Upload
mohd-azman-suwandi
View
224
Download
0
Embed Size (px)
Citation preview
8/11/2019 Exp 7 Complete
1/36
ABSTRACT
The primary objective of this experiment is to carry out the thermodynamic
processes on air and also to analyze the processes characteristics (experimental
results) using the psychometric chart. Five thermodynamics processes were tested in
this experiment, which includes cooling, heating, humidification of air, cooling and
dehumidification of air and lastly, heating and humidification of air. Through the
results, and analysis using the psychometric chart, we are to calculate the energy
reuired for air cooling, air heating, cooling and removal of water from air, heating
and addition of water into air.
The experiment was carried out using the !ilton "ir #onditioning $nit.
#alculating the enthalpy change and power of varies thermodynamic process over the
air conditioning unit validated the result. %ith prior assumption, the calculated
enthalpy change and power was smaller than the enthalpy change in there invalidating
the assumption. &t was mathematically difficult to calculate and get an accurate
reading from psychometric chart because of the nature of transient system. Therefore,
the enthalpy change and power were inconclusive.
'ased on the result, enthalpy change for heating and humidification in the air
process is highest compared to other process. n the other hand, power for the
heating and humidification process was the highest among other process.
i
8/11/2019 Exp 7 Complete
2/36
TABLE OF CONTENTS
Contents Page
"bstract i
ist of Tables iii
ist of Figures iii
*omenclature iv
+. &ntroduction +
-. Theory and %oring /uations 0
0. 1aterial and 1ethods 2
3. 4esult and 5iscussion +
6. #onclusion and 4ecommendation +6
7. 4eferences +7
"ppendix " +2
"ppendix ' -3
"ppendix # -8
"ppendix 5 -9
"ppendix / 0
ii
8/11/2019 Exp 7 Complete
3/36
LIST OF TABLES
Table Title Page
"+ %et bulb and dry bulb temperature readings taen from +2
the experiment
"- /xperimental 5ata for the %hole :rocess +9
"0 #ooling process values from psychometric chart -
"3 !eating process values from psychometric chart -
"6 ;apor humidification in air from psychometric chart-+
"7 #ooling and water dehumidification from air process -+
values from psychometric chart
"2 !eating and water humidification in air --
"8 /nergy and power results --
LIST OF FIGURES
Figure Title Page
#+ :sychometric #hart < =.&. unit -8
5+ 5ry>bulb temperature -9
5- 5ew>point temperature -9
50 4elative humidity -9
/+ !ilton "ir>conditioning $nit 0
iii
8/11/2019 Exp 7 Complete
4/36
NOMENCLATURE
" cross sectional area
d diameter
u internal energy
d heat transfer
dw wor
: power
m mass flow rate
"i inlet air area
"o outlet air area
Twb wet bulb temperature
Tdb dry bulb temperature
hinitial enthalpy for inlet air
hfinal enthalpy for outlet air
?! enthalpy change
ha absolute humidity
hr relative humidity
;! humid volume
iv
8/11/2019 Exp 7 Complete
5/36
1. INTRO!UCTION
This report discusses the various thermodynamics processes on air experiment
and to analyze the experimental results by using the psychometric chart. The five
processes that were being carried out were cooling, heating, humidification, cooling
and dehumidification of air and heating and humidification of air. The data reuired
was obtained from the computer, which was provided in the Food and :rocess
laboratory connected to the !ilton "ir>#onditioning $nit. The energy involved and
the power reuired in each process was then calculated using the psychometric chart.
:sychometric chart has been used to the study of the psychometric process.
n a psychometric chart (or humidity chart) several properties of a gas>vapor mixture
are cross>plotted, providing a concise complication of large uantity of physical
property data.
The enthalpy, ! can be read directly from the psychometric chart with
reference to the dry bulb and wet bulb temperature obtained. The dew point and the
relative humidity can determined from the chart as well.
