EVALUATION OF AK ALEV MANYEZIT LEVHA ÜRETIM SAN. VE TIC. A.Ş. “MODELPAN” MAGNESIUM-OXIDE BASED SHEATHING PANELS IN
ACCORDANCE WITH ICC-ES AC378, SECTION 4.1, REFERENC ING ASTM E72, SECTION 12 TRANSVERSE LOADS – SPECIMEN VERTICAL
Report to: Ak Alev Manyezit Levha Üretim San. ve Tic. A. Ş.
No: 1A Kay: 2 Ataşehir İstanbul, Turkiye
Attention : Bertan Ozcan CC: Sibel Hizlan Telephone: +90 (216) 469 56 77 Email: [email protected] CC: [email protected] Proposal No.: 16-006-401691, Revision 6 Report No.: 16-06-P0117-S, Revision 1 9 pages Date: December 22, 2016
Evaluation of “Modelpan” Sheathing Material Page 1 of 9 for Ak Alev Manyezit Levha Üretim San. ve Tic. A.Ş. Report No. 16-06-P0117-S, Revision 1 1.0 INTRODUCTION
At the request of Ak Alev Manyezit Levha Üretim San. ve Tic. A.Ş., Exova was retained to conduct a transverse performance evaluation of a Magnesium-Oxide Based sheathing panel identified as the “Modelpan” in accordance with ICC-ES AC378, Section 4.1, referencing ASTM E72, Section 12, Transverse load – Specimen Vertical Upon receipt and construction, the samples were assigned the following Exova Sample Number: Client Sample Description Exova Sample No.: “Modelpan” 16-06-P0117-S1 to S6 Note: Installation details as provided by the client and reviewed and used by Exova for the above sample
construction are located in Appendix A. Sample selection information is located in Appendix B. Wall Specimen Description 4’ x 8ʹ (1219 mm x 2438 mm) Opaque Wall comprising of one full sheathing without joints. Frame Construction: 18 ga. channel-shaped galvanized steel studs measured 3-5/8″
(92 mm) deep with 1-21/64″ (33.7 mm) long returns / Installed 16” (406 mm) O/C
Frame Fasteners: #8 x 1/2″ (4.1 x 12.7 mm) long modified truss-head self-drilling screws Frame Perimeter (Buck): SPF 2” x 8” (38 mm x 165 mm) Sheathing: Modelpan Sheathing Panel (Magnesium-Oxide based) Joint Sealant: None Sheathing Fasteners: #6 x1” (3.9 x 25 mm) self-tapping fasteners, spaced 7.87” (200 mm)
along panel edges, spaced 7.87” (200 mm) along intermediate studs.
Figure No. 1 – Specimen General Arrangement
Evaluation of “Modelpan” Sheathing Material Page 2 of 9 for Ak Alev Manyezit Levha Üretim San. ve Tic. A.Ş. Report No. 16-06-P0117-S, Revision 1
2.0 PROCEDURE
Testing was conducted in accordance with ICC-ES AC378, section 4.1, referencing ASTM E72, Section 12 – Transverse Loading – Specimen Vertical.
Test Method Test Description
ICC ES AC 378 Section 4.1, Referencing ASTM E72, Section 12 Transverse Loading
Transverse Loading – ICC-ES AC378, section 4.1, ref erencing ASTM E72, Section 12
Six (6) wall assemblies was constructed for three (3) positive and three (3) negative loadings in accordance with ICC-ES AC378, Section 4, Referencing ASTM E72 to a specified deflection limit of L/360 (6.77 mm / 0.266 inches of net deflection). Prior to testing, the wall assembly was instrumented with three (3) deflection gauges to quantify the assembly movement in relation to induced pressure. The locations of the various deflection gauges used are shown below in Figure 2:
Upon completion of imposing design load to L/360 deflection, the specimens were loaded to failure and the allowable loading shall be based on a safety factor of 3, based on the average L/360 test load.
Figure No. 2 – Deflection Gauge Locations (Interior View)
Evaluation of “Modelpan” Sheathing Material Page 3 of 9 for Ak Alev Manyezit Levha Üretim San. ve Tic. A.Ş. Report No. 16-06-P0117-S, Revision 1
3.0 RESULTS
Table 1 - Summarized Transverse Load Results ICC-ES AC378, Section 4.1, Referencing
ASTM E72, Section 12 Exova Specimen No.: 16-06-P0117-S1 (Test Date: 2016-06-30)
Test Pressure and Direction Pa (psf)
Cycle No. & Max Gauge Deflection - mm (inches)
Deflection allowable based on L/360 = 6.77 mm (0.267 inches)
1 2 3
-1500 (-31.32) 0.46 (0.02) 6.01 (0.24) 0.32 (0.01)
Net Deflection 5.6 (0.22)
Comment : No visual evidence of cracking of the sheathing panel and fastening location was observed.
