Existing Grounding Systems Rob Schaerer

Embed Size (px)

Citation preview

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    1/46

    April 7, 2011

    Substation Grounding Systems

    , . .

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    2/46

    Outline of Topics

    Why grounding is important

    What are we looking at

    Basic grounding system design process

    Considerations for existing substations

    Previous analysis

    Verification of previous study and data

    Mitigation

    Testin

    Maintenance Plans

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    3/46

    Personnel Protection

    IEEE 80-2000

    Provides guidance onlimits based onscenaros presen ein a substation

    environment and

    body when subjectedto an electric shock

    Additional concernsinclude equipment

    fault conditions)

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    4/46

    Personnel Protection Voltages

    Touch/ste volta es

    Touch voltage

    ground at your feet

    Typically limited to a reach distance of three feet (or one meter)

    Step voltage

    Voltage difference in ground between your feet as you are standing

    Typically limited to a stride of three feet (or one meter)

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    5/46

    Personnel Protection Voltages

    SLG Fault SLG Fault

    200Volts 100Volts

    Voltageat Foot

    Voltage1000 V

    Voltageat Foot

    Voltageat Foot

    Grid1000 V

    800 V

    Grid1000 V

    800 V900 V

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    6/46

    Behavior of Substation Under Fault Conditions

    Ground Potential Rise

    V = I * R

    Fault current into the grounding system times resistance toremo e ear

    Voltage magnitude determines grounding system performance

    rmar y use or personne comp ance

    Can also damage equipment

    Basis for determinin touch and ste volta es

    Fault Current Return Path

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    7/46

    Behavior of Substation Under Fault Conditions

    Ground Potential Rise (GPR) = I * R

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    8/46

    Process of Designing a Grounding System

    Gather and analyze soil data

    Obtain fault data Develop preliminary grounding system design

    Analyze design for touch and step voltage performance,

    plus impedance and GPR Perform mitigation until touch and step voltage

    compliance are met

    a ona equpmen spec c groun ng Test the installed grounding system to verify performance

    eexamne e groun ng sys em n e u ure

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    9/46

    Considerations for Existing Substations

    Was an analysis ever preformed?

    Many older substations were built on rules of thumb

    If not, most practical approach is to analyze before acting

    Is the previous analysis still valid?

    Has the system changed? Did the study use accurate data?

    Testing to validate performance

    Maintenance plans

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    10/46

    Examining Previous Analysis - Fault

    Fault currents

    Maximum single-line-to-ground fault

    Often increases with time as the system strengthens

    ,

    proportionally

    Clearing time (backup)

    Protection failure

    Consider worst case scenario (longest clearing delay time) anduse for grounding analysis

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    11/46

    Examining Previous Analysis - Soil

    Soil information has large impact on overall result, but is

    Soil data often collected by geotechnical or other firms that havelimited understanding of how data is used for grounding analysis

    Measurements are often insignificant (not enough data measured)

    Data collection process often produces errors that may not beexpected by experienced engineers or testers

    Examining the raw data can help validate the measurements

    Analysis of soil data measurements is both an art and a science Older techniques often involved a uniform soil approximation, or

    sometimes a two layer model that may be insufficient

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    12/46

    Soil Resistivity Tests

    Characterize soil by the electrical resistivity

    v y y u

    system for a specific performance objective All soil conducts electrical current

    Some soils have good electrical conductivity while themajority has poor electrical conductivity

    Varies widely throughout the country and world Can changes dramatically within small areas

    Soil resistivity is mainly influenced by:

    The type of soil (clay, sand, rock, etc.) Moisture content and temperature

    Amount of electrol tes (minerals and dissolved salt)

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    13/46

    Soil Testing Resistivity Test Set

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    14/46

    Wenner Resistivity Test Set-Up

    Source

    Black lines are current injectedRed lines are volta es measured

    As the probes are spread out further, the deeper the measurements will go

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    15/46

    Why Soil Data Is So Important

    Example Full Data ubstation ize is 300 by 300

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    16/46

    Why Soil Data Is So Important (cont.)

    Soil model with all data:103

    s)

    Measured DataComputed Results CurveSoil Model

    ty(O

    hm-meter Measurement Met hod. . : Wenner

    RMS er r or . . . . . . . . . . . : 10. 46%

    Layer Resi st i vi t y Thi cknessNumber ( Ohm- m) ( Feet )====== ============== ==============

    Ai r I nf i ni t e I nf i ni t e2 227. 3146 16. 94758

    102

    arentResistivi . .

