EN
for controlling three pumps, each with one- to three -
line SKF Single Line centralized lubrication systems
Lubrication Monitor Controller of series LMC 301
Version 03
Operating instructions acc. to EMC, LVD Directives and UL Standard
2
EU Declaration of Conformity in accordance with Directive 2014/30/EU on the electromagnetic compatibility
of devices and Directive 2014/35/EU on the use of electrical equipment within certain voltage limits
The manufacturer, SKF Lubrication Systems Germany GmbH , Walldorf Plant, Heinrich-Hertz-Str. 2-8, DE - 69190 Walldorf, hereby declares conformity of the device / the electrical equipment
Designation: Lubrication Monitor ControllerType: LMC 301Item number: 086500 / 086501 / 086502 / 086503Year of manufacture: See rating plate
with all relevant provisions of the following Directives at the time of placing on the market. Furthermore, the following Directives and (harmonized) standards were applied in the applicable areas:
2011/65/EU RoHS II Directive on the restriction of the use of certain hazardous substances in electrical and electronic equipment 2014/30/EU EMC Electromagnetic Compatibility 2014/35/EU LVD Use of electrical equipment within certain voltage limitsUL 61010-1 UL (Underwriters Laboratories) Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use - Part 1: General Requirements
Standard Edition
DIN EN 61000-6-2 2006
DIN EN 61000-6-3 2011
UL 61010-1 2012
DIN EN 61010-1 2011
DIN EN 50581 2013
Walldorf, 2018, March
EN Information concerning EU Declaration of Conformity
Stefan Schürmann Manager R&D Hockenheim/Walldorf SKF Lubrication Business Unit
Jürgen Kreutzkämper Manager R&D GermanySKF Lubrication Business Unit
3
Masthead
Manufacturer and service address
If you have questions, please contact:
SKF Lubrication Germany GmbH
Hockenheim Plant
2. Industriestraße 7
68766 Hockenheim
Germany
Tel. +79 (0)62 05 27-0
Fax +79 (0)62 05 27-101
www.skf.com/lubrication
ON
Masthead
These operating instructions pursuant to
the EMC and LVD Directives are an integral
part of the product described here and must
be kept for future use.
Other language versions
Versions of these instructions in other
languages can be found at: www.skf.com/
lubrication
Warranty
The instructions do not contain any infor-
mation on the warranty. This can be found
in the General Conditions of Sales, which
are available at:
www.skf.com/lubrication.
Copyright / Integration of instructions
© SKF Lubrication Systems Germany GmbH
All rights reserved.
These instructions are protected by copy-
right.
The use of the contents is permitted for the
purpose of preparing training materials for
internal, non-commercial purposes. Any
other usage of the contents without written
permission of the rights holder is prohibited
and constitutes a violation of copyright.
SKF Lubrication Systems Germany GmbH
Walldorf Plant
Heinrich-Hertz-Str. 2-8
DE - 69190 Walldorf
Tel: +49 (0) 6227 33-0
Fax: +49 (0) 6227 33-259
E-mail: [email protected]
www.skf.com/lubrication
Sales and Service Regions
Europe / Africa / Middle East / India
SKF Lubrication Systems Germany GmbH
Amerika / Asien / Pazifik
SKF Lubrication Business Unit
5178 N. Hanley Rd.,
St. Louis, MO 63137 USA
Tel: +1.317.679.7200
Fax: +1.800.727.5359
E-mail: [email protected]
www.lincolnindustrial.com
www.skf.com/lubrication
E-mail: [email protected]
www.skf.com/lubrication
4
EN
Table of contents
Table of contents
Operating instructions 1
EC Declaration of Conformity in accordance 2
Explanation of symbols and signs 6
1. Safety instructions 8
1.1 General safety instructions 8
1.2 General behavior when handling the product 8
1.3 Qualified technical personnel 9
1.4 Electric shock hazard 10
1.5 Operation 10
1.6 Assembly/maintenance/malfunction /decommissioning/disposal 10
1.7 Intended use 11
1.8 Foreseeable misuse 11
1.9 Disclaimer of liability 12
1.10 Referenced documents 12
1.11 Warning labels on the product 12
1.12 Residual risks 13
2. Overview/System description 14
2.1 LMC 301 controller unit 17
2.2 General design of a Single Line centralized lubrication system 18
2.2.1 System design 19
3. Technical data 21
3.1 General technical data 21
4. Delivery, returns, and storage 23
4.1 Checking the delivery 23
4.2 Returns 23
4.3 Storage 23
4.3.1 Electronic and electrical devices 23
4.3.2 General notes 23
5. Assembly 24
5.1 General information 24
5.2 Setup and attachment 24
5.2.1 Port dimensions, assembly holes, and minimum mounting dimensions 25
5.2.2 Opening the controller unit 26
5.2.3 Minimum mounting dimensions 26
5.2.4 Assembly of the controller unit 26
5.3 Electrical connection 5.3.1 General 27
5.3.2 Terminal board 100 to 240VAC 29
5.3.3 Terminal board 24 VDC 30
5.3.4 Line routing 31
5.3.5 Connecting wires 31
5.3.6 Power supply 100 to 240 V AC and 24 V DC 32
5.3.7 Load switching relay 32
5.3.8 Terminal strip for relay outgoing terminal 33
5.3.9 Terminal strip for digital inputs 34
5.3.10 Terminal strip for analog inputs 34
5.3.11 Adding an additional IO connection to RS485 daisy chain 35
5.4 Note on the rating plate 36
5.5 Information on CE marking 36
6. Configuration by operator/local admin 38
6.1 Configuration of the controller unit with PC software 38
6.2 Configuration of the controller unit via the display on the controller unit 39
6.2.3 Display and control elements of the control screen 40
6.2.4 Menu navigation for operators without password access 44
6.2.5 Menu navigation for local admins with password access 46
6.2.7 General setting options without (with) password access 49
6.2.8 Setting options for local admins (setters) with password access 51
5
ENTable of contents
6.2.8.1 Changing the password 52
6.3 Single Line-Control system examples 59
6.3.1 2-zone Single Line centralized lubrication system with 2/2 directional solenoid valves and 1 pressure switch 60
6.3.2 2-zone Single Line centralized lubrication system with 3/2 directional solenoid valves and 2 pressure switches 66
7. Operation/decommissioning and disposal 72
7.1 User-configurable setting options 72
7.2 Temporary shutdown 73
7.3 Recommissioning 73
7.4 Decommissioning and disposal 73
8. Maintenance 74
8.1 General information 74
8.2 Maintenance schedule 75
8.3 Battery replacement 76
8.4 Software update 76
9. Malfunctions, causes, and remedies 77
9.1 Fuse replacement 77
9.2 Display of error messages via fault LED 78
9.3 Display of error messages on the screen 78
9.4 Flex-Control unit -Commissioning malfunctions 82
9.5 System malfunctions 83
9.6 Measures in response to malfunctions 86
10. Spare parts/accessories 87
11. System configuration 88
11.1 Menu navigation for System configuration - Pump settings 88
11.1.1 Menu navigation for system configuration - zone settings 90
11.2 Menu structure for system configuration 92
11.3 Amount of pumps 93
11.4 Setting the pump 94
11.5 Zone 1 Settings (main line settings) 110
11.5.1 Zone 2 Settings (main lines) 117
11.6 Setting parameters to default 118
11.7 Reset to factory settings 118
6
EN
Possible symbols
Meaning
Note
Electric shock hazard
Slipping hazard
Hazard from hot surfaces
Risk of being drawn into machinery
Crushing hazard
Danger from suspended load
Pressure injection hazard
Explosion-proof component
Electrostatic sensitive components
Wear personal safety equipment (goggles)
Secure (lock) the machine against accidental starting
Environmentally sound disposal
Explanation of symbols and signs
Explanation of symbols and signs
Activities that present specific hazards to
persons or material assets are indicated
with warnings.
Read the instructions completely and follow
all operating instructions and the warning
and safety instructions.
Warning level Consequence Probability
DANGER Death / serious injury Immediate
WARNING Serious injury Possible
CAUTION Minor injury Possible
NOTE Property damage Possible
Symbol
Information symbols within the text
Symbol Meaning
Prompts an action
Used for itemizing
Refers to other facts, causes, or consequences
Provides additional information within procedures
7
ENExplanation of symbols and signs
Abbreviations and conversion factors
Abbreviationsre regarding oz. ounceapprox. approximately psi pounds per square inch°C degrees Celsius hp horsepowers seconds lb. pounddB (A) sound pressure level sq.in. square inchi.e. that is kp kilopondetc. et cetera cu.in. cubic inchposs. possibly mph miles per hour< less than fpsec feet per second± plus or minus °F degrees Fahrenheit> greater than fl.oz. fluid ouncee.g. for example in. inchif necessary
if necessary gal. gallon
etc. et ceterausually usuallyØ diameter Conversion factors incl. including Length 1 mm = 0.03937 in.K Kelvin Area 1 cm² = 0.155 sq.in.kg kilogram Volume 1 ml = 0.0352 fl.oz.RH relative humidity 1 l = 2.11416 pints (US)kW kilowatt Mass 1 kg = 2.205 lbsl liter 1 g = 0.03527 oz.min. minute Density 1 kg/cm³ = 8.3454 lb./gal.
