1. EXITS: (PER 2010 CBC SECTION 1007 & 1014.) THE REQUIRED ACCESS TO EXITS FROM ANY PORTION OF A BUILDING SHALL BE DIRECTLY FROM THE SPACE UNDER CONSIDERATION TO AN EXIT OR TO A CORRIDOR THAT PROVIDES DIRECT ACCESS TO AN EXIT. EXIT ACCESS SHALL NOT BE INTERRUPTED BY INTERVENING ROOMS: EXCEPTIONS: A. WHERE ACCESS TO ONLY ONE EXIT IS REQUIRED FROM A SPACE UNDER CONSIDERATION, EXIT ACCESS MAY OCCUR THROUGH AN ADJOINING OR INTERVENING ROOM, WHICH IN TURN PROVIDES DIRECT ACCESS TO AN EXIT OR TO A CORRIDOR THAT PROVIDES DIRECT ACCESS TO AN EXIT. B. ROOMS WITH A CUMULATIVE OCCUPANT LOAD OF LESS THAN 10 MAY ACCESS EXITS THROUGH MORE THAN ONE INTERVENING ROOM. C. WHERE ACCESS TO MORE THAN ONE EXIT IS REQUIRED FROM A SPACE UNDER CONSIDERATION, SUCH SPACES MAY ACCESS ONE REQUIRED EXIT THROUGH AN ADJOINING OR INTERVENING ROOM, WHICH IN TURN PROVIDES DIRECT ACCESS TO AN EXIT OR TO A CORRIDOR THAT PROVIDES DIRECT ACCESS TO AN EXIT. ALL OTHER REQUIRED ACCESS TO EXITS SHALL BE DIRECTLY FROM THE SPACE UNDER CONSIDERATION TO AN EXIT OR TO A CORRIDOR THAT PROVIDES DIRECT ACCESS TO AN EXIT. D. HALLWAYS SHALL BE CONSIDERED AS INTERVENING ROOMS E. IN OTHER THAN DWELLING UNITS, A MEANS OF EGRESS SHALL NOT PASS THROUGH EXITING GENERAL NOTES: 3. EXIT SIGNS: (PER 2010 CBC SECTION 1006 & 1007) A. EXIT SIGNS ARE REQUIRED WHENEVER TWO EXITS ARE REQUIRED. REFER TO PLAN. THE EXIT SIGNS SHALL BE PROVIDED AT THE TIME OF THE INTERIOR TENANT IMPROVEMENT. B. THE PATH OF EXIT TRAVEL TO & WITHIN EXITS SHALL BE IDENTIFIED BY EXIT SIGNS CONFORMING TO THE REQUIREMENTS OF SECTION 1006.3. EXIT SIGNS SHALL BE READILY VISIBLE FROM ANY DIRECTION OF APPROACH. EXIT SIGNS SHALL BE LOCATED AS NECESSARY TO CLEARLY INDICATE THE DIRECTION OF EGRESS TRAVEL. NO POINT SHALL BE MORE THAN 100 FT. FROM THE NEAREST VISIBLE SIGN. C. ALL EXIT SIGNS SHALL BE ILLUMINATED AT ALL TIMES. TO ENSURE CONTINUED ILLUMINATION FOR A DURATION OF NOT LESS THAN 1-1/2 HOURS IN CASE OF PRIMARY POWER LOSS, THE EXIT SIGNS SHALL ALSO BE CONNECTED TO AN EMERGENCY ELECTRICAL SYSTEM PROVIDED FROM STORAGE BATTERIES, UNIT EQUIPMENT OR AN ON-SITE GENERATOR SET AND THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE ELECTRICAL CODE. THESE TWO SOURCES OF POWER SHALL BE PROVIDED AT THE TIME OF THE TENANT IMPROVEMENT. D. ANY TIME A BUILDING IS OCCUPIED, THE MEANS OF EGRESS SHALL BE ILLUMINATED AT AN INTENSITY OF NOT LESS THAN 1 FOOTCANDLE AT THE FLOOR LEVEL. THIS ILLUMINATION SHALL BE PROVIDED AT THE TIME OF THE TENANT IMPROVEMENT. 2. DOORS: (PER 2010 CBC SECTION 1008) A. EXIT DOORS SERVING AN OCCUPANT LOAD OF 10 OR MORE SHALL BE OF THE PIVOTED, BALANCED OR SIDE-HINGED SWINGING TYPE. EXIT DOORS SHALL SWING IN THE DIRECTION OF THE PATH OF EXIT TRAVEL WHERE THE AREA SERVED HAS AN OCCUPANT LOAD OF 50 OR MORE. B. THE DOOR SHALL SWING TO THE FULLY OPEN POSITION WHEN AN OPENING FORCE NOT TO EXCEED 5 LBS. (FOR INTERIOR AND EXTERIOR DOORS) IS APPLIED AT RIGHT ANGLES TO HINGED DOORS AND AT THE CENTER PLANE OF SLIDING OR FOLDING DOORS. COMPENSATING DEVICES OR AUTOMATIC DOOR OPERATORS MAY BE UTILIZED TO MEET MAXIMUM EFFORT. C. THE BOTTOM 10" OF DOOR (EXCEPT AUTOMATIC OR SLIDING DOORS) HAVE A SMOOTH UNINTERRUPTED SURFACE THAT ALLOWS DOORS TO BE OPENED BY A WHEELCHAIR FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION. D. LOCK/LATCH TYPE: EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF A KEY OR ANY SPECIAL KNOWLEDGE OR EFFORT. EXCEPTIONS: IN GROUPS A,B AND M OCCUPANCIES, KEY-LOCKING HARDWARE MAY BE USED ON THE MAIN EXIT WHERE THE MAIN EXIT CONSISTS OF A SINGLE DOOR OR PAIR OF DOORS WHERE THERE IS A READILY VISIBLE, DURABLE SIGN ON OR ADJACENT TO THE DOOR STATING, 'THIS DOOR MUST REMAIN UNLOCKED DURING BUSINESS HOURS'. THE SIGN SHALL BE IN LETTERS NOT LESS THAN 1" HIGH ON A CONTRASTING BACKGROUND. WHEN UNLOCKED, THE SINGLE DOOR OR BOTH LEAVES OF A PAIR OF DOORS MUST BE FREE TO SWING WITHOUT OPERATION OF ANY LATCHING DEVICE. E. MANUALLY OPERATED EDGE- OR SURFACE MOUNTED FLUSH BOLTS AND SURFACE BOLTS OR ANY OTHER TYPE OF DEVICE THAT MAY BE USED TO CLOSE OR RESTAIN THE DOOR OTHER THAN BY OPERATION OF THE LOCKING DEVICE, SHALL NOT BE USED. WHERE EXIT DOORS ARE USED IN PAIRS AND APPROVED AUTOMATIC FLUSH BOLTS ARE USED, THE DOOR LEAF HAVING THE AUTOMATIC FLUSH BOLTS SHALL HAVE NO DOORKNOB OR SURFACE-MOUNTED HARDWARE. THE UNLATCHING OF ANY LEAF SHALL NOT REQUIRE MORE THAN ONE OPERATION. F. PANIC HARDWARE, WHERE INSTALLED, SHALL COMPLY WITH THE REQUIREMENTS OF U.B.C. STANDARD 10-4. THE ACTIVATING MEMBER SHALL BE MOUNTED AT A HEIGHT OF NOT LESS THAN 30" NOR MORE THAN 44" ABOVE THE FLOOR. THE UNLATCHING FORCE SHALL NOT EXCEED 15 LBS WHEN APPLIED IN THE DIRECTION OF TRAVEL. WHERE PIVOTED OR BALANCED DOORS ARE USED AND PANIC HARDWARE IS REQUIRED, PANIC HARDWARE SHALL BE OF THE PUSH-PAD TYPE AND THE PAD SHALL NOT EXTEND ACROSS MORE THAN ONE HALF OF THE WIDTH OF THE DOOR MEASURED FROM THE LATCH SIDE. DOOR CLOSERS, IF PRESENT, MUST BE SET SO THAT IT TAKES AT LEAST 3 SECONDS TO CLOSE FROM AN OPEN POSITION OF 70 DEGREES TO WITHIN 3" OF THE LATCH. 1. PROVIDE A SIGN ON OR NEAR THE MAIN EXIT DOOR, READING "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" 2. ALL EXITS ARE TO BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF A KEY OR SPECIAL KNOLEDGE DOOR NOTES NOTE: THIS PROJECT IS FOR THE SPECIFIED IMPROVEMENTS TO DEVELOP A "SHELL ONLY" FOR A FUTURE TENANT IMPROVEMENT. THIS IS NOT FOR AN APPLIED USE OR FINAL OCCUPANCY. 