Fans InPower Plants

Embed Size (px)

Citation preview

  • 7/30/2019 Fans InPower Plants

    1/48

    Fans in Power Stations

    PMI

  • 7/30/2019 Fans InPower Plants

    2/48

    Power Plant Schematic

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 2

  • 7/30/2019 Fans InPower Plants

    3/48

    Need of Fans

    BoilerCombustion Air Flue Gases

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 3

    Air needed for combustion

    Flue are needed to be evacuated

    Losses due to flow need to be overcome

  • 7/30/2019 Fans InPower Plants

    4/48

    Fan Operation

    Fans cause pressure increase by:

    Centrifugal force created by rotation of thecolumn of air trapped between two bladesKinetic energy is supplied to the air through

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 4 4

    e mpe erTotal pressure = velocity head + staticpressure

  • 7/30/2019 Fans InPower Plants

    5/48

    Selection Considerations

    Quantity of air to be moved per unit time

    Estimated system resistance andexpected variationsAmount of noise ermitted

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 5 5

    Space available for fanEconomic implications

  • 7/30/2019 Fans InPower Plants

    6/48

    SYSTEM RESISTANCE

    When a gas is forced through a duct

    system, a loss in pressure occurs. Thisloss in pressure is called systemresistance.

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 6

    System resistance is composed of twocomponents:Friction losses andDynamic losses.

  • 7/30/2019 Fans InPower Plants

    7/48

    Variation of System Resistance with Flow

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 7

  • 7/30/2019 Fans InPower Plants

    8/48

    Draft Losses

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 8

    Total losses

    p

    Percent Boiler Rating

    Furnace, SH & RH Losses

    Economizer Losses

    Ducts & dampers losses

  • 7/30/2019 Fans InPower Plants

    9/48

    Fan Classification

    Designated as dynamic pumpsCentrifugal

    Further classification by entry and exit of fluid/gas throughimpeller

    4 aerodynamic classifications:

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 9 9

    Axial flowRadial flow : referred to as centrifugal fanCross flow

    Mixed flow

  • 7/30/2019 Fans InPower Plants

    10/48

    Centrifugal Fans

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 10

  • 7/30/2019 Fans InPower Plants

    11/48

    Components of Centrifugal Fan

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 11

  • 7/30/2019 Fans InPower Plants

    12/48

    Centrifugal Fan Operation

    Fans cause a pressure increase through two methods Centrifugal force is created by the rotation of the column of airtrapped between two blades. Kinetic energy is supplied to the air through the impeller Total pressure = velocity head + static pressure

    Blades are airfoil-type, backward-curved, forwardcurved, or radial

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 12

    Airfoil-types are complex and expensive but very efficient;

    theyre used for large systems where the cost is justified.

  • 7/30/2019 Fans InPower Plants

    13/48

    Wheel Blade Types and Rotation

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 13

    Applications where the fans will handle clean air or clean gas, the highlyefficient backward inclined airfoils are the preferred design. In anapplication where the fan is subject to erosion due to heavy dustloading, a straight radial type fan provides erosion resistance, but at theexpense of efficiency.

  • 7/30/2019 Fans InPower Plants

    14/48

    Backward-Curved Fan Blades

    Have a self-limiting power characteristic,so if sized correctly the motor wontoverheat or burn out even if conditionschange.High efficiency and stable operationmake this blade type popular.

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 14

    the right of the peak pressure flow rate toachieve both high efficiency and a stableflow rate.This type of fan operates stably because

    the pressure difference provided by thefan drops if the flow rate goes up. If theopposite were true, increased anincreased flow rate would cause increasefan power, which is unstable.

  • 7/30/2019 Fans InPower Plants

    15/48

    Section of a Centrifugal Fan

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 15

  • 7/30/2019 Fans InPower Plants

    16/48

    Radial BladesSimilar performance to abackward-curved except that itseasier to overheat because as flowrate goes up, so does power.

