12
Nat. Hazards Earth Syst. Sci., 10, 2305–2316, 2010 www.nat-hazards-earth-syst-sci.net/10/2305/2010/ doi:10.5194/nhess-10-2305-2010 © Author(s) 2010. CC Attribution 3.0 License. Natural Hazards and Earth System Sciences Experimental study on the behaviour of nonductile infilled RC frames strengthened with external mesh reinforcement and plaster composite S. Z. Korkmaz 1 , M. Kamanli 2 , H. H. Korkmaz 2 , M. S. Donduren 2 , and M. T. Cogurcu 2 1 Selcuk University, Engineering and Architecture Faculty, Architecture Department, 42250, Konya, Turkey 2 Selcuk University, Engineering and Architecture Faculty, Civil Engineering Department, 42250, Konya, Turkey Received: 4 March 2010 – Revised: 19 July 2010 – Accepted: 21 October 2010 – Published: 18 November 2010 Abstract. The aim of this paper is to report on an experimental study about Turkish Earthquake Code on suggested strengthening method. The proposed method uses existing brick infill walls and the strengthening is done with the application of external mesh reinforcement and plaster. 5 nonductile 1/2 scaled, one bay, two storey RC specimens were tested under a reversed cyclic loading. The first two specimens were reference specimens and the other ones were strengthened with the proposed method. The specimens contained several design and construction mistakes such as low concrete quality and improper steel detailing. Strength, stiffness and storey drifts of the test specimens were measured. The results of the test on these frames were compared with the reference specimens. The effects of the reinforced mesh plaster application for strengthening on behaviour, strength, stiffness, failure mode and ductility of the specimens were investigated. Unexpected failure modes were observed during the testing and the results were summarized in this paper. 1 Introduction Many existing reinforced concrete (RC) frame structures, that were designed and constructed during the 1950s through to the 1990s, (according to the design codes of the 70s), in many regions of the Turkey, do not meet the current seismic design requirements set forth by the Turkish Earthquake Code (2007) and have an inadequate safety assessment (Rocha et al., 2004). A large number of those buildings exhibited fierce damage and some were on the verge of collapse (Oliveto and Decanini, 1998). Despite their rarity and moderate intensity, earthquakes not only in Turkey but Correspondence to: M. Kamanli ([email protected]) also in Europe and the USA have the potential to cause extensive damage and associated financial losses, due to the vulnerability of the local building stock (Belmouden and Lestuzzi, 2009). Reinforced concrete (RC) frame buildings with nonductile detailing represented a considerable hazard during recent earthquakes (Kaltakci et al., 2007). Structure that is not designed for prescribed earthquake forces suffered severe damage and was responsible for most of the loss of life during seismic events such as 1999 Kocaeli (Turkey) earthquake (Ghobarah and Elfath, 2001; Binici et al., 2007). Those non-ductile RC frame structures may have in- adequate lateral resistance and limited ductility. They possess an inherently low resistance to horizontal loads, resulting in large inelastic deformations (Zou and Teng, 2007) during recent earthquakes due to insufficient lateral load carrying capacity. For those structures constructed with insufficient strength and ductility, the required stiffness was not provided. The frames of these structures were designed to resist only gravity loads or gravity and moderate wind load. Older designs often do not have proper reinforcement details needed to ensure ductile behaviour (Geng et al., 1998; Ghobarah et al., 2000; Altin et al., 2007). The load carrying system for most of the existing reinforced concrete residential buildings contains flexible columns, soft stories and strong-beam weak-column con- nections (Altin et al., 2008). Reinforced concrete buildings designed without seismic considerations have significant deficiencies, such as, poor confinement of the column lap splice area (Ghobarah and Elfath, 2001) (due to the insufficient amount of ties with 90 hooks), discontinuity of positive moment reinforcement in beams and slabs resulting in bond slip of beam bottom reinforcement at the joint (Hueste and Bai, 2007), lacking transverse shear reinforcing steel, having plain bars and low strength concrete (10– 15 MPa). In 1999, Marmara earthquake caused substantial casualties and severe damage to structures (Firat et al., 2009). Published by Copernicus Publications on behalf of the European Geosciences Union.

Experimental study on the behaviour of nonductile ... · Reinforced concrete (RC) frame buildings with nonductile detailing represented a ... to resist only gravity loads or gravity

  • Upload
    vophuc

  • View
    217

  • Download
    0

Embed Size (px)

Citation preview

Nat. Hazards Earth Syst. Sci., 10, 2305–2316, 2010www.nat-hazards-earth-syst-sci.net/10/2305/2010/doi:10.5194/nhess-10-2305-2010© Author(s) 2010. CC Attribution 3.0 License.

Natural Hazardsand Earth

System Sciences

Experimental study on the behaviour of nonductile infilledRC frames strengthened with external mesh reinforcementand plaster composite

S. Z. Korkmaz1, M. Kamanli 2, H. H. Korkmaz 2, M. S. Donduren2, and M. T. Cogurcu2

1Selcuk University, Engineering and Architecture Faculty, Architecture Department, 42250, Konya, Turkey2Selcuk University, Engineering and Architecture Faculty, Civil Engineering Department, 42250, Konya, Turkey

Received: 4 March 2010 – Revised: 19 July 2010 – Accepted: 21 October 2010 – Published: 18 November 2010

Abstract. The aim of this paper is to report on anexperimental study about Turkish Earthquake Code onsuggested strengthening method. The proposed methoduses existing brick infill walls and the strengthening isdone with the application of external mesh reinforcementand plaster. 5 nonductile 1/2 scaled, one bay, two storeyRC specimens were tested under a reversed cyclic loading.The first two specimens were reference specimens and theother ones were strengthened with the proposed method.The specimens contained several design and constructionmistakes such as low concrete quality and improper steeldetailing. Strength, stiffness and storey drifts of the testspecimens were measured. The results of the test onthese frames were compared with the reference specimens.The effects of the reinforced mesh plaster application forstrengthening on behaviour, strength, stiffness, failure modeand ductility of the specimens were investigated. Unexpectedfailure modes were observed during the testing and theresults were summarized in this paper.

1 Introduction

Many existing reinforced concrete (RC) frame structures,that were designed and constructed during the 1950s throughto the 1990s, (according to the design codes of the 70s), inmany regions of the Turkey, do not meet the current seismicdesign requirements set forth by the Turkish EarthquakeCode (2007) and have an inadequate safety assessment(Rocha et al., 2004). A large number of those buildingsexhibited fierce damage and some were on the verge ofcollapse (Oliveto and Decanini, 1998). Despite their rarityand moderate intensity, earthquakes not only in Turkey but

Correspondence to:M. Kamanli([email protected])

also in Europe and the USA have the potential to causeextensive damage and associated financial losses, due to thevulnerability of the local building stock (Belmouden andLestuzzi, 2009). Reinforced concrete (RC) frame buildingswith nonductile detailing represented a considerable hazardduring recent earthquakes (Kaltakci et al., 2007). Structurethat is not designed for prescribed earthquake forces sufferedsevere damage and was responsible for most of the loss oflife during seismic events such as 1999 Kocaeli (Turkey)earthquake (Ghobarah and Elfath, 2001; Binici et al., 2007).

Those non-ductile RC frame structures may have in-adequate lateral resistance and limited ductility. Theypossess an inherently low resistance to horizontal loads,resulting in large inelastic deformations (Zou and Teng,2007) during recent earthquakes due to insufficient lateralload carrying capacity. For those structures constructed withinsufficient strength and ductility, the required stiffness wasnot provided. The frames of these structures were designedto resist only gravity loads or gravity and moderate windload. Older designs often do not have proper reinforcementdetails needed to ensure ductile behaviour (Geng et al., 1998;Ghobarah et al., 2000; Altin et al., 2007).

The load carrying system for most of the existingreinforced concrete residential buildings contains flexiblecolumns, soft stories and strong-beam weak-column con-nections (Altin et al., 2008). Reinforced concrete buildingsdesigned without seismic considerations have significantdeficiencies, such as, poor confinement of the columnlap splice area (Ghobarah and Elfath, 2001) (due to theinsufficient amount of ties with 90◦ hooks), discontinuity ofpositive moment reinforcement in beams and slabs resultingin bond slip of beam bottom reinforcement at the joint(Hueste and Bai, 2007), lacking transverse shear reinforcingsteel, having plain bars and low strength concrete (10–15 MPa). In 1999, Marmara earthquake caused substantialcasualties and severe damage to structures (Firat et al., 2009).

Published by Copernicus Publications on behalf of the European Geosciences Union.

2306 S. Z. Korkmaz et al.: RC frames strengthened

Table 1. Summary of the test specimens.