(US)max. maximum 1 kg/cm³ = 0.03613 lb./cu.in.min. minimum Force 1 N = 0.10197 kpmm millimeter Speed 1 m/s = 3.28084 fpsecml milliliter 1 m/s = 2.23694 mphN Newton Acceleration 1 m/s² = 3.28084 ft./s²Nm Newton meter Pressure 1 bar = 14.5 psi
Temperature °C = (°F-32) x 5/9Power 1 kW = 1.34109 hp
Instructions placed on a unit, machine, or
equipment, such as:
o Rotation arrow
o Fluid connection labels must be followed
and kept in fully legible condition.
o Warnings
1. Safety instructions
8
ENEN
1. Safety instructions
1.1 General safety instructions
o The operator must ensure that the in-
structions are read and fully understood
by all persons tasked with working on the
product or who supervise or instruct such
persons.
o The operator must also ensure that the
staff fully understands the content of the
instructions.
o The instructions must be kept readily
available together with the product.
o The manual forms part of the product
and must accompany the product if sold
to a new owner.
o The product described here was manu-
factured according to the state of the art.
o Risks may, however, arise from its usage
and may result in personal injury or dam-
age to property.
o Any malfunctions affecting safety must be
remedied immediately.
In addition to the assembly instructions/op-
erating instructions, all statutory regulations
and other regulations for accident prevention
and environmental protection must be
observed.
1.2 General behavior when handling the
product
o The product may only be used in aware-
ness of the potential dangers, in proper
technical condition, and according to the
information in this manual.
o Personnel must familiarize themselves
with the functions and operation of the
product. The specified assembly and op-
erating steps and their sequences must
be observed.
o Any unclear points regarding proper con-
dition or correct assembly/operation must
be clarified.
Operation is prohibited until issues have
been clarified.
o Unauthorized persons must be kept away.
o All safety instructions and in-house in-
structions relevant to the particular activity
must be observed.
o Responsibilities for different activities
must be clearly defined and observed.
Uncertainty seriously endangers safety.
o Protective and safety mechanisms can-
not be removed, modified, nor disabled
during operation and must be checked
for proper function and completeness at
regular intervals.
If protective and safety mechanisms must
be removed, they must be installed im-
mediately following conclusion of work
and checked for proper function.
o Any malfunctions that occur must be
resolved according to responsibility. The
supervisor must be notified immediately
in case of malfunctions outside one's indi-
vidual scope of responsibility.
1. Safety instructions
9
1
ENEN
1.3 Qualified technical personnel
Only qualified technical personnel may in-
stall, operate, maintain, and repair the prod-
ucts described here.
Such persons are familiar with the relevant
standards, rules, accident prevention regu-
lations, and assembly conditions as a result
of their training, experience, and instruction.
They are qualified to carry out the required
activities and in doing so recognize and
avoid any potential hazards. The definition
of qualified personnel and the prohibition
against employing non-qualified person-
nel are laid down in DIN VDE 0105 and IEC
364. Relevant country-specific definitions of
qualified technical personnel apply for coun-
tries outside the scope of DIN VDE 0105 or
IEC 364.
The operator is responsible for assigning
tasks and the area of responsibility.
The personnel must be trained and in-
structed prior to beginning work if they do
not possess the requisite knowledge.
Product training can also be performed by
SKF in exchange for costs incurred.
o Wear personal protective equipment.
o Observe the relevant safety data sheets
when handling lubricants/equipment.
1. Safety instructions
10
ENEN
1.4 Electric shock hazard 1.5 Operation
The following must be observed while work-
ing on the product.
o All information within this manual and
the information within the referenced
documents
o All laws and regulations that the operator
must observe.
All relevant persons (operating personnel,
supervisors) must be informed of the activ-
ity prior to beginning work.
Precautionary operational measures / work
instructions must be observed.
o Take appropriate measures to ensure
that moving/detached parts are im-
mobilized during the work and that no
body parts can be pinched by unintended
movements.
o Assemble the product only outside the
operating range of moving parts, at an
adequate distance from sources of heat
or cold.
o Prior to performing work, the product
and the machine/system in which the
product will be integrated must be de-
energized and depressurized and secured
against unauthorized activation.
o All work on electrical components may be
performed only with voltage-insulated
tools.
1.6 Assembly/maintenance/malfunction/
decommissioning/disposal
WARNING
Electric shock
De-energize the product prior to
beginning work.
Only qualified, trained personnel
authorized by the operator may
perform work on the Lubrication
Monitor Controller.
Local conditions for connections
and local regulations (e.g., DIN,
VDE) must be observed.
Serious injury or death and property
damage may result from improp-
erly connected products.
1. Safety instructions
1.7 Intended use 1.8 Foreseeable misuse
Any usage of the product differing from the
aforementioned conditions and stated pur-
pose is strictly prohibited.
Particularly prohibited are:
o Use for other control tasks.
o Use in a more critical explosion zone.
o Use to feed, forward, or store hazardous
substances and mixtures as defined in
Annex I Part 2-5 of the CLP Regulation
(EC 1272/2008).
o Use to feed / forward / store gases, liq-
uefied gases, dissolved gases, vapors,
or fluids whose vapor pressure exceeds
normal atmospheric pressure (14,69 psi/
1013 mbar) by more than 0.5 bar at
their maximum permissible operating
temperature.
The Lubrication Monitor Controller is used
for controlling to max. three pumps, each
with one to three zones (one-line to three-
line) SKF Single Line centralized lubrication
systems.
On LMC 301 designs 086501 and 086503
(IO Board), the power supply is provided via
a customer-supplied 110/230 VAC net-
work. They must be connected according to
DIN and VDE or national active lungs/laws.
On LMC 301 designs 086500 and 086502
(IO Board), the power supply is provided
via 24 V DC.
The technical information contained in this
manual must be observed.
Any other usage is deemed non-compliant
with the intended use.
11
1
ENEN
o Fuses must not be bridged. Always re-
place fuses with fuses of the same type.
o Ensure proper grounding of the product.
o Drill holes required for assembly only on
non-critical, non-load-bearing parts.
o Other units of the machine/the vehicle
must not be damaged or impaired in their
function by the installation.
o No parts of the centralized lubrication
system may be subjected to torsion,
shear, or bending.
o Use suitable lifting gear when working
with heavy parts.
o Avoid mixing up/incorrectly assembling
disassembled parts. Label parts.
1. Safety instructions
12
ENEN
1.9 Disclaimer of liability
The manufacturer shall not be held liable for
damage resulting from:
o Failure to comply with these instructions.
o The use of lubricants/media not approved
for the unit type.
o Contaminated or unsuitable lubricants.
o Installation of non-original SKF
components.
o Inappropriate usage.
o Improper assembly, configuration or filling.
o Improper reaction to malfunctions.
o Non-observance of maintenance intervals.
o Independent modification of system
components.
1.10 Referenced documents
In addition to this manual, the following
documents must be observed by the re-
spective target group:
o Operational instructions/approval rules.
o Instructions from suppliers of purchased
parts.
o Manual for the insulation resistance tester
o Project planning documents and other
relevant documents
The operator must supplement these docu-
ments with applicable regulations for the
country of use.
The documentation must be included if the
product is transferred to a new operator.
1.11 Warning labels on the product
The following warning labels are affixed to
the product. Before commissioning, check
that the labels are present and intact.
Immediately replace warning labels if dam-
aged or missing. The product must not be
operated until then. See the positioning
diagram for the order number and position
on the product.
Positioning of warning labels, Fig. 1
Order No. : 246-078-289
Order No : 44-1826-3122
1. Safety instructions
13
1
ENEN
1.12 Residual risks
Table 1
Residual risk Remedy
Life cycle: Assembly/commissioning/operation/setup and retrofit
Electric shock due to defective or incor-rectly connected power lead on power supply or load relay
• Inspect the power lead for damage before starting the product
• Correctly wire/connect the power lead
Tearing/damage to lines when installed on moving machine components
• When installed on movable equipment use flexible lines
Life cycle: Malfunction, troubleshooting, maintenance, repair/decommissioning and disposal
Electric shock due to defective power lead on power supply
• Inspect the power lead for damage before starting the product
Electric shock from open control cabinet or active energized components
• Disconnect the customer-provided main switch or mains plug (cut power) before performing any work on electrical components• Exercise caution when operating the product
2. Overview/System description
Display, Fig. 2
PUMP A B C
RUN
LL
FAULT
POWER RESET
LMC 301
2. Overview/System description
PUMP A B C
RUN
LL
FAULT
POWER RESET
LMC 301
CAUTION!Do not use rigid electrical conduits.
