Upload
woodstoon
View
216
Download
0
Embed Size (px)
Citation preview
7/28/2019 Existing Grounding Systems Rob Schaerer
1/46
April 7, 2011
Substation Grounding Systems
, . .
7/28/2019 Existing Grounding Systems Rob Schaerer
2/46
Outline of Topics
Why grounding is important
What are we looking at
Basic grounding system design process
Considerations for existing substations
Previous analysis
Verification of previous study and data
Mitigation
Testin
Maintenance Plans
7/28/2019 Existing Grounding Systems Rob Schaerer
3/46
Personnel Protection
IEEE 80-2000
Provides guidance onlimits based onscenaros presen ein a substation
environment and
body when subjectedto an electric shock
Additional concernsinclude equipment
fault conditions)
7/28/2019 Existing Grounding Systems Rob Schaerer
4/46
Personnel Protection Voltages
Touch/ste volta es
Touch voltage
ground at your feet
Typically limited to a reach distance of three feet (or one meter)
Step voltage
Voltage difference in ground between your feet as you are standing
Typically limited to a stride of three feet (or one meter)
7/28/2019 Existing Grounding Systems Rob Schaerer
5/46
Personnel Protection Voltages
SLG Fault SLG Fault
200Volts 100Volts
Voltageat Foot
Voltage1000 V
Voltageat Foot
Voltageat Foot
Grid1000 V
800 V
Grid1000 V
800 V900 V
7/28/2019 Existing Grounding Systems Rob Schaerer
6/46
Behavior of Substation Under Fault Conditions
Ground Potential Rise
V = I * R
Fault current into the grounding system times resistance toremo e ear
Voltage magnitude determines grounding system performance
rmar y use or personne comp ance
Can also damage equipment
Basis for determinin touch and ste volta es
Fault Current Return Path
7/28/2019 Existing Grounding Systems Rob Schaerer
7/46
Behavior of Substation Under Fault Conditions
Ground Potential Rise (GPR) = I * R
7/28/2019 Existing Grounding Systems Rob Schaerer
8/46
Process of Designing a Grounding System
Gather and analyze soil data
Obtain fault data Develop preliminary grounding system design
Analyze design for touch and step voltage performance,
plus impedance and GPR Perform mitigation until touch and step voltage
compliance are met
a ona equpmen spec c groun ng Test the installed grounding system to verify performance
eexamne e groun ng sys em n e u ure
7/28/2019 Existing Grounding Systems Rob Schaerer
9/46
Considerations for Existing Substations
Was an analysis ever preformed?
Many older substations were built on rules of thumb
If not, most practical approach is to analyze before acting
Is the previous analysis still valid?
Has the system changed? Did the study use accurate data?
Testing to validate performance
Maintenance plans
7/28/2019 Existing Grounding Systems Rob Schaerer
10/46
Examining Previous Analysis - Fault
Fault currents
Maximum single-line-to-ground fault
Often increases with time as the system strengthens
,
proportionally
Clearing time (backup)
Protection failure
Consider worst case scenario (longest clearing delay time) anduse for grounding analysis
7/28/2019 Existing Grounding Systems Rob Schaerer
11/46
Examining Previous Analysis - Soil
Soil information has large impact on overall result, but is
Soil data often collected by geotechnical or other firms that havelimited understanding of how data is used for grounding analysis
Measurements are often insignificant (not enough data measured)
Data collection process often produces errors that may not beexpected by experienced engineers or testers
Examining the raw data can help validate the measurements
Analysis of soil data measurements is both an art and a science Older techniques often involved a uniform soil approximation, or
sometimes a two layer model that may be insufficient
7/28/2019 Existing Grounding Systems Rob Schaerer
12/46
Soil Resistivity Tests
Characterize soil by the electrical resistivity
v y y u
system for a specific performance objective All soil conducts electrical current
Some soils have good electrical conductivity while themajority has poor electrical conductivity
Varies widely throughout the country and world Can changes dramatically within small areas
Soil resistivity is mainly influenced by:
The type of soil (clay, sand, rock, etc.) Moisture content and temperature
Amount of electrol tes (minerals and dissolved salt)
7/28/2019 Existing Grounding Systems Rob Schaerer
13/46
Soil Testing Resistivity Test Set
7/28/2019 Existing Grounding Systems Rob Schaerer
14/46
Wenner Resistivity Test Set-Up
Source
Black lines are current injectedRed lines are volta es measured
As the probes are spread out further, the deeper the measurements will go
7/28/2019 Existing Grounding Systems Rob Schaerer
15/46
Why Soil Data Is So Important
Example Full Data ubstation ize is 300 by 300
7/28/2019 Existing Grounding Systems Rob Schaerer
16/46
Why Soil Data Is So Important (cont.)
Soil model with all data:103
s)
Measured DataComputed Results CurveSoil Model
ty(O
hm-meter Measurement Met hod. . : Wenner
RMS er r or . . . . . . . . . . . : 10. 46%
Layer Resi st i vi t y Thi cknessNumber ( Ohm- m) ( Feet )====== ============== ==============
Ai r I nf i ni t e I nf i ni t e2 227. 3146 16. 94758
102
arentResistivi . .