Specimen Definition Strengthening Observed failure type Lap splice condition in columnsname plaster

thickness

RFB1 Reference specimen with no infill – Flexural –

RISPS2 Reference specimen with infill – Corner crushing of the infill wall panels –

SPS1 Strengthened 15 mmPremature failure –

Insufficient lap splice lengthshear failure of dowels and plaster

SPS2 Strengthened 30 mm Lap splice failure Insufficient lap splice length

SPS3 Strengthened 30 mm Frame joint failure Lap splice was improved

After the Marmara earthquake, it was observed that, failureof reinforced concrete columns usually occurred in potentialplastic hinge regions at the bottom. The reason was, lapsplices in the column longitudinal reinforcement was locatedat member ends, and the lengths of splices were oftenshorter than those required by building codes. The consistingbuilding stock must be prepared for future earthquakes(Onal, 2009) and easily applicable and occupant-friendlynew strengthening methods should be developed.

2 Materials and methods

In the experimental study, a total of five 1/2 scale, one-bay, two-storey nonductile RC frame specimens weremanufactured and tested as part of the experimental program(Kilic, 2010). The model ratio of the specimens definitelyaffect the validity of the test results. On the otherhand, production of specimens in real dimensions is costlyconsidering the limited budget of the test programme andcreates lifting and destruction problems. Another problemis the load capacity of the available hydraulic cylinders andloading setup. On the other hand, several studies in theliterature (Binici et al., 2007; Anil et al., 2007; Erdem etal., 2006; Altin et al., 2008) used 1/3 model ratio which wassmaller than 1/2 model ratio of the current study.

Two specimens, which were reference specimens andthe remaining three of which had deficient reinforcementdetailing were prepared. The first specimen tested was a bareframe with no infill wall. The second reference specimen wasinfilled with ordinary perforated clay bricks. The other threespecimens were strengthened with the details given in thenew Turkish Earthquake Code (2007). In all test specimens,the geometric dimensions and reinforcement patterns ofthe frames were identical. Structural characteristics of thespecimens were summarized in Table 1.

During the design phase of the frames, some deficienciescommonly observed in structures were purposely includedto reflect the gravity load designed residential buildings inTurkey. Insufficient confinement of concrete at the columnand beams with ties having 90◦ hooks at their free ends,weak-column, strong-beam connections that are encountered

frequently in practice and frames with inadequate lateralstiffness was provided. Also no confinement was providedat beam-column joints.

The total height of the specimens was 3 m. The columndimensions were 160× 240 mm and the beam dimensionswere 240× 240 mm. In the columns the longitudinalreinforcement consists of four 12 mm diameter plain bars(ρ = 0.0082). In the beams, three tension and threecompression reinforcements were placed. In total, six 12 mmdiameter plain bars were used as longitudinal reinforcement(effective depth of the beamd = 24− 2∗1 = 22 cm, bw =

22 cm, ρ′= 0.0064). Plain bars with a diameter of

8 mm spaced at 150 mm were used as closed stirrups inboth the beams and columns. Since specimens were 1/2scaled models of the real structure, 150 mm stirrup spacingcorresponds to the 300 mm interval in real RC members.The longitudinal reinforcements in columns were lap spliced,both at foundation level and first (middle) storey level.The lap length was chosen as 200 mm. Dimensions andreinforcement details of the test frames are shown in Fig. 1.Also in Fig. 1, reinforcement details of the joints and stirrupspacings were illustrated.

The frames of the specimens were cast from very lowstrength concrete to represent the strength of concrete inexisting buildings. Based on concrete trial mixes fromvarious recipes for attaining the 28-day target strength of10 MPa, a design mix was determined. Although theminimum concrete strength stated in the Turkish EarthquakeCode is 20 MPa for the 1st earthquake zone, existingstructures commonly have a low quality of concrete. This hasbeen observed by several researchers (Kaltakci et al., 2008;Arslan et al., 2007). Cylinder tests were performed and theconcrete strength was approximately 10 MPa at the day oftesting. The maximum size of aggregate for 1/2 scale modelspecimens was 16 mm. The average compressive strengthof the mortar and the plaster used in the construction of themasonry walls of specimens was found to be 2.6 MPa. Plainbars were used as the reinforcing steel since such steel hasbeen used in most of the existing residential buildings inTurkey.

Nat. Hazards Earth Syst. Sci., 10, 2305–2316, 2010 www.nat-hazards-earth-syst-sci.net/10/2305/2010/

S. Z. Korkmaz et al.: RC frames strengthened 2307

(a) general details

(c) column bottom lap splice detail (b) stirrup spacing

(d) top storey beam-column joint detail

(e) middle storey beam-column joint detail

150 mm

(a) general details

(c) column bottom lap splice detail (b) stirrup spacing

(d) top storey beam-column joint detail

(e) middle storey beam-column joint detail

150 mm

Fig. 1. Dimensions and details of the test specimens.

The strengthening technique was applied according to thespecification described in Turkish Earthquake Code (2007).After the specimens were lifted to the vertical position, brickinfill walls were constructed by an ordinary worker. The1/2 scaled clay bricks were used and ordinary mortar wasused. The bricks were laid in such a way that their holeswere parallel to the horizontal plane. The thickness of thewall was 100 mm (1/2 scale) which is 200 mm in an ordinaryexterior wall of a residential building. Infill walls were notconstructed on the symmetry axis of the frame for simulating

Plaster mixes were prepared according to the proportion given in TEC-2007. Both sides of the wall were plastered with the prepared plaster material. The thickness of the plaster was 15 mm and the total thickness of the masonry wall with plaster was 130 mm. The thickness of the plaster was ½ scaled and in real application it is approximately 30 mm. The representative illustration of the strengthening application is given in Figure 2. In real application an older plaster layer exist and strengthening was applied over the older plaster layer. In experimental studyi the strengthening was directly applied over the infills the contribution of the old plaster was ignored.

Figure 2 Plastered walls with welded external mesh and plaster composite (TEC-2007) The modulus of elasticity of the materials and other mechanical properties were summarized in Table2. Table 2 Mechanical propertiesof the materials Modulus of

Elasticity Copmressive Strength Yield Strength

Concrete 27000 Mpa 10 Mpa Longtidional reinforcement 200000 Mpa 480 Mpa Transverse steel 200000 Mpa 480 Mpa Mesh reinforcement 250000 Mpa 520 Mpa Steel Dowels 2000000 Mpa 480 Mpa Ordinary plaster 21000 Mpa 1.5 Mpa Strengthening plaster 20000 Mpa 2.6 Mpa Masonry bricks Not tested 5 Mpa 3. The testing system

The laboratory of the University contains a strong floor with 600 mm thickness and having uniformly distributed holes with 70 mm in diameter. There is also a strong reaction wall, with 12 m height. Specimens were cast in horizontal position and then lifted to vertical position. Production of

Fig. 2. Plastered walls with welded external mesh and plastercomposite (TEC-2007).

exterior walls of the building. One face of the wall was on thesame line of the columns while the other face was 140 mminside the other exterior face of the columns.

The external mesh reinforcement consisted of 16× 16 mmsquare meshes with 1.1 mm diameter steel. The shearconnections between the frame and infill walls wereestablished with dowel reinforcements. These dowels wereattached to the inner faces of the beams and columns with160 mm intervals in horizontal and vertical directions. The10 mm diameter bars were used as dowel reinforcement andthey were anchored to the RC members with epoxy. Holes,which were drilled on the inner faces of the frame members,were cleaned. The mesh reinforcement was placed on theinfill wall and the dowels were inserted into epoxy injectedholes. The infill wall reinforcement was also 1/2 scaled.Since both reinforcement and wall was scaled down, theratio was not changed and chosen asρv = ρh = 0.009 in bothvertical and horizontal directions.

The plaster mixes were prepared according to theproportion given in TEC-2007. Both sides of the wall wereplastered with the prepared plaster material. The thickness ofthe plaster was 15 mm and the total thickness of the masonrywall with plaster was 130 mm. The thickness of the plasterwas 1/2 scaled and in real application it is approximately30 mm. The representative illustration of the strengtheningapplication is given in Fig. 2. In a real application an olderplaster layer exists and strengthening was applied over theolder plaster layer. In experimental studies, the strengtheningwas directly applied over the infills, the contribution of theold plaster was ignored.

www.nat-hazards-earth-syst-sci.net/10/2305/2010/ Nat. Hazards Earth Syst. Sci., 10, 2305–2316, 2010

2308 S. Z. Korkmaz et al.: RC frames strengthened

Table 2. Mechanical properties of the materials.

Modulus Copmressive Yieldof Strength Strength

Elasticity

Concrete 27 000 Mpa 10 Mpa

Longtidional200 000 Mpa 480 Mpareinforcement

Transverse steel 200 000 Mpa 480 Mpa

Mesh250 000 Mpa 520 Mpareinforcement

Steel dowels 2 000 000 Mpa 480 Mpa

Ordinary plaster 21 000 Mpa 1.5 Mpa

Strengthening20 000 Mpa 2.6 Mpaplaster

Masonry bricks Not tested 5 Mpa

The modulus of elasticity of the materials and othermechanical properties were summarized in Table 2.