    4 515. 6556 i nf i ni t e

    Ap

    Grounding System Impedance is 1.07 ohms

    10-1

    100

    101

    102

    103

    Inter-Electrode Spacing (feet)

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    17/46

    Why Soil Data Is So Important (cont.)

    Soil model with only the first 50 of measurements:

    103

    s)

    LEGEND

    Measured DataComputed Results CurveSoil Model

    ty(O

    hm-mete Measur ement Met hod. . : Wenner

    RMS er r or . . . . . . . . . . . : 8. 26%

    Layer Resi st i vi t y Thi cknessNumber ( Ohm- m) ( Feet )

    ====== ============== ==============Ai r I nf i ni t e I nf i ni t e2 209. 4786 25. 52040

    102

    arentResistivi

    3 15. 40446 i nf i ni t e

    Ap

    Grounding Impedance is 0.28 ohms (~1/4 of actual)

    10-1 100 101 102

    Inter-Electrode Spacing (feet)

    10

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    18/46

    Examining Previous Analysis - Conductor

    Conductor size and ampacity

    For a given fault duration and X/R ratio, grounding conductor

    can only carry a given amount of fault current without fusing

    #1/0 AWG)

    Lar est concern is the e ui ment leads stin ers

    One may carry full fault current

    Once the current is in the main grid, the current splits in multiple

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    19/46

    Examining Previous Analysis - Conductor

    From IEEE Standard 80-2000

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    20/46

    Examining Previous Analysis - Surfacing

    Crushed rock surfacing

    Adds additional impedance to current flowing through body

    Increases allowable touch and step voltages

    SLG Fault

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    21/46

    Examining Previous Analysis - Surfacing

    Crushed rock surfacing, cont.

    Also provides clean surface for preventing vegetation, etc.

    Washing the material of fines improves performance

    Typically a crushed rock or gravel (3/4 2)

    Thickness of 3-6 inches is typical Should extend beyond the substation fence and gate swings

    Must be maintained over time to keep free of contamination,

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    22/46

    Mitigation of Non Compliant Designs

    Basic design approaches

    Check fault current distribution Optimal selection of mitigation approaches

    Horizontal ground conductors

    Ground rods

    Surfacing improvements

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    23/46

    Grounding Design Basics

    Grounding layout basics

    Entire substation area should be encompassed

    Minimize resistance of system (proportional to area of groundingsystem)

    Layout should extend 3 feet beyond substation fence, includingoutward swing of gates

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    24/46

    Grounding Design Basics (cont.)

    Conductor Spacing/Layout

    Typically laid out in a square grid covering station Typical spacings vary from 10 to 50

    Depends on soil, fault current, station size

    Large areas without equipment can be left uncovered if thereare no ste volta e issues

    A denser grid towards outside of substation is more effective

    Worst case touch voltages occur at the corners of the grid

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    25/46

    Grounding Design Basics (cont.)

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    26/46

    Fault Current Distribution (FCD)

    Most conservative case is to assume all current

    Not a practical representation in many cases

    Faut current w ta e any pat ava a e

    Transmission line shield wires

    Distribution neutrals Other metallic paths tied to grounding system

    These other paths are in parallel with the ground

    In turn, lowers the substation GPR

    Effects are most significant where poor soil exists at thesubstation (resulting in a high grounding systemimpedance)

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    27/46

    Fault Current Distribution Example

    Fault current returns through all

    Both directly on shield wires andthrough tower grounds

    TransmissionLineswithShieldWireFaultedSubstation

    e urns o sourcesubstation(s)

    SourceSubstation

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    28/46

    Optimal Mitigation Selection

    Ground rods vs. grid vs. ground wells

    Primary goal is low impedance, therefore mitigation shouldtarget the lower resistivity soil

    Horizontal ground grid

    Works well when lower

    layers are higher

    Install most copper inupper, low resistivity,la e

    Keeps surface closer toequipotential

    Trenching around existingequipment difficult attimes

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    29/46

    Existing Yard Installation

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    30/46

    Optimal Mitigation Selection(cont.)

    Ground rods vs. grid vs. ground wellscon .

    Ground rods

    os e ec ve w en op ayer s g erresistivity and fairly lower resistivity layers arebelow

    Can be useful where water table is < 20 deep

    Can also extend effective size of substationand pull touch voltages down

    Typically should not be placed closer togetherthan length of rod as effectiveness decreases

    Also can be difficult to install around existingequipment

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    31/46

    Optimal Mitigation Selection(cont.)

    Ground rods vs. grid vs. ground wells (cont.)

