Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
International Journal of Mechanical & Mechatronics Engineering IJMME-IJENS Vol:19 No:06 49
190106-7575-IJMME-IJENS © December 2019 IJENS I J E N S
Evaluation of Air Exchange Efficiency in Rooms
with Personal Ventilation in Conjunction with
Displacement Ventilation Systems Asmaa Khudhair Yakoob, Ala'a Abbas Mahdi, Qusay Rasheed Al-Amir
Abstract— This paper aims to evaluating a new
ventilation concept: displacement ventilation (DV) aided with
personalized ventilation (PV) which is assessed for improving
indoor air quality. This approach could be improved
ventilation system design that could even provide individual
control of indoor microclimate. The airflow motion and
temperature distribution by adopting DV and PDV(personal-
displacement ventilation) systems investigated experimentally
and numerically with best flow rate from personal ventilation
and best situations of occupant distribution for DV and PDV.
This work includes a discussion of ventilation strategies, air
and temperature distribution including personal-displacement
ventilation (PDV) system in office room under Iraqi climate to
predict Indoor Air Quality (IQA) and thermal human comfort
by using computational fluid dynamics (CFD) modeling and
rigorous validation experiments. The experimental study was
performed to investigate how the use of the two different
arrangement would effect on thermal environment inside a
tested room of dimensions (3×1.75×3) m used as an office
room. The results of the experimental study were used to
validate the CFD simulations. The boundary conditions for
Computational Fluid Dynamics (CFD) study were obtained
from the same set-up measurement for one way direction-
rectangular displacement and personal ventilation system.
RNG, k-ε turbulence models are evaluated to show how the
shape and location of ventilation devices and occupant would
affect the air quality and thermal environment in the room.
The supply air device has been chosen according to the data
provided by manufactures depending on supply airflow rate in
order to avoid drafts. For DV supply temperature of 18◦C
(64.4◦F) and PV air supply temperature range of 18◦C to 22◦C
(64.4◦F to 71.6◦F), it was found that PV at flow rate 10 L/s
(21.19 cfm) in addition to the distribution of occupants could
improved the inhaled air quality in the breathing zone. And
that the arrangements at an office room for the air supply
diffuser DV and PV combined give accepted thermal human
comfortable depending on the magnitude of air distribution
performance index (ADPI) and effectiveness temperature(ɛt)
which are improved about 71% and about 1.8 respectively
Index Term— Displacement and personal ventilation,
CFD simulation, thermal comfort, Air Distribution
Performance Index, effectiveness temperature, Indoor air quality.
Asmaa Khudhair Yakoob
University of Babylon, Faculty of Engineering, Mechanical Engineering department,
Iraq,
[email protected] 1Ala'a Abbas Mahdi, 2Qusay Rasheed Al-Amir
University of Babylon, Faculty of Engineering, Mechanical Engineering department,
Iraq, [email protected], [email protected]
I. INTRODUCTION The purpose of a ventilation system is to provide
acceptable microclimate in the space being ventilated.
Microclimate refers to thermal environment as well as air
quality. These two factors must be considered in the design
of a ventilation system for a room or a building, as they are
fundamental to the comfort and wellbeing of the human
occupants or the performance of industrial processes within
these spaces,[1]. Numerous studies have associated the
quality of indoor air with people’s complaints and with their
performance. It has been shown that poor air quality causes Sick Building Syndrome (SBS) symptoms such as increased
prevalence of headache decreased ability to think, increased
dizziness, etc., [2]. Providing good air quality, on the other
hand, increases occupant’s productivity,[3]. Furthermore, it
has been documented that the quality of inhaled air of low
enthalpy (low temperature and humidity) is perceived to be
better than when the enthalpy is high,[4].
In today’s office environment, computers and other heat-
generating devices are widely used, and these internal heat
gains together with intense solar conditions can result in a
high heat load in enclosures. This posse challenges for
office ventilation,[5]. Although the specific agents
associated with these problems are not known, many studies
have demonstrated that these symptoms, most of illnesses
and complaints caused by poor indoor air quality and perceived physical discomfort,[6]. The designers and
operators of ventilation systems should be familiar with the
comfort requirements and the quality of air necessary to
achieve acceptable indoor conditions. These require
knowledge of the heat balance between the human body and
the internal conditions, the factors that influence thermal
comfort and discomfort as well as the indoor pollution
concentrations that can be tolerated by the occupants and the
nature of the physically activity,[1].
