Options for ABB drives, converters and inverters
Users manualFDNA-01 DeviceNet adapter module
7/28/2019 FDNA-01 1
2/168
List of related manuals
See section Related manuals on page 16.
7/28/2019 FDNA-01 1
3/168
6. Start-up
Users manual
FDNA-01 DeviceNet adapter module
3AFE68573360 Rev EENEFFECTIVE: 2012-04-04
2012 ABB OyAll Rights Reserved.
1. Safety
Table of contents
4. Mechanical installation
5. Electrical installation
7/28/2019 FDNA-01 1
4/168
7/28/2019 FDNA-01 1
5/168
Table of contents 5
Table of contents
1. SafetyWhat this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Use of warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Safety in installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2. About the manual
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Target audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Purpose of the manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Related manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Before you start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Terms and abbreviations used in this manual . . . . . . . . . . . . . . 19
General terms and abbreviations . . . . . . . . . . . . . . . . . . . . 19DeviceNet terms and abbreviations . . . . . . . . . . . . . . . . . . . 20
3. Overview of the DeviceNet network and the FDNA-01
module
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
DeviceNet network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Example topology of the DeviceNet link . . . . . . . . . . . . . . . 24
FDNA-01 DeviceNet adapter module . . . . . . . . . . . . . . . . . . . . 25
Layout of the adapter module . . . . . . . . . . . . . . . . . . . . . . . 26
4. Mechanical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Delivery check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Mounting the adapter module . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5. Electrical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
7/28/2019 FDNA-01 1
6/168
6 Table of contents
General cabling instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Connecting the module to the DeviceNet network . . . . . . . . . . . 30
Terminal block description . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Connection examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Switching on the bus termination . . . . . . . . . . . . . . . . . . . . . . . . 31
6. Start-up
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Drive configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
DeviceNet connection configuration . . . . . . . . . . . . . . . . . . 34
FDNA-01 configuration parameters group A (group 1) 35
FDNA-01 configuration parameters group B (group 2) 47
FDNA-01 configuration parameters group C (group 3) 48Control locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Starting up ACS355 drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Parameter setting examples ACS355 . . . . . . . . . . . . . . . . 50
ABB Drives profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
ODVA AC/DC drive profile . . . . . . . . . . . . . . . . . . . . . . . 52
Starting up ACSM1 drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Parameter setting examples ACSM1 . . . . . . . . . . . . . . . . 55ABB Drives profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
ODVA AC/DC drive profile . . . . . . . . . . . . . . . . . . . . . . . 57
Starting up ACS850 and ACQ810 drives . . . . . . . . . . . . . . . . . . 59
Parameter setting examples ACS850 and ACQ810 . . . . . 60
ABB Drives profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
ODVA AC/DC drive profile . . . . . . . . . . . . . . . . . . . . . . . 63
Starting up ACS880 drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Parameter setting examples ACS880 . . . . . . . . . . . . . . . . 65
ABB Drives profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
ODVA AC/DC drive profile . . . . . . . . . . . . . . . . . . . . . . . 67
Configuring the master station . . . . . . . . . . . . . . . . . . . . . . . . . . 70
EDS files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Configuring an Allen-Bradley PLC . . . . . . . . . . . . . . . . . . 71
7. Communication profilesWhat this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
7/28/2019 FDNA-01 1
7/168
Table of contents 7
Communication profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
ODVA AC/DC drive profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
ODVA output attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Run Forward & Run Reverse
(Control supervisor object) . . . . . . . . . . . . . . . . . . . . . . . 80Fault Reset (Control supervisor object) . . . . . . . . . . . . . 80
Net Ctrl (Control supervisor object) . . . . . . . . . . . . . . . . 80
Net Ref (AC/DC drive object) . . . . . . . . . . . . . . . . . . . . . 80
Speed Reference (AC/DC drive object) . . . . . . . . . . . . . 80
Torque Reference (AC/DC drive object) . . . . . . . . . . . . 82
ODVA input attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Faulted (Control supervisor object) . . . . . . . . . . . . . . . . 83
Warning (Control supervisor object). . . . . . . . . . . . . . . . 83
Running Forward (Control supervisor object) . . . . . . . . 83
Running Reverse (Control supervisor object) . . . . . . . . 83
Ready (Control supervisor object) . . . . . . . . . . . . . . . . . 83
Ctrl From Net (Control supervisor object) . . . . . . . . . . . 83
Ref From Net (AC/DC drive object) . . . . . . . . . . . . . . . . 83
At Reference (AC/DC drive object) . . . . . . . . . . . . . . . . 84
State (Control supervisor object) . . . . . . . . . . . . . . . . . . 84Speed Actual (AC/DC drive object) . . . . . . . . . . . . . . . . 86
Torque Actual (AC/DC drive object). . . . . . . . . . . . . . . . 87
ABB Drives communication profile . . . . . . . . . . . . . . . . . . . . . . . 88
Control word and Status word . . . . . . . . . . . . . . . . . . . . . . . 88
Control word contents . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Status word contents . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
State machine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Actual values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
8. Communication protocol
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
DeviceNet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97Object modeling and functional properties . . . . . . . . . . . . . . . . . 97
7/28/2019 FDNA-01 1
8/168
8 Table of contents
Assembly objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Basic speed control assembly . . . . . . . . . . . . . . . . . . . . . . . 98
Basic speed control plus drive parameters assembly . . . . . 99
Extended speed control assembly . . . . . . . . . . . . . . . . . . . 101
Extended speed control plus drive parameters assembly . 102Basic speed and torque control assembly . . . . . . . . . . . . . 104
Basic speed and torque control
plus drive parameters assembly . . . . . . . . . . . . . . . . . . . . 105
Extended speed and torque control assembly . . . . . . . . . . 108
Extended speed and torque control
plus drive parameters assembly . . . . . . . . . . . . . . . . . . . . 109
ABB Drives profile with set speed assembly . . . . . . . . . . . 111
ABB Drives profile with set speed
plus drive parameters assembly . . . . . . . . . . . . . . . . . . . . 112
ABB Drives profile with set speed and
set torque assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
ABB Drives profile with set speed and set torque
plus drive parameters assembly . . . . . . . . . . . . . . . . . . . . 116
Transparent 16 with one assembly . . . . . . . . . . . . . . . . . . 118
Transparent 16 with one assembly plus drive parameters 119Transparent 16 with two assembly . . . . . . . . . . . . . . . . . . 121
Transparent 16 with two assembly plus drive parameters . 122
Transparent 32 with one assembly . . . . . . . . . . . . . . . . . . 125
Transparent 32 with one assembly plus drive parameters 126
Transparent 32 with two assembly . . . . . . . . . . . . . . . . . . 128
Transparent 32 with two assembly plus drive parameters . 130
Class objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133Identity object, class 01h . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Class attributes (Instance #0). . . . . . . . . . . . . . . . . . . . 134
Instance attributes (Instance #1) . . . . . . . . . . . . . . . . . 135
Attribute explanations . . . . . . . . . . . . . . . . . . . . . . . . . . 135
DeviceNet object, class 03h . . . . . . . . . . . . . . . . . . . . . . . . 137
Class attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Instance attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Connection object, class 05h . . . . . . . . . . . . . . . . . . . . . . . 138
Class attributes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
7/28/2019 FDNA-01 1
9/168
Table of contents 9
Instance attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Acknowledge handler object, class 2Bh . . . . . . . . . . . . . . 141
Class attributes (Instance #0) . . . . . . . . . . . . . . . . . . . 141
Instance attributes (Instance #1) . . . . . . . . . . . . . . . . . 141
Motor data object, class 28h . . . . . . . . . . . . . . . . . . . . . . . 142Class attributes (Instance #0) . . . . . . . . . . . . . . . . . . . 142
Instance attributes (Instance #1) . . . . . . . . . . . . . . . . . 143
Control supervisor object, class 29h . . . . . . . . . . . . . . . . . 143
Class attributes (Instance #0) . . . . . . . . . . . . . . . . . . . 144
Instance attributes (Instance #1) . . . . . . . . . . . . . . . . . 144
AC/DC-drive object, class 2Ah . . . . . . . . . . . . . . . . . . . . . 146
Class attributes (Instance #0) . . . . . . . . . . . . . . . . . . . 146
Instance attributes (Instance #1) . . . . . . . . . . . . . . . . . 146
Drive parameter object, Class 90h . . . . . . . . . . . . . . . . . . 147
Fieldbus configuration object 91h . . . . . . . . . . . . . . . . . . . 148
Class attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Instance #1: FDNA-01 configuration parameters
group A (group 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Instance #2: FDNA-01 configuration parameters
group B (group 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151Instance #3: FDNA-01 configuration parameters
group C (group 3). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
9. Diagnostics
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
LED indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
10. Technical dataWhat this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
FDNA-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
DeviceNet link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
11. Appendix A Varying the number of drive parame-
ters
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163Modification of the EDS file . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
7/28/2019 FDNA-01 1
10/168
10 Table of contents
Further information
Product and service inquiries . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Product training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Providing feedback on ABB Drives manuals . . . . . . . . . . . . . . 167
Document library on the Internet . . . . . . . . . . . . . . . . . . . . . . . 167
7/28/2019 FDNA-01 1
11/168
Safety 11
1Safety
What this chapter contains
The chapter presents the warning symbols used in this manual andthe safety instructions which you must follow when installing anoptional module into a drive, converter or inverter. If ignored,physical injury or death may follow, or damage may occur to theequipment. Read this chapter before you start the installation.