    Easier to maintain, so its used indirty situations (easy to cleanstraight blades, and they dontcollect as much)

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 16

    a es are s ronger an o ertypes.Used primarily in industrial systemsin a corrosive or erosiveenvironment, such as materialhandling of airborne particulate orwhere high static pressure isrequired.

  • 7/30/2019 Fans InPower Plants

    17/48

    Airfoil-blade centrifugal fan

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 17

  • 7/30/2019 Fans InPower Plants

    18/48

    Forward-Curved Blades

    Have problems with instabilitybecause a specified pressure

    rise can fit three different flowrates.Burnout can also be a

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 18

    increases with flow rate.Quieter than other fans; usedfor most furnace blowers

    Usually limited to cleanservice applications

  • 7/30/2019 Fans InPower Plants

    19/48

    Axial Flow Fans

    Common types: propeller,tubeaxial, vaneaxialTubeaxial: impeller is inside a tubeto guide airflow and improveperformanceVaneaxial: like a tubeaxial except

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 19

    the impeller are used to reduceswirl and improve performanceUsed to deliver large flow rates butsmall increase in pressure

    Examples include fans used forventilation without ductwork, mobileroom fans, and fans used to coolcomputers

  • 7/30/2019 Fans InPower Plants

    20/48

    Two-Stage Axial Fan Assembly

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 20

  • 7/30/2019 Fans InPower Plants

    21/48

    Axial-flow fan for induced-draft service

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 21

  • 7/30/2019 Fans InPower Plants

    22/48

    System Pressure Effects

    Fan curves are typically given in terms of total pressure vs.volumetric flow rateA typical fan running at a fixed speed can provide a greatervolumetric flow rate for systems with smaller total pressure drops (ifwere to the right of the peak in the fan curve).Total pressure loss=static pressure loss+dynamic pressure loss

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 22

    If exit and inlet area of a duct are about the same, the dynamicpressure loss (or gain) may be minimal.

  • 7/30/2019 Fans InPower Plants

    23/48

    Effect of Blade Type on Erosion

    Resistance and Efficiency

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 23

  • 7/30/2019 Fans InPower Plants

    24/48

    Fan Curves

    Manufacturer will provide a fan curve for each fanThe fan curves predict the pressure-flow rate

    performance of each fan.Choose a fan that gives you the volumetric flow rate youneed for your system pressure drop.

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 24

    Choose a fan that has its peak efficiency at or near youroperating point.Sometimes will provide data in a table rather than in agraph.

  • 7/30/2019 Fans InPower Plants

    25/48

    Centrifugal Fan Performance Curve.

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 25

  • 7/30/2019 Fans InPower Plants

    26/48

    Fan Laws

    Flow ? Speed Pressure ? (Speed) 2 Power ? (Speed)3

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 26

    1 1

    2 2

    Q N

    Q N =

    21 1

    2 2

    SP N

    SP N

    =

    31 1

    2 2

    kW N

    kW N

    =

    Varying the RPM by 10%

    decreases or increases air delivery by 10%.

    Varying the RPM by 10%

    decreases or increases the static pressure by 19%.

    Varying the RPM by 10%

    decreases or increases the power requirement by

    27%.Where Q flow, SP Static Pressure, kW Power and N speed (RPM)

  • 7/30/2019 Fans InPower Plants

    27/48

    Fan Laws

    Law 1 relates to effect of changing size, speed, or density onvolume flow, pressure, and power levelLaw 2 relates to effect of changing size, pressure, or density onvolume flow rate, speed, and powerLaw 3 shows effect of changing size, volume flow, or density onspeed, pressure, and power

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 27

    e aws on y app y to aero ynam ca y s m ar ans at t e samepoint of rating on the performance curve.

