www.marshbellofram.com 800.727.5646 79
Ele
ctr
o-P
neum
ati
cs
Type 3000 I/Ps & E/Ps
Type 3110
Type 3111
Type 3120
Type 3210
Type 3220
Type 3211
Type 3221
Type 3212
Type 3222
Type 3215
Type 3410
Type 3411
Type 3420
Type 3510
Type 3520
Type 3511
Type 3521
Type 3512
Type 3522
80 800.727.5646 www.marshbellofram.com
Ele
ctro
-Pn
eum
atic
s
Type 3110
Type 3000 Series Electro-Pneumatic Transducers
Packaging
DIN-mount Circuit Card Weatherproof Enclosure
Low Flow (1.2 SCFM)(34 LPM)
Low Flow (1.2 SCFM)(34 LPM)
Medium Flow (15 SCFM)(425 LPM)
High Flow (60 SCFM)(1700 LPM)
Very High Flow (175 SCFM)(5000 LPM)
User
In
terf
ace
Analog 0-10V 4-20mA
T3110, T3120 or T3111
T3210 or T3220
T3211, T3221 or T3311
T3212or T3222
T3215
Serial RS-485, RS-232, USB
T3410S or T3420S
T3510S or T3520S
T3511S or T3521S
T3512Sor T3522S
Keypad/DisplayProgrammer
N/AT3510P
or T3520PT3511P
or T3521PT3512P
or T3522P
DeviceNetT3410D
or T3420DT3510D
or T3520DT3511D
or T3521DT3512P
or T3522P
Mounting DIN tray, manifold, panelIn-line, DIN-rail,
panel bracket, or manifold
In-line, DIN-rail, panel bracket, or
manifold
In-line, DIN-rail, panel bracket, or
manifold
In-line or panel bracket
Type 3000 Comparison of I/Ps
Type 3000 Series Comparison Chart
T1000, T1500, T1001 and T2000 T3000 Series
Steady Air Consumption Minimal Air Consumption at Steady State
Many are Loop Powered All Require Supply Voltage
Most Available in Intrinsically Safe or Explosion Proof Versions
No Hazardous Area Approvals
Standard Pressure Range to 120 PSI, No Vacuum Models,
Limited Low Pressure Control Capability
Wide variety to 600 psi or vacuum, even possible in 0 to 0.2 psi range
Downstream Sensor Feedback Not Available Second Loop Feedback Available
Analog and Logic Output Signal Monitoring
Digital Versions have Keypad or Serial User Interface
Wide Range of Input Signal/Output Pressure Endpoint, Available in Digital
Type 3110 Manifold Mount
Air Quality
Bellofram specifies the use of instrument quality air (clean, dry, oil free) for all transducers. Transducers should be used within the following conditions:
Dew Point < 35F (2C) (indoor) Oil Content < 1ppm Particles < 3m.
The use of filters in the supply air system is highly recommended. Contact us for information on our filters and filter regulators.
www.marshbellofram.com 800.727.5646 81
Ele
ctr
o-P
neum
ati
cs
Features and Capabilities
The Type 3000 series of electro-pneumatic transducers offers an innovative set of features and capabilities. Each electronic pressure regulator utilizes a pair of reliable quick-firing solenoid valves and an onboard pressure sensor to precisely control downstream pressure and at the same time achieve excellent accuracy and stability.
Feed-and-bleed transducers are inherently resistant to shock, vibration, and orientation. To size the regulator for the application, a selection of external volume boosters up to 2000 SCFM (56,000 lpm) are available.
Analog Control Signals: 0-10v, 4-20 mA, etc. Remote Sensor Feedback Monitor Output High/Low Logic Output Digital Signal Processing PID Tuning Deadband Adjustment Serial, Keypad/Display, DeviceNet Interfaces
Theory of Operation
T3000 transducers utilize proven feed-and-bleed technology. The Supply Solenoid Valve feeds supply pressure to the downstream application. The Exhaust Solenoid Valve bleeds off overpressure. By monitoring the onboard pressure sensor (or the user-supplied remote sensor on two-loop units), the electronics rapidly fire one solenoid or the other to maintain the desired setpoint.
Standard Type 3000s hold output pressure upon loss of electrical power, as long as there are no downstream flow demands. Special versions are available for Fail High or Low Operation.
Type 3000 SeriesOverview Type 3110
Type 3210
Type 3211
2nd Loop Adjustments(3120 Only)
Control SignalJumpers (V or mA)
Supply Valve
Onboard Pressure Sensor
Supply Port
Output Port
Exhaust Port
Electrical Connections:Control Signal, DC Power, Analog Monitor Output, Logic Output, Remote Sensor Feed Back, Ground
Zero, Span and Gain Adjustment
Exhaust Valve
82 800.727.5646 www.marshbellofram.com
Ele
ctro
-Pn
eum
atic
s
Description
The compact Type 3110 (one-loop) and 3120 (two-loop) Circuit-Card Pressure Regulators are perfect for size-conscious OEMs, without sacrificing any of the high-end performance normally associated with full-size I/Ps.
Industry-standard analog control signals (0-10V or 4-20 mA) are user-selectable (V or mA) and configurable (zero and span). Industry-standard analog monitor output signal (0-10V) available for user-monitoring of actual output pressure. Industry-standard logic output signals (high or low) are available for user-monitoring of setpoint status at setpoint or still searching.
Features
Small FootprintUser Selectable InputAnalog Monitor OutputSingle Loop and Dual Loop ControlEconomical
Type 3110 / Type 3120 Analog Circuit-Card Regulators
Type 3110 Analog Circuit-Card Regulators
Type 3110/T3120 Ordering Information
1 0 T 0 600 0
Number of Loops1 1 Loop2 2 Loop
0Logic Output
T TTLAnalog Control Signal
E 0-10VI 4-20mA
Lower Output Pressure
0 Lower Limit of Output PressurePressure Units
G PSIGA PSIA absoluteV VacuumW Inches of water column
Upper Output Pressure
600 Upper Limit of Output Pressure (PSIG)Mounting
D DIN TrayP Panel-Mount *
M Manifold-Mount (150 psig max output)Supply and Output Ports
0 1/8 NPT1 1/8 BSPT2 1/8 BSPP
Connector0
Options00 None14 12VDC supply
*For flush panel mounting specify 'P' option and order 161-520-000 bracket.
Type 3110 and 3120
Performance Full-Scale Accuracy 0.5%
Electrical Inputs
Supply Voltage 15-24VDC (12VDC option)
Stand by Supply Current 80 mA
Maximum Supply Current 250 mA
E/P Control 0-10V, 10K OHMS
I/P Control 4-20 mA , 250 OHMS
Electrical Outputs
Mounting Options 0-10V
Logic Output TTL
Pneumatic Inputs
Supply Pressure
Max. Output PSIG (BAR) Max. Supply PSIG (BAR)
Up to 5 (.35) 20 (1.4)
>5 to 15 (.35-1.03) 30 (2.1)
>15 to 30 (1.03-2.1) 60 (4.1)
>30 to 100 (2.1-6.9) 165 (11.4)
>100 to 150 (6.9-10.3) 200 (13.8)
>150 to 300 (10.3-20.7) 350 (24.1)
>300 to 600 (20.7-41.4) 650 (44.8)
Pneumatic Outputs
Full-scale Atmospheric Pressure Ranges
1, 5, 15, 30, 100, 150, 300, 500, 600 psig
0.07, 0.35, 1.03, 2.07, 6.9, 10.34, 20.68, 34.47, 68.95 BAR
Vacuum Pressure Ranges 30" Hg, 30,150 PSIA (2.1 BAR, 10.3 BAR)
Forward Flow Capacity 1.25 SCFM (35.4 LPM)
Exhaust Flow Capacity 1.25 SCFM (35.4 LPM)
Environmental
Operating Temperature 32-141F (0-60C)
Media-Wetted Materials Aluminum, copper alloys, nickel, buna-n, silicon, 316SS
Recommended Accessories Manifold, Power Supply, Control Knob, Remote Pressure Sensor, External Volume Booster
www.marshbellofram.com 800.727.5646 83
Ele
ctr
o-P
neum
ati
cs
Description
The T3111 Compact Analog Pressure Controller is an economical version of the T3100 with no remote feedback or logic output capabilities. Output pressure is limited to 150 PSIG maximum. Jumper selections include AC/DC power and several control signal ranges. Manual output pressure adjustment and differential control signals are available. Overall product dimensions are identical to Type 3110.