ACHTUNG!keine starren Elektroinstallations-rohre verwenden.
PUMP A B C
RUN
LL
FAULT
POWER RESET
LMC 301
14
The installation of the cable glands and the customer provided cord sets to be done by the customer. The customer is responsible for proper installation.Cable glands and conduits -see chapter Accessories, page 83.When mounting the customer connecting cable no rigid connection pipe must be used - see sign (1) on the controller ground.
1
EN
2. Overview/System description
15
2 Status Overview and triggering an additional lubrication
Symbol Status Function
Press the arrow key to receive a status overview of the pumps resp. zones
(P1Z1 = Pump 1/Zone1 to max. P3Z3 Pump 3/Zone 3).
Press the arrow key again to display the residual pause time resp. residual runtime of the currently
selected pump/zone (e. g. P1Z1).
Press the arrow key again to display the activated inlets of the currently selected pump/zone.
Press the arrow key again to display the activated outlets of the currently selected pump/zone.
Press the "additional lubrication" key shortly to carry out an additional lubrication of the entire system
respectively of the activated zones (P1Z1 = pump 1/zone1 to max. max. P3Z3 pump 3/zone 3).
Overview StatesP1Z1
P1Z2
P1Z3
States/Timer P1Z1P1Z1State: Hold (Pause/Lube)Cycle Time:
Inputs (1) P1Z1
State: Lube
Outputs (1) P1Z1
State: Lube
Pump: O
Valve A/B: O
Additional lubrication
komplett
P1Z1
P1Z2
P1Z3
EN
2. Overview/System description
Display and control elements of control screen
Symbol Designation Function
Display o Menu display / Display of values and parameters / Fault notification o The right bar ( ) indicates that the menu extends beyond the current display
PUMP PUMPPumps A B C
Pump / main line A / B / C per pumpMax. of 3 main lines possible
RUN RUNningActive control
LED lights up =Indication of currently active pump/active control line (A/B/C)
LL Low LevelMinimum fill level reached
LED lights up =Minimum fill level (pump A/B/C) reached
FAULT FAULTError notification
o LED flashes = Error detected o LED lights up = Fault present
POWER POWERControl unit On/Off
LED lights up = Control unit switched on
Function keys Control key in combination with the display above the key
Up arrow key menu control / increase input value
"Down" arrow key menu control / reduce input value
Pressing triggers an interim lubrication.
Briefly pressing starts all systems
Actuations while in configuration mode are ignored.
RESET
Long pressing (> 3 seconds) stops all systems or resets an error message.
Long pressing acknowledges and clears error messages.
RESET
16
EN
2. Overview/System description
Display elements of the control screen
Symbol Status Function
Stopped/OFF o The system was stopped by pressing the Reset key and can
be restarted by briefly pressing the Running key.
Pause o Respective lubrication zone is in interval time
Wait Temperature o Waiting period temperature
Wait o Lubrication zone waiting because another zone currently
being lubricated
Lube o System is lubricating
Hold o Holding time
Pressure relief o System is relieving pressure
Runtime o Pump is running
Secured/access denied
o No access as local admin or supervisor
Access o Access as local admin or supervisor
Fault o Fault is present
Digital inputs and outputs on
o Digital output is enabled
Digital inputs and outputs off
o Digital output is disabled
T
!
2.1 LMC 301 controller unit
The SKF LMC 301 Controller is used to
control SKF Single Line centralized
lubrication systems.
Depending on the system design, up to
three independent lubrication zones can be
controlled.
The SKF LMC 301 controller handles control
and monitoring of the system. The current
system status is shown on the LMC 301
controller's display. The user can quickly
adapt the lubrication procedure by changing
the lubrication intensity
.
The SKF LMC 301 Controller offers the
following pump settings according to the
system design:
o Up to three lubricant pumps.
o Up to three lubrication zones (zones 1
to 3) per pump (main lines 1 to 3).
o Type of zone valves via 2/2 or
3/2 directional solenoid valves.
o Time- or pressure-based lubrication
monitoring.
17
2
EN
2. Overview/System description
o Pump control and monitoring.
o Temperature monitoring by internal or
external sensor.
o Automatic filling.
The SKF LMC 301 controller offers configu-
rations for the following zone settings for
each zone:
o Cycle Control, control mode time-based
or counter-based.
o Cycle Control for "light" or "heavy"
machine requirement with according
selection of "Light" or "Heavy" lubrication.
o Lubrication settings, setting of lubrication
time or, with counter control, the number
of pulses delivered by the machine.
o Flow rate monitoring.
o Alarm outputs and defined fault
diagnostics.
Some system settings and timings can be
modified by the customer via the password
level pocal Admin.
The previous settings can also be reset
to the default settings via the menu item
Set Params to Default.
)See Figure 3 on page 20
The following descriptions applies to a Single
Line centralized lubrication system with two
zones (two main lines).
The two zones are relieved via a reversing
valve downstream of the pump unit.
Both main lines are switched via a 2/2
directional solenoid valve upstream of the
respective main line.
Prelubrication or relubrication distributors
can be used as the Single Line distributors.
Depending on the design, the changeover
signal is sent by a shared pressure switch
(PT) or a pressure switch assigned to one of
the zones.
The pressure switch(es) can be designed as
NO-contacts (close when pre-defined pres-
sure is reached) or NC contacts (open when
pre-defined pressure is reached).
The fill level is monitored by a fill level switch
in the pump reservoir.
It can be designed as a NO-contact or an NC
contact.
2.2 General design of a Single Line
centralized lubrication system
18
EN
2. Overview/System description
Another system design involves using
3/2 directional solenoid valves instead of the
2/2 directional solenoid valves. In that case,
pressure is relieved via an additional relief
line (7).
This system design does not require an ad-
ditional relief valve.
2.2.1 System design
)See Figure 3 on page 20
Pressure is built up from the pump element
(1) via the mechanical pressure relief valve
(2) and the downstream main lubrication
line (3) to the solenoid valves of zone 1 (4)
and zone 2 (5), and from there to the down-
stream Single Line distributors (6).
The pump feeds lubricant via the mechanical
pressure relief valve (2) and the main line
(3) to both solenoid valves of zone 1 (4) and
zone 2 (5).
Depending on the programming, one of
the two solenoid valves is open, resulting
in pressure build-up of the lubricant in the
corresponding zone, while the other solenoid
valve is closed.
The lubrication proceeds as follows on a
Single Line centralized lubrication system
with prelubrication distributors:
The pump feeds lubricant to the respec-
tive zone (main line) until all prelubrication
distributors have dispensed their defined
quantity of lubricant to the respective lu-
brication lines. The pressure switch sends a
signal to the controller that the changeover
is finished. The controller then switches off
the pump and the mechanical pressure re-
lief valve (2), which leads to pressure relief in
the main line and the previously active zone
(main line).
The active solenoid valve (4 or 5) switches
to an open state once its holding time has
elapsed.
After pressure relief has been performed,
the zones (main lines) are prepared for an-
other lubricating cycle.
The lubrication proceeds as follows on a
Single Line centralized lubrication system
with relubrication distributors:
The pump feeds lubricant to the respective
zone (main line) until a predefined pressure
is reached. The pressure switch (PT) then
switches and sends a signal to the controller.
The controller switches off the pump and
19
2
EN
2. Overview/System description
switches the pressure relief valve to relief,
resulting in pressure relief in the main line
and the previously active zone (main line).
This causes the relubrication distributors to
relieve pressure, and lubricant is delivered to
the respective lubrication lines.
The active solenoid valve (4 or 5) switches
to an open state once its holding time has
elapsed.
After pressure release has been performed,
the system is now prepared for another lu-
bricating cycle.
The pump fill level is monitored by a fill level
switch in the pump reservoir.
2/2 directional solenoid valves and relief valve
3/2 directional solenoid valves and relief line
Zone 1 (main line 1)
Zone 2 (main line 2)
Zone 1 (main line 1)
Zone 2 (main line 2)
System diagrams of Single Line centralized lubrication systems, Fig. 3
M
T
P
PT
M
T
P
PT
PT
20
EN
3. Technical data
21
3
3. Technical data
Characteristics, design
GeneralMounting position Vertical, refer to graphic, see page 14Dimensions (L x W x H) 10.6299 x 6.6929 x 3.5433 inDisplay 2.3622x1.1811 in 128x64 pixels
Environmental conditions Altitude, up to AC 2000m / DC 5000mAmbient/Operating temperature AC 14 to + 122 °FAmbient/Operating temperature DC- - 40 to + 158 °FMaximum relative humidity 80 % for temperatures up to 31 °C decreasing linearly to 50 % relative humidity at 40 °CThe LCD display only operates down to -4°FStorage temperature - 40 to + 158 °F
Application ≤ 150 VAC Indoor/Outddor applications 3), UL overvoltage category III, pollution degree 2 > 150 ≤ 240 VAC only for indoor applications, UL overvoltage category II, pollution degree 2
Connectivity via terminal blockInputs: 10 count, short-circuit-proof, 2 are analog capableOutputs: 8 count, relay outputs NO-contact 8A
Residual ripple relative operating voltage ±5% acc. to DIN 417 55
3.1 General technical data 2
EN
3. Technical data
22
Characteristics, design
Output rating relaysConnection directly to the relay 01/02 100-240 VAC/ max. 15AConnection directly to the relay 01/02 24 VDC/ max. 15AOutput terminal block 01 bis 08 24 VDC; 100-240 VAC/max. 8A
Note: Do not mix 2 different voltages together (AC and DC) on one terminal block!
