -3 125 8 RPM

    -2 126 4 RPM

    -1 127 2 RPM

    0 (default) 128 1 RPM

    1 129 0.5 RPM

    2 130 0.25 RPM

    3 131 0.125 RPM

    4 132 0.0625 RPM

    5 133 0.03125 RPM

    1) Use the ODVA speed scale value when reading/writing parameterODVASPEED SCALEviaAC/DC-drive object, class 2Ah. When written via the

    AC/DC drive object, the new value takes effect immediately.2) Use the speed scale value of the drive parameter when reading/writingparameterODVA SPEED SCALEvia the drive control panel, Drive parameterobject, Class 90h and Fieldbus configuration object 91h. When written viathese methods, the new value takes effect after the drive is repowered or aFieldbus Adapter Parameter refresh is given.

  • 7/28/2019 FDNA-01 1

    42/168

    42 Start-up

    11 ODVA TORQUESCALE

    Defines the torque scale in the ODVA AC/DCdrive profile. Units of reference and actualtorques for the ODVA AC/DC drive profile aregiven by the formula below. No effect on the

    ABB Drives profiles.Note: While a wide range of resolutions may beconfigured, the actual performance is limited tothe performance capabilities of the drive.(Nm = Newton x Meter)

    Torque unit = Nm x 2(-1 X ODVA torque scale)

    128

    ACS355:FB PAR 11

    ACSM1:FBA PAR11

    ACS850/ACQ810:FBA par11

    ACS880:ODVA torquescale

    Table below shows how the values of driveparameter ODVA TORQUE SCALE correspondto the ODVA Torque Scale units.

    123133 Torque scale value of the drive parameter

    1225

    Reserved Not used by the adapter module. N/A

    No. Name/Value Description Default

    ODVA torque scale value1) Torque scale value ofdrive parameter2)

    Unit

    -5 123 32 Nm

    -4 124 16 Nm

    -3 125 8 Nm

    -2 126 4 Nm

    -1 127 2 Nm

    0 (default) 128 1 Nm

    1 129 0.5 Nm

    2 130 0.25 Nm

    3 131 0.125 Nm

    4 132 0.0625 Nm

    5 133 0.03125 Nm

    1) Use the ODVA torque scale value when reading/writing parameterODVA

    TORQUE SCALEviaAC/DC-drive object, class 2Ah. When written via theAC/DC drive object, the new value takes effect immediately.2) Use the torque scale value of the drive parameter when reading/writingparameterODVA TORQUE SCALEvia the drive control panel, Drive

    parameter object, Class 90hand Fieldbus configuration object 91h. Whenwritten via these methods, the new value takes effect after the drive isrepowered or a Fieldbus Adapter Parameter refresh is given.

  • 7/28/2019 FDNA-01 1

    43/168

    Start-up 43

    26 UNRECOVER-ABLE ERROR

    Read-only. Shows information about the causeof an unrecoverable error in the adaptermodule. Bit field parameter, that is, severalstatus bits can be set at a time. Value 0

    indicates that there are no errors.

    0

    ACS355:FB PAR 26

    ACSM1:FBA PAR26

    ACS850/ACQ810:FBA par26

    ACS880:Unrecover. error

    065535 Active unrecoverable errors

    27 FBA PARREFRESH

    Validates any changed adapter moduleconfiguration parameter settings. Afterrefreshing, the value reverts automatically to0 = Done.Note: This parameter cannot be changed while

    the drive is running.

    0 = Done

    ACS355/ACSM1:FBA PARREFRESH

    ACS850/ACQ810/ACS880:FBA par refresh

    0 = Done Refreshing done

    1 =Refresh/Configure

    Refreshing

    No. Name/Value Description Default

    Bit Name Value Description

    1 DUP_MAC_ERROR 0x0001 Duplicate MAC ID error

    2 RX_QUEUE_OVERRUN 0x0002 Message receive queue is full.3 TX_QUEUE_OVERRUN 0x0004 Message transmit queue is full.

    4 IO_SEND_ERROR 0x0008 Transmitting I/O data has failed.

    5 CAN_BUS_OFF 0x0010 Bus-off is detected.

    6 CAN_OVERRUN 0x0020 CAN message was lost.

    7 DNS_RESET 0x0040 DeviceNet driver of the module isreset.

    8 DNS_BUS_SENSE_ERROR 0x0080 No voltage detected in thenetwork.

    9 DNS_SWITCH_ERROR 0x0100 DeviceNet driver reset failed due

    to an invalid MAC ID or baud rate.13 SYS_FILE_ERR 0x1000 Initialization with the drive failed.

  • 7/28/2019 FDNA-01 1

    44/168

    44 Start-up

    28 PAR TABLE VER Read-only. Displays the parameter tablerevision of the fieldbus adapter modulemapping file stored in the memory of the drive.In format xyz, where

    x = major revision numbery = minor revision numberz = correction numberORin format axyz, wherea = major revision numberxy = minor revision numbersz = correction number or letter.

    N/A

    ACS355:FILE CPI FW REV

    ACSM1:PAR TABLE VER

    ACS850/ACQ810/ACS880:Par table ver

    0x00000xFFFF Parameter table revision

    29 DRIVE TYPECODE

    Read-only. Displays the drive type code of thefieldbus adapter module mapping file stored inthe memory of the drive.

