92
EDAU01 - 410 DAIKIN AUSTRALIA PTY. LIMITED - Heat Pump [50Hz] Engineering Data DUCTED Inverter Series

Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

  • Upload
    others

  • View
    31

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

EDAU01 - 410

DAIKIN AUSTRALIA PTY. LIMITED

- Heat Pump [50Hz]

Engineering Data

DUCTED

Inverter Series

Page 2: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

i Inverter Ducted Air Conditioners

EDAU01 - 410

External Ap1. pearances ...................................................................................................... 1

Specifications 2. .................................................................................................................... 2

Dimensions and Service Space 3. ....................................................................................... 7

3.1 Indoor Units ............................................................................................................. 7

3.2 Outdoor Units ........................................................................................................ 10

Installation and Service Space 4. ....................................................................................... 13

Piping Diagrams 5. ............................................................................................................. 16

5.1 Indoor Units ........................................................................................................... 16

5.2 Outdoor Units ........................................................................................................ 17

Capacity Correction Ratio 6. .............................................................................................. 20

Wiring Diagrams 7. ............................................................................................................ 22

7.1 Indoor Units ........................................................................................................... 22

7.2 Outdoor Units ........................................................................................................ 25

Electrical Characteristics 8. ................................................................................................ 32

8.1 Indoor Unit (FDYQ50-160) ................................................................................. 32

8.1.1 System and Outdoor............................................................................................. 32

8.2 Indoor Unit (FDYQ180-200) ................................................................................. 33

8.2.1 Outdoor Unit ....................................................................................................... 33

Capacity Tables 9. .............................................................................................................. 34

Operation Limits 10. ............................................................................................................. 40

Fan Performance 11. ........................................................................................................... 42

Sound Level 12. ................................................................................................................... 47

12.1 Overall Sound Level ............................................................................................ 47

12.1.1 Indoor Unit ............................................................................................................ 47

12.1.2 Outdoor Unit ......................................................................................................... 48

12.2 Octave Band Level ............................................................................................. 50

12.2.1 Indoor Unit ............................................................................................................ 50

12.2.2 Outdoor Unit ......................................................................................................... 51

TABLE OF CONTENTS

Table of Contents

Page 3: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

iiInverter Ducted Air Conditioners

EDAU01 - 410 TABLE OF CONTENTS

Centre of Gravity 13. ............................................................................................................. 55

Optional Accessories 14. ...................................................................................................... 58

Installation. FDYQ71-160 15. ................................................................................................ 59

15.1 Before Installation .................................................................................................. 60

15.2 Selecting Installation Site ....................................................................................... 62

15.3 Preparations Before Installation ............................................................................. 62

15.4 Indoor Unit Installation ........................................................................................... 63

15.5 Refrigerant Piping Work ......................................................................................... 63

15.6 Drain Piping Work .................................................................................................. 65

15.7 Electric Wiring Work ............................................................................................... 66

15.8 Field Setting ........................................................................................................... 70

15.9 Malfunction Codes ................................................................................................. 74

Installation. FDYQ180/200/250 16. ....................................................................................... 75

16.1 Before Installation .................................................................................................. 76

16.2 Selecting Installation Site ....................................................................................... 77

16.3 Preparations Before Installation ............................................................................. 77

16.4 Indoor Unit Installation ........................................................................................... 78

16.5 Refrigerant Piping Work ......................................................................................... 78

16.6 Drain Piping Work .................................................................................................. 80

16.7 Electric Wiring Work ............................................................................................... 81

16.8 Field Setting ........................................................................................................... 84

Page 4: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

1 Inverter Ducted Air Conditioners

EDAU01 - 410

Indoor Unit

Remote Controller

Outdoor Unit

FDYQ100KAV1

FDYQ125KAV1

FDYQ160KAV1

RZQ100KV4A

RZQ125KV4A

RZQ160KV4A

RZYQ7PY1

RZYQ8PY19

RZYQ10PUY1

FDYQ180MV1

FDYQ200PV1

FDYQ250MV19

BRC1E61 BRC4C62

Wired Type

RZQ71KBV4A

FDYQ71FAV19

RZQ100HY4A

RZQ125HY4A

RZQ160HY4A

Zone Controller

BRC230Z4

BRC230Z8

BRC24Z4

BRC24Z8

RXS50JVMA

RXS60JVMA

FDYQ50DV1

FDYQ60DV1

9

External Appearances

1. External Appearances

Page 5: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

2Inverter Ducted Air Conditioners

EDAU01 - 410 Specifications

2. Specifications

NOTES:

*1. Capacities are based on the following conditions:

Capacities are net, including a deduction for cooling (and addition for heating) for indoor fan motor heat.

Heating Piping Length Standard

20o CDB 15

o CWB

7o

CDB, 6o CWB

*2. The capacities include a deduction for defrost.

*3. AFR (Air Flow Rate), ESP (External Static Pressure) and SPL (Sound Pressure Level) are shown at 230V

*4. The indoor sound levels are determined in accordance with AS 1217.2-1985.

*5.

*6. Air filter must be installed at time of installation.

*7. Width dimension includes the electrical box.

7.5m (Horizontal) ASNZS3823 1.2

Model Cooling

Indoor 27o

CDB, 19o CWB

Outdoor 35o CDB, 24

o CWB

Outdoor sound levels are determined in an anechoic chamber and may differ once the unit is installed due to ambient conditions. Ambient noise may increase sound levels during operation.

��

Page 6: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

3 Inverter Ducted Air Conditioners

EDAU01 - 410Specifications

Page 7: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

4Inverter Ducted Air Conditioners

EDAU01 - 410 Specifications

Page 8: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

5 Inverter Ducted Air Conditioners

EDAU01 - 410Specifications

Page 9: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

6Inverter Ducted Air Conditioners

EDAU01 - 410 Specifications

Page 10: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

7 Inverter Ducted Air Conditioners

EDAU01 - 410

3. Dimensions and Service Space

3.1 Indoor Units

��

�� ��

���

��

���

��

����

��

������ �� ���� ���

���

�� �� ���� ���

��� �� �� ���� ���

���

��

���

����

�������

������������ ��� �������� ��

���������������� ��������

��� ������ � ����� ��� ������������

��

������

��� �������

���������������� ���������

��� ������

��� ���������

�������������

���!�"�������

�� �

������������������ ������������������� ����

���� ����� ���������������������� !"#�!���!���� ���� ��������

����!�$��� �

%��&�!'���� ������ �� ����������!������������ ���������� ��

���(!� �!������ ����(��� �������� ������"�)������ �!"���!������� �

����� ����������� ������� ���� � ���"����� ���������������� �!'���

���$!*� ����������������!�!����!�)��!�+��!���

,��� ����� ��������� ������������ �������!���� ��)��� �!���� �!'���

������� �������� ��� �����������!���� �� �������

-��. ������� ��)�"����������)������ ����!��� ��)��*���� �������

/��0!�����!�"����� �����1� ����!�����)��������������� ������� ��)�"�� �!��'���

%�0�23�2

��4�5�6�

�� �� ���� ���

���

��

��

������

������

��

� �

��

��

��

��

��

����7�������)!��*�� ��!����

�����������������&���������/�86������

������������ !�� 9

������

������

��� ����������������������������������������������������� ���

���������������������������������������������� ��� ��� ����������

�!����"����������������������� �����#$���������

�����������������������%����

&�'��(� ����� ������������������� ��������������� ��"�

��������)������ ������� �)��������������������#������ �����#

���������� ������������ ��������������������������#

����� �����������������������(� ��%��*����������������� ����

���������������+�����

������

,

������

��

� �

���

����

���

��

�� �

� �

��

��

��

��

����

������������������������

�������������������������

��

��

�"-���.!

���������������������������������

��� ����������!�������

�������������

���"���������

&�/�0&

��

��

��� �������

���������������� �������

�������������

��

���������������

����

���������������

� � ���������������

���

��

��

���

���

FDYQ50/60DV1

FDYQ71FAV19

Dimensions and Service Space

Page 11: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

8Inverter Ducted Air Conditioners

EDAU01 - 410

������

������

������

���

��

� �

������������������������

�������������������������

��

����

��

��

���

��

� �

� �

��

��

��

��

����

��

���������������

�������������� �

������

�����������������!���������������

���� ���������"�������

��

���

���� ��

��� ���!���

�������������

��� ���!���

�������������

������

������������������������ ���!��������"�#$����%��&���!��%'�����

��������������������������������������������!���"���!�����"�!�(�)�

*���$��������!!��#�����&�����!��������"+,�"���"���

����$�������!!������%"�-��#��

��.�"/�����&��������$�� ��� � �"��� ��%�%�%�����������

����� ��0"���"����%��&���0������!!���������� �+�(���������"+

������"�%�����$��%����������!�����������$����$��� �+

����������������%%������!���"/����-�"1��$��!%� ������������"

���"�&��"�(��"�2��"�%�

�� !��������������

�� �

!��������������

� � !��������������

���

���

����

��

��

��

� ��

�� ���

���

���

���

�� ���

���

���

� �

���

��

�� ���

������������������������

���������������������������

����

���

���������������

��

���������������

��

��

������

��

���������������������������������

���� ���������������������

���������������������������������

���� ����������!�������

��

���

������

� �������

��� ���������

� �������

��� ���������

�� ���

������� ���������� ����������� ����������� ��� �

���!������ "���� � ������ ��������� ����#�$�

%��������� �����������! ��������������&'������� �

��� ������ ���� ���� ��(�����

)��*�+��!!��$��,,������� ����� ��!�!����� � �����

�������(��������� ��������������-������� �������.����

��������/��01

2��3��4�����!������� ������������������� � � �� �����

�����������5��� ��� � ��!���5���� ���� ������ ���&�#�

�����������&� ���� ���� ���� �� ��������������� �� ��

��� ������&�������� � ��� � ���������4����(��6������

������� ������������!����#����7���� �

FDYQ100KAV1

FDYQ125KAV1

FDYQ160KAV19

FDYQ180MV1

Dimensions and Service Space

Page 12: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

9 Inverter Ducted Air Conditioners

EDAU01 - 410

����

���

���

��

���

��

� ��

������

���

������

��

��

���

��

��

���

��

������

���

���

���� ���� ��������������

�������������������� ����

��

��

����

����

��������� �����

���

��������� �����

��

������

��

���������������������������������

����������������������������

�������������������������

�������������������������������

��

���

�������

�� �������

��� � ����� �

�� �������

��� � ����� �

���

�����

���������������������� ���������������� !����"�

���#������"$����������������������������%�&�

'���!������������ �����#���������������()���������

����!���������������"��*�� ��

+��,�-��##��&��..�������"��������#�#�����""�������

�������*���������"����� ��������/���������������0��

������� 1���23

4��5��6�����#��������!������������������"�"�"��������

�����������7���������"��#���7��������������������(�%�

�����������(������"�����!���"����������������������!��

����!�����(��������������""�����������6����*��8��!���"

��������������������#����%����9����"�

����

���

���

��

���

��

� �

������

���

������

���

��

��

��

���

��

��

������

��

���

���� ���� ��������������

�������������������� ����

��

��

���

���

��������� �����

��

��������� �����

��

������

��

���������������������������������

����������������������������

�������������������������

�������������������������������

���

���

��������

�� �������

��� � ����� �

�� �������

��� � ����� �

���

�����

���������������������� ���������������� !����"�

���#������"$����������������������������%�&�

'���!������������ �����#���������������()���������

����!���������������"��*�� ��

+��,�-��##��&��..�������"��������#�#�����""�������

�������*���������"����� ��������/���������������0��

������� 1���23

4��5��6�����#��������!������������������"�"�"��������

�����������7���������"��#���7��������������������(�%�

�����������(������"�����!���"����������������������!��

����!�����(��������������""�����������6����*��8��!���"

