120
EN for controlling three pumps, each with one- to three - line SKF Single Line centralized lubrication systems Lubrication Monitor Controller of series LMC 301 Version 03 Operating instructions acc. to EMC, LVD Directives and UL Standard

erating instructions EN Lubrication Monitor Controller of ......EN for controlling three pumps, each with one- to three - line SKF Single Line centralized lubrication systems Lubrication

  • Upload
    others

  • View
    12

  • Download
    0

Embed Size (px)

Citation preview

  • EN

    for controlling three pumps, each with one- to three -

    line SKF Single Line centralized lubrication systems

    Lubrication Monitor Controller of series LMC 301

    Version 03

    Operating instructions acc. to EMC, LVD Directives and UL Standard

  • 2

    EU Declaration of Conformity in accordance with Directive 2014/30/EU on the electromagnetic compatibility

    of devices and Directive 2014/35/EU on the use of electrical equipment within certain voltage limits

    The manufacturer, SKF Lubrication Systems Germany GmbH , Walldorf Plant, Heinrich-Hertz-Str. 2-8, DE - 69190 Walldorf, hereby declares conformity of the device / the electrical equipment

    Designation: Lubrication Monitor ControllerType: LMC 301Item number: 086500 / 086501 / 086502 / 086503Year of manufacture: See rating plate

    with all relevant provisions of the following Directives at the time of placing on the market. Furthermore, the following Directives and (harmonized) standards were applied in the applicable areas:

    2011/65/EU RoHS II Directive on the restriction of the use of certain hazardous substances in electrical and electronic equipment 2014/30/EU EMC Electromagnetic Compatibility 2014/35/EU LVD Use of electrical equipment within certain voltage limitsUL 61010-1 UL (Underwriters Laboratories) Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use - Part 1: General Requirements

    Standard Edition

    DIN EN 61000-6-2 2006

    DIN EN 61000-6-3 2011

    UL 61010-1 2012

    DIN EN 61010-1 2011

    DIN EN 50581 2013

    Walldorf, 2018, March

    EN Information concerning EU Declaration of Conformity

    Stefan Schürmann Manager R&D Hockenheim/Walldorf SKF Lubrication Business Unit

    Jürgen Kreutzkämper Manager R&D GermanySKF Lubrication Business Unit

  • 3

    Masthead

    Manufacturer and service address

    If you have questions, please contact:

    SKF Lubrication Germany GmbH

    Hockenheim Plant

    2. Industriestraße 7

    68766 Hockenheim

    Germany

    Tel. +79 (0)62 05 27-0

    Fax +79 (0)62 05 27-101

    www.skf.com/lubrication

    ON

    Masthead

    These operating instructions pursuant to

    the EMC and LVD Directives are an integral

    part of the product described here and must

    be kept for future use.

    Other language versions

    Versions of these instructions in other

    languages can be found at: www.skf.com/

    lubrication

    Warranty

    The instructions do not contain any infor-

    mation on the warranty. This can be found

    in the General Conditions of Sales, which

    are available at:

    www.skf.com/lubrication.

    Copyright / Integration of instructions

    © SKF Lubrication Systems Germany GmbH

    All rights reserved.

    These instructions are protected by copy-

    right.

    The use of the contents is permitted for the

    purpose of preparing training materials for

    internal, non-commercial purposes. Any

    other usage of the contents without written

    permission of the rights holder is prohibited

    and constitutes a violation of copyright.

    SKF Lubrication Systems Germany GmbH

    Walldorf Plant

    Heinrich-Hertz-Str. 2-8

    DE - 69190 Walldorf

    Tel: +49 (0) 6227 33-0

    Fax: +49 (0) 6227 33-259

    E-mail: [email protected]

    www.skf.com/lubrication

    Sales and Service Regions

    Europe / Africa / Middle East / India

    SKF Lubrication Systems Germany GmbH

    Amerika / Asien / Pazifik

    SKF Lubrication Business Unit

    5178 N. Hanley Rd.,

    St. Louis, MO 63137 USA

    Tel: +1.317.679.7200

    Fax: +1.800.727.5359

    E-mail: [email protected]

    www.lincolnindustrial.com

    www.skf.com/lubrication

    E-mail: [email protected]

    www.skf.com/lubrication

  • 4

    EN

    Table of contents

    Table of contents

    Operating instructions 1

    EC Declaration of Conformity in accordance 2

    Explanation of symbols and signs 6

    1. Safety instructions 8

    1.1 General safety instructions 8

    1.2 General behavior when handling the product 8

    1.3 Qualified technical personnel 9

    1.4 Electric shock hazard 10

    1.5 Operation 10

    1.6 Assembly/maintenance/malfunction /decommissioning/disposal 10

    1.7 Intended use 11

    1.8 Foreseeable misuse 11

    1.9 Disclaimer of liability 12

    1.10 Referenced documents 12

    1.11 Warning labels on the product 12

    1.12 Residual risks 13

    2. Overview/System description 14

    2.1 LMC 301 controller unit 17

    2.2 General design of a Single Line centralized lubrication system 18

    2.2.1 System design 19

    3. Technical data 21

    3.1 General technical data 21

    4. Delivery, returns, and storage 23

    4.1 Checking the delivery 23

    4.2 Returns 23

    4.3 Storage 23

    4.3.1 Electronic and electrical devices 23

    4.3.2 General notes 23

    5. Assembly 24

    5.1 General information 24

    5.2 Setup and attachment 24

    5.2.1 Port dimensions, assembly holes, and minimum mounting dimensions 25

    5.2.2 Opening the controller unit 26

    5.2.3 Minimum mounting dimensions 26

    5.2.4 Assembly of the controller unit 26

    5.3 Electrical connection 5.3.1 General 27

    5.3.2 Terminal board 100 to 240VAC 29

    5.3.3 Terminal board 24 VDC 30

    5.3.4 Line routing 31

    5.3.5 Connecting wires 31

    5.3.6 Power supply 100 to 240 V AC and 24 V DC 32

    5.3.7 Load switching relay 32

    5.3.8 Terminal strip for relay outgoing terminal 33

    5.3.9 Terminal strip for digital inputs 34

    5.3.10 Terminal strip for analog inputs 34

    5.3.11 Adding an additional IO connection to RS485 daisy chain 35

    5.4 Note on the rating plate 36

    5.5 Information on CE marking 36

    6. Configuration by operator/local admin 38

    6.1 Configuration of the controller unit with PC software 38

    6.2 Configuration of the controller unit via the display on the controller unit 39

    6.2.3 Display and control elements of the control screen 40

    6.2.4 Menu navigation for operators without password access 44

    6.2.5 Menu navigation for local admins with password access 46

    6.2.7 General setting options without (with) password access 49

    6.2.8 Setting options for local admins (setters) with password access 51

  • 5

    ENTable of contents

    6.2.8.1 Changing the password 52

    6.3 Single Line-Control system examples 59

    6.3.1 2-zone Single Line centralized lubrication system with 2/2 directional solenoid valves and 1 pressure switch 60

    6.3.2 2-zone Single Line centralized lubrication system with 3/2 directional solenoid valves and 2 pressure switches 66

    7. Operation/decommissioning and disposal 72

    7.1 User-configurable setting options 72

    7.2 Temporary shutdown 73

    7.3 Recommissioning 73

    7.4 Decommissioning and disposal 73

    8. Maintenance 74

    8.1 General information 74

    8.2 Maintenance schedule 75

    8.3 Battery replacement 76

    8.4 Software update 76

    9. Malfunctions, causes, and remedies 77

    9.1 Fuse replacement 77

    9.2 Display of error messages via fault LED 78

    9.3 Display of error messages on the screen 78

    9.4 Flex-Control unit -Commissioning malfunctions 82

    9.5 System malfunctions 83

    9.6 Measures in response to malfunctions 86

    10. Spare parts/accessories 87

    11. System configuration 88

    11.1 Menu navigation for System configuration - Pump settings 88

    11.1.1 Menu navigation for system configuration - zone settings 90

    11.2 Menu structure for system configuration 92

    11.3 Amount of pumps 93

    11.4 Setting the pump 94

    11.5 Zone 1 Settings (main line settings) 110

    11.5.1 Zone 2 Settings (main lines) 117

    11.6 Setting parameters to default 118

    11.7 Reset to factory settings 118

  • 6

    EN

    Possible symbols

    Meaning

    Note

    Electric shock hazard

    Slipping hazard

    Hazard from hot surfaces

    Risk of being drawn into machinery

    Crushing hazard

    Danger from suspended load

    Pressure injection hazard

    Explosion-proof component

    Electrostatic sensitive components

    Wear personal safety equipment (goggles)

    Secure (lock) the machine against accidental starting

    Environmentally sound disposal

    Explanation of symbols and signs

    Explanation of symbols and signs

    Activities that present specific hazards to

    persons or material assets are indicated

    with warnings.

    Read the instructions completely and follow

    all operating instructions and the warning

    and safety instructions.

    Warning level Consequence Probability

    DANGER Death / serious injury Immediate

    WARNING Serious injury Possible

    CAUTION Minor injury Possible

    NOTE Property damage Possible

    Symbol

    Information symbols within the text

    Symbol Meaning

    Prompts an action

    Used for itemizing

    Refers to other facts, causes, or consequences

    Provides additional information within procedures

  • 7

    ENExplanation of symbols and signs

    Abbreviations and conversion factors

    Abbreviationsre regarding oz. ounceapprox. approximately psi pounds per square inch°C degrees Celsius hp horsepowers seconds lb. pounddB (A) sound pressure level sq.in. square inchi.e. that is kp kilopondetc. et cetera cu.in. cubic inchposs. possibly mph miles per hour< less than fpsec feet per second± plus or minus °F degrees Fahrenheit> greater than fl.oz. fluid ouncee.g. for example in. inchif necessary

    if necessary gal. gallon

    etc. et ceterausually usuallyØ diameter Conversion factors incl. including Length 1 mm = 0.03937 in.K Kelvin Area 1 cm² = 0.155 sq.in.kg kilogram Volume 1 ml = 0.0352 fl.oz.RH relative humidity 1 l = 2.11416 pints (US)kW kilowatt Mass 1 kg = 2.205 lbsl liter 1 g = 0.03527 oz.min. minute Density 1 kg/cm³ = 8.3454 lb./gal.