3 The testing system

The laboratory of the University contains a strong floorwith 600 mm thickness and having uniformly distributedholes with 70 mm in diameter. There is also a strongreaction wall, with a 12 m height. Specimens were cast ina horizontal position and then lifted to a vertical position.Production of the specimens in the vertical position createdform and scaffolding problems, making the leveling of theform of the specimens very difficult. In another experimentalprogramme, authors produced two specimens, one of whichwas casted in a vertical position and another in a horizontalposition. No clear differences under lateral loading wasobserved. So authors preferred the horizontal casting forease of production. The specimens were built on stiffreinforced concrete foundations and bolted to the rigid floorthrough holes with high strength steel bolts. The lateralloading equipment consisted of a hydraulic jack with a1000 kN capacity and three loadcell with a 500 kN capacity.Tests were conducted under reversed cyclic lateral loadingsimulating seismic action. Lateral load was applied tospecimens at the storey levels. Cycles were named asforward and backward cycles and forward cycles wereassumed to be positive. Axial load was also applied tothe top of the columns with two hydraulic cylinders andwas measured with two loadcells. A special apparatus wasmanufactured to apply axial load. The representation of thetest setup, loading system and instrumentation is shown inFig. 3.

the specimens in the vertical position was created form and scaffolding problems. Leveling of the form of the specimens was very difficult. In another experimental program, authors produced two specimens one of which was casted in vertical position and another in horizontal position. No clear diffirences under lateral loading was observed. So authors preferred horizontal casting for ease of production. The specimens were built on stiff reinforced concrete foundations and bolted to the rigid floor through holes with high strength steel bolts. The lateral loading equipment consisted of a hydraulic jack with 1000 kN capacity and three loadcell with a 500 kN capacity. Tests were conducted under reversed cyclic lateral loading simulating seismic action. Lateral load was applied to specimens at the storey levels. Cycles were named as forward and backward cycles and forward cycles were assumed to be positive. Axial load was also applied to the columns top with two hydraulic cylinders and was measured with two loadcells. A special apparatus was manufactured to apply axial load. The representation of test setup, loading system and instrumentation is shown in Figure 3.

δ3δ4 δ5 δ6 δ7

F2

F1

FTotal

HydraulicCylinderLoad

cell

HydraulicCylinder

Loadcell

Hinge

Hinge

Reaction Wall

Floor

Δ1

Δ2

δ1

δ2

Figure 3 Test setup, loading system, and instrumentation

The instrumentation setup consisted of LVDT’s, and data acquisition system. The specimens

were instrumented with LVDTs (linear variable differential transformers) to measure top and middle story displacements. During the tests, story displacements and the lateral loads were saved to the computer and monitored simultaneously. Cyclic lateral displacement excursions were imposed to simulate the seismic demand. The lateral load was applied with a rigid steel beam such that 1/3 and 2/3 of the total load was applied on the middle and top storey, respectively. Loading cycles consisted of preyield and post yield cycles. In the elastic range several cycles were applied with a load controlled history. Beyond the elastic limit, displacement controlled cycles were applied. The maximum displacement capacity of the test setup was 100 mm which corresponds to the 3% drift ratio. During the loading cycles, when target load or displacement was reached, the loading was stopped and new initiated cracks and crack propagation were marked on the specimens and failure mechanisms were observed. 4. Results

In this section experimental results were summarized with hystesis curves of the specimens. The vertical axis of the curves represents the top lateral load in kN and bottom horizontal axis is the top displacement in mm. Top horizontal axis is the lateral drift percentage of the frame. Also in curves, drift levels corresponding to 0.4% and 1.2 % were highlighted. The failure points of the specimens were marked with a black circle.

Fig. 3. Test setup, loading system and instrumentation.

The instrumentation setup consisted of LVDT’s, anddata acquisition system. The specimens were instrumentedwith LVDTs (linear variable differential transformers) tomeasure top and middle story displacements. During thetests, story displacements and the lateral loads were savedto the computer and monitored simultaneously. Cycliclateral displacement excursions were imposed to simulate theseismic demand. The lateral load was applied with a rigidsteel beam such that 1/3 and 2/3 of the total load was appliedon the middle and top storey, respectively. Loading cyclesconsisted of preyield and post yield cycles. In the elasticrange several cycles were applied with a load controlledhistory. Beyond the elastic limit, displacement controlledcycles were applied. The maximum displacement capacityof the test setup was 100 mm which corresponds to the 3%drift ratio. During the loading cycles, when target load ordisplacement was reached, the loading was stopped and newinitiated cracks and crack propagation were marked on thespecimens and failure mechanisms were observed.

4 Results

In this section, experimental results were summarized withhysteresis curves of the specimens. The vertical axis of thecurves represents the top lateral load in kN and the bottomhorizontal axis is the top displacement in mm. Top horizontalaxis is the lateral drift percentage of the frame. Also incurves, drift levels corresponding to 0.4% and 1.2% werehighlighted. The failure points of the specimens were markedwith a black circle.

A reference specimen with no infill wall was prepared andtested to understand the bare frame capacity and named asRFB1 (Fig. 4). Load-top displacement hysteresis curve of thespecimen is represented in Fig. 5. The displacement levelsof the initial elastic cycles did not generate any nonlineardeformation in the structure and the loops followed a straight

Nat. Hazards Earth Syst. Sci., 10, 2305–2316, 2010 www.nat-hazards-earth-syst-sci.net/10/2305/2010/

S. Z. Korkmaz et al.: RC frames strengthened 2309

A reference specimen with no infill wall was prepared and tested to understand the bare frame

capacity and named as RFB1 (Figure 4). Load-top displacement hysteresis curve of the specimen is represented in Figure 5. The displacement levels of the initial elastic cycles did not generate any nonlinear deformation in the structure and the loops followed a straight line. The maximum load carrying capacity of the specimen was determined as 34.5 kN. Plastic hinges were formed in the beam-column joints. No obvious failure point can be determined in specimen RFB1. Several flexural cracks were observed both on the beams and the columns. The onset of stiffness degradation was identified by simultaneous formation of tension cracks at the bottom of the columns.

Figure 4 Reference bare frame RFB1

As observed from Figure 4, the Δ1 and Δ2 readings were not displayed linear increase. Actuallyi before the occurrence of the plastic hinges, the variation is linear, but after the elastic limit, several plastic hinges were formed in the ends of beams or columns and linearity was disturbed.

-50

-40

-30

-20

-10

0

10

20

30

40

50

-150 -100 -50 0 50 100 150Displacement (mm)

Load

(kN

)

-50

-40

-30

-20

-10

0

10

20

30

40

50-5% -3% -1% 1% 3% 5%

Drift %0,4% 1,2%-1,2% -0,4%

Figure 5 Load-top displacement hysteresis curve of reference bare frame RFB1

Fig. 4. Reference bare frame RFB1.

line. The maximum load carrying capacity of the specimenwas determined as 34.5 kN. Plastic hinges were formedin the beam-column joints. No obvious failure point canbe determined in specimen RFB1. Several flexural crackswere observed both on the beams and the columns. Theonset of stiffness degradation was identified by simultaneousformation of tension cracks at the bottom of the columns.

As observed from Fig. 4, the11 and12 readings were notdisplayed linear increase. Actually, before the occurrence ofthe plastic hinges, the variation is linear, but after the elasticlimit, several plastic hinges were formed in the ends of beamsor columns and linearity was disturbed.

Second reference specimen RISPS2 was manufacturedwith the same reinforcement details of RFB1. Theconcrete compressive strength was the same with the RFB1.The frame was infilled with masonry wall panel. Nostrengthening was applied on the wall. Ordinary plaster wasapplied on both surfaces of the masonry wall.

During the testing, it was observed that, at low levels oflateral forces, the frame and infill wall behave monolithically.However, as the lateral force level increases, the framedeforms in a flexural mode while the infill corners damaged.In the early stages of the loading, the frame with infillwall displayed higher in-plane stiffness and strength. Thementioned increase can be seen from the hysteresis curves ofthe specimen RISPS2 (Fig. 6).

A reference specimen with no infill wall was prepared and tested to understand the bare frame

capacity and named as RFB1 (Figure 4). Load-top displacement hysteresis curve of the specimen is represented in Figure 5. The displacement levels of the initial elastic cycles did not generate any nonlinear deformation in the structure and the loops followed a straight line. The maximum load carrying capacity of the specimen was determined as 34.5 kN. Plastic hinges were formed in the beam-column joints. No obvious failure point can be determined in specimen RFB1. Several flexural cracks were observed both on the beams and the columns. The onset of stiffness degradation was identified by simultaneous formation of tension cracks at the bottom of the columns.

Figure 4 Reference bare frame RFB1

As observed from Figure 4, the Δ1 and Δ2 readings were not displayed linear increase. Actuallyi before the occurrence of the plastic hinges, the variation is linear, but after the elastic limit, several plastic hinges were formed in the ends of beams or columns and linearity was disturbed.

-50

-40

-30

-20

-10

0

10

20

30

40

50

-150 -100 -50 0 50 100 150Displacement (mm)

Load

(kN

)

-50

-40

-30

-20

-10

0

10

20

30

40

50-5% -3% -1% 1% 3% 5%

Drift %0,4% 1,2%-1,2% -0,4%

Figure 5 Load-top displacement hysteresis curve of reference bare frame RFB1

Fig. 5. Load-top displacement hysteresis curve of reference bareframe RFB1.

