Upload
others
View
31
Download
0
Embed Size (px)
Citation preview
EDAU01 - 410
DAIKIN AUSTRALIA PTY. LIMITED
- Heat Pump [50Hz]
Engineering Data
DUCTED
Inverter Series
i Inverter Ducted Air Conditioners
EDAU01 - 410
External Ap1. pearances ...................................................................................................... 1
Specifications 2. .................................................................................................................... 2
Dimensions and Service Space 3. ....................................................................................... 7
3.1 Indoor Units ............................................................................................................. 7
3.2 Outdoor Units ........................................................................................................ 10
Installation and Service Space 4. ....................................................................................... 13
Piping Diagrams 5. ............................................................................................................. 16
5.1 Indoor Units ........................................................................................................... 16
5.2 Outdoor Units ........................................................................................................ 17
Capacity Correction Ratio 6. .............................................................................................. 20
Wiring Diagrams 7. ............................................................................................................ 22
7.1 Indoor Units ........................................................................................................... 22
7.2 Outdoor Units ........................................................................................................ 25
Electrical Characteristics 8. ................................................................................................ 32
8.1 Indoor Unit (FDYQ50-160) ................................................................................. 32
8.1.1 System and Outdoor............................................................................................. 32
8.2 Indoor Unit (FDYQ180-200) ................................................................................. 33
8.2.1 Outdoor Unit ....................................................................................................... 33
Capacity Tables 9. .............................................................................................................. 34
Operation Limits 10. ............................................................................................................. 40
Fan Performance 11. ........................................................................................................... 42
Sound Level 12. ................................................................................................................... 47
12.1 Overall Sound Level ............................................................................................ 47
12.1.1 Indoor Unit ............................................................................................................ 47
12.1.2 Outdoor Unit ......................................................................................................... 48
12.2 Octave Band Level ............................................................................................. 50
12.2.1 Indoor Unit ............................................................................................................ 50
12.2.2 Outdoor Unit ......................................................................................................... 51
TABLE OF CONTENTS
Table of Contents
iiInverter Ducted Air Conditioners
EDAU01 - 410 TABLE OF CONTENTS
Centre of Gravity 13. ............................................................................................................. 55
Optional Accessories 14. ...................................................................................................... 58
Installation. FDYQ71-160 15. ................................................................................................ 59
15.1 Before Installation .................................................................................................. 60
15.2 Selecting Installation Site ....................................................................................... 62
15.3 Preparations Before Installation ............................................................................. 62
15.4 Indoor Unit Installation ........................................................................................... 63
15.5 Refrigerant Piping Work ......................................................................................... 63
15.6 Drain Piping Work .................................................................................................. 65
15.7 Electric Wiring Work ............................................................................................... 66
15.8 Field Setting ........................................................................................................... 70
15.9 Malfunction Codes ................................................................................................. 74
Installation. FDYQ180/200/250 16. ....................................................................................... 75
16.1 Before Installation .................................................................................................. 76
16.2 Selecting Installation Site ....................................................................................... 77
16.3 Preparations Before Installation ............................................................................. 77
16.4 Indoor Unit Installation ........................................................................................... 78
16.5 Refrigerant Piping Work ......................................................................................... 78
16.6 Drain Piping Work .................................................................................................. 80
16.7 Electric Wiring Work ............................................................................................... 81
16.8 Field Setting ........................................................................................................... 84
1 Inverter Ducted Air Conditioners
EDAU01 - 410
Indoor Unit
Remote Controller
Outdoor Unit
FDYQ100KAV1
FDYQ125KAV1
FDYQ160KAV1
RZQ100KV4A
RZQ125KV4A
RZQ160KV4A
RZYQ7PY1
RZYQ8PY19
RZYQ10PUY1
FDYQ180MV1
FDYQ200PV1
FDYQ250MV19
BRC1E61 BRC4C62
Wired Type
RZQ71KBV4A
FDYQ71FAV19
RZQ100HY4A
RZQ125HY4A
RZQ160HY4A
Zone Controller
BRC230Z4
BRC230Z8
BRC24Z4
BRC24Z8
RXS50JVMA
RXS60JVMA
FDYQ50DV1
FDYQ60DV1
9
External Appearances
1. External Appearances
2Inverter Ducted Air Conditioners
EDAU01 - 410 Specifications
2. Specifications
NOTES:
*1. Capacities are based on the following conditions:
Capacities are net, including a deduction for cooling (and addition for heating) for indoor fan motor heat.
Heating Piping Length Standard
20o CDB 15
o CWB
7o
CDB, 6o CWB
*2. The capacities include a deduction for defrost.
*3. AFR (Air Flow Rate), ESP (External Static Pressure) and SPL (Sound Pressure Level) are shown at 230V
*4. The indoor sound levels are determined in accordance with AS 1217.2-1985.
*5.
*6. Air filter must be installed at time of installation.
*7. Width dimension includes the electrical box.
7.5m (Horizontal) ASNZS3823 1.2
Model Cooling
Indoor 27o
CDB, 19o CWB
Outdoor 35o CDB, 24
o CWB
Outdoor sound levels are determined in an anechoic chamber and may differ once the unit is installed due to ambient conditions. Ambient noise may increase sound levels during operation.
��
3 Inverter Ducted Air Conditioners
EDAU01 - 410Specifications
4Inverter Ducted Air Conditioners
EDAU01 - 410 Specifications
5 Inverter Ducted Air Conditioners
EDAU01 - 410Specifications
6Inverter Ducted Air Conditioners
EDAU01 - 410 Specifications
7 Inverter Ducted Air Conditioners
EDAU01 - 410
3. Dimensions and Service Space
3.1 Indoor Units
��
�� ��
���
��
���
�
��
����
��
������ �� ���� ���
���
�� �� ���� ���
��� �� �� ���� ���
���
��
���
����
�������
������������ ��� �������� ��
���������������� ��������
��� ������ � ����� ��� ������������
��
������
��� �������
���������������� ���������
��� ������
��� ���������
�������������
���!�"�������
�
�
�
�� �
������������������ ������������������� ����
���� ����� ���������������������� !"#�!���!���� ���� ��������
����!�$��� �
%��&�!'���� ������ �� ����������!������������ ���������� ��
���(!� �!������ ����(��� �������� ������"�)������ �!"���!������� �
����� ����������� ������� ���� � ���"����� ���������������� �!'���
���$!*� ����������������!�!����!�)��!�+��!���
,��� ����� ��������� ������������ �������!���� ��)��� �!���� �!'���
������� �������� ��� �����������!���� �� �������
-��. ������� ��)�"����������)������ ����!��� ��)��*���� �������
/��0!�����!�"����� �����1� ����!�����)��������������� ������� ��)�"�� �!��'���
%�0�23�2
��4�5�6�
�
�� �� ���� ���
���
��
��
������
������
��
�
� �
�
��
��
��
�
��
��
����7�������)!��*�� ��!����
�����������������&���������/�86������
������������ !�� 9
�
�
������
������
��� ����������������������������������������������������� ���
���������������������������������������������� ��� ��� ����������
�!����"����������������������� �����#$���������
�����������������������%����
&�'��(� ����� ������������������� ��������������� ��"�
��������)������ ������� �)��������������������#������ �����#
���������� ������������ ��������������������������#
����� �����������������������(� ��%��*����������������� ����
���������������+�����
������
,
������
��
� �
���
�
����
���
��
�� �
� �
��
��
��
�
��
�
�
����
������������������������
�������������������������
�
��
��
�"-���.!
���������������������������������
��� ����������!�������
�������������
���"���������
&�/�0&
�
��
��
��� �������
���������������� �������
�������������
��
���������������
����
���������������
�
� � ���������������
���
��
��
���
���
FDYQ50/60DV1
FDYQ71FAV19
Dimensions and Service Space
8Inverter Ducted Air Conditioners
EDAU01 - 410
�
�
������
������
�
������
���
��
�
� �
������������������������
�������������������������
��
�
����
��
�
�
�
��
���
��
� �
� �
��
��
��
�
��
����
�
�
��
���������������
�������������� �
������
�����������������!���������������
���� ���������"�������
��
���
���� ��
��� ���!���
�������������
��� ���!���
�������������
������
������������������������ ���!��������"�#$����%��&���!��%'�����
��������������������������������������������!���"���!�����"�!�(�)�
*���$��������!!��#�����&�����!��������"+,�"���"���
����$�������!!������%"�-��#��
��.�"/�����&��������$�� ��� � �"��� ��%�%�%�����������
����� ��0"���"����%��&���0������!!���������� �+�(���������"+
������"�%�����$��%����������!�����������$����$��� �+
����������������%%������!���"/����-�"1��$��!%� ������������"
���"�&��"�(��"�2��"�%�
�
�
�� !��������������
�� �
!��������������
� � !��������������
���
���
����
��
��
��
� ��
�
�
�
�� ���
���
���
���
�
�
�� ���
���
���
� �
���
��
�
�� ���
������������������������
���������������������������
����
���
���������������
��
���������������
��
�
��
������
�
��
���������������������������������
���� ���������������������
���������������������������������
���� ����������!�������
��
���
������
� �������
��� ���������
� �������
��� ���������
�� ���
������� ���������� ����������� ����������� ��� �
���!������ "���� � ������ ��������� ����#�$�
%��������� �����������! ��������������&'������� �
��� ������ ���� ���� ��(�����
)��*�+��!!��$��,,������� ����� ��!�!����� � �����
�������(��������� ��������������-������� �������.����
��������/��01
2��3��4�����!������� ������������������� � � �� �����
�����������5��� ��� � ��!���5���� ���� ������ ���&�#�
�����������&� ���� ���� ���� �� ��������������� �� ��
��� ������&�������� � ��� � ���������4����(��6������
������� ������������!����#����7���� �
FDYQ100KAV1
FDYQ125KAV1
FDYQ160KAV19
FDYQ180MV1
Dimensions and Service Space
9 Inverter Ducted Air Conditioners
EDAU01 - 410
����
���
�
���
��
���
��
� ��
�
�
�
������
���
�
������
��
��
���
��
��
���
��
�
������
���
���
���� ���� ��������������
�������������������� ����
��
��
����
����
��������� �����
���
��������� �����
��
������
�
��
���������������������������������
����������������������������
�������������������������
�������������������������������
��
���
�������
�� �������
��� � ����� �
�� �������
��� � ����� �
���
�����
���������������������� ���������������� !����"�
���#������"$����������������������������%�&�
'���!������������ �����#���������������()���������
����!���������������"��*�� ��
+��,�-��##��&��..�������"��������#�#�����""�������
�������*���������"����� ��������/���������������0��
������� 1���23
4��5��6�����#��������!������������������"�"�"��������
�����������7���������"��#���7��������������������(�%�
�����������(������"�����!���"����������������������!��
����!�����(��������������""�����������6����*��8��!���"
��������������������#����%����9����"�
�
����
���
�
���
��
���
��
� �
�
�
�
������
���
�
������
���
��
��
��
���
��
��
�
������
��
���
���� ���� ��������������
�������������������� ����
��
��
���
���
��������� �����
��
��������� �����
��
������
�
��
���������������������������������
����������������������������
�������������������������
�������������������������������
���
���
��������
�� �������
��� � ����� �
�� �������
��� � ����� �
�
���
�����
���������������������� ���������������� !����"�
���#������"$����������������������������%�&�
'���!������������ �����#���������������()���������
����!���������������"��*�� ��
+��,�-��##��&��..�������"��������#�#�����""�������
�������*���������"����� ��������/���������������0��
������� 1���23
4��5��6�����#��������!������������������"�"�"��������
�����������7���������"��#���7��������������������(�%�
�����������(������"�����!���"����������������������!��
����!�����(��������������""�����������6����*��8��!���"
��������������������#����%����9����"�
FDYQ200PV1
FDYQ250MV19
Dimensions and Service Space
10Inverter Ducted Air Conditioners
EDAU01 - 410 Dimensions and Service Space
3.2 Outdoor Units
RXS50JVMA
RXS60JVMA
RZQ71KBV4A
11 Inverter Ducted Air Conditioners
EDAU01 - 410Dimensions and Service Space
RZQ100KV4A
RZQ125KV4A
RZQ160KV4A
RZQ100HY4A
RZQ125HY4A
RZQ160KHYA
12Inverter Ducted Air Conditioners
EDAU01 - 410 Dimensions and Service Space
RZYQ7PY1
RZYQ8PY19
RZYQ10PUY1
13 Inverter Ducted Air Conditioners
EDAU01 - 410Installation and Service Space
4. Installation and Service SpaceRZQ71KBV4A (For RXS50/60JVMA Refer Page No. 10)
14Inverter Ducted Air Conditioners
EDAU01 - 410 Installation and Service Space
RZQ100KV4A / RZQ100HY4A
RZQ125KV4A / RZQ125HY4A
RZQ160KV4A / RZQ160HY4A
15 Inverter Ducted Air Conditioners
EDAU01 - 410Installation and Service Space
RZYQ7PY1
RZYQ8PY19
RZYQ10PUY1
16Inverter Ducted Air Conditioners
EDAU01 - 410
5. Piping Diagrams
Piping Diagrams
5.1 Indoor Units
FDYQ180MV1
FDYQ200PV1
FDYQ250MV19
FDYQ50DV1 / FDYQ60DV1
FDYQ71FAV19 / FDYQ100KAV1
FDYQ125KAV1 / FDYQ160KAV19
17 Inverter Ducted Air Conditioners
EDAU01 - 410Piping Diagrams
5.2 Outoor Units
RXS50JVMA
RXS60JVMA
RZQ71KBV4A
18Inverter Ducted Air Conditioners
EDAU01 - 410 Piping Diagrams
RZQ100KV4A
RZQ125KV4A
RZQ160KV4A
RZQ100HY4A
RZQ125HY4A
RZQ160HY4A
19 Inverter Ducted Air Conditioners
EDAU01 - 410Piping Diagrams
RZYQ7PY1
RZYQ8PY19
RZYQ10PUY1
20Inverter Ducted Air Conditioners
EDAU01 - 410 Capacity Correction Ratio
6. Capacity Correction Ratio
RXS50JVMA
RXS60JVMA
RZQ71-160
21 Inverter Ducted Air Conditioners
EDAU01 - 410Capacity Correction Ratio
RZYQ7-8
RZYQ10
22Inverter Ducted Air Conditioners
EDAU01 - 410
7. Wiring Diagrams
7.1 Indoor Units
Wiring Diagrams
�� �� �� ��
���
�
���
��
��
�
��
��� �
��
���
�
���
���
����
��� ��
�
��
��� ���
�
��
�
��
��� �
� �� �
��
���
���
��
���
��
���
���
���
!��!