    (US)max. maximum 1 kg/cm³ = 0.03613 lb./cu.in.min. minimum Force 1 N = 0.10197 kpmm millimeter Speed 1 m/s = 3.28084 fpsecml milliliter 1 m/s = 2.23694 mphN Newton Acceleration 1 m/s² = 3.28084 ft./s²Nm Newton meter Pressure 1 bar = 14.5 psi

    Temperature °C = (°F-32) x 5/9Power 1 kW = 1.34109 hp

    Instructions placed on a unit, machine, or

    equipment, such as:

    o Rotation arrow

    o Fluid connection labels must be followed

    and kept in fully legible condition.

    o Warnings

  • 1. Safety instructions

    8

    ENEN

    1. Safety instructions

    1.1 General safety instructions

    o The operator must ensure that the in-

    structions are read and fully understood

    by all persons tasked with working on the

    product or who supervise or instruct such

    persons.

    o The operator must also ensure that the

    staff fully understands the content of the

    instructions.

    o The instructions must be kept readily

    available together with the product.

    o The manual forms part of the product

    and must accompany the product if sold

    to a new owner.

    o The product described here was manu-

    factured according to the state of the art.

    o Risks may, however, arise from its usage

    and may result in personal injury or dam-

    age to property.

    o Any malfunctions affecting safety must be

    remedied immediately.

    In addition to the assembly instructions/op-

    erating instructions, all statutory regulations

    and other regulations for accident prevention

    and environmental protection must be

    observed.

    1.2 General behavior when handling the

    product

    o The product may only be used in aware-

    ness of the potential dangers, in proper

    technical condition, and according to the

    information in this manual.

    o Personnel must familiarize themselves

    with the functions and operation of the

    product. The specified assembly and op-

    erating steps and their sequences must

    be observed.

    o Any unclear points regarding proper con-

    dition or correct assembly/operation must

    be clarified.

    Operation is prohibited until issues have

    been clarified.

    o Unauthorized persons must be kept away.

    o All safety instructions and in-house in-

    structions relevant to the particular activity

    must be observed.

    o Responsibilities for different activities

    must be clearly defined and observed.

    Uncertainty seriously endangers safety.

    o Protective and safety mechanisms can-

    not be removed, modified, nor disabled

    during operation and must be checked

    for proper function and completeness at

    regular intervals.

    If protective and safety mechanisms must

    be removed, they must be installed im-

    mediately following conclusion of work

    and checked for proper function.

    o Any malfunctions that occur must be

    resolved according to responsibility. The

    supervisor must be notified immediately

    in case of malfunctions outside one's indi-

    vidual scope of responsibility.

  • 1. Safety instructions

    9

    1

    ENEN

    1.3 Qualified technical personnel

    Only qualified technical personnel may in-

    stall, operate, maintain, and repair the prod-

    ucts described here.

    Such persons are familiar with the relevant

    standards, rules, accident prevention regu-

    lations, and assembly conditions as a result

    of their training, experience, and instruction.

    They are qualified to carry out the required

    activities and in doing so recognize and

    avoid any potential hazards. The definition

    of qualified personnel and the prohibition

    against employing non-qualified person-

    nel are laid down in DIN VDE 0105 and IEC

    364. Relevant country-specific definitions of

    qualified technical personnel apply for coun-

    tries outside the scope of DIN VDE 0105 or

    IEC 364.

    The operator is responsible for assigning

    tasks and the area of responsibility.

    The personnel must be trained and in-

    structed prior to beginning work if they do

    not possess the requisite knowledge.

    Product training can also be performed by

    SKF in exchange for costs incurred.

    o Wear personal protective equipment.

    o Observe the relevant safety data sheets

    when handling lubricants/equipment.

  • 1. Safety instructions

    10

    ENEN

    1.4 Electric shock hazard 1.5 Operation

    The following must be observed while work-

    ing on the product.

    o All information within this manual and

    the information within the referenced

    documents

    o All laws and regulations that the operator

    must observe.

    All relevant persons (operating personnel,

    supervisors) must be informed of the activ-

    ity prior to beginning work.

    Precautionary operational measures / work

    instructions must be observed.

    o Take appropriate measures to ensure

    that moving/detached parts are im-

    mobilized during the work and that no

    body parts can be pinched by unintended

    movements.

    o Assemble the product only outside the

    operating range of moving parts, at an

    adequate distance from sources of heat

    or cold.

    o Prior to performing work, the product

    and the machine/system in which the

    product will be integrated must be de-

    energized and depressurized and secured

    against unauthorized activation.

    o All work on electrical components may be

    performed only with voltage-insulated

    tools.

    1.6 Assembly/maintenance/malfunction/

    decommissioning/disposal

    WARNING

    Electric shock

    De-energize the product prior to

    beginning work.

    Only qualified, trained personnel

    authorized by the operator may

    perform work on the Lubrication

    Monitor Controller.

    Local conditions for connections

    and local regulations (e.g., DIN,

    VDE) must be observed.

    Serious injury or death and property

    damage may result from improp-

    erly connected products.

  • 1. Safety instructions

    1.7 Intended use 1.8 Foreseeable misuse

    Any usage of the product differing from the

    aforementioned conditions and stated pur-

    pose is strictly prohibited.

    Particularly prohibited are:

    o Use for other control tasks.

    o Use in a more critical explosion zone.

    o Use to feed, forward, or store hazardous

    substances and mixtures as defined in

    Annex I Part 2-5 of the CLP Regulation

    (EC 1272/2008).

    o Use to feed / forward / store gases, liq-

    uefied gases, dissolved gases, vapors,

    or fluids whose vapor pressure exceeds

    normal atmospheric pressure (14,69 psi/

    1013 mbar) by more than 0.5 bar at

    their maximum permissible operating

    temperature.

    The Lubrication Monitor Controller is used

    for controlling to max. three pumps, each

    with one to three zones (one-line to three-

    line) SKF Single Line centralized lubrication

    systems.

    On LMC 301 designs 086501 and 086503

    (IO Board), the power supply is provided via

    a customer-supplied 110/230 VAC net-

    work. They must be connected according to

    DIN and VDE or national active lungs/laws.

    On LMC 301 designs 086500 and 086502

    (IO Board), the power supply is provided

    via 24 V DC.

    The technical information contained in this

    manual must be observed.

    Any other usage is deemed non-compliant

    with the intended use.

    11

    1

    ENEN

    o Fuses must not be bridged. Always re-

    place fuses with fuses of the same type.

    o Ensure proper grounding of the product.

    o Drill holes required for assembly only on

    non-critical, non-load-bearing parts.

    o Other units of the machine/the vehicle

    must not be damaged or impaired in their

    function by the installation.

    o No parts of the centralized lubrication

    system may be subjected to torsion,

    shear, or bending.

    o Use suitable lifting gear when working

    with heavy parts.

    o Avoid mixing up/incorrectly assembling

    disassembled parts. Label parts.

  • 1. Safety instructions

    12

    ENEN

    1.9 Disclaimer of liability

    The manufacturer shall not be held liable for

    damage resulting from:

    o Failure to comply with these instructions.

    o The use of lubricants/media not approved

    for the unit type.

    o Contaminated or unsuitable lubricants.

    o Installation of non-original SKF

    components.

    o Inappropriate usage.

    o Improper assembly, configuration or filling.

    o Improper reaction to malfunctions.

    o Non-observance of maintenance intervals.

    o Independent modification of system

    components.

    1.10 Referenced documents

    In addition to this manual, the following

    documents must be observed by the re-

    spective target group:

    o Operational instructions/approval rules.

    o Instructions from suppliers of purchased

    parts.

    o Manual for the insulation resistance tester

    o Project planning documents and other

    relevant documents

    The operator must supplement these docu-

    ments with applicable regulations for the

    country of use.

    The documentation must be included if the

    product is transferred to a new operator.

    1.11 Warning labels on the product

    The following warning labels are affixed to

    the product. Before commissioning, check

    that the labels are present and intact.

    Immediately replace warning labels if dam-

    aged or missing. The product must not be

    operated until then. See the positioning

    diagram for the order number and position

    on the product.

    Positioning of warning labels, Fig. 1

    Order No. : 246-078-289

    Order No : 44-1826-3122

  • 1. Safety instructions

    13

    1

    ENEN

    1.12 Residual risks

    Table 1

    Residual risk Remedy

    Life cycle: Assembly/commissioning/operation/setup and retrofit

    Electric shock due to defective or incor-rectly connected power lead on power supply or load relay

    • Inspect the power lead for damage before starting the product

    • Correctly wire/connect the power lead

    Tearing/damage to lines when installed on moving machine components

    • When installed on movable equipment use flexible lines

    Life cycle: Malfunction, troubleshooting, maintenance, repair/decommissioning and disposal

    Electric shock due to defective power lead on power supply

    • Inspect the power lead for damage before starting the product

    Electric shock from open control cabinet or active energized components

    • Disconnect the customer-provided main switch or mains plug (cut power) before performing any work on electrical components• Exercise caution when operating the product

  • 2. Overview/System description

    Display, Fig. 2

    PUMP A B C

    RUN

    LL

    FAULT

    POWER RESET

    LMC 301

    2. Overview/System description

    PUMP A B C

    RUN

    LL

    FAULT

    POWER RESET

    LMC 301

    CAUTION!Do not use rigid electrical conduits.