��������������������#����%����9����"�

FDYQ200PV1

FDYQ250MV19

Dimensions and Service Space

Page 13: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

10Inverter Ducted Air Conditioners

EDAU01 - 410 Dimensions and Service Space

3.2 Outdoor Units

RXS50JVMA

RXS60JVMA

RZQ71KBV4A

Page 14: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

11 Inverter Ducted Air Conditioners

EDAU01 - 410Dimensions and Service Space

RZQ100KV4A

RZQ125KV4A

RZQ160KV4A

RZQ100HY4A

RZQ125HY4A

RZQ160KHYA

Page 15: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

12Inverter Ducted Air Conditioners

EDAU01 - 410 Dimensions and Service Space

RZYQ7PY1

RZYQ8PY19

RZYQ10PUY1

Page 16: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

13 Inverter Ducted Air Conditioners

EDAU01 - 410Installation and Service Space

4. Installation and Service SpaceRZQ71KBV4A (For RXS50/60JVMA Refer Page No. 10)

Page 17: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

14Inverter Ducted Air Conditioners

EDAU01 - 410 Installation and Service Space

RZQ100KV4A / RZQ100HY4A

RZQ125KV4A / RZQ125HY4A

RZQ160KV4A / RZQ160HY4A

Page 18: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

15 Inverter Ducted Air Conditioners

EDAU01 - 410Installation and Service Space

RZYQ7PY1

RZYQ8PY19

RZYQ10PUY1

Page 19: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

16Inverter Ducted Air Conditioners

EDAU01 - 410

5. Piping Diagrams

Piping Diagrams

5.1 Indoor Units

FDYQ180MV1

FDYQ200PV1

FDYQ250MV19

FDYQ50DV1 / FDYQ60DV1

FDYQ71FAV19 / FDYQ100KAV1

FDYQ125KAV1 / FDYQ160KAV19

Page 20: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

17 Inverter Ducted Air Conditioners

EDAU01 - 410Piping Diagrams

5.2 Outoor Units

RXS50JVMA

RXS60JVMA

RZQ71KBV4A

Page 21: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

18Inverter Ducted Air Conditioners

EDAU01 - 410 Piping Diagrams

RZQ100KV4A

RZQ125KV4A

RZQ160KV4A

RZQ100HY4A

RZQ125HY4A

RZQ160HY4A

Page 22: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

19 Inverter Ducted Air Conditioners

EDAU01 - 410Piping Diagrams

RZYQ7PY1

RZYQ8PY19

RZYQ10PUY1

Page 23: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

20Inverter Ducted Air Conditioners

EDAU01 - 410 Capacity Correction Ratio

6. Capacity Correction Ratio

RXS50JVMA

RXS60JVMA

RZQ71-160

Page 24: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

21 Inverter Ducted Air Conditioners

EDAU01 - 410Capacity Correction Ratio

RZYQ7-8

RZYQ10

Page 25: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

22Inverter Ducted Air Conditioners

EDAU01 - 410

7. Wiring Diagrams

7.1 Indoor Units

Wiring Diagrams

�� �� �� ��

���

���

��

��

��

��� �

��

���

���

���

����

��� ��

��

��� ���

��

��

��� �

� �� �

��

���

���

��

���

��

���

���

���

!��!

����

��

�"

���

�#�

��

���

��

��

��

����

���

��

����

��

��

���

��

��

!��

��

��

����

"

�!�

����

���

��

��

���

�!�

���

���

���

��

���

���

����

��

��

�$

%���

�&

$%

���$

�'

!��

�!�

%�

��$

!

�(

!

���

��!

�)

!

%� ��

!

���

!� �

���

��"

��

*!�

��

����

"

���

!� �

���

��"

��$

!

��

+���

���

���

!�

�,!

��*

!�

�)!

��

,!

�,

$!

&

����

��!

��

�!�

�� ��

��

���

��

��

--

��

��

����

����

��

-

��

� �

.����

����

���

.��

��

��!�

��

���

�+ �+��

���

����

����

�!�

���

���

���

��

���

���

��

���

����

���

���

���

���

����

��!

���

!���

����

���

���

����

���

���

���

!��!

���

���

!��

!�+

�+��

�*

!/��

��!�

!��

����

!�!

���

���

���

��

����

���

���

����

���

!��!

����

��

���

���!

��

����

��

���

+

&+�

���

����

��

��

���

���

���

���!

��%

!�

+��!

���

��

��

���

���

��!�

�!��

��

����

!��

!���

���

��

��

���

���

���

���

���

��!�

��+

�+��

��

��

���

���

���

��

���

����

����

��

���

����

���

��

���

���

���"

����

���

���

!��!

���

���

!��

!��!

��

���

��

��

��

��!�

!+

)+��

���

��

��

.���!

� ��

��

.���

����

�.��

����

���

�.��

���

����

.����

����

��.��

����

���

�.�

!�

��

.�

���

���

.��

!�

.���

��

����

FDYQ50DV1

FDYQ60DV1

Page 26: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

23 Inverter Ducted Air Conditioners

EDAU01 - 410Wiring Diagrams

��

��

��

���

���

� ��

��

���

���

��

�����

�� ��

� ��

� ��

� ��

���

���

����

���

���

������������

����

���

��

� � !

����

�"

"��

#�����

��

���

���

���

���

"��

�"

��

���

���

���

���

� $ ��

��

$�

� $

��

��

� $��

�� % ����%

%��"

�% �

���

�"

%

� & �

���

���

& ���

�� & �

�����

��' & �

�'

�� & �

����

"

�� & "

���

� & �

��

�"

&

���

�"

�� & �

��"

�� �����' �

�� %

���

�' �

� �

��

����� �

�������

�� �

��' �

�� ��'��� �

���

�� ��� �

�%��

��� �

� %

���

����

%

"��

�� %

��"

% �

�� �

����� %

�����

��

�� ��

�� (���) ������

��

���

� �

�% �

%�'

�� *

��� �

������

��������� �

��������

��

����%

��

& ������

��

& ���������

& ���

�' "

����

& ���

� �

�' %

����

& +�

���� �

��������

& "

��� �

����

��

�� "��

�' �

�����

��������

��

����

�"

���

���

� $��

��

� ���!

��#

�,

��

��

���

���

���

���

%"

���� �

��

���

��

��

��

(���� �

)

%%�

(���� �

) � �

� ��

� ��

���

� ��

����

��

� ��

���

"��

��'

���

���

��$��

��

��

�$�

����

����

��

%%�

���

���

��'

���

(���� �

)

(���� �

)

FDYQ71FAV19

FDYQ100KAV1

FDYQ125KAV1

FDYQ160KAV19

Page 27: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

24Inverter Ducted Air Conditioners

EDAU01 - 410 Wiring Diagrams

�� ������ �� ��

���

��� �

�����

�����

����

����

� �

� �

� �

��

��

��

��

���

���

��

�����

�� ��

����

����

����

����

����

����

����

���

���

���

������

���

���

��

����

���

� ���

������

���

�����

��

���

���

���

���

��

��

� �� �

�!�"��

��"�"��

��"�����

"

������#��������������������#�����

���� �#���� �������������#����

��� ��

�#� �����������������#��

����

��� ���#� �����������������

�#������

�������#����

�!������"���"��

������������

��

�����

������$���

�������������

�����������������������������

��������������"���������������!

�!� ���������"�����������

������

�����������������

����������������!

���"

�!������������������#�����

����

��������������������#���

�����

��������������������#��������

����

��������������������#���� �����"���

��������������������#�%��

�������

����

��������������������#��

��������

��&�

�'�

���

���������

���"���

���(�

����"�

�""����

���� ��������

��������������������������

��

��

���

���������

��

��������

)�����������""��*

"++��,-+��

���

���

���

���

���

���

�./0

"-1

)2++�-345+*

�&�

��

���

��

���

���

���

���

"��������

���

��

��

FDYQ180MV1

FDYQ200PV1

FDYQ250MV19

Page 28: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

25 Inverter Ducted Air Conditioners

EDAU01 - 410

7.2. Outdoor Units

Wiring Diagrams

RXS50JVMA

Page 29: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

26Inverter Ducted Air Conditioners

EDAU01 - 410 Wiring Diagrams

RXS60JVMA

Page 30: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

27 Inverter Ducted Air Conditioners

EDAU01 - 410Wiring Diagrams

RZQ71KBV4A

Page 31: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

28Inverter Ducted Air Conditioners

EDAU01 - 410 Wiring Diagrams

RZQ100KV4A

RZQ125KV4A

RZQ160KV4A

Page 32: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

29 Inverter Ducted Air Conditioners

EDAU01 - 410Wiring Diagrams

RZQ100HY4A

RZQ125HY4A

RZQ160HY4A

Page 33: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

30Inverter Ducted Air Conditioners

EDAU01 - 410 Wiring Diagrams

RZYQ7PY1

RZYQ8PY19

Page 34: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

31 Inverter Ducted Air Conditioners

EDAU01 - 410Wiring Diagrams

RZYQ10PUY1

Page 35: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

32Inverter Ducted Air Conditioners

EDAU01 - 410

8.1 Indoor Units (FDYQ50-160)

8.1.1 System and Outdoor

Electrical Characteristics

8. Electrical Characteristics

Page 36: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

33 Inverter Ducted Air Conditioners

EDAU01 - 410

8.2 Indoor Unit (FDYQ180-200)

8.2.1 Outdoor Unit

Electrical Characteristics

Page 37: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

34Inverter Ducted Air Conditioners

EDAU01 - 410

9. Capacity Tables

Capacity Tables

FDYQ50DV1

RXS50JVMA

FDYQ60DV1

RXS60JVMA

Page 38: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

35 Inverter Ducted Air Conditioners

EDAU01 - 410Capacity Tables

FDYQ71FAV19

RZQ71KBV4A

FDYQ100KAV19

RZQ100KV4A

Page 39: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

36Inverter Ducted Air Conditioners

EDAU01 - 410 Capacity Tables

FDYQ125KAV1

RZQ125KV4A

FDYQ160KAV19

RZQ160KV4A

Page 40: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

37 Inverter Ducted Air Conditioners

EDAU01 - 410Capacity Tables

FDYQ100KAV1

RZQ100HY4A

FDYQ125KAV1

RZQ125HY4A

Page 41: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

38Inverter Ducted Air Conditioners

EDAU01 - 410 Capacity Tables

FDYQ160KAV19

RZQ160HY4A

FDYQ180MV1

RZYQ7PY1

Page 42: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

39 Inverter Ducted Air Conditioners

EDAU01 - 410Capacity Tables

FDYQ200PV1

RZYQ8PY19

FDYQ250MV19

RZYQ10PUY1

Page 43: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

40Inverter Ducted Air Conditioners

EDAU01 - 410 Operation Limits

10. Operation Limits

RXS50JVMA

RXS60JVMA

RZQ71KBV4A

Page 44: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

41 Inverter Ducted Air Conditioners

EDAU01 - 410Operational Limits

RZYQ7PY1

RZYQ8PY19

RZYQ10PUY1

RZQ100KV4A / RZQ100HY4A

RZQ125KV4A / RZQ125HY4A

RZQ160KV4A / RZQ160HY4A

Page 45: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

42Inverter Ducted Air Conditioners

EDAU01 - 410 Fan Performance

11. Fan Performance

FDYQ50DV1

FDYQ60DV1

Fan Characteristics

Fan Automatic Adjustment

��������

Page 46: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

43 Inverter Ducted Air Conditioners

EDAU01 - 410Fan Performance

������������������

FDYQ100KAV1FDYQ71FAV19

Page 47: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

44Inverter Ducted Air Conditioners

EDAU01 - 410

��������

��������

FDYQ160KAV19FDYQ125KAV1

Fan Performance

Page 48: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

45 Inverter Ducted Air Conditioners

EDAU01 - 410

0

50

100

150

200

250

300

54 64 74 84 94

(mmH2O) (Pa)

5

10

15

25

(l/s)

(m3/min)

High (high ESP)

High (standard ESP)

Low speed

Exte

rna

l S

tatic P

ressu

re

1200 1400 1600

Air Flow

20

900 1000

3PDA1271

50Hz 230V

FDYQ200PV1FDYQ180MV1

Fan Performance

Page 49: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

46Inverter Ducted Air Conditioners

EDAU01 - 410 Fan Performance

FDYQ250MV19

Page 50: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

47 Inverter Ducted Air Conditioners

EDAU01 - 410Sound Level

12. Sound Level

12.1 Overall Sound Level

12.1.1 Indoor Unit

��(��

�()*

�()*��(��

Page 51: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

48Inverter Ducted Air Conditioners

EDAU01 - 410

12.1.2 Outdoor Unit

Sound Level

Note: 1. Operation sound is measured in an anechoic chamber.

2. Sound level will vary depending on a range of factors such as the construction

(acoustic absorption coefficient) of the particular room in which the equipments installed.

3. Operating conditions: 50Hz, 240V

��

� �

Page 52: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

49 Inverter Ducted Air Conditioners

EDAU01 - 410Sound Level

Note: 1. Operation sound is measured in an anechoic chamber.

2. Sound level will vary depending on a range of factors such as the construction

(acoustic absorption coefficient) of the particular room in which the equipments installed.