4 515. 6556 i nf i ni t e
Ap
Grounding System Impedance is 1.07 ohms
10-1
100
101
102
103
Inter-Electrode Spacing (feet)
7/28/2019 Existing Grounding Systems Rob Schaerer
17/46
Why Soil Data Is So Important (cont.)
Soil model with only the first 50 of measurements:
103
s)
LEGEND
Measured DataComputed Results CurveSoil Model
ty(O
hm-mete Measur ement Met hod. . : Wenner
RMS er r or . . . . . . . . . . . : 8. 26%
Layer Resi st i vi t y Thi cknessNumber ( Ohm- m) ( Feet )
====== ============== ==============Ai r I nf i ni t e I nf i ni t e2 209. 4786 25. 52040
102
arentResistivi
3 15. 40446 i nf i ni t e
Ap
Grounding Impedance is 0.28 ohms (~1/4 of actual)
10-1 100 101 102
Inter-Electrode Spacing (feet)
10
7/28/2019 Existing Grounding Systems Rob Schaerer
18/46
Examining Previous Analysis - Conductor
Conductor size and ampacity
For a given fault duration and X/R ratio, grounding conductor
can only carry a given amount of fault current without fusing
#1/0 AWG)
Lar est concern is the e ui ment leads stin ers
One may carry full fault current
Once the current is in the main grid, the current splits in multiple
7/28/2019 Existing Grounding Systems Rob Schaerer
19/46
Examining Previous Analysis - Conductor
From IEEE Standard 80-2000
7/28/2019 Existing Grounding Systems Rob Schaerer
20/46
Examining Previous Analysis - Surfacing
Crushed rock surfacing
Adds additional impedance to current flowing through body
Increases allowable touch and step voltages
SLG Fault
7/28/2019 Existing Grounding Systems Rob Schaerer
21/46
Examining Previous Analysis - Surfacing
Crushed rock surfacing, cont.
Also provides clean surface for preventing vegetation, etc.
Washing the material of fines improves performance
Typically a crushed rock or gravel (3/4 2)
Thickness of 3-6 inches is typical Should extend beyond the substation fence and gate swings
Must be maintained over time to keep free of contamination,
7/28/2019 Existing Grounding Systems Rob Schaerer
22/46
Mitigation of Non Compliant Designs
Basic design approaches
Check fault current distribution Optimal selection of mitigation approaches
Horizontal ground conductors
Ground rods
Surfacing improvements
7/28/2019 Existing Grounding Systems Rob Schaerer
23/46
Grounding Design Basics
Grounding layout basics
Entire substation area should be encompassed
Minimize resistance of system (proportional to area of groundingsystem)
Layout should extend 3 feet beyond substation fence, includingoutward swing of gates
7/28/2019 Existing Grounding Systems Rob Schaerer
24/46
Grounding Design Basics (cont.)
Conductor Spacing/Layout
Typically laid out in a square grid covering station Typical spacings vary from 10 to 50
Depends on soil, fault current, station size
Large areas without equipment can be left uncovered if thereare no ste volta e issues
A denser grid towards outside of substation is more effective
Worst case touch voltages occur at the corners of the grid
7/28/2019 Existing Grounding Systems Rob Schaerer
25/46
Grounding Design Basics (cont.)
7/28/2019 Existing Grounding Systems Rob Schaerer
26/46
Fault Current Distribution (FCD)
Most conservative case is to assume all current
Not a practical representation in many cases
Faut current w ta e any pat ava a e
Transmission line shield wires
Distribution neutrals Other metallic paths tied to grounding system
These other paths are in parallel with the ground
In turn, lowers the substation GPR
Effects are most significant where poor soil exists at thesubstation (resulting in a high grounding systemimpedance)
7/28/2019 Existing Grounding Systems Rob Schaerer
27/46
Fault Current Distribution Example
Fault current returns through all
Both directly on shield wires andthrough tower grounds
TransmissionLineswithShieldWireFaultedSubstation
e urns o sourcesubstation(s)
SourceSubstation
7/28/2019 Existing Grounding Systems Rob Schaerer
28/46
Optimal Mitigation Selection
Ground rods vs. grid vs. ground wells
Primary goal is low impedance, therefore mitigation shouldtarget the lower resistivity soil
Horizontal ground grid
Works well when lower
layers are higher
Install most copper inupper, low resistivity,la e
Keeps surface closer toequipotential
Trenching around existingequipment difficult attimes
7/28/2019 Existing Grounding Systems Rob Schaerer
29/46
Existing Yard Installation
7/28/2019 Existing Grounding Systems Rob Schaerer
30/46
Optimal Mitigation Selection(cont.)
Ground rods vs. grid vs. ground wellscon .
Ground rods
os e ec ve w en op ayer s g erresistivity and fairly lower resistivity layers arebelow
Can be useful where water table is < 20 deep
Can also extend effective size of substationand pull touch voltages down
Typically should not be placed closer togetherthan length of rod as effectiveness decreases
Also can be difficult to install around existingequipment
7/28/2019 Existing Grounding Systems Rob Schaerer
31/46
Optimal Mitigation Selection(cont.)