    ACHTUNG!keine starren Elektroinstallations-rohre verwenden.

    PUMP A B C

    RUN

    LL

    FAULT

    POWER RESET

    LMC 301

    14

    The installation of the cable glands and the customer provided cord sets to be done by the customer. The customer is responsible for proper installation.Cable glands and conduits -see chapter Accessories, page 83.When mounting the customer connecting cable no rigid connection pipe must be used - see sign (1) on the controller ground.

    1

    EN

  • 2. Overview/System description

    15

    2 Status Overview and triggering an additional lubrication

    Symbol Status Function

    Press the arrow key to receive a status overview of the pumps resp. zones

    (P1Z1 = Pump 1/Zone1 to max. P3Z3 Pump 3/Zone 3).

    Press the arrow key again to display the residual pause time resp. residual runtime of the currently

    selected pump/zone (e. g. P1Z1).

    Press the arrow key again to display the activated inlets of the currently selected pump/zone.

    Press the arrow key again to display the activated outlets of the currently selected pump/zone.

    Press the "additional lubrication" key shortly to carry out an additional lubrication of the entire system

    respectively of the activated zones (P1Z1 = pump 1/zone1 to max. max. P3Z3 pump 3/zone 3).

    Overview StatesP1Z1

    P1Z2

    P1Z3

    States/Timer P1Z1P1Z1State: Hold (Pause/Lube)Cycle Time:

    Inputs (1) P1Z1

    State: Lube

    Outputs (1) P1Z1

    State: Lube

    Pump: O

    Valve A/B: O

    Additional lubrication

    komplett

    P1Z1

    P1Z2

    P1Z3

    EN

  • 2. Overview/System description

    Display and control elements of control screen

    Symbol Designation Function

    Display o Menu display / Display of values and parameters / Fault notification o The right bar ( ) indicates that the menu extends beyond the current display

    PUMP PUMPPumps A B C

    Pump / main line A / B / C per pumpMax. of 3 main lines possible

    RUN RUNningActive control

    LED lights up =Indication of currently active pump/active control line (A/B/C)

    LL Low LevelMinimum fill level reached

    LED lights up =Minimum fill level (pump A/B/C) reached

    FAULT FAULTError notification

    o LED flashes = Error detected o LED lights up = Fault present

    POWER POWERControl unit On/Off

    LED lights up = Control unit switched on

    Function keys Control key in combination with the display above the key

    Up arrow key menu control / increase input value

    "Down" arrow key menu control / reduce input value

    Pressing triggers an interim lubrication.

    Briefly pressing starts all systems

    Actuations while in configuration mode are ignored.

    RESET

    Long pressing (> 3 seconds) stops all systems or resets an error message.

    Long pressing acknowledges and clears error messages.

    RESET

    16

    EN

  • 2. Overview/System description

    Display elements of the control screen

    Symbol Status Function

    Stopped/OFF o The system was stopped by pressing the Reset key and can

    be restarted by briefly pressing the Running key.

    Pause o Respective lubrication zone is in interval time

    Wait Temperature o Waiting period temperature

    Wait o Lubrication zone waiting because another zone currently

    being lubricated

    Lube o System is lubricating

    Hold o Holding time

    Pressure relief o System is relieving pressure

    Runtime o Pump is running

    Secured/access denied

    o No access as local admin or supervisor

    Access o Access as local admin or supervisor

    Fault o Fault is present

    Digital inputs and outputs on

    o Digital output is enabled

    Digital inputs and outputs off

    o Digital output is disabled

    T

    !

    2.1 LMC 301 controller unit

    The SKF LMC 301 Controller is used to

    control SKF Single Line centralized

    lubrication systems.

    Depending on the system design, up to

    three independent lubrication zones can be

    controlled.

    The SKF LMC 301 controller handles control

    and monitoring of the system. The current

    system status is shown on the LMC 301

    controller's display. The user can quickly

    adapt the lubrication procedure by changing

    the lubrication intensity

    .

    The SKF LMC 301 Controller offers the

    following pump settings according to the

    system design:

    o Up to three lubricant pumps.

    o Up to three lubrication zones (zones 1

    to 3) per pump (main lines 1 to 3).

    o Type of zone valves via 2/2 or

    3/2 directional solenoid valves.

    o Time- or pressure-based lubrication

    monitoring.

    17

    2

    EN

  • 2. Overview/System description

    o Pump control and monitoring.

    o Temperature monitoring by internal or

    external sensor.

    o Automatic filling.

    The SKF LMC 301 controller offers configu-

    rations for the following zone settings for

    each zone:

    o Cycle Control, control mode time-based

    or counter-based.

    o Cycle Control for "light" or "heavy"

    machine requirement with according

    selection of "Light" or "Heavy" lubrication.

    o Lubrication settings, setting of lubrication

    time or, with counter control, the number

    of pulses delivered by the machine.

    o Flow rate monitoring.

    o Alarm outputs and defined fault

    diagnostics.

    Some system settings and timings can be

    modified by the customer via the password

    level pocal Admin.

    The previous settings can also be reset

    to the default settings via the menu item

    Set Params to Default.

    )See Figure 3 on page 20

    The following descriptions applies to a Single

    Line centralized lubrication system with two

    zones (two main lines).

    The two zones are relieved via a reversing

    valve downstream of the pump unit.

    Both main lines are switched via a 2/2

    directional solenoid valve upstream of the

    respective main line.

    Prelubrication or relubrication distributors

    can be used as the Single Line distributors.

    Depending on the design, the changeover

    signal is sent by a shared pressure switch

    (PT) or a pressure switch assigned to one of

    the zones.

    The pressure switch(es) can be designed as

    NO-contacts (close when pre-defined pres-

    sure is reached) or NC contacts (open when

    pre-defined pressure is reached).

    The fill level is monitored by a fill level switch

    in the pump reservoir.

    It can be designed as a NO-contact or an NC

    contact.

    2.2 General design of a Single Line

    centralized lubrication system

    18

    EN

  • 2. Overview/System description

    Another system design involves using

    3/2 directional solenoid valves instead of the

    2/2 directional solenoid valves. In that case,

    pressure is relieved via an additional relief

    line (7).

    This system design does not require an ad-

    ditional relief valve.

    2.2.1 System design

    )See Figure 3 on page 20

    Pressure is built up from the pump element

    (1) via the mechanical pressure relief valve

    (2) and the downstream main lubrication

    line (3) to the solenoid valves of zone 1 (4)

    and zone 2 (5), and from there to the down-

    stream Single Line distributors (6).

    The pump feeds lubricant via the mechanical

    pressure relief valve (2) and the main line

    (3) to both solenoid valves of zone 1 (4) and

    zone 2 (5).

    Depending on the programming, one of

    the two solenoid valves is open, resulting

    in pressure build-up of the lubricant in the

    corresponding zone, while the other solenoid

    valve is closed.

    The lubrication proceeds as follows on a

    Single Line centralized lubrication system

    with prelubrication distributors:

    The pump feeds lubricant to the respec-

    tive zone (main line) until all prelubrication

    distributors have dispensed their defined

    quantity of lubricant to the respective lu-

    brication lines. The pressure switch sends a

    signal to the controller that the changeover

    is finished. The controller then switches off

    the pump and the mechanical pressure re-

    lief valve (2), which leads to pressure relief in

    the main line and the previously active zone

    (main line).

    The active solenoid valve (4 or 5) switches

    to an open state once its holding time has

    elapsed.

    After pressure relief has been performed,

    the zones (main lines) are prepared for an-

    other lubricating cycle.

    The lubrication proceeds as follows on a

    Single Line centralized lubrication system

    with relubrication distributors:

    The pump feeds lubricant to the respective

    zone (main line) until a predefined pressure

    is reached. The pressure switch (PT) then

    switches and sends a signal to the controller.

    The controller switches off the pump and

    19

    2

    EN

  • 2. Overview/System description

    switches the pressure relief valve to relief,

    resulting in pressure relief in the main line

    and the previously active zone (main line).

    This causes the relubrication distributors to

    relieve pressure, and lubricant is delivered to

    the respective lubrication lines.

    The active solenoid valve (4 or 5) switches

    to an open state once its holding time has

    elapsed.

    After pressure release has been performed,

    the system is now prepared for another lu-

    bricating cycle.

    The pump fill level is monitored by a fill level

    switch in the pump reservoir.

    2/2 directional solenoid valves and relief valve

    3/2 directional solenoid valves and relief line

    Zone 1 (main line 1)

    Zone 2 (main line 2)

    Zone 1 (main line 1)

    Zone 2 (main line 2)

    System diagrams of Single Line centralized lubrication systems, Fig. 3

    M

    T

    P

    PT

    M

    T

    P

    PT

    PT

    20

    EN

  • 3. Technical data

    21

    3

    3. Technical data

    Characteristics, design

    GeneralMounting position Vertical, refer to graphic, see page 14Dimensions (L x W x H) 10.6299 x 6.6929 x 3.5433 inDisplay 2.3622x1.1811 in 128x64 pixels

    Environmental conditions Altitude, up to AC 2000m / DC 5000mAmbient/Operating temperature AC 14 to + 122 °FAmbient/Operating temperature DC- - 40 to + 158 °FMaximum relative humidity 80 % for temperatures up to 31 °C decreasing linearly to 50 % relative humidity at 40 °CThe LCD display only operates down to -4°FStorage temperature - 40 to + 158 °F

    Application ≤ 150 VAC Indoor/Outddor applications 3), UL overvoltage category III, pollution degree 2 > 150 ≤ 240 VAC only for indoor applications, UL overvoltage category II, pollution degree 2

    Connectivity via terminal blockInputs: 10 count, short-circuit-proof, 2 are analog capableOutputs: 8 count, relay outputs NO-contact 8A

    Residual ripple relative operating voltage ±5% acc. to DIN 417 55

    3.1 General technical data 2

    EN

  • 3. Technical data

    22

    Characteristics, design

    Output rating relaysConnection directly to the relay 01/02 100-240 VAC/ max. 15AConnection directly to the relay 01/02 24 VDC/ max. 15AOutput terminal block 01 bis 08 24 VDC; 100-240 VAC/max. 8A

    Note: Do not mix 2 different voltages together (AC and DC) on one terminal block!