    N/A

    ACS355:FILE CONFIG ID

    ACSM1:DRIVE TYPECODE

    ACS850/ACQ810/ACS880:Drive type code

    065535 Drive type code of the fieldbus adapter modulemapping file

    30 MAPPING FILEVER

    Read-only. Displays the fieldbus adaptermodule mapping file revision stored in thememory of the drive in decimal format.Example: 0x107 = revision 1.07.

    N/A

    ACS355:FILE CONFIGREV

    ACSM1:

    MAPPING FILEVER

    ACS850/ACQ810/ACS880:Mapping file ver

    065535 Mapping file revision

    No. Name/Value Description Default

  • 7/28/2019 FDNA-01 1

    45/168

    Start-up 45

    31 D2FBA COMMSTA

    Read-only. Displays the status of the fieldbusadapter module communication.Note: The value names may vary by drive.

    0 = Idle

    ACS355:FBA STATUS

    ACSM1:D2FBA COMMSTA

    ACS850/ACQ810/ACS880:D2FBA comm sta

    0 = Idle Adapter is not configured.

    1 = Exec.init Adapter is initializing.

    2 = Time out Time-out has occurred in the communicationbetween the adapter and the drive.

    3 = Conf.err Adapter configuration error: Major or minorrevision code of the common program revisionin the fieldbus adapter module is not therevision required by the module or mapping fileupload has failed more than three times.

    4 = Off-line Adapter is off-line.

    5 = On-line Adapter is on-line.

    6 = Reset Adapter is performing a hardware reset.

    32 FBA COMM SWVER

    Read-only. Displays the common programrevision of the adapter module in format axyz,where:a = major revision numberxy = minor revision numbersz = correction number or letter.Example: 190A = revision 1.90A

    N/A

    ACS355:FBA CPI FW REV

    ACSM1:FBA COMM SWVER

    ACS850/ACQ810/ACS880:FBA comm SWver

    0x00000xFFFF Common program version of the adaptermodule

    No. Name/Value Description Default

  • 7/28/2019 FDNA-01 1

    46/168

    46 Start-up

    33 FBA APPL SWVER

    Read-only. Displays the application programrevision of the adapter module in format axyz,where:a = major revision number

    xy = minor revision numbersz = correction number or letter.Example: 190A = revision 1.90A

    N/A

    ACS355:FBA CPI APPLREV

    ACSM1:FBA COMM APPLVER

    ACS850/ACQ810/ACS880:FBA appl SW ver

    0x00000xFFFF Application program revision of the adaptermodule

    No. Name/Value Description Default

  • 7/28/2019 FDNA-01 1

    47/168

    Start-up 47

    FDNA-01 configuration parameters group B (group 2)

    Note: The actual parameter group number depends on the drivetype. Group B (group 2) corresponds to:

    parameter group 55 in ACS355

    parameter group 53 in ACSM1, ACS850 and ACQ810

    parameter group 53 in ACS880 if the adapter is installed asfieldbus adapter A or group 56 if the adapter is installed as

    fieldbus adapter B.

    No.1) Name/Value Description Default

    01 DATA OUT 1(master to drive)

    In the output assembly instances that includedrive parameters, this parameter specifies

    which parameters value is placed in locationDATA OUT 1 value received by the drive fromthe DeviceNet network. Content is defined by adecimal number in the range of 0 to 9999 asfollows:

    0

    ACS355:FBA DATA OUT 1

    ACSM1:FBA DATA OUT1

    ACS850/ACQ810/ACS880:FBA data out1

    Note: The FDNA-01 configuration parametersare 16-bit parameters. If the mapped parameteris a 32-bit parameter, it automatically reservestwo consecutive parameters. For example,mapping a 32-bit parameter to parameter no. 1also reserves parameter no. 2.

    0 Not used

    1019999 Parameter index with format xxyy, where xx isthe parameter group number (199) and yy isthe parameter number index within that group(0199).

    0210

    DATA OUT 2DATA OUT 10

    See parameterDATA OUT 1. 0

    1) The number of parameters in this group may vary by drive type and drive firmware.

    0 Not used

    199 Virtual address area of drive control.Not used with the FDNA-01 module.

    1019999

    Parameter area of the drive

  • 7/28/2019 FDNA-01 1

    48/168

    48 Start-up

    FDNA-01 configuration parameters group C (group 3)

    Note: The actual parameter group number depends on the drivetype. Group C (group 3) corresponds to:

    parameter group 54 in ACS355

    parameter group 52 in ACSM1, ACS850 and ACQ810

    parameter group 52 in ACS880 if the adapter is installed asfieldbus adapter A or group 55 if the adapter is installed as

    fieldbus adapter B.

    No.1) Name/Value Description Default

    01 DATA IN 1(drive to master)

    In input assembly instances that include driveparameters, this parameter specifies which

    parameters value is placed in location DATA IN1 value sent by the drive to the DeviceNetnetwork. Content is defined by a decimalnumber in the range of 0 to 9999 as follows:

    0

    ACS355:FBA DATA IN 1

    ACSM1:FBA DATA IN1

    ACS850/ACQ810/ACS880:FBA data in1

    Note: The FDNA-01 configuration parametersare 16-bit parameters. If the mapped parameteris a 32-bit parameter, it automatically reservestwo consecutive parameters. For example,mapping a 32-bit parameter to parameter no. 1also reserves parameter no. 2.