7/28/2019 FDNA-01 1
12/168
12 Safety
Use of warnings
Warnings caution you about conditions which can result in seriousinjury or death and/or damage to the equipment and advise on howto avoid the danger. The following warning symbols are used in
this manual:
Electricity warning warns of hazards from electricity
which can cause physical injury and/or damage to the
equipment.
General warning warns about conditions, other than
those caused by electricity, which can result in physical
injury and/or damage to the equipment.
7/28/2019 FDNA-01 1
13/168
Safety 13
Safety in installation
These warnings are intended for all who install an optional moduleinto a drive, converter or inverter.
WARNING! Ignoring the following instructions can cause
physical injury or death, or damage to the equipment.
Only qualified electricians are allowed to install and maintainthe drive, converter or inverter!
Disconnect the drive, converter or inverter into which themodule will be installed from all possible power sources. After
disconnecting, always wait for 5 minutes to let the intermediate
circuit capacitors discharge before you proceed.
Do not work on the control cables when power is applied to theexternal control circuits of the drive, converter or inverter.
Externally supplied control circuits may carry dangerous
voltage.
7/28/2019 FDNA-01 1
14/168
14 Safety
7/28/2019 FDNA-01 1
15/168
About the manual 15
2About the manual
What this chapter contains
This chapter introduces this manual.
Applicability
This manual applies to the FDNA-01 DeviceNet adapter module
(+K451), SW version 0.223 or later.
Compatibility
The FDNA-01 DeviceNet adapter module is compatible with thefollowing drives:
ACS355
ACSM1
ACS850
ACQ810
ACS880.
The FDNA-01 DeviceNet adapter module is compatible with allmaster stations that support the DeviceNet protocol.
7/28/2019 FDNA-01 1
16/168
16 About the manual
Target audience
The reader is expected to have a basic knowledge of fieldbusinterface, electrical fundamentals, electrical wiring practices andhow to operate the drive.
Purpose of the manual
The manual provides information on installing, commissioning andusing an FDNA-01 DeviceNet adapter module.
Related manuals
The related manuals are listed below.
Code (English)
Drive users manuals
ACS355 drives (0.3722 kW,0.530 hp) users manual
3AUA0000066143
Drive hardware manuals andguides
ACSM1-204 regen supply modules(5.3 to 61 kW) hardware manual 3AUA0000053713
ACSM1-04 drive modules (0.75 to45 kW) hardware manual
3AFE68797543
ACSM1-04 drive modules (55 to 110kW) hardware manual
3AFE68912130
ACSM1-04Lx liquid-cooled drivemodules (55 to 160 kW) hardwaremanual
3AUA0000022083
ACS850-04 (0.3745 kW)
hardware manual
3AUA0000045496
ACS850-04 (55160 kW, 75200hp) hardware manual
3AUA0000045487
ACS850-04 (200500 kW,250600 hp) hardware manual
3AUA0000026234
ACQ810-04 drive modules(0.3745 kW, 0.560 hp) hardwaremanual
3AUA0000055160
ACQ810-04 drive modules (55 to
160 kW, 75 to 200 hp) hardwaremanual
3AUA0000055161
http://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000066143&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000053713&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE68797543&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE68912130&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000022083&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000045496&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000045487&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000026234&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000055160&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000055161&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000055161&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000055160&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000026234&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000045487&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000045496&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000022083&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE68912130&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE68797543&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000053713&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000066143&LanguageCode=en&DocumentPartId=1&Action=Launch7/28/2019 FDNA-01 1
17/168
About the manual 17
You can find manuals and other product documents in PDF formaton the Internet. See section Document library on the Internetonthe inside of the back cover. For manuals not available in theDocument library, contact your local ABB representative.
Before you start
It is assumed that the drive is installed and ready to operate beforeyou start the installation of the adapter module.
In addition to conventional installation tools, have the drivemanuals available during the installation as they contain importantinformation not included in this manual. The drive manuals arereferred to at various points of this manual.
ACQ810-04 drive modules(200400 kW, 250600 hp)hardware manual
3AUA0000055155
ACS880-01 (0.55 to 250 kW, 0.75 to
350 hp) hardware manual
3AUA0000078093
Drive firmware manuals andguides
ACSM1 motion control programfirmware manual
3AFE68848270
ACSM1 speed and torque controlprogram firmware manual
3AFE68848261
ACSM1 regen supply control
program firmware manual
3AUA0000052174
ACS850 standard control programfirmware manual
3AUA0000045497
ACQ810 standard pump controlprogram firmware manual
3AUA0000055144
ACS880 primary control programfirmware manual
3AUA0000085967
Option manuals and guides
FDNA-01 DeviceNet adapter moduleusers manual
3AFE68573360
Code (English)
http://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000055155&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000078093&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE68848270&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE68848261&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000052174&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000045497&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000055144&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000085967&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE685733601&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE685733601&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000085967&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000055144&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000045497&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000052174&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE68848261&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AFE68848270&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000078093&LanguageCode=en&DocumentPartId=1&Action=Launchhttp://search.abb.com/library/ABBLibrary.asp?DocumentID=3AUA0000055155&LanguageCode=en&DocumentPartId=1&Action=Launch7/28/2019 FDNA-01 1
18/168
18 About the manual
Contents
The manual consists of the following chapters:
Safetypresents the safety instructions which you must followwhen installing a fieldbus adapter module.
About the manualintroduces this manual.
Overview of the DeviceNet network and the FDNA-01 modulecontains a short description of the DeviceNet network and the
adapter module.
Mechanical installation contains a delivery checklist andinstructions on mounting the adapter module.
Electrical installation contains cabling and bus terminationinstructions and instructions on connecting the module to the
DeviceNet network.
Start-up presents the steps to take during the start-up of thedrive with the adapter module and gives examples of
configuring the master system.
Communication profiles describes the communication profiles
used in the communication between the DeviceNet network,the adapter module and the drive.
Communication protocoldescribes the DeviceNetcommunication protocol for the adapter module and the
configuration of the scanner.
Diagnostics explains how to trace faults with the status LEDson the adapter module.
Technical data contains the technical data of the adaptermodule and the DeviceNet link.
Appendix A Varying the number of drive parametersdescribes how to reduce the number of drive parameter
members in FDNA-01 assemblies by modifying the EDS file.
7/28/2019 FDNA-01 1
19/168
About the manual 19
Terms and abbreviations used in this manual
General terms and abbreviations
Term Explanation
Command word See Control word.
Communication module Communication module is a name for a device(eg, a fieldbus adapter) through which the driveis connected to an external communicationnetwork (eg, a fieldbus). The communicationwith the module is activated with a driveparameter.
Control word 16-bit or 32-bit word from master to slave withbit-coded control signals (sometimes called theCommand word).
DCU profile Drive Control Unit profile, native profile used inthe ACS350 and ACS355 drives
DTC Direct Torque Control is a motor control methodfor AC drives. DTC allows accurate control ofboth motor speed and torque without pulseencoder feedback from the motor shaft.
FBA profile Fieldbus Adapter profile, native profile used inthe ACQ810, ACS850 and ACSM1 drives
FDNA-01 DeviceNetadapter module
One of the optional fieldbus adapter modulesavailable for ABB drives. FDNA-01 is a devicethrough which an ABB drive is connected to aDeviceNet serial communication bus.
LSW Least significant word
MSW Most significant word
Parameter An operating instruction for the drive.Parameters can be read and programmed withthe drive control panel, drive PC tools orthrough the adapter module.
Profile Adaptation of the protocol for certain applicationfield, for example, drives.
In this manual, drive-internal profiles (eg, DCU
or FBA) are called native profiles.
RFG Ramp Function Generator
7/28/2019 FDNA-01 1
20/168
20 About the manual
DeviceNet terms and abbreviations
Status word 16-bit or 32-bit word from slave to master withbit-coded status messages
Term Explanation
Change of State/CyclicMessage
Change of State/Cyclic Message is transmittedby either the master or the slave. A Change ofState/Cyclic Message is directed towards asingle specific node (point-to-point). AnAcknowledge Message may be returned in
response to this message.CIP Common Industrial Protocol (CIP) is an
industrial protocol for industrial automationapplications. It is managed by ODVA.
EDS File Electronic Data Sheet (EDS) file identifies theproperties of the device to the DeviceNetScanner. Each type of drive and applicationprogram requires its own EDS file.
Input In the ODVA DeviceNet specification the wordinput is used to describe data flow from adevice (such as FDNA-01) to the network.
I/O assembly selection Smart networked devices (like FDNA-01) canproduce and/or consume more than one I/Ovalue. Typically, they produce and/or consumeone or more I/O value, as well as status anddiagnostic information. Each piece of datacommunicated by a device is represented by an
attribute of one of the devices internal objects.Communicating multiple pieces of data(attributes) across a single I/O connectionrequires that the attributes be grouped orassembled together into a single block.
MAC ID Every node on DeviceNet network has to havea unique identifier. This node number is calledMAC ID (Media Access Control Identifier).
Term Explanation
7/28/2019 FDNA-01 1
21/168
About the manual 21
ODVA ODVA stands for Open DeviceNet Vendor Association. ODVA is an independentorganization that promotes interoperativity
between different manufacturers DeviceNetproducts. ABB is an Associate Member atODVA.
Output In the ODVA DeviceNet specification the wordoutput is used to describe data flow from thenetwork into a device (such as FDNA-01).