����
��
�"
���
�#�
��
���
��
��
�
��
����
���
��
����
��
��
���
��
��
�
!��
��
��
����
"
�!�
����
���
�
��
��
���
�!�
���
���
���
��
���
���
�
����
��
��
�$
%���
�&
$%
���$
�'
!��
�!�
%�
��$
!
�(
!
���
�
��!
�)
!
%� ��
!
���
!� �
���
��"
��
*!�
��
����
"
���
!� �
���
��"
��$
!
��
�
+���
���
���
!�
�,!
��*
!�
�)!
��
,!
�,
$!
&
�
����
��!
��
�!�
�� ��
��
���
�
��
��
--
�
��
��
����
����
��
-
��
� �
.����
����
���
.��
��
��!�
��
���
�+ �+��
���
����
�
����
�!�
���
���
���
��
���
���
��
���
����
���
���
���
���
����
��!
���
�
!���
����
���
���
����
���
���
���
!��!
���
���
!��
!�+
�+��
�*
!/��
��!�
!��
����
!�!
���
���
���
��
����
���
���
����
���
!��!
����
��
���
���!
��
����
��
���
+
&+�
���
����
��
��
���
���
���
���!
��%
!�
+��!
���
��
��
���
���
��!�
�!��
��
����
!��
!���
���
��
��
���
���
���
���
���
��!�
��+
�+��
��
��
���
���
���
��
���
����
����
��
���
����
���
��
���
���
���"
����
���
���
!��!
���
���
!��
!��!
��
���
��
��
��
��!�
!+
)+��
���
��
��
.���!
� ��
��
.���
����
�.��
����
���
�.��
���
����
�
.����
����
��.��
����
���
�.�
!�
��
�
.�
���
���
.��
!�
�
.���
��
����
FDYQ50DV1
FDYQ60DV1
23 Inverter Ducted Air Conditioners
EDAU01 - 410Wiring Diagrams
��
��
��
���
�
���
�
� ��
��
���
���
��
�����
�� ��
� ��
� ��
� ��
���
���
����
�
���
���
������������
����
���
��
� � !
����
�"
"��
#�����
��
���
���
���
���
"��
�"
��
���
���
���
���
� $ ��
��
$�
� $
��
��
� $��
�� % ����%
%��"
�% �
���
�"
%
�
� & �
���
���
& ���
�
�
�� & �
�����
��' & �
�'
�
�� & �
����
"
�� & "
���
�
�
� & �
��
�"
&
���
�"
�
�� & �
��"
�
�� �����' �
�� %
���
�' �
� �
��
�
����� �
�������
�� �
��' �
�
�
�� ��'��� �
���
�
�� ��� �
�%��
��� �
� %
���
����
%
"��
�� %
��"
% �
�� �
����� %
�����
��
�� ��
�� (���) ������
��
���
� �
�% �
%�'
�
�� *
��� �
������
��������� �
��������
��
����%
��
& ������
��
& ���������
& ���
�' "
����
�
& ���
� �
�' %
����
& +�
���� �
��������
& "
��� �
����
��
�� "��
�' �
�����
��������
��
����
�"
���
�
���
�
� $��
��
� ���!
��#
�
�,
��
��
���
���
���
���
%"
���� �
��
���
��
��
��
(���� �
)
%%�
(���� �
) � �
� ��
� ��
���
� ��
����
��
� ��
���
"��
��'
���
���
��$��
��
��
�$�
����
����
��
�
%%�
���
���
��'
���
(���� �
)
(���� �
)
FDYQ71FAV19
FDYQ100KAV1
FDYQ125KAV1
FDYQ160KAV19
24Inverter Ducted Air Conditioners
EDAU01 - 410 Wiring Diagrams
�
�� ������ �� ��
���
��� �
�����
�����
����
����
� �
� �
� �
��
��
��
��
���
���
��
�����
�� ��
����
����
����
����
����
����
����
���
���
���
�
������
���
���
��
����
���
� ���
������
���
�����
��
���
���
�
�
���
���
�
�
��
��
� �� �
�!�"��
��"�"��
��"�����
"
������#��������������������#�����
���� �#���� �������������#����
��� ��
�#� �����������������#��
����
��� ���#� �����������������
�#������
�������#����
�
�!������"���"��
������������
��
�����
������$���
�������������
�����������������������������
��������������"���������������!
�!� ���������"�����������
������
�����������������
����������������!
���"
�!������������������#�����
����
��������������������#���
�����
��������������������#��������
����
��������������������#���� �����"���
��������������������#�%��
�������
����
��������������������#��
��������
�
��&�
�'�
���
���������
���"���
���(�
����"�
�""����
���� ��������
��������������������������
��
��
���
���������
��
��������
)�����������""��*
"++��,-+��
���
���
���
���
���
���
�./0
"-1
)2++�-345+*
�&�
��
���
��
���
���
���
���
"��������
�
���
��
��
FDYQ180MV1
FDYQ200PV1
FDYQ250MV19
25 Inverter Ducted Air Conditioners
EDAU01 - 410
7.2. Outdoor Units
Wiring Diagrams
RXS50JVMA
26Inverter Ducted Air Conditioners
EDAU01 - 410 Wiring Diagrams
RXS60JVMA
27 Inverter Ducted Air Conditioners
EDAU01 - 410Wiring Diagrams
RZQ71KBV4A
28Inverter Ducted Air Conditioners
EDAU01 - 410 Wiring Diagrams
RZQ100KV4A
RZQ125KV4A
RZQ160KV4A
29 Inverter Ducted Air Conditioners
EDAU01 - 410Wiring Diagrams
RZQ100HY4A
RZQ125HY4A
RZQ160HY4A
30Inverter Ducted Air Conditioners
EDAU01 - 410 Wiring Diagrams
RZYQ7PY1
RZYQ8PY19
31 Inverter Ducted Air Conditioners
EDAU01 - 410Wiring Diagrams
RZYQ10PUY1
32Inverter Ducted Air Conditioners
EDAU01 - 410
8.1 Indoor Units (FDYQ50-160)
8.1.1 System and Outdoor
Electrical Characteristics
8. Electrical Characteristics
33 Inverter Ducted Air Conditioners
EDAU01 - 410
8.2 Indoor Unit (FDYQ180-200)
8.2.1 Outdoor Unit
Electrical Characteristics
34Inverter Ducted Air Conditioners
EDAU01 - 410
9. Capacity Tables
Capacity Tables
FDYQ50DV1
RXS50JVMA
FDYQ60DV1
RXS60JVMA
35 Inverter Ducted Air Conditioners
EDAU01 - 410Capacity Tables
FDYQ71FAV19
RZQ71KBV4A
FDYQ100KAV19
RZQ100KV4A
36Inverter Ducted Air Conditioners
EDAU01 - 410 Capacity Tables
FDYQ125KAV1
RZQ125KV4A
FDYQ160KAV19
RZQ160KV4A
37 Inverter Ducted Air Conditioners
EDAU01 - 410Capacity Tables
FDYQ100KAV1
RZQ100HY4A
FDYQ125KAV1
RZQ125HY4A
38Inverter Ducted Air Conditioners
EDAU01 - 410 Capacity Tables
FDYQ160KAV19
RZQ160HY4A
FDYQ180MV1
RZYQ7PY1
39 Inverter Ducted Air Conditioners
EDAU01 - 410Capacity Tables
FDYQ200PV1
RZYQ8PY19
FDYQ250MV19
RZYQ10PUY1
40Inverter Ducted Air Conditioners
EDAU01 - 410 Operation Limits
10. Operation Limits
RXS50JVMA
RXS60JVMA
RZQ71KBV4A
41 Inverter Ducted Air Conditioners
EDAU01 - 410Operational Limits
RZYQ7PY1
RZYQ8PY19
RZYQ10PUY1
RZQ100KV4A / RZQ100HY4A
RZQ125KV4A / RZQ125HY4A
RZQ160KV4A / RZQ160HY4A
42Inverter Ducted Air Conditioners
EDAU01 - 410 Fan Performance
11. Fan Performance
FDYQ50DV1
FDYQ60DV1
Fan Characteristics
Fan Automatic Adjustment
��������
43 Inverter Ducted Air Conditioners
EDAU01 - 410Fan Performance
������������������
FDYQ100KAV1FDYQ71FAV19
44Inverter Ducted Air Conditioners
EDAU01 - 410
��������
��������
FDYQ160KAV19FDYQ125KAV1
Fan Performance
45 Inverter Ducted Air Conditioners
EDAU01 - 410
0
50
100
150
200
250
300
54 64 74 84 94
(mmH2O) (Pa)
5
10
15
25
(l/s)
(m3/min)
High (high ESP)
High (standard ESP)
Low speed
Exte
rna
l S
tatic P
ressu
re
1200 1400 1600
Air Flow
20
900 1000
3PDA1271
50Hz 230V
FDYQ200PV1FDYQ180MV1
Fan Performance
46Inverter Ducted Air Conditioners
EDAU01 - 410 Fan Performance
FDYQ250MV19
47 Inverter Ducted Air Conditioners
EDAU01 - 410Sound Level
12. Sound Level
12.1 Overall Sound Level
12.1.1 Indoor Unit
��(��
�()*
�()*��(��
48Inverter Ducted Air Conditioners
EDAU01 - 410
12.1.2 Outdoor Unit
Sound Level
Note: 1. Operation sound is measured in an anechoic chamber.
2. Sound level will vary depending on a range of factors such as the construction
(acoustic absorption coefficient) of the particular room in which the equipments installed.
3. Operating conditions: 50Hz, 240V
��
� �
49 Inverter Ducted Air Conditioners
EDAU01 - 410Sound Level
Note: 1. Operation sound is measured in an anechoic chamber.
2. Sound level will vary depending on a range of factors such as the construction
(acoustic absorption coefficient) of the particular room in which the equipments installed.