Features
HVAC applicationMounts on panel, DIN rail, or directly to multi-station manifoldSmall FootprintNo Analog Monitor OutputEconomicalManual override for output span adjustments
Type 3111 Analog Circuit-Card Regulators
Type 3111 Analog Circuit-Card Regulators
Type 3111/Ordering Information
111Z 0 150 0
Analog Control SignalE 0-10VI 0-20 mA0 0-5V1 0-15V
Lower Output Pressure0 Lower Limit of Output Pressure
Pressure UnitsG PSIGA PSIA absoluteV VacuumW Inches of water column
Upper Output Pressure150 Upper Limit of Output Pressure (PSIG)
MountingD DIN TrayP Panel-Mount *M Manifold-Mount
Supply and Output Ports0 1/8 NPT1 1/8 BSPT2 1/8 BSPP
Connector0
Options00 None14 12 VDC supply
*For flush panel mounting specify 'P' option and order 161-520-000 bracket.
Type 3111
Performance Full-Scale Accuracy 0.5%
Electrical Inputs
Supply Voltage 24VDC (12VDC option) 24VAC
Stand by Supply Current 80 mA
Maximum Supply Current 250 mA
E/P Control 0-5V, 0-10V, 0-15V 2K-100K ohms
I/P Control 0-20 mA , 250 ohms
Pneumatic Inputs
Supply Pressure
Max. Output PSIG (BAR) Max. Supply PSIG (BAR)
Up to 5 (.35) 20 (1.4)
>5 to 15 (.35-1.03) 30 (2.1)
>15 to 30 (1.03-2.1) 60 (4.1)
>30 to 100 (2.1-6.9) 165 (11.4)
>100 to 150 (6.9-10.3) 200 (13.8)
Pneumatic Outputs
Full-scale Atmospheric Pressure Ranges
1, 5, 15, 30, 100, 150 PSIG
0.07, 0.35, 1.03, 2.07, 6.9, 10.34 BAR
Vacuum Pressure Ranges 30" Hg, 30, 150 PSIA (2.1 BAR, 10.3 BAR)
Forward Flow Capacity 1.25 SCFM (35.4 LPM)
Exhaust Flow Capacity 1.25 SCFM (35.4 LPM)
Environmental
Operating Temperature 32-141F (0-60C)
Media-Wetted Materials Aluminum, copper alloys, nickel, buna-n, silicon, 316SS
Recommended Accessories Manifold, Power Supply, Control Knob, Remote Pressure Sensor, External Volume Booster
84 800.727.5646 www.marshbellofram.com
Ele
ctro
-Pn
eum
atic
s
Description
The Type 3210 single loop and 3220 double loop electro-pneumatic servo pressure controllers incorporate two solenoid valves and an internal pressure sensor for increased sensitivity and ac-curacy. With current or voltage signal inputs, the Type 3210/3220 controls an output pressure with an accuracy of .5% or better full scale. A wide range of output pressures available, from 29" Hg vacuum to 600 psig. With a flow of 1.25 SCFM at 100 PSI, the 3210/3220 can be used alone or in conjunction with a volume booster to achieve flow rates in excess of 2,000 SCFM. The double loop (3220) option permits 0-10 VDC feedback from a remote sensor.
Applications include: Semiconductor, Robotics Controller, Machine Automation, Tire Manufacturing and Testing, Molding and Forming Operations and a wide variety of industrial applications.
Features
Weatherproof EnclosureUser Selectable Input SignalAnalog Monitor OutputSingle Loop and Dual Loop Control1.25 SCFM Flow Rate
Type 3210 & 3220Analog Weatherproof Regulators
Type 3210/3220 Analog Weatherproof Regulators
Type 3210/3220 Ordering Information
2 0 0 600 P 1
Number of Loops1 1 Loop2 2 Loop
0Logic Output
M CMOST TTLO Open-Collector
Analog Control SignalE 0-10VI 4-20mA
Lower Output Pressure
0 Lower Limit of Output PressurePressure Units
G PSIGA PSIA absoluteV VacuumW Inches of water column
Upper Output Pressure
600 Upper Limit of Output Pressure (PSIG)Mounting
P Pipe (in-line)Supply and Output Ports
0 1/8 NPT1 1/8 BSPT2 1/8 BSPP
Connector1
Options00 None14 12 VDC supply
_ _
External Volume Booster: X2, X3, Z2, Z3, Z4, N3, N4, N6, N8, Q6, Q8, QA, QB, QC, V2, V3: see chart on page 88
Type 3210 and 3220Performance Full-Scale Accuracy 0.5%Electrical InputsSupply Voltage 15-24VDC (12VDC option)Stand by Supply Current 80 mAMaximum Supply Current 325 mAE/P Control 0-10V,10K OHMSI/P Control 4-20 mA , 250 OHMS2nd-loop Remote Sensor Feedback
T3220: 0-10V
Electrical OutputsMonitor Output 0-10VLogic Output CMOS, TTL, Open-Collector
Pneumatic Inputs
Supply Pressure
Max. Output PSIG (BAR) Max. Supply PSIG (BAR)
Up to 5 (.35) 20 (1.4)
>5 to 15 (.35-1.03) 30 (2.1)
>15 to 30 (1.03-2.1) 60 (4.1)
>30 to 100 (2.1-6.9) 165 (11.4)
>100 to 150 (6.9-10.3) 200 (13.8)
>150 to 300 (10.3-20.7) 350 (24.1)
>300 to 600 (20.7-41.4) 650 (44.8)
Pneumatic Outputs
Full-scale Atmospheric Pressure Ranges
1, 5, 15, 30, 100, 150, 300, 500, 600 PSIG
0.07, 0.35, 1.03, 2.07, 6.9, 10.34, 20.68, 34.47, 68.95 BAR
Vacuum Pressure Ranges 30" Hg, 150 PSIA (2.1 BAR, 10.3 BAR)Forward Flow Capacity 1.25 SCFM (35.4 LPM)Exhaust Flow Capacity 1.25 SCFM (35.4 LPM)Environmental Operating Temperature 32-141F (0-60C)Media-Wetted Materials Aluminum, copper alloys, nickel, buna-n, silicon, 316SSRequired Accessories 6-pin micro cordsetRecommended Accessories
DIN-rail Bracket, Panel Bracket, Power Supply, Control Knob, Remote Pressure Sensor, External Volume Booster
www.marshbellofram.com 800.727.5646 85
Ele
ctr
o-P
neum
ati
cs
Description
The Type 3211 single loop and 3221 double loop controllers offer non-bleeding solenoid valve tech-nology with an integral flow booster that produces forward flows equivalent to standard industrial electronic regulators or I/P converters. The 3211/3221 offers analog monitoring of the output pressure by a 0-10 VDC signal, plus logic monitor output of the solenoid valves. Many output pres-sures are available up to 150 psi. A built in air volume booster provides for a forward flow of up to 15 SCFM and a reverse flow (exhaust) of up to 7 SCFM. The double loop (3221) option permits 0-10 VDC feedback from a remote sensor.
Applications include; Machine Automotive, Robotics Control, Web Tension Control, Tire Manufactur-ing and Testing, Torque Control, Molding and Forming Operations, and Paint Spray.
Features
Weatherproof EnclosureUser Selectable Input SignalAnalog Monitor OutputSingle Loop and Dual Loop Control
Type 3211 & 3221Analog Weatherproof Regulators
Type 3211/3221 Analog Weatherproof Regulators
Type 3211/3221 Ordering Information
2 1 0 150 1
Number of Loops1 1 Loop2 2 Loop
1Logic Output
M CMOST TTLO Open-Collector
Analog Control SignalE 0-10VI 4-20mA
Lower Output Pressure
0 Lower Limit of Output PressurePressure Units
G PSIGW Inches of water column
Upper Output Pressure
150 Upper Limit of Output Pressure (PSIG)Mounting*
P Pipe (in-line)M Manifold-Mount
Supply and Output Ports
0 1/4 NPT1 1/4 BSPT2 1/4 BSPP
Connector1
Options00 None
14 12 VDC supply*Order panel bracket and DIN rail clip separately. For Manifold-Mount (no threads), specify 0 for Supply and Output Ports.