Poll Message Most DeviceNet Scanners as well as the FDNA-01 module support two different data services.These are Poll and Change of State/Cyclicmessages.
The Poll Command is an I/O Message that istransmitted by the master. A Poll Command isdirected towards a single, specific slave (point-to-point, FDNA-01 always acts as a slave). Amaster must transmit a separate Poll CommandMessage for each of its slaves that is to bepolled. The Poll Response is an I/O Messagethat a slave transmits back to the master when
the Poll Command is received.
Scanlist DeviceNet Scanner communicates with theDeviceNet slaves in a user-defined order. Thisorder of communication is the scanlist. Thescanlist contains a complete list of the slavenodes and the order in which the slaves areaccessed.
Term Explanation
7/28/2019 FDNA-01 1
22/168
22 About the manual
7/28/2019 FDNA-01 1
23/168
Overview of the DeviceNet network and the FDNA-01 module 23
3Overview of the DeviceNetnetwork and the FDNA-01module
What this chapter contains
This chapter contains a short description of the DeviceNet network
and the FDNA-01 DeviceNet adapter module.
DeviceNet network
The DeviceNet network has a linear bus topology. Terminatingresistors are required on each end of the trunk line. Drop lines aslong as 6 metres (20 feet) each are permitted, allowing one ormore nodes to be attached. DeviceNet allows branching structuresonly on drop lines.
The maximum length of the trunk cable depends on the data rateand on the type of the cable used (see chapterTechnical data).
7/28/2019 FDNA-01 1
24/168
24 Overview of the DeviceNet network and the FDNA-01 module
Example topology of the DeviceNet link
An example of an allowable topology is shown below.
Node
Node
Node
Node
Node
Tap
Tap
TapTap
Node
Node
Node
Node
Node
Node
Trunk line
Terminating
Resistor
Drop line
7/28/2019 FDNA-01 1
25/168
Overview of the DeviceNet network and the FDNA-01 module 25
FDNA-01 DeviceNet adapter module
The FDNA-01 DeviceNet Adapter module is an optional device forABB drives. It enables the connection of the drive to a DeviceNetnetwork. The drive is considered a slave in the DeviceNet network.
Through the adapter module you can:
give control commands to the drive (for example, Start, Stop,Run enable)
feed a motor speed or torque reference to the drive
give the actual value or reference of the process to the PIDcontroller of the drive
read status information and actual values from the drive change drive parameter values
reset a drive fault.
The adapter module acts as a class 2 slave only with predefinedmaster-slave connection set services. These include the explicitmessaging, the poll-response service and the change of state/cyclic service. The DeviceNet commands and services supportedby the adapter module are described in chapterCommunication
protocol.
The adapter module is mounted into an option slot on the motorcontrol board of the drive. See the drive manuals for the moduleplacement options.
7/28/2019 FDNA-01 1
26/168
26 Overview of the DeviceNet network and the FDNA-01 module
Layout of the adapter module
Diagnostic LEDs(see chapterDiagnostics)
Bus connector X1
(see chapterElectricalinstallation)Mounting screw
7/28/2019 FDNA-01 1
27/168
Mechanical installation 27
4Mechanical installation
What this chapter contains
This chapter contains a delivery checklist and instructions onmounting the adapter module.
WARNING! Follow the safety instructions given in thismanual and the drive documentation.
Delivery check
The option package for the adapter module contains:
DeviceNet adapter module, type FDNA-01 this manual.
7/28/2019 FDNA-01 1
28/168
28 Mechanical installation
Mounting the adapter module
The adapter module is to be inserted into its specific position in thedrive. The module is held in place with plastic pins and one screw.The screw also provides the electrical connection between the
module and drive frame for cable shield termination.When the module is installed, the signal and power connection tothe drive is made through a 20-pin connector. (All drives do not useall the available signals so the connector on the drive may havefewer pins.)
Mounting procedure:
1. Insert the module carefully into its position on the drive.
2. Fasten the screw.
Note: It is essential to install the screw properly to fulfill the EMCrequirements and to ensure the proper operation of the module.
For more information on mounting, see the drive manuals.
7/28/2019 FDNA-01 1
29/168
Electrical installation 29
5Electrical installation
What this chapter contains
This chapter contains:
general cabling instructions
instructions on connecting the module to the DeviceNetnetwork
instructions on switching on the bus termination.
WARNING! Before installation, switch off the drive power
supply. Wait five minutes to ensure that the capacitor bank
of the drive is discharged. Switch off all dangerous
voltages connected from external control circuits to the inputs and
outputs of the drive.
General cabling instructions
Arrange the bus cables as far away from the motor cables aspossible.
Avoid parallel runs. Use bushings at cable entries.
7/28/2019 FDNA-01 1
30/168
30 Electrical installation
Connecting the module to the DeviceNet network
Connect the bus cable to terminal block X1 on the adapter module.
Terminal block description
Connection examples
5-pin micro-style connector:
5-pin mini-style connector:
X1 Description
1 V- Network power supply ground (0V DC)
2 CAN_L CAN_L bus line
3 SHLD Network cable shield
4 CAN_H CAN_H bus line
5 V+ Network power supply source (24V DC)
5
3
Male micro-style
SHLDCAN_L
CAN_H
V- 12
3
4
connector
4
1 2
X1
0 V+24 V
Networkpower supply
4
5
3
12
FDNA
5V+
V+
32
Male mini-style
4
5
3
12connector
4
5 1
0 V+24 V
Networkpower supply
SHLDCAN_L
CAN_H
V- 12
3
4
X1FDNA
5
7/28/2019 FDNA-01 1
31/168
Electrical installation 31
Standard open-style screw connector:
Switching on the bus termination
The adapter module does not provide bus termination. TheDeviceNet network should be terminated at both ends of the trunkcable with a 121 ohm, W, 1% metal film resistor. Connect theresistor between the two signal wires (CAN_H, CAN_L) on theDeviceNet cable, as shown in the figure below.
Further information on the DeviceNet protocol is available atwww.odva.org.
4
3
2
1
5
SHLDCAN_L
CAN_H
V-1
2
3
4
X1FDNA
5V+
0 V+24 VNetwork
power supply
Node 1 Node n
121
CAN_H
CAN_L
Scanner
1211%
Metal Film1/4 W
1%Metal Film
1/4 W
http://www.odva.org/http://www.odva.org/http://www.odva.org/7/28/2019 FDNA-01 1
32/168
32 Electrical installation
7/28/2019 FDNA-01 1
33/168
Start-up 33
6Start-up
What this chapter contains
This chapter contains:
information on configuring the drive for operation with theadapter module
drive-specific instructions on starting up the drive with the
adapter module examples of configuring the master station for communication
with the adapter module.
WARNING! Follow the safety instructions given in this
manual and the drive documentation.
7/28/2019 FDNA-01 1
34/168
34 Start-up
Drive configuration
The following information applies to all drive types compatible withthe adapter module, unless otherwise stated.
DeviceNet connection configuration
After the adapter module has been mechanically and electricallyinstalled according to the instructions in chapters Mechanicalinstallation and Electrical installation, the drive must be preparedfor communication with the module.
The detailed procedure of activating the module for DeviceNetcommunication with the drive depends on the drive type. Normally,a parameter must be adjusted to activate the communication. Seethe drive-specific start-up procedures starting on page 49.
Once communication between the drive and the adapter modulehas been established, several configuration parameters are copiedto the drive. These parameters are shown in the tables below andmust be checked first and adjusted where necessary.
Note: Not all drives display descriptive names for the configurationparameters. To help you identify the parameters in different drives,the names displayed by each drive are given in grey boxes in thetables.
Note: The new settings take effect only when the adapter moduleis powered up the next time or when the fieldbus adapter refreshparameter is activated.
Note: If communication between the adapter module andDeviceNet master is established, changes to the configurationparameters can be done also throughFieldbus configuration object91h.
7/28/2019 FDNA-01 1
35/168
Start-up 35
FDNA-01 configuration parameters group A (group 1)
Note: The actual parameter group number depends on the drivetype. Group A (group 1) corresponds to:
parameter group 51 in ACS355, ACSM1, ACS850 and
ACQ810
parameter group 51 in ACS880 if the adapter is installed asfieldbus adapter A or group 54 if the adapter is installed as
fieldbus adapter B.
No. Name/Value Description Default
01 FBA TYPE Read-only. Shows the fieldbus adapter type asdetected by the drive. Value cannot be adjusted
by the user.If the value is 0 = None, the communicationbetween the drive and the module has not beenestablished.
1 = Devi-ceNet
02 MAC ID Defines the MAC ID number for the drive theadapter module is connected to. Each deviceon the DeviceNet network must have a uniqueMAC ID number.
63
ACS355:FB PAR 2
ACSM1:FBA PAR2
ACS850/ACQ810:FBA par2
ACS880:MAC ID
063 MAC ID
03 BAUD RATE Read-only. Indicates the detectedcommunication speed in kbit/s.
0 = 125kbit/s
ACS355:FB PAR 3
ACSM1:FBA PAR3
ACS850/ACQ810:FBA par3
ACS880:Baud rate
0 = 125 kbit/s Communication speed is 125 kbit/s.
1 = 250 kbit/s Communication speed is 250 kbit/s.
2 = 500 kbit/s Communication speed is 500 kbit/s.
