TABThe Engineering Company for Testing and Balancing Services
UG Floor 1 RSCD 1 N/A 433 N/A 410 95%
UG Floor 2 RSCD 1 N/A 433 N/A 380 88%
UG Floor 3 RSCD 1 N/A 433 N/A 415 96%
1299 1205 93% 93%
UG Floor 1 RSCD 1 N/A 545 N/A 450 83%
UG Floor 2 RSCD 1 N/A 545 N/A 360 66%
UG Floor 3 RSCD 1 N/A 545 N/A 425 78%
1635 1235 76% 76%
UG Floor 1 RSCD 1 N/A 515 N/A 380 74%
UG Floor 2 RSCD 1 N/A 515 N/A 320 62%
UG Floor 3 RSCD 1 N/A 515 N/A 445 86%
1545 1145 74% 74%
UG Floor 1 RSCD 1 N/A 515 N/A 400 78%
UG Floor 2 RSCD 1 N/A 515 N/A 340 66%
UG Floor 3 RSCD 1 N/A 515 N/A 380 74%
1545 1120 72% 72%
UG Floor 1 RSCD 1 N/A 475 N/A 410 86%
UG Floor 2 RSCD 1 N/A 475 N/A 150 32%
UG Floor 3 RSCD 1 N/A 475 N/A 375 79%
UG Floor 3 RSCD 1 N/A 475 N/A 475 100%
1900 1410 74% 74%
UG Floor 1 RSCD 1 N/A 433 N/A 320 74%
UG Floor 2 RSCD 1 N/A 433 N/A 350 81%
UG Floor 3 RSCD 1 N/A 433 N/A 430 99%
1299 1100 85% 85%
UG Floor 1 RSCD 1 N/A 433 N/A 300 69%
UG Floor 2 RSCD 1 N/A 433 N/A 355 82%
UG Floor 3 RSCD 1 N/A 433 N/A 290 67%
1299 945 73% 73%
UG Floor 1 RSCD 1 N/A 650 N/A 450 69%
UG Floor 2 RSCD 1 N/A 650 N/A 360 55%
1300 810 62% 62%
TEST DATE:
READINGS BY:
Equipment Area Served
Terminal (inlet/outlet) Design Final
No Type Size (inch) AK* Velocity FPM Flow CFM Velocity FPM Flow CFM
FCU-6-1 Ø14
FCU-6-1 Ø 14
FCU-6-1 Ø14
FCU-6-1 Total air flow rate
FCU-9-2 Ø14
FCU-9-2 Ø 14
FCU-9-2 Ø14
FCU-9-2 Total air flow rate
FCU-8-3 Ø14
FCU-8-3 Ø 14
FCU-12-5 Ø14
FCU-8-3 Ø14
FCU-8-3 Total air flow rate
FCU-8-4 Total air flow rate
FCU-12-5 Ø14
FCU-12-5 Ø 14
FCU-12-5 Ø14
FCU-7-5 Total air flow rate
FCU-6-6 Ø14
FCU-6-6 Ø 14
FCU-6-6 Ø14
FCU-6-6 Total air flow rate
FCU-6-7 Ø14
FCU-6-7 Ø 14
FCU-6-7 Ø14
FCU-6-7 Total air flow rate
* Note: If AK = 1.00, velocity information and measurments are not required.
Remarks
FCU-6-8 Ø14
FCU-6-8 Ø 14
FCU-6-8 Total air flow rate
8-Aug-15Eng. Mohamed Azzam
FCU-8-4 Ø14
FCU-8-4 Ø 14
FCU-8-4 Ø14
Form: TAB 11-98 Page :1/1