Second reference specimen RISPS2 was manufactured with the same reinforcement details of

RFB1. The concrete compressive strength was same with the RFB1. Frame was infilled with masonry wall panel. No strengthening was applied on the wall. Ordinary plaster was applied on both surfaces of the masonry wall.

During the testing, it was observed that, at low levels of lateral forces, frame and infill wall behave monolithically. However, as the lateral force level increases, the frame deforms in a flexural mode while the infill corners damaged. In the early stages of the loading, frame with infill wall displayed higher in-plane stiffness and strength. The mentioned increase can be seen from the hysteresis curves of the specimen RISPS2 (Figure 6).

-60-50-40-30-20-10

0102030405060

-60 -40 -20 0 20 40 60Displacement (mm)

Load

(kN

)

-60

-40

-20

0

20

40

60-2,0% -1,5% -1,0% -0,5% 0,0% 0,5% 1,0% 1,5% 2,0%

Drift % 0,4% 1,2%-1,2% -0,4%

Figure 6 Load-top displacement hysteresis curve of reference infilled frame RISPS2

Shing and Mehrabi (2002), identified five main failure mechanisms of infilled frames. Those

failure modes are; flexural mode, horizontal sliding crack at the mid-height of an infill, diagonal cracking, sliding of multiple bed-joints (a distinct diagonal strut mechanism with two distinct parallel cracks) and corner crushing. In summary, the failure mechanism and load resistance of an infilled frame depend very much on the strength and stiffness of an infill with respect to those of the bounding frame.

In the test of the specimen RISPS2, fifth mode of the failure was observed. Corners of the wall panels damaged and crushed. Separation of the infill from the frame was obvious at the higher displacement levels. Both upper and bottom wall panels damaged. The failure mode and specimen at the end of the test is given in Figure 7. RISPS2 specimen survived %22 percent higher lateral load than RFB1 specimen.

Fig. 6. Load-top displacement hysteresis curve of reference infilledframe RISPS2.

Shing and Mehrabi (2002) identified five main failuremechanisms of infilled frames. Those failure modes are;flexural mode, horizontal sliding crack at the mid-heightof an infill, diagonal cracking, sliding of multiple bed-joints (a distinct diagonal strut mechanism with two distinctparallel cracks) and corner crushing. In summary, the failuremechanism and load resistance of an infilled frame dependvery much on the strength and stiffness of an infill withrespect to those of the bounding frame.

In the test of the specimen RISPS2, fifth mode of thefailure was observed. The corners of the wall panelsdamaged and crushed. Separation of the infill from theframe was obvious at the higher displacement levels. Bothupper and bottom wall panels damaged. The failure modeand specimen at the end of the test is given in Fig. 7.RISPS2 specimen survived 22% higher lateral load thanRFB1 specimen.

Third specimen was named as SPS1. The frame propertiesand infill configuration was the same with RISPS2 specimen.The strengthening scheme was applied as explained before(Fig. 8).

www.nat-hazards-earth-syst-sci.net/10/2305/2010/ Nat. Hazards Earth Syst. Sci., 10, 2305–2316, 2010

2310 S. Z. Korkmaz et al.: RC frames strengthened

Figure 7 Reference infilled frame RISPS2

Third specimen was named as SPS1. The frame properties and infill configuration was same with RISPS2 specimen. Strengthening scheme was applied as explained before (Figure 8).

Figure 8 Strengthening of specimen SPS1

Although specimen SPS1 survived %16 higher maximum lateral loading, its performance was

evaluated as poor. The dowels or shear keys below the middle beam were disintegrated from the plaster and lateral displacement of the frame suddenly increased. At this time there was also sudden drop in the load carried by the system. The failure point of the dowels – wall- plaster composite can be clearly seen from the last cycle of the load-displacement hysteresis curve (Figure 9).

Figure 7 Reference infilled frame RISPS2

Third specimen was named as SPS1. The frame properties and infill configuration was same with RISPS2 specimen. Strengthening scheme was applied as explained before (Figure 8).

Figure 8 Strengthening of specimen SPS1

Although specimen SPS1 survived %16 higher maximum lateral loading, its performance was

evaluated as poor. The dowels or shear keys below the middle beam were disintegrated from the plaster and lateral displacement of the frame suddenly increased. At this time there was also sudden drop in the load carried by the system. The failure point of the dowels – wall- plaster composite can be clearly seen from the last cycle of the load-displacement hysteresis curve (Figure 9).

Fig. 7. Reference infilled frame RISPS2.

Figure 7 Reference infilled frame RISPS2

Third specimen was named as SPS1. The frame properties and infill configuration was same with RISPS2 specimen. Strengthening scheme was applied as explained before (Figure 8).

Figure 8 Strengthening of specimen SPS1

Although specimen SPS1 survived %16 higher maximum lateral loading, its performance was

evaluated as poor. The dowels or shear keys below the middle beam were disintegrated from the plaster and lateral displacement of the frame suddenly increased. At this time there was also sudden drop in the load carried by the system. The failure point of the dowels – wall- plaster composite can be clearly seen from the last cycle of the load-displacement hysteresis curve (Figure 9).

Fig. 8. Strengthening of specimen SPS1.

-60-50-40-30-20-10

0102030405060

-60 -40 -20 0 20 40 60Displacement (mm)

Load

(kN

)

-60

-40

-20

0

20

40

60-2,0% -1,5% -1,0% -0,5% 0,0% 0,5% 1,0% 1,5% 2,0%

Drift % 0,4% 1,2%-1,2% -0,4%

Figure 9 Load-top displacement hysteresis curve of SPS1

After the failure of the dowels, the testing could not be continued. The failure mode of the

specimen is given in Figure 10. During testing, wall panels of specimen SPS1 was showed higher stiffness contribution to the frame than the RFB1 and RISPS2. Also ultimate lateral load carrying capacity of the SPS1 was increased as compared to SPS1 and RISPS2. Several flexural cracks were observed on the beams and columns. But below the first storey beam, premature and sudden failure of the wall-plaster-dowel interface was observed. The plaster cover over the dowels disintegrated and no more shear transfer between beam and the wall become possible. This failure mode was very sudden and in brittle nature. The full capacity of the mesh-plaster-wall composite couldn’t be used due to this premature failure. After the failure, the specimen showed similar load-displacement characteristics with the RISPS2 specimen. This failure was attributed to inadequate plaster thickness and at the end of the test; it was decided to increase the thickness of the plaster. This specimen lost 55% of its lateral load carrying capacity immediately after failure of the dowel anchorage with the mesh plaster composite.

Figure 10 Failure mode of specimen SPS1

Fig. 9. Load-top displacement hysteresis curve of SPS1.

-60-50-40-30-20-10

0102030405060

-60 -40 -20 0 20 40 60Displacement (mm)

Load

(kN

)

-60

-40

-20

0

20

40

60-2,0% -1,5% -1,0% -0,5% 0,0% 0,5% 1,0% 1,5% 2,0%

Drift % 0,4% 1,2%-1,2% -0,4%

Figure 9 Load-top displacement hysteresis curve of SPS1

After the failure of the dowels, the testing could not be continued. The failure mode of the

specimen is given in Figure 10. During testing, wall panels of specimen SPS1 was showed higher stiffness contribution to the frame than the RFB1 and RISPS2. Also ultimate lateral load carrying capacity of the SPS1 was increased as compared to SPS1 and RISPS2. Several flexural cracks were observed on the beams and columns. But below the first storey beam, premature and sudden failure of the wall-plaster-dowel interface was observed. The plaster cover over the dowels disintegrated and no more shear transfer between beam and the wall become possible. This failure mode was very sudden and in brittle nature. The full capacity of the mesh-plaster-wall composite couldn’t be used due to this premature failure. After the failure, the specimen showed similar load-displacement characteristics with the RISPS2 specimen. This failure was attributed to inadequate plaster thickness and at the end of the test; it was decided to increase the thickness of the plaster. This specimen lost 55% of its lateral load carrying capacity immediately after failure of the dowel anchorage with the mesh plaster composite.

Figure 10 Failure mode of specimen SPS1

Fig. 10. Failure mode of specimen SPS1.

Although specimen SPS1 survived 16% higher maximumlateral loading, its performance was evaluated as poor. Thedowels or shear keys below the middle beam disintegratedfrom the plaster and lateral displacement of the framesuddenly increased. At this time there was also a sudden dropin the load carried by the system. The failure point of thedowels-wall-plaster composite can be clearly seen from thelast cycle of the load-displacement hysteresis curve (Fig. 9).