7/28/2019 FDNA-01 1
36/168
36 Start-up
04 DRIVE PROFILE Defines the communication used between themodule and the drive (not fieldbus and module).If a drive supports more than one drive profile,this parameter is used to select the preferred
profile. Presently, to use the ODVA and ABBDrives profiles, the drive must support a nativeprofile (eg, DCU or FBA). Transparent16 andTransparent32 profiles may be used with anydrive profile.
0 =Nativeprof
ACS355:FB PAR 4
ACSM1:FBA PAR4
ACS850/ACQ810:FBA par4
ACS880:Drive profile
0 = Native prof Native profile of the drive selected
05 ODVA STOPFUNC
Used with the ODVA AC/DC drive profile.Determines how the motor is stopped when a
stop command is received via DeviceNet.
0 = Rampstop
ACS355:FB PAR 5
ACSM1:FBA PAR5
ACS850/ACQ810:FBA par5
ACS880:ODVA stop func
0 = Ramp stop Motor decelerates along the active decelerationramp.
1 = Coast stop Motor comes to a stop by coasting.
No. Name/Value Description Default
7/28/2019 FDNA-01 1
37/168
Start-up 37
06 OUTPUTINSTANCE
Configures the output assembly instances usedby the adapter module. Tables below list thesupported assemblies and allowedcombinations. For the descriptions of the
assembly instances, see sectionAssemblyobjects on page 98.
20
ACS355:FB PAR 6
ACSM1:FBA PAR6
ACS850/ACQ810:FBA par6
ACS880:Output instance
No. Name/Value Description Default
Name Outputinstance
Inputinstance
Defaultinput
size(bytes)
Profile
Basic speed control 20 70 4 ODVA AC/DC drive
Extended speedcontrol
21 71 4 ODVA AC/DC drive
Basic speed andtorque control
22 72 6 ODVA AC/DC drive
Extended speed andtorque control
23 73 6 ODVA AC/DC drive
Basic speed controlplus drive parameters
120 170 24 ODVA AC/DC drive
Extended speedcontrol plus driveparameters
121 171 24 ODVA AC/DC drive
Basic speed andtorque control plusdrive parameters
122 172 26 ODVA AC/DC drive
Extended speed andtorque control plusdrive parameters
123 173 26 ODVA AC/DC drive
ABB Drives profilewith set speed
801 851 4 ABB Drives
ABB Drives profilewith set speed andset torque
802 852 6 ABB Drives
(continued)
7/28/2019 FDNA-01 1
38/168
38 Start-up
No. Name/Value Description Default
Name Outputinstance
Inputinstance
Defaultinputsize
(bytes)
Profile
(continued)
ABB Drives profilewith set speed plusdrive parameters
901 951 24 ABB Drives
ABB Drives profilewith set speed andset torque plus driveparameters
902 952 26 ABB Drives
ABB Drives profile
with set speed plusdrive parameters
901 951 24 ABB Drives
Transparent16 withone
811 861 4 Transparent16
Transparent16 withtwo
812 862 6 Transparent16
Transparent16 withone plus driveparameters
911 961 24 Transparent16
Transparent16 withtwo plus driveparameters
912 962 26 Transparent16
Transparent32 withone
821 871 8 Transparent32
Transparent32 withtwo
822 872 12 Transparent32
Transparent32 withone plus driveparameters
921 971 28 Transparent32
Transparent32 withtwo plus driveparameters
922 972 32 Transparent32
7/28/2019 FDNA-01 1
39/168
Start-up 39
Note: With ACSM1, ACQ810, ACS850 and ACS880, when using the ODVAAC/DC drive or ABB Drives profile, make sure that drive parameter 50.04 FBAREF MODESEL is set to SPEED. With ACSM1, ACS850 and ACS880, makesure that 50.05 FBA REF2 MODESEL is set to TORQUE.
For alternative values, see columnOutputinstance in the table describing parameter06OUTPUT INSTANCE.
07 OUTPUT NUMPARS
Some assembly instances support transferringdrive parameter values between the I/Oscanner and drive. Parameters 07OUTPUTNUM PARSand 09INPUT NUM PARS specifyhow many drive parameter values should be
included in the respective assembly instance.Changing the numbers of the drive parametersto values other than the defaults also changesthe lengths of the associated assemblyinstances. This requires manual changes toeither the EDS file or I/O scanner configuration.Before changing these parameters, consult
Appendix A Varying the number of driveparameters.Note: This parameter is only used when the
output assembly instance is 120, 121, 122, 123,901, 902, 911, 912, 921, 922. It must always beset to the default, 10, except as described in
Appendix A Varying the number of driveparameters
10
ACS355:FB PAR 7
ACSM1:FBA PAR7
ACS850/ACQ810:FBA par7
ACS880:Output num pars
110 Number or drive parameter values to beincluded in the assembly instance
No. Name/Value Description Default
Input
ODVA
(70-73; 170-173)
ABB DRIVES
(851-852; 951-952
TRANSPARENT16
(861-862; 961-962)
TRANSPARENT32
(871-872; 971-972)
Output
ODVA
(20-23; 120-123)x
ABB DRIVES
(801-802; 901-902)x
TRANSPARENT16
(811-812; 911-912)x
TRANSPARENT32
(821-822; 921-922)
x
7/28/2019 FDNA-01 1
40/168
40 Start-up
08 INPUT INSTANCE Configures the input assembly instances usedby the adapter module. See parameter06OUTPUT INSTANCE.
70
ACS355:FB PAR 9
ACSM1:FBA PAR9
ACS850/ACQ810:FBA par9
ACS880:Input instance
For alternative values, see parameter06OUTPUT INSTANCE.
09 INPUT NUM
PARS
See parameter07OUTPUT NUM PARS.
Note: This parameter is only used when theinput assembly instance is 170, 171, 172, 173,951, 952, 961, 962, 971, 972. It must always beset to the default, 10, except as described in
Appendix A Varying the number of driveparameters.
10
ACS355:FB PAR 9
ACSM1:FBA PAR9
ACS850/ACQ810:FBA par9
ACS880:Input num pars
110 Number or drive parameter values to beincluded in the assembly instance
No. Name/Value Description Default
7/28/2019 FDNA-01 1
41/168
Start-up 41
10 ODVA SPEEDSCALE
Defines the speed scale in the ODVA AC/DCdrive profile. Units of reference and actualspeeds for the ODVA AC/DC drive profile aregiven by the formula below. No effect on the
ABB Drives profiles.Note: While a wide range of resolutions may beconfigured, the actual performance is limited tothe performance capabilities of the drive.
Speed unit = RPM X 2(-1 X ODVA speed scale value)
128
ACS355:FB PAR 10
ACSM1:FBA PAR10
ACS850/ACQ810:FBA par10
ACS880:ODVA speed scale
Table below shows how the values of driveparameter ODVA SPEED SCALE correspondto the ODVA Speed Scale units.
123133 Speed scale value of the drive parameter
No. Name/Value Description Default
ODVA speed scale value1) Speed scale value ofdrive parameter2)
Unit
-5 123 32 RPM
-4 124 16 RPM
-3 125 8 RPM
-2 126 4 RPM
-1 127 2 RPM
0 (default) 128 1 RPM
1 129 0.5 RPM
2 130 0.25 RPM
3 131 0.125 RPM
4 132 0.0625 RPM
5 133 0.03125 RPM
1) Use the ODVA speed scale value when reading/writing parameterODVASPEED SCALEviaAC/DC-drive object, class 2Ah. When written via the
AC/DC drive object, the new value takes effect immediately.2) Use the speed scale value of the drive parameter when reading/writingparameterODVA SPEED SCALEvia the drive control panel, Drive parameterobject, Class 90h and Fieldbus configuration object 91h. When written viathese methods, the new value takes effect after the drive is repowered or aFieldbus Adapter Parameter refresh is given.
7/28/2019 FDNA-01 1
42/168
42 Start-up
11 ODVA TORQUESCALE
Defines the torque scale in the ODVA AC/DCdrive profile. Units of reference and actualtorques for the ODVA AC/DC drive profile aregiven by the formula below. No effect on the
ABB Drives profiles.Note: While a wide range of resolutions may beconfigured, the actual performance is limited tothe performance capabilities of the drive.(Nm = Newton x Meter)
Torque unit = Nm x 2(-1 X ODVA torque scale)
128
ACS355:FB PAR 11
ACSM1:FBA PAR11
ACS850/ACQ810:FBA par11
ACS880:ODVA torquescale
Table below shows how the values of driveparameter ODVA TORQUE SCALE correspondto the ODVA Torque Scale units.
123133 Torque scale value of the drive parameter
1225
Reserved Not used by the adapter module. N/A
No. Name/Value Description Default
ODVA torque scale value1) Torque scale value ofdrive parameter2)
Unit
-5 123 32 Nm
-4 124 16 Nm
-3 125 8 Nm
-2 126 4 Nm
-1 127 2 Nm
0 (default) 128 1 Nm
1 129 0.5 Nm
2 130 0.25 Nm
3 131 0.125 Nm
4 132 0.0625 Nm
5 133 0.03125 Nm
1) Use the ODVA torque scale value when reading/writing parameterODVA
TORQUE SCALEviaAC/DC-drive object, class 2Ah. When written via theAC/DC drive object, the new value takes effect immediately.2) Use the torque scale value of the drive parameter when reading/writingparameterODVA TORQUE SCALEvia the drive control panel, Drive
parameter object, Class 90hand Fieldbus configuration object 91h. Whenwritten via these methods, the new value takes effect after the drive isrepowered or a Fieldbus Adapter Parameter refresh is given.