Type 3211 and 3221
Performance Full-Scale Accuracy 0.5%
Electrical Inputs
Supply Voltage 15-24VDC (12VDC option)
Stand by Supply Current 80 mA
Maximum Supply Current 325 mA
E/P Control 0-10V,10K OHMS
I/P Control 4-20 mA , 250 OHMS
2nd-loop Remote Sensor Feedback
T3221: 0-10V (4-20mA option)
Electrical Outputs
Monitor Output 0-10V (4-20 mA option)
Logic Output CMOS, TTL, Open-Collector
Pneumatic Inputs
Supply Pressure
Max. Output PSIG (BAR) Max. Supply PSIG (BAR)
Up to 5 (.35) 20 (1.4)
>5 to 15 (.35-1.03) 30 (2.1)
>15 to 30 (1.03-2.1) 60 (4.1)
>30 to 100 (2.1-6.9) 165 (11.4)
>100 to 150 (6.9-10.3) 200 (13.8)
Pneumatic Outputs
Full-scale Atmospheric Pressure Ranges
1, 5, 15, 30, 100, 150 psig
0.07, 0.35, 1.03, 2.07, 6.9, 10.34 BAR
Forward Flow Capacity 15 SCFM425 LPM
Exhaust Flow Capacity 7 SCFM198 LPMEnvironmental Operating Temperature 32-141F (0-60C)
Media-Wetted Materials Aluminum, copper alloys, nickel, buna-n, silicon, 316SS
Required Accessories 6-pin micro cordsetRecommended Accessories
DIN-rail Bracket, Panel Bracket, Power Supply, Control Knob, Remote Pressure Sensor, External Volume Booster
86 800.727.5646 www.marshbellofram.com
Ele
ctro
-Pn
eum
atic
s
Description
The Type 3212 single loop and 3222 double loop are non-bleeding electro-pneumatic controller with flows exceeding those of most compact standard industrial electronic regulators or I/P transduc-ers. The 3212/3222 offers analog monitoring of the output pressure by a 0-10 VDC signal. Many output pressures are available up to 150 PSI. Flows to 60 SCFM are possible from the compact Type 3212/3222 electronic controller with integrated booster relay. A reliable twin solenoid valve system, with an integral pressure sensor, controls pressures to an accuracy of .5%. Custom output ranges are available.
Applications include: Automotive, Industrial Machinery, Web Tension Control, and Tire Manufactur-ing and Testing.
Features
Closed Loop TechnologyIntegrated Air Volume BoosterCurrent/Voltage Command and Monitor SignalsCompact Unit with Flows up to 60 SCFM
Type 3212 & 3222Analog Weatherproof Regulators
Type 3212/3222 Analog Weatherproof Regulators
Type 3212/3222 Ordering Information
2 2 0 G 150 P 1
Number of Loops1 1 Loop2 2 Loop
2Logic Output
M CMOST TTLO Open-Collector
Analog Control SignalE 0-10VI 4-20mA
Lower Output Pressure
0 Lower Limit of Output PressurePressure Units
G PSIGUpper Output Pressure
150 Upper Limit of Output Pressure (PSIG)Mounting
P Pipe (in-line)Supply and Output Ports
0 1/4 NPT1 1/4 BSPT2 1/4 BSPP3 3/8 NPT4 3/8 BSPT5 3/8 BSPP
Connector1
Options00 None14 12 VDC supply
Type 3212 and 3222
Performance Full-Scale Accuracy 0.5%
Electrical Inputs
Supply Voltage 15-24VDC (12VDC option)
Stand by Supply Current 80 mA
Maximum Supply Current 325 mA
E/P Control 0-10V,10K OHMS
I/P Control 4-20 mA , 250 OHMS
2nd-loop Remote Sensor Feedback
T3222: 0-10V (4-20mA option)
Electrical Outputs
Monitor Output 0-10V
Logic Output CMOS, TTL, Open-Collector
Pneumatic Inputs
Supply Pressure
Max. Output PSIG (BAR) Max. Supply PSIG (BAR)
Up to 5 (.35) 20 (1.4)
>5 to 15 (.35-1.03) 30 (2.1)
>15 to 30 (1.03-2.1) 60 (4.1)
>30 to 100 (2.1-6.9) 165 (11.4)
>100 to 150 (6.9-10.3) 200 (13.8)
Pneumatic Outputs
Full-scale Atmospheric Pressure Ranges
1, 5, 15, 30, 100, 150, 300 PSIG
0.07, 0.35, 1.03, 2.07, 6.9, 10.34, 20.68 BAR
Forward Flow Capacity 60 SCFM (1700 LPM)
Exhaust Flow Capacity 15 SCFM (425 LPM)
Environmental
Operating Temperature 32-141F (0-60C)
Media-Wetted Materials Aluminum, copper alloys, nickel, buna-n, silicon, 316SS
Required Accessories 6-pin micro cordset
Recommended Accessories
DIN-rail Bracket, Panel Bracket, Power Supply, Control Knob, Remote Pressure Sensor, External Volume Booster
www.marshbellofram.com 800.727.5646 87
Ele
ctr
o-P
neum
ati
cs
Description
The T3215 High-Flow Pressure Controller utilizes reliable, quick-firing solenoids, an onboard pressure sensor, and a precision 180 scfm booster to achieve excellent accuracy and stability. There are many custom output ranges between 0 and 150 PSIG (1.0 MPa). The T3215 is CE-rated, weatherproof, and vibration-resistant. Analog electrical connections include control and monitor output. Mounting options include in-line and panel.
The T3215 is available with or without pressure monitor and logic outputs (6-pin or 4-pin micro connector, respectively). The T3215 is also available with a 6-pin DIN 43650 connector. Differential inputs mean problem-free integration with PLC grounding systems.
Type 3215Weatherproof Regulator with Super High Flow
Type 3215Weatherproof Regulators
Type 3215 Ordering Information215 0 G P 00
Logic OutputM CMOST TTLO Open-CollectorZ No Logic Output
Analog Control SignalE 0-10VI 4-20mA
Lower Output Pressure0 Lower Limit of Output Pressure
Pressure UnitsG PSIG
Upper Output Pressure030 30 PSIG100 100 PSIG150 150 PSIG
MountingP Pipe (in-line)
Supply and Output Ports3 3/8 NPT4 1/2 BSPT6 3/4 BSPP8 1 NPT
Connector1 Micro ConnectorD DIN 43650 Connector
Options00 None
Type 3215
Performance Full-Scale Accuracy 1.0%Electrical InputsSupply Voltage 15-24VDC (12VDC option)Stand by Supply Current 80 mAMaximum Supply Current 325 mAE/P Control 0-10V, 10K OHMSI/P Control 4-20 mA , 250 OHMSElectrical OutputsMonitor Output 0-10VLogic Output CMOS, TTL, Open-CollectorPneumatic Inputs
Supply Pressure
Max. Output PSIG (BAR) Max. Supply PSIG (BAR)Up to 5 (.35) 20 (1.4)
>5 to 15 (.35-1.03) 30 (2.1)>15 to 30 (1.03-2.1) 60 (4.1)>30 to 100 (2.1-6.9) 165 (11.4)
>100 to 150 (6.9-10.3) 200 (13.8)
Pneumatic OutputsFull-scale Atmospheric Pressure Ranges
30, 100, 150, PSIG2.07, 6.9, 10.34 BAR
Forward Flow Capacity 180 SCFM (5100 LPM)Exhaust Flow Capacity 30 SCFM (850 LPM)Environmental Operating Temperature 32-141F (0-60C)Media-Wetted Materials Aluminum, copper alloys, nickel, buna-n, silicon, 316SSRequired Accessories 4 or 6-pin micro cordset
Recommended Accessories Panel Bracket, Power Supply, Control Knob, External Volume Booster
Features
Single UnitIntegrated Controller and BoosterVery High Flow Volume BoosterGreater than
200 SCFMHigh Accuracy Control of Air PressureLow Air ConsumptionWeatherproof HousingShock Resistant, Position InsensitiveCE Approved
88 800.727.5646 www.marshbellofram.com
Ele
ctro
-Pn
eum
atic
s
Description
External Volume Boosters
External Volume Boosters
Volume Boosters increase the flow capacity of electro-pneumatic transducers, leading to faster response time and increased ability to remain at setpoint.