3. Operating conditions: 50Hz, 415V

Page 53: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

50Inverter Ducted Air Conditioners

EDAU01 - 410 Sound Level

12.2 Octave Band Level

12.2.1 Indoor Unit

FDYQ71FAV19 FDYQ100KAV1 FDYQ125KAV1

FDYQ180MV1 FDYQ200PV1

FDYQ250MV19

FDYQ160KAV19

Page 54: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

51 Inverter Ducted Air Conditioners

EDAU01 - 410Sound Level

12.2.2 Outdoor Unit

RXS50JVMA (Cooling) RXS50JVMA (Heating)

RXS60JVMA (Cooling) RXS60JVMA (Heating)

RZQ71KBV4A (Cooling) RZQ71KBV4A (Heating)

Page 55: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

52Inverter Ducted Air Conditioners

EDAU01 - 410 Sound Level

RZQ100KV4A (Cooling) RZQ100KV4A (Heating)

RZQ125KV4A (Cooling) RZQ125KV4A (Heating)

RZQ160KV4A (Cooling) RZQ160KV4A (Heating)

Page 56: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

53 Inverter Ducted Air Conditioners

EDAU01 - 410Sound Level

RZQ100HY4A (Cooling) RZQ100HY4A (Heating)

RZQ125HY4A (Cooling) RZQ125HY4A (Heating)

RZQ160HY4A (Cooling) RZQ160HY4A (Heating)

Page 57: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

54Inverter Ducted Air Conditioners

EDAU01 - 410

RZYQ7PY1 (Cooling) RZYQ7PY1 (Heating)

RZYQ8PY19 (Cooling) RZYQ8PY19 (Heating)

RZYQ10PUY1 (Cooling) RZYQ10PUY1 (Heating)

Sound Level

Page 58: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

55 Inverter Ducted Air Conditioners

EDAU01 - 410Centre of Gravity

13. Centre of Gravity

RXS50JVMA

RXS60JVMA

RZQ71KBV4A

Page 59: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

56Inverter Ducted Air Conditioners

EDAU01 - 410 Sound Level

RZQ100KV4A

RZQ125KV4A

RZQ160KV4A

RZQ100HY4A

RZQ125HY4A

RZQ160HY4A

Page 60: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

57 Inverter Ducted Air Conditioners

EDAU01 - 410Sound Level

RZYQ7PY1

RZYQ8PY19

RZYQ10PUY1

Page 61: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

58Inverter Ducted Air Conditioners

EDAU01 - 410

14. Optional Accessories

Optional Accessories

Page 62: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

59 Inverter Ducted Air Conditioners

EDAU01 - 410

SAFETY CONSIDERATIONS

Please read these “SAFETY CONSIDERATIONS” carefully before installing the air conditioning equipment and be sure to install

it correctly. After completing the installation, make sure that the unit operates properly during the start-up operation. Please

instruct the customer on how to operate the unit and keep it maintained.

Please inform the customer that they should store this installation manual along with the operation manual for future reference.

This air conditioner comes under the term “appliances not accessible to the general public”.

Meaning of warning and caution symbols

WARNING . . . . . . Failure to observe a warning may result in death, injury or damage to the equipment.

CAUTION . . . . . . Failure to observe a caution may result in injury or damage to the equipment.

WARNING

l Ask your Dealer or qualified personnel to carry out installation work. Do not try to install the machine yourself.Improper installation may result in water leakage, electric shock or fire.

l Perform installation work in accordance with this installation manual.Improper installation may result in water leakage, electric shock or fire.

l Be sure to use only the specified accessories and parts for installation work.Failure to use the specified parts may result in water leakage, electric shock, fire or the unit failing.

l Install the air conditioner on a structure strong enough to withstand the weight of the unit.A structure of insufficient strength may result in the equipment falling and causing injuries.

l Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes.Improper installation work may result in the equipment falling and causing accidents.

l Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualified personnel according to local laws, regulations and this installation manual.

An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire.

l Make sure that all wiring is secured, the specified wires are used, and no external forces act on the terminal connections or wires.Improper connections or installation may result in fire.

l When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the wires so that the switch box cover can be securely fastened.

Improper positioning of the switch box cover may result in electric shock, fire or the terminals overheating.

l If the refrigerant gas leaks during installation, ventilate the area immediately.Toxic gas may be produced if the refrigerant gas comes into contact with fire.

l After completing the installation work, check that the refrigerant gas does not leak.Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire, such as a fan heater,

stove or cooker.

l Before obtaining access to the terminals and electrical parts, all supply circuits must be disconnected.

l Do not install the indoor unit or remote controller where they may be exposed to rain or moisture.Water or other fluids on the electrical components may result in fire or electric shock.

l Earth the air conditioner. Do not connect the earth wire to gas or water pipes, a lightning conductor or a telephone ground wire.Incomplete earthing may result in electric shock.

l Be sure to install an earth leakage breaker. Failure to install an earth leakage breaker may result in electric shock.

l Do not install the indoor unit or remote controller where flammable gases may leak, where there are carbon fibre or ignitable dust suspended in the air, or where volatile flammables such as thinner or gasoline are handled.

l Do not install the indoor unit or remote controller where the area is filled with steam or the ground is always wet. Insulation of the electric components may be damaged in such conditions and may result in electric shock.

l Be sure to only use refrigerant piping approved for use with R410A refrigerant. The use of unapproved piping may result in explosive rupture.

CAUTION

l Do not install the air conditioner for purposes other than for human comfort. Do not use the air conditioner for special applications such as the storage of foods, animals and plants, precision machines and art objects. Deterioration of quality may result.

l This model is not designed for free blow operation. Supply and Return air duct work must be installed. External duct work and air boxes must be adequately insulated to prevent condensation.

l It is recommended that a safety drain tray is installed. Ensure that it drains separately.

l While following the instructions in this installation manual, install drain piping in order to ensure proper drainage and insulate piping in order to prevent condensation. Improper drain piping may result in water leakage and property damage.

l Install the indoor and outdoor units, power cords and connecting wires at least 1 metre away from televisions or radios in order to prevent image interference or noise.

(Depending on the radio waves, a distance of 1 metre may not be sufficient enough to eliminate noise.)

l Do not install the air conditioner in the following locations:(a) Where a mineral oil mist, oil spray or vapour is produced, for example in a kitchen.

Plastic parts may deteriorate.

(b) Where corrosive gas, such as sulfuric acid gas, is produced.

Corroding copper pipes or soldered parts may result in refrigerant leakage.

(c) Near machinery emitting electromagnetic waves.

Electromagnetic waves may disturb the operation of the control system and result in a malfunction of the equipment.

(d) Where salinity in the air is relatively high.

l Be sure to attach a return air filter (field supplied) inside the return air passage. Failure to install the filter will cause equipment failure.

15. Installation Manual FDYQ50-60DV1

FDYQ(N)71FAV1

FDYQ(N)100-160KAV1

Installation Manual

Page 63: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

60Inverter Ducted Air Conditioners

EDAU01 - 410

ACCESSORIES Check that the following accessories are included with your unit.

OPTIONAL ACCESSORIES

l A Daikin remote controller is not included with the indoor unit.

Install the remote controller in an appropriate place according to the customer’s request.

If utilising the temperature sensor in the remote controller BRC1D619 (see page 14) ensure that the controller

is installed in a location where the correct air temperature is measured.

l Hanging brackets are required if the indoor unit is to be suspended. (Available in packs of 4)

BEFORE INSTALLATION

l The accessories needed for installation must be retained in your custody until the installation work is completed.

Do not discard them!

l Decide upon a safe line of transport.

l Try to leave the unit inside its packaging whilst moving. Where unpacking is unavoidable use a sling of soft

material or protective plates together with a rope when lifting to avoid damage or scratches to the unit.

l When opening the unit or moving it after opening be sure to lift it by holding onto the unit carefully without

exerting any pressure on other parts, especially drain piping, refrigerant piping and other resin parts.

l Be sure to check the type of refrigerant to be used before doing any work. (Using an incorrect refrigerant will

prevent normal operation of the unit.) This model uses R410A.

l Refer to the installation manual of the outdoor unit in conjunction with this manual for items not described in this

manual.

PRECAUTIONS

l Be sure to read this manual before installing the indoor unit.

l This unit is for indoor use only.

l This unit is suitable for installation in a household, commercial and light industrial environment.

l Do not install or operate the unit in rooms mentioned below.

l Laden with mineral oil or filled with oil vapour or spray like in kitchens.

l Where corrosive gas like sulfuric gas exists.

l Where volatile flammable gas like thinner or petrol is used.

l Where machines can generate electromagnetic waves.

l Where the air contains high levels of salt or other corrosive materials.

l Where voltage fluctuates greatly.

l In vehicles or vessels.

l To avoid water leaks, etc., be sure to install a return air filter (field supplied) inside the return air passage.

Installation Manual

Page 64: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

61 Inverter Ducted Air Conditioners

EDAU01 - 410

FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER

INSTALLATION IS FINISHED.

(1) Items to be checked after completion of work

Items to be checked If not properly done, what is likely to occur Check

Is the indoor unit fixed firmly? The unit may drop, vibrate or make noise.

Is the gas leak test finished? It may result in insufficient cooling or heating

Does the unit require external insulation? Condensate water may drip.

Does drainage flow smoothly? Condensate water may drip.

Does the power supply voltage correspond to that shown on

the name plate?

The unit may malfunction or the components burn out.

Is the wiring and piping correct? The unit may malfunction or the components burn out.

Is the unit safely grounded? Dangerous during electric leakage.

Is the wiring size according to specifications? The unit may malfunction or the components burn out.

Is something blocking the air outlet or inlet of either the

indoor or outdoor units?

It may result in insufficient cooling or heating.

Are refrigerant piping length and additional refrigerant charge

noted down?

The refrigerant charge in the system is not clear.

Is the indoor unit positioned so that it is not in contact with

parts of the ceiling?

Vibration and noise can be transmitted into building.

Is the airflow within specification? Poor performance or malfunction.

Is an air filter installed in the return air?Blocked heat exchanger causing malfunction or compressor

failure.

Is an external drain tray installed? Condensate water may drip.

(2) Items to be checked at completion

l Did you show the customer how to operate the system while referring to the operation manual?

Detailed explanation about operation.

Review the safety considerations.

l Did you hand the operation manual over to the customer?

NOTE TO THE INSTALLER

Be sure to instruct the customer how to properly operate the system (especially cleaning filters, operating the

different functions and adjusting the temperature). It is recommended to ask the customer to carry out the

operations themselves while you instruct them and refer them to the applicable place in the operation manual.

(1) Select an installation site where the following

conditions are fulfilled and that meets your

customer’s approval.

l Where the indoor unit and remote controller are

not exposed to rain or moisture.

l Where the casing of the unit does not contact

parts of the ceiling.

l Where optimum air distribution can be ensured.

l Where nothing blocks the air passage.

l Where condensate can be properly drained.

l Where the structure is strong enough to safely

bear the indoor unit weight.

l Where sufficient clearance for maintenance and

service can be ensured. (see Fig. 1)

l Where there is no risk of flammable gas leakage.

SELECTING INSTALLATION SITE

l Where piping between indoor and outdoor units is

possible within the allowable limit. (Refer to the

installation manual for the outdoor unit.)

CAUTION

l Keep the indoor unit, outdoor unit, power supply

wiring and transmission wiring at least 1 metre

away from televisions and radios. This is to

prevent image interference and noise in those

electrical appliances. (Noise may be generated

depending on the conditions under which the

electric wave is generated, even if 1 metre is kept.)

(2) When using suspension bolts for installation, hanging

brackets should be installed. Confirm that the

ceiling is strong enough to support the weight of

the indoor unit.

Installation Manual

Page 65: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

62Inverter Ducted Air Conditioners

EDAU01 - 410

AF B

Inspection Hatch(450 mm X 450 mm

E

C

D

61 61

30,555,5

AIR OUTLET

AIR INLET

Moun

ting

Cent

re

Electrical Box

Inspection Hatch(450 mm X 450 mm

l Hanging brackets are sold as an optional accessory

for FDYQ(N) series.

(3) If the installation requires the indoor unit to be exposed

please ensure the unit is more than 1.8m above the floor so

that children can not touch the unit.

(4) A suitable air filter (field supplied) must be installed within the

return air duct.

Liquid pipe

Gas pipe

Drain pipeElectrical boxcoverFDYQ(N)71-160

Electrical boxcoverFDYQ50-60DV1

Spigot

Service Space300m(See service space note below)

m or more

Service Space450mmor more

Ceiling

H*

Notes:

H* (20-30 mm) is necessary to connect the drain pipe.

Determine size H* based on 1/100 of the required

downward inclination indicated in “DRAIN PIPING WORK”.

Pg9

“Service Space” is the minimum recommended distance. In

some “restricted space” installations it may be necessary to

reduce this distance. Please note that this may necessitate

additional service work should maintenance or repair be

required.