    Safety per DIN EN 60204-1Safety class Class I

    Customer connection cablesTemperature resistance of >158 °F

    EMCInterference suppression VDE 0875 T 11, EN 55011 Class AEmitted interference acc. to EN 61000-6-3Immunity acc. to EN 61000-6-2

    NoteThe emitted interference meets the requirements for industrial use; use in a residential area may cause interference under some circumstances.

    LMC 301 Version Order No.24 VDC 086500100 to 240 VAC 08650124 VDC I/O 086502100 to 240 VAC I/O 086503

    Characteristics, design

    Protection and monitoringCurrent limit Sustained short-circuit-proofOverload-proof/ Open-circuit-proof Yes

    Protection class 1) 4) IP 65, protection class only with appropiate cable glands PG-M20, without UL certification

    Electronic consumingIternal fuse (LMC-Controller) 3 A Input ACInput voltage 100-240 VAC (50/60Hz)customer Fusing (slow). 4 A (100-240 VAC)

    Input DC 2) 3)Input voltage 24 V DC ±10%custermer Fusing (slow) 10 A

    1) strain relief kid/cable glands -see page 832) Applicable precautions for proper operation: “ Protective Extra Low Voltage“ (PELV) and “Safe Extra Low Voltage“ (SELV). 3) The application as Outdoor (outdoor installation) has not been tested in connection / certification with the UL standard4) The degree of protection class for the controller LMC 301 has not been tested in connection with the UL certification

    EN

  • 4. Delivery, returns, and storage

    23

    4

    3

    4. Delivery, returns, and storage

    Do not top load / This side up

    Keep dry

    Handle with care, Do not drop

    4.3.2 General notes

    o The product can be wrappedin plastic film

    to provide low-dust storage.

    o Protect against ground moisture by storing

    on a shelf or wooden pallet.

    Bare metallic surfaces must be protected

    using anti-corrosion agents Check corrosion

    protection every 6 months and reapply if

    necessary.

    Immediately after receipt, the delivery must

    be checked for completeness according

    to the shipping documents. Any transport

    damage must be reported to the transport

    company immediately. The packaging material

    should be preserved until any discrepancies

    are resolved.

    4.3.1 Electronic and electrical devices

    o Dry and dust-free surroundings, store in

    well ventilated dry area.

    o Storage time: max. 24 months.

    o Relative humidity: < 65%.

    o Storage temperature: -40 - +158 °F.

    o No direct sun or UV exposure.

    o Protected against nearby sources of heat

    or cold.

    4.1 Checking the delivery

    4.2 Returns

    WARNING

    Personal injury/property damage

    Do not drop the product.

    4.3 Storage

    The following conditions apply to storage:

    Before return shipment, all parts must be cleaned and properly packed (i.e., according to the requirements of the recipient country).

    There are no restrictions for land, air, or

    sea transport.

    The following must be marked on the packaging of return shipments:

    EN

  • 5. Assembly

    NOTE

    Observe the technical data (Chapter 3).

    WARNING

    Electric shock

    De-energize controller unit before

    beginning work.

    Only qualified personnel autho-

    rized by operator may perform

    work on Lubrication Monitor

    Controller.

    Electrical operating conditions and

    local regulations (e.g., DIN, VDE)

    must be observed.

    24

    5. Assembly

    Only qualified technical personnel may

    install, operate, maintain, and repair the

    LMC 301 Lubrication Monitor Controller.

    Qualified technical personnel are persons

    who have been trained, assigned, and in-

    structed by the Owner of the final prod-

    uct into which the described Lubrication

    Monitor Controller is incorporated.

    Such persons are familiar with the rele-

    vant standards, rules, accident prevention

    regulations, and operating conditions as

    a result of their training, experience, and

    instruction. They are qualified to carry

    out the required activities and in doing so

    recognize and avoid potential hazards.

    The definition of qualified personnel

    and the prohibition against employing

    non-qualified personnel are laid down in

    DIN VDE 0105 and IEC 364.

    Before assembling/setting up the Lubri-

    cation Monitor Controller, the packaging

    material and any shipping braces (e.g.,

    plugs) must be removed.

    Keep all packing material until product has

    been inspected and no defects are found.

    5.1 General information 5.2 Setup and attachment

    The product should be protected from

    humidity and vibration, and should be

    mounted so that it is easily accessible, allowing

    all further installation work to be done with-

    out difficulty. Ensure that there is sufficient

    air circulation to prevent excessive heating.

    For the maximum permissible ambient tem-

    perature, see "Technical data, Chapter 3."

    The mounting position of the product is as

    shown in the assembly drawing (Page 24).

    WARNING

    Personal injury/property damage

    Drill assembly holes in such a way

    that no lines, units, or moving

    parts are damaged or their function

    impaired.

    Maintain safety clearances and

    comply with regulations for as-

    sembly and accident prevention.

    EN

  • 5. Assembly

    25

    5

    Fig. 4

    5.2.1 Port dimensions, assembly holes, and minimum mounting dimensions

    C

    B

    A

    6.0

    2

    10.31

    9.72

    10.67

    6.6

    89

    9

    2.7

    6

    3.5

    4

    105 °

    0.17

    0.0

    4

    Minimum mounting dimensions

    A = width: 12.99 inB = height 17.72 inC = depth 13.78 in

    EN

  • 5. Assembly

    26

    5.2.2 Opening the controller unit

    Opening the controller unit, Fig. 5

    • Insert a flat tip screwdriver (1) with a

    maximum blade width of 0.22 in into the

    opening slot (2)

    • Turn the screwdriver (1) slightly into the

    gap, pusch the screwdriver to the right to

    open the cover (3)

    )Open the cover with screwdriver up to briefly clicking and then opening the cover

    by hand.

    ) See Figures 4 and 5

    5.2.3 Minimum mounting dimensions

    To ensure enough space for maintenance

    work and possible disassembly of the product,

    ensure that the minimum mounting dimen-

    sions (Fig. 4) are maintained.

    5.2.4 Assembly of the controller unit

    ) See Figure 4The controller unit is installed by using 4

    cylinder-head screws of thread size M4.

    If M4 tapped bores are used to fasten the

    unit, the screws must have a minimum

    length of 15 mm.

    Fastening material to be provided by the

    customer:

    o Cylinder-head screws with hexagon socket

    (4x) according to DIN6912-M4x.. -8.8,

    o Washers (4x) acc to.

    DIN EN ISO 7090-4-200HV

    o Self-locking nuts M4 (4x) according to

    DIN EN ISO 10511

    • Drill assembly holes (Ø 0.1 in) accord-

    ing to assembly drawing (Fig. 4) and the

    conditions on the mounting surface.

    • Clean surface to remove drilling chips.

    • Open the controller unit, place it on the

    surface, and roughly align it.

    • Pass cylinder-head screws (4x) through

    the fixing holes on the controller unit and

    the mounting surface.

    • Apply washers to cylinder-head screws,

    gently tighten cylinder-head screws.

    • Tighten the cylinder-head screws to a

    torque of 4Nm (35 lbf in.)

    1

    2

    3

    EN

  • 5. Assembly

    NOTE

    Mains voltage (supply voltage) must

    match specifications on rating plate of

    Lubrication Monitor Controller. Check fuse

    protection of electrical circuit. Use only

    fuses with prescribed amperage.

    27

    5

    5.3 Electrical connection

    5.3.1 General

    The controller unit is supplied with

    100 to 240 VAC voltage or optionally with

    24 V DC voltage.

    In both designs, the cables are introduced

    through a cable fitting with a clamping

    range of Ø 0.18 in to 0.39 in and terminal

    blocks with tension springs (maximum con-

    ductor cross-section 0,1 in, conductor strip-

    ping length 0.59 in).

    Refer toChapter 4, Technical Data, Chapter

    3, for the electrical characteristics of the

    controller unit.

    The connections on the controller unit are

    established according to the customer-

    specific design of the lubrication system/

    main lines. The system manufacturer is thus

    liable for correct connection to the controller

    unit.

    EN

  • 5. Assembly

    NOTE

    On the controller unit's electrical

    connections, ensure that appropriate

    measures prevent interference

    between signals due to inductive,

    capacitive, or electro-magnetic

    couplings.

    Shielded cables must be used in

    places where electrical interference

    fields can distort signal transmis-

    sions despite separate laying of

    cables.

    The rules and empirical values for

    "EMC-compliant" cabling must be

    taken into consideration.

    NOTE

    Lubrication Monitor Controller

    contains electronic components

    that can be destroyed by accidental

    electrostatic charge or discharge

    (ESD). Use appropriate measures to

    prevent interference between

    signals due to different types of

    couplings. due to ESD, hands and

    any tools must be discharged on

    a bare grounded position on the

    installation site prior to performing

    any work on the opened controller

    unit. Conductors or components

    within the device must not be

    touched under any circumstances.

    NOTE

    An appropriate switch or circuit-breaker

    (min. 10A) who protect all pole must be

    included in the building installation and

    shall be in close proximity to the equip-

    ment within easy reach of the OPERATOR.

    The disconnecting device shall be marked

    as the device for the equipment.