Low-flow transducers (T3210, T3220, T3510, and T3520) can be mounted on the volume booster of your choice. Simply add the boosters 2-letter code (from below) to the Options field of the T3000 part number.
The RPS sensor can be used with two-loop transducers (T3120, T322X, T3420, and T352X), closing the loop to the boosters output and increasing overall accuracy.
When the distance between transducer and volume booster is large (e.g., when the trans-ducer is mounted in a cabinet and the booster is installed directly at the application), one of the high-flow transducers (e.g., T3211 or T3512) can drive the booster over distance.
The X booster is the Marsh Bellofram Type 20EXHR. It utilizes two-stage technology to maintain setpoint over a wide range of flows
(Note: minimum output is 2 PSIG). The Z booster is the Marsh Bellofram Type 75HR. The N booster is the Marsh Bellofram Type 79. Consult the documentation for these products for more information.
The Q boosters are ultra-high flow boosters. The V booster can be used with vacuum ver-sions of the T3210, T3220, T3510, and T3520.
Flow capacities are for comparison purposes only. Forward flow is typically measured at 100 PSIG / 6.9 BAR supply and 80 PSIG / 5.5 BAR output. Exhaust flow is typically measured at 5-10 psig / 8.3-6.7 BAR above 20 PSIG setpoint.
External Volume Boosters
Part Number Marsh BelloframBooster
Supply andOutput PortSize (NPT)
Maximum Supply
(PSIG / BAR)
MaximumSignal and Output
(PSIG / BAR)
TypicalForward Flow
(SCFM / SLPM)
Typical Exhaust Flow
(SCFM / SLPM)
X2 T20 EX HRPg. 40
1/4 150 / 10.3 120 / 8.3 14 / 396 10 / 283
X3 3/8 150 / 10.3 120 / 8.3 14 / 396 10 / 283
Z2T75 HRPg. 42
1/4 250 / 17.2 150 / 10.3 40 / 1133 15 / 425
Z3 3/8 250 / 17.2 150 / 10.3 50 / 1416 15 / 425
Z4 1/2 250 / 17.2 150 / 10.3 50 / 1416 15 / 425
N3
T79Pg. 43
3/8 400 / 27.6 200 / 13.8 170 / 4814 31 / 878
N4 1/2 400 / 27.6 200 / 13.8 200 / 5664 31 / 878
N6 3/4 400 / 27.6 200 / 13.8 220 / 6230 31 / 878
N8 1 400 / 27.6 200 / 13.8 220 / 6230 31 / 878
Q6 3/4 300 / 20.7 160 / 11 550 / 15576 220 / 6230Q8 1 300 / 20.7 160 / 11 550 / 15576 220 / 6230QA 1-1/4 300 / 20.7 160 / 11 2200 / 62304 200 / 5664QB 1-1/2 300 / 20.7 160 / 11 2200 / 62304 200 / 5664QC 2 300 / 20.7 160 / 11 2200 / 62304 200 / 5664
V2 1/4 140 / 9.7 100 / 6.9 50 / 1416 6 / 170V3 3/8 140 / 9.7 100 / 6.9 50 / 1416 6 / 170
www.marshbellofram.com 800.727.5646 89
Ele
ctr
o-P
neum
ati
cs
Multiple User Interfaces
(See examples on these pages)
Analog interface (mA or voltage signal)Serial RS-485 (RS-232 and USB via convert-
ers) use our program or write your own, as several high tech customers have done! Control up to 24 addressable units on an RS485 link. The serial link permits custom-izing the factory settings to your needs.
Keypad /display: easily configure the trans-ducer to your needs
DeviceNet through serial communications link
Input and Output Settings
With keypad or serial communications, you can set almost any low and high end points (input/output points) within the range of the selected sensor. You are not limited to points on a linear zero to maximum span I/O plot as on other I/Ps and E/Ps. (For example, if your primary process settings require an output of 25 psi at 2 volts signal and 50 psi at 8.5 volts, you can choose those as your Cal-L and Cal-H points and the unit will be linear between those two settings. if you would like the reverse, then select 50 psi at 2 volts, and so forth.)
Capability to change PID settings to match your system requirements
Second loop feedback (from a remote sensor) available. Digital units permit user to add, delete, or scale the second loop signal.
Choices of circuit card mounted or weather-proof factory/field units
Very wide range of output pressures, includ-ing vacuum, absolute, and high pressures.
Monitor output signal options Resistant to vibration and changes in orientationMultiple mounting options
Features
Digital Electro- Pneumatic Transducers
Type 3400Circuit-Card RegulatorsElectrical Connections
Serial RS-485 ConnectionsDC PowerOptional Monitor Output, Analog
Setpoint and Remote Sensor Feedback
T3410S Panel Mount
Digital Circuit-Card Regulators
The compact Type 3410 (one-loop) and 3420 (two-loop) Circuit-Card Pressure Regulators are perfect for size-conscious OEMs, without sacri-ficing any of the high-end performance normally associated with full-size I/Ps.
The T3400 can be controlled digitally or with industry-standard analog control signals (0-10V or 4-20mA). Industry-standard analog monitor output signals (0-10V or 4-20mA optional) are available for user-monitoring of actual output pressure.
Keypad/Display Interface
Selection include: input signal, minimum and maximum input signal/output values, units in the display, second loop feedback signal set-tings, deadband, and proportional gain factor.
A CD with the user manual and a program to configure and control the serial units is included with all digital units, including those with keypad. A small adapter cable is included to permit removal of the keypad to connect to a computer PID settings and other functions not available through the keypad. In effect, this permits serial communications with the keypad removed.
Analog Interface
Type 3500Digital Weatherproof
Regulators with Keypad
90 800.727.5646 www.marshbellofram.com
Ele
ctro
-Pn
eum
atic
s
Device Net Board
Serial to DeviceNet BridgeDeviceNet Connections
Type 3410SType 3410D
(Din Tray Mount Shown)
Digital User InterfacesType 3000 Serial RS-485 User Interfaces
Type 3500Digital Weatherproof Regulator
with Serial Interface
Serial RS-485 User Interface
(RS-232 and USB via converters)
User connection to the T3500 serial interface is made via the 4-pin connector near the top of the product. The 4N cordset is a required accessory.
User connection to the T3400 serial interface is made via the products terminal block.
Serial Interface Analog Interface
The T3500D DeviceNet cap communicates with its Base through a Serial Communications link. The 5P cordset is a required accessory. DeviceNet communication with the T3500D includes Send Setpoint and Get Actual Pressure. The EDS file and Device Profile are available upon request.
DeviceNet Connection
(5-pin micro-style connector)
Power Supplied by DeviceNet busVoltage: 11 to 25 VDCCurrent: 70 mA at 12 VDC (nominal)
Base Power
(6-pin micro-style connector)
Must be supplied by userVoltage: 24VDC (+/-1VDC) - (15VDC
optional)Current: 375 mA maximum
Network Specifics
Compatibility: Group 2 Server Only, not UCMM capable.
Baud Rates: 125 Kbaud, 250 Kbaud, and 500 Kbaud.
Bus Interface: Phillips 82C250; mis-wiring protection per DeviceNet Vol. I Sec 10.2.2.
DeviceNet
Node Isolation: Bus powered, optically isolated node.
Bus Connection: Micro connector per DeviceNet Volume I Appendix C-5.
FactoryDefaults:Baudrate=125Kbaud.MACID=63.
Device Type: 0 (Generic)Device Profile: DeviceNet Specification
(Volumes I and II of version 2.0).Device Configuration: No DeviceNet
configuration is supported.Status LEDs: Network Status (NS)
and Module Status (MS) LEDs are provided.
www.marshbellofram.com 800.727.5646 91
Ele
ctr
o-P
neum
ati
cs
Description
The compact Type 3410 (one-loop) and 3420 (two-loop) Circuit-Card Pressure Regulators are perfect for size-conscious OEMs, without sacrificing any of the high-end performance normally associated with full-size I/Ps.
The T3400 is available with either of two user interfaces: the T3400S with serial interface or the T3400D with DeviceNet interface. The T3400D consists of the T3400S plus a sister board for DeviceNet functions.
The T3400 can be controlled digitally (via the serial or DeviceNet interfaces) or with industry stan-dard analog control signals (0-10V or 4-20mA). Industry-standard analog monitor output signals (0-10V or 4-20mA optional) are available for user-monitoring of actual output pressure.