Fig. 1

Fig. 2

Model A B C D

FDYQ50-60DV1

1090 1055 348 869FDYQ(N)71FV1

1400 1365 348 899

E

461

1000 1051 341 852 393

461FDYQ(N)100-160KV1

981

1055

1365

F

Table 1

PREPARATIONS BEFORE INSTALLATION

To facilitate installation, the indoor unit can be easily separated into smaller parts to make it easier to move to the

final position. See page 16 for details.

(1) Refer to Table 1 and Fig 3 for suspension bolt position and horizontal representation of the indoor unit.

NOTE: Additional thermal insulation material (thickness 10mm or more of glass wool or polyethylene foam)

may be required if the conditions in the ceiling exceeds 30oC and RH 80% or outside air is introduced into the

ceiling or the unit operates for 24 hours. It is also important that a safety drain tray be used. (see Fig.11)

AIR INLETAIR OUTLET

Inspection Hatch(450 mm X 450 mm

E

B

C

D

F

A

53 26

26

26

4470Mo

untin

g Ce

ntre

Inspection Hatch(450 mm X 450 mm

ELECTRICAL BOX

Fig. 3

Installation Manual

Page 66: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

63 Inverter Ducted Air Conditioners

EDAU01 - 410

(2) Install the suspension bolts. (Fig. 3 & 4)

(Use M10 size rod for the suspension bolt)

Use an anchor suitable for both the material being

anchored to and the weight of the unit.

(3) Be sure to completely insulate all external duct work

and fittings.

(4) If using rigid duct work install a canvas (or similar) duct

to the air inlet and air outlet so as not to transmit vibration

from the unit to the duct.

Apply acoustic insulation to the inside of the duct.

(5) Install suitable vibration isolator to the suspension bolts.

Ceiling slab

Anchor

Long nut or turn-buckle

Suspension bolt

Indoor unit

CeilingFig. 4

NOTE: All the above parts are field supplied

INDOOR UNIT INSTALLATION

(1) For suspended installation, hanging brackets should be installed

on the unit.

Attach the hanging brackets to the 8 mounting holes located on the

sides of the unit. (Fig. 3) The maximum length of the securing bolts

must not exceed 20mm (M6 - bolt)

(2) Carefully lift the unit so that the hanging brackets can locate on to

the suspension bolts. (Fig 5) Be sure to clamp the bracket securely

by using a nut and washer (field supplied) from the upper and

lower sides of the hanging bracket. Ensure that the suspension

bolts are firmly secured. (No up or down movement) (Fig. 5)

CAUTION

(3) Make sure the unit is level.

l Level the unit with a water level or other suitable means. If the

unit is not level, it could become the source of water leaks.

l Check if the unit is level at all four corners with a water level or a

water-filled vinyl tube as shown in the diagram. (Fig. 6)

(4) Tighten the upper nut.

Nut (field supply)

Tighten

(double nuts)

Washer

Hanging Bracket

Fig. 5

Vinyl tube

Water level

Supply air flange

Fig. 6

REFRIGERANT PIPING WORK

ALL REFRIGERANT PIPING WORK MUST ONLY BE CARRIED OUT BY A QUALIFIED PERSON

** For refrigerant piping of outdoor units, see the installation manual attached to the outdoor unit. **

Fully insulate the liquid and gas piping separately. Do not leave any gaps otherwise a water leak may occur.

(Seal any joints with glue or duct tape)

When operating in the heating mode, the temperature of the gas piping can reach up to approximately 120o C,

so use insulation which has a suitable temperature rating.

Also, in cases where the temperature and humidity surrounding the refrigerant piping can exceed 30o C or RH

80%, reinforce or use thicker pipe insulation (20 mm or thicker). Otherwise condensation may form on the

surface of the insulating material.

** Be sure to check the type of refrigerant to be used before doing any work. Using an incorrect refrigerant

will prevent normal operation of the unit. ** In case of FDYQ50-60DV1, FDYQ(N)71F & FDYQ(N) 100-160K

model(s) = R410a

CAUTION

l Avoid introduction of air or other contaminents into the refrigerant piping. If any air, moisture or other contaminent

remains in the refrigerant piping after the completion of installation the system will malfunction.

l Carry out sufficient ventilation if the refrigerant gas leaks during installation work.

l Use only R410a rated copper seamless tube manufactured to AS/NZS1571.

Page 67: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

64Inverter Ducted Air Conditioners

EDAU01 - 410

Torque wrench

SpannerFlare nut

Piping union

Fig. 7

Coat here with ether oil

Fig. 8

l Be sure to use both a spanner and torque wrench together, as shown in the diagram, when connecting or

disconnecting pipes to/from the unit. (Fig. 7)

l Use only a flaring block suitable for R410a tube. Refer to Table 2 for the specifications of the flare work.

l When connecting the flare nut, coat the flare both inside and outside with ether oil and initially tighten

by hand 3 or 4 turns before tightening firmly. (Fig. 8)

l Use the flare nuts included with the indoor unit.

l Refer to Table 2 to determine the proper tightening torque.

CAUTION

l Over tightening the flare nuts may cause the flare nuts or copper tube to fail and allow the refrigerant to leak.

l Caution to be taken when brazing refrigerant piping. (Where applicable)

Do not use flux when brazing refrigerant piping. Use the phosphor copper brazing filler metal (BCuP)

which does not require flux. (Flux has an extremely harmful influence on refrigerant piping systems. For

instance, if chlorine based flux is used, it will cause pipe corrosion, particularly if the flux contains fluorine, it will

damage the refrigerant oil.)

During any brazing of the refrigerant piping, you must continually blow dry nitrogen gas through the piping to

expel air from the piping. (Fig. 9) If you braze the piping without doing so a large amount of oxide film

develops inside the piping and could cause system failure.

Ensure that you use a pressure reducing valve on the dry nitrogen bottle to prevent pinholes caused by

excessively high pressure. (Set the pressure of nitrogen gas to about 0.2 kg / cm2 [19.6 kPa])

Nitrogen

Refrigerant piping

Tape the pipe

Valve

Nitrogen

Reducing valve

Fig. 9

Pipe size Tightening torque Flare dimensions A (mm) Flare

6.4 (1/4") 14.2 - 17.2 N m (144 - 175 kgf cm) 8.6 - 9.0

9.5 (3/8") 32.7 - 39.9 N m (333 - 407 kgf cm) 12.6 - 13.0l

l l

l

12.7 (1/2") 49.5 - 60.3 N m (504 - 614 kgf cm) 15.8 - 16.2l l

15.9 (5/8") 61.8 - 75.4 N m (630 - 770 kgf cm) 19.3 - 19.7l l

R0.4 ~ 0.8

A

45

o ± 2

o

90

o ±

2o

Table 2

Page 68: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

65 Inverter Ducted Air Conditioners

EDAU01 - 410

DRAIN PIPING WORKWARNING Install the drain pipe as shown below and take measures against condensation, improperly

installed piping may result in water leaks and eventually wet furniture and belongings.

(1) Installing

l Route the pipes so as to ensure that drainage can occur with no problems. (Fig. 10)

l Employ piping with either the same diameter or with the diameter larger

(excluding the raised section) than that of the connecting pipe (PVC

pipe, nominal diameter 25 mm, outside diameter 32 mm).

l Keep the drain pipe short and sloping downward at a gradient of

at least 1/100 to prevent air pockets from forming.

l To prevent the drain pipe from sagging, secure the pipe every

1 to 1.5 m.

l Use the provided drain hose 2 and clamp 1 . (Fig. 11)

Tighten the clamp firmly.

l Insulate the metal clamp with a field supplied sealing pad. (Fig. 11)

l Insulate the drain hose inside the building.

l As a safety measure, please use a safety drain tray (field supplied) and drain separately.

l Insulate drain pipe using piping thermal insulation to prevent condensate dripping during humid conditions.

Note

l To ensure no excessive pressure is applied to the included drain hose 2 , do not bend or twist when

installing. (This may cause leakage.)

WRONG CORRECT

Fig. 10

Not recommended but in case of an emergency

You must use a torque wrench but if you are obliged to install the unit without a torque wrench, you may follow

the installation method mentioned below.

As you keep on tightening the flare nut with a spanner there is a point where the tightening torque suddenly

increases. From that position, further tighten the flare nut using the angle shown below in Table 3:

After the work is finished, make sure to check that there is no gas leak.

Pipe size Further tightening angle

6.4 (1/4") 60 to 90 degrees

9.5 (3/8") 60 to 90 degrees

Recommended arm length of tool

Approx. 150mm

Approx. 200mm

12.7 (1/2") 30 to 60 degrees Approx. 250mm

15.9 (5/8") 30 to 60 degrees Approx. 300mm

Make absolutely sure to properly insulate the connecting pipe work and connections using field supplied

insulation after checking for gas leakage.

CAUTION

Be sure to insulate local piping all the way into the pipe connections inside the machine. Exposed piping may

cause condensation or burns on contact.

Table 3

CAUTION

Drain piping connections.

Do not connect the drain piping directly to sewage pipes. Drainage must conform to local plumbing regulations.

The vapour in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger

or escape into the room.

Installation Manual

Page 69: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

66Inverter Ducted Air Conditioners

EDAU01 - 410

Metal clamp 1

(provided)(field supplied)

Large sealing pad

Drain hose 2

4mm or lessTape (white) (provided)

Metal clamp 1

Drain hose 2

Bottom of the unit

Slo

pe

Safety drain tray

(field supplied)

Fig. 11

NOTE:

l If installing central drain piping,

install according to Fig. 12. 100

mm

o

r m

ore

Note: use this outlet to drain water from the drain pan

Watering can

Drain tray

Refrigerant pipes

Drain outlet

(2) After the piping work is finished, check that

the drainage flows smoothly.

l Pour approximately 1 Litre of water

gradually into the drain tray and check

drainage flow. (Fig.13)

Fig. 13

l Check drainage flow during COOLING OPERATION, explained under the section entitled TEST OPERATION.

WHEN ELECTRIC WIRING WORK IS FINISHED

ELECTRIC WIRING WORK

l All field supplied parts, materials and electric works must conform to local codes. (ie. AS / NZS 3000)

l Use copper wire only.

l For electric wiring work, refer to the "WIRING DIAGRAM" label attached to the electrical box cover.

l For remote controller wiring details, refer to page 13 of this manual for BRC1D619 or the installation manual

supplied with the chosen remote controller.

l All wiring must be performed by an authorised electrician in accordance with local codes. (ie. AS / NZS 3000)

l A circuit breaker capable of shutting down power supply to the entire system must be installed.

l Refer to the installation manual attached to the outdoor unit for the size of the power supply cable connected to

the outdoor unit and wiring instructions.

l Ensure that the air conditioner is effectively earthed.

NOTE: 1. Shield wire materials may be used for transmission wiring, and must comply with EMI (AS / NZS 3548)

or (CISPR 14).

2. Use double insulation wire for the remote controller (Sheath thickness is 1mm or more) or run wires

through a wall or conduit so that the user cannot come in contact with them.

3. Run indoor to outdoor transmission wiring and indoor power supply wiring through a conduit to protect

against external forces. Feed the conduit through the wall together with refrigeration piping.

Fig. 12

Installation Manual

Page 70: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

67 Inverter Ducted Air Conditioners

EDAU01 - 410

Method of wiring. - Refer to Fig. 14 for the wiring details.

NOTE: All wires must be wired through bushes at the bottom of the electrical box.

l Remove the electrical box cover as indicated.

l Power and earth wiring.

Connect the power supply wires to terminals (L, N) and the earth wire to terminal .

Secure the cable to the anchor point below the terminal block. Do not connect the N-line with the

earth terminal.

l Wiring between indoor and outdoor units.

Connect the transmission wire between the indoor and outdoor unit using terminals (1, 2, 3).

Secure the cable to the anchor point below the terminal block.

l Remote controller cords.

Connect the cords to the remote controller terminals - (P1, P2 No polarity) and the shield wire (if

applicable) to the shielding earth terminal .

Secure the cable to the anchor point below the terminal block.

l Replace and secure electrical box cover.

For optional centralremote controller connection

Terminal X2M Block

Shielding Earth

Terminal X1 M Block

Protective earth terminal

Cable Tie

Remote ControllerPower and Earth

Wiring between indoor and outdoor units

Cable Tie

Terminal X2M Block

Shielding Earth

Terminal X1 M Block

Protective earth terminal

Cable Tie

Remote ControllerPower and Earth

Wiring between indoor and

outdoor units

Cable Tie

Fig. 14

Installation Manual

Page 71: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

68Inverter Ducted Air Conditioners

EDAU01 - 410

Round crimp-style

terminal

Electric wire

PRECAUTIONS

Precaution for wiring on site

When connecting the indoor unit to a single phase of a 3 phase power supply, give consideration to the other

electrical equipment connected to the main breaker and select the phase (L1, L2, L3) so that the current (or

voltage) unbalance does not occur.

