[Eng. Rec No.11 – Std. Conn. Arr. V 1.1] Page 1 of 18

Engineering Recommendation No. 11 of the Electricity Distribution Code

Standard Connection Arrangements

Version 1.1

09 July 19

Prepared by:

Al Ain Distribution Company, Abu Dhabi Distribution Company,

Approved by:

Department of Energy

Page 2: ER 11 - Standard Connection Arrangements DoE comment 11 Standard Connection Arrangeme… · f 0hwhulqj fxuuhqw wudqviruphuv &7v iru hdfk 8vhu g &xuuhqw dqg ixvhg yrowdjh phwhulqj

[Eng. Rec No.11 – Std. Conn. Arr. V 1.1] Page 2 of 18

CONTENTS

1.0 DESIGN PRINCIPLES ............................................................................................... 3

Introduction ........................................................................................................ 3

Summary of design principles ............................................................................ 3

2.0 STANDARD CONNECTION ARRANGEMENTS ....................................................... 5

Introduction ........................................................................................................ 5

Category A1 - Connections at 400V from LV network or HV/LV substation not

located at the User premises ............................................................................. 5

Category A2 - Connections at 400V from HV/LV substation(s) located

at the User premises .......................................................................................... 6

Category B - Connections at 11kV ..................................................................... 7

Category C - Connections at 22kV ..................................................................... 9

Category D - Connections at 33kV ................................................................... 10

Page 3: ER 11 - Standard Connection Arrangements DoE comment 11 Standard Connection Arrangeme… · f 0hwhulqj fxuuhqw wudqviruphuv &7v iru hdfk 8vhu g &xuuhqw dqg ixvhg yrowdjh phwhulqj

[Eng. Rec No.11 – Std. Conn. Arr. V 1.1] Page 3 of 18

1.0 DESIGN PRINCIPLES

Introduction

1.1 The DISCO shall be responsible for the detailed design, engineering and agreement

by the User of all connections where User Systems are connected to the DISCO

Distribution System. The detailed design and engineering shall consider the User

System contribution to fault current, voltage drop and effects on power quality as well

as ensure compliance with the requirements of the Electricity Supply Regulations

and the Electricity Distribution Code.

1.2 This Engineering Recommendation provides standard connection arrangements for

the connection of User Systems to the DISCO Distribution System. The standard

connection arrangements are relevant to connections at 400V, 11kV, 22kV and 33kV

and for User Systems involving Generator Units and/or Distribution Systems

and/or Equipment connecting Generator Units or Distribution Systems. In addition,

it provides typical LV connections of small-scale Solar PV installation in the User

premises in accordance with The Electricity Wiring Regulations (Third Edition), March

2014 as amended.

1.3 For all Embedded Generator connections, refer to Engineering Recommendation No.3

– Connection of Embedded Generating Plant up to and including 30MW.

Summary of design principles

1.4 The standard connection arrangements for connections of User Systems to the

DISCO Distribution System are based on the following design principles:

(a) to meet the requirements of the Distribution Planning and Connection Code

(DPCC) ;

(b) to meet the requirements of Engineering Recommendation No.4 - Security of

Supply Standard for the Electricity Distribution System ;

(c) to provide for an easily defined and operationally practical Ownership

Boundary i.e. at bolted connection locations of User cables on to DISCO

switchgear ;

(d) to provide DISCO owned and operated interface switchgear at the User

premises that enables integration with the DISCO distribution management

system and disconnection through switching by the DISCO of the User

System;

(e) to facilitate the remote disconnection by the DISCO of each metered Customer

initiated by command via the associated tariff meter ;

(f) DISCO standard assets to be used whereby the design of the connection uses

standard components rated to achieve the required capacity ;

Page 4: ER 11 - Standard Connection Arrangements DoE comment 11 Standard Connection Arrangeme… · f 0hwhulqj fxuuhqw wudqviruphuv &7v iru hdfk 8vhu g &xuuhqw dqg ixvhg yrowdjh phwhulqj

[Eng. Rec No.11 – Std. Conn. Arr. V 1.1] Page 4 of 18

(g) on-going costs for operation, maintenance and repair of DISCO connection

assets to be borne by the DISCO ;

(h) land and buildings (for DISCO connection assets) at User premises to be

funded, provided and maintained by the User with full access rights granted to

the DISCO.