The remainder of the report provides detailed analysis of the Theory and
%oring euations for this experiment. The specific procedure is outlined in 1aterial
and 1ethod section. :resentation of the findings and detailed discussion of the result
can be found in 4esult and 5iscussion section. &n a nutshell, summary of the report
+
8/11/2019 Exp 7 Complete
6/36
and recommendation are integrated into the #onclusion and 4ecommendation
section.
-
8/11/2019 Exp 7 Complete
7/36
". T#EOR$ AN! %OR&ING E'UATIONS
:sychometric is the study of energy and the water vapor in the air when the
thermodynamic go through process such as cooling, heating, humidification of the air,
cooling and dehumidification of air and also heating and dehumidification in air. "ll
these process can be presented and defined by using the psychometric chart.
:sychometric chart is based on the @ibbs phase rule, which states that specifying a
certain number of the intensive variables of a system automatically fixes the value of
the remaining intensive variables. The process can be traced and well monitored. &t is
well presented and defined by using psychometric chart, Figure #+.
The different properties of humid air at + atm that appear on the psychometric
chart are defined and described as followsA
5ry>bulb temperature, TdbA
&t is the air temperature as measured by a standard thermometer that has no
water on its surface. &t indicates the intensity of the sensible heat content of
the substance. &t does not signify anything about the latent heat content.
Temperature of the air is actually referred as the dry>bulb temperature.
%et>bulb temperature,TwbA
&t is a temperature associated with the moisture content of the air. The uantity
is best defined in terms of how it is measured. " wic (water>soaed cloth
which is wrapped around the bulb of a thermometer) evaporates water into the
flowing air. "s heat transfer from the bulb accompanies the evaporation, the
0
8/11/2019 Exp 7 Complete
8/36
bulb temperature will drop at a certain value and remains there. The final
temperature reading is the wet>bulb temperature of the air flowing past the
wic.
"bsolute humidity (moisture content), haA
&t is the ratio of mass of vapor to mass of dry air. &t is the ordinate of the chart.
4elative humidity, hrA
&t is a measure of how saturated the air is with the water. &n other words,
relative humidity is the ratio of the actual mass of water vapor in the air to the
mass of water vapor that would saturate the air at the same temperature. &f the
air is holding all the moisture it can for a specific set of conditions, then it is
said to be saturated, +B hr. The amount of moisture the air can hold
increases as the dry>bulb temperature of the air increase. %hen relative
humidity of the air is referred, it is important to define the dry>bulb
temperature of the air that being referred. #urve on the chart correspond to
specified values of hr(+B, 9B, 8B, etc.).
!umid volume, ;!A
&t is the volume occupied by + g of dry air plus the water vapor that
accompanies it.
5ew point, TdpA
&t is a temperature at which humid air becomes saturated if it is cooled at
constant pressure. &f moist air is cooled, it cannot hold the same amount of
moisture. "t some point, the moisture will condense out of the air onto any
nearby surface. 5ew point is reached as the dry>bulb temperature is reduced
3
8/11/2019 Exp 7 Complete
9/36
and the specific humidity is held constant. n the chart, dew point is read
along the saturation line (+B hr).
=pecific enthalpy of saturated airA
The diagonal scale above the saturation curve on the chart shows the enthalpy
of a unit mass of dry air plus the water vapor it contains at saturation. To
obtain the enthalpy, constant wet>bulb temperature line is determined from the
saturation curve at the desired temperature to the enthalpy scale.
/nthalpy deviationA
The remaining curves on the chart are almost vertical and convex to the left,
with labeled values of>.6, >.+, >.-, and so on. /nthalpy deviation is added
to the value of specific enthalpy.
The heated refrigerant vapor that is drawn into the compressor is subjected to
higher pressure. "s a result of being pressurized, the temperature of the vapor
increases. The refrigerant then passes into the condenser where enough heat is
removed and the hot vapor changes bac to a hot liuid refrigerant, which is still
under pressure. The liuid refrigerant then flow to the expansion valve. "s the liuid
passes through the valve, pressure is reduced immediately. The pressure decrease
lowers the temperature of the liuid even more and it is ready to absorb heat.