7/28/2019 FDNA-01 1
43/168
Start-up 43
26 UNRECOVER-ABLE ERROR
Read-only. Shows information about the causeof an unrecoverable error in the adaptermodule. Bit field parameter, that is, severalstatus bits can be set at a time. Value 0
indicates that there are no errors.
0
ACS355:FB PAR 26
ACSM1:FBA PAR26
ACS850/ACQ810:FBA par26
ACS880:Unrecover. error
065535 Active unrecoverable errors
27 FBA PARREFRESH
Validates any changed adapter moduleconfiguration parameter settings. Afterrefreshing, the value reverts automatically to0 = Done.Note: This parameter cannot be changed while
the drive is running.
0 = Done
ACS355/ACSM1:FBA PARREFRESH
ACS850/ACQ810/ACS880:FBA par refresh
0 = Done Refreshing done
1 =Refresh/Configure
Refreshing
No. Name/Value Description Default
Bit Name Value Description
1 DUP_MAC_ERROR 0x0001 Duplicate MAC ID error
2 RX_QUEUE_OVERRUN 0x0002 Message receive queue is full.3 TX_QUEUE_OVERRUN 0x0004 Message transmit queue is full.
4 IO_SEND_ERROR 0x0008 Transmitting I/O data has failed.
5 CAN_BUS_OFF 0x0010 Bus-off is detected.
6 CAN_OVERRUN 0x0020 CAN message was lost.
7 DNS_RESET 0x0040 DeviceNet driver of the module isreset.
8 DNS_BUS_SENSE_ERROR 0x0080 No voltage detected in thenetwork.
9 DNS_SWITCH_ERROR 0x0100 DeviceNet driver reset failed due
to an invalid MAC ID or baud rate.13 SYS_FILE_ERR 0x1000 Initialization with the drive failed.
7/28/2019 FDNA-01 1
44/168
44 Start-up
28 PAR TABLE VER Read-only. Displays the parameter tablerevision of the fieldbus adapter modulemapping file stored in the memory of the drive.In format xyz, where
x = major revision numbery = minor revision numberz = correction numberORin format axyz, wherea = major revision numberxy = minor revision numbersz = correction number or letter.
N/A
ACS355:FILE CPI FW REV
ACSM1:PAR TABLE VER
ACS850/ACQ810/ACS880:Par table ver
0x00000xFFFF Parameter table revision
29 DRIVE TYPECODE
Read-only. Displays the drive type code of thefieldbus adapter module mapping file stored inthe memory of the drive.
N/A
ACS355:FILE CONFIG ID
ACSM1:DRIVE TYPECODE
ACS850/ACQ810/ACS880:Drive type code
065535 Drive type code of the fieldbus adapter modulemapping file
30 MAPPING FILEVER
Read-only. Displays the fieldbus adaptermodule mapping file revision stored in thememory of the drive in decimal format.Example: 0x107 = revision 1.07.
N/A
ACS355:FILE CONFIGREV
ACSM1:
MAPPING FILEVER
ACS850/ACQ810/ACS880:Mapping file ver
065535 Mapping file revision
No. Name/Value Description Default
7/28/2019 FDNA-01 1
45/168
Start-up 45
31 D2FBA COMMSTA
Read-only. Displays the status of the fieldbusadapter module communication.Note: The value names may vary by drive.
0 = Idle
ACS355:FBA STATUS
ACSM1:D2FBA COMMSTA
ACS850/ACQ810/ACS880:D2FBA comm sta
0 = Idle Adapter is not configured.
1 = Exec.init Adapter is initializing.
2 = Time out Time-out has occurred in the communicationbetween the adapter and the drive.
3 = Conf.err Adapter configuration error: Major or minorrevision code of the common program revisionin the fieldbus adapter module is not therevision required by the module or mapping fileupload has failed more than three times.
4 = Off-line Adapter is off-line.
5 = On-line Adapter is on-line.
6 = Reset Adapter is performing a hardware reset.
32 FBA COMM SWVER
Read-only. Displays the common programrevision of the adapter module in format axyz,where:a = major revision numberxy = minor revision numbersz = correction number or letter.Example: 190A = revision 1.90A
N/A
ACS355:FBA CPI FW REV
ACSM1:FBA COMM SWVER
ACS850/ACQ810/ACS880:FBA comm SWver
0x00000xFFFF Common program version of the adaptermodule
No. Name/Value Description Default
7/28/2019 FDNA-01 1
46/168
46 Start-up
33 FBA APPL SWVER
Read-only. Displays the application programrevision of the adapter module in format axyz,where:a = major revision number
xy = minor revision numbersz = correction number or letter.Example: 190A = revision 1.90A
N/A
ACS355:FBA CPI APPLREV
ACSM1:FBA COMM APPLVER
ACS850/ACQ810/ACS880:FBA appl SW ver
0x00000xFFFF Application program revision of the adaptermodule
No. Name/Value Description Default
7/28/2019 FDNA-01 1
47/168
Start-up 47
FDNA-01 configuration parameters group B (group 2)
Note: The actual parameter group number depends on the drivetype. Group B (group 2) corresponds to:
parameter group 55 in ACS355
parameter group 53 in ACSM1, ACS850 and ACQ810
parameter group 53 in ACS880 if the adapter is installed asfieldbus adapter A or group 56 if the adapter is installed as
fieldbus adapter B.
No.1) Name/Value Description Default
01 DATA OUT 1(master to drive)
In the output assembly instances that includedrive parameters, this parameter specifies
which parameters value is placed in locationDATA OUT 1 value received by the drive fromthe DeviceNet network. Content is defined by adecimal number in the range of 0 to 9999 asfollows:
0
ACS355:FBA DATA OUT 1
ACSM1:FBA DATA OUT1
ACS850/ACQ810/ACS880:FBA data out1
Note: The FDNA-01 configuration parametersare 16-bit parameters. If the mapped parameteris a 32-bit parameter, it automatically reservestwo consecutive parameters. For example,mapping a 32-bit parameter to parameter no. 1also reserves parameter no. 2.
0 Not used
1019999 Parameter index with format xxyy, where xx isthe parameter group number (199) and yy isthe parameter number index within that group(0199).
0210
DATA OUT 2DATA OUT 10
See parameterDATA OUT 1. 0
1) The number of parameters in this group may vary by drive type and drive firmware.
0 Not used
199 Virtual address area of drive control.Not used with the FDNA-01 module.
1019999
Parameter area of the drive
7/28/2019 FDNA-01 1
48/168
48 Start-up
FDNA-01 configuration parameters group C (group 3)
Note: The actual parameter group number depends on the drivetype. Group C (group 3) corresponds to:
parameter group 54 in ACS355
parameter group 52 in ACSM1, ACS850 and ACQ810
parameter group 52 in ACS880 if the adapter is installed asfieldbus adapter A or group 55 if the adapter is installed as
fieldbus adapter B.
No.1) Name/Value Description Default
01 DATA IN 1(drive to master)
In input assembly instances that include driveparameters, this parameter specifies which
parameters value is placed in location DATA IN1 value sent by the drive to the DeviceNetnetwork. Content is defined by a decimalnumber in the range of 0 to 9999 as follows:
0
ACS355:FBA DATA IN 1
ACSM1:FBA DATA IN1
ACS850/ACQ810/ACS880:FBA data in1
Note: The FDNA-01 configuration parametersare 16-bit parameters. If the mapped parameteris a 32-bit parameter, it automatically reservestwo consecutive parameters. For example,mapping a 32-bit parameter to parameter no. 1also reserves parameter no. 2.
0 Not used
1019999 Parameter index with format xxyy, where xx isthe parameter group number (199) and yy is
the parameter number index within that group(0199).
0210
DATA IN 2DATA IN 10
See parameterDATA IN 1. 0
1) The number of parameters in this group may vary by drive type and drive firmware.
0 Not used
199 Virtual address area of drive control.Not used with the FDNA-01 module.
1019999
Parameter area of the drive
7/28/2019 FDNA-01 1
49/168
Start-up 49
Control locations
ABB drives can receive control information from multiple sourcesincluding digital inputs, analog inputs, the drive control panel and acommunication module (for example, the adapter module). ABB
drives allow the user to separately determine the source for eachtype of control information (Start, Stop, Direction, Reference, FaultReset, and so on).
To give the fieldbus master station the most complete control overthe drive, the communication module must be selected as thesource for this information. The parameter setting examples belowcontain the drive control parameters needed in the examples. Fora complete parameter list, see the drive documentation.
Starting up ACS355 drives
1. Power up the drive.
2. Enable the communication between the adapter module and
the drive by setting parameter 9802 COMM PROT SEL to EXT
FBA.
3. Set the FDNA-01 configuration parameters in parameter group51.
At the minimum, set the required number in parameter 5102
MAC ID and the required baud rate in 5103 BAUD RATE. In
addition, select the communication profile in 5104 DRIVE
PROFILE. With the ODVA AC/DC drive profile select the way
in which the motor is stopped in 5105 ODVA STOP FUNC.
4. Define the process data transferred to and from the drive inFDNA-01 parameter groups 54 and 55.
Note: If communication between the FDNA-01 and DeviceNet
master is established, changes to the configuration parameters
can be done also through Fieldbus configuration object 91h.
5. Validate the settings made in parameter group 51 by setting
parameter 5127 FBA PAR REFRESH to REFRESH.