Page 5: ER 11 - Standard Connection Arrangements DoE comment 11 Standard Connection Arrangeme… · f 0hwhulqj fxuuhqw wudqviruphuv &7v iru hdfk 8vhu g &xuuhqw dqg ixvhg yrowdjh phwhulqj

[Eng. Rec No.11 – Std. Conn. Arr. V 1.1] Page 5 of 18

2.0 STANDARD CONNECTION ARRANGEMENTS

Introduction

2.1 There are five categories of standard connection arrangements.

(a) Category A1 - Connections at 400V from LV network or HV/LV substation not

located at the User premises.

(b) Category A2 - Connections at 400V from HV/LV substation(s) located at the

User premises.

(c) Category B - Connections at 11kV.

(d) Category C - Connections at 22kV.

(e) Category D - Connections at 33kV.

2.2 Under special circumstances non-standard connections arrangements may be

adopted subject to special Connection Agreement conditions and the specific

approval of the DISCO Technical Committee.

Category A1 - Connections at 400V from LV network or HV/LV substation not located at the User premises

2.3 Category A1 connections are applicable where the DISCO existing or intended

distribution architecture for the development area can accommodate a Category A1

connection of the capacity required. Should this not be the case then a Category A2

connection shall be applicable.

2.4 The various connection arrangements within Category A1 are shown in Figure 2.1.

2.5 These connections involve DISCO LV cable laid underground from a fuse way of a

DISCO feeder pillar (or service turret) or from a fuse way or moulded case circuit

breaker (MCCB) of a DISCO HV/LV substation not located at the User Premises.

2.6 The DISCO LV service cable will terminate at the LV incomer circuit breaker(s) of the

User main distribution board(s) at the User premises located either in a dedicated

room at the User premises (for premises with multiple Users and single User with

multiple feeders for distribution within the same premises) OR wall mounted panel with

the LV Incomer and meters (with / without CTs) for single User premises subject to

the DISCO acquiring “Control Authority” of the LV incomer circuit breaker(s) and of the

outgoing circuit breaker(s) for User connections i.e. the User cannot operate the LV

** Disco Control authority : is the authority of providing the approval on the point of isolation by Disco’s to users for any means of

operations and Disco’s shall confirm the safety locks and proper earthing been applied by users in both ends ( isolation points) as

per Disco’s System safety rules, using RISSP as a control measure.

Page 6: ER 11 - Standard Connection Arrangements DoE comment 11 Standard Connection Arrangeme… · f 0hwhulqj fxuuhqw wudqviruphuv &7v iru hdfk 8vhu g &xuuhqw dqg ixvhg yrowdjh phwhulqj

[Eng. Rec No.11 – Std. Conn. Arr. V 1.1] Page 6 of 18

incomer circuit breaker(s) without first obtaining approval from the DISCO. Such

Control Authority ** arrangement shall be formalised in a Connection Agreement and

would require the User appointed electrical contractor or facilities manager to liaise

with the DISCO before any operation on the LV incomer circuit breaker(s) or outgoing

circuit breaker(s) is carried out in case of multiple User sites and the provision of

access to the DISCO. In case of Single User sites the LV Incomer may be operated

by DISCO or the User’s representative under the supervision of DISCO for isolation

purpose.

The User main distribution board(s) may be wall mounted or back to wall in order to

conserve space.

2.7 The User main Distribution boards(s) shall be of type tested design, metal enclosed,

approved by the DISCO and shall include where applicable:

(a) A Moulded case circuit breaker (MCCB) for the incomer User feeder.

(b) An outgoing moulded case circuit breaker (MCCB) for each User feeder.

(c) Metering current transformers (CTs) for each User.

(d) Current and fused voltage metering circuits.

(e) Tariff meter for each User feeder.

(f) Control circuitry for tripping and lockout of each MCCB by command from the

associated tariff meter.