1 MIXED USE CALCULATION (PER CBC SEC. 506.5.2) A-2 ACTUAL AREA + M ACTUAL AREA = <1.00 A-2 ALLOWABLE AREA M ALLOWABLE AREA 0..25 + 0..41 = 0.66 < 1.00 [OKAY] EXIT EXIT PROPERTY LINE UP ELEC. UP (E) ADA ACCESIBLE RAMP: UP FIRST FLOOR VANILLA SHELL (E) RETAIL (NO WORK) EXISTING FIRST FLOOR SHELL (NO WORK) EXISTING NORTH DECK (NO WORK) FUTURE DECK UP UP A B C D D E E F F G G H H I I J J K K L L M M 1 2 3 4 A 2 3 4 1 PROPERTY LINE NOTE: USE CAUTION WITH WALL COVERINGS OF ADJACENT RETAIL SPACE. THERE IS (E) 5/8" DRYWALL TYPE 'X' GYPSUM. PREVIOUSLY INSTALLED WHICH CREATES A PORTION OF THE 1-HR. WALL ASSEMBLY. PROPOSED A-2 OCCUPANCY DINING 4,524 S.F. ACCESSIBLE PATH OF TRAVEL: 161'- 1 1/2" OCCUPANT LOAD: 1 PER 15= #302 OCC. SIGN EXIT EXIT EXIT FIRST FLOOR OCCUPANCY ALLOWABLE AREA ALLOWABLE AREA INCREASE ACTUAL AREA RATIO A-2 6,000 18,000 4,524 S.F. 0.25 S.F. M 9,000 27,000 11,121 S.F. 0.41 S.F. PROPOSED A-2 OCCUPANCY PROPOSED A-2 OCCUPANCY PROPOSED A-2 OCCUPANCY PROPOSED A-2 OCCUPANCY KITCHEN & PREP AREA PREP AREA STORAGE STORAGE PROPOSED A-2 OCCUPANCY EXISTING M OCCUPANCY NOTES: A MOCK FLOOR PLAN HAS BEEN PREPARED ASSUMING POTENTIAL PROJECT VARIABLES AND CRITICAL CODE REQUIREMENTS. PROJECT VARIABLES INCLUDE LIKELY USES WITHIN THE BUILDING SUCH AS DINING, STORAGE INCIDENTAL OFFICE AREA, RESTROOMS AND CIRCULATION AREAS AND A COMMUNITY CONFERENCE ROOM. CRITICAL CODE REQUIREMENTS ARE: OCCUPANCY CLASSIFICATIONS OCCUPANT LOAD FACTORS EXIT ACCESS TRAVEL DISTANCE COMMON PATH OF EGRESS TRAVEL EXIT WIDTH 3 ALLOWABLE BUILDING AREA CALCULATION (PER CBC SEC. 508.3.2) BASED ON THE MOST RESTRICTIVE ALLOWANCES FOR THE OCCUPANCY CROUPS UNDER CONSIDERATION FOR THE TYPE OF CONSTRUCTION OF THE BUILDING. A a = A t +[A t x I s ] A a = ALLOWABLE AREA A t = ALLOWABLE AREA PER TABLE 503 I s = AREA INCREASE FACTOR DUE TO SPRINKLER PROTECTION PER CBC 506.3 ( I s =2) EXIT EXIT 1. MAXIMUM OCCUPANCY SIGNAGE TO READ: "MAXIMUM OCCUPANCY = # "PERSONS" REFER TO T-1.0 FOR CALCULATION. 2. ALL SIGNAGE IS WALL MOUNTED @/NEAR THE ENTRY/EXIT, WITH A MINIMUM OF 1" HIGH CONTRASTING LETTERS. 3. ALL SIGNAGE IS TO BE IN PLACE PRIOR TO USE/OCCUPANCY OF THE SPECIFIC SPACE, ROOM, OR AREA DESIGNATED. OCCUPANCY SIGNAGE NOTES: EMERGENCY LIGHTING. REFER TO SHEETS ELECTRICAL, BY OTHERS. LIGHTING TO BE MOUNTED @ UPPER 18" OF WALL AND DIRECTED TOWARDS THE EXITS & EXITWAYS WHEN ENERGIZED. : : : ILLUMINATED EXIT SIGNS. REFER TO ELECTRICAL FOR WIRING AND LIGHT FIXTURE SCHEDULE FOR TYPE AND SIZE. TACTILE EXIT SIGNS. LOCATE ADJACENT TO EXIT DOORS, PER PLAN, @ +60" A.F.F. SIGNS ARE TO BE CONTRACTED GRADE 2 BRAILLE "EXIT" SIGNS. EACH GRADE LEVEL EXTERIOR DOOR SHALL BE IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORD "EXIT". MAXIMUM OCCUPANCY SIGN. REFER TO OCCUPANCY SIGNAGE NOTES, THIS SHEET. EXIT ROUTE T : EACH EXIT ACCESS DOOR FROM AN INTERIOR ROOM TO A CORRIDOR, HALLWAY OR ADJACENT ROOM THAT EXITS, SHALL BE IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORDS "EXIT ROUTE". (SEE NOTE ABOVE FOR LOCATION). OR EXIT EXIT ILLUMINATED EXIT SIGN W/ EMERGENCY LIGHTING. REFER TO ELECTRICAL, BY OTHERS. LIGHTING TO BE MOUNTED @ UPPER 18" OF WALL AND DIRECTED TOWARDS THE EXITS & EXITWAYS WHEN ENERGIZED. : DIRECTIONAL ILLUMINATED EXIT SIGNS. REFER TO ELECTRICAL FOR WIRING AND LIGHT FIXTURE SCHEDULE FOR TYPE AND SIZE. : F.E. : 44" WIDE AISLE. ALSO COMPLIES WITH LIFE SAFETY CODES REQUIRING 44" WIDE EGRESS AISLES. (CBC 2010 1133B.6.2) LIFE SAFETY / ACCESSIBILITY LEGEND: 36" WIDE AISLE REQUIRED. EMPLOYEE ONLY AREAS MUST BE DESIGNED TO PROVIDE ACCESS INTO, THROUGH AND OUT OF AREA (CBC 2010 1104B.5.5) EMERGENCY/ EXIT NOTES & SYMBOLS: NOTE: ALL EMERGENCY LIGHTING & ILLUMINATED EXIT SIGNAGE SHALL BE INSTALLED W/ STANDBY POWER BATTERY PACK & TEST OPTION FOR EGRESS LIGHTING. CONNECT TO EGRESS LIGHT CIRCUIT. THE MEANS OF EGRESS ILLUMINATION LEVEL SHALL NOT BE LESS THAN 1 FT.-CANDLE (11 LUX) AT THE WALKING SURFACE). THE EMERGENCY POWER SYSTEM SHALL PROVIDE POWER FOR A DURATION OF NOT LESS THAN 90 MINUTES AND SHALL CONSIST OF STORAGE BATTERIES, UNIT EQUIPMENT, OR AN ON-SITE GENERATOR. THE INSTALLATION OF THE EMERGENCY POWER SYSTEM SHALL BE IN ACCORDANCE WITH 2010 C.B.C., CHAPTER 27. OCC. SIGN EXIT : EXIT T EXIT ROUTE T EXIST ACCESS TRAVEL DISTANCE WITH SPRINKLER SYSTEM FOR OCCUPANCY A-2 AND OCCUPANCY M IS 250' MAXIMUM. PER CBC TABLE 1016.1 EXIT ACCESS TRAVEL DISTANCE: © 2013 - CRSA BOARDWALK PLAZA 175 POMEROY STREET PISMO BEACH,CA 93451 These drawings are instruments of service and are the property of Craig R. Smith Architect. All designs and other information on the drawings are for use on the specified project and shall not be used otherwise without the expressed written permission of Craig R. Smith Architect. 011064 MP PISMO INVESTMENTS, LLC C/O: THOMAS J WATTS, SR. P.O.BOX 580426 HOUSTON TX, 77258-0426 13 11 30 MASTER IMPROVEMENT PLAN 28 JAN 2013 BUILDING SUBMITTAL 26 MAR 2013 BUILDING RE-SUBMITTAL 1 03 JUNE 2013 BUILDING 2 ND RE-SUBMITTAL 2 19 JUNE 2013 BUILDING 3 RD RE-SUBMITTAL SCALE: 1/8" = 1'-0" MASTER IMPROVEMENT PLAN - FIRST FLOOR MOCK EXHIBIT