7/28/2019 FDNA-01 1
50/168
50 Start-up
6. Set the relevant drive control parameters to control the drive
according to the application. Examples of appropriate values
are shown in the tables below.
Parameter setting examples ACS355
ABB Drives profile
This example shows how to configure the ACS355 drive to use theABB Drives profile with set speed and set torque plus driveparameters assembly.
The used I/O assembly instances are 902 and 952.
The table below gives the recommended drive parameter settings.Drive parameter Setting for
ACS355 drivesDescription
9802 COMM PROT SEL 4 = EXT FBA Enables communication betweendrive and adapter module.
5101 FBA TYPE DEVICENET1) Displays the type of the adaptermodule.
5102 FB PAR 2(MAC ID) 2 Defines the MAC ID number of theadapter module.
5103 FB PAR 3(BAUD RATE)
0 (= 125 kbit/s) Sets the baud rate for theDeviceNet interface.
5104 FB PAR 4(DRIVE PROFILE)
0 (= DCU Profile) Selects the profile used in thecommunication between drive andadapter module.
5105 FB PAR 5(ODVA STOP FUNC)
0 (= Ramp) Motor decelerates along the activedeceleration ramp.
5106 FB PAR 6(OUTPUT INSTANCE)
902 Selects the ABB Drives profile withspeed and torque plus driveparameters output instance.
5107 FB PAR 7(OUTPUT NUM PARS)
10 Must always be set to 10, except asprovided inAppendix A Varyingthe number of drive parameters.
5108 FB PAR 8(INPUT INSTANCE)
952 Selects the ABB Drives profile withspeed and torque plus driveparameters input instance.
7/28/2019 FDNA-01 1
51/168
Start-up 51
5109 FB PAR 9(INPUT NUM PARS)
10 Must always be set to 10, except asprovided inAppendix A Varyingthe number of drive parameters.
5110 FB PAR 10(ODVA SPEED SCALE)
128 Sets the scaling as 1 rpm for theODVA speed reference.
5111 FB PAR 11(ODVA TORQUE SCALE)
128 Sets the scaling as 1 Nm for theODVA torque reference.
5401 FBA DATA IN 1 104 Current
5402 FBA DATA IN 2 107 DC bus voltage
5403 FB DATA IN 3
5410 DATA IN 10
0
5501 FBA DATA OUT 1 2205 Acceleration time 2
5502 FBA DATA OUT 2 2206 Deceleration time 2
5503 FB DATA OUT 35510 DATA OUT 10
0
51.27 FBA PAR REFRESH 1 = REFRESH Validates the FDNA-01configuration parameter settings.
1001 EXT1 COMMANDS 10 = COMM Selects the fieldbus interface as thesource of the start and stopcommands for external controllocation 1.
1003 DIRECTION 3 = REQUEST Allows control of rotation direction.
1103 REF1 SELECT 8 = COMM Selects the fieldbus reference 1 asthe source for speed reference.
1604 FAULT RESET SEL 8 = COMM Selects the fieldbus interface as the
source for the fault reset signal.
9904 MOTOR CTRL MODE 2 = VECTOR:TORQ
Selects the vector control mode asthe motor control mode.
1002 EXT2 COMMANDS 10 = COMM Selects the fieldbus interface as thesource of the start and stopcommands for external controllocation 2.
1102 EXT1/EXT2 SEL 8 = COMM Enables external control location1/2 selection through the fieldbus.
1106 REF2 SELECT 8 = COMM Selects the fieldbus reference 2 asthe source for torque reference.
Drive parameter Setting for ACS355 drives
Description
7/28/2019 FDNA-01 1
52/168
52 Start-up
The start sequence for the parameter example above is givenbelow.
Control word:
47Eh (1150 decimal) > READY TO SWITCH ON
47Fh (1151 decimal) > OPERATING (Speed mode)
or
C7Fh (3199 decimal) > OPERATING (Torque mode).
ODVA AC/DC drive profile
The following example shows how to configure the ACS355 driveto use the Extended speed and torque control assembly of theODVA AC/DC drive profile.
The used I/O assembly instances are 23 and 73.
The table below gives the recommended drive parameter settings.
1601 RUN ENABLE 7 = COMM Selects the fieldbus interface as thesource for the inverted Run enablesignal (Run disable).
1) Read-only or automatically detected/set
Drive parameter Setting for ACS355 drives
Description
9802 COMM PROT SEL 4 = EXT FBA Enables communication betweendrive and adapter module.
5101 FBA TYPE DEVICENET1)
Displays the type of the adaptermodule.
5102 FB PAR 2(MAC ID)
5 Defines the MAC ID number of theadapter module.
5103 FB PAR 3(BAUD RATE)
0 (= 125 kbit/s) Sets the baud rate for theDeviceNet interface.
5104 FB PAR 4(DRIVE PROFILE)
0 (= DCU Profile) Selects the profile used in thecommunication between drive andadapter module.
5105 FB PAR 5(ODVA STOP FUNC)
0 (= Ramp) Motor decelerates along the activedeceleration ramp.
Drive parameter Setting for ACS355 drives
Description
7/28/2019 FDNA-01 1
53/168
Start-up 53
5106 FB PAR 6(OUTPUT INSTANCE)
23 Selects the ODVA extended speedand torque control output instance.
5108 FB PAR 8(INPUT INSTANCE)
73 Selects the ODVA extended speedand torque control input instance.
5110 FB PAR 10(ODVA SPEED SCALE)
128 Sets the scaling as 1 rpm for theODVA speed reference.
5111 FB PAR 11(ODVA TORQUE SCALE)
128 Sets the scaling as 1 Nm for theODVA torque reference.
51.27 FBA PAR REFRESH 1 = REFRESH Validates the FDNA-01configuration parameter settings.
1001 EXT1 COMMANDS 10 = COMM Selects the fieldbus interface asthe source of the start and stopcommands for external controllocation 1.
1003 DIRECTION 3 = REQUEST Allows control of rotation direction.
1103 REF1 SELECT 8 = COMM Selects the fieldbus reference 1 asthe source for speed reference.
1604 FAULT RESET SEL 8 = COMM Selects the fieldbus interface as
the source for the fault resetsignal.
9904 MOTOR CTRL MODE 2 = VECTOR:TORQ
Selects the vector control mode asthe motor control mode.
1002 EXT2 COMMANDS 10 = COMM Selects the fieldbus interface asthe source of the start and stopcommands for external controllocation 2.
1102 EXT1/EXT2 SEL 1 = DI1 Selects digital input DI1 as thesource for the external controllocation EXT1/EXT2 selection.
1106 REF2 SELECT 8 = COMM Selects the fieldbus reference 2 asthe source for torque reference.
1601 RUN ENABLE 7 = COMM Selects the fieldbus interface asthe source for the inverted Runenable signal (Run disable).
1) Read-only or automatically detected/set
Drive parameter Setting for ACS355 drives
Description
7/28/2019 FDNA-01 1
54/168
54 Start-up
Note: In this example, digital input DI1 has been configured tocontrol whether to use the speed or torque control mode.
The start sequence for the parameter example above is givenbelow.
Control word: 0h (0 decimal) > READY
1h (1 decimal) > ENABLED (Running forward)
2h (2 decimal) > ENABLED (Running reverse)
Starting up ACSM1 drives
1. Power up the drive.2. Enable the communication between the adapter module and
the drive by setting parameter 50.01 FBA ENABLE to Enable.
3. Ensure that 50.04 FBA REF1 MODESEL is set to Speed and
50.05 FBA REF2 MODESEL is set to Torque.
4. Set the FDNA-01 configuration parameters in parameter group
51.
5. Define the process data transferred to and from the drive in
FDNA-01 parameter groups 52 and 53.
Note: If communication between the FDNA-01 and DeviceNet
master is established, changes to the configuration parameters
can be done also through Fieldbus configuration object 91h.
6. Validate the settings made in parameter groups 51, 52 and 53by setting parameter 51.27 FBA PAR REFRESH to REFRESH.
7. Set the relevant drive control parameters to control the drive
according to the application. Examples of appropriate values
are shown in the tables below.
7/28/2019 FDNA-01 1
55/168
Start-up 55
Parameter setting examples ACSM1
ABB Drives profile
The following example shows how to configure the ACSM1 drive to
use the ABB Drives profile.
The used I/O assembly instances are 902 and 952.
The table below gives the recommended drive parameter settings.
Drive parameter Setting for ACSM1 drives
Description
50.01 FBA ENABLE 1 = Enable Enables communication betweendrive and adapter module.
50.04 FBA REF1MODESEL
Speed Selects speed as the adapter module REF1 type.
50.05 FBA REF2MODESEL
Torque Selects torque as the adapter module REF2 type.
51.01 FBA TYPE DEVICENET1) Displays the type of the adaptermodule.
51.02 FBA PAR2
(MAC ID)
6 Defines the MAC ID number of the
adapter module.51.03 FBA PAR3(BAUD RATE)
0 (= 125 kbit/s) Sets the baud rate for the DeviceNetinterface.