Indoor environmental conditions are important to the
health, comfort and productivity of occupants.
Accumulating evidence has shown that poor climate quality
is related to increase Sick Building Syndrome (SBS)
symptoms and decreased work performance,[7]. Ventilation
systems are therefore widely used to provide a good indoor environment with respect to thermal comfort and indoor air
quality. By delivering a sufficient amount of outdoor cool
fresh air into the room, excess heat and internally generated
contaminant concentration levels can be removed and
reduced. Natural ventilation appeared as an attractive
International Journal of Mechanical & Mechatronics Engineering IJMME-IJENS Vol:19 No:06 50
190106-7575-IJMME-IJENS © December 2019 IJENS I J E N S
strategy used in the past to provide an acceptable
microclimate in the space being ventilated, [1] but it is
limited to range of climates, microclimates, building types,
etc. Heat is exchanged between the human body and its
environment by four main modes: evaporation, radiation,
convection and, to an insignificant extent because of the small area of contact usually involved, conduction. Since
displacement ventilation was initially used in the welding
industry in 1978, it has been gaining popularity in
Scandinavia as a method of ventilation suitable to maintain
good indoor air quality(IAQ) in occupied zone and improve
energy-efficiency not only for large spaces with high
ceilings, such as assembly halls, but also for offices and
other commercial spaces use. In 1989 in Nordic countries, it
was estimated that displacement ventilation share represents
a 50% of industrial applications market and 25% in office
applications. A typical displacement ventilation system
provides cool air at a temperature several degrees below room air temperature and at a very low velocity of less than
0.5 m/s through large-area supply devices near the floor
level and extracts air at the ceiling level. The supply air
spreads over the floor and then moves up as it comes into
contact with hot surfaces, e.g. persons or electrical devices
exist in occupied space. A displacement system is not
suitable for heating as the outdoor supply air rises towards
the ceiling before it fills the occupied zone,[8]. The
displacement ventilation system could be used with under
floor systems and can provide higher thermal comfort
degree and better cooling efficiency comparing with the all air condition systems,[9]. The temperature different limit
between head and feet about (2-3°C) due to the comfort
requirements, therefore the inlet air cannot be too cold,[10].
Personal ventilation is a generic descriptor for desk- or workstation mounted air-conditioning registers that deliver
conditioned air directly to the breathing zone of office
workers. PV systems have the potential to improve occupant
comfort by increasing individual control over air
conditioning outlets as well as by improving indoor air
quality at the point of use. They may also have the potential
to reduce energy use by reducing the amount of conditioned
air delivered to a workspace [11]. Personalized ventilation
has been applied for many years in theatres and vehicle
cabins, in most cases in order to improve occupants’ thermal
comfort. Only few studies report on the performance of PV in office buildings [12]. The effectiveness of the
personalized ventilation depends greatly on the design of the
PV Air-Terminal Device [13]. Design of PV with high
ventilation effectiveness easily applicable in practice is not
an easy task. Apart of the ventilation effectiveness other
factors, such as background room air distribution, control
strategies, occupant activities, appearance of air supply
devices, etc., are also important [14]. Personalized
ventilation (PV) aims to supply clean air directly to the
breathing zone of room occupants and therefore it has
potential to achieve ventilation effectiveness substantially
higher (ventilation effectiveness §50 or more) than the
ventilation effectiveness of mixing and displacement
ventilation [15].
In rooms with DV the workstations are at a distance from
the supply devices in order to avoid draft discomfort at the
feet. The use of ducts for transporting clean air to the PV
systems installed at each desk is inconvenient and for many
cases unacceptable. A novel idea of “ductless” personalized
ventilation (DPV) has been explored [16]. The key feature is
the utilization of the displacement principle of air distribution, i.e., the creation of a layer of clean and cool air
above the floor. The air from this layer is sucked from,
transported, and supplied directly to the breathing zone of
each occupant by the DPV system.