Features
Small FootprintSerial or DeviceNet InterfaceDigital or Analog InputsAnalog Monitor OutputSingle Loop and Dual Loop Control
Type 3410 & 3420 Digital Circuit-Card Regulators
Type 3410/3420 Digital Circuit-Card Regulators
Type 3410 and 3420 Ordering Information
4 0 0 600 0
Loops1 1 loop2 2 loops
0Digital Interface
S Serial RS-485 (RS-232 and USB via converters)D DeviceNet
Analog Control SignalE 0-10VI 4-20mA
Lower Output Pressure0 Lower Limit of Output Pressure
Pressure UnitsG PSIGA PSIG AbsoluteV VacuumW Inches of Water Column
Upper Output Pressure600 Upper Limit of Output Pressure
MountingD DIN trayP Panel Mount
M Manifold-Mount (150 PSIG/ 16.3 BAR max output)Supply and Output Ports
0 1/8 NPT1 1/8 BSPT2 1/8 BSPP
Options00 None15 15VDC Supply
* Type 3400 DeviceNet D mounting, Type 3400S and DeviceNet board installed in a single extended DIN tray. 'P' or 'M' mounting, DeviceNet board is supplied with 4 screws and stand-offs for panel mounting.
Type 3410 and 3420
Performance Full-Scale Accuracy 0.5%Electrical InputsSupply Voltage 24VDC (optional 15VDC)Stand by Supply Current 80 mAMaximum Supply Current 250 mASupply Pressure
Atmospheric Pressure Ranges
1, 5, 15, 30, 100, 150, 300, 500 PSIG
0.07, 0.35, 1.03, 2.07, 6.9, 10.34, 20.68, 34.47, 68.95 BAR
Vacuum Pressure Ranges 30" Hg, 150 PSIA (2.1 BAR, 10.3 BAR)Forward Flow Capacity 1.25 SCFM (35.4 LPM)Exhaust Flow Capacity 1.25 SCFM (35.4 LPM)
Analog Setpoint Control 0-5V, 0-10V, 4-20mA*Digital Setpoint Control 0-100%fullscale(installedsensor=100%)Digital Communications Serial RS-485 interface
Serial Address Addresses a-z available (except p and q reserved). 'r' default*
Loop Options Regulate 1st loop (onboard sensor) or 2nd loop (remote sensor)
Remote Sensor Feedback 0-10V, 0-5V, 4-20 mA, (Forward and Reverse Acting)*
Analog Output Source Follow Setpoint, Output Pressure, or Remote Sensor*
Analog Output Range 0-10V, 0-5V*
EnvironmentalOperating Temperature 32-141F (0-60C)
Media-Wetted Materials Aluminum, copper alloys, nickel, buna-n, silicon, 316SS
* Selectable and configurable via Serial or DeviceNet Interface
92 800.727.5646 www.marshbellofram.com
Ele
ctro
-Pn
eum
atic
s
Description
The Type 3411 Circuit Card Pressure Regulator regulates air pressure in proportion to an analog electrical signal (AUTO) or via an over-ride thumbwheel (MANUAL). The 3411 utilizes a unique patent-pending LEARN mode to characterize the users specific downstream load. Quiet Valve Operation produces crisp accurate regulation without the chattering noise typical of other solenoid-valve-based products.
The Type 3411 is specifically designed for use with spring-return air-duct cylinders in the Heat-ing, Ventilating, and Air Conditioning (HVAC) industries. Any application involving single-acting cylinders, valves, or bladders may benefit from the unique advanced features of this product. These include Vent Hood Control, Damper Control, Instrumentation, and Medical Applications. At just 2.1" / 51mm by 2.8" / 71mm with a height of 1.3" / 33mm, the 3411 is ideal for OEMs and other space-conscious customers.
Features
Mounting DIN Tray, Panel, or Multi-Unit ManifoldZero Air Consumption at steady stateFailure Mode upon loss of power: Lock-in-Place or To-AtmosphereAvailable with snap tracks, barbed air fittings, and pressure gaugesQuiet Valve OperationAUTO / MANUAL / LEARN Modes
Type 3411 Digital Circuit-Card Pressure Regulators
Type 3411 Digital Circuit-Card Pressure Regulators
Type 3411 Ordering Information
411 Z 0 G 0 0
Logic Output
Z No Logic Output
Analog Control Signal
E 0-10VI 4-20mA
Lower Output Pressure0 Lower Limit of Output Pressure
Pressure Units
G PSIG
Upper Limit Output Pressure
015 15 PSIG030 30 PSIG
Mounting
D DIN tray
P Panel Mount
M Manifold-Mount (150 PSIG maximum output)Supply and Output Ports
0 1/8 NPT1 1/8 BSPT2 1/8 BSPP
Connector0 Terminal Block
Options00 None
03 Fail Safe (to atmosphere)
Type 3411
Performance Full-Scale Accuracy 1.0%
Electrical Inputs
Supply Voltage 24VDC, 24 VAC
Stand by Supply Current 80 mA
Maximum Supply Current 120 mA
E/P Control 0-10V, 15K OHMS
I/P Control 4-20 mA , 250 OHMS
Electrical Outputs
Monitor Output 0-10V, 0-5V
Pneumatic Inputs
For outputs 15 PSIG 30 PSIGFor outputs > 15 PSIG 60 PSIG
Pneumatic Outputs
Full-scale Atmospheric Pressure Ranges
15, 30 PSIG(1.0, 2.1 BAR)
Forward Flow Capacity 1.25 SCFM(35.4 LPM)
Exhaust Flow Capacity 1.25 SCFM(35.4 LPM)
Environmental
Operating Temperature 32-141F (0-60C)
Media-Wetted Materials Aluminum, copper alloys, nickel, buna-n, silicon, 316SS
Recommended Accessories
Manifold, Power Supply, Control Knob, External Volume Booster, Snap Track, Barbed Air Fittings, Gauge
www.marshbellofram.com 800.727.5646 93
Ele
ctr
o-P
neum
ati
cs
Description
The Type 3510 single and 3520 double loop electro-pneumatic servo pressure controllers combine the advantages of reliable solenoid valves and digital control. Available with a local keypad programming option or RS-485 Digital Communications for PLC or PC control. The digital pressure controller is one of the most precise, accurate, and reliable devices available in the industry today, by giving the user the ability to set and extract data directly from the transducer with a PC or automation system. With a forward flow of 1.25 SCFM at 100 PSI, the 3510/3520 can be used alone for many applications or combined with a volume booster for flows in excess of 2,000 SCFM. Many output ranges are available, from 29" Hg vacuum to 600 PSIG. Standard accuracy is 0.5% FS or better. A four digit display of the output pressure is available with the keypad model.
Applications include: Gripper Control, Welding Operations, Actuator Control, Machinery Automation, Precision Robotics, Tire Production and Testing, Web Tension, Semiconductor Equipment, and Molding and Forming Operations.
Features
Digital DisplaySerial or DeviceNet InterfaceDigital or Analog InputsAnalog Monitor OutputSingle Loop and Dual Loop ControlForward Flow 1.25 SCFM at 100 PSIWeather Proof Housing
Type 3510 & 3520 Digital Weatherproof Regulators
Type 3510/3520 Digital Weatherproof Regulators
Type 3510 and 3520 Ordering Information5 0 0 600 P 1
Loops1 1 loop2 2 loops
0Digital Interface
S Serial RS-485 (RS-232 and USB via converters)P Keypad/display programmerD DeviceNet
Analog Control SignalE 0-10VI 4-20mA
Lower Output Pressure0 Lower Limit of Output Pressure (PSIG)
Pressure UnitsG PSIGA PSIG AbsoluteV VacuumW Inches of Water Column
Upper Output Pressure600 Upper Limit of Output Pressure
MountingP Pipe Mount
Supply and Output Ports0 1/8 NPT1 1/8 BSPT2 1/8 BSPP
1Options
00 None15 15VDC Supply
_ _External Volume Booster: X2, X3, Z2, Z3, Z4, N3, N4, N6, N8, Q6, Q8, QA, QB, QC, V2, V3: see chart on page 88
Type 3510/3520
Performance Full-Scale Accuracy 0.5%Electrical InputsSupply Voltage 24VDC (optional 15VDC)Stand by Supply Current 80 mAMaximum Supply Current 325 mASupply Pressure
Max. Output PSIG (BAR) Max. Supply PSIG (BAR)
Up to 5 (.35) 20 (1.4)
>5 to 15 (.35-1.0) 30 (2.1)
>15 to 30 (1.0-2.1) 60 (4.1)
> 30 to 100 (2.1-6.9) 165 (11.4)
>100 to 150 (6.9-10.3) 200 (13.8)
>150 to 300 (10.3-20.7) 350 (24.1)
>300 to 600 (20.7-41.4) 650 (44.8)
Outputs
Atmospheric Pressure Ranges
1, 5, 15, 30, 100, 150, 300, 500, 600 PSIG
0.07, 0.35, 1.03, 2.07, 6.9, 10.34, 20.68, 34.47, 68.95 BAR
Vacuum Pressure Ranges 30" Hg, 150 PSIA (2.1 bar, 10.3 bar)Forward Flow Capacity 1.25 SCFM (425 LPM)Exhaust Flow Capacity 1.25 SCFM (198 LPM)Analog Setpoint Control 0-5V, 0-10V, 4-20mADigital Setpoint Control 0-100%fullscale(installedsensor=100%)Digital Communications Serial RS-485 interface
Serial AddressAddresses a-z available (except p and q reserved).