  • 7/30/2019 Fans InPower Plants

    28/48

    Fan Applications in Power Plant

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 28

  • 7/30/2019 Fans InPower Plants

    29/48

    Scheme of Air and Gas Path

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 2913 June 2011 PMI Revision 00 29

  • 7/30/2019 Fans InPower Plants

    30/48

    Draught System Pressure Variation

    Pressure drop calculation in air & gas path and itscomparison with design value.Assessment of ID and FD fan power as a function of

    furnace pressure.Assessment of effective kinetic rate coefficient as afunction of furnace pressure.

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 30

    FDFan

    Duct APH Duct F urnace Duct APHBackpass

    ESP IDFan

    Chimney D u c

    t D u c

    t

  • 7/30/2019 Fans InPower Plants

    31/48

    Pressure Variation

    Furnace Pressure At Various Points in Boiler

    50

    100

    150

    200

    250

    1 FD Fan Inlet

    2FD Fan Outlet

    3 Airheater Inlet

    4 Airheater Outlet

    5Windbox Pressure

    6 Furnace

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 31

    -300

    -250

    -200

    -150

    -100

    -50

    0

    1 2 3 4 5 6 7 8 9 10 11 12 13 14

    Points in Boiler

    F u r n a c e

    P r e

    s s u r

    7Superheater Platen Inlet

    8Reheater Inlet

    9 LTSH Inlet

    10 Economiser Inlet

    11 Airheater Inlet

    12 E.P. Inlet

    13 I.D. Fan Inlet

    14I.D. Fan Outlet

  • 7/30/2019 Fans InPower Plants

    32/48

    Induced Draft Fans

    Move the combustion flue gas through the boiler, air heater, andprecipitator or the baghouse, scrubber, and chimney to theatmospheretypically consume approximately 2% of the gross electrical output.ID fans have the largest design margins of any major equipment in afossil-fueled power plant. typically 15% on flow, 30% on head, and

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 32

    .Large margins are intended to allow for the following

    Uncertainty in determining system requirementsAllowance for wearOperating flexibility

    Allowance for pluggage and leakageAir infiltration

  • 7/30/2019 Fans InPower Plants

    33/48

    Gas to be handled by ID fan

    Theoretical air for combustion

    Excess air required at burnerInfiltration- -

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 33

  • 7/30/2019 Fans InPower Plants

    34/48

    Forced Draft & PA Fans

    FD fans provide combustion air for boilersIn pulverized coal-fired boilers, approximately one-third

    of the combustion air is PA that is used to transport thepulverized coal to the burners.The PA fan application is similar to the FD fan;

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 34

    The FD fans for a coal-fired plant consumeapproximately 0.7% of the gross electrical output.The design margins on FD fans are typically smaller thanthe margins on ID fans but still larger than on other major

    equipment. Margins of 15% on flow and 30% on head atthe maximum expected ambient temperature arecommon.

  • 7/30/2019 Fans InPower Plants

    35/48

    Two-Stage Axial Fan Impeller

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 35

  • 7/30/2019 Fans InPower Plants

    36/48

    Balanced Draft

    The draft to be provided by the fan is determinedby losses through the following boiler

    components:FurnaceBoiler and Super-heater

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 36

    EconomizerAir heaterPrecipitator or Bag-house

    DuctworkFlue gas desulfurization system (scrubber)Stack

  • 7/30/2019 Fans InPower Plants

    37/48

    Other Fans in The System

    Ignitor Air Fan : Provide combustion air to theignitors. Take suction air from the atmosphere andsupplies air to the ignitor wind box.Scanner Air Fan : Supplies cooling air to flamescanners. Normally there are two fans taking suctionfrom FD Fan discharge duct.

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 3713 June 2011 PMI Revision 00 37

    Mill Seal air fan : Seal air fans provide air for thesealing of Mill bearing. Suction is from cold Primaryair and pressure is boosted up to maintain thedifferential pressure

  • 7/30/2019 Fans InPower Plants

    38/48

    Fan ControlsInlet Vanes

    Inlet vanes introduce a swirl to the flow entering a fan.The major disadvantage of inlet vanes is poor efficiency at lower loads.