&n the air>cooling process, the refrigerant vapor is passed through a fan>cooled
coil. The air blown over the coil is cooler than the refrigerant vapor. Thus the vapor
gives off heat to the air through the coils wall. The air is then blown to the outdoors
6
8/11/2019 Exp 7 Complete
10/36
and the heat is dissipated in the atmosphere. &n the condensing process, the air pics
up heat from the refrigerant. &n both instances, a coil is the heat transfer surface.
The following are woring euations that had been used in the experimentA
From the First aw of Thermodynamics,
C D /nthalpy change, ?h
D ?hfinal> ?hinitial EEEEE (0)
The power is defined asA
: D .m
x ..............................................................................(3)
#hanges in the humidity of air
D (absolute humidity of air at state of cooling and dehumidification
of air process) (absolute humidity of air at final state of cooling
process)
#hanges in the humidity volume of the water
D (humid volume of water at initial state of cooling G
dehumidification of air process) (humid volume of water at final
state of cooling G dehumidification)
&n this experiment, the assumptions made are as listed belowA
The inlet and outlet ducts were round pipes.
The processes were steady>flow process and the mass flow rate of dry air
remained constant during the process.
5ry air and the water vapor were ideal gases.
The inetic and potential energy changes were negligible.
7
8/11/2019 Exp 7 Complete
11/36
(. MATERIALS AN! MET#O!S
@enerally, air conditioner is operating using the vapor>compression refrigeration
cycle. 'asically, an air>conditioning system consists of four parts which includes A
i. :reheaters A Four electrical heaters used to heat the air entering the air>condition
ii. 'oilerA &t is used to supply steam for humidifier. &t is made of stainless steel
container and three electrical heaters dipped into the water
iii. #ooling #oil A &t is used to cool the air with or without dehumidification
iv. 4otating vane anemometer A &t is used to measure air flow rate in feet per minute
v. 4eheaters A Four electrical heaters after the cooling coil which reheats the cooled
air before delivery to the space, if reuired
vi. #ompressor>#ondenser unit A To complete the refrigeration cycle
vii. Fan A For air circulation
viii. Thermocouples and thermometers ) For measuring dry and wet bulb
temperatures
The specific procedures for the experiment are as followA>
A* Cooling +ro,ess
+. Fan and compressor of the !ilton air>conditioning is switched on.
-. The air velocity is determined by adjusting rotation of the fan.
0. The air velocity then, is measured and recorded.
3. "ir>cooling process continued until the stability of the system was reached.
2
8/11/2019 Exp 7 Complete
12/36
6. The wet>bulb temperature and dry>bulb temperature for the entering air and
leaving air were recorded.
7. The heat transfers enthalpy and power for the air>cooling process was
calculated.
B* #eating +ro,ess
+. The fan was switched on and the velocity of air was measure and recorded.
-. Then, electrical heaterswere switched on and it was left that way until the
stable
condition was reached by the system.
0. Temperature readings of the wet>bulb and the dry>bulb for both inlet air and
outlet air were recorded.
3. Finally, the enthalpy and energy for the heating process was calculated.
C* -a+or u/i0ii,ation in air
+. The fan was switched on. The velocity of air was measured and recorded.
-. Then, electrical heaters (The lower heater, upper heater and water heater) were
switched on to heat the water in tan until mist was observed on the glass in the
euipment.
0. Temperature readings of the wet>bulb and the dry>bulb for both inlet air and
outlet air were recorded.
3. The amount of humidity in air was calculated.
6. Finally, the enthalpy, sensible heat and latent heat for the vapor humidification
7. :rocess in air ware also calculated.
8
8/11/2019 Exp 7 Complete
13/36
!* Cooling +ro,ess an0 2ater 0eu/i0ii,ation ro/ air
+. The fan was switched on. The velocity of air was measured and recorded.