EXCEPTIONS: THE MEANS OF EGRESS ILLUMINATION … space remodel phase 3/PISMO... · a= allowable area a t = allowable area per table 503 i s = area increase factor due to sprinkler

  • Upload
    lamngoc

  • View
    216

  • Download
    0

Embed Size (px)

Citation preview

1. EXITS: (PER 2010 CBC SECTION 1007 & 1014.) THE REQUIRED ACCESS TO EXITS FROM ANY PORTION OF A BUILDING SHALL BE DIRECTLY FROM THE SPACE UNDER CONSIDERATION TO AN EXIT OR TO A CORRIDOR THAT PROVIDES DIRECT ACCESS TO AN EXIT. EXIT ACCESS SHALL NOT BE INTERRUPTED BY INTERVENING ROOMS:

EXCEPTIONS:A. WHERE ACCESS TO ONLY ONE EXIT IS REQUIRED FROM A SPACE UNDER CONSIDERATION,

EXIT ACCESS MAY OCCUR THROUGH AN ADJOINING OR INTERVENING ROOM, WHICH IN TURN PROVIDES DIRECT ACCESS TO AN EXIT OR TO A CORRIDOR THAT PROVIDES DIRECT ACCESS TO AN EXIT.

B. ROOMS WITH A CUMULATIVE OCCUPANT LOAD OF LESS THAN 10 MAY ACCESS EXITS THROUGH MORE THAN ONE INTERVENING ROOM.

C. WHERE ACCESS TO MORE THAN ONE EXIT IS REQUIRED FROM A SPACE UNDER CONSIDERATION, SUCH SPACES MAY ACCESS ONE REQUIRED EXIT THROUGH AN ADJOINING OR INTERVENING ROOM, WHICH IN TURN PROVIDES DIRECT ACCESS TO AN EXIT OR TO A CORRIDOR THAT PROVIDES DIRECT ACCESS TO AN EXIT. ALL OTHER REQUIRED ACCESS TO EXITS SHALL BE DIRECTLY FROM THE SPACE UNDER CONSIDERATION TO AN EXIT OR TO A CORRIDOR THAT PROVIDES DIRECT ACCESS TO AN EXIT.

D. HALLWAYS SHALL BE CONSIDERED AS INTERVENING ROOMSE. IN OTHER THAN DWELLING UNITS, A MEANS OF EGRESS SHALL NOT PASS THROUGH

KITCHENS, STOREROOMS, RESTROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES

EXITING GENERAL NOTES:

3. EXIT SIGNS: (PER 2010 CBC SECTION 1006 & 1007)A. EXIT SIGNS ARE REQUIRED WHENEVER TWO EXITS ARE REQUIRED. REFER TO PLAN. THE

EXIT SIGNS SHALL BE PROVIDED AT THE TIME OF THE INTERIOR TENANT IMPROVEMENT.B. THE PATH OF EXIT TRAVEL TO & WITHIN EXITS SHALL BE IDENTIFIED BY EXIT SIGNS

CONFORMING TO THE REQUIREMENTS OF SECTION 1006.3. EXIT SIGNS SHALL BE READILY VISIBLE FROM ANY DIRECTION OF APPROACH. EXIT SIGNS SHALL BE LOCATED AS NECESSARY TO CLEARLY INDICATE THE DIRECTION OF EGRESS TRAVEL. NO POINT SHALL BE MORE THAN 100 FT. FROM THE NEAREST VISIBLE SIGN.