After the failure of the dowels, the testing could notcontinue. The failure mode of the specimen is given inFig. 10. During testing, the wall panels of specimen SPS1showed a higher stiffness contribution to the frame thanthe RFB1 and RISPS2. Also the ultimate lateral loadcarrying capacity of the SPS1 was increased as compared toSPS1 and RISPS2. Several flexural cracks were observedon the beams and columns. But below the first storeybeam, premature and sudden failure of the wall-plaster-dowel interface was observed. The plaster cover over thedowels disintegrated and no more shear transfer between thebeam and the wall were possible. This failure mode was

Nat. Hazards Earth Syst. Sci., 10, 2305–2316, 2010 www.nat-hazards-earth-syst-sci.net/10/2305/2010/

S. Z. Korkmaz et al.: RC frames strengthened 2311

very sudden and brittle in nature. The full capacity of themesh-plaster-wall composite could not be used due to thispremature failure. After the failure, the specimen showedsimilar load-displacement characteristics with the RISPS2specimen. This failure was attributed to inadequate plasterthickness and at the end of the test, it was decided to increasethe thickness of the plaster. This specimen lost 55% of itslateral load carrying capacity immediately after failure of thedowel anchorage with the mesh plaster composite.

After obtaining a dowel-plaster anchorage failure inspecimen SPS1, the thickness of the plaster was increasedto 30 mm in specimen SPS2 (Fig. 11). Other properties werethe same as SPS1. During the test of SPS2, no damage wasobserved on the wall panels, but instead some minor cracksformed. Serious cracks were observed on both column bases.These cracks were also extended through the bottom of thelower wall panel (Fig. 12).

The lateral load-top storey displacement hysteresis curvesare presented in Fig. 13. The maximum lateral load obtainedduring the testing was 63.2 kN, which was 82% higherthan bare frame and 50% higher than the reference infilledspecimen. The wall panels contributed to the load carried bythe system and also increased the stiffness of the frame, butfailure of the panel could not be obtained. The reason forthe failure attributed to the slippage of the reinforcing bars atthe bottom of the columns. The low concrete strength, plainundeformed bars and insufficient lap splice length at the jointcreated such a failure mode.

Specimen SPS3 was prepared according to the resultsobtained in the SPS2 testing. The bottom joints of thecolumns were improved by increasing the lap length ofthe longitudinal reinforcements. The 200 mm lap lengthwas increased to 420 mm (20 f×1.5) lap length which wasapplied in the Turkish Earthquake Code. Other propertieswere as SPS2. The maximum lateral load carried by thesystem was obtained as 69 kN. No lap splice failure wasobserved at the bottom of the columns. Also dowel-plasterfailure did not form. The specimen survived a 10% higherlateral load than SPS2. On the other hand, as the load levelsincreased, several cracks were concentrated on the middlebeam-column joint and those cracks determine the failuremode. Middle joints were seriously damaged and the lateralload carried by the system dropped drastically. Left and rightjoint failure photos are given in Fig. 14 and 15, respectively.

The column stirrups did not exist in the beam columnjoints. Also lap splice length of the column’s longitudinalreinforcement was insufficient at those points. In additionto these detailing mistakes, another effective parameter tothe failure was poor concrete quality. The lateral load atthe joints was transferred to the foundation, through diagonalstruts along the wall panel. As a result, inclined inner forceswere acting on the joints. Since the joints did not haveenough confinement and strength, they failed. The failurepoint of the joints can also be seen from load hysteresiscurves (Fig. 16).

After obtaining a dowel-plaster anchorage failure in specimen SPS1, the thickness of the

plaster was increased to 30 mm in specimen SPS2 (Figure 11). Other properties were same as SPS1. During the test of the SPS2, no damage was observed on the wall panels; instead some minor cracks were formed. Serious cracks were observed on both column bases. These cracks were also extended through the bottom of the lower wall panel (Figure 12).

Figure 11 Preparation of specimen SPS2

Figure 12 Slip failures at the bottom of the columns

The lateral load-top storey displacement hysteresis curves are presented in Figure 13. The

maximum lateral load obtain during the testing was 63.2 kN, which was %82 higher than bare frame and %50 higher than reference infilled specimen. The wall panels were contributed to the load carried by the system and also increased the stiffness of the frame, but failure of the panel couldn’t be

Fig. 11. Preparation of specimen SPS2.

5 Comparison of results

The lateral load-top displacement characteristics for allthe specimens are presented and compared in this section.The comparison of the behaviour of the test specimensis made in terms of lateral strength, stiffness, maximumstorey drifts and energy dissipation characteristics. Theenvelopes let us compare the relative performance of thespecimens. To enable the comparison among the testspecimens studied here, the load-displacement envelopesare plotted by connecting the maximum peak points ofconsecutive hysteresis curves. The response envelope curvesof the strengthened specimens are given in Fig. 17 togetherwith that of the reference bare frame and reference infilledspecimen. These plots have a better representation of therate of stiffness degradation. As can be seen from this figure,strength and stiffness of both strengthened frames weresignificantly higher than those of the reference specimens

Also in Fig. 18, the comparison ratio of the ultimate lateralloads to the reference empty specimen RFB1 is given in aclustered column type chart. This figure lets us compare therelative performance of the specimens.

www.nat-hazards-earth-syst-sci.net/10/2305/2010/ Nat. Hazards Earth Syst. Sci., 10, 2305–2316, 2010

2312 S. Z. Korkmaz et al.: RC frames strengthened

After obtaining a dowel-plaster anchorage failure in specimen SPS1, the thickness of the

plaster was increased to 30 mm in specimen SPS2 (Figure 11). Other properties were same as SPS1. During the test of the SPS2, no damage was observed on the wall panels; instead some minor cracks were formed. Serious cracks were observed on both column bases. These cracks were also extended through the bottom of the lower wall panel (Figure 12).

Figure 11 Preparation of specimen SPS2

Figure 12 Slip failures at the bottom of the columns

The lateral load-top storey displacement hysteresis curves are presented in Figure 13. The

maximum lateral load obtain during the testing was 63.2 kN, which was %82 higher than bare frame and %50 higher than reference infilled specimen. The wall panels were contributed to the load carried by the system and also increased the stiffness of the frame, but failure of the panel couldn’t be

Fig. 12. Slip failures at the bottom of the columns.obtained. The reason of the failure attributed to the slippage of the reinforcing bars at the bottom of the columns. The low concrete strength, plain undeformed bars and insufficient lap splice length at the joint created such a failure mode.

-80-70-60-50-40-30-20-10

01020304050607080

-40 -30 -20 -10 0 10 20 30 40Displacement (mm)

Load

(kN

)

-80

-60

-40

-20

0

20

40

60

80-1,3% -0,8% -0,3% 0,2% 0,7% 1,2%

Drift %0,4% 1,2%-1,2% -0,4%

Figure 13 Hysteresis curves of specimen SPS2

Specimen SPS3 was prepared according to the results obtained in SPS2 testing. The bottom joints of the columns were improved by increasing the lap length of the longitudinal reinforcements. The 200 mm lap length was increased to 420 mm(20fx1.5) lap length which was given in the Turkish Earthquake Code. Other properties were as SPS2. Maximum lateral load carried by the system was obtained as 69 kN. No lap splice failure was observed at the bottom of the columns. Also dowel-plaster failure didn’t formed. The specimen survived %10 higher lateral load than SPS2. On the other hand, as the load levels increased, several cracks were concentrated on the middle beam-column joint and those cracks determine the failure mode. Middle joints were seriously damaged and lateral load carried by the system dropped drastically. Left and right joint failure photos are given in Figure 14 and Figure 15, respectively.

Figure 14 Failure of left beam-column joint

Fig. 13. Hysteresis curves of specimen SPS2.

The maximum ultimate load was obtained in SpecimenSPS3 and a relatively low ultimate load capacity wasobserved in Specimen SPS1. From this figure, thecontribution of the infill can be seen (RISPS2) as comparedto the bare frame capacity. By examining Figs. 17 and 18,it can be concluded that, both the strength and the stiffnesswere significantly improved by introducing external meshreinforced infill.

Another phenomenon that must be considered for com-parison purposes is the maximum drift of the frame. Thedeformation control is important to ensure the serviceabilityrequirements (Dundar and Kara, 2007). In the design processof reinforced concrete buildings, the serviceability limit state

for lateral drift is an important design criterion that must besatisfied to prevent large second-order P-delta effects. AllSeismic Codes provide limits to prevent extensive structuraland non-structural damage and to minimize the second ordereffects (Erdem, 2006). Turkish seismic code specifies theinterstorey drift limit as 0.02 for the RC framed systems, yetthis value in Eurocode 8 regulations, for brittle nonstructuralinfills in contact with the RC frame, is taken equal to 0.5%(Altin et al., 2007). Calvi (2000) states that the 0.4%drift corresponds to the condition called “design earthquake”while 1.2% drift represents the “extreme earthquake” one.The maximum drift (1max) was approximated as the driftratio corresponding to the strength deteriorated by 20%of the ultimate load (0.8 times ultimate load-Vmax) (Hanand Jee, 2005). The calculated maximum load Vmax,corresponding top displacements were presented togetherwith the yield point at 0.75× Vmax and the ultimate driftlimit at 0.8× Vmax were tabulated in Table 3.

For specimen RISPS2 and SPS1, maximum drift ratioswere 1.99 and 1.31, respectively. External mesh reinforce-ment application caused a decrease in the drift value, but itwas also above the code requirements. Also for specimensSPS2, this drift ratio corresponding to the 20% of theultimate load is 1.69. The slip at the bottom of the columnsincreased the drift ratio of the specimen. The minimumdrift was obtained in the SPS3 specimen, which was 1.19.The measured storey drift ratios for all the strengthenedspecimens at ultimate load were greater than the limit driftratio that was suggested by the regulations.