    0 Not used

    1019999 Parameter index with format xxyy, where xx isthe parameter group number (199) and yy is

    the parameter number index within that group(0199).

    0210

    DATA IN 2DATA IN 10

    See parameterDATA IN 1. 0

    1) The number of parameters in this group may vary by drive type and drive firmware.

    0 Not used

    199 Virtual address area of drive control.Not used with the FDNA-01 module.

    1019999

    Parameter area of the drive

  • 7/28/2019 FDNA-01 1

    49/168

    Start-up 49

    Control locations

    ABB drives can receive control information from multiple sourcesincluding digital inputs, analog inputs, the drive control panel and acommunication module (for example, the adapter module). ABB

    drives allow the user to separately determine the source for eachtype of control information (Start, Stop, Direction, Reference, FaultReset, and so on).

    To give the fieldbus master station the most complete control overthe drive, the communication module must be selected as thesource for this information. The parameter setting examples belowcontain the drive control parameters needed in the examples. Fora complete parameter list, see the drive documentation.

    Starting up ACS355 drives

    1. Power up the drive.

    2. Enable the communication between the adapter module and

    the drive by setting parameter 9802 COMM PROT SEL to EXT

    FBA.

    3. Set the FDNA-01 configuration parameters in parameter group51.

    At the minimum, set the required number in parameter 5102

    MAC ID and the required baud rate in 5103 BAUD RATE. In

    addition, select the communication profile in 5104 DRIVE

    PROFILE. With the ODVA AC/DC drive profile select the way

    in which the motor is stopped in 5105 ODVA STOP FUNC.

    4. Define the process data transferred to and from the drive inFDNA-01 parameter groups 54 and 55.

    Note: If communication between the FDNA-01 and DeviceNet

    master is established, changes to the configuration parameters

    can be done also through Fieldbus configuration object 91h.

    5. Validate the settings made in parameter group 51 by setting

    parameter 5127 FBA PAR REFRESH to REFRESH.

  • 7/28/2019 FDNA-01 1

    50/168

    50 Start-up

    6. Set the relevant drive control parameters to control the drive

    according to the application. Examples of appropriate values

    are shown in the tables below.

    Parameter setting examples ACS355

    ABB Drives profile

    This example shows how to configure the ACS355 drive to use theABB Drives profile with set speed and set torque plus driveparameters assembly.

    The used I/O assembly instances are 902 and 952.

    The table below gives the recommended drive parameter settings.Drive parameter Setting for

    ACS355 drivesDescription

    9802 COMM PROT SEL 4 = EXT FBA Enables communication betweendrive and adapter module.

    5101 FBA TYPE DEVICENET1) Displays the type of the adaptermodule.

    5102 FB PAR 2(MAC ID) 2 Defines the MAC ID number of theadapter module.

    5103 FB PAR 3(BAUD RATE)

    0 (= 125 kbit/s) Sets the baud rate for theDeviceNet interface.

    5104 FB PAR 4(DRIVE PROFILE)

    0 (= DCU Profile) Selects the profile used in thecommunication between drive andadapter module.

    5105 FB PAR 5(ODVA STOP FUNC)

    0 (= Ramp) Motor decelerates along the activedeceleration ramp.

    5106 FB PAR 6(OUTPUT INSTANCE)

    902 Selects the ABB Drives profile withspeed and torque plus driveparameters output instance.

    5107 FB PAR 7(OUTPUT NUM PARS)

    10 Must always be set to 10, except asprovided inAppendix A Varyingthe number of drive parameters.

    5108 FB PAR 8(INPUT INSTANCE)

    952 Selects the ABB Drives profile withspeed and torque plus driveparameters input instance.

  • 7/28/2019 FDNA-01 1

    51/168

    Start-up 51

    5109 FB PAR 9(INPUT NUM PARS)

    10 Must always be set to 10, except asprovided inAppendix A Varyingthe number of drive parameters.

    5110 FB PAR 10(ODVA SPEED SCALE)

    128 Sets the scaling as 1 rpm for theODVA speed reference.

    5111 FB PAR 11(ODVA TORQUE SCALE)

    128 Sets the scaling as 1 Nm for theODVA torque reference.

    5401 FBA DATA IN 1 104 Current

    5402 FBA DATA IN 2 107 DC bus voltage

    5403 FB DATA IN 3

    5410 DATA IN 10

    0

    5501 FBA DATA OUT 1 2205 Acceleration time 2

    5502 FBA DATA OUT 2 2206 Deceleration time 2

    5503 FB DATA OUT 35510 DATA OUT 10

    0

    51.27 FBA PAR REFRESH 1 = REFRESH Validates the FDNA-01configuration parameter settings.

    1001 EXT1 COMMANDS 10 = COMM Selects the fieldbus interface as thesource of the start and stopcommands for external controllocation 1.

    1003 DIRECTION 3 = REQUEST Allows control of rotation direction.

    1103 REF1 SELECT 8 = COMM Selects the fieldbus reference 1 asthe source for speed reference.

    1604 FAULT RESET SEL 8 = COMM Selects the fieldbus interface as the

    source for the fault reset signal.

    9904 MOTOR CTRL MODE 2 = VECTOR:TORQ

    Selects the vector control mode asthe motor control mode.

    1002 EXT2 COMMANDS 10 = COMM Selects the fieldbus interface as thesource of the start and stopcommands for external controllocation 2.