C. ALL EXIT SIGNS SHALL BE ILLUMINATED AT ALL TIMES. TO ENSURE CONTINUED ILLUMINATION FOR A DURATION OF NOT LESS THAN 1-1/2 HOURS IN CASE OF PRIMARY POWER LOSS, THE EXIT SIGNS SHALL ALSO BE CONNECTED TO AN EMERGENCY ELECTRICAL SYSTEM PROVIDED FROM STORAGE BATTERIES, UNIT EQUIPMENT OR AN ON-SITE GENERATOR SET AND THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE ELECTRICAL CODE. THESE TWO SOURCES OF POWER SHALL BE PROVIDED AT THE TIME OF THE TENANT IMPROVEMENT.

D. ANY TIME A BUILDING IS OCCUPIED, THE MEANS OF EGRESS SHALL BE ILLUMINATED AT AN INTENSITY OF NOT LESS THAN 1 FOOTCANDLE AT THE FLOOR LEVEL. THIS ILLUMINATION SHALL BE PROVIDED AT THE TIME OF THE TENANT IMPROVEMENT.

2. DOORS: (PER 2010 CBC SECTION 1008)A. EXIT DOORS SERVING AN OCCUPANT LOAD OF 10 OR MORE SHALL BE OF THE PIVOTED,

BALANCED OR SIDE-HINGED SWINGING TYPE. EXIT DOORS SHALL SWING IN THE DIRECTION OF THE PATH OF EXIT TRAVEL WHERE THE AREA SERVED HAS AN OCCUPANT LOAD OF 50 OR MORE.

B. THE DOOR SHALL SWING TO THE FULLY OPEN POSITION WHEN AN OPENING FORCE NOT TO EXCEED 5 LBS. (FOR INTERIOR AND EXTERIOR DOORS) IS APPLIED AT RIGHT ANGLES TO HINGED DOORS AND AT THE CENTER PLANE OF SLIDING OR FOLDING DOORS. COMPENSATING DEVICES OR AUTOMATIC DOOR OPERATORS MAY BE UTILIZED TO MEET MAXIMUM EFFORT.

C. THE BOTTOM 10" OF DOOR (EXCEPT AUTOMATIC OR SLIDING DOORS) HAVE A SMOOTH UNINTERRUPTED SURFACE THAT ALLOWS DOORS TO BE OPENED BY A WHEELCHAIR FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION.

D. LOCK/LATCH TYPE: EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF A KEY OR ANY SPECIAL KNOWLEDGE OR EFFORT.

EXCEPTIONS:IN GROUPS A,B AND M OCCUPANCIES, KEY-LOCKING HARDWARE MAY BE USED ON THE MAIN

EXIT WHERE THE MAIN EXIT CONSISTS OF A SINGLE DOOR OR PAIR OF DOORS WHERE THERE IS A READILY VISIBLE, DURABLE SIGN ON OR ADJACENT TO THE DOOR STATING, 'THIS DOOR MUST REMAIN UNLOCKED DURING BUSINESS HOURS'. THE SIGN SHALL BE IN LETTERS NOT LESS THAN 1" HIGH ON A CONTRASTING BACKGROUND. WHEN UNLOCKED, THE SINGLE DOOR OR BOTH LEAVES OF A PAIR OF DOORS MUST BE FREE TO SWING WITHOUT OPERATION OF ANY LATCHING DEVICE.

E. MANUALLY OPERATED EDGE- OR SURFACE MOUNTED FLUSH BOLTS AND SURFACE BOLTS OR ANY OTHER TYPE OF DEVICE THAT MAY BE USED TO CLOSE OR RESTAIN THE DOOR OTHER THAN BY OPERATION OF THE LOCKING DEVICE, SHALL NOT BE USED. WHERE EXIT DOORS ARE USED IN PAIRS AND APPROVED AUTOMATIC FLUSH BOLTS ARE USED, THE DOOR LEAF HAVING THE AUTOMATIC FLUSH BOLTS SHALL HAVE NO DOORKNOB OR SURFACE-MOUNTED HARDWARE. THE UNLATCHING OF ANY LEAF SHALL NOT REQUIRE MORE THAN ONE OPERATION.

F. PANIC HARDWARE, WHERE INSTALLED, SHALL COMPLY WITH THE REQUIREMENTS OF U.B.C. STANDARD 10-4. THE ACTIVATING MEMBER SHALL BE MOUNTED AT A HEIGHT OF NOT LESS THAN 30" NOR MORE THAN 44" ABOVE THE FLOOR. THE UNLATCHING FORCE SHALL NOT EXCEED 15 LBS WHEN APPLIED IN THE DIRECTION OF TRAVEL.

WHERE PIVOTED OR BALANCED DOORS ARE USED AND PANIC HARDWARE IS REQUIRED, PANIC HARDWARE SHALL BE OF THE PUSH-PAD TYPE AND THE PAD SHALL NOT EXTEND ACROSS MORE THAN ONE HALF OF THE WIDTH OF THE DOOR MEASURED FROM THE LATCH SIDE.

DOOR CLOSERS, IF PRESENT, MUST BE SET SO THAT IT TAKES AT LEAST 3 SECONDS TO CLOSE FROM AN OPEN POSITION OF 70 DEGREES TO WITHIN 3" OF THE LATCH.

1. PROVIDE A SIGN ON OR NEAR THE MAIN EXIT DOOR, READING "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED"

2. ALL EXITS ARE TO BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF A KEY OR SPECIAL KNOLEDGE

DOOR NOTES

NOTE: THIS PROJECT IS FOR THE SPECIFIED IMPROVEMENTS TO DEVELOP A "SHELL ONLY" FOR A FUTURE TENANT IMPROVEMENT. THIS IS NOT FOR AN APPLIED USE OR FINAL OCCUPANCY.

1

MIXED USE CALCULATION (PER CBC SEC. 506.5.2) A-2 ACTUAL AREA + M ACTUAL AREA = <1.00A-2 ALLOWABLE AREA M ALLOWABLE AREA

0..25 + 0..41 = 0.66 < 1.00 [OKAY]

EXIT

EXIT

PROPERTY LINE

UP

ELEC.

UP

(E) A

DA A

CCES

IBLE

RAM

P: U

P(E

) ADA

ACC

ESIB

LE R

AMP:

UP

(E) A

DA A

CCES

IBLE

RAM

P: U

P(E

) ADA

ACC

ESIB

LE R

AMP:

UP

1

FIRST FLOORVANILLA SHELL

(E)RETAIL

(NO WORK)

EXISTINGFIRST FLOOR

SHELL(NO WORK)

EXISTINGNORTHDECK

(NO WORK)

FUTUREDECK

UP

UP

A

B

B

C

C

D

D

E

E

F

F

G

G

H

H

I

I

J

J

K

K

L

L

M

M

1

2

3

4

A

2

3

4

1

PROPERTY LINE

NOTE: USE CAUTION WITH WALL COVERINGS OF ADJACENT RETAIL SPACE. THERE IS (E) 5/8" DRYWALL TYPE 'X' GYPSUM. PREVIOUSLY INSTALLED WHICH CREATES A PORTION OF THE 1-HR. WALL ASSEMBLY.