'r' default selectable and configurable via Serial or Keypad Display Interface
Loop Options Regulate first loop (onboard sensor) or 2nd loop (remote sensor)Remote Sensor Feedback 0-10V, 0-5V, 4-20 mA, (Forward and Reverse Acting)Analog Output Source Follow Setpoint, Output Pressure, or Remote SensorAnalog Output Range 0-10V, 0-5VEnvironmentalOperating Temperature 32-141F (0-60C)
Media-Wetted Materials Aluminum, copper alloys, nickel, buna-n, silicon, 316SS
94 800.727.5646 www.marshbellofram.com
Ele
ctro
-Pn
eum
atic
s
Description
The 3511 offers solenoid valve technology with forward flow equivalent to standard industrial electronic regulators or I/P transducers. Available with local keypad programming option or RS-485 Digital Communications for PLC or PC control. Dual solenoid valves with internal pressure sensor and advanced microprocessor control. A built-in air volume booster provides the 3511 with forward flow up to 17 SCFM. Proportional - Integral - Derivative (PID) control. Ranges from 0 to 150 PSIG. Reverse flow (exhaust) of up to 7 SCFM. The double loop (3521) option permits 0-10 VDC feedback from a remote sensor. The keypad is available with a four digit display of the output pressure.
Applications include: Gripper Control, Welding Operations, Actuator Control, Machinery Automation, Precision Robotics, Tire Production and Testing, Web Tension Semiconductor Equipment and Mold-ing and Forming Operations.
Features
Serial or DeviceNet InterfaceDigital or Analog InputsAnalog Monitor OutputSingle Loop and Dual Loop ControlForward Flow up to 17 SCFMDigital DisplayWeather Proof Housing
Type 3511 & 3521 Digital Weatherproof Regulators
Type 3511/3521 Digital Weatherproof Regulators
Type 3511/3521
Performance Full-Scale Accuracy 0.5%
Electrical Inputs
Supply Voltage 24VDC (optional 15VDC)
Stand by Supply Current 80 mA
Maximum Supply Current 325 mA
Supply PressureMax. Output PSIG (BAR) Max. Supply PSIG (BAR)
Up to 5 (.35) 20 (1.4)
>5 to 15 (.35-1.0) 30 (2.1)
>15 to 30 (1.0-2.1) 60 (4.1)
> 30 to 100 (2.1-6.9) 165 (11.4)
>100 to 150 (6.9-10.3) 200 (13.8)
Outputs
Atmospheric Pressure Ranges
5, 15, 30, 100, 150 PSIG
0.35, 1.03, 2.07, 6.9, 10.34 BAR
Forward Flow Capacity 15 SCFM (425 LPM)
Exhaust Flow Capacity 7 SCFM (198 LPM)
Analog Setpoint Control 0-5V, 0-10V, 4-20mA
Digital Setpoint Control 0-100%fullscale(installedsensor=100%)
Digital Communications Serial RS-485 interface
Serial AddressAddresses a-z available (except p and q reserved).
'r' default selectable and configurable via Serial or Keypad Display Interface
Loop Options Regulate first loop (onboard sensor) or 2nd loop (remote sensor)
Remote Sensor Feedback 0-10V, 0-5V, 4-20 mA, (Forward and Reverse Acting)
Analog Output Source Follow Setpoint, Output Pressure, or Remote Sensor
Analog Output Range 0-10V, 0-5V
Environmental
Operating Temperature 32-141F (0-60C)
Media-Wetted Materials Aluminum, copper alloys, nickel, buna-n, silicon, 316SS
Type 3511 and 3521 Ordering Information5 1 0 150 P 1
Loops1 1 loop2 2 loops
1Digital Interface
S Serial RS-485 (RS-232 and USB via converters)P Keypad/display programmerD DeviceNet
Analog Control SignalE 0-10VI 4-20mA
Lower Output Pressure0 Lower Limit of Output Pressure
Pressure UnitsG PSIGW Inches of Water Column
Upper Output Pressure150 Upper Limit of Output Pressure
Mounting*
P Pipe MountM Manifold-Mount
Supply and Output Ports0 1/4 NPT1 1/4 BSPT2 1/4 BSPP
1Options
00 None15 15VDC Supply
*Order panel bracket and DIN rail clip separately. For Manifold-Mount (no threads), specify 0 for Supply and Output Ports.
www.marshbellofram.com 800.727.5646 95
Ele
ctr
o-P
neum
ati
cs
Description
The Type 3512 single loop and 3522 double loop are single units - integrated controller and booster. The 3512/3522 offers solenoid valve technology with forward flow exceeding those of most stan-dard industrial electronic regulators or I/P transducers. Available with a local keypad programming option or RS-485 digital communications for PLC or PC control. Many output pressure ranges are available up to 150 PSI. With a reliable twin solenoid valve system, and an integral pressure sen-sor, an accuracy of 0.5% is obtainable.
Applications include; Gripper Control, Welding Operations, Actuator Control, Machinery Automation, Precision Robotics, Web Tension, Semiconductor Equipment, Molding and Forming Operations and Tire Manufacturing and Testing.
Features
Serial or DeviceNet InterfaceDigital or Analog InputsAnalog Monitor OutputSingle Loop and Dual Loop ControlForward Flow up to 60 SCFMDigital Display
Type 3512 & 3522 Digital Weatherproof Regulators
Type 3512/3522 Digital Weatherproof Regulators
Type 3512/3522
Performance Full-Scale Accuracy 0.5%
Electrical Inputs
Supply Voltage 24VDC (optional 15VDC)
Stand by Supply Current 80 mA
Maximum Supply Current 325 mA
Supply PressureMax. Output PSIG (BAR) Max. Supply PSIG (BAR)
Up to 5 (.35) 20 (1.4)
>5 to 15 (.35-1.0) 30 (2.1)
>15 to 30 (1.0-2.1) 60 (4.1)
> 30 to 100 (2.1-6.9) 165 (11.4)
>100 to 150 (6.9-10.3) 200 (13.8)
Outputs
Atmospheric Pressure Ranges
5, 15, 30, 100, 150 PSIG
0.35, 1.03, 2.07, 6.9, 10.34 BAR
Forward Flow Capacity 60 SCFM (1700 LPM)
Exhaust Flow Capacity 15 SCFM (425 LPM)
Analog Setpoint Control 0-5V, 0-10V, 4-20mA
Digital Setpoint Control 0-100%fullscale(installedsensor=100%)
Digital Communications Serial RS-485 interface
Serial AddressAddresses a-z available (except p and q reserved).