(g) Facilities for locking and sealing to prevent tampering of the metering circuitry

and meter connections.

(h) For small-scale solar PV installations, an additional meter dedicated to

monitoring the amount of electricity generation1 and a switch disconnector2.

Category A2 - Connections at 400V from HV/LV substation(s) located at the User premises

2.8 Category A2 connections are applicable where the DISCO existing or intended

distribution architecture for the development area includes for 11kV or 22kV feeders

and where the connection capacity cannot be accommodated by a Category A1

connection.

2.9 The various connection arrangements within Category A2 are shown in Figure 2.2 for

single Customer premises and Figures 2.3 for multiple Customers premises.

2.10 If determined by the DISCO, multiple Category A2 connections shall be provided at

the User premises as required to meet the demand or contingency associated with the

1 Small-Scale Solar Photovoltaic Energy Netting Regulations (First Edition), January 2017 as amended 2 The Electricity Wiring Regulations (Third Edition), March 2014 as amended

Page 7: ER 11 - Standard Connection Arrangements DoE comment 11 Standard Connection Arrangeme… · f 0hwhulqj fxuuhqw wudqviruphuv &7v iru hdfk 8vhu g &xuuhqw dqg ixvhg yrowdjh phwhulqj

[Eng. Rec No.11 – Std. Conn. Arr. V 1.1] Page 7 of 18

User System. For example larger high rise buildings and commercial / retail

complexes may require numerous Category A2 connections.

2.11 These connections involve multiple DISCO LV cables laid on trays, in ducts or in cable

troughs from the transformer(s) of DISCO HV/LV substation(s). The DISCO HV/LV

substation(s) as required shall be constructed within the User premises.

2.12 The DISCO LV cables will terminate at the LV incomer circuit breaker(s) of the User

main distribution board(s) located in a dedicated room(s) at the User premises subject

to the DISCO acquiring “Control Authority” of the LV incomer circuit breaker(s), i.e. the

User cannot operate the LV incomer circuit breaker(s) without first obtaining approval

from the DISCO. Such Control Authority arrangement shall be formalised in a

Connection Agreement and would require the User appointed electrical contractor

or facilities manager to liaise with the DISCO before any operation on the LV incomer

circuit breaker(s) is carried out and the provision of access to the DISCO.

2.13 The User main distribution board(s) shall be of type design tested, metal enclosed,

approved by the DISCO and shall include:

(a) An air circuit breaker (ACB) or moulded case circuit breaker (MCCB) for the

incomer User feeder.

(b) Control circuitry for tripping and lockout of the incomer ACB or MCCB by

command from the associated DISCO tariff meter.

(c) For small-scale solar PV installations, an additional meter dedicated to

monitoring the amount of electricity generation and a switch disconnector.

Category B - Connections at 11kV

2.14 2.15 Category B connections are applicable for User Systems that include 11kV

loads or HV generation and where the DISCO existing or intended distribution

architecture for the development area caters for 11kV feeders.

2.15 The various connection arrangements within Category B are shown in Figure 2.4 to

Figure 2.6.

2.16 If determined by the DISCO multiple Category B connections shall be provided at the

User premises as required to meet the demand, generation capacity or contingency

associated with the User System. For example district cooling plants, pumping

stations, factories and larger than 6MVA generation plants may require numerous

Category B connections.

2.17 The DISCO shall determine the number of Category B connections provided at the

User premises giving due consideration to Engineering Recommendation No.4 -

Security of Supply Standard for the Electricity Distribution System and to the

configuration of the primary substations (quantity and rating of transformers) existing

and intended for the development area.

Page 8: ER 11 - Standard Connection Arrangements DoE comment 11 Standard Connection Arrangeme… · f 0hwhulqj fxuuhqw wudqviruphuv &7v iru hdfk 8vhu g &xuuhqw dqg ixvhg yrowdjh phwhulqj

[Eng. Rec No.11 – Std. Conn. Arr. V 1.1] Page 8 of 18

2.18 Category B connections involve a number of DISCO 11kV cables laid underground

from circuit breakers at DISCO primary substation(s) or from DISCO ring main HV/LV

substations.