    28

    EN

  • 5. Assembly

    29

    5

    Legend to Figure 6

    Item Description Chapter

    1 Power supply X1 5.3.6

    1aInternal 100 to 240 VAC connection for the AC/DC power supply unit

    1bInternal 24 VDC connection from AC/DC power supply unit to the board

    2 Digital inputs X2 5.3.9

    3 DigitalAnalog inputs X3 5.3.10

    44.1 Relay Outputs X4

    5.3.84.2 Relay Outputs X4

    5 RS485-Interface

    6 24 VDC output for mainboard

    7USB port (external)Not for User

    8 DIP switch addresses 5.3.11

    9 RESET switch Hardware Reset

    10 Fuse (FK1) 3A acc. to ISO 8820-3

    11 Load switching relay (2x) X5 5.3.7

    12

    PE/Ground terminals for relay outputs X6Ground connection mustmade by the customer !

    5.3.8

    5.3.2 Terminal board 100 to 240VAC

    NOTEYou can run each terminal block (4.1 or 4.2) only with one operating voltage (24 VDC or 100 to 240 VAC). Do not mix 2 different voltages together on 1 terminal block!

    Connections on mainboard, design 100 to 240 VAC, Fig. 6

    1a 1 10 1b 2 11 4.2

    6 5 8 7 9 3 12 4.1

    Cable glands for sensors

    Cable glands for power supply/interface Cable glands for valves/motor

    EN

  • 5. Assembly

    30

    5.3.3 Terminal board 24 VDC

    Legend to Figure 7

    Item Description Chapter

    1 Power supply X1 5.3.6

    2 Digital inputs X2 5.3.9

    3 Digital/Analog inputs X3 5.3.10

    44.1 Relay outputs X4

    5.3.84.2 Relay outputs X4

    5 RS485 Interface

    6 24 VDC output for main board

    7 USB port (external)

    Not for User

    8 DIP switch addresses 5.3.11

    9 RESET switch

    Hardware Reset

    10 Fuse (FK1) 3A acc. to ISO 8820-3

    11 Load switching relay (2x) X5 5.3.7

    12 PE Ground terminals for

    relay outputs X6

    Ground connection must

    made by the customer !

    5.3.8

    NOTEYou can run each terminal block (4.1 or 4.2) only with one operating voltage (24 VDC or 100 to 240 VAC). Do not mix 2 different voltages together on 1 terminal block!

    1 10 2 11 4.2

    Connections on mainboard, design 24 VDC, Fig. 7

    Cable glands for sensors

    Cable glands for power supply/interfaceCable glands for valves/motor

    6 5 8 7 9 3 12 4.1

    EN

  • 5. Assembly

    31

    5

    ) See Figures 6 and 7

    5.3.4 Line routing

    The lines are routed through cable glands

    on both sides and the bottom

    Cable glands are provided for the following

    lines:

    optinal Cable glands on left side:

    o Power supply.

    o Master/slave connection.

    optional Cable glands on right side:

    o Relay outlets (load-dependent).

    o Pump motor.

    Cable glands on bottom:

    o Inputs and outputs for monitoring units

    (sensors).

    • Loosen the cable gland.

    • Route the connection cable (provided by

    customer) into the cable gland.

    • Connect the cable according to the wiring

    diagram (see Figs. 9 to 16).

    • Tighten the cable gland.

    ) See Figures 6, page 27 and 7, page 28, item 1, and Fig. 8

    The cables on the terminal strips for:

    o Power connection (item 1).

    o Digital outputs (item 2).

    o Analog outputs (item 3).

    o Relay (item 4).

    are connected via a tension spring

    mechanism.

    Perform the following:

    • Press the tension spring back using the

    flat tip screwdriver.

    • Insert flexible cable leads into the

    terminals.

    • Release pressure on the tension spring

    • Check that the wires are securely con-

    nected .

    5.3.5 Connecting wires

    Fig. 8

    Wiresstripped Length 15 mm

    Terminal strip

    Tension spring

    Flat tip screwdriver

    maximum

    cable insulation section

    to customer-sided

    of cable 2.5 mm2

    EN

  • 5. Assembly

    X1 X1

    32

    5.3.6 Power supply 100 to 240 V AC and 24 V DC

    Terminal diagram 100 to 240 VAC, Fig. 9

    ) See Figure 6, item 1, and Fig. 9

    Terminal diagram 24 VDC, Fig. 10

    • Connect customer-provided cable for

    power supply acc. to terminal diagram

    24 V DC, Fig. 10.

    • Connect customer-provided cable for

    power supply acc. to terminal diagram

    100 to 240 VAC, Fig. 9.

    )The 24 VDC are generated internally . Not Connect externally generated 24 VDC

    supply + and terminal -

    5.3.7 Load switching relay

    ) See Figures 6/7, item 11, and Fig. 11

    Example Load switching relay, Fig. 11

    • Connect (loop) customer-provided load

    voltage cable to both terminals of the load

    relay. Fig. 11.

    ) See Figure 7, item 1, and Fig. 10

    O 3

    O 2

    O 2

    O 1

    O 1

    Input 230 VACmax. 8 Ampere

    Input 230 VACmax. 8 Ampere

    M

    Outputmax. 8 Ampere

    M

    Input 230 VAC, max. 15 Ampere

    Input 24 VDC, max. 15 Ampere

    Input 230 VAC,

    max. 15 Ampere

    Input 24 VDC,

    max. 15 Ampere

    M

    Relay 2

    Relay 1

    Connection up tomax. 8 amperes

    Load relay

    controlled

    directly

    X5

    EN

  • 5. Assembly

    NOTEYou can run each terminal block (4.1 or 4.2) only with one operating voltage (24 VDC or 100 to 230 VAC). Do not mix 2 different volt-ages together on 1 terminal block!

    33

    5

    O 4

    O 4

    O 3

    O 3

    O 2

    O 2

    O 1

    O 1

    O 8

    O 8

    O 7

    O 7

    O 6

    O 6

    O 5

    O 5

    Ground

    Power

    5.3.8 Terminal strip for relay outgoing terminal

    The outputs on the terminal strip X4 are

    provided for downstream relays or loads

    installed by the customer.

    Note the following:

    Two terminal rows (e.g.: 01/01) are

    provided for each connection. Both are

    connected to the switching contacts of the

    corresponding relay. The customer's power

    supply must be connected to one of the

    terminal rows, while the load contact is

    connected to the second, opposite terminal

    row. The ground connection is established

    via the ground terminal strip on the con-

    troller, which must be grounded by the cus-

    tomer (see Figure 13). The load on outlets

    01 and 02 can optionally also be connected

    directly to the load relay (see Fig. 11).

    Connections in conjunction with load switching relay Max. 8 Ampere

    Terminal diagram for relay outgoing terminal, Fig. 12

    O 4

    O 4

    O 3

    O 3

    O 2

    O 2

    O 1

    O 1

    O 8

    O 8

    O 7

    O 7

    O 6

    O 6

    O 5

    O 5

    O = Output

    Terminals

    O3 to O8

    Max. 8 Ampere

    Connections in conjunction with load switching relay Max. 8 Ampere

    X4

    01/01 connection example for relay outputs,

    Fig. 13

    Signalmonitoring

    Reversing valve

    Pump motor,Connection max. 8 Ampere

    X64.1

    4.2

    4.1

    4.2

    )see Figures 6/7, item 4, and Figs. 12 and 13

    Ground connection must

    made by the customer !

    EN

  • 5. Assembly

    34

    )See Figures 6/7, item 2, and Fig. 14

    5.3.9 Terminal strip for digital inputs

    Terminal strip for digital inputs, Fig. 14

    +

    I 3

    I 4

    -

    +

    I 5

    I 6_

    +

    I 7

    I 8

    -

    +

    I 9

    I10_

    I = Input

    The digital inputs are provided for:

    o Pressure switch

    o Proximity switch

    o Flow sensor

    o Fill level switch

    o Interim lubrication switch

    • Connect power supply for digital switch (+)

    to plus terminal (+)

    • Attach ground connection for analog

    switch (-) to minus terminal (-)

    • Attach signal line for digital switch to

    corresponding input terminal (I3 to I10)

    5.3.10 Terminal strip for analog inputs

    Terminal strip for analog capable inputs,

    Fig. 15

    +

    I 1

    I 2_

    I = Input

    The analog inputs are provided for:

    o Pressure transducer

    o Temperature switch

    o Switch polled in mA or volt, e.g.,

    4-20 mA, 1-6 volt

    • Connect power supply for analog switch

    (+) to plus terminal (+)

    • Connect ground connection for analog

    switch (-) to minus terminal (-)

    • Connect signal line for analog switch to

    corresponding input terminal (I1 /I2)

    )See Figures 5/6, item 3, and Fig. 15

    X2

    X3

    Plus

    Minus 1)

    Plus

    Minus

    1) 2 wire sensors do not need minus.

    EN

  • 5. Assembly

    NOTE

    A separate address must be assigned to

    each IO board!

    To differentiate between multiple IOPCBs in

    an RS485 daisy chain, each IOPCB needs its

    own address.

    This can be set in the binary code using the

    DIP switch (address switch).

    If all four DIP switches are set to top , the

    address is "1". See Figure 16 for further

    addresses.

    Adr. 1

    Adr.2

    Adr.8

    +

    NOTEshielded cables use.Maximum cable length 200 m

    35

    5

    5.3.11 Adding an additional IO connection to RS485 daisy chain

    Another IPCB communication connection

    can be established using the two RS485

    connectors (5).

    Up to 7 IOPCBs can be connected to a

    mainboard. Each IOPCB must be supplied

    separately.