K.C. Ng et.al.,[17], focused on the influence of changing
three design variables at the same time in displacement
ventilated offices, i.e. diffusers locations, temperature of
supplied air and position of exhaust grills on response
variables behaviour (air diffusion performance index).
Proving that the response surface methodology is an
efficacious method to carry out the detailed investigation of
air diffusion performance index when using different
combinations of three design variables. The accurate of
these models by comparing the ADPI values with values
obtained when CFD technique was used. Also, it was checked the used governing equations for their acceptability
with a confidence interval of 95%.
Kanaan et.al.,[18], assessed the air quality in spaces
conditioned by displacement ventilation (DV) aided with personalized ventilation (PV) on the basis of the average
CO2 concentration levels. The interaction between the
displacement ventilation flow, upward flow of the rising
occupant plume, exhalation flow, and personalized airflow
is modeled in order to predict the CO2 transport inside the
space and the inhalation zone of occupants to monitor the
air quality. The contribution of PV in lowering the CO2
concentration of the inhaled air is evaluated by computing
the personal exposure effectiveness in terms of the CO2
concentrations in PV air and inhaled air with and without
PV. The developed model was validated by comparing
model results of CO2 concentrations with results obtained from 3D simulations using commercial software and with
published experimental data for different PV distances from
the occupant, flow rates, and temperatures of PV jets. The
performance of PV in conjunction with DV regarding
inhaled air quality depends on the location with respect to
the human face and the PV airflow rate and temperature.
Different aspects of personal exposure at different
stratification heights in a displacement ventilated room were
examined by Nielsen,1996,[19]. For the experiments, a
thermal manikin was used to measure personal exposure.
The results showed that the flow in the boundary layer
around a person is able to entrain and transport air from
International Journal of Mechanical & Mechatronics Engineering IJMME-IJENS Vol:19 No:06 51
190106-7575-IJMME-IJENS © December 2019 IJENS I J E N S
below the breathing zone to a great extent, thus improving
the quality of the inhaled air.
As mentioned in the literature, the air quality in an office
room conditioned by DV aided with PV ventilation systems
has not been explored. The present work aims to find out
how air quality affected in the breathing zone when the DV
system is aided by PV that introduces fresh air directly at
the breathing level. Also, studying the DV and PV
performance and determining the Air Distribution
Performance Index (ADPI), effective assessed.
II. EXPERIMENTAL METHOD
A. The Office Room Design
All experiments in this work were done in isothermal
tested room insulated by glass wool and a layer of thermal
nylon in a laboratory of Mechanical Engineering, College of
Engineering, University of Babylon as shown in Fig. (1).
A steady state working conditions were assumed in both
experimental and numerical analysis. Full-scale office room
was used to study temperature distribution, velocity
magnitude and flow rate by adopting two air supply diffuser
DV and PV under Iraqi climate with variation in location
and occupant situation. The test studied room dimensions
are:(3 x 1.75 x 3) m, which is included for case-I displacement ventilation only, two person office, two PC-
simulator, one grille located at north side and one door at
west side as shown in Fig. (2) and. The basic configuration
requirements for the test room have been indicated and they
are summarized in table I.
Fig. 1. Front view of experimental isothermal tested room insulated
by glass wool and a layer of thermal nylon
Fig. 2. Schematic diagram of office room with diffuser DV
The different objects which located at tested room and
adopted during experiment part were three types of heat
sources used in tested room and described by: two Human body properties represented by used human thermal
manikin, two computer with a heat of 45W and one
florescent lights were placed as heat sources and installed
in suspended ceiling as described in details in Fig.(2). Also,
commercial air-conditioner was used to deliver the cooled
air to indoor space of the room.
Table I
Room configuration for case-I
For case-II displacement and personal combined, one
person office, one grille located at north side and one door
at west side as shown in Fig. (3) and. The basic
configuration requirements for the test room have been
indicated and they are summarized in table II.
International Journal of Mechanical & Mechatronics Engineering IJMME-IJENS Vol:19 No:06 52
190106-7575-IJMME-IJENS © December 2019 IJENS I J E N S
Fig. 3. Schematic diagram of office room with diffuser
DV and PV
The different objects which located at tested room and
adopted during experiment part were three types of heat sources used in tested room and described by: one Human
body properties represented by used human thermal
manikin, one computer with a heat of 45W and one
florescent lights were placed as heat sources and installed
in suspended ceiling as described in details in Fig.(3).