2.19 In order of preference, the following DISCO/User interface arrangements shall apply;

subject to mutual agreement between both DISCO and User:

(a) Each of the DISCO 11kV cables shall terminate at separate DISCO interface

switchgear located at the User premises. The separate DISCO interface

switchgear shall be located in a dedicated single room or in dedicated separate

rooms at different locations with direct access for DISCO authorised staff. (or)

(b) Each of the DISCO 11kV cables shall terminate at the 11kV incomer circuit

breaker(s) of the User HV switchgear panel(s) located in a dedicated room(s)

at the User premises subject to the DISCO acquiring “Control Authority” of the

11kV incomer circuit breaker(s), i.e. the User cannot operate the 11kV incomer

circuit breaker(s) without first obtaining approval from the DISCO. Such Control

Authority arrangement shall be formalised in a Connection Agreement and

would require the User HV authorised staff to liaise with the DISCO before any

operation on the 11kV incomer circuit breaker(s) is carried out and the provision

of access to the DISCO. Where access is restricted within the User premises,

then the above option would apply. Note that this arrangement is applicable for

dedicated 11kV connections only.

2.20 For connections above 3MVA to User Systems which are effectively single Customer

installations, the User System shall enable the transfer of load in the case of an outage

on any one of the DISCO incomer feeders. The User System shall meet the approval

of the DISCO in this regard.

2.21 The DISCO interface switchgear shall be of type tested design, metal enclosed,

approved by the DISCO and shall include:

(a) A load break / fault make switch or vacuum circuit breaker (VCB) for each

DISCO feeder.

(b) Isolation and earthing facility for each DISCO feeder.

(c) A VCB for each User feeder (from generation and to demand).

(d) Isolation and earthing facility for each User feeder (from generation and to

demand).

(e) Metering current transformers (CTs) and voltage transformer (VT) on each

User feeder (from generation and to demand).

(f) Current and fused voltage metering circuits.

(g) Tariff meters for each User feeder (from generation and to demand).

(h) Facilities for integration with the DISCO distribution management system.

Page 9: ER 11 - Standard Connection Arrangements DoE comment 11 Standard Connection Arrangeme… · f 0hwhulqj fxuuhqw wudqviruphuv &7v iru hdfk 8vhu g &xuuhqw dqg ixvhg yrowdjh phwhulqj

[Eng. Rec No.11 – Std. Conn. Arr. V 1.1] Page 9 of 18

(i) Control circuitry for tripping and lockout of the VCB of each User feeder by

command from the associated DISCO tariff meter.

(j) Facilities for locking and sealing to prevent tampering of the metering circuitry

and meter connections.

Category C - Connections at 22kV

2.22 Category C connections are applicable for User Systems that include 22kV loads or

HV generation and where the DISCO existing or intended distribution architecture for

the development area caters for 22kV feeders.

2.23 The various connection arrangements within Category B are shown in Figure 2.7 to

Figure 2.9.

2.24 If determined by the DISCO multiple Category C connections shall be provided at the

User premises as required to meet the demand, generation capacity or contingency

associated with the User System. For example, district cooling plants, pumping

stations, factories and larger than 12MVA generation plants may require numerous

Category C connections.

2.25 The DISCO shall determine the number of Category C connections provided at the

User premises giving due consideration to Engineering Recommendation No.4 -

Security of Supply Standard for the Electricity Distribution System and to the

configuration of the primary substations (quantity and rating of transformers) existing

and intended for the development area.

2.26 Category C connections involve a number of DISCO 22kV cables laid underground

from circuit breakers at DISCO primary substation(s) or from DISCO ring main HV/LV

substations.

2.27 In order of preference, the following DISCO/User interface arrangements shall apply;

subject to mutual agreement between both DISCO and User:

(a) Each of the DISCO 22kV cables shall terminate at separate DISCO interface

switchgear located at the User premises. The separate DISCO interface

switchgear shall be located in a dedicated single room or in dedicated separate

rooms at different locations with direct access for DISCO authorised staff.