-. Then, the compressor was switched on and the cooling process was carried on
until the water evaporation from the air occurs.
0. Temperature readings of the web>bulb and dry>bulb for both inlet air and outlet
air were recorded when the evaporation occur.
3. Cuantity of the wasted water was calculated.
6. Finally, the energy of the whole process was calculated
E* #eating +ro,ess an0 2ater u/i0ii,ation in air
+. The fan was switched on. The velocity of air was measured and recorded.
-. The lower heater (-%) was switched on to boil the water.
0. The first and second pre heaters (+%) were switched on to dry the water.
3. Temperature readings of the web>bulb and dry>bulb for inlet air, air after
sprayer, air after heater and outlet air were recorded.
6. Finally, the energy of the whole process was calculated.
9
8/11/2019 Exp 7 Complete
14/36
3. RESULTS AN! !ISCUSSION
a* Cooling Pro,ess
From Table "0, the increase in wet bulb and dry bulb temperature of the outlet
air before cooling process compared to that of the inlet air was due to the unwanted
external heat supply to the system from surrounding namely the heat from the
compressor which gives rise to the initial enthalpy change of .8 H I g 5" that can be
determined from the psychometric chart. There was a great decrease in both wet bulb
and dry bulb temperature of the outlet air after the cooling process had been carried out
and it gave a final stage enthalpy change of >2.2 H I g. Therefore the total enthalpy
change of the cooling process was >8.6 H I g.
The negative sign showed that the process was exothermic reaction. /xothermic
reaction is a reaction that releases heat or energy to the surroundings. Therefore, the final
enthalpy was less than the initial enthalpy. The power of cooling was calculated to be
>+.620 %. The negative sign means that the wor was done on the system by the
surroundings.
The relative humidity of air increased during the cooling process even if the
specific humidity remained constant. This was due to the humidity was the ratio of the
moisture content to the moisture capacity of the air at the same temperature. The dew
point temperature decreased to --.8 o # at the final outlet.
+
8/11/2019 Exp 7 Complete
15/36
4b* #eating Pro,ess
&n heating process, there was no moisture added or removed from the air and the
amount of moisture in the air was constant. From Table "3, the enthalpy increased after
the heating process which had a change of -2.+ H I g. The positive sign showed that
the process was endothermic reaction and the energy was absorbed into the process from
the surrounding. Therefore, the initial enthalpy was less than the final enthalpy. The
power of heating was calculated to be 3.98- %. The positive sign means that the wor
was done by the system. From Table -, the relative humidity decreased during heating
process. The relative humidity at the final was -. B.
4,* -a+or #u/i0ii,ation in Air Pro,ess.
From the Table "6, the enthalpy change was -6.6 HIg because energy was
needed to add moisture into the air. The positive sign showed that heat transfer from the
surrounding to the system. The power that was supplied by the !ilton>air conditioning
was 3.22 %. The dew point temperature for outlet air at final stage is higher than other
in the table 0 which means that vapor humidification in air becomes saturated if it is
cooled at constant pressure only at 0+.+o#.
40* Cooling an0 %ater !eu/i0ii,ation Pro,ess.
For cooling and dehumidification, the sensible heat is transferred out of the air
due to the drop of temperature and the latent heat is removed as water dehumidification
++
8/11/2019 Exp 7 Complete
16/36
too place when the air reaches the final temperature. &n this process the liuid
temperature is low enoughJ the air is cooled below its dew point, --.6o# and caused
some of the water vapor in it to condense. The uantity of water disposal is -6 ml. Then,
the enthalpy for this process is>+3.9HIg and it was exothermic reaction because of the
negative sign. The power of this process is >-.20+ % and the negative sign shows that
the wor is done by the system. &n this process, the changes in the humidity of air are
>.-8 g !-Ig 5". The negative sign in the answer of changes in the humidity of
air shows that the moisture content is reduced in the dehumidification process. Thus,
there is water disposal from the air in the form of liuid.
4e* #eating an0 #u/i0ii,ation in Air Pro,ess.