PROPOSED A-2OCCUPANCY

DINING4,524 S.F.

ACCESSIBLE PATHOF TRAVEL: 161'- 1 1/2"

OCCUPANT LOAD: 1 PER 15= #302

OC

C. S

IGN

EXIT

EXIT

EXIT

FIRST FLOOROCCUPANCY ALLOWABLE AREA ALLOWABLE AREA

INCREASE ACTUAL AREA RATIO

A-2 6,000 18,000 4,524 S.F. 0.25 S.F. M 9,000 27,000 11,121 S.F. 0.41 S.F.

PROPOSED A-2OCCUPANCY

PROPOSED A-2OCCUPANCY PROPOSED A-2

OCCUPANCY

PROPOSED A-2OCCUPANCY

KITCHEN & PREPAREA

PREP AREASTORAGE

STORAGE

PROPOSED A-2OCCUPANCY

EXISTING MOCCUPANCY

NOTES:A MOCK FLOOR PLAN HAS BEEN PREPARED ASSUMING POTENTIAL PROJECT VARIABLES AND CRITICAL CODE REQUIREMENTS. PROJECT VARIABLES INCLUDE LIKELY USES WITHIN THE BUILDING SUCH AS DINING, STORAGE INCIDENTAL OFFICE AREA, RESTROOMS AND CIRCULATION AREAS AND A COMMUNITY CONFERENCE ROOM.

CRITICAL CODE REQUIREMENTS ARE:OCCUPANCY CLASSIFICATIONSOCCUPANT LOAD FACTORSEXIT ACCESS TRAVEL DISTANCECOMMON PATH OF EGRESS TRAVEL EXIT WIDTH

3ALLOWABLE BUILDING AREA CALCULATION (PER CBC SEC. 508.3.2)BASED ON THE MOST RESTRICTIVE ALLOWANCES FOR THE OCCUPANCY CROUPS UNDER CONSIDERATION FOR THE TYPE OF CONSTRUCTION OF THE BUILDING.

Aa= At +[At x Is]

Aa= ALLOWABLE AREAAt = ALLOWABLE AREA PER TABLE 503Is = AREA INCREASE FACTOR DUE TO SPRINKLER PROTECTION PER CBC 506.3 ( Is =2)

EXIT

EXIT

1. MAXIMUM OCCUPANCY SIGNAGE TO READ: "MAXIMUM OCCUPANCY = # "PERSONS" REFER TO T-1.0 FOR CALCULATION.2. ALL SIGNAGE IS WALL MOUNTED @/NEAR THE ENTRY/EXIT, WITH A MINIMUM OF 1" HIGH CONTRASTING LETTERS.3. ALL SIGNAGE IS TO BE IN PLACE PRIOR TO USE/OCCUPANCY OF THE SPECIFIC SPACE, ROOM, OR AREA DESIGNATED.

OCCUPANCY SIGNAGE NOTES:EMERGENCY LIGHTING. REFER TO SHEETS ELECTRICAL, BY OTHERS. LIGHTING TO BE MOUNTED @ UPPER 18" OF WALL AND DIRECTED TOWARDS THE EXITS & EXITWAYS WHEN ENERGIZED.

:

:

: ILLUMINATED EXIT SIGNS. REFER TO ELECTRICAL FOR WIRING AND LIGHT FIXTURE SCHEDULE FOR TYPE AND SIZE.

TACTILE EXIT SIGNS. LOCATE ADJACENT TO EXIT DOORS, PER PLAN, @ +60" A.F.F. SIGNS ARE TO BE CONTRACTED GRADE 2 BRAILLE "EXIT" SIGNS. EACH GRADE LEVEL EXTERIOR DOOR SHALL BE IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORD "EXIT".

MAXIMUM OCCUPANCY SIGN. REFER TO OCCUPANCY SIGNAGE NOTES, THIS SHEET.

EXITROUTE

T

:

EACH EXIT ACCESS DOOR FROM AN INTERIOR ROOM TO A CORRIDOR, HALLWAY OR ADJACENT ROOM THAT EXITS, SHALL BE IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORDS "EXIT ROUTE". (SEE NOTE ABOVE FOR LOCATION).

OR

EXIT

EXIT

ILLUMINATED EXIT SIGN W/ EMERGENCY LIGHTING. REFER TO ELECTRICAL, BY OTHERS. LIGHTING TO BE MOUNTED @ UPPER 18" OF WALL AND DIRECTED TOWARDS THE EXITS & EXITWAYS WHEN ENERGIZED.

:

DIRECTIONAL ILLUMINATED EXIT SIGNS. REFER TO ELECTRICAL FOR WIRING AND LIGHT FIXTURE SCHEDULE FOR TYPE AND SIZE.

:

F.E. :

44" WIDE AISLE. ALSO COMPLIES WITH LIFE SAFETY CODES REQUIRING 44" WIDE EGRESS AISLES. (CBC 2010 1133B.6.2)

LIFE SAFETY / ACCESSIBILITY LEGEND:

36" WIDE AISLE REQUIRED. EMPLOYEE ONLY AREAS MUST BE DESIGNED TO PROVIDE ACCESS INTO, THROUGH AND OUT OF AREA (CBC 2010 1104B.5.5)

EMERGENCY/ EXIT NOTES & SYMBOLS:NOTE: ALL EMERGENCY LIGHTING & ILLUMINATED EXIT SIGNAGE SHALL BE INSTALLED W/ STANDBY POWER BATTERY PACK & TEST OPTION FOR EGRESS LIGHTING. CONNECT TO EGRESS LIGHT CIRCUIT.

THE MEANS OF EGRESS ILLUMINATION LEVEL SHALL NOT BE LESS THAN 1 FT.-CANDLE (11 LUX) AT THE WALKING SURFACE).

THE EMERGENCY POWER SYSTEM SHALL PROVIDE POWER FOR A DURATION OF NOT LESS THAN 90 MINUTES AND SHALL CONSIST OF STORAGE BATTERIES, UNIT EQUIPMENT, OR AN ON-SITE GENERATOR. THE INSTALLATION OF THE EMERGENCY POWER SYSTEM SHALL BE IN ACCORDANCE WITH 2010 C.B.C., CHAPTER 27.

OCC. SIGN

EXIT

:

EXITT

EXITROUTE

T

EXIST ACCESS TRAVEL DISTANCE WITH SPRINKLER SYSTEM FOR OCCUPANCY A-2 AND OCCUPANCY M IS 250' MAXIMUM. PER CBC TABLE 1016.1

EXIT ACCESS TRAVEL DISTANCE:

© 2013 - CRSA

BOAR

DWAL

K PL

AZA

175

POM

ERO

Y ST

REET

PISM

O B

EACH

,CA

9345

1

Thes

e dr

awin

gs a

re in

stru

men

tsof

ser

vice

and

are

the

prop

erty

of C

raig

R. S

mith

Arc

hite

ct.