51.06 FBA PAR6(OUTPUT INSTANCE)
902 Selects the ABB Drives profile withspeed and torque plus driveparameters output instance.
51.07 FBA PAR7(OUTPUT NUM PARS)
10 Must always be set to 10, except asprovided inAppendix A Varyingthe number of drive parameters.
51.08 FBA PAR8(INPUT INSTANCE)
952 Selects the ABB Drives profile withspeed and torque plus driveparameters input instance.
51.09 FBA PAR9(INPUT NUM PARS)
10 Must always be set to 10, except asprovided inAppendix A Varyingthe number of drive parameters.
52.01 FBA DATA IN1 117 Motor temp
52.02 FBA DATA IN2 104 Motor current - MSW
52.03 FBA DATA IN3 0 Motor current - LSW
52.04 FBA DATA IN4 107 DC voltage - MSW
7/28/2019 FDNA-01 1
56/168
56 Start-up
52.05 FBA DATA IN5 0 DC voltage - LSW
52.06 FBA DATA IN6 108 Encoder 1 speed - MSW
52.07 FBA DATA IN7 0 Encoder 1 speed - LSW
52.08 FBA DATA IN852.10 FBA DATA IN10
0
53.01 FBA DATA OUT1 2503 Acceleration time - MSW
53.02 FBA DATA OUT2 0 Acceleration time - LSW
53.03 FBA DATA OUT3 2504 Deceleration time - MSW
53.04 FBA DATA OUT4 0 Deceleration time - LSW
53.05 FBA DATA OUT5 2408 Constant speed
53.06 FBA DATA OUT6 2410 Speed ref jog1
53.07 FBA DATA OUT7 2411 Speed ref jog2
53.08 FBA DATA OUT853.10 FBA DATA OUT10
0
51.27 FBA PAR REFRESH 1 = REFRESH Validates the FDNA-01 configurationparameter settings.
10.01 EXT1 START FUNC 3 = FBA Selects the fieldbus interface as thesource of the start and stopcommands for external controllocation 1.
10.04 EXT2 START FUNC 3 = FBA Selects the fieldbus interface as thesource of the start and stopcommands for external controllocation 2.
24.01 SPEED REF1 SEL 3 = FBA REF1 Selects the fieldbus reference 1 as
the source for speed reference 1.
32.01 TORQ REF1 SEL 4 = FBA REF2 Selects the fieldbus reference 2 asthe source for torque reference 1.
34.02 EXT1 MODE 1/2SEL P.2.12.15 =P.FBA MAINCW.15
Selects FBA Control word bit 15 asthe source for the external controllocation EXT1/EXT2 selection.
34.03 EXT1 CTRL MODE1 1 = Speed Selects speed as the control modefor external control location 1.
34.05 EXT2 CTRL MODE1 2 =Torque Selects torque as the control modefor external control location 2.
Drive parameter Setting for ACSM1 drives
Description
7/28/2019 FDNA-01 1
57/168
Start-up 57
The start sequence for the parameter example above is givenbelow.
Control word:
47Eh (1150 decimal) > READY TO SWITCH ON
47Fh (1151 decimal) > OPERATING (Speed mode)
orC7Fh (3199 decimal) > OPERATING (Torque mode).
ODVA AC/DC drive profile
The following example shows how to configure the ACSM1 drive touse the ODVA AC/DC drive profile.
The used I/O assembly instances are 23 and 73.
The table below gives the recommended drive parameter settings.
99.05 MOTOR CTRLMODE
0 = DTC Selects DTC as the motor controlmode.
1) Read-only or automatically detected/set
Drive parameter Setting for ACSM1 drives
Description
50.01 FBA ENABLE 1 = Enable Enables communication betweendrive and adapter module.
50.04 FBA REF1MODESEL
Speed Selects speed as the adapter module REF1 type.
50.05 FBA REF2MODESEL
Torque Selects torque as the adapter module REF2 type.
51.01 FBA TYPE DEVICENET1 Displays the type of the adaptermodule.
51.02 FBA PAR2(MAC ID)
5 Defines the MAC ID number of theadapter module.
51.03 FBA PAR3(BAUD RATE)
0 (= 125 kbit/s) Sets the baud rate for the DeviceNetinterface.
51.06 FBA PAR6(OUTPUT INSTANCE)
23 Selects the ODVA extended speedand torque control output instance.
Drive parameter Setting for ACSM1 drives
Description
7/28/2019 FDNA-01 1
58/168
58 Start-up
Note: In this example, digital input DI1 has been configured tocontrol whether to use the speed or torque control mode.
The start sequence for the parameter example above is givenbelow.
Control word:
0h (0 decimal) > READY
1h (1 decimal) > ENABLED (Running forward)
2h (2 decimal) > ENABLED (Running reverse)
51.08 FBA PAR8(INPUT INSTANCE)
73 Selects the ODVA extended speedand torque control input instance.
51.27 FBA PAR REFRESH 1 = REFRESH Validates the FDNA-01 configurationparameter settings.
10.01 EXT1 START FUNC 3 = FBA Selects the fieldbus interface as thesource of the start and stopcommands for external controllocation 1.
10.04 EXT2 START FUNC 3 = FBA Selects the fieldbus interface as thesource of the start and stopcommands for external control
location 2
24.01 SPEED REF1 SEL 3 = FBA REF1 Selects the fieldbus reference 1 asthe source for speed reference 1.
32.01 TORQ REF1 SEL 4 = FBA REF2 Selects the fieldbus reference 2 asthe source for torque reference 1.
34.01 EXT1/EXT2 SEL P.2.1.0 = PI.DISTATUS.0
Selects digital input DI1 as thesource for the external controllocation EXT1/EXT2 selection.
34.03 EXT1 CTRL MODE1 1 = Speed Selects speed as the control modefor external control location 1.
34.05 EXT2 CTRL MODE1 2 =Torque Selects torque as the control modefor external control location 2.
99.05 MOTOR CTRLMODE
0 = DTC Selects DTC as the motor controlmode.
1) Read-only or automatically detected/set
Drive parameter Setting for ACSM1 drives
Description
7/28/2019 FDNA-01 1
59/168
Start-up 59
Starting up ACS850 and ACQ810 drives
1. Power up the drive.
2. Enable the communication between the adapter module and
the drive by setting parameter 50.01 Fba enable to Enable.
3. Ensure that 50.04 Fb ref1 modesel is set to Speed (both
ACS850 and ACQ810) and 50.05 Fb ref2 modesel is set to
Torque (only ACS850).
4. Set the FDNA-01 configuration parameters in drive parameter
group 51.
5. Define the process data transferred to and from the drive inFDNA-01 parameter groups 52 and 53.
Note: If communication between the FDNA-01 and DeviceNet
master is established, changes to the configuration parameters
can be done also through Fieldbus configuration object 91h.
6. Validate the settings made in parameter groups 51, 52 and 53
by setting parameter 51.27 FBA par refresh to Refresh.
7. Set the relevant drive control parameters to control the drive
according to the application. Examples of appropriate values
are shown in the tables below.
7/28/2019 FDNA-01 1
60/168
60 Start-up
Parameter setting examples ACS850 and ACQ810
ABB Drives profile
The following example shows how to configure the ACS850 or
ACQ810 drive to use the ABB Drives profile.
The used I/O assembly instances are 902 and 952.
The table below gives the recommended drive parameter settings.
Drive parameter Setting for ACS850/ACQ810drives
Description
50.01 Fba enable 1 = Enable Enables communication between
drive and adapter module.
50.04 Fb ref1 modesel Speed Selects speed as the adapter module ref1 type.
50.05 Fb ref2 modesel Torque Selects torque as the adapter module ref2 type (only with
ACS850).
51.01 Fba type DEVICENET1) Displays the type of the adaptermodule.
51.02 FBA par2(MAC ID)
5 Defines the MAC ID number of theadapter module.
51.03 FBA par3(BAUD RATE)
0 (= 125 kbit/s) Sets the baud rate for theDeviceNet interface.
51.06 FBA par6(OUTPUT INSTANCE)
902 Selects the ABB Drives profile withspeed and torque plus driveparameters output instance.
51.07 FBA par7
(OUTPUT NUM PARS)
10 Must always be set to 10, except as
provided inAppendix A Varyingthe number of drive parameters.
51.08 FBA par8(INPUT INSTANCE)
952 Selects the ABB Drives profile withspeed and torque plus driveparameters input instance.
51.09 FBA par9(INPUT NUM PARS)
10 Must always be set to 10, except asprovided inAppendix A Varyingthe number of drive parameters.
52.01 FBA data in1 123 Motor power 52.02 FBA data in2 0 Motor power - LSW
7/28/2019 FDNA-01 1
61/168
Start-up 61
52.03 FBA data in3 105 Motor current percent
52.04 FBA data in4 107 DC voltage
52.05 FBA data in5 0 DC voltage - LSW
52.06 FBA data in6 108 Encoder1 speed
52.07 FBA data in7 0 Encoder 1 speed - LSW
52.08 FBA data in852.10 FBA data in10
0
53.01 FBA data out1 2204 Acc time 2
53.02 FBA data out2 0 Acceleration time 2 - LSW
53.03 FBA data out3 2205 Dec time 2
53.04 FBA data out4 0 Deceleration time 2 - LSW
53.05 FBA data out5 2606 Const speed1
53.06 FBA data out6 2607 Const speed2
53.07 FBA data out7 2608 Const speed3
53.08 FBA data out853.10 FBA data out10
0
51.27 FBA par refresh 1 = Refresh Validates the FDNA-01configuration parameter settings.
10.01 Ext1 start func FB Selects the fieldbus interface as thesource of the start and stopcommands for external controllocation 1.
10.04 Ext2 Start func 3 = FB Selects the fieldbus as the source
for start and stop commands forexternal control location EXT2 (onlywith ACS850).