'r' default selectable and configurable via Serial or Keypad Display Interface
Loop Options Regulate first loop (onboard sensor) or 2nd loop (remote sensor)
Remote Sensor Feedback 0-10V, 0-5V, 4-20 mA, (Forward and Reverse Acting)
Analog Output Source Follow Setpoint, Output Pressure, or Remote Sensor
Analog Output Range 0-10V, 0-5V
Environmental
Operating Temperature 32-141F (0-60C)
Media-Wetted Materials Aluminum, copper alloys, nickel, buna-n, silicon, 316SS
Type 3512 and 3522 Ordering Information5 2 0 150 P 1
Loops1 1 loop2 2 loops
2Digital Interface
S Serial RS-485 (RS-232 and USB via converters)P Keypad/display programmerD DeviceNet
Analog Control SignalE 0-10VI 4-20 mA
Lower Output Pressure0 Lower Limit of Output Pressure
Pressure UnitsG PSIG
Upper Output Pressure150 Upper Limit of Output Pressure
MountingP Pipe Mount
Supply and Output Ports0 1/4 NPT1 1/4 BSPT2 1/4 BSPP3 3/8 NPT4 3/8 BSPT5 3/8 BSPP
1Options
00 None15 15 VDC Supply
96 800.727.5646 www.marshbellofram.com
Ele
ctro
-Pn
eum
atic
s
Dimensional Drawings
(3100, 3400) DustCover=157-201-01
DIN Tray Mount Panel Mount
Manifold Mount
(3100, 3400)
High-Pressure Units (>300 PSIG) T3111, 3410 and 3420 Flush Panel Mount T3100, T3111
High Pressure (>300 PSIG / 20.7 BAR) units
(3100, 3400)
2.363.900
.601
3.540
2.210
3.321
2.363.900
.601
3.540
2.210
3.321
www.marshbellofram.com 800.727.5646 97
Ele
ctr
o-P
neum
ati
cs
Type 3100 and 3400 Series Manifold Block ( 7 Station Manifold Shown)
( 7 station manifold shown)
Manifolds are available in 2 to 10 stations. To calculate the overall length L of the manifold use the following formula:
L=2X1.16+(S-1)X1.224
WhereS=thenumberofmanifold stations
EXAMPLE: 7 Station Manifold:
L=2X1.16+(7-1)X1.224
L=9.664in.[245.47mm]
Circuit Board Regulators Mounting and PackagingMounting Product Configuration Accessories
DIN Tray Product mounted in DIN Tray None
Panel Product configured for panel mountingFor flush mounting, order Flush Mount Bracket
(161-520-00) separately
Multi-Unit Manifold Product configured for multi-unit manifold mountingOrder Multi-Unit Manifold (350-110-XX) separately.
XX=#stations.
.320 [8.13]
2.880 [73.15]
1.250 [31.75]
5.305 [134.75]
Weatherproof Regulator Mounting Options
The Type 3200 and 3500 regulators can be mounted in-line or by brackets which are available separately (DIN-rail bracket 010-115-000; Panel bracket 010-135-000). Bracket mounting holes (2 X 8-32 UNC 2B X 0.375"/9.5mm deep minimum) are available on the rear and right faces (when looking at product with IN/OUT flow from left to right) and also on the bottom of the medium-flow booster (shown in diagram).
2.25"57mm
0.54"14mm
2.25"57mm
0.375" TYP
3.46"88mm*
0.63716mm
0.285"7mm
SUPPLY PORT1/8-27 NPT
EXHAUST PORT1032 UNF2B
* High Pressure (>300 PSIG / 20.7BAR) & DeviceNet units are 5.00" / 127mm tall.
DUAL OUTPUT PORTS1/8-27" NPT (Rear) &1/4" NPT (Bottom)
Low-Flow Weatherproof T3210, T3220, T3510, T3520
98 800.727.5646 www.marshbellofram.com
Ele
ctro
-Pn
eum
atic
s
Medium-Flow Weatherproof T3211, T3221, 3511, 3521 Manifold Mount T3211, T3221, 3511, 3521
High -Flow Weatherproof T3212, T3222
www.marshbellofram.com 800.727.5646 99
Ele
ctr
o-P
neum
ati
cs
Sensor Wiring Diagrams
OE10
4120 Model
Description
The RPS is designed for connection to the T3000s 2nd loop input. When used to monitor pressure at the output of an external volume booster, or directly at the users remote application, the RPS sensor increases overall accuracy and speed of response to downstream changes.
Pressure ranges from vacuum to 1000 PSIG / 69 BAR are available. RPS outputs (0-10V or 4-20 mA) are field-adjustable. 4-20 mA versions require 12-24 VDC external power, while 0-10V ver-sions require 15-24 VDC. The RPS weatherproof housing is 1.8" / 46mm wide X 2.6" / 66mm tall (for pressures above 300 PSIG / 20.7 BAR, extended height housing is required). The RPS can be directly mounted to the application with its male 1/4 NPT pneumatic connection, or with the SPC-MB1 bracket (available separately).
Temperature range is 0-50C.
Part Numbers: RPS 0GXXX YYYY ZZ XXX=upperendofpressurerange(e.g.,030for30PSIG)*
YYYY=electricaloutput(0E10for0-10Vor4I20for4-20mA)
ZZ=lengthofwiring(Wfor3'orW6for6')
*Full scale ranges: 1, 5, 15, 30, 100, 150, 300, 500, 1000 PSIG 0.07, 0.3, 1.0, 2.1, 6.9, 10.3, 20.7, 34.5, 69 BAR Vacuum (29" Hg)
Remote Pressure Sensors (RPS)
Cable Applications
RPS Remote Pressure Sensor
100 800.727.5646 www.marshbellofram.com
Ele
ctro
-Pn
eum
atic
s
DC Power and Analog I/O
Required on all T3200 and T3500 transducers. Single-ended cordset with 6-pin female M12 micro-style connector.
Length of Wiring Part Number3' (0.9m) 122-004-086' (1.83m) 122-004-0912' (3.66m) 122-004-1020' (6.10m) 122-004-11
DC Power and Analog I/O
Required on Z-option Type 3215.
Single-ended cordset with 4-pin female M12 micro-style connector.
Length of Wiring Part Number3' (0.9m) 122-004-046' (1.83m) 122-004-0512' (3.66m) 122-004-0620' (6.10m) 122-004-07
Cordsets
Cordsets
Serial RS-485
Required on all T3500 Serial RS-485 transducers.
Single-ended cordset with 4-pin female nano-style connector.
Length of Wiring Part Number6.5' (2m) 122-000-0016.5' (5m) 122-000-01
DeviceNet
Required on all T3500 DeviceNet transducers. Single-ended cordset with 5-pin female M12 micro-style connector.
Length of Wiring Part Number3' (0.9m) 160-560-0116.5' (5m) 122-000-01
Converters RS-232 Converter
Converts T3400/T3500 Serial RS-485 interface to RS-232. Part Number: 160-700-00.
USB Converter
Used in combination with RS-232 Converter, allows connection of T3400 or T3500 Serial to USB port. Part Number: 160-710-00
A pair of 15VDC circuit-card power supplies is available for integration of Type 3000 transduc-ers into 120VAC systems. The ZMS-JR powers a single Type 3000; the ZMS15-2 powers up to two. In addition, the ZMS15-2 can control a pair of Type 3000 transducers with 0-10V when combined with the P1 Control Knob.
The ZMSJR is rated at 375 mA maximum output; the ZMS15-2 at 750mA. Connections are made via removable terminal blocks. Both power supplies are short circuit protected, and mounted in trays for easy DIN rail mounting. The ZMSJR (without DIN tray) can also be
standoff mounted. AC power cords are included. The ZMS-JR has a 3.6" / 91mm X 3.1" / 79mm footprint and is 2.6" / 66mm high when mounted in its DIN tray; the ZMS15-2 is 5.4" / 137mm X 3.1" / 79mm and 2.7" / 69mm.
Part Number
ZMSJR Powers one Type 3000 501-200-04
ZMS15-2 Powers and Controls two T3000s 501-200-00
P1-3 Control Knob with 3' (0.91m) wiring 504-100-00
P1-6 Control Knob with 6' (1.83m) wiring 504-100-01
P1-12 Control Knob with 12' (3.66m) wiring 504-100-02
Power Supplies & Control Knobs
Converters
www.marshbellofram.com 800.727.5646 101
Ele
ctr
o-P
neum
ati
cs
Applications Doctor Blade Control
Doctor blades are used through-out the paper process to remove water and contaminants from the roll. The use of a double-acting cylinder (or bladders or bellows) on each end of the roll, with two T3512s controlling the position of each cylinder, increases the positioning accuracy of the doctor blade.