3. Operating conditions: 50Hz, 415V
50Inverter Ducted Air Conditioners
EDAU01 - 410 Sound Level
12.2 Octave Band Level
12.2.1 Indoor Unit
FDYQ71FAV19 FDYQ100KAV1 FDYQ125KAV1
FDYQ180MV1 FDYQ200PV1
FDYQ250MV19
FDYQ160KAV19
51 Inverter Ducted Air Conditioners
EDAU01 - 410Sound Level
12.2.2 Outdoor Unit
RXS50JVMA (Cooling) RXS50JVMA (Heating)
RXS60JVMA (Cooling) RXS60JVMA (Heating)
RZQ71KBV4A (Cooling) RZQ71KBV4A (Heating)
52Inverter Ducted Air Conditioners
EDAU01 - 410 Sound Level
RZQ100KV4A (Cooling) RZQ100KV4A (Heating)
RZQ125KV4A (Cooling) RZQ125KV4A (Heating)
RZQ160KV4A (Cooling) RZQ160KV4A (Heating)
53 Inverter Ducted Air Conditioners
EDAU01 - 410Sound Level
RZQ100HY4A (Cooling) RZQ100HY4A (Heating)
RZQ125HY4A (Cooling) RZQ125HY4A (Heating)
RZQ160HY4A (Cooling) RZQ160HY4A (Heating)
54Inverter Ducted Air Conditioners
EDAU01 - 410
RZYQ7PY1 (Cooling) RZYQ7PY1 (Heating)
RZYQ8PY19 (Cooling) RZYQ8PY19 (Heating)
RZYQ10PUY1 (Cooling) RZYQ10PUY1 (Heating)
Sound Level
55 Inverter Ducted Air Conditioners
EDAU01 - 410Centre of Gravity
13. Centre of Gravity
RXS50JVMA
RXS60JVMA
RZQ71KBV4A
56Inverter Ducted Air Conditioners
EDAU01 - 410 Sound Level
RZQ100KV4A
RZQ125KV4A
RZQ160KV4A
RZQ100HY4A
RZQ125HY4A
RZQ160HY4A
57 Inverter Ducted Air Conditioners
EDAU01 - 410Sound Level
RZYQ7PY1
RZYQ8PY19
RZYQ10PUY1
58Inverter Ducted Air Conditioners
EDAU01 - 410
14. Optional Accessories
Optional Accessories
59 Inverter Ducted Air Conditioners
EDAU01 - 410
SAFETY CONSIDERATIONS
Please read these “SAFETY CONSIDERATIONS” carefully before installing the air conditioning equipment and be sure to install
it correctly. After completing the installation, make sure that the unit operates properly during the start-up operation. Please
instruct the customer on how to operate the unit and keep it maintained.
Please inform the customer that they should store this installation manual along with the operation manual for future reference.
This air conditioner comes under the term “appliances not accessible to the general public”.
Meaning of warning and caution symbols
WARNING . . . . . . Failure to observe a warning may result in death, injury or damage to the equipment.
CAUTION . . . . . . Failure to observe a caution may result in injury or damage to the equipment.
WARNING
l Ask your Dealer or qualified personnel to carry out installation work. Do not try to install the machine yourself.Improper installation may result in water leakage, electric shock or fire.
l Perform installation work in accordance with this installation manual.Improper installation may result in water leakage, electric shock or fire.
l Be sure to use only the specified accessories and parts for installation work.Failure to use the specified parts may result in water leakage, electric shock, fire or the unit failing.
l Install the air conditioner on a structure strong enough to withstand the weight of the unit.A structure of insufficient strength may result in the equipment falling and causing injuries.
l Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes.Improper installation work may result in the equipment falling and causing accidents.
l Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualified personnel according to local laws, regulations and this installation manual.
An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire.
l Make sure that all wiring is secured, the specified wires are used, and no external forces act on the terminal connections or wires.Improper connections or installation may result in fire.
l When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the wires so that the switch box cover can be securely fastened.
Improper positioning of the switch box cover may result in electric shock, fire or the terminals overheating.
l If the refrigerant gas leaks during installation, ventilate the area immediately.Toxic gas may be produced if the refrigerant gas comes into contact with fire.
l After completing the installation work, check that the refrigerant gas does not leak.Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire, such as a fan heater,
stove or cooker.
l Before obtaining access to the terminals and electrical parts, all supply circuits must be disconnected.
l Do not install the indoor unit or remote controller where they may be exposed to rain or moisture.Water or other fluids on the electrical components may result in fire or electric shock.
l Earth the air conditioner. Do not connect the earth wire to gas or water pipes, a lightning conductor or a telephone ground wire.Incomplete earthing may result in electric shock.
l Be sure to install an earth leakage breaker. Failure to install an earth leakage breaker may result in electric shock.
l Do not install the indoor unit or remote controller where flammable gases may leak, where there are carbon fibre or ignitable dust suspended in the air, or where volatile flammables such as thinner or gasoline are handled.
l Do not install the indoor unit or remote controller where the area is filled with steam or the ground is always wet. Insulation of the electric components may be damaged in such conditions and may result in electric shock.
l Be sure to only use refrigerant piping approved for use with R410A refrigerant. The use of unapproved piping may result in explosive rupture.
CAUTION
l Do not install the air conditioner for purposes other than for human comfort. Do not use the air conditioner for special applications such as the storage of foods, animals and plants, precision machines and art objects. Deterioration of quality may result.
l This model is not designed for free blow operation. Supply and Return air duct work must be installed. External duct work and air boxes must be adequately insulated to prevent condensation.
l It is recommended that a safety drain tray is installed. Ensure that it drains separately.
l While following the instructions in this installation manual, install drain piping in order to ensure proper drainage and insulate piping in order to prevent condensation. Improper drain piping may result in water leakage and property damage.
l Install the indoor and outdoor units, power cords and connecting wires at least 1 metre away from televisions or radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 metre may not be sufficient enough to eliminate noise.)
l Do not install the air conditioner in the following locations:(a) Where a mineral oil mist, oil spray or vapour is produced, for example in a kitchen.
Plastic parts may deteriorate.
(b) Where corrosive gas, such as sulfuric acid gas, is produced.
Corroding copper pipes or soldered parts may result in refrigerant leakage.
(c) Near machinery emitting electromagnetic waves.
Electromagnetic waves may disturb the operation of the control system and result in a malfunction of the equipment.
(d) Where salinity in the air is relatively high.
l Be sure to attach a return air filter (field supplied) inside the return air passage. Failure to install the filter will cause equipment failure.
15. Installation Manual FDYQ50-60DV1
FDYQ(N)71FAV1
FDYQ(N)100-160KAV1
Installation Manual
60Inverter Ducted Air Conditioners
EDAU01 - 410
ACCESSORIES Check that the following accessories are included with your unit.
OPTIONAL ACCESSORIES
l A Daikin remote controller is not included with the indoor unit.
Install the remote controller in an appropriate place according to the customer’s request.
If utilising the temperature sensor in the remote controller BRC1D619 (see page 14) ensure that the controller
is installed in a location where the correct air temperature is measured.
l Hanging brackets are required if the indoor unit is to be suspended. (Available in packs of 4)
BEFORE INSTALLATION
l The accessories needed for installation must be retained in your custody until the installation work is completed.
Do not discard them!
l Decide upon a safe line of transport.
l Try to leave the unit inside its packaging whilst moving. Where unpacking is unavoidable use a sling of soft
material or protective plates together with a rope when lifting to avoid damage or scratches to the unit.
l When opening the unit or moving it after opening be sure to lift it by holding onto the unit carefully without
exerting any pressure on other parts, especially drain piping, refrigerant piping and other resin parts.
l Be sure to check the type of refrigerant to be used before doing any work. (Using an incorrect refrigerant will
prevent normal operation of the unit.) This model uses R410A.
l Refer to the installation manual of the outdoor unit in conjunction with this manual for items not described in this
manual.
PRECAUTIONS
l Be sure to read this manual before installing the indoor unit.
l This unit is for indoor use only.
l This unit is suitable for installation in a household, commercial and light industrial environment.
l Do not install or operate the unit in rooms mentioned below.
l Laden with mineral oil or filled with oil vapour or spray like in kitchens.
l Where corrosive gas like sulfuric gas exists.
l Where volatile flammable gas like thinner or petrol is used.
l Where machines can generate electromagnetic waves.
l Where the air contains high levels of salt or other corrosive materials.
l Where voltage fluctuates greatly.
l In vehicles or vessels.
l To avoid water leaks, etc., be sure to install a return air filter (field supplied) inside the return air passage.
Installation Manual
61 Inverter Ducted Air Conditioners
EDAU01 - 410
FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER
INSTALLATION IS FINISHED.
(1) Items to be checked after completion of work
Items to be checked If not properly done, what is likely to occur Check
Is the indoor unit fixed firmly? The unit may drop, vibrate or make noise.
Is the gas leak test finished? It may result in insufficient cooling or heating
Does the unit require external insulation? Condensate water may drip.
Does drainage flow smoothly? Condensate water may drip.
Does the power supply voltage correspond to that shown on
the name plate?
The unit may malfunction or the components burn out.
Is the wiring and piping correct? The unit may malfunction or the components burn out.
Is the unit safely grounded? Dangerous during electric leakage.
Is the wiring size according to specifications? The unit may malfunction or the components burn out.
Is something blocking the air outlet or inlet of either the
indoor or outdoor units?
It may result in insufficient cooling or heating.
Are refrigerant piping length and additional refrigerant charge
noted down?
The refrigerant charge in the system is not clear.
Is the indoor unit positioned so that it is not in contact with
parts of the ceiling?
Vibration and noise can be transmitted into building.
Is the airflow within specification? Poor performance or malfunction.
Is an air filter installed in the return air?Blocked heat exchanger causing malfunction or compressor
failure.
Is an external drain tray installed? Condensate water may drip.
(2) Items to be checked at completion
l Did you show the customer how to operate the system while referring to the operation manual?
Detailed explanation about operation.
Review the safety considerations.
l Did you hand the operation manual over to the customer?
NOTE TO THE INSTALLER
Be sure to instruct the customer how to properly operate the system (especially cleaning filters, operating the
different functions and adjusting the temperature). It is recommended to ask the customer to carry out the
operations themselves while you instruct them and refer them to the applicable place in the operation manual.
(1) Select an installation site where the following
conditions are fulfilled and that meets your
customer’s approval.
l Where the indoor unit and remote controller are
not exposed to rain or moisture.
l Where the casing of the unit does not contact
parts of the ceiling.
l Where optimum air distribution can be ensured.
l Where nothing blocks the air passage.
l Where condensate can be properly drained.
l Where the structure is strong enough to safely
bear the indoor unit weight.
l Where sufficient clearance for maintenance and
service can be ensured. (see Fig. 1)
l Where there is no risk of flammable gas leakage.
SELECTING INSTALLATION SITE
l Where piping between indoor and outdoor units is
possible within the allowable limit. (Refer to the
installation manual for the outdoor unit.)
CAUTION
l Keep the indoor unit, outdoor unit, power supply
wiring and transmission wiring at least 1 metre
away from televisions and radios. This is to
prevent image interference and noise in those
electrical appliances. (Noise may be generated
depending on the conditions under which the
electric wave is generated, even if 1 metre is kept.)
(2) When using suspension bolts for installation, hanging
brackets should be installed. Confirm that the
ceiling is strong enough to support the weight of
the indoor unit.
Installation Manual
62Inverter Ducted Air Conditioners
EDAU01 - 410
AF B
Inspection Hatch(450 mm X 450 mm
E
C
D
61 61
30,555,5
AIR OUTLET
AIR INLET
Moun
ting
Cent
re
Electrical Box
Inspection Hatch(450 mm X 450 mm
l Hanging brackets are sold as an optional accessory
for FDYQ(N) series.
(3) If the installation requires the indoor unit to be exposed
please ensure the unit is more than 1.8m above the floor so
that children can not touch the unit.
(4) A suitable air filter (field supplied) must be installed within the
return air duct.
Liquid pipe
Gas pipe
Drain pipeElectrical boxcoverFDYQ(N)71-160
Electrical boxcoverFDYQ50-60DV1
Spigot
Service Space300m(See service space note below)
m or more
Service Space450mmor more
Ceiling
H*
Notes:
H* (20-30 mm) is necessary to connect the drain pipe.
Determine size H* based on 1/100 of the required
downward inclination indicated in “DRAIN PIPING WORK”.
Pg9
“Service Space” is the minimum recommended distance. In
some “restricted space” installations it may be necessary to
reduce this distance. Please note that this may necessitate
additional service work should maintenance or repair be
required.
Fig. 1
Fig. 2
Model A B C D
FDYQ50-60DV1
1090 1055 348 869FDYQ(N)71FV1
1400 1365 348 899
E
461
1000 1051 341 852 393
461FDYQ(N)100-160KV1
981
1055
1365
F
Table 1
PREPARATIONS BEFORE INSTALLATION
To facilitate installation, the indoor unit can be easily separated into smaller parts to make it easier to move to the
final position. See page 16 for details.