Nat. Hazards Earth Syst. Sci., 10, 2305–2316, 2010 www.nat-hazards-earth-syst-sci.net/10/2305/2010/

S. Z. Korkmaz et al.: RC frames strengthened 2313

obtained. The reason of the failure attributed to the slippage of the reinforcing bars at the bottom of the columns. The low concrete strength, plain undeformed bars and insufficient lap splice length at the joint created such a failure mode.

-80-70-60-50-40-30-20-10

01020304050607080

-40 -30 -20 -10 0 10 20 30 40Displacement (mm)

Load

(kN

)

-80

-60

-40

-20

0

20

40

60

80-1,3% -0,8% -0,3% 0,2% 0,7% 1,2%

Drift %0,4% 1,2%-1,2% -0,4%

Figure 13 Hysteresis curves of specimen SPS2

Specimen SPS3 was prepared according to the results obtained in SPS2 testing. The bottom joints of the columns were improved by increasing the lap length of the longitudinal reinforcements. The 200 mm lap length was increased to 420 mm(20fx1.5) lap length which was given in the Turkish Earthquake Code. Other properties were as SPS2. Maximum lateral load carried by the system was obtained as 69 kN. No lap splice failure was observed at the bottom of the columns. Also dowel-plaster failure didn’t formed. The specimen survived %10 higher lateral load than SPS2. On the other hand, as the load levels increased, several cracks were concentrated on the middle beam-column joint and those cracks determine the failure mode. Middle joints were seriously damaged and lateral load carried by the system dropped drastically. Left and right joint failure photos are given in Figure 14 and Figure 15, respectively.

Figure 14 Failure of left beam-column joint

obtained. The reason of the failure attributed to the slippage of the reinforcing bars at the bottom of the columns. The low concrete strength, plain undeformed bars and insufficient lap splice length at the joint created such a failure mode.

-80-70-60-50-40-30-20-10

01020304050607080

-40 -30 -20 -10 0 10 20 30 40Displacement (mm)

Load

(kN

)

-80

-60

-40

-20

0

20

40

60

80-1,3% -0,8% -0,3% 0,2% 0,7% 1,2%

Drift %0,4% 1,2%-1,2% -0,4%

Figure 13 Hysteresis curves of specimen SPS2

Specimen SPS3 was prepared according to the results obtained in SPS2 testing. The bottom joints of the columns were improved by increasing the lap length of the longitudinal reinforcements. The 200 mm lap length was increased to 420 mm(20fx1.5) lap length which was given in the Turkish Earthquake Code. Other properties were as SPS2. Maximum lateral load carried by the system was obtained as 69 kN. No lap splice failure was observed at the bottom of the columns. Also dowel-plaster failure didn’t formed. The specimen survived %10 higher lateral load than SPS2. On the other hand, as the load levels increased, several cracks were concentrated on the middle beam-column joint and those cracks determine the failure mode. Middle joints were seriously damaged and lateral load carried by the system dropped drastically. Left and right joint failure photos are given in Figure 14 and Figure 15, respectively.

Figure 14 Failure of left beam-column joint

obtained. The reason of the failure attributed to the slippage of the reinforcing bars at the bottom of the columns. The low concrete strength, plain undeformed bars and insufficient lap splice length at the joint created such a failure mode.

-80-70-60-50-40-30-20-10

01020304050607080

-40 -30 -20 -10 0 10 20 30 40Displacement (mm)

Load

(kN

)

-80

-60

-40

-20

0

20

40

60

80-1,3% -0,8% -0,3% 0,2% 0,7% 1,2%

Drift %0,4% 1,2%-1,2% -0,4%

Figure 13 Hysteresis curves of specimen SPS2

Specimen SPS3 was prepared according to the results obtained in SPS2 testing. The bottom joints of the columns were improved by increasing the lap length of the longitudinal reinforcements. The 200 mm lap length was increased to 420 mm(20fx1.5) lap length which was given in the Turkish Earthquake Code. Other properties were as SPS2. Maximum lateral load carried by the system was obtained as 69 kN. No lap splice failure was observed at the bottom of the columns. Also dowel-plaster failure didn’t formed. The specimen survived %10 higher lateral load than SPS2. On the other hand, as the load levels increased, several cracks were concentrated on the middle beam-column joint and those cracks determine the failure mode. Middle joints were seriously damaged and lateral load carried by the system dropped drastically. Left and right joint failure photos are given in Figure 14 and Figure 15, respectively.

Figure 14 Failure of left beam-column joint

Fig. 14. Failure of the left beam-column joint.

Figure 15 Right beam-column joint failure

The column stirrups did not exist in the beam column joints. Also lap splice length of the

column longitudinal reinforcement was insufficient at those points. In addition to these detailing mistakes, another effective parameter to the failure was low concrete quality. The lateral load at the joints was transferred to the foundation, through diagonal struts along the wall panel. As a result, inclined inner forces were acting to the joints. Since joints didn’t have enough confinement and strength, they failed. The failure point of the joints can also be seen from load hysteresis curves ((Figure 16).

Fig. 15. Right beam-column joint failure.

Table 3. Ultimate load and drift values with yield load and displacement values.

Displacement Max. Load Vmax Displacement 0.75× Vmax Displacement 0.8× Vmax Story drift(mm) (kN) (mm) (kN) (mm) (kN) (%)

RFB1 40.00 34.51 16.70 25.88 – 27.61 –RISPS2 12.71 42.41 5.13 31.81 59.76 33.93 1.99%SPS1 22.39 49.29 7.48 36.97 39.43 39.43 1.31%SPS2 27.39 63.30 13.84 47.47 50.63 50.64 1.69%SPS3 9.97 69.01 16.71 51.75 35.56 55.20 1.19%

www.nat-hazards-earth-syst-sci.net/10/2305/2010/ Nat. Hazards Earth Syst. Sci., 10, 2305–2316, 2010

2314 S. Z. Korkmaz et al.: RC frames strengthened

-80-70-60-50-40-30-20-10

01020304050607080

-60 -40 -20 0 20 40 60Displacement (mm)

Load

(kN

)

-80

-60

-40

-20

0

20

40

60

80-2,0% -1,5% -1,0% -0,5% 0,0% 0,5% 1,0% 1,5% 2,0%

Drift %0,4% 1,2%-1,2% -0,4%

Figure 16 Hysteresis curves of specimen SPS3

5. Comparison of Results

The lateral load–top displacement characteristics for all the specimens are presented and compared at this section. The comparison of the behavior of the test specimens is made in terms of lateral strength, stiffness, maximum story drifts and energy dissipation characteristics. The envelopes let us compare the relative performance of the specimens. To enable comparison among the test specimens, studied here, the load–displacement envelopes are plotted by connecting the maximum peak points of consecutive hysteresis curves. Response envelope curves of the strengthened specimens are given in Figure 17 together with that of the reference bare frame and reference infilled specimen. These plots have better representation of the rate of stiffness degradation. As can be seen from this figure, strength and stiffness of both strengthened frames were significantly higher than those of the reference specimens

Figure 17 Comparison of envelope curves

Fig. 16. Hysteresis curves of specimen SPS3.

-80-70-60-50-40-30-20-10

01020304050607080

-60 -40 -20 0 20 40 60Displacement (mm)

Load

(kN

)

-80

-60

-40

-20

0

20

40

60

80-2,0% -1,5% -1,0% -0,5% 0,0% 0,5% 1,0% 1,5% 2,0%

Drift %0,4% 1,2%-1,2% -0,4%

Figure 16 Hysteresis curves of specimen SPS3

5. Comparison of Results

The lateral load–top displacement characteristics for all the specimens are presented and compared at this section. The comparison of the behavior of the test specimens is made in terms of lateral strength, stiffness, maximum story drifts and energy dissipation characteristics. The envelopes let us compare the relative performance of the specimens. To enable comparison among the test specimens, studied here, the load–displacement envelopes are plotted by connecting the maximum peak points of consecutive hysteresis curves. Response envelope curves of the strengthened specimens are given in Figure 17 together with that of the reference bare frame and reference infilled specimen. These plots have better representation of the rate of stiffness degradation. As can be seen from this figure, strength and stiffness of both strengthened frames were significantly higher than those of the reference specimens

Figure 17 Comparison of envelope curves

Fig. 17. Comparison of envelope curves.

With the increase in displacement and in the numberof cycles, the hysteretic loops tend to be inclined.This modification corresponds to a reduction in stiffness.This characteristic permits a quantification of the damage(Colomb et al., 2008). The stiffness values of the hysteresisloops were evaluated and they are presented in graphicalform in Fig. 19. The horizontal axe of the graphic is themaximum displacement of the cycle. The rate of stiffnessdegradation can also be calculated from these plots. Thepost yield behaviour is signified by monotonic degradationof stiffness. The stiffness of the strengthened specimens wassignificantly higher than the stiffness of the bare frame andreference infilled specimen.