    1102 EXT1/EXT2 SEL 8 = COMM Enables external control location1/2 selection through the fieldbus.

    1106 REF2 SELECT 8 = COMM Selects the fieldbus reference 2 asthe source for torque reference.

    Drive parameter Setting for ACS355 drives

    Description

  • 7/28/2019 FDNA-01 1

    52/168

    52 Start-up

    The start sequence for the parameter example above is givenbelow.

    Control word:

    47Eh (1150 decimal) > READY TO SWITCH ON

    47Fh (1151 decimal) > OPERATING (Speed mode)

    or

    C7Fh (3199 decimal) > OPERATING (Torque mode).

    ODVA AC/DC drive profile

    The following example shows how to configure the ACS355 driveto use the Extended speed and torque control assembly of theODVA AC/DC drive profile.

    The used I/O assembly instances are 23 and 73.

    The table below gives the recommended drive parameter settings.

    1601 RUN ENABLE 7 = COMM Selects the fieldbus interface as thesource for the inverted Run enablesignal (Run disable).

    1) Read-only or automatically detected/set

    Drive parameter Setting for ACS355 drives

    Description

    9802 COMM PROT SEL 4 = EXT FBA Enables communication betweendrive and adapter module.

    5101 FBA TYPE DEVICENET1)

    Displays the type of the adaptermodule.

    5102 FB PAR 2(MAC ID)

    5 Defines the MAC ID number of theadapter module.

    5103 FB PAR 3(BAUD RATE)

    0 (= 125 kbit/s) Sets the baud rate for theDeviceNet interface.

    5104 FB PAR 4(DRIVE PROFILE)

    0 (= DCU Profile) Selects the profile used in thecommunication between drive andadapter module.

    5105 FB PAR 5(ODVA STOP FUNC)

    0 (= Ramp) Motor decelerates along the activedeceleration ramp.

    Drive parameter Setting for ACS355 drives

    Description

  • 7/28/2019 FDNA-01 1

    53/168

    Start-up 53

    5106 FB PAR 6(OUTPUT INSTANCE)

    23 Selects the ODVA extended speedand torque control output instance.

    5108 FB PAR 8(INPUT INSTANCE)

    73 Selects the ODVA extended speedand torque control input instance.

    5110 FB PAR 10(ODVA SPEED SCALE)

    128 Sets the scaling as 1 rpm for theODVA speed reference.

    5111 FB PAR 11(ODVA TORQUE SCALE)

    128 Sets the scaling as 1 Nm for theODVA torque reference.

    51.27 FBA PAR REFRESH 1 = REFRESH Validates the FDNA-01configuration parameter settings.

    1001 EXT1 COMMANDS 10 = COMM Selects the fieldbus interface asthe source of the start and stopcommands for external controllocation 1.

    1003 DIRECTION 3 = REQUEST Allows control of rotation direction.

    1103 REF1 SELECT 8 = COMM Selects the fieldbus reference 1 asthe source for speed reference.

    1604 FAULT RESET SEL 8 = COMM Selects the fieldbus interface as

    the source for the fault resetsignal.

    9904 MOTOR CTRL MODE 2 = VECTOR:TORQ

    Selects the vector control mode asthe motor control mode.

    1002 EXT2 COMMANDS 10 = COMM Selects the fieldbus interface asthe source of the start and stopcommands for external controllocation 2.

    1102 EXT1/EXT2 SEL 1 = DI1 Selects digital input DI1 as thesource for the external controllocation EXT1/EXT2 selection.

    1106 REF2 SELECT 8 = COMM Selects the fieldbus reference 2 asthe source for torque reference.

    1601 RUN ENABLE 7 = COMM Selects the fieldbus interface asthe source for the inverted Runenable signal (Run disable).

    1) Read-only or automatically detected/set

    Drive parameter Setting for ACS355 drives

    Description

  • 7/28/2019 FDNA-01 1

    54/168

    54 Start-up

    Note: In this example, digital input DI1 has been configured tocontrol whether to use the speed or torque control mode.

    The start sequence for the parameter example above is givenbelow.

    Control word: 0h (0 decimal) > READY

    1h (1 decimal) > ENABLED (Running forward)

    2h (2 decimal) > ENABLED (Running reverse)

    Starting up ACSM1 drives

    1. Power up the drive.2. Enable the communication between the adapter module and

    the drive by setting parameter 50.01 FBA ENABLE to Enable.

    3. Ensure that 50.04 FBA REF1 MODESEL is set to Speed and

    50.05 FBA REF2 MODESEL is set to Torque.

    4. Set the FDNA-01 configuration parameters in parameter group

    51.

    5. Define the process data transferred to and from the drive in

    FDNA-01 parameter groups 52 and 53.

    Note: If communication between the FDNA-01 and DeviceNet

    master is established, changes to the configuration parameters

    can be done also through Fieldbus configuration object 91h.

    6. Validate the settings made in parameter groups 51, 52 and 53by setting parameter 51.27 FBA PAR REFRESH to REFRESH.

    7. Set the relevant drive control parameters to control the drive

    according to the application. Examples of appropriate values

    are shown in the tables below.

  • 7/28/2019 FDNA-01 1

    55/168

    Start-up 55

    Parameter setting examples ACSM1

    ABB Drives profile

    The following example shows how to configure the ACSM1 drive to

    use the ABB Drives profile.