(1) Refer to Table 1 and Fig 3 for suspension bolt position and horizontal representation of the indoor unit.
NOTE: Additional thermal insulation material (thickness 10mm or more of glass wool or polyethylene foam)
may be required if the conditions in the ceiling exceeds 30oC and RH 80% or outside air is introduced into the
ceiling or the unit operates for 24 hours. It is also important that a safety drain tray be used. (see Fig.11)
AIR INLETAIR OUTLET
Inspection Hatch(450 mm X 450 mm
E
B
C
D
F
A
53 26
26
26
4470Mo
untin
g Ce
ntre
Inspection Hatch(450 mm X 450 mm
ELECTRICAL BOX
Fig. 3
Installation Manual
63 Inverter Ducted Air Conditioners
EDAU01 - 410
(2) Install the suspension bolts. (Fig. 3 & 4)
(Use M10 size rod for the suspension bolt)
Use an anchor suitable for both the material being
anchored to and the weight of the unit.
(3) Be sure to completely insulate all external duct work
and fittings.
(4) If using rigid duct work install a canvas (or similar) duct
to the air inlet and air outlet so as not to transmit vibration
from the unit to the duct.
Apply acoustic insulation to the inside of the duct.
(5) Install suitable vibration isolator to the suspension bolts.
Ceiling slab
Anchor
Long nut or turn-buckle
Suspension bolt
Indoor unit
CeilingFig. 4
NOTE: All the above parts are field supplied
INDOOR UNIT INSTALLATION
(1) For suspended installation, hanging brackets should be installed
on the unit.
Attach the hanging brackets to the 8 mounting holes located on the
sides of the unit. (Fig. 3) The maximum length of the securing bolts
must not exceed 20mm (M6 - bolt)
(2) Carefully lift the unit so that the hanging brackets can locate on to
the suspension bolts. (Fig 5) Be sure to clamp the bracket securely
by using a nut and washer (field supplied) from the upper and
lower sides of the hanging bracket. Ensure that the suspension
bolts are firmly secured. (No up or down movement) (Fig. 5)
CAUTION
(3) Make sure the unit is level.
l Level the unit with a water level or other suitable means. If the
unit is not level, it could become the source of water leaks.
l Check if the unit is level at all four corners with a water level or a
water-filled vinyl tube as shown in the diagram. (Fig. 6)
(4) Tighten the upper nut.
Nut (field supply)
Tighten
(double nuts)
Washer
Hanging Bracket
Fig. 5
Vinyl tube
Water level
Supply air flange
Fig. 6
REFRIGERANT PIPING WORK
ALL REFRIGERANT PIPING WORK MUST ONLY BE CARRIED OUT BY A QUALIFIED PERSON
** For refrigerant piping of outdoor units, see the installation manual attached to the outdoor unit. **
Fully insulate the liquid and gas piping separately. Do not leave any gaps otherwise a water leak may occur.
(Seal any joints with glue or duct tape)
When operating in the heating mode, the temperature of the gas piping can reach up to approximately 120o C,
so use insulation which has a suitable temperature rating.
Also, in cases where the temperature and humidity surrounding the refrigerant piping can exceed 30o C or RH
80%, reinforce or use thicker pipe insulation (20 mm or thicker). Otherwise condensation may form on the
surface of the insulating material.
** Be sure to check the type of refrigerant to be used before doing any work. Using an incorrect refrigerant
will prevent normal operation of the unit. ** In case of FDYQ50-60DV1, FDYQ(N)71F & FDYQ(N) 100-160K
model(s) = R410a
CAUTION
l Avoid introduction of air or other contaminents into the refrigerant piping. If any air, moisture or other contaminent
remains in the refrigerant piping after the completion of installation the system will malfunction.
l Carry out sufficient ventilation if the refrigerant gas leaks during installation work.
l Use only R410a rated copper seamless tube manufactured to AS/NZS1571.
64Inverter Ducted Air Conditioners
EDAU01 - 410
Torque wrench
SpannerFlare nut
Piping union
Fig. 7
Coat here with ether oil
Fig. 8
l Be sure to use both a spanner and torque wrench together, as shown in the diagram, when connecting or
disconnecting pipes to/from the unit. (Fig. 7)
l Use only a flaring block suitable for R410a tube. Refer to Table 2 for the specifications of the flare work.
l When connecting the flare nut, coat the flare both inside and outside with ether oil and initially tighten
by hand 3 or 4 turns before tightening firmly. (Fig. 8)
l Use the flare nuts included with the indoor unit.
l Refer to Table 2 to determine the proper tightening torque.
CAUTION
l Over tightening the flare nuts may cause the flare nuts or copper tube to fail and allow the refrigerant to leak.
l Caution to be taken when brazing refrigerant piping. (Where applicable)
Do not use flux when brazing refrigerant piping. Use the phosphor copper brazing filler metal (BCuP)
which does not require flux. (Flux has an extremely harmful influence on refrigerant piping systems. For
instance, if chlorine based flux is used, it will cause pipe corrosion, particularly if the flux contains fluorine, it will
damage the refrigerant oil.)
During any brazing of the refrigerant piping, you must continually blow dry nitrogen gas through the piping to
expel air from the piping. (Fig. 9) If you braze the piping without doing so a large amount of oxide film
develops inside the piping and could cause system failure.
Ensure that you use a pressure reducing valve on the dry nitrogen bottle to prevent pinholes caused by
excessively high pressure. (Set the pressure of nitrogen gas to about 0.2 kg / cm2 [19.6 kPa])
Nitrogen
Refrigerant piping
Tape the pipe
Valve
Nitrogen
Reducing valve
Fig. 9
Pipe size Tightening torque Flare dimensions A (mm) Flare
6.4 (1/4") 14.2 - 17.2 N m (144 - 175 kgf cm) 8.6 - 9.0
9.5 (3/8") 32.7 - 39.9 N m (333 - 407 kgf cm) 12.6 - 13.0l
l l
l
12.7 (1/2") 49.5 - 60.3 N m (504 - 614 kgf cm) 15.8 - 16.2l l
15.9 (5/8") 61.8 - 75.4 N m (630 - 770 kgf cm) 19.3 - 19.7l l
R0.4 ~ 0.8
A
45
o ± 2
o
90
o ±
2o
Table 2
65 Inverter Ducted Air Conditioners
EDAU01 - 410
DRAIN PIPING WORKWARNING Install the drain pipe as shown below and take measures against condensation, improperly
installed piping may result in water leaks and eventually wet furniture and belongings.
(1) Installing
l Route the pipes so as to ensure that drainage can occur with no problems. (Fig. 10)
l Employ piping with either the same diameter or with the diameter larger
(excluding the raised section) than that of the connecting pipe (PVC
pipe, nominal diameter 25 mm, outside diameter 32 mm).
l Keep the drain pipe short and sloping downward at a gradient of
at least 1/100 to prevent air pockets from forming.
l To prevent the drain pipe from sagging, secure the pipe every
1 to 1.5 m.
l Use the provided drain hose 2 and clamp 1 . (Fig. 11)
Tighten the clamp firmly.
l Insulate the metal clamp with a field supplied sealing pad. (Fig. 11)
l Insulate the drain hose inside the building.
l As a safety measure, please use a safety drain tray (field supplied) and drain separately.
l Insulate drain pipe using piping thermal insulation to prevent condensate dripping during humid conditions.
Note
l To ensure no excessive pressure is applied to the included drain hose 2 , do not bend or twist when
installing. (This may cause leakage.)
WRONG CORRECT
Fig. 10
Not recommended but in case of an emergency
You must use a torque wrench but if you are obliged to install the unit without a torque wrench, you may follow
the installation method mentioned below.
As you keep on tightening the flare nut with a spanner there is a point where the tightening torque suddenly
increases. From that position, further tighten the flare nut using the angle shown below in Table 3:
After the work is finished, make sure to check that there is no gas leak.
Pipe size Further tightening angle
6.4 (1/4") 60 to 90 degrees
9.5 (3/8") 60 to 90 degrees
Recommended arm length of tool
Approx. 150mm
Approx. 200mm
12.7 (1/2") 30 to 60 degrees Approx. 250mm
15.9 (5/8") 30 to 60 degrees Approx. 300mm
Make absolutely sure to properly insulate the connecting pipe work and connections using field supplied
insulation after checking for gas leakage.
CAUTION
Be sure to insulate local piping all the way into the pipe connections inside the machine. Exposed piping may
cause condensation or burns on contact.
Table 3
CAUTION
Drain piping connections.
Do not connect the drain piping directly to sewage pipes. Drainage must conform to local plumbing regulations.
The vapour in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger
or escape into the room.
Installation Manual
66Inverter Ducted Air Conditioners
EDAU01 - 410
Metal clamp 1
(provided)(field supplied)
Large sealing pad
Drain hose 2
4mm or lessTape (white) (provided)
Metal clamp 1
Drain hose 2
Bottom of the unit
Slo
pe
Safety drain tray
(field supplied)
Fig. 11
NOTE:
l If installing central drain piping,
install according to Fig. 12. 100
mm
o
r m
ore
Note: use this outlet to drain water from the drain pan
Watering can
Drain tray
Refrigerant pipes
Drain outlet
(2) After the piping work is finished, check that
the drainage flows smoothly.
l Pour approximately 1 Litre of water
gradually into the drain tray and check
drainage flow. (Fig.13)
Fig. 13
l Check drainage flow during COOLING OPERATION, explained under the section entitled TEST OPERATION.
WHEN ELECTRIC WIRING WORK IS FINISHED
ELECTRIC WIRING WORK
l All field supplied parts, materials and electric works must conform to local codes. (ie. AS / NZS 3000)
l Use copper wire only.
l For electric wiring work, refer to the "WIRING DIAGRAM" label attached to the electrical box cover.
l For remote controller wiring details, refer to page 13 of this manual for BRC1D619 or the installation manual
supplied with the chosen remote controller.
l All wiring must be performed by an authorised electrician in accordance with local codes. (ie. AS / NZS 3000)
l A circuit breaker capable of shutting down power supply to the entire system must be installed.
l Refer to the installation manual attached to the outdoor unit for the size of the power supply cable connected to
the outdoor unit and wiring instructions.
l Ensure that the air conditioner is effectively earthed.
NOTE: 1. Shield wire materials may be used for transmission wiring, and must comply with EMI (AS / NZS 3548)
or (CISPR 14).
2. Use double insulation wire for the remote controller (Sheath thickness is 1mm or more) or run wires
through a wall or conduit so that the user cannot come in contact with them.
3. Run indoor to outdoor transmission wiring and indoor power supply wiring through a conduit to protect
against external forces. Feed the conduit through the wall together with refrigeration piping.
Fig. 12
Installation Manual
67 Inverter Ducted Air Conditioners
EDAU01 - 410
Method of wiring. - Refer to Fig. 14 for the wiring details.
NOTE: All wires must be wired through bushes at the bottom of the electrical box.
l Remove the electrical box cover as indicated.
l Power and earth wiring.
Connect the power supply wires to terminals (L, N) and the earth wire to terminal .
Secure the cable to the anchor point below the terminal block. Do not connect the N-line with the
earth terminal.
l Wiring between indoor and outdoor units.
Connect the transmission wire between the indoor and outdoor unit using terminals (1, 2, 3).
Secure the cable to the anchor point below the terminal block.
l Remote controller cords.
Connect the cords to the remote controller terminals - (P1, P2 No polarity) and the shield wire (if
applicable) to the shielding earth terminal .
Secure the cable to the anchor point below the terminal block.
l Replace and secure electrical box cover.
For optional centralremote controller connection
Terminal X2M Block
Shielding Earth
Terminal X1 M Block
Protective earth terminal
Cable Tie
Remote ControllerPower and Earth
Wiring between indoor and outdoor units
Cable Tie
Terminal X2M Block
Shielding Earth
Terminal X1 M Block
Protective earth terminal
Cable Tie
Remote ControllerPower and Earth
Wiring between indoor and
outdoor units
Cable Tie
Fig. 14
Installation Manual
68Inverter Ducted Air Conditioners
EDAU01 - 410
Round crimp-style
terminal
Electric wire
PRECAUTIONS
Precaution for wiring on site
When connecting the indoor unit to a single phase of a 3 phase power supply, give consideration to the other
electrical equipment connected to the main breaker and select the phase (L1, L2, L3) so that the current (or
voltage) unbalance does not occur.