12.01 Ext1/Ext sel P.2.22.15 = P.FBAmain cw.15
Selects FBA Control word bit 15 asthe source for external controllocation EXT1/EXT2 selection (onlywith ACS850).
12.03 Ext1 ctrl mode 1 = Speed Selects speed as the operatingmode for external control locationEXT1.
Drive parameter Setting for ACS850/ACQ810drives
Description
7/28/2019 FDNA-01 1
62/168
62 Start-up
The start sequence for the parameter example above is givenbelow.
Control word:
47Eh (1150 decimal) > READY TO SWITCH ON
47Fh (1151 decimal) > OPERATING (Speed mode)or
C7Fh (3199 decimal) > OPERATING (Torque mode in
ACS850).
12.05 Ext2 ctrl mode 2 = Torque Selects torque as the operatingmode for external control location
EXT2 (only with ACS850).
16.15 Menu set sel(ACS850)16.21 Menu selection(ACQ810)
2 = Load long(ACS850)2= Full (ACQ810)
Load long parameter list. Allparameters will be displayed.
21.01 Speed ref1 sel FB Selects the fieldbus reference 1 asthe source for speed reference 1.
24.01 Torq ref1 sel FBA ref2 Selects fieldbus reference 2 as thesource of the torque reference 1
(only with ACS850).1) Read-only or automatically detected/set
Drive parameter Setting for ACS850/ACQ810drives
Description
7/28/2019 FDNA-01 1
63/168
Start-up 63
ODVA AC/DC drive profile
The following example shows how to configure the ACS850 orACQ810 drive to use the ODVA AC/DC drive profile.
The used I/O assembly instances are 23 and 73.
The table below gives the recommended drive parameter settings.
Drive parameter Setting for ACS850/ACQ810drives
Description
50.01 Fba enable 1 = Enable Enables communication betweendrive and adapter module.
50.04 Fb ref1 modesel Speed Selects speed as the adapter
module ref1 type.
50.05 Fb ref2 modesel Torque Selects torque as the adapter module ref2 type (only with
ACS850).
51.01 FBA type DEVICENET1) Displays the type of the adaptermodule.
51.02 FBA par2(MAC ID)
5 Defines the MAC ID number of theadapter module.
51.03 FBA par3(BAUD RATE)
0 (= 125 kbit/s) Sets the baud rate for theDeviceNet interface.
51.06 FBA par6(OUTPUT INSTANCE)
23 Selects the ODVA AC/DC driveprofile output instance.
51.08 FBA par8(INPUT INSTANCE)
73 Selects the ODVA AC/DC profileinput instance.
51.27 FBA par refresh 1 = Refresh Validates the FDNA-01configuration parameter settings.
10.01 Ext1 start func 3 = FB Selects the fieldbus interface as thesource of the start and stopcommands for external controllocation 1.
10.04 Ext2 Start func 3 = FB Selects the fieldbus as the sourcefor start and stop commands forexternal control location EXT2 (onlywith ACS850).
7/28/2019 FDNA-01 1
64/168
64 Start-up
Note: For ACS850 in this example, digital input DI1 has been
configured to control whether to use the speed or torque controlmode.
The start sequence for the parameter example above is givenbelow.
Control word:
0h (0 decimal) > READY
1h (1 decimal) > ENABLED (Running forward)
2h (2 decimal) > ENABLED (Running reverse)
12.01 Ext1/Ext2 sel DI1 Selects digital input DI1 as thesource for external control location
EXT1/EXT2 selection (only withACS850).
12.05 Ext2 ctrl mode 2 = Torque Selects torque as the operatingmode for external control locationEXT2 (only with ACS850).
16.15 Menu set sel(ACS850)16.21 Menu selection(ACQ810)
2 = Load long(ACS850)1= Full (ACQ810)
Load long parameter list. Allparameters will be displayed.
21.01 Speed ref1 sel FBA ref1 Selects the fieldbus reference 1 asthe source for speed reference 1.
24.01 Torq ref1 sel FBA ref2 Selects fieldbus reference 2 as thesource of the torque reference 1(only with ACS850).
1) Read-only or automatically detected/set
Drive parameter Setting for ACS850/ACQ810drives
Description
7/28/2019 FDNA-01 1
65/168
Start-up 65
Starting up ACS880 drives
This example sets up the fieldbus adapter installed as fieldbusadapter A. To set up the fieldbus adapter B, perform the sametasks with the corresponding parameters in parameter groups 50,
54, 55, and 56.1. Power up the drive.
2. Enable the communication between the adapter module and
the drive by setting parameter 50.01 FBA A enable to Enable.
3. Ensure that parameter 50.04 FBA A ref1 type is set to Speed
and parameter 50.05 FBA A ref2 type is set to Torque.
4. Set the FDNA-01 configuration parameters in drive parameter
group 51.
5. Define the process data transferred to and from the drive in
FDNA-01 parameter groups 52 and 53.
Note: If communication between the FDNA-01 and DeviceNet
master is established, changes to the configuration parameters
can be done also through Fieldbus configuration object 91h.6. Validate the settings made in parameter groups 51, 52 and 53
by setting parameter 51.27 FBA par refresh to Refresh.
7. Set the relevant drive control parameters to control the drive
according to the application.
Examples of appropriate values are shown in the tables below.
Parameter setting examples ACS880
ABB Drives profile
The following example shows how to configure the ACS880 driveto use the ABB Drives profile.
The used I/O assembly instances are 902 and 952.
7/28/2019 FDNA-01 1
66/168
66 Start-up
The table below gives the recommended drive parameter settings.
Drive parameter Setting for ACS880 drives
Description
50.01 FBA A enable 1 = Enable Enables communication betweendrive and adapter module.
50.04 FBA A ref1 type 4 = Speed Selects speed as the fieldbus Areference 1 type.
50.05 FBA A ref2 type 3 = Torque Selects torque as the fieldbus Areference 2 type.
51.01 FBA type DeviceNet1) Displays the type of the adaptermodule.
51.02 MAC ID 6 Defines the MAC ID number of theadapter module.
51.03 Baud rate 0 = 125kbit/s Sets the baud rate for the DeviceNetinterface.
51.06 Output instance 902 Selects the ABB Drives profile withspeed and torque plus driveparameters output instance.
51.07 Output num pars 10 Must always be set to 10. For exceptions, seeAppendix A
Varying the number of driveparameters.
52.01 FBA data in1 1.7 Motor current - MSW
52.02 FBA data in2 0 = None Motor current - LSW
52.03 FBA data in3 1.11 DC voltage - MSW
52.04 FBA data in4 0 = None DC voltage - LSW
52.05 FBA data in5
52.10 FBA data in10
0 = None
53.01 FBA data out1 23.12 Acceleration time - MSW
53.02 FBA data out2 0 = None Acceleration time - LSW
53.03 FBA data out3 23.13 Deceleration time - MSW
53.04 FBA data out4 0 = None Deceleration time - LSW
53.05 FBA data out553.10 FBA data out10
0 = None
51.27 FBA par refresh 1 = Configure Validates the FDNA-01 configurationparameter settings.
7/28/2019 FDNA-01 1
67/168
Start-up 67
The start sequence for the parameter example above is givenbelow.
Control word:
47Eh (1150 decimal) > READY TO SWITCH ON
47Fh (1151 decimal) > OPERATING (Speed mode)
or
C7Fh (3199 decimal) > OPERATING (Torque mode)
ODVA AC/DC drive profile
The following example shows how to configure the ACS880 driveto use the ODVA AC/DC drive profile.
The used I/O assembly instances are 23 and 73.
19.11 Ext1/Ext2 selection 2 = MCW bit11: Extctrl
Selects FBA Control word bit 11 asthe source for the external controllocation EXT1/EXT2 selection.
19.12 Ext1 control mode 1 2 = MCW bit11: Extctrl loc
Selects speed control as the controlmode 1 for external control locationEXT1.
19.14 Ext2 control mode 1 3 = Torque Selects torque control as the controlmode 1 for external control locationEXT2.
20.01 Ext1 commands 12 = Fieldbus A Selects fieldbus interface A as thesource of the start and stopcommands for external control
location EXT1.
20.06 Ext2 commands 12 = Fieldbus A Selects fieldbus interface A as thesource of the start and stopcommands for external controllocation EXT2.
22.11 Speed ref1selection
4 = FB A ref1 Selects fieldbus A reference 1 as thesource for speed reference 1.
26.11 Torque ref1selection
5 = FB A ref2 Selects fieldbus reference 2 as thesource for torque reference 1.
1) Read-only or automatically detected/set2) Example
Drive parameter Setting for ACS880 drives
Description
7/28/2019 FDNA-01 1
68/168
68 Start-up
The table below gives the recommended drive parameter settings.
Drive parameter Setting for ACS880 drives
Description
50.01 FBA A enable 1 = Enable Enables communication betweendrive and adapter module.
50.04 FBA A ref1 type 4 = Speed Selects Speed as the fieldbus Areference 1 type.
50.05 FBA A ref2 type 3 = Torque Selects Torque as the fieldbus Areference 2 type.
51.01 FBA type DeviceNet1) Displays the type of the adaptermodule.
51.02 MAC ID 6 Defines the MAC ID number of theadapter module.
51.03 Baud rate 0 = 125kbit/s Sets the baud rate for the DeviceNetinterface.
51.06 Output instance 23 Selects the ABB Drives profile withspeed and torque plus driveparameters output instance.
51.07 Output num pars 10 Must always be set to 10. For exceptions, see