If current unbalance occurs, the phase current of the compressor may become unbalanced and there is a risk of

protective device actuating or compressor breakdown.

l Do not clamp remote controller cords together with wires connecting the units together. Doing so may cause

malfunction.

l Remote controller cords and wires connecting the units should be located at least 50 mm from other electric

wires. Not following this guideline may result in malfunction due to electrical noise.

Observe the notes mentioned below when wiring to the power supply terminal block. Precautions to be taken for

power supply wiring.

(Use a round crimp-style terminal for connection to the power supply terminal block. (Fig. 15) In case it cannot be

used due to unavoidable reasons, be sure to observe the following instructions.)

l Do not connect wires of different gauge to the same power supply terminal. (Fig. 16)

(Looseness in the connection may cause overheating.)

l When connecting wires of the same gauge, connect them according to the figure below.

l Make certain that prescribed wires are used, carry out complete connections, and secure the wires so that

outside forces are not applied to the terminals.

Fig. 15

Fig. 16

CAUTION

l After connecting the wires, be sure that no pressure is applied to the wire connections by using cable ties (field

supplied) and securing them to the anchor points. Also, when wiring, make sure the cover of the terminal box fits

snugly by arranging the wires neatly and attaching the terminal box cover firmly. When attaching the terminal

box cover make sure no wires get caught under the edges. Ensure that all the cables pass under the offset

section of the electrical box cover.

l Make sure the remote control cord, the wiring between the units, and other electrical wiring do not pass through

the same locations outside the unit, separating them by at least 50 mm, otherwise electrical noise (external

static) could cause incorrect operation of the unit or damage.

WIRING EXAMPLE for BRC1D619 only

(For the wiring of outdoor units, refer to the installation manual attached to the outdoor unit.)

Confirm the system type.

l Single phase pair type: 1 remote controller controls 1 indoor unit (standard system). (Fig. 17)

l 2 remote controller control: 2 remote controller controls 1 indoor unit. (Fig. 18)

l Group control: 1 remote controller controls up to 16 indoor units (All indoor units operate according to the

remote controller). (Fig. 19)

CORRECT WRONG WRONG

Connect wires of

the same gauge to

both sides

Do not connect

wires of the same

gauge to one side

Do not connect

wires of different

gauges

Installation Manual

Page 72: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

69 Inverter Ducted Air Conditioners

EDAU01 - 410

Main power supply

Isolation switch

Fuse

Outdoor unit

(example)

Indoor unit

P1 P2

P1 P2

(NOTE 2)

Remote controller

(option) BRC1D619

NL

NL

NL

Isolation switch

FuseNL

Power supply

1

1 2

2 3

3

P1P2

P1P2Remote controller

(option) BRC1D619

P1P2 P1P2

(NOTE 2)

P1P2

(NOTE 2)

Remote

controller

(option)

BRC1D619

P1P2

Indoor unit Indoor unit Indoor unit

Main power supply

Isolation switch

Fuse

Outdoor unit

(example)

N

Isolation switch

FuseN

Power supply

NL

L

NL

Main power supply

Isolation switch

Fuse

Outdoor unit

(example)

N

Isolation switch

FuseN

Power supply

NL

NL

Main power supply

Isolation switch

Fuse

Outdoor unit

(example)

N

Isolation switch

FuseN

Power supply

NL

NL 1

1 2

2

L

1

1 2

2

L

1

1 2

2

3

3

3

3

3

3

Main power supply

Isolation switch

Fuse

Outdoor unit

(example)

Indoor unit

P1 P2

P1 P2

(NOTE 2)

Remote controller 2

(option) BRC1D619

1 2 3NL

1 2 3NL

NL

Power supply

Isolation switch

FuseNL

P1 P2

P1 P2

Remote controller 1

Group Control (Only Applies To BRC1D619)

Control by 2 remote

controllers

NOTE: 1. All transmission wiring except for the remote controller wires must match the terminal symbol.

2. If using shielded wire for transmission wiring ground the shield of the shield wire to at the

grounding screw of the remote controller cord grounding terminal inside the control box.

3. For group control remote controller choose the remote controller that suits the indoor unit which has

the most functions (as indicated by the swing flap).

l Only applies when other types of indoor units are used within the group eg. Cassette type.

4. When “Group Control” and “Control by 2 remote controllers” are used, connect the remote controller

with the indoor unit which is at the end. (Fig. 19)

(Do not connect three wires or more to the remote control terminals.)

Control by 2 remote controllers

Fig. 18

Fig. 19

Single phase pair type

Fig. 17

Installation Manual

Page 73: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

70Inverter Ducted Air Conditioners

EDAU01 - 410

SECONDCODE NO.

UNIT NO.

FIRSTCODE NO.

MODE NO.

FIELDSETMODE

TEST1 245

6

SETTING

UNIT NO.

3

Setting duct static pressure

Settings

Standard static pressure

High static pressure

Second Code No.

01

02

Mode No. First Code No.

13 (23) 6

Fig. 20

Note:

Remote control displayed

is indicative only.

Depending on the remote

control supplied, the

button layout may be

different.

FIELD SETTINGThe following instructions relate to the BRC1D619 (fig.20) controller, when installing other optional controllers

please refer to the accompanying installation manual for field setting information.

Field setting must be made from the remote controller in accordance with the installation condition.

l Setting can be made by changing the "Mode number", "FIRST CODE No." and "SECOND CODE No.".

l Mode No. without ( ) means the setting will apply to all units connected to the controller. (Group control)

l Mode No. with ( ) means the settings will apply to individual units. It can also be used to check current field settings.

1) Press & hold the test button until 01 or 10 appears.

2) By pressing the temperature up arrow button scroll until the required mode setting number appears.

3) By pressing the timer up arrow button scroll until the required first code setting number appears.

4) By pressing the timer down arrow button scroll until the required second code setting number appears.

5) Press the confirmation button once.

6) Press the test button once & 88 will appear for a few seconds before returning to the normal operation.

Note: The external static pressure setting for the indoor unit is factory set to “standard” external static

pressure. For installations with a duct system that presents a high external static pressure, set the static

pressure value to the “high” position. Refer to the table below and the fan performance curves in the

Engineering Data.

HOW TO SET FIELD SETTING MODES

l Refer to page 15 for models FDYQ50DV1 & FDYQ60DV1

Setting

Filter sign indication [ON]

Filter sign indication [OFF]

Second Code No.

01

02

Mode No. First Code No.

10 (20) 3

Setting air filter sign

Setting temperature sensor location

Settings

Alternate between indoor unit andremote controller sensor

Indoor unit sensor only

Remote controller sensor only

Second Code No.

01

02

03

Mode No. First Code No.

10(20) 2

Indoor fan settings during heating thermo off

Settings

LL

Set speed

OFF

Second Code No.

01

02

03

Mode No. First Code No.

12(22) 3

Installation Manual

Page 74: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

71 Inverter Ducted Air Conditioners

EDAU01 - 410

l When using 2 remote controllers, one must be set to "MAIN" and the other to "SUB".

l When the sub remote controller is required, use optional remote controller model: BRC1D619.

MAIN/SUB CHANGEOVER

(1) Insert a flat blade screwdriver into the recess between the upper and lower part of remote controller and working

from the 2 positions, pry off the upper part. (Fig. 21)

(The remote controller PC board is attached to the upper part of remote controller.)

(2) Turn the main/sub changeover switch on one of the two remote controller PC boards to "S".

(Leave the switch of the other remote controller set to "M".) (Fig. 22)

Indoor fan settings during cooling/heating thermo off

Settings

Normal

Fan OFF

Second Code No.

01

02

Mode No. First Code No.

11(21) 2

ESP (Pa) 10 Pa increments

40-50-60..............180

eg. 80Pa = 13-6-05

Second Code No.Mode No. First Code No.

13 (23) 6 01-02-03......................15

Indoor fan settings during cooling thermo off

Settings

LL Fan Speed

Set Fan Speed

Second Code No.

01

02

Mode No. First Code No.

12(22) 6

SETTING FAN AUTOMATIC ADJUSTMENT (FDYQ50-60DV1 Only)During commissioning stage use this mode to automatically adjust the fan RPM to achieve within +/- 10% of the rated

“High fan” speed airflow (HH). The High fan speed airflow can be adjusted to the rated airflow when the duct

External Static Pressure (ESP) is within the range of 40 – 180 Pa.

Note: Setting Fan Automatic Adjustment for multi zone systems.

Prior to the setting of Fan Automatic Adjustment, the zone that has the highest heat load should be nominated. For

example if the day zone is the nominated area, this area must be activated and the night zone must be deactivated

before commencing the Fan Automatic Adjustment mode.

HOW TO SET FAN AUTOMATIC ADJUSTMENT1) Set the controller to “Fan” mode.

2) Ensure the unit is switched “Off” by the controller “On-Off” button.

3) Hold down the “Test” button until “01” or “10” appears.

4) By pressing the temperature up arrow button scroll until mode number “21” appears.

5) By pressing the timer up arrow button scroll until the first code number setting “7” appears.

6) By pressing the timer down arrow button scroll until the second code setting “03” appears.

7) Press the confirmation button once & then the test button once. 88 will appear for a short time before returning to

normal operation.

8) Press the “On-Off” button to commence the Fan Automatic Adjustment setting. The operation lamp will illuminate &

the indoor fan will operate for a period of 1-8 minutes. To signal the completion of the adjustment, the indoor fan

will stop & the operation lamp will extinguish.

9) To confirm Fan Automatic Adjustment was successfully completed, repeat steps 3-5. Mode “21-7-02” should

appear. (If the indoor fan does not stop or 02 did not appear when Field Set Mode 21 is selected it means the Fan

Automatic Adjustment must be set again).

10) Press the test button once to return to normal operation.

Auto airflow adjustment

Settings

OFF

Completion of airflow adjustment

Start of airflow adjustment

Second Code No.

01

02

03

Mode No. First Code No.

11(21) 7

SETTING THE INDOOR FAN RPM MANUALLY TO SUIT YOUR AIRFLOW REQUIREMENTSIn the case Fan Automatic Adjustment does not suit your airflow requirements the airflow can be manually increased

or decreased. You have a choice of 15 settings.

CONTROL BY 2 REMOTE CONTROLLERS (Controlling 1 indoor unit by 2 remote controllers)

Installation Manual

Page 75: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

72Inverter Ducted Air Conditioners

EDAU01 - 410

S

M

S

S

M

Remote controller

PC board

(Factory setting)

(Only one remote controller needs to be changed)

Upper part of

remote controller

Lower part of

remote controllerInsert the screwdriver here and

gently work off the upper part of

remote controller.

Fig. 22Fig. 21

TEST OPERATION when using BRC1D619 remote control.

X1A

X17A

X18A X2A

1 3

28 10 12

4

6

7 11

1315 14

Fig 23

Fig 24

Fig 25

Fig 26

Rubber BushInsert fan plug in this orientation

Supply Air

Return Air

Heat Exchanger Compartment

Heat Exchanger Compartment

Fan Deck Fan DeckCompartment

Electrical BoxAssembly

ATTENTION: Please separate the indoor unit only when necessary. Please disassemble and reassemble on

a flat surface.

l Separate the indoor unit in the following order.

1) Remove (4) screws located on the electrical box cover. (Fig. 23)

2) Carefully unplug the (2) thermistor cables and fan harness assemblies. Socket location (X17A, X18A, X2A

and X1A) (Fig 25)

3) Remove (6) screws securing the electrical box to the fan deck compartment. (Fig. 23)

4) Untwist wire clamp securing the (2) thermistor cables and carefully remove cables through the rubber

bush. Similarly remove fan harness by carefully passing the plug through the rubber bush. (Fig. 26)

5) Carefully separate the electrical box from the fan deck compartment.

6) Remove (3) M6 and (1) M8 bolts from the fan deck compartment.

7) Carefully separate the fan deck compartment from the heat exchanger compartment, taking care not to

damage the fan motor wiring. (Fig. 23)

8) Remove (5) M8 bolts securing the fan deck to the heat exchanger compartment and detach the fan deck. (Fig. 24)

SEPARATING THE INDOOR UNIT FDYQ50-60DV1

(When using BRC230Z4,BRC230Z8,BRC24Z4 or BRC24Z8 please use zone controller installation instructions.)

Refer to the section of "FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION

AND CHECK AFTER INSTALLATION IS FINISHED" (page 5).

After installation is complete (ie. refrigerant piping, drain piping, electrical wiring, duct work, filter installation and

field settings) conduct a check test as described below to confirm correct operation and installation of the complete

system.

1) Replace all electrical covers.

2) Energise the crank case heater for at least 6 hours before commencing next step.