Ground rods vs. grid vs. ground wells (cont.)
Ground wells
Most expensive option
Involves drilling a hole (typically 6) to a significant depth (can varyfrom 50-500+ feet)
May use a steel casing or be free standing (in stable/firm soils)
, ,
concrete/bentonite slurry)
Typically installed near the edges of the substation, away fromu
7/28/2019 Existing Grounding Systems Rob Schaerer
32/46
Optimal Mitigation Selection - Surfacing
Crushed rock can be added if not alread resent
Existing rock can be washed or thickness increased
Asphalt is occasionally used
Provides much better electrical performance
7/28/2019 Existing Grounding Systems Rob Schaerer
33/46
Testing
Fall-of-Potential (FOP)
Measured grounding system impedance
Touch and Ste Volta e Checks
Measured grounding system impedance
Point-to-Point Resistance Tests Check continuity of conductors
Validate data if in question
7/28/2019 Existing Grounding Systems Rob Schaerer
34/46
Testing - Grounding System Impedance
Fall-of-Potential (FOP)
Measures resistance of grounding system after installation Inject a current into grid and collect in remote current return probe
placed at 3-6.5x the system diagonal (6.5x preferred)
Voltage probe distance varied from 10% - 100% of current probe
distance
Resistance (V/I) of each point plotted versus distance
Curve flattens around 61.8% (demonstrating grounding system
resistance) with a 0 degree test Point varies based on soil structure (Standard 81-1983)
7/28/2019 Existing Grounding Systems Rob Schaerer
35/46
Fall-of-Potential Test Set-Up
Substation Grounding System Impedance
6
4
5
(OHMS
1
2
3
RESIST
ANC
0
0 500 1000 1500 2000 2500 3000 3500 4000
PROBE SPACING
7/28/2019 Existing Grounding Systems Rob Schaerer
36/46
Testing Touch and Step Voltages
Touch and step voltage check
Performed rarely, generally requires injection of significant testcurrent to provide reasonable voltage levels
Can be done in conjunction with FOP test
Inject a current similar to the FOP test
For touch voltages, measure voltage between any equipment ofconcern and a test probe placed just into the soil surface 3 feet fromthe equipment
For step voltages, measure the voltage between any two points inthe substation with probes placed just into the soil, separated bythree feet
7/28/2019 Existing Grounding Systems Rob Schaerer
37/46
Testing Connectivity
Point-to-point resistance check
Used to verify that all equipment is attached solidly to the maingrounding system
Select a reference point (often a piece of equipment with multiplegrounds) and measure resistance between all grounded objects
and the reference
Since resistance is primarily of the lead, value should be verylow (less than one ohm)
If resistance is very high, a second equipment connection can beadded to the main grid, or the existing can be replaced.
7/28/2019 Existing Grounding Systems Rob Schaerer
38/46
Maintenance of Existing Grounding
Maintenance of grounding systems after installation isoften overlooked
In 2005, a IEEE PES task force surveyed utilities
Key Findings/Recommendations
~80% evaluate the grounding systems after they are installed os o s examna on ony occurs a er a pro em appens, or
when expanding the substation
By proactively examining the grounding system (which very few do),many of these problems could be prevented in the first place
Recommends a review of the grounding system regularly Those who have a plan perform it every five to ten years, and more
often should there be concerns
n erva o es ng a ec e y age o e groun ng sys em ancharacteristics of the soil (for example very low resistivity soils
can be corrosive and degrade buried conductors over time)
7/28/2019 Existing Grounding Systems Rob Schaerer
39/46
Maintenance Plan
Typical plan involves:
Visual inspection of all above grade connections
Point-to-point resistance test
Fall-of-potential grounding system impedance test
Surface layer visual inspection Thickness and cleanliness (resistivity test if needed)
Reanalysis of design when significant system changes occur
7/28/2019 Existing Grounding Systems Rob Schaerer
40/46
Example Unique Substation
7/28/2019 Existing Grounding Systems Rob Schaerer
41/46
Example Unique Substation
7/28/2019 Existing Grounding Systems Rob Schaerer
42/46
Example Soil Resistivity Test
7/28/2019 Existing Grounding Systems Rob Schaerer
43/46
Example Point-to-Point Test
7/28/2019 Existing Grounding Systems Rob Schaerer
44/46
Example Point-to-Point Test
GROUND SYSTEM LAYOUT
39 49 56
34 36 40 42 44 45 51 53 57 59
33 47
50 30 2232 24 18 15
31 23
25 19 16
29 26 20 17
2813,R3
14 21
12
11
8,
R27 6
5 4 3 2,
R1
7/28/2019 Existing Grounding Systems Rob Schaerer
45/46
Conclusions
Substation grounding is critical for protection ofpersonnel and equipment
Some older substations were built with little analysisand/or data
Grounding can degrade over time
Systems (fault current) change over time
the grounding system continues to serve its purpose
Q i /C
7/28/2019 Existing Grounding Systems Rob Schaerer
46/46
Questions/Comments
Rob Schaerer, P.E. POWER Engineers, Inc. (858) 503-5975 ext. 2237 [email protected]