5uring heating and water humidification in air process, notice on the table "2
that when the air and water mixture move to higher relative humidity, the dry bulb
temperature rises. For instance, the outlet would move to a state of 23.6 B relative
humidity. !owever, this value is not constant for all the humidification process because
relative humidity of air different everyday.
For heating and humidification in air process, the enthalpy change is 39.7 HIg.
The positive sign showed that more energy reuired releasing the vapor from the air.
:ower needed is 8.980 %. Thus the surrounding was moist in the experiment, since a
lots of power was reuired to vaporize the water.
+-
8/11/2019 Exp 7 Complete
17/36
For spraying temperature, the enthalpy change is -3.6HIg and power is 3.302
%. !owever, the experiment data is different from the theoretical data because the wet
bulb temperature decreased with a small amount. This is due to the inconsistency of
temperature, the movement of student around created a mild wind (moving air) that
affected the measurement.
Finally for heating temperature, the enthalpy change is -6.+ HIg and the power
is 3.637 %. &n heating, energy is needed to brea the bond of water to vapor and mix
into the air. Therefore, the enthalpy is positive.
The problems encountered in the experiment
&nconsistent of temperature
The body temperature of the student was also a factor affects temperature. The
movement of student created mild wind (moving air) that could affect the measurement
of temperature. The sensitive thermometer in the air>conditioning unit could detect even
a very small change in the surrounding. 'esides that, the transmission resistance of the
computer cable will also cause inaccuracy of the data.
&nconsistent of mass flow rateA
The movement of student created a mild wind (moving air) inside the laboratory room
even though the experiment was conducted inside a laboratory.The transmission
resistance of the computer also contributed to the inconsistency.
+0
8/11/2019 Exp 7 Complete
18/36
The precaution step involved in this experiment
+. &n order to reduce the instability of data cause by air flow from surrounding, the
experiment was carried out inside a closed laboratory room.
-. The body temperature is one of the factors that cause the inconsistent of the
temperature. %e are avoided to stand in front of the fan chamber.
0. The amount of water collected in the cooling and dehumidification process is
measured by cylinder. The water was poured carefully in order to avoid spillage.
+3
8/11/2019 Exp 7 Complete
19/36
5. CONCLUSION AN! RECOMEN!ATIONS
&n conclusion, the heating and humidification in air process attained the highest
change of enthalpy which is 39.7 HIg with the power of 8.980 % . The second
highest enthalpy change was heating process with an enthalpy change of -2.+ HIg and
the third highest enthalpy change was changes of vapor humidification in air process as
-6.6 HIg. &n addition, cooling had an enthalpy change of >8.6 HIg, while cooling
and dehumidification with >+3.9 HIg enthalpy change. Furthermore, the spraying
temperature had -3.6 HIg enthalpy change and for the heating temperature, it had
-6.+ HIg change of enthalpy.
For future experiments, no one is supposed stand or sit near or in front of the air
inlet and air outlet area to ensure that the velocity of inlet air and outlet air are stable. %e
also must wait until the temperature of inlet air and outlet air is stable before the data to
be taen. "fter finish one process, we must wait for 6 minutes to ensure the temperature
of the system is stable before continue with the following process. &n process of cooling
and dehumidification in air, we must wait until all of water has finished dripping before
reading of amount of water dripped is taen. 'esides that, no people should stand in
front of the air inlet and air outlet area to prevent any disruption on the air flow that will
cause inaccuracy in the data obtained.
+6
8/11/2019 Exp 7 Complete
20/36
6. REFERENCES
+. 4ichard /. =onntag, #laus 'orgnae. (+998).Introduction to
Engineering Thermodynamics. (-nd/dition) *ew Hersey A Hohn %iley G =ons,
&nc.
-. 4ichard 1. Felder, 4onald %. 4ousseau. (-). Elementary Principles of
Chemical Processes(0rd /dition). *ew Hersey A Hohn %iley G =ons, &nc.