    Ground wells

    Most expensive option

    Involves drilling a hole (typically 6) to a significant depth (can varyfrom 50-500+ feet)

    May use a steel casing or be free standing (in stable/firm soils)

    , ,

    concrete/bentonite slurry)

    Typically installed near the edges of the substation, away fromu

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    32/46

    Optimal Mitigation Selection - Surfacing

    Crushed rock can be added if not alread resent

    Existing rock can be washed or thickness increased

    Asphalt is occasionally used

    Provides much better electrical performance

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    33/46

    Testing

    Fall-of-Potential (FOP)

    Measured grounding system impedance

    Touch and Ste Volta e Checks

    Measured grounding system impedance

    Point-to-Point Resistance Tests Check continuity of conductors

    Validate data if in question

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    34/46

    Testing - Grounding System Impedance

    Fall-of-Potential (FOP)

    Measures resistance of grounding system after installation Inject a current into grid and collect in remote current return probe

    placed at 3-6.5x the system diagonal (6.5x preferred)

    Voltage probe distance varied from 10% - 100% of current probe

    distance

    Resistance (V/I) of each point plotted versus distance

    Curve flattens around 61.8% (demonstrating grounding system

    resistance) with a 0 degree test Point varies based on soil structure (Standard 81-1983)

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    35/46

    Fall-of-Potential Test Set-Up

    Substation Grounding System Impedance

    6

    4

    5

    (OHMS

    1

    2

    3

    RESIST

    ANC

    0

    0 500 1000 1500 2000 2500 3000 3500 4000

    PROBE SPACING

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    36/46

    Testing Touch and Step Voltages

    Touch and step voltage check

    Performed rarely, generally requires injection of significant testcurrent to provide reasonable voltage levels

    Can be done in conjunction with FOP test

    Inject a current similar to the FOP test

    For touch voltages, measure voltage between any equipment ofconcern and a test probe placed just into the soil surface 3 feet fromthe equipment

    For step voltages, measure the voltage between any two points inthe substation with probes placed just into the soil, separated bythree feet

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    37/46

    Testing Connectivity

    Point-to-point resistance check

    Used to verify that all equipment is attached solidly to the maingrounding system

    Select a reference point (often a piece of equipment with multiplegrounds) and measure resistance between all grounded objects

    and the reference

    Since resistance is primarily of the lead, value should be verylow (less than one ohm)

    If resistance is very high, a second equipment connection can beadded to the main grid, or the existing can be replaced.

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    38/46

    Maintenance of Existing Grounding

    Maintenance of grounding systems after installation isoften overlooked

    In 2005, a IEEE PES task force surveyed utilities

    Key Findings/Recommendations

    ~80% evaluate the grounding systems after they are installed os o s examna on ony occurs a er a pro em appens, or

    when expanding the substation

    By proactively examining the grounding system (which very few do),many of these problems could be prevented in the first place

    Recommends a review of the grounding system regularly Those who have a plan perform it every five to ten years, and more

    often should there be concerns

    n erva o es ng a ec e y age o e groun ng sys em ancharacteristics of the soil (for example very low resistivity soils

    can be corrosive and degrade buried conductors over time)

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    39/46

    Maintenance Plan

    Typical plan involves:

    Visual inspection of all above grade connections

    Point-to-point resistance test

    Fall-of-potential grounding system impedance test

    Surface layer visual inspection Thickness and cleanliness (resistivity test if needed)

    Reanalysis of design when significant system changes occur

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    40/46

    Example Unique Substation

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    41/46

    Example Unique Substation

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    42/46

    Example Soil Resistivity Test

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    43/46

    Example Point-to-Point Test

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    44/46

    Example Point-to-Point Test

    GROUND SYSTEM LAYOUT

    39 49 56

    34 36 40 42 44 45 51 53 57 59

    33 47

    50 30 2232 24 18 15

    31 23

    25 19 16

    29 26 20 17

    2813,R3

    14 21

    12

    11

    8,

    R27 6

    5 4 3 2,

    R1

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    45/46

    Conclusions

    Substation grounding is critical for protection ofpersonnel and equipment

    Some older substations were built with little analysisand/or data

    Grounding can degrade over time

    Systems (fault current) change over time

    the grounding system continues to serve its purpose

    Q i /C

  • 7/28/2019 Existing Grounding Systems Rob Schaerer

    46/46

    Questions/Comments

    Rob Schaerer, P.E. POWER Engineers, Inc. (858) 503-5975 ext. 2237 [email protected]