All

desig

ns a

nd o

ther

info

rmat

ion

on th

e dr

awin

gs a

re fo

r use

on

the

spec

ified

proj

ect a

nd s

hall

not b

e us

ed o

ther

wise

with

out

the

expr

esse

d wr

itten

perm

issio

n of

Cra

ig R

. Sm

ithAr

chite

ct.

011064

A-1.0

MP

PISM

O IN

VEST

MEN

TS, L

LCC/

O: T

HOM

AS J

WAT

TS, S

R.P.

O.B

OX

5804

26HO

USTO

N TX

, 772

58-0

426

1311 30

MAS

TER

IMPR

OVE

MEN

TPL

AN

28 JAN 2013BUILDING SUBMITTAL

26 MAR 2013BUILDING RE-SUBMITTAL

A-1.0

1

03 JUNE 2013BUILDING 2ND RE-SUBMITTAL2

19 JUNE 2013BUILDING 3RD RE-SUBMITTAL

SCALE: 1/8" = 1'-0"

MASTER IMPROVEMENT PLAN - FIRST FLOOR MOCK EXHIBIT

EXIT ACCESS TRAVEL DISTANCE:

DN3'-8"

DN

DN

23 R @ 6"22 T @ 11.25"

A

05

06

A

A

A

160'-0" - V.I.F.7'-3" - V.I.F. 13'-9" - V.I.F. 13'-9" - V.I.F. 13'-9" - V.I.F. 13'-9" - V.I.F. 13'-9" - V.I.F. 13'-9" - V.I.F. 13'-9" - V.I.F. 15'-2" - V.I.F.13'-9" - V.I.F. 13'-9" - V.I.F. 13'-9" - V.I.F.

160'-0" - V.I.F.7'-3" - V.I.F. 13'-9" - V.I.F. 13'-9" - V.I.F. 13'-9" - V.I.F. 13'-9" - V.I.F. 13'-9" - V.I.F. 13'-9" - V.I.F. 13'-9" - V.I.F. 13'-9" - V.I.F. 13'-9" - V.I.F. 13'-9" - V.I.F. 15'-2" - V.I.F.

103'

-0" -

V.I.

F.41

'-6" -

V.I.

F.11

'-11"

- V.

I.F.

49'-7

" - V

.I.F.

103'

-0" -

V.I.

F.

41'-6

" - V

.I.F.

11'-1

1" -

V.I.F

.49

'-7" -

V.I.

F.

6'-6"

6'-3

"8'

-11"

A

A

B

B

C

C

D

D

E

E

F

F

G

G

H

H

I

I

J

J

K

K

L

L

M

M

1 1

2 2

3 3

44

EXISTINGSTAIRS EXISTING

STAIRS

EXISTINGDECK

NOTE: USE CAUTION WITH WALL COVERINGS OF ADJACENT RETAIL SPACE. THERE IS (E) 5/8" DRYWALL TYPE 'X' GYPSUM. PREVIOUSLY INSTALLED WHICH CREATES A PORTION OF THE 1-HR. WALL ASSEMBLY.

(E) ELEV.

OUTLINE OF PROPOSEDNEW DECK EXPANSION

PROPOSED A-2OCCUPANCY

PROPOSEDA-2 OCCUPANCY

1,060 S.F.

PROPOSED A-2OCCUPANCY

OCCUPANT LOAD:1 PER 7 = #151

1,060 S.F.OCCUPANT LOAD 1 PER 100 = #11

JANITORCLOSET

(E) 1 HR WALL(E) 1-HR WALL

3,471 S.F.

PROPOSEDA-2 OCCUPANCY

OCCUPANT LOAD:1 PER 15= #231 BELOW

NOTES:A MOCK FLOOR PLAN HAS BEEN PREPARED ASSUMING POTENTIAL PROJECT VARIABLES AND CRITICAL CODE REQUIREMENTS. PROJECT VARIABLES INCLUDE LIKELY USES WITHIN THE BUILDING SUCH AS DINING, STORAGE INCIDENTAL OFFICE AREA, RESTROOMS AND CIRCULATION AREAS AND A COMMUNITY CONFERENCE ROOM.

CRITICAL CODE REQUIREMENTS ARE:OCCUPANCY CLASSIFICATIONSOCCUPANT LOAD FACTORSEXIT ACCESS TRAVEL DISTANCECOMMON PATH OF EGRESS TRAVEL EXIT WIDTH

SECOND FLOOROCCUPANCY ALLOWABLE AREA ALLOWABLE AREA

W/ INCREASE ACTUAL RATIO

A-2 6,000 18,000 5,717 S.F. 0.32

3

EXIT

EXIT

ELECT.ROOM

5'-0"

EXIT ACCESS TRAVELDISTANCE: 95'-9"

MIXED USE CALCULATION (PER CBC SEC. 506.5.2) A-2 ACTUAL AREA = <1.00A-2 ALLOWABLE AREA

0.32 < 1.00 [OKAY]

ALLOWABLE BUILDING AREA CALCULATION (PER CBC SEC. 508.3.2)BASED ON THE MOST RESTRICTIVE ALLOWANCES FOR THE OCCUPANCY CROUPS UNDER CONSIDERATION FOR THE TYPE OF CONSTRUCTION OF THE BUILDING.

Aa= At +[At x Is]

Aa= ALLOWABLE AREAAt = ALLOWABLE AREA PER TABLE 503Is = AREA INCREASE FACTOR DUE TO SPRINKLER PROTECTION PER CBC 506.3 ( Is =2)

EXITEXITEXIT EXIT

EXIT

EXIT

EXIT

EXIT ACCESS TRAVELDISTANCE: 56'-11"

EXIT ACCESS TRAVELDISTANCE: 120'-8"

EXIT ACCESS TRAVELDISTANCE: 76'-10"

EXIT ACCESS TRAVELDISTANCE: 125'-2"

EXITEXIT

1. EXITS: (PER 2010 CBC SECTION 1007 & 1014.) THE REQUIRED ACCESS TO EXITS FROM ANY PORTION OF A BUILDING SHALL BE DIRECTLY FROM THE SPACE UNDER CONSIDERATION TO AN EXIT OR TO A CORRIDOR THAT PROVIDES DIRECT ACCESS TO AN EXIT. EXIT ACCESS SHALL NOT BE INTERRUPTED BY INTERVENING ROOMS:

EXCEPTIONS:A. WHERE ACCESS TO ONLY ONE EXIT IS REQUIRED FROM A SPACE UNDER CONSIDERATION,

EXIT ACCESS MAY OCCUR THROUGH AN ADJOINING OR INTERVENING ROOM, WHICH IN TURN PROVIDES DIRECT ACCESS TO AN EXIT OR TO A CORRIDOR THAT PROVIDES DIRECT ACCESS TO AN EXIT.