If current unbalance occurs, the phase current of the compressor may become unbalanced and there is a risk of
protective device actuating or compressor breakdown.
l Do not clamp remote controller cords together with wires connecting the units together. Doing so may cause
malfunction.
l Remote controller cords and wires connecting the units should be located at least 50 mm from other electric
wires. Not following this guideline may result in malfunction due to electrical noise.
Observe the notes mentioned below when wiring to the power supply terminal block. Precautions to be taken for
power supply wiring.
(Use a round crimp-style terminal for connection to the power supply terminal block. (Fig. 15) In case it cannot be
used due to unavoidable reasons, be sure to observe the following instructions.)
l Do not connect wires of different gauge to the same power supply terminal. (Fig. 16)
(Looseness in the connection may cause overheating.)
l When connecting wires of the same gauge, connect them according to the figure below.
l Make certain that prescribed wires are used, carry out complete connections, and secure the wires so that
outside forces are not applied to the terminals.
Fig. 15
Fig. 16
CAUTION
l After connecting the wires, be sure that no pressure is applied to the wire connections by using cable ties (field
supplied) and securing them to the anchor points. Also, when wiring, make sure the cover of the terminal box fits
snugly by arranging the wires neatly and attaching the terminal box cover firmly. When attaching the terminal
box cover make sure no wires get caught under the edges. Ensure that all the cables pass under the offset
section of the electrical box cover.
l Make sure the remote control cord, the wiring between the units, and other electrical wiring do not pass through
the same locations outside the unit, separating them by at least 50 mm, otherwise electrical noise (external
static) could cause incorrect operation of the unit or damage.
WIRING EXAMPLE for BRC1D619 only
(For the wiring of outdoor units, refer to the installation manual attached to the outdoor unit.)
Confirm the system type.
l Single phase pair type: 1 remote controller controls 1 indoor unit (standard system). (Fig. 17)
l 2 remote controller control: 2 remote controller controls 1 indoor unit. (Fig. 18)
l Group control: 1 remote controller controls up to 16 indoor units (All indoor units operate according to the
remote controller). (Fig. 19)
CORRECT WRONG WRONG
Connect wires of
the same gauge to
both sides
Do not connect
wires of the same
gauge to one side
Do not connect
wires of different
gauges
Installation Manual
69 Inverter Ducted Air Conditioners
EDAU01 - 410
Main power supply
Isolation switch
Fuse
Outdoor unit
(example)
Indoor unit
P1 P2
P1 P2
(NOTE 2)
Remote controller
(option) BRC1D619
NL
NL
NL
Isolation switch
FuseNL
Power supply
1
1 2
2 3
3
P1P2
P1P2Remote controller
(option) BRC1D619
P1P2 P1P2
(NOTE 2)
P1P2
(NOTE 2)
Remote
controller
(option)
BRC1D619
P1P2
Indoor unit Indoor unit Indoor unit
Main power supply
Isolation switch
Fuse
Outdoor unit
(example)
N
Isolation switch
FuseN
Power supply
NL
L
NL
Main power supply
Isolation switch
Fuse
Outdoor unit
(example)
N
Isolation switch
FuseN
Power supply
NL
NL
Main power supply
Isolation switch
Fuse
Outdoor unit
(example)
N
Isolation switch
FuseN
Power supply
NL
NL 1
1 2
2
L
1
1 2
2
L
1
1 2
2
3
3
3
3
3
3
Main power supply
Isolation switch
Fuse
Outdoor unit
(example)
Indoor unit
P1 P2
P1 P2
(NOTE 2)
Remote controller 2
(option) BRC1D619
1 2 3NL
1 2 3NL
NL
Power supply
Isolation switch
FuseNL
P1 P2
P1 P2
Remote controller 1
Group Control (Only Applies To BRC1D619)
Control by 2 remote
controllers
NOTE: 1. All transmission wiring except for the remote controller wires must match the terminal symbol.
2. If using shielded wire for transmission wiring ground the shield of the shield wire to at the
grounding screw of the remote controller cord grounding terminal inside the control box.
3. For group control remote controller choose the remote controller that suits the indoor unit which has
the most functions (as indicated by the swing flap).
l Only applies when other types of indoor units are used within the group eg. Cassette type.
4. When “Group Control” and “Control by 2 remote controllers” are used, connect the remote controller
with the indoor unit which is at the end. (Fig. 19)
(Do not connect three wires or more to the remote control terminals.)
Control by 2 remote controllers
Fig. 18
Fig. 19
Single phase pair type
Fig. 17
Installation Manual
70Inverter Ducted Air Conditioners
EDAU01 - 410
SECONDCODE NO.
UNIT NO.
FIRSTCODE NO.
MODE NO.
FIELDSETMODE
TEST1 245
6
SETTING
UNIT NO.
3
Setting duct static pressure
Settings
Standard static pressure
High static pressure
Second Code No.
01
02
Mode No. First Code No.
13 (23) 6
Fig. 20
Note:
Remote control displayed
is indicative only.
Depending on the remote
control supplied, the
button layout may be
different.
FIELD SETTINGThe following instructions relate to the BRC1D619 (fig.20) controller, when installing other optional controllers
please refer to the accompanying installation manual for field setting information.
Field setting must be made from the remote controller in accordance with the installation condition.
l Setting can be made by changing the "Mode number", "FIRST CODE No." and "SECOND CODE No.".
l Mode No. without ( ) means the setting will apply to all units connected to the controller. (Group control)
l Mode No. with ( ) means the settings will apply to individual units. It can also be used to check current field settings.
1) Press & hold the test button until 01 or 10 appears.
2) By pressing the temperature up arrow button scroll until the required mode setting number appears.
3) By pressing the timer up arrow button scroll until the required first code setting number appears.
4) By pressing the timer down arrow button scroll until the required second code setting number appears.
5) Press the confirmation button once.
6) Press the test button once & 88 will appear for a few seconds before returning to the normal operation.
Note: The external static pressure setting for the indoor unit is factory set to “standard” external static
pressure. For installations with a duct system that presents a high external static pressure, set the static
pressure value to the “high” position. Refer to the table below and the fan performance curves in the
Engineering Data.
HOW TO SET FIELD SETTING MODES
l Refer to page 15 for models FDYQ50DV1 & FDYQ60DV1
Setting
Filter sign indication [ON]
Filter sign indication [OFF]
Second Code No.
01
02
Mode No. First Code No.
10 (20) 3
Setting air filter sign
Setting temperature sensor location
Settings
Alternate between indoor unit andremote controller sensor
Indoor unit sensor only
Remote controller sensor only
Second Code No.
01
02
03
Mode No. First Code No.
10(20) 2
Indoor fan settings during heating thermo off
Settings
LL
Set speed
OFF
Second Code No.
01
02
03
Mode No. First Code No.
12(22) 3
Installation Manual
71 Inverter Ducted Air Conditioners
EDAU01 - 410
l When using 2 remote controllers, one must be set to "MAIN" and the other to "SUB".
l When the sub remote controller is required, use optional remote controller model: BRC1D619.
MAIN/SUB CHANGEOVER
(1) Insert a flat blade screwdriver into the recess between the upper and lower part of remote controller and working
from the 2 positions, pry off the upper part. (Fig. 21)
(The remote controller PC board is attached to the upper part of remote controller.)
(2) Turn the main/sub changeover switch on one of the two remote controller PC boards to "S".
(Leave the switch of the other remote controller set to "M".) (Fig. 22)
Indoor fan settings during cooling/heating thermo off
Settings
Normal
Fan OFF
Second Code No.
01
02
Mode No. First Code No.
11(21) 2
ESP (Pa) 10 Pa increments
40-50-60..............180
eg. 80Pa = 13-6-05
Second Code No.Mode No. First Code No.
13 (23) 6 01-02-03......................15
Indoor fan settings during cooling thermo off
Settings
LL Fan Speed
Set Fan Speed
Second Code No.
01
02
Mode No. First Code No.
12(22) 6
SETTING FAN AUTOMATIC ADJUSTMENT (FDYQ50-60DV1 Only)During commissioning stage use this mode to automatically adjust the fan RPM to achieve within +/- 10% of the rated
“High fan” speed airflow (HH). The High fan speed airflow can be adjusted to the rated airflow when the duct
External Static Pressure (ESP) is within the range of 40 – 180 Pa.
Note: Setting Fan Automatic Adjustment for multi zone systems.
Prior to the setting of Fan Automatic Adjustment, the zone that has the highest heat load should be nominated. For
example if the day zone is the nominated area, this area must be activated and the night zone must be deactivated
before commencing the Fan Automatic Adjustment mode.
HOW TO SET FAN AUTOMATIC ADJUSTMENT1) Set the controller to “Fan” mode.
2) Ensure the unit is switched “Off” by the controller “On-Off” button.
3) Hold down the “Test” button until “01” or “10” appears.
4) By pressing the temperature up arrow button scroll until mode number “21” appears.
5) By pressing the timer up arrow button scroll until the first code number setting “7” appears.
6) By pressing the timer down arrow button scroll until the second code setting “03” appears.
7) Press the confirmation button once & then the test button once. 88 will appear for a short time before returning to
normal operation.
8) Press the “On-Off” button to commence the Fan Automatic Adjustment setting. The operation lamp will illuminate &
the indoor fan will operate for a period of 1-8 minutes. To signal the completion of the adjustment, the indoor fan
will stop & the operation lamp will extinguish.
9) To confirm Fan Automatic Adjustment was successfully completed, repeat steps 3-5. Mode “21-7-02” should
appear. (If the indoor fan does not stop or 02 did not appear when Field Set Mode 21 is selected it means the Fan
Automatic Adjustment must be set again).
10) Press the test button once to return to normal operation.
Auto airflow adjustment
Settings
OFF
Completion of airflow adjustment
Start of airflow adjustment
Second Code No.
01
02
03
Mode No. First Code No.
11(21) 7
SETTING THE INDOOR FAN RPM MANUALLY TO SUIT YOUR AIRFLOW REQUIREMENTSIn the case Fan Automatic Adjustment does not suit your airflow requirements the airflow can be manually increased
or decreased. You have a choice of 15 settings.
CONTROL BY 2 REMOTE CONTROLLERS (Controlling 1 indoor unit by 2 remote controllers)
Installation Manual
72Inverter Ducted Air Conditioners
EDAU01 - 410
S
M
S
S
M
Remote controller
PC board
(Factory setting)
(Only one remote controller needs to be changed)
Upper part of
remote controller
Lower part of
remote controllerInsert the screwdriver here and
gently work off the upper part of
remote controller.
Fig. 22Fig. 21
TEST OPERATION when using BRC1D619 remote control.
X1A
X17A
X18A X2A
1 3
28 10 12
4
6
7 11
1315 14
Fig 23
Fig 24
Fig 25
Fig 26
Rubber BushInsert fan plug in this orientation
Supply Air
Return Air
Heat Exchanger Compartment
Heat Exchanger Compartment
Fan Deck Fan DeckCompartment
Electrical BoxAssembly
ATTENTION: Please separate the indoor unit only when necessary. Please disassemble and reassemble on
a flat surface.
l Separate the indoor unit in the following order.
1) Remove (4) screws located on the electrical box cover. (Fig. 23)
2) Carefully unplug the (2) thermistor cables and fan harness assemblies. Socket location (X17A, X18A, X2A
and X1A) (Fig 25)
3) Remove (6) screws securing the electrical box to the fan deck compartment. (Fig. 23)
4) Untwist wire clamp securing the (2) thermistor cables and carefully remove cables through the rubber
bush. Similarly remove fan harness by carefully passing the plug through the rubber bush. (Fig. 26)
5) Carefully separate the electrical box from the fan deck compartment.
6) Remove (3) M6 and (1) M8 bolts from the fan deck compartment.
7) Carefully separate the fan deck compartment from the heat exchanger compartment, taking care not to
damage the fan motor wiring. (Fig. 23)
8) Remove (5) M8 bolts securing the fan deck to the heat exchanger compartment and detach the fan deck. (Fig. 24)
SEPARATING THE INDOOR UNIT FDYQ50-60DV1
(When using BRC230Z4,BRC230Z8,BRC24Z4 or BRC24Z8 please use zone controller installation instructions.)
Refer to the section of "FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION
AND CHECK AFTER INSTALLATION IS FINISHED" (page 5).
After installation is complete (ie. refrigerant piping, drain piping, electrical wiring, duct work, filter installation and
field settings) conduct a check test as described below to confirm correct operation and installation of the complete
system.
1) Replace all electrical covers.
2) Energise the crank case heater for at least 6 hours before commencing next step.