    The used I/O assembly instances are 902 and 952.

    The table below gives the recommended drive parameter settings.

    Drive parameter Setting for ACSM1 drives

    Description

    50.01 FBA ENABLE 1 = Enable Enables communication betweendrive and adapter module.

    50.04 FBA REF1MODESEL

    Speed Selects speed as the adapter module REF1 type.

    50.05 FBA REF2MODESEL

    Torque Selects torque as the adapter module REF2 type.

    51.01 FBA TYPE DEVICENET1) Displays the type of the adaptermodule.

    51.02 FBA PAR2

    (MAC ID)

    6 Defines the MAC ID number of the

    adapter module.51.03 FBA PAR3(BAUD RATE)

    0 (= 125 kbit/s) Sets the baud rate for the DeviceNetinterface.

    51.06 FBA PAR6(OUTPUT INSTANCE)

    902 Selects the ABB Drives profile withspeed and torque plus driveparameters output instance.

    51.07 FBA PAR7(OUTPUT NUM PARS)

    10 Must always be set to 10, except asprovided inAppendix A Varyingthe number of drive parameters.

    51.08 FBA PAR8(INPUT INSTANCE)

    952 Selects the ABB Drives profile withspeed and torque plus driveparameters input instance.

    51.09 FBA PAR9(INPUT NUM PARS)

    10 Must always be set to 10, except asprovided inAppendix A Varyingthe number of drive parameters.

    52.01 FBA DATA IN1 117 Motor temp

    52.02 FBA DATA IN2 104 Motor current - MSW

    52.03 FBA DATA IN3 0 Motor current - LSW

    52.04 FBA DATA IN4 107 DC voltage - MSW

  • 7/28/2019 FDNA-01 1

    56/168

    56 Start-up

    52.05 FBA DATA IN5 0 DC voltage - LSW

    52.06 FBA DATA IN6 108 Encoder 1 speed - MSW

    52.07 FBA DATA IN7 0 Encoder 1 speed - LSW

    52.08 FBA DATA IN852.10 FBA DATA IN10

    0

    53.01 FBA DATA OUT1 2503 Acceleration time - MSW

    53.02 FBA DATA OUT2 0 Acceleration time - LSW

    53.03 FBA DATA OUT3 2504 Deceleration time - MSW

    53.04 FBA DATA OUT4 0 Deceleration time - LSW

    53.05 FBA DATA OUT5 2408 Constant speed

    53.06 FBA DATA OUT6 2410 Speed ref jog1

    53.07 FBA DATA OUT7 2411 Speed ref jog2

    53.08 FBA DATA OUT853.10 FBA DATA OUT10

    0

    51.27 FBA PAR REFRESH 1 = REFRESH Validates the FDNA-01 configurationparameter settings.

    10.01 EXT1 START FUNC 3 = FBA Selects the fieldbus interface as thesource of the start and stopcommands for external controllocation 1.

    10.04 EXT2 START FUNC 3 = FBA Selects the fieldbus interface as thesource of the start and stopcommands for external controllocation 2.

    24.01 SPEED REF1 SEL 3 = FBA REF1 Selects the fieldbus reference 1 as

    the source for speed reference 1.

    32.01 TORQ REF1 SEL 4 = FBA REF2 Selects the fieldbus reference 2 asthe source for torque reference 1.

    34.02 EXT1 MODE 1/2SEL P.2.12.15 =P.FBA MAINCW.15

    Selects FBA Control word bit 15 asthe source for the external controllocation EXT1/EXT2 selection.

    34.03 EXT1 CTRL MODE1 1 = Speed Selects speed as the control modefor external control location 1.

    34.05 EXT2 CTRL MODE1 2 =Torque Selects torque as the control modefor external control location 2.

    Drive parameter Setting for ACSM1 drives

    Description

  • 7/28/2019 FDNA-01 1

    57/168

    Start-up 57

    The start sequence for the parameter example above is givenbelow.

    Control word:

    47Eh (1150 decimal) > READY TO SWITCH ON

    47Fh (1151 decimal) > OPERATING (Speed mode)

    orC7Fh (3199 decimal) > OPERATING (Torque mode).

    ODVA AC/DC drive profile

    The following example shows how to configure the ACSM1 drive touse the ODVA AC/DC drive profile.

    The used I/O assembly instances are 23 and 73.

    The table below gives the recommended drive parameter settings.

    99.05 MOTOR CTRLMODE

    0 = DTC Selects DTC as the motor controlmode.

    1) Read-only or automatically detected/set

    Drive parameter Setting for ACSM1 drives

    Description

    50.01 FBA ENABLE 1 = Enable Enables communication betweendrive and adapter module.

    50.04 FBA REF1MODESEL

    Speed Selects speed as the adapter module REF1 type.

    50.05 FBA REF2MODESEL

    Torque Selects torque as the adapter module REF2 type.

    51.01 FBA TYPE DEVICENET1 Displays the type of the adaptermodule.

    51.02 FBA PAR2(MAC ID)

    5 Defines the MAC ID number of theadapter module.

    51.03 FBA PAR3(BAUD RATE)

    0 (= 125 kbit/s) Sets the baud rate for the DeviceNetinterface.