3) Set to cooling operation with the remote controller and start operation by pushing ON/OFF button. ( )

4) Press Inspection/Test Operation button 4 times ( ) and operate at Test Operation mode for 3 minutes.

5) Press Inspection/Test Operation button ( ) and operate normally.

6) Confirm function of unit according to the operation manual.

PRECAUTIONS 1. In case something is wrong with the unit an error code will appear on the remote control,

refer to the Error Code List (pg18).

2. After completing the test run, press the INSPECTION / TEST OPERATION button once to put

the unit in inspection mode and make sure the malfunction code is “00”. (Normal)

If the code reads anything other than “00”, refer to the Error Code List as shown on page 18.

TEST

TEST

Installation Manual

Page 76: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

73 Inverter Ducted Air Conditioners

EDAU01 - 410

SEPARATING THE INDOOR UNIT FDYQ(N)71FAV1 FDYQ(N)100-125KAV1

ATTENTION: Please separate the indoor unit only when necessary. Please disassemble and reassemble on

a flat surface.

l Separate the indoor unit in the following order.

1) Unscrew the (4) M6 bolts located on the back of the heat exchanger compartment. (Fig. 27)

2) Carefully pull the fan deck compartment away, taking care not to damage the fan motor wiring. (Fig. 27)

Supply Air

Return Air

Heat Exchanger Compartment

Fan DeckCompartment

Electrical BoxAssembly

Fig. 27

Fan deck

Fan earthFan connector

Electricalbox assy

Thermostat

Heat exchangercompartment

3 7

Fig. 28

3) If further disassembly is required, unplug the fan connector and unscrew the fan earth. (Fig. 28)

4) Remove (4) M8 bolts and the (4) screws securing the fan deck to the heat exchanger compartment and

detach the fan deck. (Fig. 28)

l Reassemble the fan deck and heat exchanger compartments in the following order.

5) Carefully place the fan deck back into position.

6) Secure the fan deck onto the heat exchanger compartment with the (4) screws and (4) M8 bolts. (Fig. 28)

7) Re-connect the fan connector into the plug on the heat exchanger compartment. BE SURE TO

RE-ATTACH THE FAN EARTH. (Fig. 28)

8) Carefully replace the fan deck compartment, taking care not to damage the fan motor wiring, and

secure the compartment with the (4) M6 bolts. (Fig. 27)

l Reassemble the fan deck and heat exchanger compartments in the following order:

9) Carefully place the fan deck back in the position.

10) Secure the fan deck onto the heat exchanger compartment with the (5) M8 bolts. (Fig. 24)

11) Carefully replace the fan deck compartment, taking care not to damage the fan motor wiring. (Fig. 23)

12) Secure the fan deck compartment with (3) M6 bolts & (1) M8 bolt. (Fig. 23)

13) Pass the thermister and fan harnesses through the rubber bushes on the electrical box and plug in the

respective sockets (X17A, X18A, X2A and X1A) (Fig. 25)

14) Dress thermister lead and fan motor lead on (2) wire clips provided on base panel.

15) Replace the electrical box and secure onto the fan deck compartment with 6 screws.( Fig. 23)

16) Replace the electrical box cover and secure it with (4) screws. (Fig. 23)

Installation Manual

Page 77: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

74Inverter Ducted Air Conditioners

EDAU01 - 410

Faul

ty c

entra

l

equi

pmen

t in

conn

ectio

n

Dou

ble

assi

gnm

ent

of c

entra

l equ

ipm

ent

addr

ess

Inco

rrect

wiri

ng/p

ipin

g

(wiri

ng/p

ipin

g

conn

ectio

n er

ror)

Cen

tral e

quip

men

t

faul

ty P

CB

Faul

ty

com

mun

icat

ion

to/fr

om c

entra

l

equi

pmen

t

Indo

or/o

utdo

or u

nit

addr

ess

not e

nter

ed

Faul

ty c

entra

l

cont

rol a

ddre

ss

setti

ng

Faul

ty tr

ansm

issi

on

to/fr

om p

erip

hera

l

equi

pmen

t (ai

r

cont

rol e

quip

men

t,

etc)

Faul

ty tr

ansm

issi

on

betw

een

indo

or u

nit

and

cent

ral

cont

rolle

r

Faul

ty tr

ansm

issi

on

betw

een

outd

oor

units

or t

o/fro

m h

eat

stor

age

unit

Faul

ty tr

ansm

issi

on

to/fr

om re

mot

e

cont

rolle

r

Faul

ty tr

ansm

issi

on

to/fr

om o

ther

sys

tem

Faul

ty fi

eld

setti

ng

Faul

ty c

apac

ity

setti

ng

Shor

t of g

asR

ever

sed

phas

e

conn

ectio

n

Faul

ty p

ower

sup

ply

volta

ge s

yste

m

Faul

ty tr

ansm

issi

on

(gen

eral

)

Failu

re o

f

trans

mis

sion

betw

een

indo

or a

nd

outd

oor u

nits

Faul

ty tr

ansm

issi

on

betw

een

indo

or u

nit

and

rem

ote

cont

rolle

r

Faul

ty tr

ansm

issi

on

betw

een

indo

or

units

(mai

n &

sub)

Gas

sho

rtage

(ice

ther

mal

sto

rage

equi

pmen

t)

Mis

sing

pha

se,

imba

lanc

e in

pow

er

supp

ly

Faul

ty te

mp.

rise

sens

or in

side

cont

rol b

ox

Faul

ty ra

diat

ion

fin

(pow

er tr

ansi

stor

)

tem

p. ri

se s

enso

r

syst

em

Faul

ty D

C c

urre

nt

sens

or s

yste

m

Faul

ty A

C o

r DC

outp

ut c

urre

nt

sens

or s

yste

m

Air c

ondi

tione

r

(mul

ti) g

ener

al in

put

over

-cur

rent

Faul

ty tr

ansm

issi

on

betw

een

INV

and

outd

oor u

nits

Air c

ondi

tione

r

(mul

ti) g

ener

al in

put

over

-cur

rent

Elec

troni

c

ther

mos

tat (

time

lag)

Stal

l pre

vent

ion

(tim

e la

g)

Faul

ty p

ower

trans

isto

r

Faul

ty o

il pr

essu

re

sens

or s

yste

m

Faul

ty s

urfa

ce o

il

leve

l sen

sor s

yste

m

Faul

ty IN

V sy

stem

Abno

rmal

tem

p. ri

se

insi

de c

ontro

l box

Abno

rmal

tem

p. ri

se

of ra

diat

ion

fin

(pow

er tr

ansi

stor

)

DC

out

put o

ver-

curre

nt

(inst

anta

neou

s)

AC o

utpu

t ove

r-

curre

nt

(inst

anta

neou

s)

Faul

ty g

as p

ipe

tem

p. s

enso

r

syst

em

Faul

ty d

isch

arge

pres

sure

sen

sor

syst

em

Faul

ty o

il te

mp.

sens

or s

yste

m

Faul

ty s

uctio

n

pres

sure

sen

sor

syst

em

Abno

rmal

sur

face

oil

leve

l

Faul

ty re

frige

rant

tem

p. s

enso

r

syst

em

Faul

ty p

ress

ure

sens

or s

yste

m

(gen

eral

)

Faul

ty c

urre

nt

sens

or s

yste

m

Faul

ty d

isch

arge

pipe

tem

p. s

enso

r

syst

em

Faul

ty lo

w p

ress

ure

equi

vale

nt

satu

ratio

n te

mp.

sens

or s

yste

m

Faul

ty s

uctio

n pi

pe

tem

p. s

enso

r

syst

em

Faul

ty h

eat

exch

ange

r (1)

tem

p.

sens

or s

yste

m

Faul

ty h

eat

exch

ange

r (2)

tem

p.

sens

or s

yste

m

Faul

ty li

quid

pip

e

tem

p. s

enso

r

syst

em

Abno

rmal

hig

h oi

l

tem

p.

Abno

rmal

suc

tion

pres

sure

Abno

rmal

oil

pres

sure

Abno

rmal

disc

harg

e

pres

sure

Faul

ty d

rain

wat

er

leve

l sen

sor s

yste

m

Hea

t sto

rage

uni

t

alar

m

Activ

atio

n of

com

mon

saf

ety

devic

e fo

r sys

tem

No.

1 &

No.

2

Activ

atio

n of

saf

ety

devic

e fo

r sys

tem

No.

1

Activ

atio

n of

saf

ety

devic

e fo

r sys

tem

No.

2

Faul

ty d

isch

arge

pipe

tem

p.

Abno

rmal

hea

t

exch

ange

r (1)

tem

p.

Faul

ty o

utdo

or a

ir

tem

p. s

enso

r

syst

em

Faul

ty d

isch

arge

air

tem

p. s

enso

r

syst

em

Pum

p ov

er-c

urre

nt

lock

faul

ty s

enso

r

syst

em

Faul

ty h

ot w

ater

sens

or s

yste

m

Faul

ty h

eat s

tora

ge

unit

Faul

ty s

enso

r

syst

em (g

ener

al)

Faul

ty a

ir te

mp.

sens

or s

yste

m

Faul

ty p

ower

sup

ply

sens

or s

yste

m

Faul

ty h

igh

pres

sure

switc

h

Faul

ty lo

w p

ress

ure

switc

h

Com

pres

sor m

otor

faul

ty o

verlo

ad

sens

or s

yste

m

Com

pres

sor m

otor

over

-cur

rent

lock

faul

ty s

enso

r sys

tem

Fan

mot

or o

verlo

ad

over

-cur

rent

, fau

lty

lock

sen

sor s

yste

m

Faul

ty A

C in

put

pow

er s

enso

r

syst

em

Pum

p ov

er-c

urre

nt

lock

Abno

rmal

wat

er

tem

p.

Activ

atio

n of

fiel

d

adde

d sa

fety

dev

ice

Faul

ty d

rain

wat

er

leve

l sys

tem

Fan

mot

or o

verlo

ad

over

-cur

rent

lock

AC in

put o

ver-

curre

nt

Faul

ty e

lect

roni

c

expa

nsio

n va

lve

Faul

ty te

mp.

sen

sor

syst

em (r

emot

e

cont

rolle

r, et

c.)

Faul

ty ra

ditio

n

sens

or s

yste

m

Faul

ty h

igh

pres

sure

switc

h

Activ

atio

n of

saf

ety

devic

e (g

ener

al)

Faul

ty P

CB

Hig

h pr

essu

re

(HPS

)

Com

pres

sor m

otor

over

load

Com

pres

sor m

otor

over

-cur

rent

lock

Low

pre

ssur

e (L

PS)

Faul

ty a

ir su

ctio

n

tem

p. s

enso

r

syst

em

Faul

ty d

isch

arge

air

tem

p. s

enso

r

syst

em

Faul

ty d

irt s

enso

rFa

ulty

hum

idity

sens

or s

yste

m

Faul

ty h

eat

exch

ange

r (2)

tem

p.

sens

or s

yste

m

Fan

mot

or o

verlo

ad

over

-cur

rent

, fau

lty

lock

sen

sor s

yste

m

Air d

irect

ion

mot

or

lock

, fau

lty s

enso

r

syst

em

Faul

ty A

C in

put

curre

nt s

enso

r

Failu

re o

f

trans

mis

sion

betw

een

indo

or u

nit

PC b

oard

and

fan

PC b

oard

Faul

ty d

rain

wat

er

leve

l sen

sor s

yste

m

Faul

ty h

eat

exch

ange

r (1)

tem

p.

sens

or s

yste

m

INDOOR OUTDOOR SYSTEM

Faul

ty s

enso

r

syst

em (g

ener

al)

U MF J L PA C E H

No

load

up

Faul

ty c

apac

ity

setti

ng

Insu

ffici

ent w

ater

supp

ly

Faul

ty h

umid

ifier

AC in

put o

ver-

curre

nt

Faul

ty e

lect

roni

c

expa

nsio

n va

lve

Hea

ter o

verh

eatin

gFa

ulty

or d

irty

air

clean

er

Abno

rmal

hea

t

exch

ange

r (1)

tem

p.

Abno

rmal

hea

t

exch

ange

r (2)

tem

p.