    Set IO addresses, Fig. 16

    ON

    1 2 3 4

    ON

    1 2 3 4

    ON

    1 2 3 4

    ON

    1 2 3 4

    ON

    1 2 3 4

    ON

    1 2 3 4

    ON

    Off

    ON

    1 2 3 4

    ON

    1 2 3 4

    Address 1 Address 2

    Address 3 Address 4

    Address 5 Address 6

    Address 7 Address 8

    Daisy chain with external IO boards, Fig. 17

    )See Figures 6/7, item 8 )See Figures 16/17

    +

    EN

  • 5. Assembly

    36

    5.4 Note on the rating plate

    The rating plate provides important data

    such as the type designation, order number,

    etc.

    To avoid loss of this data in case the rating

    plate becomes illegible, these characteristics

    should be entered in the manual.

    P No. ________________________________

    S No. ________________________________

    Model ________________________________

    5.5 Information on CE marking

    The CE marking is based on the requirements of the applied Directives:

    o 2014/30/EC Electromagnetic Compatibility

    o 2011/65/EU (RoHS II) Directive on the restriction of the use of certain hazardous

    substances in electrical and electronic equipment

    o 2006/95/EG (LVD) Use of electrical equipment within certain voltage limits

    Note on Pressure Equipment Directive 2014/68/EU (if pressurized parts are present)

    Due to its performance characteristics, the product does not reach the limit values defined in

    Article 4, Paragraph 1, Subparagraph (a) item (i) and is, pursuant to Article 4, Paragraph 3,

    excluded from the scope of Pressure Equipment Directive 2014/68/EU.

    Rating plate, Fig. 18

    SKF Lubrication Systems Germany GmbH

    Made in Germany D-69190 Walldorf

    02/16

    Model: LMC 301

    2016100024/001 A

    0865..

    Serial-No:

    P.No.:S-No:

    I= 4 A

    2016100024/001 A

    U=

    Proc.Cont.Eq.

    EN

  • 5. Assembly

    37

    5

    EN

  • 6. Configuration by operator/local admin

    6. Configuration by operator/local admin

    General

    38

    There are two options for configuring the

    controller:

    o Configuration with PC software and USB

    connection -see Chapter 6.1.

    The PC software application is designed for

    Windows XP, Windows 7, and Windows 8

    operating systems and is included as data

    media with the controller. The software

    can also be downloaded as freeware from

    the SKF website. After installing the pro-

    gram, data transfer occurs

    via the USB interface in the controller.

    SKF recommends this procedure for

    initial installations.

    o Configuration of the system using the dis-

    play attached to the controller and menu

    keys - See Chapter 6.2.

    The complete configuration can be done

    via the controller display and the associ-

    ated menu keys.

    6.1 Configuration of the controller unit with PC software

    • From the SKF homepage

    http://www.skf.com/pMC301/

    download the file of LMC 301 software

    pMC 301 PC Software

    • Close all applications on the laptop.

    • Open the file.

    )The LMC 301 software installs automati-cally. SKF recommends not starting any

    other applications during this period.

    • Install the controller unit (Chapter 5)

    • Open the controller unit (Chapter 5.2.2)

    • Connect the USB cable (2) from the laptop

    on the inside of the controller lid (1).

    • Turn on the power supply-

    Connect the USB cable, Fig. 19

    NOTE

    USB cable may only be

    connected to USB port installed inside

    controller lid of LMC 301. See Fig. 19.

    • Start the LMC 301 software

    )The description of the PC configuration is included with the software.

    • Configure according to the included de-

    scription for configuration on the PC.

    )See Figure 19

    1

    2

    EN

  • 6. Configuration by operator/local admin

    6.2.1 Structure of a lubricating cycle

    Display, Fig. 20

    Pressure build-up time

    Holding time

    Residual system pressure

    Pressure build-up time

    Holding time

    System with 3/2 zone directional solenoid valve System with 2/2 zone directional solenoid valve

    Pre

    ssure

    (MPa)

    Time

    39

    6

    6.2 Configuration of the controller unit via the display on the controller unit

    Opening pressurePressure switch min.

    Pressure relief time Pressure relieftime

    Work cycle time

    Lubrication time =Pump cycle time

    Lubrication time =Pump cycle time

    Interval time Interval time

    Work cycle time

    Opening pressurePressure switch max.

    Cracking pressure

    Pressure regulating valve

    EN

  • 6. Configuration by operator/local admin

    Display, Fig. 21

    PUMP A B C

    RUN

    LL

    FAULT

    POWER RESET

    LMC 301

    6.2.3 Display and control elements of

    the control screen 6.2.2 Status/overview

    After switching on the supply voltage, the

    Overview States menu appears on the

    display.

    The current parameter settings and values

    are displayed. This is done continuously and

    automatically.

    The parameters and settings can optionally

    be accessed using the two arrow keys

    No entries can be made and the symbol

    shows a closed lock .

    To change the configuration, select the

    menu item Menu using the control key .

    This will take you to the Main menu.

    Changes can be made within the main menu

    only after entering the password.

    This is done in the pogin settings menu

    level.

    When entering the password, there is

    a differentiation between pocal Admin

    (customer access) and Supervisor (only ser-

    vice staff, no customer access).

    The open lock icon indicates that the

    system has been unlocked.

    NOTE

    To save data, press the Save control key for

    at least 3 seconds.

    40

    EN

  • 6. Configuration by operator/local admin

    41

    6

    Status Overview and triggering an additional lubrication

    Symbol Status Function

    Press the arrow key to receive a status overview of the pumps resp. zones

    (P1Z1 = Pump 1/Zone1 to max. P3Z3 Pump 3/Zone 3).

    Press the arrow key again to display the residual pause time resp. residual runtime of the currently

    selected pump/zone (e. g. P1Z1).

    Press the arrow key again to display the activated inlets of the currently selected pump/zone.

    Press the arrow key again to display the activated outlets of the currently selected pump/zone.

    Press the "additional lubrication" key shortly to carry out an additional lubrication of the entire system

    respectively of the activated zones (P1Z1 = pump 1/zone1 to max. max. P3Z3 pump 3/zone 3).

    Overview StatesP1Z1

    P1Z2

    P1Z3

    States/Timer P1Z1P1Z1State: Hold (Pause/Lube)Cycle Time:

    Inputs (1) P1Z1

    State: Lube

    Outputs (1) P1Z1

    State: Lube

    Pump: O

    Valve A/B: O

    Additional lubrication

    komplett

    P1Z1

    P1Z2

    P1Z3

    EN

  • 6. Configuration by operator/local admin

    Display and control elements of control screen

    Symbol Designation Function

    Display o Menu display / Display of values and parameters / Fault notification o The right bar ( ) indicates that the menu extends beyond the current display

    PUMP PUMPPumps A B C

    Pump / main line A / B / C per pumpMax. of 3 main lines possible

    RUN RUNningActive control

    LED lights up =Indication of currently active pump/active control line (A/B/C)

    LL Low LevelMinimum fill level reached

    LED lights up =Minimum fill level (pump A/B/C) reached

    FAULT FAULTError notification

    o LED flashes = Error detected o LED lights up = Fault present

    POWER POWERControl unit On/Off

    LED lights up = Control unit switched on

    Function keys Control key in combination with the display above the key

    Up arrow key menu control / increase input value

    "Down" arrow key menu control / reduce input value

    Pressing triggers an interim lubrication.

    Briefly pressing starts all systems

    Actuations while in configuration mode are ignored.

    RESET

    Long pressing (> 3 seconds) stops all systems or resets an error message.

    Long pressing acknowledges and clears error messages.

    RESET

    42

    EN

  • 6. Configuration by operator/local admin

    Display elements of the control screen

    Symbol Status Function

    Stopped/OFF o The system was stopped by pressing the Reset key and can be restarted by briefly pressing the Running key.

    Pause o Respective lubrication zone is in interval time.

    Wait Temperature o Waiting period temperature.

    Wait o Lubrication zone waiting because other zone currently being lubricated.

    Lube o System is lubricating.

    Hold o Holding time.

    Pressure relief o System relieves pressure.

    Runtime o Pump runs.

    Secured/access denied

    o No access as local admin or supervisor.

    Access o Access as local admin or supervisor.

    Fault o Fault is present.

    Digital inputs and outputs on

    o Digital output is enabled.

    Digital inputs and outputs off

    o Digital output is disabled.

    T

    !

    43

    6

    EN

  • 6. Configuration by operator/local admin

    Login settingsUser SettingsDevice settingsPump 1 Timings

    Pump 2 Timings

    Pump 3 TimingsInformation

    Main menu

    Device settingsBacklight

    Contrast

    [ 00% ]

    Date

    [ 00/00/00 ]

    System Clock

    [ 00:00:00 ]

    User settingsUnit Settings

    [imperal] > [metric]

    Language[German] > [English]

    Login settingsEnter Password

    Set PW local adminSet PW Supervisor

    Enter Password

    Please Enter Passwordto Continue0000

    Password correct

    Your locked in as

    Local Operator

    [enablrd > disabled]

    Login settings

    6.2.4 Menu navigation for operators without password access

    44

    EN

  • 6. Configuration by operator/local admin

    Pump 1 Timings

    Zone 1 SettingsZone 2 Settings

    Information

    HW/FW Version

    Hours of operating

    Error history

    Serial Number

    HW/FW Version

    Hardware version

    [.....]

    Firmware version[.....]

    Hours of operation

    Cumulatedoperating Time.................................

    Error historyNo. 1 .........

    !

