    Bulletin 00

    The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552

    Model DH80Model DH80 RecessedModel DH80 ConcealedQuick Response,Extended Coverage Sprinkler

    DH80ConcealedwithSWCcover plate

    DH80 FP RecessedDH80

    For coverages up to 28 feet wide and

    14 feet long. * 250 psi (17,2 bar) Rated.

    Features:1.   Coverage for long and narrow spaces such

    as hallways, corridors, decks and roomsup to 28 feet wide and 14 feet long.*

    2.   Deflector to ceiling dimensions are:4 (100mm) min. to 12 (305mm) max.

    3.   Minimum spacing between sprinklers12 feet (3,6m).

    4.   UL Listed for light hazard applications.

    5.   8.0 K Factor.6.   Sprinkler is approved for250 psi (17,2 bar) applications.

    7.   Quick response performance.8.   ½ (13mm) adjustment of escutcheon

    and cover.9.   Rugged, damage resistant assembly.

    No exposed thermal element with theconcealed version.

    10. Push-on/thread-off sturdy convenientescutcheon for recessed and cover forconcealed.

    11. Factory assembled sprinkler & cup,shipped complete with protective cap forconcealed version.

    12. Sprinkler & cup assembly and escutcheonor cover are separately packaged.

    13. Cover finishes available in standard whitepaint, special bronze, black paint or flatwhite paint.

    14. Patent Pending

    * See Figure 3

    Approval Organizations

    •  Listed by Underwriters Laboratories Inc. andUL certified for Canada (cULus)

    Products DescriptionThe Model DH80 family of sprinklers are quick response

    extended coverage sidewall sprinklers for use in light hazardapplications. The Model DH80 with SWC cover plate is aconcealed sprinkler that uses Reliable’s push on/thread offsidewallcover.Thissprinklerhasthecupfactorymounted andis shipped with a protective cap that protects the 3mmfrangible glass bulb during shipping and post installationfinishing operations. The DH80 can be combined in the field

    with the FP or F2 Escutcheon to make a recessed sprinkler.The SWC cover plate, FPand F2recessedescutcheons have½” adjustment. The SWC cover plate is attached with

    135-degree solder. In the event of a fire the rising ambientemperature melts the solder and the cover plate is ejectedawayby springsexposing the 3mm frangible glassbulb. Theuse of a 3mm bulb allows quick response which enables thesprinkler to apply water to a fire sooner than standardresponse sprinkles of the same temperature rating.

    ApplicationThe Model DH80 is a horizontal sidewall sprinkler intended

    for installation in light hazard occupancies in accordance withNFPA 13. These sprinklers are designed to provide fireprotection in long and narrow spaces such as hallwayscorridors, decks and rooms up to 28 feet (8,5m) wide and 14feet(4,3m)long. Theyare rated for 250 psi (17,2 bar)and canbe mounted between 4 and 12 inches (102 and 305mm

    down from the ceiling.Installation

    DH80 Recessed, FP EscutcheonTo install the DH80 with the FP Escutcheon as a recessed

    sprinkler cut a 2   5 8 diameter hole in the wall as shown inFig.5. Thread the DH80 into the cup hand tight, then use theGFR1 wrench to tighten the sprinkler until secured. NOTEThe GFR1 wrench has a notch in it to accommodate thedeflector top. This wrench can only be inserted one wayCare must be taken not to damage the deflector duringtightening. Apply a Teflon* based sealant to the sprinklethreads before installing in the fitting. When inserting o

    DH80 F2 Recessed

  • 8/18/2019 Extended Coverage

    2/4

    (1)Other colors and finishes are available. Consult factory for details.

    Note: Paint or any other coatings applied over the factory finishwill void all approvals and warranties.

    Standard Finishes(1)

    Sprinkler FP Escutcheon F2 Escutcheon CoverPlate

    White/ Chrome / Raw Bronze

      White / Chrome   White / Chrome / Bright Brass

      White

    Finishes (1)

    Approval Type:•   Quick Response, Extended Coverage.

    •   Approved for installation in accordance with NFPA 13for Light hazard occupancies.

    UL Listing CategorySprinklers, Automaticand Open.Quick Response Sprinklers.

    Installation WrenchModel GFR1 Sprinkler Wrench

    Installation AidForconcealed, a protective plastic

    cap is included for use duringinstallation.

    Escutcheon Data:FP cup/escutcheonassembly- 12(13mm)adjustmentF2 -  1 2 (13mm) adjustment

    DuPont Registered Trademark

    K Factor

    ThreadSize

    TemperatureRating

    MaximumAmbientTemperature

    Sprinkler

    IdentificationNumber(SIN)US Metric Sprinkler

    SWCCover

    8.0 115,3   3 4

    155°F(68°C)135°F(57C)

    135°F(57°C)

    100°F(38°C)

      RA0362

    Technical Data*:

    *Minimum spacing of 12 feet (3,7m).

    removing the wrench from the sprinkler cup, care must betaken to prevent damage to the sprinkler. Wrench only onthe square boss. DO NOT WRENCH ON ANY OTHERPART OF THE SPRINKLER. It is recommended that thesprinkler be protected during plastering and paintingoperations by using the protective cap P/N 6802710003.These must be orderedseparately. Installationis completedby removing the protective cap and inserting the push-onEscutcheon. Turn to adjust the Escutcheon.