(b) Each of the DISCO 22kV cables shall terminate at the 22kV incomer circuit

breaker(s) of the User HV switchgear panel(s) located in a dedicated room(s)

at the User premises subject to the DISCO acquiring “Control Authority” of the

22kV incomer circuit breaker(s), i.e. the User cannot operate the 22kV incomer

circuit breaker(s) without first obtaining approval from the DISCO. Such Control

Authority arrangement shall be formalised in a Connection Agreement and

would require the User HV authorised staff to liaise with the DISCO before any

operation on the 22kV incomer circuit breaker(s) is carried out and the provision

of access to the DISCO. Where access is restricted within the User premises,

Page 10: ER 11 - Standard Connection Arrangements DoE comment 11 Standard Connection Arrangeme… · f 0hwhulqj fxuuhqw wudqviruphuv &7v iru hdfk 8vhu g &xuuhqw dqg ixvhg yrowdjh phwhulqj

[Eng. Rec No.11 – Std. Conn. Arr. V 1.1] Page 10 of 18

than the above option would apply. Note that this arrangement is applicable for

dedicated 22kV connections only.

2.28 For connections above 3MVA to User Systems which are effectively single Customer

installations, the User System shall enable the transfer of load in the case of an outage

on any one of the DISCO incomer feeders. The User System shall meet the approval

of the DISCO in this regard.

2.29 The DISCO interface switchgear shall be of type tested design, metal enclosed,

approved by the DISCO and shall include:

(a) A load break / fault make switch or vacuum circuit breaker (VCB) for each

DISCO feeder.

(b) Isolation and earthing facility for each DISCO feeder.

(c) A VCB for each User feeder (from generation and to demand).

(d) Isolation and earthing facility for each User feeder (from generation and to

demand).

(e) Metering current transformers (CTs) and voltage transformer (VT) on each

User feeder (from generation and to demand).

(f) Current and fused voltage metering circuits.

(g) Tariff meters for each User feeder (from generation and to demand).

(h) Facilities for integration with the DISCO distribution management system.

(i) Control circuitry for tripping and lockout of the VCB of each User feeder by

command from the associated DISCO tariff meter.

(j) Facilities for locking and sealing to prevent tampering of the metering circuitry

and meter connections.

Category D - Connections at 33kV

2.30 Category D connections are applicable for User Systems that include HV loads or HV

generation and where the DISCO existing or intended distribution architecture for the

development area caters for 33kV feeders and where the connection capacity cannot

be accommodated by a Category B connection.

2.31 The various connection arrangements within Category D are shown in Figure 2.10 to

Figure 2.12.

2.32 If determined by the DISCO multiple Category D connections shall be provided at the

User premises as required to meet the demand, generation capacity or contingency

associated with the User System. For example, district cooling plants, pumping

stations, factories and larger than 18MVA generation plants may require numerous

Category D connections.

Page 11: ER 11 - Standard Connection Arrangements DoE comment 11 Standard Connection Arrangeme… · f 0hwhulqj fxuuhqw wudqviruphuv &7v iru hdfk 8vhu g &xuuhqw dqg ixvhg yrowdjh phwhulqj

[Eng. Rec No.11 – Std. Conn. Arr. V 1.1] Page 11 of 18

2.33 The DISCO shall determine the number of Category D connections provided at the

User premises giving due consideration to Engineering Recommendation No.4 -

Security of Supply Standard for the Electricity Distribution System and to the

configuration of the primary substations (quantity and rating of transformers) existing

and intended for the development area.

2.34 Category D connections involve a number of DISCO 33kV cables laid underground

from circuit breakers at grid stations or from DISCO 33kV network.

2.35 In order of preference, the following DISCO/User interface arrangements shall apply;

subject to mutual agreement between both DISCO and User:

(a) Each of the DISCO 33kV cables shall terminate at separate DISCO interface

switchgear located at the User premises. The separate DISCO interface

switchgear shall be located in a dedicated single room or in dedicated separate

rooms at different locations with direct access for DISCO authorised staff.