    Serial Number

    Serial Number

    [00000000]

    Zone 1 Settings

    Lube load

    [Normal Cycle Set] > [Heavy Cycle Set]

    Zone 2 Settings

    Lube load

    [Normal Cycle Set] > [Heavy Cycle Set]

    Lube Event Counter

    P1Z1[ 0]P1Z2[ 0]P1Z3[ 0]

    Lube Event Counter

    Setting options for operators without password access, Fig. 22

    45

    6

    EN

  • 6. Configuration by operator/local admin

    6.2.5 Menu navigation for local admins with password access

    Enter Password

    Set PW local adminSet PW SuperDisor

    Enter PasswordPlease Enter Passwordto Continue0000

    Back OK

    Login settingsUser Settings2eDice settingsPump 1 3imings

    Pump 2 3imings

    Pump 3 3imingsInformationen

    Main menu

    Login settingsEnter Password

    Set PW local adminSet PW SuperDisor

    Enter Password

    Please Enter Passwordto Continue0000

    Password correct

    Your locked in as

    Local Operator

    Login settings Login settings

    User settingsUnit Settings

    [imperial] > [metric]

    Language[German] > [English]

    Device settingsBacklight

    Contrast

    [ 00% ]

    Date

    [ 00/00/00 ]

    System Clock

    [ 00:00:00 ]

    [enablrd > disabled]

    46

    EN

  • 6. Configuration by operator/local admin

    Zone 1 Settings

    Lube Load

    Normal Cycle Time[ 0000: 00:00 ]

    Heavy Cycle Time[ 0000: 00:00 ]

    Lube Time[ 00: 00:00 ]

    Holding time[ 00:00 ] s

    Pump 1 Timings

    Zone 1 SettingsZone 2 Settings

    Zone 2 Settings

    Lube Load

    Normal Cycle Time[ 0000: 00:00 ]

    Heavy Cycle Time[ 0000: 00:00 ]

    Lube Time[ 00: 00:00 ]

    Holding time[ 00:00 ] s

    Information

    HW/FW Version

    Hours of operating

    Error history

    Serial Number

    HW/FW Version

    Hardware version

    [.....]

    Firmware version[.....]

    Hours of operation

    Cumulatedoperating Time.................................

    Error historyNo. 1 .........

    !

    Serial Number

    Serial Number

    [00000000]

    [Normal Cycle Set] > [Heavy Cycle Set]

    [Normal Cycle Set] > [Heavy Cycle Set]

    Lube Event CounterP1Z1[ 0]

    P1Z2[ 0]P1Z3[ 0]

    Lube Event Counter

    Setting options for local admins, Fig. 23

    47

    6

    EN

  • 6. Configuration by operator/local admin

    6.2.6 Main menu

    The main menu shows the following

    options:

    Login settings

    )refer to chapter 6.2.7 pg 49The menu is used to manage

    access to the menus with a password.

    The password can also be changed here.

    User settings

    )refer to chapter 6.2.6(Setting options for operators without

    password access)

    In this menu, the measurement units (metric

    or inch) and the language for the user

    menu can be selected.

    Device settings

    )refer to chapter 6.2.8 pages 51In this menu, the display properties of the

    screen, such as backlight and contrast, can

    be modified. The date and time are also set

    here.

    Main menu, Fig. 24

    Pump 1 Timings

    )refer to chapter 6.2.9 pages 53In this menu, the timing of the pump and

    the settings for the associated main line

    are set

    Information

    )refer to chapter 6.2.10 pages 54The hardware and firmware versions

    are stored in this menu. The hours of

    controller operation, the error history, and

    the serial number of the controller unit can

    also be viewed here.

    Main menu

    Login settings

    User settings

    Device settings

    Pump 1 Timings

    Information

    Back OK

    48

    NOTE

    The description of the main menu is based

    on the setting options that the end cus-

    tomer can adjust.

    (password level Set PW local admin)

    EN

  • 6. Configuration by operator/local admin

    User settings

    Step Key Display Description

    User settings - Set units and menu language

    1

    • Press

    )You will be taken to the main menu

    2

    • Use to select the User settings menu item

    • Confirm with

    ) You will enter the User settings menu

    3

    • Use to select the menu item panguage [English /Deutsch]

    • Press

    • Use to select the language [English /German]

    • Press

    Main menuLogin settings

    User settings

    Device settings

    Pump 1 Timings

    Information

    6.2.7 General setting options without (with) password access

    Overview StatesP1Z1:

    User settingsUnit Settings

    [metric ]

    Language

    [English ]

    Back Select

    Back

    49

    6

    EN

  • 6. Configuration by operator/local admin

    User settings

    Step Key Display Description

    User settings - Set units and menu language

    4

    • Use to select the Unit Settings menu item [imperial/metric]

    • Press

    • Use to select Input Settings [Imperial/Metric]

    • Press

    • Press

    )You will return to the User settings menu

    User settingsUnit Settings

    [metric ]

    Language

    [English ]

    Back Select

    50

    EN

  • 6. Configuration by operator/local admin

    Login settings

    Step Key Display Description

    pogin settings- Enter Set PassWord local admin

    1

    • Press

    )You will enter the pogin settings menu. The following menu items are available: o Enter password (enter existing password) o Set PassWord local admin for customer's personnel (change password)

    o Set PW Supervisor for SKF Service and SKF dealers (change password)

    o If the password has already been entered (open lock), the menu item Log Off is also available.

    • Use to select Set PassWord local admin

    • Press

    )You will enter the Enter Password menu The password contains four characters that can be either numerals or letters.

    • Use to set the first character of the password

    • Confirm the entry with

    • Repeat the entry for the following 3 password characters

    • Press

    )You will return to the pogin Settings menu.

    Main menuLogin settings

    User settings

    Device settings

    Pump 1 Timings

    Information

    6.2.8 Setting options for local admins (setters) with password access

    Enter PasswordPlease Enter Password

    to Continue

    0000

    Cancel OK

    Login settingsEnter Password

    Set PW local admin

    Set PW Supervisor

    Back OK

    Password Correct

    You are logged in as

    Local Admin

    Back OK

    51

    6

    EN

  • 6. Configuration by operator/local admin

    Login settings

    Step Key Display Description

    pogin settings- change existing password

    2

    • Press

    )You will enter the Login settings menu. • Use to select Enter Password

    • Enter current password (see previous chapter)

    • Use to select password level Set PassWord local admin (cus-

    tomer service) or Set PW Supervisor (SKF Service)

    • Press

    )You will enter the Set PW local admin or Set PW Supervisor menu. The current pass-word and the entry field for the new password are displayed in this menu.

    • Enter the new password as described above under Enter Password

    )You will return to the Login Settings menu.

    Main menuLogin settings

    User settings

    Device settings

    Pump 1 Timings

    Information

    Login settingsEnter Password

    Set PW local admin

    Set PW Supervisor

    Log Off

    Back OK

    Local AdminOld password

    0000

    New password

    0000

    Back OK

    6.2.8.1 Changing the password

    52

    EN

  • 6. Configuration by operator/local admin

    6.2.9 Device settings

    Device settings

    Step Key Display Description

    Device settings- Display, system date, and system time

    1

    • Use to select Device settings

    • Press

    )You will enter the Device Settings menu. The following menu items are available: o Backlight (display enabled/disabled)

    o Contrast (display 0-100%)

    o Date (year/month/day)

    o System Clock (seconds/minutes/hours)

    o Use to select a menu item

    • Press

    • Use to set the value

    • Use to save the entry

    )If there are multiple entries, the cursor automatically moves to the next entry field after saving.

    • Press

    )You will return to the Main menu.

    Main menuLogin settings

    User settings

    Device settings

    Pump 1 Timings

    Information

    Device settingsBacklight

    [enabled/disabled]

    Contrast

    [ 60% ]

    Date

    [ 00/00/00 ]

    System Clock

    [ 00:00:00 ]

    Back Select

    53

    6

    EN

  • 6. Configuration by operator/local admin

    6.2.10 Pump 1 timings

    General

    Up to three pumps can be connected

    to the LMC 301 Controller; the maximum

    number of zones (main lines) that the Con-

    troller can control is limited to three. Up to

    three main lines (zone 1 to zone 3) can be

    programmed per pump.

    These can be accessed in the Main menu

    under:

    Pump 1 Timings

    Zone 1 Settings

    Zone 2 Settings

    (if 2nd line available)

    Zone 3 Settings

    (if 3rd line available)

    Depending on the access level, the following

    settings can be made:

    See Pages 40/41, Fig. 22 and 42/43, Fig. 23

    The following entries can be made here:

    o

    or

    o

    The two lubrication settings differ in terms

    of the duration of work cycle time.

    The cycle time consists of the pump cycle

    time + interval time - see Figure 20.

    A longer lubrication time is typically pro-

    grammed for Heavy Cycle Set compared

    with Normal Cycle Set.

    6.2.10.1 Operator level without password access

    54

    EN

  • 6. Configuration by operator/local admin

    Pump 1 Timings

    Step Key Display Description

    Pump 1 Timings User Settings- without password level

    1

    • Use to select

    Pump 1 Timings

    • Press

    )You will enter the Pump 1 Timings menu.

    )The following menu item is available: o Zone 1 Settings

    • Press

    • Press

    • Use to select

    Normal Cycle Set or Heavy Cycle Set

    • Press to save the

    selection

    • Press

    )You will return to the Pump 1 Timings menu.

    Main menuLogin settings

    User settings

    Device settings

    Pump 1 Timings

    Information

    Pump 1 Timings

    Back

    Zone 1 Settings

    Zone 2 Settings

    Pump 1 Timings

    Back

    Lubrication settings

    [Normal Cycle Set]

    Select

    6.2.10.2 Local Admin (setter) or

    Supervisor with password access

    See Page 41 and Pages 45 to 47

    The following entries can be made at the

    password level:

    Zone 1 Settings

    o Selection of lube load

    or , - refer to chapter 6.2.9 pg. 49

    o Entry of for

    basic lubrication

    o Entry of for

    increased lubricant demand

    o Entry of monitoring time

    >

    o Entry of holding time, delay time of

    zone valves

    The procedure is typically identical for set-

    ting parameters for the main lines (zone 1

    to zone 3).