Also, PV system consists of a fan with different flow rates
controlled by an electric regulator where the air is pushed
from the bottom at 0.4 meters Through air terminal device
(ATD) to the top at the human seating level of 1.1 meters.
Table II
Room configuration for case-II
B. Supply System
There are some steps to find ventilation rate and supply air
temperature for displacement ventilation applications. The
procedures are based on the Iraqi cooling code, [21].
1- Ventilation air flow rate
The required air flow rate for cooling load, is:
𝑄 =0.295𝑞𝑜𝑒+0.132𝑞𝑙+0.185𝑞𝑒𝑥
𝜌𝑐𝑝∆𝑇ℎ𝑓 (1)
Q = U ∗ A ∗ ∆T (2)
(3)
2- Air supply temperature:
Equation (4) was used to predict temperature of supplied
air (Ts) during the experiments, [22].
The air change per hour (ACH) was determined by
equation (5) and its value 8.32, [23].
ACH = (Q/VRoom) ∗ 3600 (5)
The one direction air supply diffuser DV was shown in
Fig.(4). The air supply diffuser of personal ventilation was
shown in Fig.(5).
C. Measurement devices:
The measuring devices are divided into three main systems:
- Sample units: During all the tests there are three sample units ,each sample unit has six nods being
placed at various height levels of (0,0.4, 0.8, 1.1, 1.4 ,
1.8)m and used to record the parameters that are
located at first pole (x=2 m, y=0 m, z=0.875 m),second
pole(x=0.7 m, y=0 m, z=0.5 m) and third pole(x=0.7
m, y=0 m, z=1.25 m) for all cases as shown in Fig.(6).
- Air velocity: The hot wire thermo-anemometer sensors
model YK.2005AH.
- Temperature measurement tools: A large number of
thermocouples type K were used to record air
temperature. The thermocouples measure the
temperature with time average 600s.
w
International Journal of Mechanical & Mechatronics Engineering IJMME-IJENS Vol:19 No:06 53
190106-7575-IJMME-IJENS © December 2019 IJENS I J E N S
Fig. 5. Air supply outlet for PV diffuser
Fig. 6. Photograph of pole with node level location and thermocouple
measurement
D. Experimental Procedures:
The experiment part has done in two stages according to
type of ventilation devices. the experiments were done in April 2019. The tested room was prepared by installed
suspended ceiling at distance (3 m) from floor. The
measurements of air parameters were taken after one hour of
cooling unit working. The experiment measurement
repeated for two cases at three times to be sure about
readings. Tables III and table V show the results of cases for
each pole.
1- Case-I (air supply system is DV only)
Table III
Temperature(oC)obtained by adopting DV System
2- Case-II (combined DV and PV system)
In this case personal system draw air at level 0.4m and
direct it to breathing zone at 1.1m by fan have flow rate
10l/s.
Table IV
Temperature (ºC) obtained by adopting DV and PV System
III. ANALYTICAL INVESTIGATION
A. General Governing Conservation Equations:
Problem of flowing fluid can be modeled by a
combining conservation equation for each of mass,
momentum, energy and transport species. In present
work simulation, air motion is assumed to be three
dimensional incompressible and at steady state.
-Conservation of mass:
Conservation of mass is given by the following
equation, [1].
(6)
Pole
No.
Thermocouple height from the foot level(m)
0
0.4
0.8
1.1
1.4
1.8
Air temperature (oC)
Pole1 20 21.6 22.1 22.4 23 23.6
Pole2 20.2 21.9 22.3 23.1 23.7 24
Pole3 20.4 22 22.5 23.4 23.9 24.3
Pole
No.