(b) Each of the DISCO 33kV cables shall terminate at the 33kV incomer circuit

breaker(s) of the User HV switchgear panel(s) located in a dedicated room(s)

at the User premises subject to the DISCO acquiring “Control Authority” of the

33kV incomer circuit breaker(s), i.e. the User cannot operate the 33kV incomer

circuit breaker(s) without first obtaining approval from the DISCO. Such Control

Authority arrangement shall be formalised in a Connection Agreement and

would require the User HV authorised staff to liaise with the DISCO before any

operation on the 33kV incomer circuit breaker(s) is carried out and the provision

of access to the DISCO. Where access is restricted within the User premises,

than the above option would apply. Note that this arrangement is applicable for

dedicated 33kV connections only.

2.36 For connections above 3MVA to User Systems which are effectively single Customer

installations, the User System shall enable the transfer of load in the case of an outage

on any one of the DISCO incomer feeders. The User System shall meet the approval

of the DISCO in this regard.

2.37 The DISCO interface switchgear shall be of type tested design, metal enclosed,

approved by the DISCO and shall include:

(a) A load break / fault make switch or vacuum circuit breaker (VCB) for each

DISCO feeder.

(b) Isolation and earthing facility for each DISCO feeder.

(c) A VCB for each User feeder (from generation and to demand).

(d) Isolation and earthing facility for each User feeder (from generation and to

demand).

Page 12: ER 11 - Standard Connection Arrangements DoE comment 11 Standard Connection Arrangeme… · f 0hwhulqj fxuuhqw wudqviruphuv &7v iru hdfk 8vhu g &xuuhqw dqg ixvhg yrowdjh phwhulqj

[Eng. Rec No.11 – Std. Conn. Arr. V 1.1] Page 12 of 18

(e) Metering current transformers (CTs) and voltage transformer (VT) for each

User feeder (from generation and to demand).

(f) Current and fused voltage metering circuits.

(g) Tariff meters for each User feeder (from generation and to demand).

(h) Facilities for integration with the DISCO distribution management system.

(i) Control circuitry for tripping and lockout of the VCB of each User feeder by

command from the associated DISCO tariff meter.

(j) Facilities for locking and sealing to prevent tampering of the metering circuitry

and meter connections.

Figure 2.1 : Category A1 - Connections at 400V from LV network or HV/LV substation not located at the User premises

400V

M

Userpremises

Solar PV Generation up to 250kVA

from LV network or

HV/LV substation

from LV network or

HV/LV substation

400V User premises

M

PVM

Solar PV Generationup to 250kVA

Customer demand up to 250kVA (Single Villa)

DISCO assetUser assettariff meterconnection pointcircuit breaker (with isolating capability)DISCO load break / fault make switch (alternatively circuit breaker ) or PV generation switch disconnector PV generation output monitoring meter

M

Customer 1 Customer 2 Customer 3 Customer n Customers demand

up to 250kVA(Multiple Villas in a single plot)

PVM

PVM

M M

DISCO Shall have “Control Authority” over LV incomer CB

M

Page 13: ER 11 - Standard Connection Arrangements DoE comment 11 Standard Connection Arrangeme… · f 0hwhulqj fxuuhqw wudqviruphuv &7v iru hdfk 8vhu g &xuuhqw dqg ixvhg yrowdjh phwhulqj

[Eng. Rec No.11 – Std. Conn. Arr. V 1.1] Page 13 of 18

Figure 2.2 : Category A2 - Connections at 400V from HV/LV substation(s) located at the User premises – Single Customer

Figure 2.3 : Category A2 - Connections at 400V from HV/LV substation(s) located at the User premises – Multiple Customers in one premises (User

interface switchgear)

DISCO assetUser assettariff meterconnection pointcircuit breakeroff load switchDISCO load break / fault make switch (alternatively circuit breaker) or PV generation switch disconnectorPV generation output monitoring meter

M

PVM

from HV network

400V

22kV or 11kV

Customer demandup to 1.5MVA

Userpremises

Solar PV Generationup to 1.5MVA

PVM

M

DISCO shall have “Control Authority” over LV incomer CB

User LV main distribution

board

User interface switchgear option

M

22kV or 11kV

M

Userpremises

chiller plant

services

400V

from HV network

MM

apartments

MM

apartments

Customers demand up to 1.5MVASolar PV Generation

up to 1.5MVA

PVMDISCO assetUser assettariff meterconnection pointcircuit breakerDISCO load break / fault make switch (alternatively circuit breaker) or PV generation switch disconnectorPV generation output monitoring meter