    Set PW local adminFactory setting: 1000

    55

    6

    EN

  • 6. Configuration by operator/local admin

    Pump 1 Timings

    Step Key Display Description

    Pump 1 timings- with password level pocal Admin or Supervisor

    1

    • Use to select Pump 1 Timings

    • Press

    )You will enter the Pump 1 Timings menu. )The following menu items are available:

    o Zone 1 Settings

    o Zone 2 Settings, if applicable

    o Use to select Zone 1 Settings

    • Press

    )You will enter the Zone 1 Settings menu.

    Main menuLogin settings

    User settings

    Device settings

    Pump 1 Timings

    Information

    Pump 1 Timings

    Back Ok

    Zone 1 Settings

    Zone 2 Settings

    Zone 1 Settings

    Back Select

    Lube Load

    [Normal Cycle Set]

    Normal Cycle Time

    [0000 : 00 : 00]

    Heavy Cycle Time

    [0000 : 00 : 00]

    Monitoring Time

    [00:00:00]

    Holding time

    [00:00] s

    Back

    56

    EN

  • 6. Configuration by operator/local admin

    Pump 1 Timings

    Step Key Display Description

    Pump 1 timings- with password level pocal Admin or Supervisor

    2

    )The following menu items are available: o Lube Load: Selection between Normal Cycle Set and Heavy Cycle Set. The two lubri-

    cation settings differ in terms of the duration of cycle time. A longer lubrication time is

    typically programmed for Heavy Cycle Set compared with Normal Cycle Set.

    o Normal Cycle Time: Entry of the time unit for a normal lubrication process. The total

    value to be entered consists of pump cycle time+holding time+interval time. The lubri-

    cation time is the time required by the lubrication system to build up pressure in the

    respective zone until all distributors in the zone have actuated or reversed. The interval

    time is the time differential between the set cycle time and the required pump cycle time

    + holding time. The entry is in hours/minutes/seconds.

    o Heavy Cycle Time: Entry of the time unit for a lubrication process with increased lubri-

    cant demand. The heavy cycle time has the same structure as the normal cycle time. The

    entry is in hours/minutes/seconds.

    o Monitoring Time: Monitoring of lubrication time Pressure build-up must be completed

    within the monitoring time (time slot).

    o Holding time: After the end of the pump cycle time, the controller switches off the pump,

    though pressure relief by the zone valves is delayed by the holding time. The entry is in

    minutes and seconds.

    Zone 1 Settings

    Back

    Select

    Lube Load

    [Normal Cycle Set]

    Normal Cycle Time

    [0000 : 00 : 00]

    Heavy Cycle Time

    [0000 : 00 : 00]

    Monitoring Time

    [00:00:00]

    Holding time

    [00:00] s

    57

    6

    EN

  • 6. Configuration by operator/local admin

    6.2.11 Information

    The information menu presents information.

    Parameters cannot be changed, and error

    Information

    Step Key Display Description

    Information menu - without password level

    1

    • Use to select Information

    • Press

    )You will enter the Information menu. )The following menu item is available:

    o HW/FW Version: Display of the controller unit's hardware and software version

    o Hours of operation: Current number of operating hours of the controller unit

    o Error history: previous error messages, with error coding

    o Serial Number: Serial number of the control unit

    • Use to select a menu item

    • Press

    • Press

    )You will return to the Information menu.• Press

    )You will return to the Main menu.

    Main menuLogin settings

    User settings

    Device settings

    Pump 1 Timings

    Information

    Information

    Back

    HW/FW Version

    Operating hours

    Error history

    Serial No.

    Ok

    messages cannot be cleared.

    Back

    58

    EN

  • 6. Configuration by operator/local admin

    6.3 Single Line system examples

    Several examples of Single Line systems

    with an LMC 301 Controller are listed below

    and can be used as the basis for local ad-

    mins to make their settings.

    The individual examples are divided into

    three sections.

    Section 1 is a brief description of the struc-

    ture of the Single Line centralized lubrica-

    tion system shown.

    Section 2 shows the structure of the

    particular Single Line centralized lubrication

    system (system design) with the associated

    LMC 301 terminal diagram.

    Section 3 shows the customer program-

    ming of the LMC 301 Controller via its dis-

    play and keyboard (see Chapter 6.2).

    59

    6

    EN

  • 6. Configuration by operator/local admin

    LMC301, electrical terminal diagram, Fig. 25

    Design

    The example applies to a Single Line

    centralized lubrication system with two

    zones (zone 1/zone 2 (line 1/line 2)).

    It is composed of the main components

    Single Line pump (1) with mechanical

    pressure relief valve (2) and one pumpout-

    let. A main line (3) connects the pump

    outlet with the two 2/2 directional sole-

    noid valves for zone 1 (4) and zone 2 (5).

    A pressure switch PT (6) is mounted at the

    end of the main line to monitor pressure.

    Chapter 3 contains a general functional

    description.

    )See Figures 25 and 26

    6.3.1 2-zone Single Line centralized lubrication system with 2/2 directional solenoid valves and 1 pressure switch

    O 4

    O 4

    O 3

    O 3

    O 2

    O 2

    O 1

    O 1

    O 8

    O 8

    O 7

    O 7

    O 6

    O 6

    O 5

    O 5

    Ground

    Power

    X4

    X6

    +

    I 1

    I 2_

    X3

    PT

    +

    I 3

    I 4

    -

    +

    I 5

    I 6_

    +

    I 7

    I 8

    -

    +

    I 9

    I10_

    X2

    Terminal +

    Ground -

    Signal I 2

    Valve, zone 2

    Valve, zone 1

    Pump motor, max. 8 amp.

    use also PE vor Valve

    NOTEYou can run each terminal block (4.1 or 4.2) only with one operating voltage (24 VDC or 100 to 240 VAC). Do not mix 2 different volt-ages together on 1 terminal block!

    60

    EN

  • 6. Configuration by operator/local admin

    M

    T

    P

    PT

    (Zone

    2)

    X4

    (Zone

    1)

    X4

    Zone 1 (Schmierstrang 1)

    Zone 2 (Schmierstrang 2)

    (Ground) X6

    PT

    P

    System design, Fig. 26

    (pressure monitoring PT, voltage) X3, terminal +

    (pressure monitoring PT, ground) X3, terminal -

    (pressure monitoring PT, signal) X3, terminal I 1

    (fill level monitoring) X3, terminal I 3

    Pump motor, max. 8 amp.

    61

    6

    EN

  • 6. Configuration by operator/local admin

    Programming via the SKF LMC 301

    Step Key Display Description

    1

    The following requirements are met:

    • User settings have been made according to Chapter 6.2.5, pages 42

    • Login settings have been made according to Chapter 6.2.6, pages 44

    (only at pocal Admin level)

    • Device settings have been made according to Chapter 6.2.7, pages 45

    Timing User Settings

    2

    • Use to select Pump 1 Timings

    • Press

    )You will enter the Pump 1 Timings menu.

    )The following menu item is available: o Zone 1 Settings

    o Zone 2 Settings

    • Use to select the Zone 1 Settings menu item

    • Press

    Main menuLogin settings

    User settings

    Device settings

    Pump 1 Timings

    Information

    Pump 1 Timings

    Zone 1 Settings

    Zone 2 Settings

    Customer programming of the LMC 301 unit via the controller display and controller keys

    62

    EN

  • 6. Configuration by operator/local admin

    Pump 1 Timing and Cycle Control

    Step Key Display Description

    Pump 1 Timing User Settings

    2

    )You will enter the Zone 1 Settings menu. )The following menu items are available

    o or . Entry of lubrication intensity, normal or

    heavy cycle set

    o Normal Cycle Counts: Entry of cycle time for normal cycle set

    o Heavy Cycle Counts: Entry of cycle time for increased lubricant demand (longer pump

    cycle time)

    o Monitoring Time: Monitoring of lubrication time The lubricating cycle must be com-

    pleted within the monitoring time (time slot).

    o Holding time: After the end of the pump cycle time, the controller switches off the pump,

    though pressure relief by the zone valves is delayed by the holding time.

    • Use to select Normal Cycle Set (or Heavy Cycle Set)

    • Press

    • Use to select between Normal Cycle Set /Heavy Cycle Set

    • Press

    • Use to select the Normal Cycle Time menu item

    • Press

    • Use to enter an eight-digit cycle count [hhhh:mm:ss]

    )Press to advance to the next digit• Press

    Zone 1 SettingsLubrication settings

    [Normal Cycle Set]

    Normal Cycle Counts:

    [0000:00:00]

    Heavy Cycle Counts:

    [0000:00:00]

    Monitoring Time

    [00:00:00]

    Holding time

    [00:00]

    63

    6

    EN

  • 6. Configuration by operator/local admin

    Pump 1 Timing and Cycle Control

    Step Key Display Description

    Pump 1 Timing User Settings

    2

    • Use to select the Heavy Cycle Counts menu item

    • Press

    • Use to enter an eight-digit cycle count [hhhh:mm:ss]

    )Press to advance to the next digit• Press

    • Use to select the Monitoring Time menu item

    • Press

    • Use to enter a six-digit cycle count [hh:mm:ss]

    )Press to advance to the next digit• Press

    • Use to select the Holding time menu item

    • Press

    • Use to enter a four-digit cycle count [mm:ss]

    )Press to advance to the next digit• Press

    Zone 1 Settings

    Lubrication settings

    [Normal Cycle Set]

    Normal Cycle Counts:

    [0000:00:00]

    Heavy Cycle Counts:

    [0000:00:00]

    Monitoring Time

    [00:00:00]

    Holding time

    [00:00]

    64

    EN

  • 6. Configuration by operator/local admin

    Pump 1 Timing and Cycle Control

    Step Key Display Description

    Pump 1 Timing User Settings- Zone 2 Settings

    3

    • Use to select the Zone 2 Settings menu item

    • Press

    • Make settings according to the procedure