Thermocouple height from the foot level(m)
0
0.4
0.8
1.1
1.4
1.8
Air temperature (oC)
Pole1 20.1 22.3 23.3 23.5 24.3 24.6
Pole2 20.2 22.5 24.1 23.2 24.1 24.3
Pole3 20.4 22.7 23.9 22.8 23.8 24.1
Fig. 4. The supply air diffuser (DV) manufacturing
International Journal of Mechanical & Mechatronics Engineering IJMME-IJENS Vol:19 No:06 54
190106-7575-IJMME-IJENS © December 2019 IJENS I J E N S
Conservation of momentum (Navier–Stokes Equations):
The resultant forces effecting a differential control volume
can be determined by applying momentum conservation law
in each coordinate direction to get three force components
in the x, y and z directions.
Conservation of thermal energy:
(7)
Where:
(Γ) is the diffusion coefficient (diffusivity), which is given
by:
(𝜎 =𝜇𝐶p ⁄k) is the Prandtl or Schmidt number for the
fluid.
The terms and are the turbulent
heat fluxes, St is a source term allowing for the rate of
thermal energy production.
-The concentration of species equation:
Equation of species concentration can be written as:
:𝜕
𝜕(𝜌𝑢𝑐) +
𝜕
𝜕𝑦(𝜌𝑣𝑐) +
𝜕
𝜕𝑧(𝜌𝑤𝑐) =
𝜕
𝜕𝑥(Г
𝜕𝑐
𝜕𝑥) +
𝜕
𝜕𝑦(Г
𝜕𝑐
𝜕𝑦) +
𝜕
𝜕𝑧(Г
𝜕𝑐
𝜕𝑧) +
𝜕
𝜕𝑥(−𝜌𝑢′𝑐′) +
𝜕
𝜕𝑦(−𝜌𝑣′𝑐′) +
𝜕
𝜕𝑧(−𝜌𝑤′𝑐′) + SC
(8)
In this equation, (c) is the time-mean concentration
and c' is the deviation from the mean. The terms
and are the turbulent diffusion
fluxes.
B. Computational Set and Numerical Scheme:
The present study includes an office room with DV only, two heat source above a solid tables and two person
for case-I, and DV combined with PV, one heat source
above a solid table and a single person for case-II, besides,
new case was studied numerically which was used DV only
with one person and one computer and named as case-III.
The effective draft temperature (EDT) was taken in (100)
points distributed along ten horizontal range at Y=0 and
Y=1.8 inside the occupied zone. Also, have been performed
to compare practical results with theoretical results through
pole (1) at distance (x=2 m, y=0 m, z=0.875 m).
Many steps in fluent part are used in (CFD) program. At
the begging simulation Problem setup and included Model. Also, the solution to flow field problems (temperature,
pressure, velocity, etc) is defined at nodes for each cell. The
number of elements for case-I, case II and case-III were
289496, 267492 and 199382, respectively as shown in Fig.
(7). Materials setup which included material properties
used in simulation such as density (ρ), specific Heat (Cp)
and thermal Conductivity (k)with values1.189, 1005 and
0.0258, respectively. The Boundary conditions which has a significant impact on CFD simulation success in giving a
reliable results for solved problem. Boundary conditions
that imposed in CFD simulation implemented in this work
consist of three types: velocity inlet and outflow as
tabulated in table V. wall boundary included Walls with
constant temperatures and also constant heat fluxes from
other internal source such as Person, Computer and Light
are 44.69, 176.47 and 2000 respectively.
(a)
(b)
(c)
Fig. 7. Meshed model for experimental domain (a)Case-I
(b)Case-II (c)Case-III
y
x
z
y
x
z
y
x
z
International Journal of Mechanical & Mechatronics Engineering IJMME-IJENS Vol:19 No:06 55
190106-7575-IJMME-IJENS © December 2019 IJENS I J E N S
Table V Momentum boundary conditions
Part Type Momentum condition
Wall
motion Shear condition
Person Wall Stationary No Slipping
Computer Wall Stationary No Slipping side walls, floor, ceil,
Wall Stationary No Slipping
tables and lights Wall Stationary No Slipping Supply air diffuser
velocity inlet
magnitude, normal to boundary
Extract Grill Pressure outlet
-Gauge Pressure = (0 Pascal), [constant]. -Backflow direction specification Method: (Normal to Boundary).
When solving problem numerically it’s impossible to
get an exact solution, so accepted scaled error residuals
should be specified for different terms such as continuity,
velocity components and energy.