B. ROOMS WITH A CUMULATIVE OCCUPANT LOAD OF LESS THAN 10 MAY ACCESS EXITS THROUGH MORE THAN ONE INTERVENING ROOM.

C. WHERE ACCESS TO MORE THAN ONE EXIT IS REQUIRED FROM A SPACE UNDER CONSIDERATION, SUCH SPACES MAY ACCESS ONE REQUIRED EXIT THROUGH AN ADJOINING OR INTERVENING ROOM, WHICH IN TURN PROVIDES DIRECT ACCESS TO AN EXIT OR TO A CORRIDOR THAT PROVIDES DIRECT ACCESS TO AN EXIT. ALL OTHER REQUIRED ACCESS TO EXITS SHALL BE DIRECTLY FROM THE SPACE UNDER CONSIDERATION TO AN EXIT OR TO A CORRIDOR THAT PROVIDES DIRECT ACCESS TO AN EXIT.

D. HALLWAYS SHALL BE CONSIDERED AS INTERVENING ROOMSE. IN OTHER THAN DWELLING UNITS, A MEANS OF EGRESS SHALL NOT PASS THROUGH

KITCHENS, STOREROOMS, RESTROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES

EXITING GENERAL NOTES:

3. EXIT SIGNS: (PER 2010 CBC SECTION 1006 & 1007)A. EXIT SIGNS ARE REQUIRED WHENEVER TWO EXITS ARE REQUIRED. REFER TO PLAN. THE

EXIT SIGNS SHALL BE PROVIDED AT THE TIME OF THE INTERIOR TENANT IMPROVEMENT.B. THE PATH OF EXIT TRAVEL TO & WITHIN EXITS SHALL BE IDENTIFIED BY EXIT SIGNS

CONFORMING TO THE REQUIREMENTS OF SECTION 1006.3. EXIT SIGNS SHALL BE READILY VISIBLE FROM ANY DIRECTION OF APPROACH. EXIT SIGNS SHALL BE LOCATED AS NECESSARY TO CLEARLY INDICATE THE DIRECTION OF EGRESS TRAVEL. NO POINT SHALL BE MORE THAN 100 FT. FROM THE NEAREST VISIBLE SIGN.

C. ALL EXIT SIGNS SHALL BE ILLUMINATED AT ALL TIMES. TO ENSURE CONTINUED ILLUMINATION FOR A DURATION OF NOT LESS THAN 1-1/2 HOURS IN CASE OF PRIMARY POWER LOSS, THE EXIT SIGNS SHALL ALSO BE CONNECTED TO AN EMERGENCY ELECTRICAL SYSTEM PROVIDED FROM STORAGE BATTERIES, UNIT EQUIPMENT OR AN ON-SITE GENERATOR SET AND THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE ELECTRICAL CODE. THESE TWO SOURCES OF POWER SHALL BE PROVIDED AT THE TIME OF THE TENANT IMPROVEMENT.

D. ANY TIME A BUILDING IS OCCUPIED, THE MEANS OF EGRESS SHALL BE ILLUMINATED AT AN INTENSITY OF NOT LESS THAN 1 FOOTCANDLE AT THE FLOOR LEVEL. THIS ILLUMINATION SHALL BE PROVIDED AT THE TIME OF THE TENANT IMPROVEMENT.

2. DOORS: (PER 2010 CBC SECTION 1008)A. EXIT DOORS SERVING AN OCCUPANT LOAD OF 10 OR MORE SHALL BE OF THE PIVOTED,

BALANCED OR SIDE-HINGED SWINGING TYPE. EXIT DOORS SHALL SWING IN THE DIRECTION OF THE PATH OF EXIT TRAVEL WHERE THE AREA SERVED HAS AN OCCUPANT LOAD OF 50 OR MORE.

B. THE DOOR SHALL SWING TO THE FULLY OPEN POSITION WHEN AN OPENING FORCE NOT TO EXCEED 5 LBS. (FOR INTERIOR AND EXTERIOR DOORS) IS APPLIED AT RIGHT ANGLES TO HINGED DOORS AND AT THE CENTER PLANE OF SLIDING OR FOLDING DOORS. COMPENSATING DEVICES OR AUTOMATIC DOOR OPERATORS MAY BE UTILIZED TO MEET MAXIMUM EFFORT.

C. THE BOTTOM 10" OF DOOR (EXCEPT AUTOMATIC OR SLIDING DOORS) HAVE A SMOOTH UNINTERRUPTED SURFACE THAT ALLOWS DOORS TO BE OPENED BY A WHEELCHAIR FOOTREST WITHOUT CREATING A TRAP OR HAZARDOUS CONDITION.

D. LOCK/LATCH TYPE: EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF A KEY OR ANY SPECIAL KNOWLEDGE OR EFFORT.

EXCEPTIONS:IN GROUPS A,B AND M OCCUPANCIES, KEY-LOCKING HARDWARE MAY BE USED ON THE MAIN

EXIT WHERE THE MAIN EXIT CONSISTS OF A SINGLE DOOR OR PAIR OF DOORS WHERE THERE IS A READILY VISIBLE, DURABLE SIGN ON OR ADJACENT TO THE DOOR STATING, 'THIS DOOR MUST REMAIN UNLOCKED DURING BUSINESS HOURS'. THE SIGN SHALL BE IN LETTERS NOT LESS THAN 1" HIGH ON A CONTRASTING BACKGROUND. WHEN UNLOCKED, THE SINGLE DOOR OR BOTH LEAVES OF A PAIR OF DOORS MUST BE FREE TO SWING WITHOUT OPERATION OF ANY LATCHING DEVICE.

E. MANUALLY OPERATED EDGE- OR SURFACE MOUNTED FLUSH BOLTS AND SURFACE BOLTS OR ANY OTHER TYPE OF DEVICE THAT MAY BE USED TO CLOSE OR RESTAIN THE DOOR OTHER THAN BY OPERATION OF THE LOCKING DEVICE, SHALL NOT BE USED. WHERE EXIT DOORS ARE USED IN PAIRS AND APPROVED AUTOMATIC FLUSH BOLTS ARE USED, THE DOOR LEAF HAVING THE AUTOMATIC FLUSH BOLTS SHALL HAVE NO DOORKNOB OR SURFACE-MOUNTED HARDWARE. THE UNLATCHING OF ANY LEAF SHALL NOT REQUIRE MORE THAN ONE OPERATION.

F. PANIC HARDWARE, WHERE INSTALLED, SHALL COMPLY WITH THE REQUIREMENTS OF U.B.C. STANDARD 10-4. THE ACTIVATING MEMBER SHALL BE MOUNTED AT A HEIGHT OF NOT LESS THAN 30" NOR MORE THAN 44" ABOVE THE FLOOR. THE UNLATCHING FORCE SHALL NOT EXCEED 15 LBS WHEN APPLIED IN THE DIRECTION OF TRAVEL.