0. ;. :aul ang. (+993). :rinciples of "ir>conditioning. *ew Kor A 5elmar
:ublishers &nc.
3. Kunus ". #engel, 1ichael ". 'oles. (-7). Thermodynamics < "n /ngineering
"pproach (6th/dition). *ew Kor A 1c@raw>!ill :ublications.
+7
8/11/2019 Exp 7 Complete
21/36
APPEN!ICES
"::/*5&L "
Ra2 !ata
Table A1) %et bulb an0 0r7 bulb te/+erature rea0ings ta8en ro/ te e9+eri/ent.
:rocess &nlet "ir Temperature
Ti ( o # )
utlet "ir
Temperature
Te ( o # )
#hange of
Temperature
Tchange (o # )
%et bulb 5ry bulb %et bulb 5ry bulb %et bulb 5ry bulb
". #ooling 'efore -3.- 0+.+ -3.3 0+.0 >.3 >.0
"fter -3.9 0+.9 --.9 -0.0 0.- 2.7
'. !eating 'efore -6.0 0+.8 -6.0 -2.3 .- 0.
"fter -6.9 0-. 0+.7 66. >6.9 >--.8
#. ;apor
!umidification in
"ir
'efore -6.6 0-. -7.- 0-.9 >.7 >+.-
"fter -7.+ 0-.2 0+.8 03.6 >2.7 >-.3
5. #ooling and
%ater
5ehumidification
'efore -6.9 0-.6 -7.3 00.0 >.6 >.7
"fter -7. 0-.8 --.8 -0.7 0.3 8.9
/. !eating and
!umidification in
"ir
'efore -7.+ 0-.9 -7.+ 0+.- >.0 .3
"fter -7.7 0+.6 06.7 3.+ >++. >+7.+=praying
temperature "fter 0+.6 07.+ *" *" *" *"
!eating
Temperature "fter 06.7 3.+ *" *" *" *"
*" D *ot applicable
+2
8/11/2019 Exp 7 Complete
22/36
Table A") E9+eri/ental !ata or te %ole Pro,ess.
:rocess
&nlet
Temperature Tin
(o#)
utlet
Temperature
Tout(o#)
Temperature
#hanges
(o#)
"ir F
4ate,
(gIs%eb
'ulb
5ry
'ulb
%eb
'ulb
5ry
'ulb
%eb
'ulb
5ry
'ulb
+8
8/11/2019 Exp 7 Complete
23/36
")#ooling
&nitial-3.- 0+.+ -3.3 0+.0 .- .-
+86
Final-6.- 0+.9 --. --.8 >0.- >9.+
+80
')!eating
&nitial
-6.0 0+.8 -6.0 -2.3 >3.3
+86
Final
-6.9 0-. 0+.7 66. 6.2 -0.+8+
#)#hanges of
!umidification in the
"ir
&nitial
-6.6 0-. -7.- 0-.9 .2 .9+82
Final
-7.+ 0-.2 0+.8 03.6 6.6 +.8+83
5)#ooling and
5ehumidification
&nitial
-6.9 0-.6 -7.3 00.0 .6 .8
+86
Final
-7. 0-.8 --.8 -0.7 >0.- >9.-
+80
/)5ehumidification of
"ir
&nitial
-7.+ 0-.9 -7.+ 0+.- >+.2+83
Final-7.- 0-.9 0-.8 3-.3 7.7 9.6
+8+
Table A() Cooling +ro,ess :alues ro/ +s7,o/etri, ,art.
#ooling :rocess %et
'ulb
Tweto
#
5ry
'ulb Tdry
o
#
/nthalpy
! (H I g
5")
"bsolute
!umidity
% ( g
!- I g
5" )
4elative
humidity
hr (B)
5ew
:oint
Tdew (o
#)
'efore &nlet "ir -3.- 0+.+ 2-.2 .+7-+ 67.9 -+.7
utlet "ir -3.3 0+.0 20.6 .-+6 62.+ -+.8
"fter &nlet "ir -3.9 0+.9 26.7 .+2 62. --.0
+9
8/11/2019 Exp 7 Complete
24/36
utlet "ir --.9 -0.0 72.9 .+232 97.2 --.8
Table A3) #eating +ro,ess :alues ro/ +s7,o/etri, ,art.