Net Deflection vs. Time graph is shown below in Figure 4.
Figure No. 4 – Transverse Load Net Deflection vs Time
Table 2 - Summarized Transverse Load Results ICC-ES AC378, Section 4.1, Referencing ASTM E72, Section 12 – Load to Failure
Exova Specimen No.: 16-06-P0117-S1 (Test Date: 2016-06-30)
Ultimate Load Pa (psf) Observation
-4680 (-97.74) Sheathing panel fracture around fastener location
Evaluation of “Modelpan” Sheathing Material Page 4 of 9 for Ak Alev Manyezit Levha Üretim San. ve Tic. A.Ş. Report No. 16-06-P0117-S, Revision 1
Table 3 - Summarized Transverse Load Results ICC-ES AC378, Section 4.1, Referencing
ASTM E72, Section 12 Exova Specimen No.: 16-06-P0117-S2 (Test Date: 2016-06-30)
Test Pressure and Direction Pa (psf)
Cycle No. & Max Gauge Deflection - mm (inches)
Deflection allowable based on L/360 = 6.77 mm (0.267 inches)
1 2 3
-1500 (-31.32) 0.89 (0.04) 5.81 (0.23) 0.19 (0.01)
Net Deflection 5.27 (0.21)
Comment : No visual evidence of cracking of the sheathing panel and fastening location was observed.
Net Deflection vs. Time graph is shown below in Figure 5.
Figure No. 5– Transverse Load Net Deflection vs Time
Table 4 - Summarized Transverse Load Results ICC-ES AC378, Section 4.1, Referencing ASTM E72, Section 12 – Load to Failure
Exova Specimen No.: 16-06-P0117-S2 (Test Date: 2016-06-30)
Ultimate Load Pa (psf) Observation
-5102 (106.56) Sheathing panel fracture around fastener location
Evaluation of “Modelpan” Sheathing Material Page 5 of 9 for Ak Alev Manyezit Levha Üretim San. ve Tic. A.Ş. Report No. 16-06-P0117-S, Revision 1
Table 5 - Summarized Transverse Load Results ICC-ES AC378, Section 4.1, Referencing
ASTM E72, Section 12 Exova Specimen No.: 16-06-P0117-S3 (Test Date: 2016-06-30)
Test Pressure and Direction Pa (psf)
Cycle No. & Max Gauge Deflection - mm (inches)
Deflection allowable based on L/360 = 6.77 mm (0.267 inches)
1 2 3
-1500 (-31.32) 0.10 (0.00) 5.23 (0.21) 0.29 (0.01)
Net Deflection 5.03 (0.20)
Comment : No visual evidence of cracking of the sheathing panel and fastening location was observed.
Net Deflection vs. Time graph is shown below in Figure 6.
Figure No. 6– Transverse Load Net Deflection vs Time
Table 6 - Summarized Transverse Load Results ICC-ES AC378, Section 4.1, Referencing ASTM E72, Section 12 – Load to Failure
Exova Specimen No.: 16-06-P0117-S3 (Test Date: 2016-06-30)
Ultimate Load Pa (psf) Observation
-5030 (105.05) Sheathing panel fracture around fastener location
Evaluation of “Modelpan” Sheathing Material Page 6 of 9 for Ak Alev Manyezit Levha Üretim San. ve Tic. A.Ş. Report No. 16-06-P0117-S, Revision 1
Table 7 - Summarized Transverse Load Results ICC-ES AC378, Section 4.1, Referencing
ASTM E72, Section 12 Exova Specimen No.: 16-06-P0117-S4 (Test Date: 2016-08-08)
Test Pressure and Direction Pa (psf)
Cycle No. & Max Gauge Deflection - mm (inches)
Deflection allowable based on L/360 = 6.77 mm (0.267 inches)
1 2 3
+2500 (52.21) -1.19 (-0.05) -6.41 (-0.25) -0.56 (-0.02)
Net Deflection -5.54 (-0.22)
Comment : No visual evidence of cracking of the sheathing panel and fastening location was observed.
Net Deflection vs. Time graph is shown below in Figure 7.
Figure No. 7– Transverse Load Net Deflection vs Time
Table 8 - Summarized Transverse Load Results ICC-ES AC378, Section 4.1, Referencing ASTM E72, Section 12 – Load to Failure
Exova Specimen No.: 16-06-P0117-S4 (Test Date: 2016-08-08)
Ultimate Load Pa (psf) Observation
+8435 (176.17) Metal studs buckled and pulled off wooden buck.