    DH80 Recessed, F2 Escutcheon

    To install the DH80 with the F2 Escutcheon as a recessedsprinkler cut a 2 ¼” diameter hole in the wall as shown inFigure 2. Thread the DH80 into the collar hand tight. Apply aTeflon* based sealant to the sprinkler threads and install inthe fitting. Wrench only on the square boss. NOTE: TheGFR1wrench has a notch init toaccommodate the deflectortop. This wrench can only be inserted one way. Wheninserting or removing the wrench from the sprinkler cup caremust be taken to prevent damage to the sprinkler. DO NOTWRENCH ON ANY OTHER PART OF THE SPRINKLER. It isrecommended that the sprinkler be protected duringplastering and painting operations by using the protectivecap P/N 6999991009. These must be ordered separately.Installationis completedby removing theprotective cap andinserting the F2 Escutcheon over the collar.

    DH80 with SWC Cover Plate ConcealedToinstall the sprinkler,cut a 2 5 8diameterhole into thewall

    as shown in Fig.1. A Teflon* based thread sealant should beapplied to the sprinkler threads only. Remove the protectivecap (P/N 6802710003) and then position the GFR1 wrenchinto thesprinkler/cup assembly until thewrenchengages theflats of the square boss. Then tighten the sprinkler into thepipe fitting. When inserting or removing the wrench from thesprinkler/cup assembly, care should be taken to preventdamage to the sprinkler. DO NOT WRENCH ON ANYOTHER PART OF THE SPRINKLER. The protective capsshould be reinstalled for protection during plastering andpainting. Remove caps only when covers are beinginstalled.The cover assembly is then pushed onto the cup.

    Cover assemblies provide ½ (13mm) of adjustment. Finaladjustment is made by turning the cover clockwise until theskirt flange makes full contact with the wall surface. Coverremovalrequiresturningin thecounter-clockwisedirection.

    Concealed cover/cup assemblies are listed only for usewith specific sprinklers. The use of any other concealedcover/cup assembly with theModel DH80 Horizontal SidewallSprinkler or the use of the concealed cover assembly on anysprinkler with which it is not specifically listed will void allguarantees, warranties, listings and approvals.

    Ordering Information

    Specify:

    •   DH80- Sprinkler Finish

    •  DH80 Recessed-Sprinkler FinishFP or F2 Escutcheo

    -Escutcheon Finish

    •  SWC Concealed-Cover-Plate Finish

    •  Protective cap foruse with F2 or FPescutcheons

    MaintenanceModel DH80 should be inspected quarterly and the

    sprinkler maintained in accordance with NFPA 25. Do notclean sprinklers with soap and water, ammonia or anyother cleaning fluids. Removedust byusing a softbrush orgentlevacuuming. Remove anysprinkler/coverassembly,which has been painted (other than factory applied) ordamaged in any way. A stock of spare sprinklers shouldbe maintained to allow quick replacement of damaged oroperated sprinklers. Prior to installation, sprinklers should

    be maintained in their original cartons and packaging untilused tominimize the potential for damagetosprinklers thatwould cause improper operation or non-operation.

    2.

    Coverage Area

    Flow Rategpm (L/min)

    Pressurepsi (bar)

    Maximum Coverage AreaWidth x Length

    ft x ft (m xm)

    40 (151,4) 25 (1,7) 28 x 14 (8,5 x 4,3)

  • 8/18/2019 Extended Coverage

    3/4

    3.

    Figure 1.

    Figure 2.

    Figure 3.

  • 8/18/2019 Extended Coverage

    4/4

    The Reliable Automatic Sprinkler Co., Inc.

    (800) 431-1588 Sales Offices(800) 848-6051 Sales Fax(914) 668-3470 Corporate Officeswww.reliablesprinkler.com   Internet Address

    Manufactured by

    RecycledPaper

    Revision lines indicate updated or new data.

    E.G. Printed in U.S.A. 3/03   P/N 9999970246

    The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, FactoryMutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.

    Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highlyqualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.

    Reliable...For Complete ProtectionReliable offers a wide selection of sprinkler components. Following are some of the manyprecision-made Reliable products that guard life and property from fire around the clock.

    •  Automatic sprinklers

    •  Flush automatic sprinklers

    •  Recessed automatic sprinklers

    •  Concealed automatic sprinklers

    •  Adjustable automatic sprinklers

    •  Dry automatic sprinklers

    •   Intermediate level sprinklers

    •  Open sprinklers

    •   Spray nozzles

    •   Alarm valves

    •  Retarding chambers

    •  Dry pipe valves

    •  Accelerators for dry pipe valves

    •  Mechanical sprinkler alarms

    •  Electrical sprinkler alarm switches

    •  Water flow detectors

    •   Deluge valves

    •  Detector check valves

    •   Check valves

    •  Supertrol electrical system

    •  Sprinkler emergency cabinets

    •  Sprinkler wrenches

    •   Sprinkler escutcheons and guards

    •   Inspectors test connections

    •   Sight drains

    •  Ball drips and drum drips

    •  Control valve seals

    •  Air maintenance devices

    •   Air compressors

    •  Pressure gauges

    •   Identification signs

    •  Fire department connection