In this Distribution Performance Index (ADPI) was
evaluated to assessment diffusion performance of air for
different cases in a ventilated space. The effective draft
temperature (EDT) is calculated from equation below:
𝐸𝐷𝑇 = (𝑇𝑥 − Tav) − 8 ∗ (𝑉𝑥 − 0.15) (9)
The validation was carried out by comparing obtained
CFD results with data obtained from experiments in tested
room for case-I and case-II (displacement and personal
ventilation system). The comparison depends on the vertical
temperature which measured in tested room in six levels and
that of numerical studies. The overall average error calculations due to the following equation (10), [24].
The average percentage error were 10.5% and 13.5% for
case-I and case-II, respectively.
𝐴𝑣𝑒𝑟𝑎𝑔𝑒 𝑑𝑒𝑣𝑖𝑎𝑡𝑖𝑜𝑛(𝐸𝑎𝑣%) =1
𝑛∑
𝑋𝐶𝐹𝐷𝑖 −𝑋𝐸𝑋𝑃
𝑖
𝑋𝐸𝑋𝑃𝑖 ∗ 100𝑛
𝑖
(10)
IV. RESULTS AND DISCUSSION
A. Experimental and Numerical Results
The numerical and experimental results inside the
modeled room for case-I and case-II were studied.
Experimental results obtained at different diffuser and
locations for different occupant distribution. Besides
measured air temperature distribution, velocity distribution
from the three poles for the cases studied at locations first pole (x=2 m, y=0 m, z=0.875 m),second pole(x=0.7 m, y=0
m, z=0.5 m) and third pole(x=0.7 m, y=0 m, z=1.25 m) .
The numerical results in the present study for the tested
room was adopted using many computational runs at
various planes and for all the domain. Air Distribution
Performance Index (ADPI) and effectiveness temperature
were determined. Fig. (8) shows the relation of air
temperature versus the room height through poles 1,2 and 3.
Since the temperature changes directly proportional with the
room height. The reason of this temperature values increase
is due to increase of distance from air supply level.
(a)
(b)
Fig. 8. Measured temperature distributions for poles1,2 and 3, (a) case I,
(b) case-II.
International Journal of Mechanical & Mechatronics Engineering IJMME-IJENS Vol:19 No:06 56
190106-7575-IJMME-IJENS © December 2019 IJENS I J E N S
Table-VI presents numerical results of Air Distribution
Performance Index (ADPI) and effectiveness temperature(ɛt)
for three cases. The maximum value of effectiveness and Air
Distribution Performance Index (ADPI) founded at case-II
that evaluated at five levels of room layers.
Table VI
Numerical values of ADPI and effectiveness temperature
Fig. (9) display numerically the contours of air temperature
distribution at five plans in the test room. Also, showed that the
temperature increases from 20 oC closely to the supply terminal
and reach about 30oC near the human body. It found in case-I
and case-III that the floor region near the supply diffuser zone
would show the lowest temperature values, due to the cooling
effect of the supply entering air. In addition, a gradual increase
in temperature obtained as elevation increase inside the room
except that case-III show little increase of temperature level
because of the heat source were less than case-I, for case-II
showed that PV draw the cold air at low level at 0.4 meter to seat level at 1.1 meter (breathing zone) so the temperature
degree at seat level is less than case-I and case- III. Also, an
increase in indoor temperature can be noted near the person,
computer, lighting for all cases.
(a)
(b)
(c)
Fig. 9. Compute temperature contours plans (1,2,3,4&5), (a) Case-I, (b) Case-II, (c) Case-III
In case-II (combined displacement and personal ventilation),
Fig(9-b) shows the computed temperature distribution is better
than case-I and case-III (displacement ventilation only) obtained
in Fig (9- a,c). For case-I and case-III where the person, computer and light located, the hot region around them effect on
all of room air temperature due to reduce ventilation efficiency,
for case-II suitable distribution and air circulation obtained near
the three heat source result from the movement of cold air from
personal ventilation which reduced heat emitted by the person
and computer.
From numerical results, the velocity field for the three cases
are shown in Fig. (10). High values of air velocity obtained at
the lower region due to location of air supply diffuser DV in
this zone. The heat transfer process at this location is more
efficient in reducing the temperature of the domain since the
supply air stream itself has low temperature, therefore it decreases the temperature in this zone.