The ability of the structure to survive an earthquakedepends on its ability to dissipate the input energy. Theenergy dissipation with hysteretic damping was determinedby calculating the areas enclosed by the hysteretic load-displacement loops. An estimate of the dissipated energy can

Also in Figure 18, comparison of ratio of the ultimate lateral loads to the reference empty

specimen RFB1 is given in clustered column type chart. This figure let us compare the relative performance of the specimens.

0

0,2

0,4

0,6

0,8

1

1,2

1,4

1,6

1,8

2

RFB1 RISPS2 SPS1 SPS2 SPS3

Ratio (KN/KN)

Ultimate Load/Reference Ultimate Load

e reference empty specimen’s ultimate load Figure 18 Ratio of specimen ultimate load to th

The maximum ultimate load was obtained in Specimen SPS3 and a relatively low ultimate load capacity was observed in Specimen SPS1. From this figure, contribution of the infill can be seen (RISPS2) as compared to the bare frame capacity. By examining the Figures 17 and 18, it can be concluded that, both the strength and the stiffness were significantly improved by the introducing external mesh reinforced infill.

Another phenomenon that must be considered for comparison purposes is the maximum drift of the frame. Deformation control is important to ensure the serviceability requirements (Dundar and Kara, 2007). In the design process of reinforced concrete buildings, the serviceability limit state for lateral drift is an important design criterion that must be satisfied to prevent large second-order P–delta effects. All Seismic Codes provide limits to prevent extensive structural and non-structural damage and to minimize the second order effects (Erdem, 2006). Turkish seismic code specifies the interstorey drift limit as 0.02 for the RC framed systems, yet this value in Eurocode 8 regulations, for brittle nonstructural infills in contact with the RC frame, is taken equal to 0.5% (Altin et al., 2007). Calvi (2000), states the 0.4% drift corresponds to the condition called “design earthquake” while 1.2% drift represents the “extreme earthquake” one. The maximum drift (Δmax) was approximated as the drift ratio corresponding to the strength deteriorated by 20% of ultimate load (0.8 times ultimate load-Vmax) (Han and Jee, 2005). Calculated maximum load Vmax, corresponding top displacements were presented together with the yield point at 0.75xVmax and ultimate drift limit at 0.8xVmax were tabulated in Table 3. Table 3 Ultimate load and drift values with yield load and displacement values

Displacement

(mm)

Max. Load Vmax (kN)

Displacement (mm)

0,75xVmax (kN)

Displacement (mm)

0,8xVmax (kN)

Story drift %

RFB1 40,00 34,51 16,70 25,88 ----- 27,61 -----RISPS2 12,71 42,41 5,13 31,81 59,76 33,93 1,99%SPS1 22,39 49,29 7,48 36,97 39,43 39,43 1,31%

Fig. 18. Ratio of specimen ultimate load to the reference emptyspecimen’s ultimate load.

SPS2 27,39 63,30 13,84 47,47 50,63 50,64 1,69%SPS3 9,97 69,01 16,71 51,75 35,56 55,20 1,19%

For specimen RISPS2 and SPS1, maximum drift ratios were 1,99 and 1,31 respectively.

External mesh reinforcement application caused a decrease in the drift value, but it was also above the code requirements. Also for specimens SPS2, this drift ratio corresponding to the 20% of the ultimate load is 1.69. The slip at the bottom of the columns increased the drift ratio of the specimen. The minimum drift was obtained in SPS3 specimen, which was 1.19. Measured storey drift ratios for all strengthened specimens at ultimate load were greater than the limit drift ratio that was suggested by the regulations.

With the increase in displacement and in the number of cycles, the hysteretic loops tend to be inclined. This modification corresponds to a reduction in stiffness. This characteristic permits a quantification of the damage (Colomb et al., 2008). Stiffness values of the hysteresis loops were evaluated and they are presented in graphical form in Figure 19. The horizontal axe of the graphic is the maximum displacement of the cycle. The rate of stiffness degradation can also be found out from these plots. The post yield behavior is signified by monotonic degradation of stiffness. The stiffness of the strengthened specimens was significantly higher than those of the bare frame and reference infilled specimen.

Figure 19 Comparison of stiffness degradation

Ability of the structure to survive an earthquake depends on its ability to dissipate the input

energy. The energy dissipation with hysteretic damping was determined by calculating the areas enclosed by the hysteretic load-displacement loops. An estimate of the dissipated energy can be found by the area inside the load–displacement hysteresis loops. The width of the loop also depends on the maximum cycle displacement. Since imposed displacements were not same for all specimens, energy dissipation values were normalized by dividing them to the corresponding cycle displacement. Cumulative energy values were evaluated by successive summation of the values. Figure 20 depicts the variation of cumulative dissipated energy as a function of cycle displacements. It may be noted that a wider loop (i.e. a large difference in ordinates in the ascending and the descending paths) would signify higher hysteretic damping.

Fig. 19. Comparison of stiffness degradation.

be found by the area inside the load-displacement hysteresisloops. The width of the loop also depends on the maximumcycle displacement. Since imposed displacements were notthe same for all specimens, energy dissipation values werenormalized by dividing them into the corresponding cycledisplacement. Cumulative energy values were evaluated bysuccessive summation of the values. Figure 20 depicts thevariation of cumulative dissipated energy as a function ofcycle displacements. It may be noted that a wider loop(i.e. a large difference in ordinates in the ascending and thedescending paths) would signify higher hysteretic damping.

Reference specimens dissipated the smallest amount ofenergy. Also specimen SPS1 displayed the poorest energydissipation performance among the strengthened specimens.The energy dissipation capacity of strengthened specimenswas significantly improved by the increase in the thicknessof the plaster. Specimen SPS3 dissipated the largest amountof energy among the others (Kilic, 2009).

Nat. Hazards Earth Syst. Sci., 10, 2305–2316, 2010 www.nat-hazards-earth-syst-sci.net/10/2305/2010/

S. Z. Korkmaz et al.: RC frames strengthened 2315

Figure 20 Energy consumption comparisons

Reference specimens dissipated the smallest amount of energy. Also specimen SPS1 displayed poorest energy dissipation performance among the strengthened specimens. The energy dissipation capacity of strengthened specimens was significantly improved by the increase in the thickness of the plaster. Specimen SPS3 dissipated the largest amount of energy among the others (Kilic, 2009). 6. Discussion

Examination of existing structures brings to light initial design and/or construction mistakes and many existing structures in Turkey are inadequate based on the current seismic design codes. Since the potential for damage and loss of life during future seismic events is unacceptably high (Ghobarah and Elfath, 2001), it is important to improve the seismic resistance of systems that are found to be vulnerable. It is urgent to develop effective and economic seismic rehabilitation systems and to retrofit nonductile deficient RC buildings before an earthquake occurs.

One of the main reasons for catastrophic results after the earthquakes is the inadequacy in lateral stiffness. The necessary amount of strengthening must be provided to increase the lateral stiffness and to improve the seismic behavior of buildings (Erdem et al., 2006).

The lateral stiffness of the frame systems can be increased by introducing new RC shear walls, diagonal steel bracings or rehabilitation of existing brick infill walls. The significant effects of the infills on structural responses of frames have been realized by many researchers (Hao et al., 2002). Presence of infill walls can be beneficial and they enable the building to avoid collapse by limiting inter-storey deformations and providing additional base shear capacity to the existing structural system (Binici et al, 2007). Infills can completely change the distribution of damage throughout the structure (Dolšek and Fajfar, 2008). In order to rely on infill wall during an earthquake, they need to be strengthened so that they contribute to lateral load-carrying capacity. New Turkish Earthquake Code stated three strengthening techniques for brick infill walls. The aim is to convert the existing infill into a load carrying system acting as a cast-in-place concrete shear wall. Fist method is the use of CFRP material. The diagonal CFRP strips that were used to retrofit brick masonry infilled reinforced concrete frames were effective in increasing lateral strength and lateral stiffness significantly. Second method is, bonding precast concrete panels on hollow brick masonry infill walls.

The last method is to apply external mesh reinforcement, attached to the existing brick wall. Since this method was recently introduced in TEC-2007, few studies exist in the literature. In order to

Fig. 20. Energy consumption comparisons.

6 Discussion

The examination of existing structures brings to light theinitial design and/or construction mistakes and many existingstructures in Turkey are inadequate based on the currentseismic design codes. Since the potential for damage andloss of life during future seismic events is unacceptably high(Ghobarah and Elfath, 2001), it is important to improve theseismic resistance of systems that are found to be vulnerable.It is urgent to develop effective and economic seismicrehabilitation systems and to retrofit nonductile deficient RCbuildings before an earthquake occurs.

One of the main reasons for catastrophic results afterthe earthquakes is the inadequacy in lateral stiffness. Thenecessary amount of strengthening must be provided toincrease the lateral stiffness and to improve the seismicbehaviour of buildings (Erdem et al., 2006).