Evaluation of “Modelpan” Sheathing Material Page 7 of 9 for Ak Alev Manyezit Levha Üretim San. ve Tic. A.Ş. Report No. 16-06-P0117-S, Revision 1
Table 9 - Summarized Transverse Load Results ICC-ES AC378, Section 4.1, Referencing
ASTM E72, Section 12 Exova Specimen No.: 16-06-P0117-S5 (Test Date: 2016-06-30)
Test Pressure and Direction Pa (psf)
Cycle No. & Max Gauge Deflection - mm (inches)
Deflection allowable based on L/360 = 6.77 mm (0.267 inches)
1 2 3
+2500 (52.21) -0.26 (-0.01) -6.48 (-0.26) -0.48 (-0.02)
Net Deflection -6.11 (-0.24)
Comment : No visual evidence of cracking of the sheathing panel and fastening location was observed.
Net Deflection vs. Time graph is shown below in Figure 8.
Figure No. 8– Transverse Load Net Deflection vs Time
Table 10 - Summarized Transverse Load Results ICC-ES AC378, Section 4.1, Referencing ASTM E72, Section 12 – Load to Failure
Exova Specimen No.: 16-06-P0117-S5 (Test Date: 2016-06-30)
Ultimate Load (Pa) Observation
+8961 (187.15) Metal studs buckled and pulled off wooden buck.
Evaluation of “Modelpan” Sheathing Material Page 8 of 9 for Ak Alev Manyezit Levha Üretim San. ve Tic. A.Ş. Report No. 16-06-P0117-S, Revision 1
Table 11 - Summarized Transverse Load Results ICC-ES AC378, Section 4.1, Referencing
ASTM E72, Section 12 Exova Specimen No.: 16-06-P0117-S6 (Test Date: 2016-07-01)
Test Pressure and Direction Pa (psf)
Cycle No. & Max Gauge Deflection - mm (inches)
Deflection allowable based on L/360 = 6.77 mm (0.267 inches)
1 2 3
+2500 (52.21) -0.93 (-0.04) -7.39 (-0.29) -0.86 (-0.03)
Net Deflection -6.50 (-0.26)
Comment : No visual evidence of cracking of the sheathing panel and fastening location was observed.
Net Deflection vs. Time graph is shown below in Figure 9.
Figure No. 9– Transverse Load Net Deflection vs Time
Table 12 - Summarized Transverse Load Results ICC-ES AC378, Section 4.1, Referencing ASTM E72, Section 12 – Load to Failure
Exova Specimen No.: 16-06-P0117-S6 (Test Date: 2016-07-01)
Ultimate Load Pa (psf) Observation
+9042 (188.85) Metal studs buckled and pulled off wooden buck.
Evaluation of “Modelpan” Sheathing Material Page 9 of 9 for Ak Alev Manyezit Levha Üretim San. ve Tic. A.Ş. Report No. 16-06-P0117-S, Revision 1
4.0 CONCLUSION
The sheathing panel identified as “Modelpan” was tested in accordance with ICC-ES AC378, section 4.1, referencing ASTM E72, Section 12 – Transverse Loading – Specimen Vertical. The pressure tested to obtain L/360 deflection, ultimate test pressure, and ultimate test pressure deviation can be obtained below:
Table 13 - Summarized Transverse Load Results ICC-ES AC378, Section 4.1, Referencing
ASTM E72, Section 12 Exova Sample No.: 16-06-P0117-S
Specimen # Pressure
Direction
Pressure
Pa (psf) at
L/360 Deflection
Ultimate Test Pressure
Pa (psf)
Average
Pa (psf)
Ultimate Test
Pressure Deviation
16-06-P0117-S1 Infiltration 1500 (31.33) 4680 (97.74) 4937
(103.12)
-5.37%
16-06-P0117-S2 Infiltration 1500 (31.33) 5102 (106.56) 0.97%
16-06-P0117-S3 Infiltration 1500 (31.33) 5030 (105.05) 0.98%
16-06-P0117-S4 Exfiltration 2500 (52.21) 8435 (176.17) 8812
(184.06)
-1.04%
16-06-P0117-S5 Exfiltration 2500 (52.21) 8961 (187.15) 0.98%
16-06-P0117-S6 Exfiltration 2500 (52.21) 9042 (188.85) 0.97%
5.0 REPORT REVISION HISTORY Date: Revision: Comments: 2016-09-04 Original Document N/A 2016-12-22 1 Correction made to Client’s company name and