Safety per DIN EN 60204-1Safety class Class I
Customer connection cablesTemperature resistance of >158 °F
EMCInterference suppression VDE 0875 T 11, EN 55011 Class AEmitted interference acc. to EN 61000-6-3Immunity acc. to EN 61000-6-2
NoteThe emitted interference meets the requirements for industrial use; use in a residential area may cause interference under some circumstances.
LMC 301 Version Order No.24 VDC 086500100 to 240 VAC 08650124 VDC I/O 086502100 to 240 VAC I/O 086503
Characteristics, design
Protection and monitoringCurrent limit Sustained short-circuit-proofOverload-proof/ Open-circuit-proof Yes
Protection class 1) 4) IP 65, protection class only with appropiate cable glands PG-M20, without UL certification
Electronic consumingIternal fuse (LMC-Controller) 3 A Input ACInput voltage 100-240 VAC (50/60Hz)customer Fusing (slow). 4 A (100-240 VAC)
Input DC 2) 3)Input voltage 24 V DC ±10%custermer Fusing (slow) 10 A
1) strain relief kid/cable glands -see page 832) Applicable precautions for proper operation: “ Protective Extra Low Voltage“ (PELV) and “Safe Extra Low Voltage“ (SELV). 3) The application as Outdoor (outdoor installation) has not been tested in connection / certification with the UL standard4) The degree of protection class for the controller LMC 301 has not been tested in connection with the UL certification
EN
4. Delivery, returns, and storage
23
4
3
4. Delivery, returns, and storage
Do not top load / This side up
Keep dry
Handle with care, Do not drop
4.3.2 General notes
o The product can be wrappedin plastic film
to provide low-dust storage.
o Protect against ground moisture by storing
on a shelf or wooden pallet.
Bare metallic surfaces must be protected
using anti-corrosion agents Check corrosion
protection every 6 months and reapply if
necessary.
Immediately after receipt, the delivery must
be checked for completeness according
to the shipping documents. Any transport
damage must be reported to the transport
company immediately. The packaging material
should be preserved until any discrepancies
are resolved.
4.3.1 Electronic and electrical devices
o Dry and dust-free surroundings, store in
well ventilated dry area.
o Storage time: max. 24 months.
o Relative humidity: < 65%.
o Storage temperature: -40 - +158 °F.
o No direct sun or UV exposure.
o Protected against nearby sources of heat
or cold.
4.1 Checking the delivery
4.2 Returns
WARNING
Personal injury/property damage
Do not drop the product.
4.3 Storage
The following conditions apply to storage:
Before return shipment, all parts must be cleaned and properly packed (i.e., according to the requirements of the recipient country).
There are no restrictions for land, air, or
sea transport.
The following must be marked on the packaging of return shipments:
EN
5. Assembly
NOTE
Observe the technical data (Chapter 3).
WARNING
Electric shock
De-energize controller unit before
beginning work.
Only qualified personnel autho-
rized by operator may perform
work on Lubrication Monitor
Controller.
Electrical operating conditions and
local regulations (e.g., DIN, VDE)
must be observed.
24
5. Assembly
Only qualified technical personnel may
install, operate, maintain, and repair the
LMC 301 Lubrication Monitor Controller.
Qualified technical personnel are persons
who have been trained, assigned, and in-
structed by the Owner of the final prod-
uct into which the described Lubrication
Monitor Controller is incorporated.
Such persons are familiar with the rele-
vant standards, rules, accident prevention
regulations, and operating conditions as
a result of their training, experience, and
instruction. They are qualified to carry
out the required activities and in doing so
recognize and avoid potential hazards.
The definition of qualified personnel
and the prohibition against employing
non-qualified personnel are laid down in
DIN VDE 0105 and IEC 364.
Before assembling/setting up the Lubri-
cation Monitor Controller, the packaging
material and any shipping braces (e.g.,
plugs) must be removed.
Keep all packing material until product has
been inspected and no defects are found.
5.1 General information 5.2 Setup and attachment
The product should be protected from
humidity and vibration, and should be
mounted so that it is easily accessible, allowing
all further installation work to be done with-
out difficulty. Ensure that there is sufficient
air circulation to prevent excessive heating.
For the maximum permissible ambient tem-
perature, see "Technical data, Chapter 3."
The mounting position of the product is as
shown in the assembly drawing (Page 24).
WARNING
Personal injury/property damage
Drill assembly holes in such a way
that no lines, units, or moving
parts are damaged or their function
impaired.
Maintain safety clearances and
comply with regulations for as-
sembly and accident prevention.
EN
5. Assembly
25
5
Fig. 4
5.2.1 Port dimensions, assembly holes, and minimum mounting dimensions
∅
C
B
A
6.0
2
10.31
9.72
10.67
6.6
89
9
2.7
6
3.5
4
105 °
0.17
0.0
4
Minimum mounting dimensions
A = width: 12.99 inB = height 17.72 inC = depth 13.78 in
EN
5. Assembly
26
5.2.2 Opening the controller unit
Opening the controller unit, Fig. 5
• Insert a flat tip screwdriver (1) with a
maximum blade width of 0.22 in into the
opening slot (2)
• Turn the screwdriver (1) slightly into the
gap, pusch the screwdriver to the right to
open the cover (3)
)Open the cover with screwdriver up to briefly clicking and then opening the cover
by hand.
) See Figures 4 and 5
5.2.3 Minimum mounting dimensions
To ensure enough space for maintenance
work and possible disassembly of the product,
ensure that the minimum mounting dimen-
sions (Fig. 4) are maintained.
5.2.4 Assembly of the controller unit
) See Figure 4The controller unit is installed by using 4
cylinder-head screws of thread size M4.
If M4 tapped bores are used to fasten the
unit, the screws must have a minimum
length of 15 mm.
Fastening material to be provided by the
customer:
o Cylinder-head screws with hexagon socket
(4x) according to DIN6912-M4x.. -8.8,
o Washers (4x) acc to.
DIN EN ISO 7090-4-200HV
o Self-locking nuts M4 (4x) according to
DIN EN ISO 10511
• Drill assembly holes (Ø 0.1 in) accord-
ing to assembly drawing (Fig. 4) and the
conditions on the mounting surface.
• Clean surface to remove drilling chips.
• Open the controller unit, place it on the
surface, and roughly align it.
• Pass cylinder-head screws (4x) through
the fixing holes on the controller unit and
the mounting surface.
• Apply washers to cylinder-head screws,
gently tighten cylinder-head screws.
• Tighten the cylinder-head screws to a
torque of 4Nm (35 lbf in.)
1
2
3
EN
5. Assembly
NOTE
Mains voltage (supply voltage) must
match specifications on rating plate of
Lubrication Monitor Controller. Check fuse
protection of electrical circuit. Use only
fuses with prescribed amperage.
27
5
5.3 Electrical connection
5.3.1 General
The controller unit is supplied with
100 to 240 VAC voltage or optionally with
24 V DC voltage.
In both designs, the cables are introduced
through a cable fitting with a clamping
range of Ø 0.18 in to 0.39 in and terminal
blocks with tension springs (maximum con-
ductor cross-section 0,1 in, conductor strip-
ping length 0.59 in).
Refer toChapter 4, Technical Data, Chapter
3, for the electrical characteristics of the
controller unit.
The connections on the controller unit are
established according to the customer-
specific design of the lubrication system/
main lines. The system manufacturer is thus
liable for correct connection to the controller
unit.
EN
5. Assembly
NOTE
On the controller unit's electrical
connections, ensure that appropriate
measures prevent interference
between signals due to inductive,
capacitive, or electro-magnetic
couplings.
Shielded cables must be used in
places where electrical interference
fields can distort signal transmis-
sions despite separate laying of
cables.
The rules and empirical values for
"EMC-compliant" cabling must be
taken into consideration.
NOTE
Lubrication Monitor Controller
contains electronic components
that can be destroyed by accidental
electrostatic charge or discharge
(ESD). Use appropriate measures to
prevent interference between
signals due to different types of
couplings. due to ESD, hands and
any tools must be discharged on
a bare grounded position on the
installation site prior to performing
any work on the opened controller
unit. Conductors or components
within the device must not be
touched under any circumstances.
NOTE
An appropriate switch or circuit-breaker
(min. 10A) who protect all pole must be
included in the building installation and
shall be in close proximity to the equip-
ment within easy reach of the OPERATOR.