(a)
(b)
Ventilation
devices
Case-I
DV
only
Case-II
DV combined
PV
Case-III
DV
only
ADPI% 0.6 0.71 0.65
Effectiveness 1.32 1.8 1.34
y
x
z
y
x
z
y
x
z
y
x
z
z
y
x
International Journal of Mechanical & Mechatronics Engineering IJMME-IJENS Vol:19 No:06 57
190106-7575-IJMME-IJENS © December 2019 IJENS I J E N S
(c)
Fig. 10. Computed velocity contour at planes 1.2&5 at (a) Case-I (b) Case-II
(c) Case-III
Comparison between measured temperature profiles at pole-1 at
distance (1) m from air supply diffuser DV, with simulated
temperature profile using RNG, K-ε turbulence model. This
comparison shown in Fig.(11). The average deviation between
the experimental and numerical values, for case-I and case-II
were:10.5% and 13.5% respectively.
(a)
(b)
Fig. 11. Comparison between predicted and experimental results
using three direction-square diffuser
B. Comparison Between Cases
From the previous results for the three cases. Accepted results
can be obtained for three cases but case-II gives more suitable
thermal comfort in modeled room. Numerically and from RNG
K-ε turbulence model, amongst the three cases, for one
direction-rectangular diffuser for DV and PV at case-II and DV
only at case-III gives:
temperature contour for all plane inside occupied zone shown in
Fig. (12), the cold air spreads through the floor of the room
from the inlet close to the floor level where DV found, the
maximum velocity was found out at temperature 18oc which
spreading accumulated only at smallest zone at northern region,
besides PV drawing air from that zone to breathing zone, so that allows staying the occupied zone in thermal comfort.
Numerically, Fig. (13) presents streamlines flow patterns for the
case-II and case-III entered to room from diffuser at one
direction. The main face directed to the southern wall and
slightly raise towards the return grille. This process causes some
small eddies near opposite corner and then these streams moves
in similar path of the main stream towards return air grille. The
movement of air caused by buoyancy and inertia forces.
(a)
(b)
Fig. 12. Temperature contour at 1.1 m (breathing zone) plane-2 and plane5 (a)
Case-II (b) Case-III
y
x
z
y
x
z
y
x
z
International Journal of Mechanical & Mechatronics Engineering IJMME-IJENS Vol:19 No:06 58
190106-7575-IJMME-IJENS © December 2019 IJENS I J E N S
(a)
(b)
Fig. 13. Computed streamlines flow pattern, (a) case-II (b) case-III
V. CONCLUDING REMARKS
From the results of the present study, the following
conclusions can be summarized as follow:
1. The performance of PV in conjunction with DV regarding
inhaled air quality depends on the location with respect to
the human face and the PV airflow rate and temperature.
2. At elevated room temperature, the supply of clean and cool
air to the breathing zone of occupants with DPV will
improve occupants’ thermal comfort, perceived air quality,
and quality of inhaled air in comparison with DV alone.
Under some conditions energy saving may be achieved with
this strategy.
3. RNG k-ε turbulence model gives a good agreement between
the experimental and numerical data in the validation cases
by predicting the airflow patterns and thermal behaviour of
displacement and personal ventilation devices in an office
room.
4. It was found that the PV air temperature may affect the
ventilation effectiveness of the system, where higher PV temperature results in better air quality in the breathing
zone.
5. The simulated data was found to be slightly underestimated
as compared to the measured data.
6. The situation of occupant distribution affects on result of Air
Distribution Performance Index (ADPI) and air
effectiveness.
7. From the results comparisons, the values of (ADPI) were
calculated to all cases. The maximum value was about 71%
and for (εt), the maximum value was about 1.8 and obtained
from case-II.
REFERENCES [1] Awbi, Hazim, “Ventilation of Buildings”, Taylor and Francis group,
second edition,2003.
[2] Wargocki, P., Wyon, D.P., Sundell, J., Clausen, G., and Fanger, P.O.
2000. The effects of outdoor air supply rate in an office on perceived
air quality, Sick Building Syndrome (SBS) symptoms and
productivity”, Indoor Air, 10, pp. 222-236 .