    51.06 FBA PAR6(OUTPUT INSTANCE)

    23 Selects the ODVA extended speedand torque control output instance.

    Drive parameter Setting for ACSM1 drives

    Description

  • 7/28/2019 FDNA-01 1

    58/168

    58 Start-up

    Note: In this example, digital input DI1 has been configured tocontrol whether to use the speed or torque control mode.

    The start sequence for the parameter example above is givenbelow.

    Control word:

    0h (0 decimal) > READY

    1h (1 decimal) > ENABLED (Running forward)

    2h (2 decimal) > ENABLED (Running reverse)

    51.08 FBA PAR8(INPUT INSTANCE)

    73 Selects the ODVA extended speedand torque control input instance.

    51.27 FBA PAR REFRESH 1 = REFRESH Validates the FDNA-01 configurationparameter settings.

    10.01 EXT1 START FUNC 3 = FBA Selects the fieldbus interface as thesource of the start and stopcommands for external controllocation 1.

    10.04 EXT2 START FUNC 3 = FBA Selects the fieldbus interface as thesource of the start and stopcommands for external control

    location 2

    24.01 SPEED REF1 SEL 3 = FBA REF1 Selects the fieldbus reference 1 asthe source for speed reference 1.

    32.01 TORQ REF1 SEL 4 = FBA REF2 Selects the fieldbus reference 2 asthe source for torque reference 1.

    34.01 EXT1/EXT2 SEL P.2.1.0 = PI.DISTATUS.0

    Selects digital input DI1 as thesource for the external controllocation EXT1/EXT2 selection.

    34.03 EXT1 CTRL MODE1 1 = Speed Selects speed as the control modefor external control location 1.

    34.05 EXT2 CTRL MODE1 2 =Torque Selects torque as the control modefor external control location 2.

    99.05 MOTOR CTRLMODE

    0 = DTC Selects DTC as the motor controlmode.

    1) Read-only or automatically detected/set

    Drive parameter Setting for ACSM1 drives

    Description

  • 7/28/2019 FDNA-01 1

    59/168

    Start-up 59

    Starting up ACS850 and ACQ810 drives

    1. Power up the drive.

    2. Enable the communication between the adapter module and

    the drive by setting parameter 50.01 Fba enable to Enable.

    3. Ensure that 50.04 Fb ref1 modesel is set to Speed (both

    ACS850 and ACQ810) and 50.05 Fb ref2 modesel is set to

    Torque (only ACS850).

    4. Set the FDNA-01 configuration parameters in drive parameter

    group 51.

    5. Define the process data transferred to and from the drive inFDNA-01 parameter groups 52 and 53.

    Note: If communication between the FDNA-01 and DeviceNet

    master is established, changes to the configuration parameters

    can be done also through Fieldbus configuration object 91h.

    6. Validate the settings made in parameter groups 51, 52 and 53

    by setting parameter 51.27 FBA par refresh to Refresh.

    7. Set the relevant drive control parameters to control the drive

    according to the application. Examples of appropriate values

    are shown in the tables below.

  • 7/28/2019 FDNA-01 1

    60/168

    60 Start-up

    Parameter setting examples ACS850 and ACQ810

    ABB Drives profile

    The following example shows how to configure the ACS850 or

    ACQ810 drive to use the ABB Drives profile.

    The used I/O assembly instances are 902 and 952.

    The table below gives the recommended drive parameter settings.

    Drive parameter Setting for ACS850/ACQ810drives

    Description

    50.01 Fba enable 1 = Enable Enables communication between

    drive and adapter module.

    50.04 Fb ref1 modesel Speed Selects speed as the adapter module ref1 type.

    50.05 Fb ref2 modesel Torque Selects torque as the adapter module ref2 type (only with

    ACS850).

    51.01 Fba type DEVICENET1) Displays the type of the adaptermodule.

    51.02 FBA par2(MAC ID)

    5 Defines the MAC ID number of theadapter module.

    51.03 FBA par3(BAUD RATE)

    0 (= 125 kbit/s) Sets the baud rate for theDeviceNet interface.

    51.06 FBA par6(OUTPUT INSTANCE)

    902 Selects the ABB Drives profile withspeed and torque plus driveparameters output instance.

    51.07 FBA par7

    (OUTPUT NUM PARS)

    10 Must always be set to 10, except as

    provided inAppendix A Varyingthe number of drive parameters.

    51.08 FBA par8(INPUT INSTANCE)

    952 Selects the ABB Drives profile withspeed and torque plus driveparameters input instance.

    51.09 FBA par9(INPUT NUM PARS)

    10 Must always be set to 10, except asprovided inAppendix A Varyingthe number of drive parameters.

    52.01 FBA data in1 123 Motor power 52.02 FBA data in2 0 Motor power - LSW

  • 7/28/2019 FDNA-01 1

    61/168

    Start-up 61

    52.03 FBA data in3 105 Motor current percent

    52.04 FBA data in4 107 DC voltage

    52.05 FBA data in5 0 DC voltage - LSW

    52.06 FBA data in6 108 Encoder1 speed

    52.07 FBA data in7 0 Encoder 1 speed - LSW

    52.08 FBA data in852.10 FBA data in10

    0

    53.01 FBA data out1 2204 Acc time 2

    53.02 FBA data out2 0 Acceleration time 2 - LSW

    53.03 FBA data out3 2205 Dec time 2

    53.04 FBA data out4 0 Deceleration time 2 - LSW

    53.05 FBA data out5 2606 Const speed1

    53.06 FBA data out6 2607 Const speed2

    53.07 FBA data out7 2608 Const speed3

    53.08 FBA data out853.10 FBA data out10

    0

    51.27 FBA par refresh 1 = Refresh Validates the FDNA-01configuration parameter settings.

    10.01 Ext1 start func FB Selects the fieldbus interface as thesource of the start and stopcommands for external controllocation 1.