!eating :rocess %et
'ulb
Tweto#
5ry
'ulb Tdry
o #
/nthalpy
! (H I g
5")
"bsolute
!umidity
% ( g
!- I g
5" )
4elative
humidity
hr (B)
5ew
:oint
Tdew (o#)
'efore &nlet "ir -6.0 0+.8 22.0 .+22+ 69.7 -0.
utlet "ir -6.0 -2.3 22.6 .+962 83.7 -3.7
"fter &nlet "ir -6.9 0-. 29.9 .+873 7-. -0.8utlet "ir 0+.7 66. +2.- .+993 -. -3.9
Table A5) -a+or u/i0ii,ation in air ro/ +s7,o/etri, ,art.
;apour
!umidification
:rocess
%et
'ulb
Tweto#
5ry
'ulb Tdry
o #
/nthalpy
! (H I g
5")
"bsolute
!umidity
% ( g
!- I g
5" )
4elative
humidity
hr (B)
5ew
:oint
Tdew (o#)
'efore &nlet "ir -6.6 0-. 28.+ .+297 69.8 -0.-
utlet "ir -7.- 0-.9 8+.- .+828 69.0 -0.9
"fter &nlet "ir -7.+ 0-.2 8.2 .+879 69.2 -0.8
utlet "ir 0+.8 03.6 +9.0 .-9+- 8-.8 0+.+
Table A6) Cooling an0 2ater 0eu/i0ii,ation ro/ air +ro,ess :alues ro/
+s7,o/etri, ,art.
#ooling and %ater %et 5ry /nthalpy "bsolute 4elative 5ew
-
8/11/2019 Exp 7 Complete
25/36
5ehumidification
:rocess
'ulb
Tweto#
'ulb Tdry
o #
! (H I g
5")
!umidity
% ( g
!- I g
5" )
humidity
hr (B)
:oint
Tdew (o#)
'efore &nlet "ir -6.9 0-.6 29.9 .+830 69.7 -0.7
utlet "ir -7.3 00.0 8-. .+896 68.6 -3.+
"fter &nlet "ir -7. 0-.8 8.0 .+832 68.2 -0.2
utlet "ir --.8 -0.7 72.6 .+2+9 90.6 --.6
Table A;) #eating an0 2ater u/i0ii,ation in air.
!eating and
!umidification
:rocess
%et
'ulb
Tweto#
5ry
'ulb Tdry
o #
/nthalpy
! (H I g
5")
"bsolute
!umidity
% ( g
!- I g
5" )
4elative
humidity
hr (B)
5ew
:oint
Tdew (o#)
'efore &nlet "ir -7.+ 0-.9 8.2 .+87 68.8 -0.8
utlet "ir -7.+ 0+.- 8.8 .+90- 72.+ -3.3
"fter &nlet "ir -7.7 0+.6 80. .-2 78.6 -6.
;apour
=pray
0+.6 07.+ +2.7 .-227 2-.3 0.0
utlet "ir 06.7 3.+ +0-.2 .069 23.6 03.2
Table A8.6 >+.67-
!eating -2.+ 3.98-;apor !umidification in "ir -6.6 3.22
#ooling and
5ehumidification
>+3.9 >-.20+
!eating and !umidification
in "ir
39.7 8.980
-+
8/11/2019 Exp 7 Complete
26/36
=praying Temperature -3.6 3.302
!eating temperature -6.+ 3.637
--
8/11/2019 Exp 7 Complete
27/36
APPEN!I= B
Cal,ulation
("ll the enthalpies are obtained from psychometric chart)
Cal,ulation or ,ooling +ro,ess>
Flow rate D +86 gIs
?h initial = 20.6 HIg < 2-.2 HIg
D .8 HIg
?h final D 72.9 HIg < 26.7 HIg
D > 2.2 HIg
/nthalpy change, ?! D ?h final >?h initial
D >2.2 HIg < .8 HIg
D > 8.6 HIg
:ower, % D m ?!