[3] Seppänen, O. and Fisk, W.J. 2005. A model toestimate the cost-
effectiveness of improving office work through indoor
environmental control, ASHRAE Transactions, Part 2 .4.
[4] Fang, L., Clausen, G., and Fanger P.O. 1998. Impact of temperature
and humidity on the perception of indoor air quality during
immediate and longer whole-body exposures, Indoor Air ,8 ,pp. 276-
284 .
[5] Huijuan Chen, “Experimental and numerical investigations of a
Ventilation strategy impinging jet ventilation for an, office
Environment”, M.Sc. Thesis, Linköping Studies in Science and
Technology Dissertation No. 1606, and ISBN: 978-91-7519-299-4,
2014.
[6] Isaac Turiel, “Indoor Air Quality and Human Health”, Taylor and
Francis group,first edition, 1985.
[7] Mcquiston, F.C and J.D. Parker, Heating, Ventilating conditioning
Analysis and Design, Third Edition, John Wiley & sons, USA,1988.
[8] Ahmad A.M.saleh, Experimental an numerical study of velocity
and temperature distributions in air conditioning spaces,
Mech..Eng. Dep. of University of Technology,2005.
[9] Y. Ren, D. Li, Y. Zhang, “Numerical Simulation of Thermal
Comfort Degree in Radiant Floor Cooling Room” Building
Simulation, pp. 427431,2007.
[10] E. Skaret, “Displacement ventilation Procedure room vent.”,
Stockholm, Sweden, 1987.
[11] S. Drake. “The use of personal ventilation in open plan offices: a
study of the TASK AIR system” University of Melbourne,
Melbourne, Australia,2008.
[12] Kroner WM, Stark-Martin JA (1994). Environmentally responsive
workstations and office-worker productivity, ASHRAE Transactions,
vol 100 (2), 750-755 .
[13] Melikov, A.K., Cermak, R., Kovar, O., Forejt, L., Impact of airflow
interaction on inhaled air quality and transport of contaminants in
rooms with personalized and total volume ventilation ,Proceedings of
Healthy Buildings 2003, Singapore, 7-1 National University of
Singapore ,Department of Building, vol. 2, pp. 592-597 .
[14] Schiavon, S., Melikov, A., Cermak, R., De Carli, M., Li, X. 2007.
An index for evaluation of air quality improvement in rooms with
personalized ventilation based on occupied density and normalized
concentration, Proceedings of Roomvent 2007, June 13-15, Helsinki,
Finland.
[15] Melikov, A.K. 2004. Personalized ventilation, Indoor Air, vol. 14,
supplement 7, pp. 157-167 .
[16] Halvonova, B., and A.K. Melikov. 2008. “Ductless” personalized
ventilation in conjunction with displace-ment ventilation. Proceeding
ofIndoor Air 2008, Denmark, Paper ID: 411.
[17] K.C. Ng, K. Kadirgama, E.Y.K. Ng,response surface models for
CFD predictions of air diffusion performance index in a
displacement ventilated office, Energy and Buildings 40, 2008.
[18] M. Kanaan, N. Ghaddar, ∗ and K. Ghali, “Quality of inhaled air in
displacement ventilation systems assisted by personalized
ventilation”, American University of Beirut, 1078-9669 (Print) 1938-
5587 (Online) Journal, Vol.18 No.3, pp.500–514, 2012.
[19] Brohus, H., Nielsen, P.V. “Personal exposure in displacement
ventilated rooms”, Indoor air, Vol. 6, pp. 157-167.1996.
[20] Radim Cermak. Performance of Personalized Ventilation in
Conjunction with Mixing and Displacement Ventilation.2011 Iraqi
cooling code, 2012.
[21] J.P.Holman, “Heat transfer”, sixth edition, 1986.
[22] Qasim H., Numerical Study of Air Velocity and Temperature
Distribution by Displacement Ventilation, thesis,2010.
[23] Kisup Lee, Comparison of airflow and pollutant distributions in
rooms with traditional displacement ventilation and under-floor air
distribution systems ASHRAE Transactions, 115 ,2009.
y
x
z
y
x
z