    10.04 Ext2 Start func 3 = FB Selects the fieldbus as the source

    for start and stop commands forexternal control location EXT2 (onlywith ACS850).

    12.01 Ext1/Ext sel P.2.22.15 = P.FBAmain cw.15

    Selects FBA Control word bit 15 asthe source for external controllocation EXT1/EXT2 selection (onlywith ACS850).

    12.03 Ext1 ctrl mode 1 = Speed Selects speed as the operatingmode for external control locationEXT1.

    Drive parameter Setting for ACS850/ACQ810drives

    Description

  • 7/28/2019 FDNA-01 1

    62/168

    62 Start-up

    The start sequence for the parameter example above is givenbelow.

    Control word:

    47Eh (1150 decimal) > READY TO SWITCH ON

    47Fh (1151 decimal) > OPERATING (Speed mode)or

    C7Fh (3199 decimal) > OPERATING (Torque mode in

    ACS850).

    12.05 Ext2 ctrl mode 2 = Torque Selects torque as the operatingmode for external control location

    EXT2 (only with ACS850).

    16.15 Menu set sel(ACS850)16.21 Menu selection(ACQ810)

    2 = Load long(ACS850)2= Full (ACQ810)

    Load long parameter list. Allparameters will be displayed.

    21.01 Speed ref1 sel FB Selects the fieldbus reference 1 asthe source for speed reference 1.

    24.01 Torq ref1 sel FBA ref2 Selects fieldbus reference 2 as thesource of the torque reference 1

    (only with ACS850).1) Read-only or automatically detected/set

    Drive parameter Setting for ACS850/ACQ810drives

    Description

  • 7/28/2019 FDNA-01 1

    63/168

    Start-up 63

    ODVA AC/DC drive profile

    The following example shows how to configure the ACS850 orACQ810 drive to use the ODVA AC/DC drive profile.

    The used I/O assembly instances are 23 and 73.

    The table below gives the recommended drive parameter settings.

    Drive parameter Setting for ACS850/ACQ810drives

    Description

    50.01 Fba enable 1 = Enable Enables communication betweendrive and adapter module.

    50.04 Fb ref1 modesel Speed Selects speed as the adapter

    module ref1 type.

    50.05 Fb ref2 modesel Torque Selects torque as the adapter module ref2 type (only with

    ACS850).

    51.01 FBA type DEVICENET1) Displays the type of the adaptermodule.

    51.02 FBA par2(MAC ID)

    5 Defines the MAC ID number of theadapter module.

    51.03 FBA par3(BAUD RATE)

    0 (= 125 kbit/s) Sets the baud rate for theDeviceNet interface.

    51.06 FBA par6(OUTPUT INSTANCE)

    23 Selects the ODVA AC/DC driveprofile output instance.

    51.08 FBA par8(INPUT INSTANCE)

    73 Selects the ODVA AC/DC profileinput instance.

    51.27 FBA par refresh 1 = Refresh Validates the FDNA-01configuration parameter settings.

    10.01 Ext1 start func 3 = FB Selects the fieldbus interface as thesource of the start and stopcommands for external controllocation 1.

    10.04 Ext2 Start func 3 = FB Selects the fieldbus as the sourcefor start and stop commands forexternal control location EXT2 (onlywith ACS850).

  • 7/28/2019 FDNA-01 1

    64/168

    64 Start-up

    Note: For ACS850 in this example, digital input DI1 has been

    configured to control whether to use the speed or torque controlmode.

    The start sequence for the parameter example above is givenbelow.

    Control word:

    0h (0 decimal) > READY

    1h (1 decimal) > ENABLED (Running forward)

    2h (2 decimal) > ENABLED (Running reverse)

    12.01 Ext1/Ext2 sel DI1 Selects digital input DI1 as thesource for external control location

    EXT1/EXT2 selection (only withACS850).

    12.05 Ext2 ctrl mode 2 = Torque Selects torque as the operatingmode for external control locationEXT2 (only with ACS850).

    16.15 Menu set sel(ACS850)16.21 Menu selection(ACQ810)

    2 = Load long(ACS850)1= Full (ACQ810)

    Load long parameter list. Allparameters will be displayed.

    21.01 Speed ref1 sel FBA ref1 Selects the fieldbus reference 1 asthe source for speed reference 1.

    24.01 Torq ref1 sel FBA ref2 Selects fieldbus reference 2 as thesource of the torque reference 1(only with ACS850).

    1) Read-only or automatically detected/set

    Drive parameter Setting for ACS850/ACQ810drives

    Description

  • 7/28/2019 FDNA-01 1

    65/168

    Start-up 65

    Starting up ACS880 drives

    This example sets up the fieldbus adapter installed as fieldbusadapter A. To set up the fieldbus adapter B, perform the sametasks with the corresponding parameters in parameter groups 50,

    54, 55, and 56.1. Power up the drive.