WHERE PIVOTED OR BALANCED DOORS ARE USED AND PANIC HARDWARE IS REQUIRED, PANIC HARDWARE SHALL BE OF THE PUSH-PAD TYPE AND THE PAD SHALL NOT EXTEND ACROSS MORE THAN ONE HALF OF THE WIDTH OF THE DOOR MEASURED FROM THE LATCH SIDE.

DOOR CLOSERS, IF PRESENT, MUST BE SET SO THAT IT TAKES AT LEAST 3 SECONDS TO CLOSE FROM AN OPEN POSITION OF 70 DEGREES TO WITHIN 3" OF THE LATCH.

1. PROVIDE A SIGN ON OR NEAR THE MAIN EXIT DOOR, READING "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED"

2. ALL EXITS ARE TO BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF A KEY OR SPECIAL KNOLEDGE

DOOR NOTES

NOTE: THIS PROJECT IS FOR THE SPECIFIED IMPROVEMENTS TO DEVELOP A "SHELL ONLY" FOR A FUTURE TENANT IMPROVEMENT. THIS IS NOT FOR AN APPLIED USE OR FINAL OCCUPANCY.

1

1. MAXIMUM OCCUPANCY SIGNAGE TO READ: "MAXIMUM OCCUPANCY = # "PERSONS" REFER TO T-1.0 FOR CALCULATION.2. ALL SIGNAGE IS WALL MOUNTED @/NEAR THE ENTRY/EXIT, WITH A MINIMUM OF 1" HIGH CONTRASTING LETTERS.3. ALL SIGNAGE IS TO BE IN PLACE PRIOR TO USE/OCCUPANCY OF THE SPECIFIC SPACE, ROOM, OR AREA DESIGNATED.

OCCUPANCY SIGNAGE NOTES:EMERGENCY LIGHTING. REFER TO SHEETS ELECTRICAL, BY OTHERS. LIGHTING TO BE MOUNTED @ UPPER 18" OF WALL AND DIRECTED TOWARDS THE EXITS & EXITWAYS WHEN ENERGIZED.

:

:

: ILLUMINATED EXIT SIGNS. REFER TO ELECTRICAL FOR WIRING AND LIGHT FIXTURE SCHEDULE FOR TYPE AND SIZE.

TACTILE EXIT SIGNS. LOCATE ADJACENT TO EXIT DOORS, PER PLAN, @ +60" A.F.F. SIGNS ARE TO BE CONTRACTED GRADE 2 BRAILLE "EXIT" SIGNS. EACH GRADE LEVEL EXTERIOR DOOR SHALL BE IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORD "EXIT".

MAXIMUM OCCUPANCY SIGN. REFER TO OCCUPANCY SIGNAGE NOTES, THIS SHEET.

EXITROUTE

T

:

EACH EXIT ACCESS DOOR FROM AN INTERIOR ROOM TO A CORRIDOR, HALLWAY OR ADJACENT ROOM THAT EXITS, SHALL BE IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORDS "EXIT ROUTE". (SEE NOTE ABOVE FOR LOCATION).

OR

EXIT

EXIT

ILLUMINATED EXIT SIGN W/ EMERGENCY LIGHTING. REFER TO ELECTRICAL, BY OTHERS. LIGHTING TO BE MOUNTED @ UPPER 18" OF WALL AND DIRECTED TOWARDS THE EXITS & EXITWAYS WHEN ENERGIZED.

:

DIRECTIONAL ILLUMINATED EXIT SIGNS. REFER TO ELECTRICAL FOR WIRING AND LIGHT FIXTURE SCHEDULE FOR TYPE AND SIZE.

:

F.E. :

44" WIDE AISLE. ALSO COMPLIES WITH LIFE SAFETY CODES REQUIRING 44" WIDE EGRESS AISLES. (CBC 2010 1133B.6.2)

LIFE SAFETY / ACCESSIBILITY LEGEND:

36" WIDE AISLE REQUIRED. EMPLOYEE ONLY AREAS MUST BE DESIGNED TO PROVIDE ACCESS INTO, THROUGH AND OUT OF AREA (CBC 2010 1104B.5.5)

EMERGENCY/ EXIT NOTES & SYMBOLS:NOTE: ALL EMERGENCY LIGHTING & ILLUMINATED EXIT SIGNAGE SHALL BE INSTALLED W/ STANDBY POWER BATTERY PACK & TEST OPTION FOR EGRESS LIGHTING. CONNECT TO EGRESS LIGHT CIRCUIT.

THE MEANS OF EGRESS ILLUMINATION LEVEL SHALL NOT BE LESS THAN 1 FT.-CANDLE (11 LUX) AT THE WALKING SURFACE).

THE EMERGENCY POWER SYSTEM SHALL PROVIDE POWER FOR A DURATION OF NOT LESS THAN 90 MINUTES AND SHALL CONSIST OF STORAGE BATTERIES, UNIT EQUIPMENT, OR AN ON-SITE GENERATOR. THE INSTALLATION OF THE EMERGENCY POWER SYSTEM SHALL BE IN ACCORDANCE WITH 2010 C.B.C., CHAPTER 27.

OCC. SIGN

EXIT

:

EXITT

EXIST ACCESS TRAVEL DISTANCE WITH SPRINKLER SYSTEM FOR OCCUPANCY A-2 IS 250' MAXIMUM. PER CBC TABLE 1016.1

© 2013 - CRSA

BOAR

DWAL

K PL

AZA

175

POM

ERO

Y ST

REET

PISM

O B

EACH

,CA

9345

1

Thes

e dr

awin

gs a

re in

stru

men

tsof

ser

vice

and

are

the

prop

erty

of C

raig

R. S

mith

Arc

hite

ct.

All

desig

ns a

nd o

ther

info

rmat

ion

on th

e dr

awin

gs a

re fo

r use

on

the

spec

ified

proj

ect a

nd s

hall

not b

e us

ed o

ther

wise

with

out

the

expr

esse

d wr

itten

perm

issio

n of

Cra

ig R

. Sm

ithAr

chite

ct.

011064

MP

PISM

O IN

VEST

MEN

TS, L

LCC/

O: T

HOM

AS J

WAT

TS, S

R.P.

O.B

OX

5804

26HO

USTO

N TX

, 772

58-0

426

1311 30

28 JAN 2013BUILDING SUBMITTAL

26 MAR 2013BUILDING RE-SUBMITTAL

1

03 JUNE 2013BUILDING 2ND RE-SUBMITTAL2

19 JUNE 2013BUILDING 3RD RE-SUBMITTAL

SCALE: 1/8" = 1'-0"

MASTER IMPROVEMENT PLAN- SECOND FLOOR

DIM

ENSI

ONA

L PL

AN-

SECO

ND F

LOO

R

A-1.1

-

MOCK EXHIBIT

3