3) Set to cooling operation with the remote controller and start operation by pushing ON/OFF button. ( )
4) Press Inspection/Test Operation button 4 times ( ) and operate at Test Operation mode for 3 minutes.
5) Press Inspection/Test Operation button ( ) and operate normally.
6) Confirm function of unit according to the operation manual.
PRECAUTIONS 1. In case something is wrong with the unit an error code will appear on the remote control,
refer to the Error Code List (pg18).
2. After completing the test run, press the INSPECTION / TEST OPERATION button once to put
the unit in inspection mode and make sure the malfunction code is “00”. (Normal)
If the code reads anything other than “00”, refer to the Error Code List as shown on page 18.
TEST
TEST
Installation Manual
73 Inverter Ducted Air Conditioners
EDAU01 - 410
SEPARATING THE INDOOR UNIT FDYQ(N)71FAV1 FDYQ(N)100-125KAV1
ATTENTION: Please separate the indoor unit only when necessary. Please disassemble and reassemble on
a flat surface.
l Separate the indoor unit in the following order.
1) Unscrew the (4) M6 bolts located on the back of the heat exchanger compartment. (Fig. 27)
2) Carefully pull the fan deck compartment away, taking care not to damage the fan motor wiring. (Fig. 27)
Supply Air
Return Air
Heat Exchanger Compartment
Fan DeckCompartment
Electrical BoxAssembly
Fig. 27
Fan deck
Fan earthFan connector
Electricalbox assy
Thermostat
Heat exchangercompartment
3 7
Fig. 28
3) If further disassembly is required, unplug the fan connector and unscrew the fan earth. (Fig. 28)
4) Remove (4) M8 bolts and the (4) screws securing the fan deck to the heat exchanger compartment and
detach the fan deck. (Fig. 28)
l Reassemble the fan deck and heat exchanger compartments in the following order.
5) Carefully place the fan deck back into position.
6) Secure the fan deck onto the heat exchanger compartment with the (4) screws and (4) M8 bolts. (Fig. 28)
7) Re-connect the fan connector into the plug on the heat exchanger compartment. BE SURE TO
RE-ATTACH THE FAN EARTH. (Fig. 28)
8) Carefully replace the fan deck compartment, taking care not to damage the fan motor wiring, and
secure the compartment with the (4) M6 bolts. (Fig. 27)
l Reassemble the fan deck and heat exchanger compartments in the following order:
9) Carefully place the fan deck back in the position.
10) Secure the fan deck onto the heat exchanger compartment with the (5) M8 bolts. (Fig. 24)
11) Carefully replace the fan deck compartment, taking care not to damage the fan motor wiring. (Fig. 23)
12) Secure the fan deck compartment with (3) M6 bolts & (1) M8 bolt. (Fig. 23)
13) Pass the thermister and fan harnesses through the rubber bushes on the electrical box and plug in the
respective sockets (X17A, X18A, X2A and X1A) (Fig. 25)
14) Dress thermister lead and fan motor lead on (2) wire clips provided on base panel.
15) Replace the electrical box and secure onto the fan deck compartment with 6 screws.( Fig. 23)
16) Replace the electrical box cover and secure it with (4) screws. (Fig. 23)
Installation Manual
74Inverter Ducted Air Conditioners
EDAU01 - 410
Faul
ty c
entra
l
equi
pmen
t in
conn
ectio
n
Dou
ble
assi
gnm
ent
of c
entra
l equ
ipm
ent
addr
ess
Inco
rrect
wiri
ng/p
ipin
g
(wiri
ng/p
ipin
g
conn
ectio
n er
ror)
Cen
tral e
quip
men
t
faul
ty P
CB
Faul
ty
com
mun
icat
ion
to/fr
om c
entra
l
equi
pmen
t
Indo
or/o
utdo
or u
nit
addr
ess
not e
nter
ed
Faul
ty c
entra
l
cont
rol a
ddre
ss
setti
ng
Faul
ty tr
ansm
issi
on
to/fr
om p
erip
hera
l
equi
pmen
t (ai
r
cont
rol e
quip
men
t,
etc)
Faul
ty tr
ansm
issi
on
betw
een
indo
or u
nit
and
cent
ral
cont
rolle
r
Faul
ty tr
ansm
issi
on
betw
een
outd
oor
units
or t
o/fro
m h
eat
stor
age
unit
Faul
ty tr
ansm
issi
on
to/fr
om re
mot
e
cont
rolle
r
Faul
ty tr
ansm
issi
on
to/fr
om o
ther
sys
tem
Faul
ty fi
eld
setti
ng
Faul
ty c
apac
ity
setti
ng
Shor
t of g
asR
ever
sed
phas
e
conn
ectio
n
Faul
ty p
ower
sup
ply
volta
ge s
yste
m
Faul
ty tr
ansm
issi
on
(gen
eral
)
Failu
re o
f
trans
mis
sion
betw
een
indo
or a
nd
outd
oor u
nits
Faul
ty tr
ansm
issi
on
betw
een
indo
or u
nit
and
rem
ote
cont
rolle
r
Faul
ty tr
ansm
issi
on
betw
een
indo
or
units
(mai
n &
sub)
Gas
sho
rtage
(ice
ther
mal
sto
rage
equi
pmen
t)
Mis
sing
pha
se,
imba
lanc
e in
pow
er
supp
ly
Faul
ty te
mp.
rise
sens
or in
side
cont
rol b
ox
Faul
ty ra
diat
ion
fin
(pow
er tr
ansi
stor
)
tem
p. ri
se s
enso
r
syst
em
Faul
ty D
C c
urre
nt
sens
or s
yste
m
Faul
ty A
C o
r DC
outp
ut c
urre
nt
sens
or s
yste
m
Air c
ondi
tione
r
(mul
ti) g
ener
al in
put
over
-cur
rent
Faul
ty tr
ansm
issi
on
betw
een
INV
and
outd
oor u
nits
Air c
ondi
tione
r
(mul
ti) g
ener
al in
put
over
-cur
rent
Elec
troni
c
ther
mos
tat (
time
lag)
Stal
l pre
vent
ion
(tim
e la
g)
Faul
ty p
ower
trans
isto
r
Faul
ty o
il pr
essu
re
sens
or s
yste
m
Faul
ty s
urfa
ce o
il
leve
l sen
sor s
yste
m
Faul
ty IN
V sy
stem
Abno
rmal
tem
p. ri
se
insi
de c
ontro
l box
Abno
rmal
tem
p. ri
se
of ra
diat
ion
fin
(pow
er tr
ansi
stor
)
DC
out
put o
ver-
curre
nt
(inst
anta
neou
s)
AC o
utpu
t ove
r-
curre
nt
(inst
anta
neou
s)
Faul
ty g
as p
ipe
tem
p. s
enso
r
syst
em
Faul
ty d
isch
arge
pres
sure
sen
sor
syst
em
Faul
ty o
il te
mp.
sens
or s
yste
m
Faul
ty s
uctio
n
pres
sure
sen
sor
syst
em
Abno
rmal
sur
face
oil
leve
l
Faul
ty re
frige
rant
tem
p. s
enso
r
syst
em
Faul
ty p
ress
ure
sens
or s
yste
m
(gen
eral
)
Faul
ty c
urre
nt
sens
or s
yste
m
Faul
ty d
isch
arge
pipe
tem
p. s
enso
r
syst
em
Faul
ty lo
w p
ress
ure
equi
vale
nt
satu
ratio
n te
mp.
sens
or s
yste
m
Faul
ty s
uctio
n pi
pe
tem
p. s
enso
r
syst
em
Faul
ty h
eat
exch
ange
r (1)
tem
p.
sens
or s
yste
m
Faul
ty h
eat
exch
ange
r (2)
tem
p.
sens
or s
yste
m
Faul
ty li
quid
pip
e
tem
p. s
enso
r
syst
em
Abno
rmal
hig
h oi
l
tem
p.
Abno
rmal
suc
tion
pres
sure
Abno
rmal
oil
pres
sure
Abno
rmal
disc
harg
e
pres
sure
Faul
ty d
rain
wat
er
leve
l sen
sor s
yste
m
Hea
t sto
rage
uni
t
alar
m
Activ
atio
n of
com
mon
saf
ety
devic
e fo
r sys
tem
No.
1 &
No.
2
Activ
atio
n of
saf
ety
devic
e fo
r sys
tem
No.
1
Activ
atio
n of
saf
ety
devic
e fo
r sys
tem
No.
2
Faul
ty d
isch
arge
pipe
tem
p.
Abno
rmal
hea
t
exch
ange
r (1)
tem
p.
Faul
ty o
utdo
or a
ir
tem
p. s
enso
r
syst
em
Faul
ty d
isch
arge
air
tem
p. s
enso
r
syst
em
Pum
p ov
er-c
urre
nt
lock
faul
ty s
enso
r
syst
em
Faul
ty h
ot w
ater
sens
or s
yste
m
Faul
ty h
eat s
tora
ge
unit
Faul
ty s
enso
r
syst
em (g
ener
al)
Faul
ty a
ir te
mp.
sens
or s
yste
m
Faul
ty p
ower
sup
ply
sens
or s
yste
m
Faul
ty h
igh
pres
sure
switc
h
Faul
ty lo
w p
ress
ure
switc
h
Com
pres
sor m
otor
faul
ty o
verlo
ad
sens
or s
yste
m
Com
pres
sor m
otor
over
-cur
rent
lock
faul
ty s
enso
r sys
tem
Fan
mot
or o
verlo
ad
over
-cur
rent
, fau
lty
lock
sen
sor s
yste
m
Faul
ty A
C in
put
pow
er s
enso
r
syst
em
Pum
p ov
er-c
urre
nt
lock
Abno
rmal
wat
er
tem
p.
Activ
atio
n of
fiel
d
adde
d sa
fety
dev
ice
Faul
ty d
rain
wat
er
leve
l sys
tem
Fan
mot
or o
verlo
ad
over
-cur
rent
lock
AC in
put o
ver-
curre
nt
Faul
ty e
lect
roni
c
expa
nsio
n va
lve
Faul
ty te
mp.
sen
sor
syst
em (r
emot
e
cont
rolle
r, et
c.)
Faul
ty ra
ditio
n
sens
or s
yste
m
Faul
ty h
igh
pres
sure
switc
h
Activ
atio
n of
saf
ety
devic
e (g
ener
al)
Faul
ty P
CB
Hig
h pr
essu
re
(HPS
)
Com
pres
sor m
otor
over
load
Com
pres
sor m
otor
over
-cur
rent
lock
Low
pre
ssur
e (L
PS)
Faul
ty a
ir su
ctio
n
tem
p. s
enso
r
syst
em
Faul
ty d
isch
arge
air
tem
p. s
enso
r
syst
em
Faul
ty d
irt s
enso
rFa
ulty
hum
idity
sens
or s
yste
m
Faul
ty h
eat
exch
ange
r (2)
tem
p.
sens
or s
yste
m
Fan
mot
or o
verlo
ad
over
-cur
rent
, fau
lty
lock
sen
sor s
yste
m
Air d
irect
ion
mot
or
lock
, fau
lty s
enso
r
syst
em
Faul
ty A
C in
put
curre
nt s
enso
r
Failu
re o
f
trans
mis
sion
betw
een
indo
or u
nit
PC b
oard
and
fan
PC b
oard
Faul
ty d
rain
wat
er
leve
l sen
sor s
yste
m
Faul
ty h
eat
exch
ange
r (1)
tem
p.
sens
or s
yste
m
INDOOR OUTDOOR SYSTEM
Faul
ty s
enso
r
syst
em (g
ener
al)
U MF J L PA C E H
No
load
up
Faul
ty c
apac
ity
setti
ng
Insu
ffici
ent w
ater
supp
ly
Faul
ty h
umid
ifier
AC in
put o
ver-
curre
nt
Faul
ty e
lect
roni
c
expa
nsio
n va
lve
Hea
ter o
verh
eatin
gFa
ulty
or d
irty
air
clean
er
Abno
rmal
hea
t
exch
ange
r (1)
tem
p.
Abno
rmal
hea
t
exch
ange
r (2)
tem
p.