    2. Enable the communication between the adapter module and

    the drive by setting parameter 50.01 FBA A enable to Enable.

    3. Ensure that parameter 50.04 FBA A ref1 type is set to Speed

    and parameter 50.05 FBA A ref2 type is set to Torque.

    4. Set the FDNA-01 configuration parameters in drive parameter

    group 51.

    5. Define the process data transferred to and from the drive in

    FDNA-01 parameter groups 52 and 53.

    Note: If communication between the FDNA-01 and DeviceNet

    master is established, changes to the configuration parameters

    can be done also through Fieldbus configuration object 91h.6. Validate the settings made in parameter groups 51, 52 and 53

    by setting parameter 51.27 FBA par refresh to Refresh.

    7. Set the relevant drive control parameters to control the drive

    according to the application.

    Examples of appropriate values are shown in the tables below.

    Parameter setting examples ACS880

    ABB Drives profile

    The following example shows how to configure the ACS880 driveto use the ABB Drives profile.

    The used I/O assembly instances are 902 and 952.

  • 7/28/2019 FDNA-01 1

    66/168

    66 Start-up

    The table below gives the recommended drive parameter settings.

    Drive parameter Setting for ACS880 drives

    Description

    50.01 FBA A enable 1 = Enable Enables communication betweendrive and adapter module.

    50.04 FBA A ref1 type 4 = Speed Selects speed as the fieldbus Areference 1 type.

    50.05 FBA A ref2 type 3 = Torque Selects torque as the fieldbus Areference 2 type.

    51.01 FBA type DeviceNet1) Displays the type of the adaptermodule.

    51.02 MAC ID 6 Defines the MAC ID number of theadapter module.

    51.03 Baud rate 0 = 125kbit/s Sets the baud rate for the DeviceNetinterface.

    51.06 Output instance 902 Selects the ABB Drives profile withspeed and torque plus driveparameters output instance.

    51.07 Output num pars 10 Must always be set to 10. For exceptions, seeAppendix A

    Varying the number of driveparameters.

    52.01 FBA data in1 1.7 Motor current - MSW

    52.02 FBA data in2 0 = None Motor current - LSW

    52.03 FBA data in3 1.11 DC voltage - MSW

    52.04 FBA data in4 0 = None DC voltage - LSW

    52.05 FBA data in5

    52.10 FBA data in10

    0 = None

    53.01 FBA data out1 23.12 Acceleration time - MSW

    53.02 FBA data out2 0 = None Acceleration time - LSW

    53.03 FBA data out3 23.13 Deceleration time - MSW

    53.04 FBA data out4 0 = None Deceleration time - LSW

    53.05 FBA data out553.10 FBA data out10

    0 = None

    51.27 FBA par refresh 1 = Configure Validates the FDNA-01 configurationparameter settings.

  • 7/28/2019 FDNA-01 1

    67/168

    Start-up 67

    The start sequence for the parameter example above is givenbelow.

    Control word:

    47Eh (1150 decimal) > READY TO SWITCH ON

    47Fh (1151 decimal) > OPERATING (Speed mode)

    or

    C7Fh (3199 decimal) > OPERATING (Torque mode)

    ODVA AC/DC drive profile

    The following example shows how to configure the ACS880 driveto use the ODVA AC/DC drive profile.

    The used I/O assembly instances are 23 and 73.

    19.11 Ext1/Ext2 selection 2 = MCW bit11: Extctrl

    Selects FBA Control word bit 11 asthe source for the external controllocation EXT1/EXT2 selection.

    19.12 Ext1 control mode 1 2 = MCW bit11: Extctrl loc

    Selects speed control as the controlmode 1 for external control locationEXT1.

    19.14 Ext2 control mode 1 3 = Torque Selects torque control as the controlmode 1 for external control locationEXT2.

    20.01 Ext1 commands 12 = Fieldbus A Selects fieldbus interface A as thesource of the start and stopcommands for external control

    location EXT1.

    20.06 Ext2 commands 12 = Fieldbus A Selects fieldbus interface A as thesource of the start and stopcommands for external controllocation EXT2.

    22.11 Speed ref1selection

    4 = FB A ref1 Selects fieldbus A reference 1 as thesource for speed reference 1.

    26.11 Torque ref1selection

    5 = FB A ref2 Selects fieldbus reference 2 as thesource for torque reference 1.

    1) Read-only or automatically detected/set2) Example

    Drive parameter Setting for ACS880 drives

    Description

  • 7/28/2019 FDNA-01 1

    68/168

    68 Start-up

    The table below gives the recommended drive parameter settings.

    Drive parameter Setting for ACS880 drives

    Description

    50.01 FBA A enable 1 = Enable Enables communication betweendrive and adapter module.

    50.04 FBA A ref1 type 4 = Speed Selects Speed as the fieldbus Areference 1 type.

    50.05 FBA A ref2 type 3 = Torque Selects Torque as the fieldbus Areference 2 type.

    51.01 FBA type DeviceNet1) Displays the type of the adaptermodule.

    51.02 MAC ID 6 Defines the MAC ID number of theadapter module.

    51.03 Baud rate 0 = 125kbit/s Sets the baud rate for the DeviceNetinterface.

    51.06 Output instance 23 Selects the ABB Drives profile withspeed and torque plus driveparameters output instance.

    51.07 Output num pars 10 Must always be set to 10. For exceptions, see