Web Tension
A web-tensioning system serves as a kind of shock absorber, keeping the web at the same tension no matter what the roll size. The T3522 utilizes closed-loop feedback from the dancer arm, to adjust pressure delivered to the pneumatic brake, keep the dancer arm at the desired position, and maintain the desired web tension. The two-loop capability of the T3522 frees up the Controller for other tasks.
PNEUMATIC BRAKE
WEBDANCER ARM
POTENTIOMETERREGULATEDPRESSURE
T3522
0-10V
CONTROLLER
Web Caliper (Thickness)
In the calendar section of the paper machine, the T3512 regulates pressure delivered to an air cylinder (or bladder or bellows) to regulate the thickness of the paper. The calendar section consists of calendar stacks with a reel de-vice for winding the paper onto a reel as it leaves the machine. The calendar finishes the paper by smoothing it to the desired finish, thickness, or gloss.
Tire Molding
During the vulcanization stage of tire making, a green tire is molded into a finished tire ready for testing, inspection, and shipment. Tight control of pressure and temperature is absolutely critical to the making of high-quality tires. This requires valves for steam, cold water, and air pressure, as well as devices to monitor pressure and temperature. In the illustration, the T3510P I/P is mounted in the cabinet with the PLC, to locate all the electronics in a single location. The T79V volume booster provides the flow capacity to open and close the valve rapidly, as well as a tunable integral needle valve to provide stable operation.
Other products used in tire molding include filter-regulators (T51), regulators (T70 and T78), and Positive-Bias Relays (T72).
PLC
STEAM ORCOLD WATER TO MOLD
SENSOR(PRESSURE ORTEMPERATURE)
T79VVOLUMEBOOSTER
T3510P
VALVEVULCANIZATION
Valve Control
Valves are used throughout the paper-making process to control the flow of water, steam, pulp, and chemicals. Valves are found in Water Treatment facilities (both incoming and outgoing), as well as Power Generation facili-ties. Some paper mills install steam-shower valves after the dryer section to control paper curl.
Valves can be actuated by Valve Positioners, I/P Electro-Pneumatic Transduc-ers, or both. In the example below, the Type 3210 is used to regulate the amount of water (or other fluid) passing through a valve. The T3210 receives a control signal from a Programmable Logic Controller and regulates the speed and position of the valve actuator. The T79V Volume Booster increases valve opening/closing speed by increasing dramatically the amount of compressed air being fed to the actuator. Other products used in valve control include Filter-Regulators (T50 and T51), Regulators (T70), Positive-Bias Relays (T72), P/I Transducers (T5000), and pressure gauges.
102 800.727.5646 www.marshbellofram.com
Ele
ctro
-Pn
eum
atic
s
Edge-Guiding and Web-Break Detection
The Controller uses feedback from an infrared edge detector to control horizontal web position. The T3512 controls the extension of a cylinder (or bladder or bellows) which moves the web from side to side. In the event of a web break, the output of the edge detector signals the Controller to begin remedial action. The T1000 (or T1500) supplies a steady stream of air to keep the edge detectors sensing elements free of contamination.
Edge Guiding
Using a Web Sensor and Type 3221
As the web position varies, the web sensor detects the change and feeds a signal back to the Type 3221 Pressure Controller. The Type 3221 then applies pressure to the cylinder to compensate for the shift in web position. The ZMS15-2 Power Supply provides both the command signal and the supply voltage that sets the initial web position while allowing for adjustments.
Sidewall Grinding
Using the Type 3212
A Type 3212 provides pressure control in a tire sidewall grinding application. A command signal is channeled through a ZMS15-2 Power Supply which feeds the command signal as well as the 15 volts DC supply voltage to the Type 3212. A gauge monitors the downstream pressure of the Type 3212, with a relief valve to protect against over pressurization.
CommandSignal
110 VAC
ZMS15-2
SidewallGrinder
T-3212
Supply
ReliefValve
ProcessGauge
Tire Testing
Most manufacturers run finished tires through a battery of tests and inspec-tions. To minimize total testing time, multiple tires must be inflated and deflated very rapidly, with pressure held constant during the testing.
In the illustrated example, the PLC begins the test by sending a setpoint to the T3220 electronic pressure controller. The T20 pre-amplifies the flow of the T3220, to provide tight responsive control of pressure delivered to the High Flow Booster. The T3220 and T20 can be ordered as a single integrated unit.
The High Flow Booster is selected based on the size and number of tires to be tested. Marsh Bellofram has a full range of flow boosters up to 2" port size and 2000 SCFM / 56640 SLPM.
In order to maintain the highest accuracy, the RPS pressure sensor is mounted close to the tire. The T3220s two-loop capability allows it to close the loop with the downstream sensor, freeing up the PLC for other things.
TIRE TESTINGMACHINE
PLCOR
CONTROLLER
RPS PRESSURE SENSOR
QRCHIGH FLOWBOOSTER
T20PRECISION
FLOW BOOSTER
T3220I/P
Hot Stamping Force Control
Using the Type 3211
The Type 3211 pressure controller applies pressure to the cylinder to develop a force for the hot stamping operation. In this configuration, the ZMS15-2 Power Supply provides both the command signal and supply voltage neces-sary to control the Type 3211. A programmable controller may also supply this command signal.
www.marshbellofram.com 800.727.5646 103
Ele
ctr
o-P
neum
ati
cs
Air Over Oil Speed Control
Using the Type 3211
The Type 3211 varies the cylinder speed by varying the pressure in the air over oil tanks. The ZMS15-2 Power Supply provides both the command signal and the supply voltage to the Type 3211. The output pressure, through a directional control valve, controls the speed at which the cylinder extends and retracts.
Adhesive Dispensing
Using the Type 3511
The Type 3511 pressure controller, after receiving its signal from the PLC, applies air pressure to the glue pot. This in turn controls the glue pressure and flow to the automatic glue dispensing machine. A sensor in the auto-matic glue dispensing machine provides feedback to the PLC for fine tuning of the application.
Surface Winding Control
Using the Type 3110
As the roll diameter and the cylinder position change, the feedback arm moves the rotary potentiometer. This rotary potentiometer output changes the regulated output pressure of the Type 3110 to control the pressure to the surface wind cylinder.
Surface Mount Force Control
Using the Type 3210
The Type 3210 Pressure Controller can provide precise control of force for automated placement of surface mount ICs. In this application, an SMD Machine Controller sets the pressure for each chip placement.
Electronic Control of Vacuum Through Pressure
Using the Type 3210
The Type 3210 can be calibrated to operate in both the vacuum and pressure ranges. The ZMS15-2 Power Supply provides the Type 3210 with the com-mand signal and supply voltage. Supply pressure is routed to both the vacu-um generator and the Type 3210 with an on-off switch in front of the vacuum generator. The Type 3210 then can regulate both vacuum and pressure to the chamber. A compound gauge monitors the pressure in the chamber.
104 800.727.5646 www.marshbellofram.com
Ele
ctro
-Pn
eum
atic
s
Electronic Control of Vacuum
Using a Type 3110
The Type 3110 is used to control pressure to a vacuum process chamber. A control potentiometer channels the command signal through a ZMS15-2 Power Supply to operate the Type 3110. A vacuum gauge is used to monitor the regulated vacuum from the Type 3110.
Automated Pressure Switch Calibrator
Using a Type 3510
The Type 3110 is used to control pressure to a vacuum process chamber. A control potentiometer channels the command signal through a ZMS15-2 Power Supply to operate the Type 3110. A vacuum gauge is used to monitor the regulated vacuum from the Type 3110.
Liquid Level Control
Using the Type 3521
The ultrasonic sensor provides feedback to the Type 3521 for controlling the liquid level of an ink tank. The liquid level setpoint is controlled by the PLC by varying the command signal to the Type 3521.
Clamping Force Control
Using the Type 3510
This circuit provides an adjustable control of clamping force that is directly proportional to the tension of the material being stretched by the servo motor. The initial clamping pressure is set by the process controller and as the servo motor applies tension to the material being tested, the load cells output signal commands the Type 3510 pressure controller to increase the clamping force.
Control of High Flow, Low Pressure
Using the Type 3220
This circuit provides an adjustable control of clamping force that is directly proportional to the tension of the material being stretched by the servo motor. The initial clamping pressure is set by the process controller and as the servo motor applies tension to the material being tested, the load cells output signal commands the Type 3510 pressure controller to increase the clamping force.