Fan
mot
or o
verlo
ad
over
-cur
rent
lock
Air d
irect
ion
adju
st
mot
or lo
ck
Activ
atio
n of
saf
ety
devic
e (g
ener
al)
Faul
ty P
CB
Fan
inte
rlock
(man
ual)
Abno
rmal
dra
in
wat
er le
vel
CJ
EF
89
AH
45
67
01
23
Con
tent
s C
ode
Sect
ion
Cod
e
ER
RO
R C
OD
E L
IST
Installation Manual
75 Inverter Ducted Air Conditioners
EDAU01 - 410
16. Installation Manual FDYQ180MV1
FDYQ200PV1
FDYQ250MV19
Installation Manual
76Inverter Ducted Air Conditioners
EDAU01 - 410
INSTALLATION MANUAL
SINGLE SPLIT & VRV SYSTEM
OPERATION MANUAL
Name M6 ScrewHangingBracket
InstallationManual
OperationManual
FDYQ(N) Series
FXDYQ Series
16
16
4
4
1
1
1
-
Installation Manual
77 Inverter Ducted Air Conditioners
EDAU01 - 410
Liquid pipe
Gas pipe
Drain pipeElectrical boxcover
(1) Select an installation site where the following conditions
are fulfiled and that meets your customer’s approval.
l Where the indoor unit and remote controller are not
exposed to rain or moisture.
l Where the casing of the unit does not contact parts of the ceiling.
l Where optimum air distribution can be ensured.
l Where nothing blocks the air passage.
l Where condensate can be properly drained.
l Where the structure is strong enough to safely
bear the indoor unit weight.
l Where sufficient clearance for maintenance and service can be provided. (see Fig. 1)
l Where there is no risk of flammable gas leakage.
l Where piping between indoor and outdoor units is
possible within the allowable limit. (Refer to the
installation manual for the outdoor unit).
CAUTION
l Keep the indoor unit, outdoor unit, power supply wiring and
transmission wiring at least 1 metre away from televisions
and radios. This is to prevent image interference and noise
in those electrical appliances.
(Noise may be generated depending on the conditions
under which the electric wave is generated, even if 1 metre
is kept.)
(2) When using suspension bolts for installation, the hanging
brackets must be installed. Confirm that the ceiling is strong
enough to support the weight of the indoor unit.
(3) If the installation requires the indoor unit to be exposed
please ensure the unit is more than 1.8m above the floor so
that children can not touch the unit.
(4) A suitable air filter (field supplied) must be installed within the
return air duct.
SELECTING INSTALLATION SITE
*Service Space300mm or more
*Service Space450mm or more
Ceiling
H
Notes:
H = Approx 100mm for drain trap plus additional allowance
for drainage fall. (see section on DRAIN PIPING WORK)
* Service space is the minimum recommended distance. In
some “restricted space” installations it may be necessary to
reduce this distance. Please note that this may necessitate
additional service work should maintenance or repair be
required.
Fig. 1
Fig. 2
401 35080
WA
46
78
Electrical box
Refrigerantpipes and drainconnection
Air-owdirection
Inspection hatch(45 0 x 450 min)
880
910
Fig. 3
Table 1
PREPARATIONS BEFORE INSTALLATIONTo facilitate installation, the indoor unit can be easily separated
into smaller parts to make it easier to move to the final position.
See page 15 for details.
(1) Refer to Table 1 and Fig 3 for suspension bolt positionand horizontal (top view) representation of the indoorunit.
(2) The external static pressure setting for the indoor
unit is factory set to “standard” external static
pressure.For installations with a duct system that
presents a high external static pressure, set the static
pressure value to the “high” position. Refer to page 12
in this manual and the fan performance curves in the
Engineering Data.
NOTE Additional thermal insulation material (thickness 10mm or more of glass wool or polyethylene foam) may be
required if the conditions in the ceiling exceeds 30oC and RH 80% or outside air is introduced into the ceiling or the
unit operates for 24 hours. It is also important that a safety drain tray be used. (see Fig.12)
Model A B W
F(X)DYQ180MFXDYQ200M
F(X)DYQ250M
FDYQN250K
1037mm 1046mm 1210mm
1238mm 1247mm 1410mm
FDYQ200P
FDYQN200P
B
Installation Manual
78Inverter Ducted Air Conditioners
EDAU01 - 410
(X) N A
A
Installation Manual
79 Inverter Ducted Air Conditioners
EDAU01 - 410
Indoor unitCut
before
heating
Plug
Cut
before
heating
Cut
before
heating
Cut
before
heating
Wet cloth
Indoor unit
Insertion length
Liquid = 8 mm
Gas = 12 mm
Brazing
To outdoor unit
90o
Wet cloth
Indoor unit
Fitting insulation
(field supplied)
Indoor unit
Tape
(field supplied)
or clamp
Fig. 7a
Fig. 8a
Fig. 9
Fig. 10
CAUTION
Be sure to insulate local piping all the
way into the pipe connections inside
the machine. Exposed piping may
cause condensation or burns on
contact.
Model Liquid Pipe Gas Pipe
F(X)DYQ180MF(X)DYQ200M
9.5mm dia 19.1mm diaFDYQ200PFDYQN200P
F(X)DYQ250MFDYQN250K
9.5mm dia 22.2mm dia
Table 2
Indoor unit
Plug
Cut bytube cutter
Wet cloth
25mm
Approx.
Indoor unit
19.1 mm
Brazing
joint A
To outdoor unit
Pre brazed
joint B
22.2 mm
Wet cloth
Fig. 7
Fig. 8
Insertion
length
12mm
WARNING
• Cut off the ends of the plugs before heating in order
to release pressure, otherwise the plugs may
burst. (Fig. 7)
• Ensure a wet cloth is wrapped around the copper pipe
before applying a flame to prevent burning of felt
insulation. (Fig. 7 and 8)
• Take extreme care not to burn the air conditioner body
when brazing.
Applies to FDYQ200P & FDYQN200P models only:
• Cut off the end of both plugs before heating the liquid pipe
to remove the liquid pipe plug.
• Using tube cutters (1/8 - 1 1/8) cut the 22.2mm gas pipe plug
approximately 25mm or more from the expanded section of
the pipe. (Fig. 7)
• Remove the burr from the inlet of the gas pipe. ENSURE all
copper shavings are removed
• Insert 19.1mm field supplied gas pipe into the 22.2mm
pipe previously cut. Insertion length must be at least 12mm.
(Fig. 8)
• Braze joint A as shown in Fig. 8. To ensure joint (B) has not
been disturbed by the heating of joint (A) reheat joint (B)
and apply solder if necessary.
• Braze the liquid line joint.
Applies to all models except FDYQ200P & FDYQN200P
• Cut the end of the plugs before heating the pipes to
remove the plugs. (Fig. 7a)
• Braze the pipes as shown in Fig. 8a.
Applies to all models.
• Ensure the pipe insulation is sealing against the body.
(Fig. 9)
• Install the clamps (field supplied) as close to the body as
possible to absorb leaking condensation. (Fig. 10)
• Prevent any mixture of air into the refrigerant.
• Ensure sufficient ventilation if the refrigerant leaks during
installation work.
• Make sure to completely insulate the connecting pipe
work and connections using field supplied insulation after
checking for gas leakage.
• When in heating mode, the temperature of gas piping
may reach 120°C. Ensure that the insulation will safely
withstand 120°C.
Caution to be taken when brazing refrigerant piping
Do not use flux when brazing refrigerant piping. Use the
phosphor copper brazing filler metal (BCuP) which does
not require flux. (Flux has an extremely harmful influence
on refrigerant piping systems. For instance, if chlorine
based flux is used, it will cause pipe corrosion, particularly
if the flux contains fluorine, it will damage the refrigerant
oil.)
During any brazing of the refrigerant piping, you must
continually blow dry nitrogen gas through the piping to
expel air from the piping. (see Fig. 11) If you braze the
piping without doing so, a large amount of oxide film
develops inside the piping which can cause system failure.
Ensure that you use a pressure reducing valve on the dry
nitrogen bottle to prevent pinholes caused by excessively
high pressure. (Set the pressure of nitrogen gas to about
0.2 kg / cm2 [19.6 kPa])
Installation Manual
80Inverter Ducted Air Conditioners
EDAU01 - 410
DRAIN PIPING WORK
WARNING
The drain pipe must be installed as shown in the diagram below to avoid water damage caused by
leaks and condensation.
• Assemble the unit as shown in Fig. 12.
• For best results, try to keep the piping as short as possible. Slant the piping at an angle to improve flow (the
drain pipe provided with the indoor unit has a PT 3/4 internal thread). Fig. 12.
• Securely insulate the drain pipe.
• It is necessary to provide a drain trap in the drain outlet to relieve negative pressure that exists within the unit
compared to the outside atmospheric pressure when the unit is operating. If a drain trap is not provided,
condensation carry over or an odour may occur.
• Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris.
• Pour water in the drain pan to test the drainage.
• Always use an extra safety drain pan (field supplied) to cover the entire area of the indoor unit.
• Insulate drain pipe using piping thermal insulation to prevent condensate dripping during humid conditions.
CAUTION
Drain piping connections. Do not connect the drain piping directly to sewage pipes. Drainage must conform to
local plumbing regulations.The vapour in the sewage might enter the indoor unit through the drain pipes and
corrode the heat exchanger or escape into the room.
Bottom of the unit
Slo
pe
Extra drain tray(field supplied)
PT 3/4 internal thread
Drain trap
50
mm
or
mo
re5
0m
m o
r m
ore
Do not leave in water
Insulate securely(field supplied)
Gradient of at least 1:100
Fig. 12
After the piping work is finished, check that the drainage flows smoothly by pouring approximately 1000 cc of
water gradually into the drain tray and check drainage flow. (Fig.13)
Drain outletWatering can
Refrigerant pipes
Drain trayFig. 13
WHEN THE INSTALLATION IS COMPLETE
Check drainage flow during COOLING OPERATION, explained under the section entitled TEST OPERATION.
Nitrogen
Refrigerant piping
Tape the pipe
Valve
Nitrogen
Reducing valve
Fig. 11
Installation Manual
81 Inverter Ducted Air Conditioners
EDAU01 - 410Installation Manual
82Inverter Ducted Air Conditioners
EDAU01 - 410
External Switching Device eg. fire trip or timer
(min. contact requirement) 15V DC 10mA
F1 F2 T1 T2P1 P2
Fig. 17
Forced OFF or ON-OFF control by external control
If required, external control (eg. fire trip, external timer, etc) can be applied by connecting the switching device to
terminals (T1 & T2) as shown in Fig 17. The functionality of the control is set and configured under field settings
on page 13.
CAUTION
Precautions for wiring
• When connecting the indoor unit, give consideration to the other electrical equipment connected to the main
breaker and select the phase (L1, L2, L3) so that current (or voltage) unbalance does not occur. If current
unbalance occurs, the phase current of the compressor may become unbalanced and there is a risk of
protective device actuating or compressor breakdown.
• Do not clamp the remote controller cord or F1/F2 cord together with electrical wires. Doing so may cause a
malfunction.
• Remote controller cords and wires connecting the units should be located at least 50 mm from other electric
wires. Not following this guideline may result in malfunction due to electrical noise.
• Use a round crimp-style terminal for connection to the power supply terminal board. (Fig. 15) Where this is not
possible due to unavoidable reasons, be sure to observe the following instructions.
Do not connect wires of different gauge to the same power supply terminal. (Fig. 16). Looseness in the
connection will cause overheating.
When connecting wires of the same gauge, connect them according to the figure below.
• Make certain that prescribed wires are used, carry out complete connections, and secure the wires so that
outside forces are not transmitted to the terminals.
• Shielded wire is recommended for transmission wiring to comply with EMI (AS/NZSCISPR14.1)
• Use double insulation wire for the remote controller and ON-OFF Input T1, T2 (Sheath thickness is 1mm or
more) or run wires through a wall or conduit so that the user cannot come in contact with them.
• Run transmission wiring separate from power supply wiring. Ensure transmission and power supply wiring is
protected by conduit against external forces.
• After connecting the wires, be sure that no pressure is applied to the wire connections by using cable ties and
securing them to the anchor points. Also, when wiring, make sure the lid of the terminal box fits snugly by
arranging the wires neatly and attaching the terminal box lid firmly. When attaching the terminal box lid, make
sure no wires get caught under the edges.
• Make sure the remote control cord or the wiring between the units (ie F1/F2) do not pass through the same
locations outside the unit as any other electrical wiring. Separate them by at least 50 mm, otherwise electrical
noise could cause a malfunction or damage to the unit. 50mm is considered the minimum for domestic
applications where there is relatively low current flowing in other electrical wiring. In applications where high
current or voltage is present in nearby electrical wiring additional separation will be required.