M

PVM

DISCO shall have “Control Authority” over LV incomer CB

User LV main distribution

board

Page 14: ER 11 - Standard Connection Arrangements DoE comment 11 Standard Connection Arrangeme… · f 0hwhulqj fxuuhqw wudqviruphuv &7v iru hdfk 8vhu g &xuuhqw dqg ixvhg yrowdjh phwhulqj

[Eng. Rec No.11 – Std. Conn. Arr. V 1.1] Page 14 of 18

Figure 2.4 : Category B - Connections at 11kV (DISCO interface switchgear)

Figure 2.5 : Category B - Connections at 11kV (User interface switchgear)

Max 1 of 6MVA from a 2 transformer 33/11kV substationMax 2 of 6MVA from a 3 transformer 33/11kV substationMax 3 of 6MVA from a 4 transformer 33/11kV substationMax 6 of 6MVA from a 4 transformer 132/11kV substation

DISCO assetUser assettariff meterconnection pointcircuit breakerload break / fault make switch (alternatively circuit breaker)

M

fromHV networkor substation

Userpremises

M

Userpremises

from HV network

Customer installation shall enable transferof load between connection points A & B

A B

Customer demandup to 6MVA

Customer demandup to 3MVA

M M

Max 1 of 3MVA

11KV 11KV

Max 1 of 6MVA from a 2 transformer 33/11kV substationMax 2 of 6MVA from a 3 transformer 33/11kV substationMax 3 of 6MVA from a 4 transformer 33/11kV substationMax 6 of 6MVA from a 4 transformer 132/11kV substation

DISCO assetUser assettariff meterconnection pointcircuit breakerload break / fault make switch (alternatively circuit breaker)

M

from HV networkor substation

(dedicated feeders only)

Userpremises

Customer installation shall enable transferof load between connection points A & B

A B

Customer demandup to 6MVA

M

11kVDISCO shall have “Control Authority” over HV incomer CB

User HV switchgear panel

M

Page 15: ER 11 - Standard Connection Arrangements DoE comment 11 Standard Connection Arrangeme… · f 0hwhulqj fxuuhqw wudqviruphuv &7v iru hdfk 8vhu g &xuuhqw dqg ixvhg yrowdjh phwhulqj

[Eng. Rec No.11 – Std. Conn. Arr. V 1.1] Page 15 of 18

Figure 2.6 : Category B - Connections at 11kV (Embedded Generator)

Figure 2.7 : Category C - Connections at 22kV (DISCO interface switchgear)

Userpremises

M

from HV network

Customer installation shall enable transferof load between connection points A & B

Customer demandup to 12MVA

Customer demandup to 3MVA

Max 5 of 12MVA from a 4 transformer 132/22kV substation

fromHV networkor substation

Userpremises

A B

M M

Max 1 of 3MVA

22kV 22kV

DISCO assetUser assettariff meterconnection pointcircuit breakerload break / fault make switch (alternatively circuit breaker)

M

M

Userpremises

fromHV network

Generation up to 6MVA

Userpremises

from HV network

or substation

Max 1 of 6MVA from a 2 transformer 33/11kV substationMax 2 of 6MVA from a 3 transformer 33/11kV substationMax 3 of 6MVA from a 4 transformer 33/11kV substationMax 6 of 6MVA from a 4 transformer 132/11kV substation

11kV 11kV

M

DISCO assetUser assettariff metertariff meter if required by ADWEC power purchase agreementconnection pointcircuit breakerload break / fault make switch (alternatively circuit breaker)

M

M

DISCO shall have “Control Authority” over HV incomer CB

User HV switchgear panel

GCustomer demand

Refer to ER3 - Connection of Embedded Generating Plant up to and including

20MW

Max 1 of 6MVAon a ring circuit

Generation up to 6MVA

M

GCustomer demand

Page 16: ER 11 - Standard Connection Arrangements DoE comment 11 Standard Connection Arrangeme… · f 0hwhulqj fxuuhqw wudqviruphuv &7v iru hdfk 8vhu g &xuuhqw dqg ixvhg yrowdjh phwhulqj