The disconnecting device shall be marked
as the device for the equipment.
28
EN
5. Assembly
29
5
Legend to Figure 6
Item Description Chapter
1 Power supply X1 5.3.6
1aInternal 100 to 240 VAC connection for the AC/DC power supply unit
1bInternal 24 VDC connection from AC/DC power supply unit to the board
2 Digital inputs X2 5.3.9
3 DigitalAnalog inputs X3 5.3.10
44.1 Relay Outputs X4
5.3.84.2 Relay Outputs X4
5 RS485-Interface
6 24 VDC output for mainboard
7USB port (external)Not for User
8 DIP switch addresses 5.3.11
9 RESET switch Hardware Reset
10 Fuse (FK1) 3A acc. to ISO 8820-3
11 Load switching relay (2x) X5 5.3.7
12
PE/Ground terminals for relay outputs X6Ground connection mustmade by the customer !
5.3.8
5.3.2 Terminal board 100 to 240VAC
NOTEYou can run each terminal block (4.1 or 4.2) only with one operating voltage (24 VDC or 100 to 240 VAC). Do not mix 2 different voltages together on 1 terminal block!
Connections on mainboard, design 100 to 240 VAC, Fig. 6
1a 1 10 1b 2 11 4.2
6 5 8 7 9 3 12 4.1
Cable glands for sensors
Cable glands for power supply/interface Cable glands for valves/motor
EN
5. Assembly
30
5.3.3 Terminal board 24 VDC
Legend to Figure 7
Item Description Chapter
1 Power supply X1 5.3.6
2 Digital inputs X2 5.3.9
3 Digital/Analog inputs X3 5.3.10
44.1 Relay outputs X4
5.3.84.2 Relay outputs X4
5 RS485 Interface
6 24 VDC output for main board
7 USB port (external)
Not for User
8 DIP switch addresses 5.3.11
9 RESET switch
Hardware Reset
10 Fuse (FK1) 3A acc. to ISO 8820-3
11 Load switching relay (2x) X5 5.3.7
12 PE Ground terminals for
relay outputs X6
Ground connection must
made by the customer !
5.3.8
NOTEYou can run each terminal block (4.1 or 4.2) only with one operating voltage (24 VDC or 100 to 240 VAC). Do not mix 2 different voltages together on 1 terminal block!
1 10 2 11 4.2
Connections on mainboard, design 24 VDC, Fig. 7
Cable glands for sensors
Cable glands for power supply/interfaceCable glands for valves/motor
6 5 8 7 9 3 12 4.1
EN
5. Assembly
31
5
) See Figures 6 and 7
5.3.4 Line routing
The lines are routed through cable glands
on both sides and the bottom
Cable glands are provided for the following
lines:
optinal Cable glands on left side:
o Power supply.
o Master/slave connection.
optional Cable glands on right side:
o Relay outlets (load-dependent).
o Pump motor.
Cable glands on bottom:
o Inputs and outputs for monitoring units
(sensors).
• Loosen the cable gland.
• Route the connection cable (provided by
customer) into the cable gland.
• Connect the cable according to the wiring
diagram (see Figs. 9 to 16).
• Tighten the cable gland.
) See Figures 6, page 27 and 7, page 28, item 1, and Fig. 8
The cables on the terminal strips for:
o Power connection (item 1).
o Digital outputs (item 2).
o Analog outputs (item 3).
o Relay (item 4).
are connected via a tension spring
mechanism.
Perform the following:
• Press the tension spring back using the
flat tip screwdriver.
• Insert flexible cable leads into the
terminals.
• Release pressure on the tension spring
• Check that the wires are securely con-
nected .
5.3.5 Connecting wires
Fig. 8
Wiresstripped Length 15 mm
Terminal strip
Tension spring
Flat tip screwdriver
maximum
cable insulation section
to customer-sided
of cable 2.5 mm2
EN
5. Assembly
X1 X1
32
5.3.6 Power supply 100 to 240 V AC and 24 V DC
Terminal diagram 100 to 240 VAC, Fig. 9
) See Figure 6, item 1, and Fig. 9
Terminal diagram 24 VDC, Fig. 10
• Connect customer-provided cable for
power supply acc. to terminal diagram
24 V DC, Fig. 10.
• Connect customer-provided cable for
power supply acc. to terminal diagram
100 to 240 VAC, Fig. 9.
)The 24 VDC are generated internally . Not Connect externally generated 24 VDC
supply + and terminal -
5.3.7 Load switching relay
) See Figures 6/7, item 11, and Fig. 11
Example Load switching relay, Fig. 11
• Connect (loop) customer-provided load
voltage cable to both terminals of the load
relay. Fig. 11.
) See Figure 7, item 1, and Fig. 10
O 3
O 2
O 2
O 1
O 1
Input 230 VACmax. 8 Ampere
Input 230 VACmax. 8 Ampere
M
Outputmax. 8 Ampere
M
Input 230 VAC, max. 15 Ampere
Input 24 VDC, max. 15 Ampere
Input 230 VAC,
max. 15 Ampere
Input 24 VDC,
max. 15 Ampere
M
Relay 2
Relay 1
Connection up tomax. 8 amperes
Load relay
controlled
directly
X5
EN
5. Assembly
NOTEYou can run each terminal block (4.1 or 4.2) only with one operating voltage (24 VDC or 100 to 230 VAC). Do not mix 2 different volt-ages together on 1 terminal block!
33
5
O 4
O 4
O 3
O 3
O 2
O 2
O 1
O 1
O 8
O 8
O 7
O 7
O 6
O 6
O 5
O 5
Ground
Power
5.3.8 Terminal strip for relay outgoing terminal
The outputs on the terminal strip X4 are
provided for downstream relays or loads
installed by the customer.
Note the following:
Two terminal rows (e.g.: 01/01) are
provided for each connection. Both are
connected to the switching contacts of the
corresponding relay. The customer's power
supply must be connected to one of the
terminal rows, while the load contact is
connected to the second, opposite terminal
row. The ground connection is established
via the ground terminal strip on the con-
troller, which must be grounded by the cus-
tomer (see Figure 13). The load on outlets
01 and 02 can optionally also be connected
directly to the load relay (see Fig. 11).
Connections in conjunction with load switching relay Max. 8 Ampere
Terminal diagram for relay outgoing terminal, Fig. 12
O 4
O 4
O 3
O 3
O 2
O 2
O 1
O 1
O 8
O 8
O 7
O 7
O 6
O 6
O 5
O 5
O = Output
Terminals
O3 to O8
Max. 8 Ampere
Connections in conjunction with load switching relay Max. 8 Ampere
X4
01/01 connection example for relay outputs,
Fig. 13
Signalmonitoring
Reversing valve
Pump motor,Connection max. 8 Ampere
X64.1
4.2
4.1
4.2
)see Figures 6/7, item 4, and Figs. 12 and 13
Ground connection must
made by the customer !
EN
5. Assembly
34
)See Figures 6/7, item 2, and Fig. 14
5.3.9 Terminal strip for digital inputs
Terminal strip for digital inputs, Fig. 14
+
I 3
I 4
-
+
I 5
I 6_
+
I 7
I 8
-
+
I 9
I10_
I = Input
The digital inputs are provided for:
o Pressure switch
o Proximity switch
o Flow sensor
o Fill level switch
o Interim lubrication switch
• Connect power supply for digital switch (+)
to plus terminal (+)
• Attach ground connection for analog
switch (-) to minus terminal (-)
• Attach signal line for digital switch to
corresponding input terminal (I3 to I10)
5.3.10 Terminal strip for analog inputs
Terminal strip for analog capable inputs,
Fig. 15
+
I 1
I 2_
I = Input
The analog inputs are provided for:
o Pressure transducer
o Temperature switch
o Switch polled in mA or volt, e.g.,
4-20 mA, 1-6 volt
• Connect power supply for analog switch
(+) to plus terminal (+)
• Connect ground connection for analog
switch (-) to minus terminal (-)
• Connect signal line for analog switch to
corresponding input terminal (I1 /I2)
)See Figures 5/6, item 3, and Fig. 15
X2
X3
Plus
Minus 1)
Plus
Minus
1) 2 wire sensors do not need minus.
EN
5. Assembly
NOTE
A separate address must be assigned to
each IO board!
To differentiate between multiple IOPCBs in
an RS485 daisy chain, each IOPCB needs its
own address.
This can be set in the binary code using the
DIP switch (address switch).
If all four DIP switches are set to top , the
address is "1". See Figure 16 for further
addresses.
Adr. 1
Adr.2
Adr.8
+
NOTEshielded cables use.Maximum cable length 200 m
35
5
5.3.11 Adding an additional IO connection to RS485 daisy chain
Another IPCB communication connection
can be established using the two RS485
connectors (5).
Up to 7 IOPCBs can be connected to a
mainboard. Each IOPCB must be supplied
separately.