Round crimp-style
terminal
Electric wire
Connect wires of
the same gauge to
both sides
Do not connect
wires of the same
gauge to one side
Do not connect
wires of different
gauges
Fig. 15
Fig. 16
Power Supply Wire type (F1,F2)
(wiring between units)
Remote controller (P1,P2) & On/Off Input (T1,T2) T1,T2
Contact Spec.Field fuse Wire type Size Wire type Size Length
Circuit protection and wire size
must comply with local codes (ie
AS/NZS3000)
Sheathed wire
(2 wires) See
precautions
below0.75-1.25mm2
(P1,P2)
Max 500m
(T1,T2)
Max 100m
Min 15V DC
10 mAOutdoor - Indoor Max
wiring length 1000m
Table 3
Installation Manual
83 Inverter Ducted Air Conditioners
EDAU01 - 410
L1 L2 L3 N
F1 F2
F1 F2
T1 T2P1 P2
P1 P2
Main Power Supply
OutdoorUnit
IndoorUnit
L N
Main Power Supply
RemoteControls
Fuses or breaker
Isolation Switch
P1 P2
S MS M
Note 2.
L1 L2 L3 N
F1 F2
F1 F2
T1 T2P1 P2
P1 P2
Main Power Supply
OutdoorUnit
IndoorUnit
L N
Main Power Supply
RemoteContro l
Fuses or breaker
Isolation Switch
S M
L1 L2 L3 N
F1 F2
F1 F2
T1 T2P1 P2
Main Power Supply
OutdoorUnit
IndoorUnit
L N
Main Power Supply
Fuses or breaker
Isolation Switch
L1 L2 L3 N
F1 F2
F1 F2
T1 T2P1 P2
Main Power Supply
OutdoorUnit
IndoorUnit
L N
Main Power Supply
Fuses or breaker
Isolation Switch
P1 P2
IndoorUnit
P1 P2 RemoteContro l
S M
Note 2. Note 2. Note 2.
L1 L2 L3 N
F1 F2
F1 F2
T1 T2P1 P2
P1 P2
Main Power Supply
OutdoorUnit
IndoorUnit
L N
Main Power Supply
RemoteContro l
Fuses or breaker
Isolation Switch
S M
Note 2.
Fig. 19Fig. 18
Group Control
Fig. 20
Fig. 21(Note 4)
1. All transmission wiring except for the remote controller wires must match the terminal symbol.
2. If using shielded wire for transmission wiring, ground the shield of the shield wire to , at the
grounding screw of the remote controller cord grounding terminal inside the control box.
3. For group control remote controller, choose the remote controller that suits the indoor unit which has the
most functions (as indicated by the swing flap).
4. When two remote controllers are used in "Group Control", connect the remote controller to the indoor unit
which is at the end of the loop. (Fig. 21). Do not connect three or more wires to the P1, P2 remote control
Notes:
Single pair type Control by 2 remote controllers
terminals.
Installation Manual
84Inverter Ducted Air Conditioners
EDAU01 - 410
FIELD SETTING
GREY BROWN GREY BROWN
Standard Static(factory default)
High Static(reposition orange wire)
ORANGE ORANGE
X3M X3M
Fig. 22
Field settings must be made from the remote controller in accordance with the installation requirements
(external static pressure can not be set by field setting in these models).
Setting External Static Pressure
For “HIGH” ESP Setting, move the Orange Jumper Lead on terminal block XM3 (inside electrical box) from the
left hand side terminal (grey) to the right hand side terminal (brown) as shown below in Fig 22.
OTHER FIELD SETTINGS (WHEN INSTALLING BRC1D619)
When installing other optional controllers please refer to the accompanying installation manual for field
setting information.
Field setting must be made from the remote controller in accordance with the installation condition.
l Setting can be made by changing the "Mode number", "FIRST CODE No.", and "SECOND CODE No.".
l Mode No. without ( ) means the setting will apply to all units connected to the controller. (Group control)
l Mode No. with ( ) means the settings will apply to individual units. It can also be used to check current field settings.
SECONDCODE NO.
UNIT NO.
FIRSTCODE NO.
MODE NO.
FIELDSETMODE
TEST1 245
6
SETTING
UNIT NO.
3
Fig. 20
Note:
Remote control displayed
is indicative only.
Depending on the remote
control supplied, the
button layout maybe
different.
1) Press & hold the test button until 00, 01 or 10 appears.
2) By pressing the temperature up arrow button scroll until the required mode setting number appears.
3) By pressing the timer up arrow button scroll until the required first code setting number appears.
4) By pressing the timer down arrow button scroll until the required second code setting number appears.
5) Press the confirmation button once.
6) Press the test button once & 88 will appear for a few seconds before returning to the normal operation.
How to set field setting modes
Installation Manual
85 Inverter Ducted Air Conditioners
EDAU01 - 410
S
M
S
S
M
Remote controller
PC board
(Factory setting)
(Only one remote controller needs to be changed)
Fig. 24
Upper part of
remote controller
Lower part of
remote controllerInsert the screwdriver here and
gently work off the upper part of
remote controller.
Settings Mode No. FIRST CODE No. SECOND CODE No.
Forced OFF 01 (FACTORY SET)
ON - OFF Input
12 (22) 1
(Bridge T1, T2)To Force OFF
(Bridge T1, T2 to switch ON)(Open T1, T2 to switch OFF)
Using 2 remote controllers
When using 2 remote controllers, one must be set to "MAIN" and the other to "SUB".
(1) Insert a flat screwdriver into the recess between the upper and lower part of remote controller and working fromthe 2 positions, pry off the upper part. (Fig. 23) (The remote controller PC board is attached to the upper part of remote controller.)
Fig. 23
Table 4
Setting T1 T2 Input
Settings
Alternate between both sensors
Indoor unit sensor only
Remote controller sensor only
Second Code No.
01
02
03
Mode No. First Code No.
10(20) 2
Settings
LL
Set speed
OFF
Second Code No.
01
02
03
Mode No. First Code No.
12(22) 3
(FACTORY SET)
(FACTORY SET)
(FOR HEATING MODE)
Setting air filter sign
Setting
Filter sign indication [ON]
Filter sign indication [OFF]
Second Code No.
01
02
Mode No. First Code No.
10 (20) 3(FACTORY SET)
Indoor fan settings during thermo off
Setting temperature sensor location
l Filter maintenance should be carried out which is appropriate to the type of filter in use.
(2) Turn the main/sub changeover switch on one of the two remote controller PC boards to "S". (Leave the switch
of the other remote controller set to "M".) (Fig. 24)
Table 5
Table 6
Table 7
02
Installation Manual
86Inverter Ducted Air Conditioners
EDAU01 - 410
Refer to the section of "FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION
AND CHECK AFTER INSTALLATION IS FINISHED" (pg 2).
After installation is complete (ie refrigerant piping, drain piping, electrical wiring, duct work, filter installation and
field settings) conduct a check test as described below to confirm correct operation and installation of the complete
system.
(1) Replace all electrical covers.
(2) Energise the crank case heater for at least 6 hours before commencing next step.
(3) Refer to the installation manual of the unit for additional field settings.
(4) Set to cooling operation with the remote controller and start operation by pushing ON/OFF button.
(5) (When using BRC1D619 controller) Press Inspection/Test Operation button 4 times and operate at Test Operation
for 3 minutes.
(6) Press Inspection/Test Operation button and operate normally.
(7) Confirm function of unit according to the operation manual.
PRECAUTIONS
TEST
TEST OPERATION
Code RemarksMalfunction
A1
A6
A3
AJ
Indoor unit's PCBfaulty
Drain water level abnormalor jumper on PCB missing
Indoor fan motoroverloaded, over-current orlocked
(not applicable)
Type set improper
Capacity data is wronglypreset. Or there isnothing programmed inthe data hold 1C.
H3High pressure switch faulty(outdoor unit)
C5
C9
E0
E1
E3
E4
E5
E6
E9
F3
Sensor for heat exchangertemperature is faulty
Sensor for suction airtemperature is faulty
Action of safety device(outdoor unit)
High pressure abnormal(outdoor unit)
Outdoor unit's PCB faulty
Low pressure abnormal(outdoor unit)
OL activation
Compressor startup error
Electronic expansion valvefaulty (outdoor unit)
Discharge pipe temperatureabnormal (outdoor unit)
Code RemarksMalfunction
PJ
U1
U4
UA
UC
UF
H4
H9
J3
Low pressure switch faulty(outdoor unit)
Outdoor air thermistorfaulty (outdoor unit)
Discharge pipe thermistorfaulty (outdoor unit)
Type set improper(outdoor unit)
Capacity data is wronglypreset. Or there isnothing programmed inthe data hold 1C.
Reverse phase or Openphase
Transmission error(indoor unit - outdoor unit)
Miss setting for multisystem
Wrong wiring betweenindoor and outdoor units
Central control addressoverlapping
J6Heat exchanger thermistorfaulty (outdoor unit)
Transmission is improperbetween the indoor andoutdoor units.
U5
Transmission error(indoor unit - remotecontroller)
Transmission is improperbetween the indoor unit andremote controller.
Setting is wrong for selectorswitch of multi-system
Check the wiring betweenindoor and outdoor units
C4Sensor for heat exchangertemperature is faulty
Liquid line (sensor R2T)
Gas line (sensor R3T)
1. In case something is wrong with the unit and an error code appears on the remote control,
refer to the malfunction diagnosis table below.
2. After completing the test run, press the INSPECTION / TEST OPERATION button once to put
the unit in inspection mode, and make sure the malfunction code is "00", (normal). If the code
reads anything other than "00", refer to the malfunction diagnosis table below.
TEST
Installation Manual
87 Inverter Ducted Air Conditioners
EDAU01 - 410
Fan deck
section
Heat exchanger
section
Heat exchanger
top cover
Side lock strap
Electrical box cover
x18A, x19A
Fan deck
section
Heat exchanger
section
To facilitate installation, the indoor unit can be easily separated into 2 sections making it lighter to carry and easier to
maneuver through openings and in the ceiling.
ATTENTION: Separate the indoor unit only when necessary. Disassemble and reassemble on a flat surface.
Separate the indoor unit in the following order.
1. Remove the two side lock straps. (Fig. 26)
2. Unscrew the top cover of the heat exchanger section. (Fig. 26)
3. Unscrew the three M8 bolts securing the two sections. (Fig. 27)
Fig. 27
Fig. 28
4. a) Unplug the expansion valve motor in-line connector located internally on the heat exchanger side plate (Fig
26). Release the harness retaining clip securing the expansion valve motor connecting cable. Place the now
loose expansion valve motor cable in the fan deck section of the unit.
b) Remove the electrical box cover and unplug the air and two heat exchanger thermistors (Plugs X11A, X12A
and X13A) (Fig. 28)
c) Carefully un-clip the three thermistor leads and push the leads through the back of the electrical box.
d) un-clip the thermistor leads from inside the fan deck section.
5. Carefully unlatch the heat exchanger section from the fan deck section (Fig. 29) by lifting up the heat exchanger
section and then pulling away. Ensure that the thermistor or expansion valve motor cables do not catch on either
section as the unit is separated.
Rejoin the Heat Exchanger and Fan Deck sections in the following order.
6. Carefully align the heat exchanger section and fan deck section.
7. Lift the heat exchanger section about 50mm, push it forward and then back down so that the bottom edge latches
over the bottom lip of the fan deck section. (Fig. 29)
8. Secure the two sections together with the 3 bolts (M8). (Fig. 27) Re-attach the side lock strap. (Fig. 26)
9. Re-connect the air and heat exchanger thermistors (Fig. 28). Reconnect the expansion valve motor in-line
connector (Fig. 26) Reclip all leads inside the electrical box as well as inside the fan deck and heat exchanger
sections. Replace the electrical box cover.
10.Carefully replace the heat exchanger section top cover and secure the cover with the screws. (Fig. 26)
Fan deck
section
Heat exchanger
section
M8 Bolts
Fig. 29
Fan deck
section
Heat exchanger
section
SEPARATING THE INDOOR UNIT (if required)
Fig. 26
X11A, X12A, X13A
Expansion valve
motor connector
Installation Manual
DAIKIN AUSTRALIA PTY. LIMITED
77-83 Alfred Road, Chipping Norton, NSW 2170 Australia
Phone: 1300 78 72 66
www.daikin.com.au
DAIKIN INDUSTRIES LTD.
Head office:
Umeda Centre Building, 4-12 Nakazaki-Nishi 2 chome,
Kita-ku, Osaka, 530-8323 Japan
Tokyo office:
Shinjuku Sumitomo Building, 6-1 Nishi-Shinjuku
2 chome, Shinjuku, Tokyo, 163-0290 Japan
EDAU01 - 410