Fan

mot

or o

verlo

ad

over

-cur

rent

lock

Air d

irect

ion

adju

st

mot

or lo

ck

Activ

atio

n of

saf

ety

devic

e (g

ener

al)

Faul

ty P

CB

Fan

inte

rlock

(man

ual)

Abno

rmal

dra

in

wat

er le

vel

CJ

EF

89

AH

45

67

01

23

Con

tent

s C

ode

Sect

ion

Cod

e

ER

RO

R C

OD

E L

IST

Installation Manual

Page 78: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

75 Inverter Ducted Air Conditioners

EDAU01 - 410

16. Installation Manual FDYQ180MV1

FDYQ200PV1

FDYQ250MV19

Installation Manual

Page 79: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

76Inverter Ducted Air Conditioners

EDAU01 - 410

INSTALLATION MANUAL

SINGLE SPLIT & VRV SYSTEM

OPERATION MANUAL

Name M6 ScrewHangingBracket

InstallationManual

OperationManual

FDYQ(N) Series

FXDYQ Series

16

16

4

4

1

1

1

-

Installation Manual

Page 80: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

77 Inverter Ducted Air Conditioners

EDAU01 - 410

Liquid pipe

Gas pipe

Drain pipeElectrical boxcover

(1) Select an installation site where the following conditions

are fulfiled and that meets your customer’s approval.

l Where the indoor unit and remote controller are not

exposed to rain or moisture.

l Where the casing of the unit does not contact parts of the ceiling.

l Where optimum air distribution can be ensured.

l Where nothing blocks the air passage.

l Where condensate can be properly drained.

l Where the structure is strong enough to safely

bear the indoor unit weight.

l Where sufficient clearance for maintenance and service can be provided. (see Fig. 1)

l Where there is no risk of flammable gas leakage.

l Where piping between indoor and outdoor units is

possible within the allowable limit. (Refer to the

installation manual for the outdoor unit).

CAUTION

l Keep the indoor unit, outdoor unit, power supply wiring and

transmission wiring at least 1 metre away from televisions

and radios. This is to prevent image interference and noise

in those electrical appliances.

(Noise may be generated depending on the conditions

under which the electric wave is generated, even if 1 metre

is kept.)

(2) When using suspension bolts for installation, the hanging

brackets must be installed. Confirm that the ceiling is strong

enough to support the weight of the indoor unit.

(3) If the installation requires the indoor unit to be exposed

please ensure the unit is more than 1.8m above the floor so

that children can not touch the unit.

(4) A suitable air filter (field supplied) must be installed within the

return air duct.

SELECTING INSTALLATION SITE

*Service Space300mm or more

*Service Space450mm or more

Ceiling

H

Notes:

H = Approx 100mm for drain trap plus additional allowance

for drainage fall. (see section on DRAIN PIPING WORK)

* Service space is the minimum recommended distance. In

some “restricted space” installations it may be necessary to

reduce this distance. Please note that this may necessitate

additional service work should maintenance or repair be

required.

Fig. 1

Fig. 2

401 35080

WA

46

78

Electrical box

Refrigerantpipes and drainconnection

Air-owdirection

Inspection hatch(45 0 x 450 min)

880

910

Fig. 3

Table 1

PREPARATIONS BEFORE INSTALLATIONTo facilitate installation, the indoor unit can be easily separated

into smaller parts to make it easier to move to the final position.

See page 15 for details.

(1) Refer to Table 1 and Fig 3 for suspension bolt positionand horizontal (top view) representation of the indoorunit.

(2) The external static pressure setting for the indoor

unit is factory set to “standard” external static

pressure.For installations with a duct system that

presents a high external static pressure, set the static

pressure value to the “high” position. Refer to page 12

in this manual and the fan performance curves in the

Engineering Data.

NOTE Additional thermal insulation material (thickness 10mm or more of glass wool or polyethylene foam) may be

required if the conditions in the ceiling exceeds 30oC and RH 80% or outside air is introduced into the ceiling or the

unit operates for 24 hours. It is also important that a safety drain tray be used. (see Fig.12)

Model A B W

F(X)DYQ180MFXDYQ200M

F(X)DYQ250M

FDYQN250K

1037mm 1046mm 1210mm

1238mm 1247mm 1410mm

FDYQ200P

FDYQN200P

B

Installation Manual

Page 81: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

78Inverter Ducted Air Conditioners

EDAU01 - 410

(X) N A

A

Installation Manual

Page 82: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

79 Inverter Ducted Air Conditioners

EDAU01 - 410

Indoor unitCut

before

heating

Plug

Cut

before

heating

Cut

before

heating

Cut

before

heating

Wet cloth

Indoor unit

Insertion length

Liquid = 8 mm

Gas = 12 mm

Brazing

To outdoor unit

90o

Wet cloth

Indoor unit

Fitting insulation

(field supplied)

Indoor unit

Tape

(field supplied)

or clamp

Fig. 7a

Fig. 8a

Fig. 9

Fig. 10

CAUTION

Be sure to insulate local piping all the

way into the pipe connections inside

the machine. Exposed piping may

cause condensation or burns on

contact.

Model Liquid Pipe Gas Pipe

F(X)DYQ180MF(X)DYQ200M

9.5mm dia 19.1mm diaFDYQ200PFDYQN200P

F(X)DYQ250MFDYQN250K

9.5mm dia 22.2mm dia

Table 2

Indoor unit

Plug

Cut bytube cutter

Wet cloth

25mm

Approx.

Indoor unit

19.1 mm

Brazing

joint A

To outdoor unit

Pre brazed

joint B

22.2 mm

Wet cloth

Fig. 7

Fig. 8

Insertion

length

12mm

WARNING

• Cut off the ends of the plugs before heating in order

to release pressure, otherwise the plugs may

burst. (Fig. 7)

• Ensure a wet cloth is wrapped around the copper pipe

before applying a flame to prevent burning of felt

insulation. (Fig. 7 and 8)

• Take extreme care not to burn the air conditioner body

when brazing.

Applies to FDYQ200P & FDYQN200P models only:

• Cut off the end of both plugs before heating the liquid pipe

to remove the liquid pipe plug.

• Using tube cutters (1/8 - 1 1/8) cut the 22.2mm gas pipe plug

approximately 25mm or more from the expanded section of

the pipe. (Fig. 7)

• Remove the burr from the inlet of the gas pipe. ENSURE all

copper shavings are removed

• Insert 19.1mm field supplied gas pipe into the 22.2mm

pipe previously cut. Insertion length must be at least 12mm.

(Fig. 8)

• Braze joint A as shown in Fig. 8. To ensure joint (B) has not

been disturbed by the heating of joint (A) reheat joint (B)

and apply solder if necessary.

• Braze the liquid line joint.

Applies to all models except FDYQ200P & FDYQN200P

• Cut the end of the plugs before heating the pipes to

remove the plugs. (Fig. 7a)

• Braze the pipes as shown in Fig. 8a.

Applies to all models.

• Ensure the pipe insulation is sealing against the body.

(Fig. 9)

• Install the clamps (field supplied) as close to the body as

possible to absorb leaking condensation. (Fig. 10)

• Prevent any mixture of air into the refrigerant.

• Ensure sufficient ventilation if the refrigerant leaks during

installation work.

• Make sure to completely insulate the connecting pipe

work and connections using field supplied insulation after

checking for gas leakage.

• When in heating mode, the temperature of gas piping

may reach 120°C. Ensure that the insulation will safely

withstand 120°C.

Caution to be taken when brazing refrigerant piping

Do not use flux when brazing refrigerant piping. Use the

phosphor copper brazing filler metal (BCuP) which does

not require flux. (Flux has an extremely harmful influence

on refrigerant piping systems. For instance, if chlorine

based flux is used, it will cause pipe corrosion, particularly

if the flux contains fluorine, it will damage the refrigerant

oil.)

During any brazing of the refrigerant piping, you must

continually blow dry nitrogen gas through the piping to

expel air from the piping. (see Fig. 11) If you braze the

piping without doing so, a large amount of oxide film

develops inside the piping which can cause system failure.

Ensure that you use a pressure reducing valve on the dry

nitrogen bottle to prevent pinholes caused by excessively

high pressure. (Set the pressure of nitrogen gas to about

0.2 kg / cm2 [19.6 kPa])

Installation Manual

Page 83: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

80Inverter Ducted Air Conditioners

EDAU01 - 410

DRAIN PIPING WORK

WARNING

The drain pipe must be installed as shown in the diagram below to avoid water damage caused by

leaks and condensation.

• Assemble the unit as shown in Fig. 12.

• For best results, try to keep the piping as short as possible. Slant the piping at an angle to improve flow (the

drain pipe provided with the indoor unit has a PT 3/4 internal thread). Fig. 12.

• Securely insulate the drain pipe.

• It is necessary to provide a drain trap in the drain outlet to relieve negative pressure that exists within the unit

compared to the outside atmospheric pressure when the unit is operating. If a drain trap is not provided,

condensation carry over or an odour may occur.

• Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris.

• Pour water in the drain pan to test the drainage.

• Always use an extra safety drain pan (field supplied) to cover the entire area of the indoor unit.

• Insulate drain pipe using piping thermal insulation to prevent condensate dripping during humid conditions.

CAUTION

Drain piping connections. Do not connect the drain piping directly to sewage pipes. Drainage must conform to

local plumbing regulations.The vapour in the sewage might enter the indoor unit through the drain pipes and

corrode the heat exchanger or escape into the room.

Bottom of the unit

Slo

pe

Extra drain tray(field supplied)

PT 3/4 internal thread

Drain trap

50

mm

or

mo

re5

0m

m o

r m

ore

Do not leave in water

Insulate securely(field supplied)

Gradient of at least 1:100

Fig. 12

After the piping work is finished, check that the drainage flows smoothly by pouring approximately 1000 cc of

water gradually into the drain tray and check drainage flow. (Fig.13)

Drain outletWatering can

Refrigerant pipes

Drain trayFig. 13

WHEN THE INSTALLATION IS COMPLETE

Check drainage flow during COOLING OPERATION, explained under the section entitled TEST OPERATION.

Nitrogen

Refrigerant piping

Tape the pipe

Valve

Nitrogen

Reducing valve

Fig. 11

Installation Manual

Page 84: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

81 Inverter Ducted Air Conditioners

EDAU01 - 410Installation Manual

Page 85: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

82Inverter Ducted Air Conditioners

EDAU01 - 410

External Switching Device eg. fire trip or timer

(min. contact requirement) 15V DC 10mA

F1 F2 T1 T2P1 P2

Fig. 17

Forced OFF or ON-OFF control by external control

If required, external control (eg. fire trip, external timer, etc) can be applied by connecting the switching device to

terminals (T1 & T2) as shown in Fig 17. The functionality of the control is set and configured under field settings

on page 13.

CAUTION

Precautions for wiring

• When connecting the indoor unit, give consideration to the other electrical equipment connected to the main

breaker and select the phase (L1, L2, L3) so that current (or voltage) unbalance does not occur. If current

unbalance occurs, the phase current of the compressor may become unbalanced and there is a risk of

protective device actuating or compressor breakdown.

• Do not clamp the remote controller cord or F1/F2 cord together with electrical wires. Doing so may cause a

malfunction.

• Remote controller cords and wires connecting the units should be located at least 50 mm from other electric

wires. Not following this guideline may result in malfunction due to electrical noise.

• Use a round crimp-style terminal for connection to the power supply terminal board. (Fig. 15) Where this is not

possible due to unavoidable reasons, be sure to observe the following instructions.

Do not connect wires of different gauge to the same power supply terminal. (Fig. 16). Looseness in the

connection will cause overheating.

When connecting wires of the same gauge, connect them according to the figure below.

• Make certain that prescribed wires are used, carry out complete connections, and secure the wires so that

outside forces are not transmitted to the terminals.

• Shielded wire is recommended for transmission wiring to comply with EMI (AS/NZSCISPR14.1)

• Use double insulation wire for the remote controller and ON-OFF Input T1, T2 (Sheath thickness is 1mm or

more) or run wires through a wall or conduit so that the user cannot come in contact with them.

• Run transmission wiring separate from power supply wiring. Ensure transmission and power supply wiring is

protected by conduit against external forces.

• After connecting the wires, be sure that no pressure is applied to the wire connections by using cable ties and

securing them to the anchor points. Also, when wiring, make sure the lid of the terminal box fits snugly by

arranging the wires neatly and attaching the terminal box lid firmly. When attaching the terminal box lid, make

sure no wires get caught under the edges.

• Make sure the remote control cord or the wiring between the units (ie F1/F2) do not pass through the same

locations outside the unit as any other electrical wiring. Separate them by at least 50 mm, otherwise electrical

noise could cause a malfunction or damage to the unit. 50mm is considered the minimum for domestic

applications where there is relatively low current flowing in other electrical wiring. In applications where high

current or voltage is present in nearby electrical wiring additional separation will be required.