Set IO addresses, Fig. 16
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
Off
ON
1 2 3 4
ON
1 2 3 4
Address 1 Address 2
Address 3 Address 4
Address 5 Address 6
Address 7 Address 8
Daisy chain with external IO boards, Fig. 17
)See Figures 6/7, item 8 )See Figures 16/17
+
EN
5. Assembly
36
5.4 Note on the rating plate
The rating plate provides important data
such as the type designation, order number,
etc.
To avoid loss of this data in case the rating
plate becomes illegible, these characteristics
should be entered in the manual.
P No. ________________________________
S No. ________________________________
Model ________________________________
5.5 Information on CE marking
The CE marking is based on the requirements of the applied Directives:
o 2014/30/EC Electromagnetic Compatibility
o 2011/65/EU (RoHS II) Directive on the restriction of the use of certain hazardous
substances in electrical and electronic equipment
o 2006/95/EG (LVD) Use of electrical equipment within certain voltage limits
Note on Pressure Equipment Directive 2014/68/EU (if pressurized parts are present)
Due to its performance characteristics, the product does not reach the limit values defined in
Article 4, Paragraph 1, Subparagraph (a) item (i) and is, pursuant to Article 4, Paragraph 3,
excluded from the scope of Pressure Equipment Directive 2014/68/EU.
Rating plate, Fig. 18
SKF Lubrication Systems Germany GmbH
Made in Germany D-69190 Walldorf
02/16
Model: LMC 301
2016100024/001 A
0865..
Serial-No:
P.No.:S-No:
I= 4 A
2016100024/001 A
U=
Proc.Cont.Eq.
EN
5. Assembly
37
5
EN
6. Configuration by operator/local admin
6. Configuration by operator/local admin
General
38
There are two options for configuring the
controller:
o Configuration with PC software and USB
connection -see Chapter 6.1.
The PC software application is designed for
Windows XP, Windows 7, and Windows 8
operating systems and is included as data
media with the controller. The software
can also be downloaded as freeware from
the SKF website. After installing the pro-
gram, data transfer occurs
via the USB interface in the controller.
SKF recommends this procedure for
initial installations.
o Configuration of the system using the dis-
play attached to the controller and menu
keys - See Chapter 6.2.
The complete configuration can be done
via the controller display and the associ-
ated menu keys.
6.1 Configuration of the controller unit with PC software
• From the SKF homepage
http://www.skf.com/pMC301/
download the file of LMC 301 software
pMC 301 PC Software
• Close all applications on the laptop.
• Open the file.
)The LMC 301 software installs automati-cally. SKF recommends not starting any
other applications during this period.
• Install the controller unit (Chapter 5)
• Open the controller unit (Chapter 5.2.2)
• Connect the USB cable (2) from the laptop
on the inside of the controller lid (1).
• Turn on the power supply-
Connect the USB cable, Fig. 19
NOTE
USB cable may only be
connected to USB port installed inside
controller lid of LMC 301. See Fig. 19.
• Start the LMC 301 software
)The description of the PC configuration is included with the software.
• Configure according to the included de-
scription for configuration on the PC.
)See Figure 19
1
2
EN
6. Configuration by operator/local admin
6.2.1 Structure of a lubricating cycle
Display, Fig. 20
Pressure build-up time
Holding time
Residual system pressure
Pressure build-up time
Holding time
System with 3/2 zone directional solenoid valve System with 2/2 zone directional solenoid valve
Pre
ssure
(MPa)
Time
39
6
6.2 Configuration of the controller unit via the display on the controller unit
Opening pressurePressure switch min.
Pressure relief time Pressure relieftime
Work cycle time
Lubrication time =Pump cycle time
Lubrication time =Pump cycle time
Interval time Interval time
Work cycle time
Opening pressurePressure switch max.
Cracking pressure
Pressure regulating valve
EN
6. Configuration by operator/local admin
Display, Fig. 21
PUMP A B C
RUN
LL
FAULT
POWER RESET
LMC 301
6.2.3 Display and control elements of
the control screen 6.2.2 Status/overview
After switching on the supply voltage, the
Overview States menu appears on the
display.
The current parameter settings and values
are displayed. This is done continuously and
automatically.
The parameters and settings can optionally
be accessed using the two arrow keys
No entries can be made and the symbol
shows a closed lock .
To change the configuration, select the
menu item Menu using the control key .
This will take you to the Main menu.
Changes can be made within the main menu
only after entering the password.
This is done in the pogin settings menu
level.
When entering the password, there is
a differentiation between pocal Admin
(customer access) and Supervisor (only ser-
vice staff, no customer access).
The open lock icon indicates that the
system has been unlocked.
NOTE
To save data, press the Save control key for
at least 3 seconds.
40
EN
6. Configuration by operator/local admin
41
6
Status Overview and triggering an additional lubrication
Symbol Status Function
Press the arrow key to receive a status overview of the pumps resp. zones
(P1Z1 = Pump 1/Zone1 to max. P3Z3 Pump 3/Zone 3).
Press the arrow key again to display the residual pause time resp. residual runtime of the currently
selected pump/zone (e. g. P1Z1).
Press the arrow key again to display the activated inlets of the currently selected pump/zone.
Press the arrow key again to display the activated outlets of the currently selected pump/zone.
Press the "additional lubrication" key shortly to carry out an additional lubrication of the entire system
respectively of the activated zones (P1Z1 = pump 1/zone1 to max. max. P3Z3 pump 3/zone 3).
Overview StatesP1Z1
P1Z2
P1Z3
States/Timer P1Z1P1Z1State: Hold (Pause/Lube)Cycle Time:
Inputs (1) P1Z1
State: Lube
Outputs (1) P1Z1
State: Lube
Pump: O
Valve A/B: O
Additional lubrication
komplett
P1Z1
P1Z2
P1Z3
EN
6. Configuration by operator/local admin
Display and control elements of control screen
Symbol Designation Function
Display o Menu display / Display of values and parameters / Fault notification o The right bar ( ) indicates that the menu extends beyond the current display
PUMP PUMPPumps A B C
Pump / main line A / B / C per pumpMax. of 3 main lines possible
RUN RUNningActive control
LED lights up =Indication of currently active pump/active control line (A/B/C)
LL Low LevelMinimum fill level reached
LED lights up =Minimum fill level (pump A/B/C) reached
FAULT FAULTError notification
o LED flashes = Error detected o LED lights up = Fault present
POWER POWERControl unit On/Off
LED lights up = Control unit switched on
Function keys Control key in combination with the display above the key
Up arrow key menu control / increase input value
"Down" arrow key menu control / reduce input value
Pressing triggers an interim lubrication.
Briefly pressing starts all systems
Actuations while in configuration mode are ignored.
RESET
Long pressing (> 3 seconds) stops all systems or resets an error message.
Long pressing acknowledges and clears error messages.
RESET
42
EN
6. Configuration by operator/local admin
Display elements of the control screen
Symbol Status Function
Stopped/OFF o The system was stopped by pressing the Reset key and can be restarted by briefly pressing the Running key.
Pause o Respective lubrication zone is in interval time.
Wait Temperature o Waiting period temperature.
Wait o Lubrication zone waiting because other zone currently being lubricated.
Lube o System is lubricating.
Hold o Holding time.
Pressure relief o System relieves pressure.
Runtime o Pump runs.
Secured/access denied
o No access as local admin or supervisor.
Access o Access as local admin or supervisor.
Fault o Fault is present.
Digital inputs and outputs on
o Digital output is enabled.
Digital inputs and outputs off
o Digital output is disabled.
T
!
43
6
EN
6. Configuration by operator/local admin
Login settingsUser SettingsDevice settingsPump 1 Timings
Pump 2 Timings
Pump 3 TimingsInformation
Main menu
Device settingsBacklight
Contrast
[ 00% ]
Date
[ 00/00/00 ]
System Clock
[ 00:00:00 ]
User settingsUnit Settings
[imperal] > [metric]
Language[German] > [English]
Login settingsEnter Password
Set PW local adminSet PW Supervisor
Enter Password
Please Enter Passwordto Continue0000
Password correct
Your locked in as
Local Operator
[enablrd > disabled]
Login settings
6.2.4 Menu navigation for operators without password access
44
EN
6. Configuration by operator/local admin
Pump 1 Timings
Zone 1 SettingsZone 2 Settings
Information
HW/FW Version
Hours of operating
Error history
Serial Number
HW/FW Version
Hardware version
[.....]
Firmware version[.....]
Hours of operation
Cumulatedoperating Time.................................
Error historyNo. 1 .........
!
