    Model H (SIN R5012)Early SuppressionFast Response Sprinkler

    Product Description

    The Reliable Model H Early Suppression FastResponse (ESFR) Sprinkler is intended for use againstsevere fire challenges. This sprinkler is designed torespond quickly to growing fires and will deliver aheavy water discharge to “suppress” rather than“control” fires.

    The ModelH Sprinkler utilizes a 2.5 mm glass bulb ineither the 155°F (68C), 200°F (93C), or 286°F(141C) ratings. The sprinkler has a Nominal K Factor

    of 14.0 (metric 200) and will deliver approximately 100gpm (397 L/min) of water at 50 psi (3,4 bar).

    The deflector and frame provide a broad, verysymmetrical, hemispherical pattern capable ofsuppressing fires between sprinklers in high storageheight areas and at the same time retaining a highmomentum central core to penetrate and suppressfires occurring directly beneath the sprinkler in lowstorage height areas.

    Model H ESFR Sprinkler

     Approvals

    The Model H ESFR Sprinkler is FM approved [155°F(68C) and 200°F (93C) temperature ratings only] fouse in buildings to 45 ft. (13.7m) high with storageheights to 40 ft. (12.1m) when installed in accordancewith Factory Mutual Loss Prevention Data Sheet 2-2 oother FM Installation Standards.

    The Model H ESFR Sprinkler is UL and ULC Listed(all ratings) for installation in accordance with NFPAStandards for storage heights to 35 ft. (10.7m) inbuildings to 40 ft. (12.1m). high.

    The Model H ESFR Sprinkler [155°F (68C) and200°F (93C) ratings only] is also approved by both theVerband der Schadenversicherer e.V. (VdS Germanyand the Loss Prevention Council (LPC, UK). VdSGermany requires review prior to each installation.

    TheReliableAutomatic Sprinkler Co., Inc.   525 North MacQuesten Parkway,MountVernon, NewYork 10552

    Bulletin 150   Rev. G

     Application and Installation

    The Model H ESFR sprinkler is intended forinstallation in accordance with NFPA 13, NFPA 231,NFPA 231C and FM Loss Prevention Data Sheet 2-2 aswell as the Authority Having Jurisdiction.

    This sprinkler is intended for protection of palletizedand solid piled and open frame single row, doublerow, multiple row and portable rack storage of mostcommon materials including unexpanded andcartoned expanded plastics.

    The 286°F (141C) temperature rated Model HSprinkler is intended for installation in the proximity oflocalized heat sources.

    Listings

    1. Listed by Underwriters Laboratories Inc. andUL certified for Canada (cULus)

    2. Certified by FM Approvals

    3. NYC MEA 258-93-E4. Verband der Schadenversicherer e.V. (VdS Germany)5. Loss Prevention Council (LPC, UK)

  • 8/18/2019 ESFR

    2/2

    Recycled Paper 

    SprinklerType

    ThreadSize

    “K” Factor Maximum WorkingPressure

    FinishUS Metri c

    PendentOnly

      ¾ (R¾)   14.0 200 175 psi (12,1 bar) Bronze

    Theequipmentpresentedin this bulletin is tobe installedin accordance with thelatest pertinent Standards ofthe National FireProtectionAssociation,FactoryMutual ResearchCorporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.

    Products manufacturedand distributed by Reliable havebeen protecting life and propertyfor over 80 years, and are installed and serviced by the most highly qualified andreputable sprinkler contractors located throughout the United States, Canada and foreign countries.

    The Reliable Automatic Sprinkler Co., Inc.

    (800) 431-1588 Sales Offices(800) 848-6051 Sales Fax(914) 668-3470 Corporate Officehttp://www.reliablesprinkler.com   Internet Address

    Manufactured by

    Installation Data

    Classification

    SprinklerTemperature   Bulb

    ColorFrameColor

    Maximum AmbientTemperature

    Approvals

    SprinklerIdentification

    Number(SIN)°F °C °F °C

    OrdinaryIntermediateHigh

    155200286

    6893

    141

    RedGreen

    Blue

    UncoloredWhiteBlue

    100150225

    3866

    107

    UL, FM, ULC, MEA, VdS, LPCUL, FM, ULC, MEA, VdS, LPCUL, ULC

    R5012

    MaintenanceThe Model H ESFR Sprinkler should be inspected

    quarterly and the sprinkler system maintained in

    accordance with NFPA 25. Do not clean sprinkler withsoap and water, ammonia or any other cleaning fluid.Remove any sprinkler that has been painted (otherthan factory applied) or damaged in any way. A stockof spare sprinklers should be maintained to allow quickreplacement of damaged or operated sprinklers. Priorto installation, sprinklers should be maintained in theoriginal cartons and packaging until used to minimizethe potential for damage to sprinklers that would causeimproper operation or non-operation.

    Once operated, automatic sprinklers cannot bereassembled and reused. New sprinklers of the samesize, type and temperature rating must be installed. Acabinet of replacement sprinklers should be providedfor this purpose.

    Model H Sprinkler Wrench

    Use only the Model Hsprinkler wrench for re-moval and installation. Anyother type of wrench maydamage the sprinkler.

    Model H Temperature Ratings and Approvals