D +86 gIs x ( >8.6 HIg ) x +gI+g
D >+.620 %
Cal,ulation or eating +ro,ess>
Flow rate D +8+.6 gIs
?h initial D 22.6 HIg < 22.0 HIg
D .- HIg
?hfinal D +2.- HIg < 29.9 HIg
-0
8/11/2019 Exp 7 Complete
28/36
D -2.0 HIg
/nthalpy change, ?! D ?h final > ?h initial
D -2.0 HIg < .- HIg
D -2.+ HIg
:ower, % D m ?!
D +8+.6 gIs x -2.+ HIg x +gI+g
D 3.98- %
Cal,ulation or :a+or u/i0ii,ation in air>
Flow rate D +83.7 gIs
?h initial D 8+.- HIg < 28.+ HIg
D 0.+ HIg
?h final D +9.0 HIg < 8.2 HIg
D -8.7 HIg
/nthalpy change, ?! D ?h final >?h initial
D -8.7 HIg < 0.+ HIg
D -6.6 HIg
:ower, % D m ?!
D +83.7 gIs x -6.6 HIg x +gI+g
D 3.22 %
-3
8/11/2019 Exp 7 Complete
29/36
Cal,ulation or ,ooling +ro,ess an0 0eu/i0ii,ation o air +ro,ess>
Flow rate D +80.0 gIs
?h initial D 8-. HIg < 29.9 HIg
D -.+ HIg
?h final D 72.6 HIg < 8.0 HIg
D >+-.8 HIg
/nthalpy change, ?! D ?h final >?h initial
D >+-.8 HIg < ( >-.+ HIg)
D>+3.9 HIg
:ower, % D m ?!
D +80.0 gIs x (>+3.9 HIg) x +gI+g)
D >-.20+ %
Cuantity of water disposedA -6ml
#hanges in the humidity of airA
("bsolute humidity of air at final state of cooling and dehumidification of air process) kg,+232., !-Ig 5"
D >.-8g !-Ig 5"
Cal,ulation or eating an0 u/i0ii,ation in air +ro,ess>
Flow rate D +8+.+ gIs
?h initial D 8.8 H I g < 8.2 H I g
-6
8/11/2019 Exp 7 Complete
30/36
D .+ H I g
?h final D +0-.2 H I g < 80. H I g
D 39.2 H I g
/nthalpy change, ?! D ?h final >?h initial
D 39.2 H I g < .+ H I g
D 39.7 H I g
:ower, % D m ?!
D+8+.+ gIs x 39.7 H I g x +gI +g
D 8.980 %
For s+ra7ing te/+erature>
/nthalpy change, ?! D ?h final >?h initial
D +2.7 H I g < 80. H I g
D -3.6 H I g
:ower, % D m ?!
D +8+.+ gIs x -3.6 H I g x +gI+g
D 3.302 %
For eating +ro,ess>
/nthalpy change, ?! D ?h final >?h initial
D +0-.2 HIg < +2.7 HIg
D -6.+ HIg
:ower, % D m ?!
D +8+.+ gIs x -6.+ HIg x +gI+g
D 3.637 %
-7
8/11/2019 Exp 7 Complete
31/36
APPEN!I= C
Figure C1) Ps7,o/etri, ,art
-2
8/11/2019 Exp 7 Complete
32/36
APPEN!I= !
Figure 5+A 5ry bulb temperature.
Figure 5-A 5ew point temperature.
Figure 50A 4elative humidity
-8
8/11/2019 Exp 7 Complete
33/36
8/11/2019 Exp 7 Complete
34/36
8/11/2019 Exp 7 Complete
35/36
0+
8/11/2019 Exp 7 Complete
36/36