Serial Number
Serial Number
[00000000]
Zone 1 Settings
Lube load
[Normal Cycle Set] > [Heavy Cycle Set]
Zone 2 Settings
Lube load
[Normal Cycle Set] > [Heavy Cycle Set]
Lube Event Counter
P1Z1[ 0]P1Z2[ 0]P1Z3[ 0]
Lube Event Counter
Setting options for operators without password access, Fig. 22
45
6
EN
6. Configuration by operator/local admin
6.2.5 Menu navigation for local admins with password access
Enter Password
Set PW local adminSet PW SuperDisor
Enter PasswordPlease Enter Passwordto Continue0000
Back OK
Login settingsUser Settings2eDice settingsPump 1 3imings
Pump 2 3imings
Pump 3 3imingsInformationen
Main menu
Login settingsEnter Password
Set PW local adminSet PW SuperDisor
Enter Password
Please Enter Passwordto Continue0000
Password correct
Your locked in as
Local Operator
Login settings Login settings
User settingsUnit Settings
[imperial] > [metric]
Language[German] > [English]
Device settingsBacklight
Contrast
[ 00% ]
Date
[ 00/00/00 ]
System Clock
[ 00:00:00 ]
[enablrd > disabled]
46
EN
6. Configuration by operator/local admin
Zone 1 Settings
Lube Load
Normal Cycle Time[ 0000: 00:00 ]
Heavy Cycle Time[ 0000: 00:00 ]
Lube Time[ 00: 00:00 ]
Holding time[ 00:00 ] s
Pump 1 Timings
Zone 1 SettingsZone 2 Settings
Zone 2 Settings
Lube Load
Normal Cycle Time[ 0000: 00:00 ]
Heavy Cycle Time[ 0000: 00:00 ]
Lube Time[ 00: 00:00 ]
Holding time[ 00:00 ] s
Information
HW/FW Version
Hours of operating
Error history
Serial Number
HW/FW Version
Hardware version
[.....]
Firmware version[.....]
Hours of operation
Cumulatedoperating Time.................................
Error historyNo. 1 .........
!
Serial Number
Serial Number
[00000000]
[Normal Cycle Set] > [Heavy Cycle Set]
[Normal Cycle Set] > [Heavy Cycle Set]
Lube Event CounterP1Z1[ 0]
P1Z2[ 0]P1Z3[ 0]
Lube Event Counter
Setting options for local admins, Fig. 23
47
6
EN
6. Configuration by operator/local admin
6.2.6 Main menu
The main menu shows the following
options:
Login settings
)refer to chapter 6.2.7 pg 49The menu is used to manage
access to the menus with a password.
The password can also be changed here.
User settings
)refer to chapter 6.2.6(Setting options for operators without
password access)
In this menu, the measurement units (metric
or inch) and the language for the user
menu can be selected.
Device settings
)refer to chapter 6.2.8 pages 51In this menu, the display properties of the
screen, such as backlight and contrast, can
be modified. The date and time are also set
here.
Main menu, Fig. 24
Pump 1 Timings
)refer to chapter 6.2.9 pages 53In this menu, the timing of the pump and
the settings for the associated main line
are set
Information
)refer to chapter 6.2.10 pages 54The hardware and firmware versions
are stored in this menu. The hours of
controller operation, the error history, and
the serial number of the controller unit can
also be viewed here.
Main menu
Login settings
User settings
Device settings
Pump 1 Timings
Information
Back OK
48
NOTE
The description of the main menu is based
on the setting options that the end cus-
tomer can adjust.
(password level Set PW local admin)
EN
6. Configuration by operator/local admin
User settings
Step Key Display Description
User settings - Set units and menu language
1
• Press
)You will be taken to the main menu
2
• Use to select the User settings menu item
• Confirm with
) You will enter the User settings menu
3
• Use to select the menu item panguage [English /Deutsch]
• Press
• Use to select the language [English /German]
• Press
Main menuLogin settings
User settings
Device settings
Pump 1 Timings
Information
6.2.7 General setting options without (with) password access
Overview StatesP1Z1:
User settingsUnit Settings
[metric ]
Language
[English ]
Back Select
Back
49
6
EN
6. Configuration by operator/local admin
User settings
Step Key Display Description
User settings - Set units and menu language
4
• Use to select the Unit Settings menu item [imperial/metric]
• Press
• Use to select Input Settings [Imperial/Metric]
• Press
• Press
)You will return to the User settings menu
User settingsUnit Settings
[metric ]
Language
[English ]
Back Select
50
EN
6. Configuration by operator/local admin
Login settings
Step Key Display Description
pogin settings- Enter Set PassWord local admin
1
• Press
)You will enter the pogin settings menu. The following menu items are available: o Enter password (enter existing password) o Set PassWord local admin for customer's personnel (change password)
o Set PW Supervisor for SKF Service and SKF dealers (change password)
o If the password has already been entered (open lock), the menu item Log Off is also available.
• Use to select Set PassWord local admin
• Press
)You will enter the Enter Password menu The password contains four characters that can be either numerals or letters.
• Use to set the first character of the password
• Confirm the entry with
• Repeat the entry for the following 3 password characters
• Press
)You will return to the pogin Settings menu.
Main menuLogin settings
User settings
Device settings
Pump 1 Timings
Information
6.2.8 Setting options for local admins (setters) with password access
Enter PasswordPlease Enter Password
to Continue
0000
Cancel OK
Login settingsEnter Password
Set PW local admin
Set PW Supervisor
Back OK
Password Correct
You are logged in as
Local Admin
Back OK
51
6
EN
6. Configuration by operator/local admin
Login settings
Step Key Display Description
pogin settings- change existing password
2
• Press
)You will enter the Login settings menu. • Use to select Enter Password
• Enter current password (see previous chapter)
• Use to select password level Set PassWord local admin (cus-
tomer service) or Set PW Supervisor (SKF Service)
• Press
)You will enter the Set PW local admin or Set PW Supervisor menu. The current pass-word and the entry field for the new password are displayed in this menu.
• Enter the new password as described above under Enter Password
)You will return to the Login Settings menu.
Main menuLogin settings
User settings
Device settings
Pump 1 Timings
Information
Login settingsEnter Password
Set PW local admin
Set PW Supervisor
Log Off
Back OK
Local AdminOld password
0000
New password
0000
Back OK
6.2.8.1 Changing the password
52
EN
6. Configuration by operator/local admin
6.2.9 Device settings
Device settings
Step Key Display Description
Device settings- Display, system date, and system time
1
• Use to select Device settings
• Press
)You will enter the Device Settings menu. The following menu items are available: o Backlight (display enabled/disabled)
o Contrast (display 0-100%)
o Date (year/month/day)
o System Clock (seconds/minutes/hours)
o Use to select a menu item
• Press
• Use to set the value
• Use to save the entry
)If there are multiple entries, the cursor automatically moves to the next entry field after saving.
• Press
)You will return to the Main menu.
Main menuLogin settings
User settings
Device settings
Pump 1 Timings
Information
Device settingsBacklight
[enabled/disabled]
Contrast
[ 60% ]
Date
[ 00/00/00 ]
System Clock
[ 00:00:00 ]
Back Select
53
6
EN
6. Configuration by operator/local admin
6.2.10 Pump 1 timings
General
Up to three pumps can be connected
to the LMC 301 Controller; the maximum
number of zones (main lines) that the Con-
troller can control is limited to three. Up to
three main lines (zone 1 to zone 3) can be
programmed per pump.
These can be accessed in the Main menu
under:
Pump 1 Timings
Zone 1 Settings
Zone 2 Settings
(if 2nd line available)
Zone 3 Settings
(if 3rd line available)
Depending on the access level, the following
settings can be made:
See Pages 40/41, Fig. 22 and 42/43, Fig. 23
The following entries can be made here:
o
or
o
The two lubrication settings differ in terms
of the duration of work cycle time.
The cycle time consists of the pump cycle
time + interval time - see Figure 20.
A longer lubrication time is typically pro-
grammed for Heavy Cycle Set compared
with Normal Cycle Set.
6.2.10.1 Operator level without password access
54
EN
6. Configuration by operator/local admin
Pump 1 Timings
Step Key Display Description
Pump 1 Timings User Settings- without password level
1
• Use to select
Pump 1 Timings
• Press
)You will enter the Pump 1 Timings menu.
)The following menu item is available: o Zone 1 Settings
• Press
• Press
• Use to select
Normal Cycle Set or Heavy Cycle Set
• Press to save the
selection
• Press
)You will return to the Pump 1 Timings menu.
Main menuLogin settings
User settings
Device settings
Pump 1 Timings
Information
Pump 1 Timings
Back
Zone 1 Settings
Zone 2 Settings
Pump 1 Timings
Back
Lubrication settings
[Normal Cycle Set]
Select
6.2.10.2 Local Admin (setter) or
Supervisor with password access
See Page 41 and Pages 45 to 47
The following entries can be made at the
password level:
Zone 1 Settings
o Selection of lube load
or , - refer to chapter 6.2.9 pg. 49
o Entry of for
basic lubrication
o Entry of for
increased lubricant demand
o Entry of monitoring time
>
o Entry of holding time, delay time of
zone valves
The procedure is typically identical for set-
ting parameters for the main lines (zone 1
to zone 3).