    Inlet vanes are subject to erosion if ash concentrations are high

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 38

  • 7/30/2019 Fans InPower Plants

    39/48

    Inlet Dampers

    Inlet dampers control air flow by introducing aswirl in the flow and pressure drop.Inlet dampers have a low initial cost, are simple,and are not as prone to erosion as inlet vanes.

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 39

    outside the duct.The biggest disadvantage of inlet dampers istheir low efficiency at low loads.

  • 7/30/2019 Fans InPower Plants

    40/48

    Two-Speed Motors

    The fan selection with two-speed motors isthe same as with inlet vane control or inletdamper control. The fans for two-speedmotors are often sized so that the fan can

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 40

    opera e on ow spee a u oa an a normal operating temperature. The highspeed provides the design margin.

  • 7/30/2019 Fans InPower Plants

    41/48

    Fluid Drive

    Fluid drive is a method of varying the fan speed for flow control.The fan selection is essentially the same as the inlet damperalternative, except that a fluid drive is located between the motorand the fan to control the fan speed.Inlet dampers are typically used in addition to the fluid drive to

    increase the speed of response to avoid furnace pressure

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 41

    The use of the dampers for control during normal operation is typicalbut can be eliminated in most installations.Using speed control with the dampers full open can result in asignificant power savings

  • 7/30/2019 Fans InPower Plants

    42/48

    Hydraulic Coupling

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 42

  • 7/30/2019 Fans InPower Plants

    43/48

    Variable-Speed Motors

    Variable-speed motors are directly connected to the fan.The speed of the motor is continuously variable from approximately

    10% up to the full speed.Synchronous or induction motors can be used with variable

    frequency drives, and the frequency of the power to the motor iscontrolled by an electronic system.

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 43

    e ncom ng ac power s converte to a usta e vo tage c powerby a thyristor.The adjustable dc power is connected to an inverter, which converts

    it to an adjustable ac power output.

  • 7/30/2019 Fans InPower Plants

    44/48

    Variable-Pitch Blades (For Axial Fans )

    Axial fans can be controlled by varying the blade pitch or speed orby using variable inlet vanes.Either varying the blade pitch or using variable inlet vanes controlsthe flow by operating on the same principle as do variable inletvanes on a centrifugal fan.Varying the blade pitch is more efficient than using variable inlet

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 44

    .

    Variable-pitch blades can provide efficiency as high as that ofvariable-speed control over most of the load range for a lower initialcost.Variable-pitch blades are the most common method of control;

    variable inlet vanes are used occasionally, and variable-speedcontrol is rare.

  • 7/30/2019 Fans InPower Plants

    45/48

    Variable-Pitch Axial Fan Components

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 45

  • 7/30/2019 Fans InPower Plants

    46/48

    Bearings

    Both centrifugal and axial fans can use eitherball or roller bearings; however, ball and roller

    bearings are more common on axial fans.Sliding contact bearings are more common oncentrifu al fans.

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 46

    Ball and roller bearings consist of four majorcomponents:

    Outer race

    Inner race Rolling elements Spacer for the rolling elements

  • 7/30/2019 Fans InPower Plants

    47/48

    Sleeve Bearing Components

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 47

    b

  • 7/30/2019 Fans InPower Plants

    48/48

    Lubrication Systems

    Static lubrication in which each bearing has a fixed supply of oil intheir sumps is very common.This method is simple and very cost-effective; however, it relies onoperator vigilance to detect low oil levels or poor oil quality.Use of temperature sensors to provide remote warning to the controlroom operators, in case of a hot bearing, offers added protection for

    Chapter 1: Basic ConceptsESOE 505221 Fluid Mechanics 48

    .

    A gear pump attached to the input shaft of the driver is a secondmethod used to provide lube oil to fan and motor bearings.A third method, the use of fluid drives to supply oil to the bearings,

    is also used on some fans.

    A fourth method involves the use of a dedicated circulating lube oilsystem.