[Eng. Rec No.11 – Std. Conn. Arr. V 1.1] Page 16 of 18

Figure 2.8 : Category C - Connections at 22kV (User interface switchgear)

Max 5 of 12MVA from a 4 transformer 132/22kV substation

DISCO assetUser assettariff meterconnection pointcircuit breakerload break / fault make switch (alternatively circuit breaker)

M

from HV networkor substation

(dedicated feeders only)

Userpremises

Customer installation shall enable transferof load between connection points A & B

A B

Customer demandup to 12MVA

M

22kVDISCO shall have “Control Authority” over HV incomer CB

User HV switchgear panel

M

Page 17: ER 11 - Standard Connection Arrangements DoE comment 11 Standard Connection Arrangeme… · f 0hwhulqj fxuuhqw wudqviruphuv &7v iru hdfk 8vhu g &xuuhqw dqg ixvhg yrowdjh phwhulqj

[Eng. Rec No.11 – Std. Conn. Arr. V 1.1] Page 17 of 18

Figure 2.9 : Category C - Connections at 22kV (Embedded Generator)

Figure 2.10 : Category D - Connections at 33kV (DISCO interface switchgear)

Userpremises

M

from HV network

Customer installation shall enable transferof load between connection points A & B

Customer demandup to 18MVA

Customer demandup to 3MVA

Max 4 of 18MVA from a 220/33kV substation

fromHV networkor substation

Userpremises

A B

M M

Max 1 of 3MVA

33kV 33kV

DISCO assetUser assettariff meterconnection pointcircuit breakerload break / fault make switch (alternatively circuit breaker)

M

M

Userpremises

fromHV network

Generation up to 12MVA

Userpremises

from HV network

or substation

Max 5 of 12MVA from a 4 transformer 132/22kV substation

22kV 22kV

M

DISCO assetUser assettariff metertariff meter if required by ADWEC power purchase agreementconnection pointcircuit breakerload break / fault make switch (alternatively circuit breaker)

M

M

DISCO shall have “Control Authority” over HV incomer CB

User HV switchgear panel

GCustomer demand

Refer to ER3 - Connection of Embedded Generating Plant up to and including

20MW

Max 1 of 12MVAon a ring circuit

Generation up to 12MVA

M

GCustomer demand

Page 18: ER 11 - Standard Connection Arrangements DoE comment 11 Standard Connection Arrangeme… · f 0hwhulqj fxuuhqw wudqviruphuv &7v iru hdfk 8vhu g &xuuhqw dqg ixvhg yrowdjh phwhulqj

[Eng. Rec No.11 – Std. Conn. Arr. V 1.1] Page 18 of 18

Figure 2.11 : Category D - Connections at 33kV (User interface switchgear)

Figure 2.12 : Category D - Connections at 33kV (Embedded Generator)

Max 4 of 18MVA from a 220/33kV substation

DISCO assetUser assettariff meterconnection pointcircuit breakerload break / fault make switch (alternatively circuit breaker)

M

from HV networkor substation

(dedicated feeders only)

Userpremises

Customer installation shall enable transferof load between connection points A & B

A B

Customer demandup to 18MVA

M

33kVDISCO shall have “Control Authority” over HV incomer CB

User HV switchgear panel

M

M

Userpremises

fromHV network

Generation up to 18MVA

Userpremises

from HV network

or substation

Max 4 of 18MVA from a 220/33kV substation

33kV 33kV

M

DISCO assetUser assettariff metertariff meter if required by ADWEC power purchase agreementconnection pointcircuit breakerload break / fault make switch (alternatively circuit breaker)

M

M

DISCO shall have “Control Authority” over HV incomer CB

User HV switchgear panel

GCustomer demand

Refer to ER3 - Connection of Embedded Generating Plant up to and including

20MW

Max 1 of 18MVAon a ring circuit

Generation up to 18MVA

M

GCustomer demand