Set PW local adminFactory setting: 1000
55
6
EN
6. Configuration by operator/local admin
Pump 1 Timings
Step Key Display Description
Pump 1 timings- with password level pocal Admin or Supervisor
1
• Use to select Pump 1 Timings
• Press
)You will enter the Pump 1 Timings menu. )The following menu items are available:
o Zone 1 Settings
o Zone 2 Settings, if applicable
o Use to select Zone 1 Settings
• Press
)You will enter the Zone 1 Settings menu.
Main menuLogin settings
User settings
Device settings
Pump 1 Timings
Information
Pump 1 Timings
Back Ok
Zone 1 Settings
Zone 2 Settings
Zone 1 Settings
Back Select
Lube Load
[Normal Cycle Set]
Normal Cycle Time
[0000 : 00 : 00]
Heavy Cycle Time
[0000 : 00 : 00]
Monitoring Time
[00:00:00]
Holding time
[00:00] s
Back
56
EN
6. Configuration by operator/local admin
Pump 1 Timings
Step Key Display Description
Pump 1 timings- with password level pocal Admin or Supervisor
2
)The following menu items are available: o Lube Load: Selection between Normal Cycle Set and Heavy Cycle Set. The two lubri-
cation settings differ in terms of the duration of cycle time. A longer lubrication time is
typically programmed for Heavy Cycle Set compared with Normal Cycle Set.
o Normal Cycle Time: Entry of the time unit for a normal lubrication process. The total
value to be entered consists of pump cycle time+holding time+interval time. The lubri-
cation time is the time required by the lubrication system to build up pressure in the
respective zone until all distributors in the zone have actuated or reversed. The interval
time is the time differential between the set cycle time and the required pump cycle time
+ holding time. The entry is in hours/minutes/seconds.
o Heavy Cycle Time: Entry of the time unit for a lubrication process with increased lubri-
cant demand. The heavy cycle time has the same structure as the normal cycle time. The
entry is in hours/minutes/seconds.
o Monitoring Time: Monitoring of lubrication time Pressure build-up must be completed
within the monitoring time (time slot).
o Holding time: After the end of the pump cycle time, the controller switches off the pump,
though pressure relief by the zone valves is delayed by the holding time. The entry is in
minutes and seconds.
Zone 1 Settings
Back
Select
Lube Load
[Normal Cycle Set]
Normal Cycle Time
[0000 : 00 : 00]
Heavy Cycle Time
[0000 : 00 : 00]
Monitoring Time
[00:00:00]
Holding time
[00:00] s
57
6
EN
6. Configuration by operator/local admin
6.2.11 Information
The information menu presents information.
Parameters cannot be changed, and error
Information
Step Key Display Description
Information menu - without password level
1
• Use to select Information
• Press
)You will enter the Information menu. )The following menu item is available:
o HW/FW Version: Display of the controller unit's hardware and software version
o Hours of operation: Current number of operating hours of the controller unit
o Error history: previous error messages, with error coding
o Serial Number: Serial number of the control unit
• Use to select a menu item
• Press
• Press
)You will return to the Information menu.• Press
)You will return to the Main menu.
Main menuLogin settings
User settings
Device settings
Pump 1 Timings
Information
Information
Back
HW/FW Version
Operating hours
Error history
Serial No.
Ok
messages cannot be cleared.
Back
58
EN
6. Configuration by operator/local admin
6.3 Single Line system examples
Several examples of Single Line systems
with an LMC 301 Controller are listed below
and can be used as the basis for local ad-
mins to make their settings.
The individual examples are divided into
three sections.
Section 1 is a brief description of the struc-
ture of the Single Line centralized lubrica-
tion system shown.
Section 2 shows the structure of the
particular Single Line centralized lubrication
system (system design) with the associated
LMC 301 terminal diagram.
Section 3 shows the customer program-
ming of the LMC 301 Controller via its dis-
play and keyboard (see Chapter 6.2).
59
6
EN
6. Configuration by operator/local admin
LMC301, electrical terminal diagram, Fig. 25
Design
The example applies to a Single Line
centralized lubrication system with two
zones (zone 1/zone 2 (line 1/line 2)).
It is composed of the main components
Single Line pump (1) with mechanical
pressure relief valve (2) and one pumpout-
let. A main line (3) connects the pump
outlet with the two 2/2 directional sole-
noid valves for zone 1 (4) and zone 2 (5).
A pressure switch PT (6) is mounted at the
end of the main line to monitor pressure.
Chapter 3 contains a general functional
description.
)See Figures 25 and 26
6.3.1 2-zone Single Line centralized lubrication system with 2/2 directional solenoid valves and 1 pressure switch
O 4
O 4
O 3
O 3
O 2
O 2
O 1
O 1
O 8
O 8
O 7
O 7
O 6
O 6
O 5
O 5
Ground
Power
X4
X6
+
I 1
I 2_
X3
PT
+
I 3
I 4
-
+
I 5
I 6_
+
I 7
I 8
-
+
I 9
I10_
X2
Terminal +
Ground -
Signal I 2
Valve, zone 2
Valve, zone 1
Pump motor, max. 8 amp.
use also PE vor Valve
NOTEYou can run each terminal block (4.1 or 4.2) only with one operating voltage (24 VDC or 100 to 240 VAC). Do not mix 2 different volt-ages together on 1 terminal block!
60
EN
6. Configuration by operator/local admin
M
T
P
PT
(Zone
2)
X4
(Zone
1)
X4
Zone 1 (Schmierstrang 1)
Zone 2 (Schmierstrang 2)
(Ground) X6
PT
P
System design, Fig. 26
(pressure monitoring PT, voltage) X3, terminal +
(pressure monitoring PT, ground) X3, terminal -
(pressure monitoring PT, signal) X3, terminal I 1
(fill level monitoring) X3, terminal I 3
Pump motor, max. 8 amp.
61
6
EN
6. Configuration by operator/local admin
Programming via the SKF LMC 301
Step Key Display Description
1
The following requirements are met:
• User settings have been made according to Chapter 6.2.5, pages 42
• Login settings have been made according to Chapter 6.2.6, pages 44
(only at pocal Admin level)
• Device settings have been made according to Chapter 6.2.7, pages 45
Timing User Settings
2
• Use to select Pump 1 Timings
• Press
)You will enter the Pump 1 Timings menu.
)The following menu item is available: o Zone 1 Settings
o Zone 2 Settings
• Use to select the Zone 1 Settings menu item
• Press
Main menuLogin settings
User settings
Device settings
Pump 1 Timings
Information
Pump 1 Timings
Zone 1 Settings
Zone 2 Settings
Customer programming of the LMC 301 unit via the controller display and controller keys
62
EN
6. Configuration by operator/local admin
Pump 1 Timing and Cycle Control
Step Key Display Description
Pump 1 Timing User Settings
2
)You will enter the Zone 1 Settings menu. )The following menu items are available
o or . Entry of lubrication intensity, normal or
heavy cycle set
o Normal Cycle Counts: Entry of cycle time for normal cycle set
o Heavy Cycle Counts: Entry of cycle time for increased lubricant demand (longer pump
cycle time)
o Monitoring Time: Monitoring of lubrication time The lubricating cycle must be com-
pleted within the monitoring time (time slot).
o Holding time: After the end of the pump cycle time, the controller switches off the pump,
though pressure relief by the zone valves is delayed by the holding time.
• Use to select Normal Cycle Set (or Heavy Cycle Set)
• Press
• Use to select between Normal Cycle Set /Heavy Cycle Set
• Press
• Use to select the Normal Cycle Time menu item
• Press
• Use to enter an eight-digit cycle count [hhhh:mm:ss]
)Press to advance to the next digit• Press
Zone 1 SettingsLubrication settings
[Normal Cycle Set]
Normal Cycle Counts:
[0000:00:00]
Heavy Cycle Counts:
[0000:00:00]
Monitoring Time
[00:00:00]
Holding time
[00:00]
63
6
EN
6. Configuration by operator/local admin
Pump 1 Timing and Cycle Control
Step Key Display Description
Pump 1 Timing User Settings
2
• Use to select the Heavy Cycle Counts menu item
• Press
• Use to enter an eight-digit cycle count [hhhh:mm:ss]
)Press to advance to the next digit• Press
• Use to select the Monitoring Time menu item
• Press
• Use to enter a six-digit cycle count [hh:mm:ss]
)Press to advance to the next digit• Press
• Use to select the Holding time menu item
• Press
• Use to enter a four-digit cycle count [mm:ss]
)Press to advance to the next digit• Press
Zone 1 Settings
Lubrication settings
[Normal Cycle Set]
Normal Cycle Counts:
[0000:00:00]
Heavy Cycle Counts:
[0000:00:00]
Monitoring Time
[00:00:00]
Holding time
[00:00]
64
EN
6. Configuration by operator/local admin
Pump 1 Timing and Cycle Control
Step Key Display Description
Pump 1 Timing User Settings- Zone 2 Settings
3
• Use to select the Zone 2 Settings menu item
• Press
• Make settings according to the procedure