The lateral stiffness of the frame systems can be increasedby introducing new RC shear walls, diagonal steel bracingsor the rehabilitation of existing brick infill walls. Thesignificant effects of the infills on structural responses offrames have been realized by many researchers (Hao et al.,2002). The presence of infill walls can be beneficial and theyenable the building to avoid collapse by limiting inter-storeydeformations and providing additional base shear capacityto the existing structural system (Binici et al, 2007). Infillscan completely change the distribution of damage throughoutthe structure (Dolsek and Fajfar, 2008). In order to rely oninfill wall during an earthquake, they need to be strengthenedso that they contribute to lateral load-carrying capacity.New Turkish Earthquake Code stated three strengtheningtechniques for brick infill walls. The aim is to convert theexisting infill into a load carrying system acting as a cast-in-place concrete shear wall. The first method is the useof CFRP material. The diagonal CFRP strips that wereused to retrofit brick masonry infilled reinforced concrete

frames were effective in increasing lateral strength and lateralstiffness significantly. The second method is bonding precastconcrete panels on hollow brick masonry infill walls.

The last method is to apply external mesh reinforcement,attached to the existing brick wall. Since this method wasrecently introduced in TEC-2007, few studies exist in theliterature. In order to evaluate a new strengthening methodwhich is rapid, practical, economical and occupant-friendly,an experimental study was conducted in the StructuralLaboratory of the University.

In this paper, an experimental investigation was conductedto assess the behaviour of RC frames with externalmesh reinforcement over the infill walls. The followingconclusions were drawn based on the results of the cyclictests.

The thickness of the plaster is important. Specimen SPS1developed the lowest strength among the infilled specimens.This specimen lost 50% of its lateral load carrying capacityimmediately after failure of the dowel anchorage withthe mesh plaster composite. 15 mm plaster thickness isinsufficient and is increased to 30 mm in other specimens.In real dimensions, 30 mm plaster thickness corresponds to60 mm plaster thickness. Definitely the model study involvesscale errors. At this point, an experimental study about thethickness of the plaster is needed in real dimensions. Theframe may be one storey and only plaster thickness is thevariable of the study.

Reinforcement details of the beam-column joints areimportant. A nonductile frame with bad reinforcement con-figuration cannot be strengthened with mesh reinforcementand plaster application which was presented in TEC-2007.The design engineer must solve the lap splice or confinementproblems of the joints, first. A similar conclusion was alsostated in the study of Altin et al. (2007).

For structures with very low concrete quality, this methodis not an optimal choice. One can increase the strengthof the brick walls with mesh reinforcement, but the framemay be damaged on the most forced points where stressconcentration occurs. If the concrete quality is near to10 MPa, jacketing of columns is needed. Rehabilitation ofthe existing brick walls with mesh reinforcement and theplaster application method can be applied after the jacketing.

Another discussion about the rehabilitation of the non-ductile frames is the existing foundations. Increasing theshear/force capacity of the frame resulted in an increaseon the demand of the foundations and the failure ofthe foundation should be avoided in any case. Thedesign engineer must investigate and analyse the existingfoundation. If the capacity of the existing foundation isnot satisfactory, additional rehabilitation must be appliedconcerning the foundations.

Additional experimental work is needed to understand theframe behaviour. This test can be repeated with a concretequality of 15 MPa.

www.nat-hazards-earth-syst-sci.net/10/2305/2010/ Nat. Hazards Earth Syst. Sci., 10, 2305–2316, 2010

2316 S. Z. Korkmaz et al.: RC frames strengthened

Acknowledgements.This study was a part of the research projectsupported by the Selcuk University Scientific Research ProjectOffice (BAP). The authors acknowledge Haluk Sucuoglu andBora Acun for their contribution in the planning the experimentalwork and Serra Z. Korkmaz for paper preparation.

Edited by: M. E. ContadakisReviewed by: four anonymous referees

References

Altin, S., Anil, O., Kara, M. E., and Kaya, M.: An experimentalstudy on strengthening of masonry infilled RC frames usingdiagonal CFRP strips, Compos. Part B-Eng., 39(4), 680–693,2008.

Altin, S., Anil, O., Kara, M. E., and Kaya, M.: Strengthening ofRC nonductile frames with RC infills:An experimental study,Cement Concrete Comp., 30, 612–621, 2007.

Anil, O. and Altin, S.: An experimental study on reinforcedconcrete partially infilled frames, Eng. Struct., 29(3), 449–460,2007.

Arslan, M. H. and Korkmaz, H. H.: What is to be learned fromdamage and failure of reinforced concrete structures duringrecent earthquakes in Turkey?, Eng. Fail. Anal., 14(1), 1–22,2007.

Belmouden, Y. and Lestuzzi, P.: An equivalent frame model forseismic analysis of masonry and reinforced concrete buildings,Constr. Build. Mater., 23, 40–53, 2009.

Binici, B., Ozcebe, G., and Ozcelik, R.: Analysis and design ofFRP composites for seismic retrofit of infill walls in reinforcedconcrete frames, Compos. Part B-Eng., 38, 575–583, 2007.

Colomb, F., Tobbi, H., Ferrier, E., and Hamelin, P.: Seismicretrofit of reinforced concrete short columns by CFRP materials,Compos. Struct., 82, 475–487, 2008.

Calvi, G. M.: The Behaviour of Frames Infilled With non-Reinforced and MURFOR Reinforced Clay Brick MasonryWalls, Universita Degli Studi Di Pavia Dipartimento DiMeccanica Strutturale Laboratorio Materiali e Strutture, ViaAbbiategrasso, Italy, 2000.

Dolsek, M. and Fajfar, P.: The effect of masonry infills on theseismic response of a four storey reinforced concrete frame –a probabilistic assessment, Eng. Struct., 30, 3186–3192, 2008.

Dundar, C. and Kara, I. F.: Three dimensional analysis of reinforcedconcrete frames with cracked beam and column elements, Eng.Struct., 29, 2262–2273, 2007.

Erdem, I., Akyuz, U., Ersoy, U., and Ozcebe, G.: An experimentalstudy on two different strengthening techniques for RC frames,Eng. Struct., 28(13), 1843–1851, 2006.

Firat, S., Arman, H., and Kutanis, M.: Assessment of liquefactionsusceptibility of Adapazari City after 17th August, 1999Marmara earthquake, Sci. Res. Essays, 4(10), 1012–1023, 2009.

Geng, Z. J., Chajes, M. J., Chouc, T.W., Yen, D., and Pan, C.: Theretrofitting of reinforced concrete column to beam connections,Compos. Sci. Technol., 58, 1297–1305, 1998.

Ghobarah, A., El-Attar, M., and Aly, N. M.: Evaluation of retrofitstrategies for reinforced concrete columns: a case study, Eng.Struct., 22, 490–501, 2000.

Ghobarah, A. and Elfath, H. A.: Rehabilitation of a reinforcedconcrete frame using eccentric steel Bracing, Eng. Struct., 23,745–755, 2001.

Han, S. W. and Jee, N. Y.: Seismic behaviors of columns in ordinaryand intermediate moment resisting concrete frames, Eng. Struct.,27:951–962, 2005.

Hao, H., Ma, G. W., and Lu, Y.: Damage assessment ofmasonry infilled RC frames subjected to blasting induced groundexcitations, Eng. Struct., 24, 799–809, 2002.

Hueste, M. B. D. and Bai, J. M.: Seismic retrofit of a reinforcedconcrete flat-slab structure: Part I – seismic performanceevaluation, Eng. Struct., 29, 1165–1177, 2007.

Kaltakci, M. Y., Arslan, M. H., Korkmaz, H. H., and Ozturk, M.: Aninvestigation on failed or damaged reinforced concrete structuresunder their own-weight in Turkey, Eng. Fail. Anal., 14(6), 962–969, 2007.

Kaltakci, M. Y., Arslan, M. H., Yilmaz, U. S., and Arslan, H. D.: Anew approach on the strengthening of primary school buildingsin Turkey: An application of external shear wall, Build. Environ.,43, 983–990, 2008.

Oliveto, G. and Decanini, L. D.: Repair and retrofit of a sixstorey reinforced concrete building damaged by the earthquake insouth-east Sicily on the 13th December 1990, Soil Dyn. Earthq.Eng., 17, 57–71, 1998.

Onal, M.: Reinforcement of beams by using carbon fiber reinforcedpolimer in concrete building, Sci. Res. Essays, 4(10), 1136–1145, 2009.

Rocha, P., Delgado, P., Costa, A., and Delgado, R.: Seismic retrofitof RC frames, Comput. Struct., 82, 1523–1534, 2004.

Shing, P. B. and Mehrabi, A. B.: Behaviour and analysis ofmasonry-infilled frames, Prog. Struct. Eng. Mat., 4, 320–331,2002.

Turkish Earthquake Code: Turkish Code for Buildings in SeismicZones, Turkish Seismic Code, The Ministry of Public Works andSettlement, Ankara, Turkey, 2007.

Zou, X. K., Teng, J. G., Lorenzis, L. D., and Xia, S. H.: Optimalperformance-based design of FRP jackets for seismic retrofit ofreinforced concrete frames, Compos. Part B-Eng., 38, 584–597,2007.

Nat. Hazards Earth Syst. Sci., 10, 2305–2316, 2010 www.nat-hazards-earth-syst-sci.net/10/2305/2010/