Round crimp-style

terminal

Electric wire

Connect wires of

the same gauge to

both sides

Do not connect

wires of the same

gauge to one side

Do not connect

wires of different

gauges

Fig. 15

Fig. 16

Power Supply Wire type (F1,F2)

(wiring between units)

Remote controller (P1,P2) & On/Off Input (T1,T2) T1,T2

Contact Spec.Field fuse Wire type Size Wire type Size Length

Circuit protection and wire size

must comply with local codes (ie

AS/NZS3000)

Sheathed wire

(2 wires) See

precautions

below0.75-1.25mm2

(P1,P2)

Max 500m

(T1,T2)

Max 100m

Min 15V DC

10 mAOutdoor - Indoor Max

wiring length 1000m

Table 3

Installation Manual

Page 86: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

83 Inverter Ducted Air Conditioners

EDAU01 - 410

L1 L2 L3 N

F1 F2

F1 F2

T1 T2P1 P2

P1 P2

Main Power Supply

OutdoorUnit

IndoorUnit

L N

Main Power Supply

RemoteControls

Fuses or breaker

Isolation Switch

P1 P2

S MS M

Note 2.

L1 L2 L3 N

F1 F2

F1 F2

T1 T2P1 P2

P1 P2

Main Power Supply

OutdoorUnit

IndoorUnit

L N

Main Power Supply

RemoteContro l

Fuses or breaker

Isolation Switch

S M

L1 L2 L3 N

F1 F2

F1 F2

T1 T2P1 P2

Main Power Supply

OutdoorUnit

IndoorUnit

L N

Main Power Supply

Fuses or breaker

Isolation Switch

L1 L2 L3 N

F1 F2

F1 F2

T1 T2P1 P2

Main Power Supply

OutdoorUnit

IndoorUnit

L N

Main Power Supply

Fuses or breaker

Isolation Switch

P1 P2

IndoorUnit

P1 P2 RemoteContro l

S M

Note 2. Note 2. Note 2.

L1 L2 L3 N

F1 F2

F1 F2

T1 T2P1 P2

P1 P2

Main Power Supply

OutdoorUnit

IndoorUnit

L N

Main Power Supply

RemoteContro l

Fuses or breaker

Isolation Switch

S M

Note 2.

Fig. 19Fig. 18

Group Control

Fig. 20

Fig. 21(Note 4)

1. All transmission wiring except for the remote controller wires must match the terminal symbol.

2. If using shielded wire for transmission wiring, ground the shield of the shield wire to , at the

grounding screw of the remote controller cord grounding terminal inside the control box.

3. For group control remote controller, choose the remote controller that suits the indoor unit which has the

most functions (as indicated by the swing flap).

4. When two remote controllers are used in "Group Control", connect the remote controller to the indoor unit

which is at the end of the loop. (Fig. 21). Do not connect three or more wires to the P1, P2 remote control

Notes:

Single pair type Control by 2 remote controllers

terminals.

Installation Manual

Page 87: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

84Inverter Ducted Air Conditioners

EDAU01 - 410

FIELD SETTING

GREY BROWN GREY BROWN

Standard Static(factory default)

High Static(reposition orange wire)

ORANGE ORANGE

X3M X3M

Fig. 22

Field settings must be made from the remote controller in accordance with the installation requirements

(external static pressure can not be set by field setting in these models).

Setting External Static Pressure

For “HIGH” ESP Setting, move the Orange Jumper Lead on terminal block XM3 (inside electrical box) from the

left hand side terminal (grey) to the right hand side terminal (brown) as shown below in Fig 22.

OTHER FIELD SETTINGS (WHEN INSTALLING BRC1D619)

When installing other optional controllers please refer to the accompanying installation manual for field

setting information.

Field setting must be made from the remote controller in accordance with the installation condition.

l Setting can be made by changing the "Mode number", "FIRST CODE No.", and "SECOND CODE No.".

l Mode No. without ( ) means the setting will apply to all units connected to the controller. (Group control)

l Mode No. with ( ) means the settings will apply to individual units. It can also be used to check current field settings.

SECONDCODE NO.

UNIT NO.

FIRSTCODE NO.

MODE NO.

FIELDSETMODE

TEST1 245

6

SETTING

UNIT NO.

3

Fig. 20

Note:

Remote control displayed

is indicative only.

Depending on the remote

control supplied, the

button layout maybe

different.

1) Press & hold the test button until 00, 01 or 10 appears.

2) By pressing the temperature up arrow button scroll until the required mode setting number appears.

3) By pressing the timer up arrow button scroll until the required first code setting number appears.

4) By pressing the timer down arrow button scroll until the required second code setting number appears.

5) Press the confirmation button once.

6) Press the test button once & 88 will appear for a few seconds before returning to the normal operation.

How to set field setting modes

Installation Manual

Page 88: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

85 Inverter Ducted Air Conditioners

EDAU01 - 410

S

M

S

S

M

Remote controller

PC board

(Factory setting)

(Only one remote controller needs to be changed)

Fig. 24

Upper part of

remote controller

Lower part of

remote controllerInsert the screwdriver here and

gently work off the upper part of

remote controller.

Settings Mode No. FIRST CODE No. SECOND CODE No.

Forced OFF 01 (FACTORY SET)

ON - OFF Input

12 (22) 1

(Bridge T1, T2)To Force OFF

(Bridge T1, T2 to switch ON)(Open T1, T2 to switch OFF)

Using 2 remote controllers

When using 2 remote controllers, one must be set to "MAIN" and the other to "SUB".

(1) Insert a flat screwdriver into the recess between the upper and lower part of remote controller and working fromthe 2 positions, pry off the upper part. (Fig. 23) (The remote controller PC board is attached to the upper part of remote controller.)

Fig. 23

Table 4

Setting T1 T2 Input

Settings

Alternate between both sensors

Indoor unit sensor only

Remote controller sensor only

Second Code No.

01

02

03

Mode No. First Code No.

10(20) 2

Settings

LL

Set speed

OFF

Second Code No.

01

02

03

Mode No. First Code No.

12(22) 3

(FACTORY SET)

(FACTORY SET)

(FOR HEATING MODE)

Setting air filter sign

Setting

Filter sign indication [ON]

Filter sign indication [OFF]

Second Code No.

01

02

Mode No. First Code No.

10 (20) 3(FACTORY SET)

Indoor fan settings during thermo off

Setting temperature sensor location

l Filter maintenance should be carried out which is appropriate to the type of filter in use.

(2) Turn the main/sub changeover switch on one of the two remote controller PC boards to "S". (Leave the switch

of the other remote controller set to "M".) (Fig. 24)

Table 5

Table 6

Table 7

02

Installation Manual

Page 89: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

86Inverter Ducted Air Conditioners

EDAU01 - 410

Refer to the section of "FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION

AND CHECK AFTER INSTALLATION IS FINISHED" (pg 2).

After installation is complete (ie refrigerant piping, drain piping, electrical wiring, duct work, filter installation and

field settings) conduct a check test as described below to confirm correct operation and installation of the complete

system.

(1) Replace all electrical covers.

(2) Energise the crank case heater for at least 6 hours before commencing next step.

(3) Refer to the installation manual of the unit for additional field settings.

(4) Set to cooling operation with the remote controller and start operation by pushing ON/OFF button.

(5) (When using BRC1D619 controller) Press Inspection/Test Operation button 4 times and operate at Test Operation

for 3 minutes.

(6) Press Inspection/Test Operation button and operate normally.

(7) Confirm function of unit according to the operation manual.

PRECAUTIONS

TEST

TEST OPERATION

Code RemarksMalfunction

A1

A6

A3

AJ

Indoor unit's PCBfaulty

Drain water level abnormalor jumper on PCB missing

Indoor fan motoroverloaded, over-current orlocked

(not applicable)

Type set improper

Capacity data is wronglypreset. Or there isnothing programmed inthe data hold 1C.

H3High pressure switch faulty(outdoor unit)

C5

C9

E0

E1

E3

E4

E5

E6

E9

F3

Sensor for heat exchangertemperature is faulty

Sensor for suction airtemperature is faulty

Action of safety device(outdoor unit)

High pressure abnormal(outdoor unit)

Outdoor unit's PCB faulty

Low pressure abnormal(outdoor unit)

OL activation

Compressor startup error

Electronic expansion valvefaulty (outdoor unit)

Discharge pipe temperatureabnormal (outdoor unit)

Code RemarksMalfunction

PJ

U1

U4

UA

UC

UF

H4

H9

J3

Low pressure switch faulty(outdoor unit)

Outdoor air thermistorfaulty (outdoor unit)

Discharge pipe thermistorfaulty (outdoor unit)

Type set improper(outdoor unit)

Capacity data is wronglypreset. Or there isnothing programmed inthe data hold 1C.

Reverse phase or Openphase

Transmission error(indoor unit - outdoor unit)

Miss setting for multisystem

Wrong wiring betweenindoor and outdoor units

Central control addressoverlapping

J6Heat exchanger thermistorfaulty (outdoor unit)

Transmission is improperbetween the indoor andoutdoor units.

U5

Transmission error(indoor unit - remotecontroller)

Transmission is improperbetween the indoor unit andremote controller.

Setting is wrong for selectorswitch of multi-system

Check the wiring betweenindoor and outdoor units

C4Sensor for heat exchangertemperature is faulty

Liquid line (sensor R2T)

Gas line (sensor R3T)

1. In case something is wrong with the unit and an error code appears on the remote control,

refer to the malfunction diagnosis table below.

2. After completing the test run, press the INSPECTION / TEST OPERATION button once to put

the unit in inspection mode, and make sure the malfunction code is "00", (normal). If the code

reads anything other than "00", refer to the malfunction diagnosis table below.

TEST

Installation Manual

Page 90: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

87 Inverter Ducted Air Conditioners

EDAU01 - 410

Fan deck

section

Heat exchanger

section

Heat exchanger

top cover

Side lock strap

Electrical box cover

x18A, x19A

Fan deck

section

Heat exchanger

section

To facilitate installation, the indoor unit can be easily separated into 2 sections making it lighter to carry and easier to

maneuver through openings and in the ceiling.

ATTENTION: Separate the indoor unit only when necessary. Disassemble and reassemble on a flat surface.

Separate the indoor unit in the following order.

1. Remove the two side lock straps. (Fig. 26)

2. Unscrew the top cover of the heat exchanger section. (Fig. 26)

3. Unscrew the three M8 bolts securing the two sections. (Fig. 27)

Fig. 27

Fig. 28

4. a) Unplug the expansion valve motor in-line connector located internally on the heat exchanger side plate (Fig

26). Release the harness retaining clip securing the expansion valve motor connecting cable. Place the now

loose expansion valve motor cable in the fan deck section of the unit.

b) Remove the electrical box cover and unplug the air and two heat exchanger thermistors (Plugs X11A, X12A

and X13A) (Fig. 28)

c) Carefully un-clip the three thermistor leads and push the leads through the back of the electrical box.

d) un-clip the thermistor leads from inside the fan deck section.

5. Carefully unlatch the heat exchanger section from the fan deck section (Fig. 29) by lifting up the heat exchanger

section and then pulling away. Ensure that the thermistor or expansion valve motor cables do not catch on either

section as the unit is separated.

Rejoin the Heat Exchanger and Fan Deck sections in the following order.

6. Carefully align the heat exchanger section and fan deck section.

7. Lift the heat exchanger section about 50mm, push it forward and then back down so that the bottom edge latches

over the bottom lip of the fan deck section. (Fig. 29)

8. Secure the two sections together with the 3 bolts (M8). (Fig. 27) Re-attach the side lock strap. (Fig. 26)

9. Re-connect the air and heat exchanger thermistors (Fig. 28). Reconnect the expansion valve motor in-line

connector (Fig. 26) Reclip all leads inside the electrical box as well as inside the fan deck and heat exchanger

sections. Replace the electrical box cover.

10.Carefully replace the heat exchanger section top cover and secure the cover with the screws. (Fig. 26)

Fan deck

section

Heat exchanger

section

M8 Bolts

Fig. 29

Fan deck

section

Heat exchanger

section

SEPARATING THE INDOOR UNIT (if required)

Fig. 26

X11A, X12A, X13A

Expansion valve

motor connector

Installation Manual

Page 91: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A
Page 92: Engineering Data - SAC Contractor management...1 Inverter Ducted Air Conditioners EDAU01 - 410 Indoor Unit Remote Controller Outdoor Unit FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1 RZQ100KV4A

DAIKIN AUSTRALIA PTY. LIMITED

77-83 Alfred Road, Chipping Norton, NSW 2170 Australia

Phone: 1300 78 72 66

www.daikin.com.au

DAIKIN INDUSTRIES LTD.

Head office:

Umeda Centre Building, 4-12 Nakazaki-Nishi 2 chome,

Kita-ku, Osaka, 530-8323 Japan

Tokyo office:

Shinjuku Sumitomo Building, 6-1 Nishi-Shinjuku

2 chome, Shinjuku, Tokyo, 163-0290 Japan

EDAU01 - 410