Engineering Control Drawing

Embed Size (px)

Citation preview

  • 8/18/2019 Engineering Control Drawing

    1/18

     

    Engineering Control Drawing

    Qazi Arsalan Hamid

    Testing and Commissioning Engineer

  • 8/18/2019 Engineering Control Drawing

    2/18

     

    Thanks to my Mother and Father who always

    encourage me to learn new things and spread it

    without expecting reward

    Also thanks My Friends Mr. Khalid Anwar and Mr.

    Rizwan Syed ,they helped me understanding

    Different Concepts regarding Engineering.

  • 8/18/2019 Engineering Control Drawing

    3/18

    Engineering Drawing

    Drawing is like X Ray for engineers of power grid. Engineer can examine the three different aspect or

    classes of grid equipments , whenever we are working in power grid or any master substation we need

    to concentrate on

      Equipment which need to be protected

      Equipment which need to be sensed abnormal/normal Condition

      Equipment need to be take action in case of normal/abnormal condition

    basically in every substation there are

      Sensing panel(Relays)

      Control Panels

      Action Panels(Circuit breakers,contactors etc)

     

    Auxiliary Circuits (latching relays, timing relays, Sockets etc)

    these all are interconnected , and modern relays make it easy for Grid peoples as it provide multi

    function in one package.

    interconnection of relays and panels is done by about 6sqmm low voltage insulated wires as modern

    relays are low voltage operated with very low burden.

    i am taking one example for capacitor panel protection engineering drawing , and we will try to

    understand it what that drawing informing us.

    in all drawings , they 1st give you contents of drawing then legends , but remember some legends must

    be on engineer finger tips , K sysmbol is universally accepted for auxiliary relays, remember auxiliary

    relays are relays used for circuit isolation, multiple contacts and indication purposes . Q symbol is forBreaker , Relays will be shown by there ANSII numbers like

      51 for OC

      51N for Earth Fault overcurrent Relay

      64G for ground Detector relay

      74 for trip circuit supervision relay

  • 8/18/2019 Engineering Control Drawing

    4/18

      86 for master trip or lock out relay

      96 for DC supply supervision

      87 for differential relay

      21 for Distance Relay

      27 for undervoltage relay

     

    59 for overcoltage relay

      81 for frequency relay

      Breaker failure relay is intertripping relay , but it will show by associated breaker

    but nowadays in some drawing you see relay make and number in place of ansi code, like RET670,

    7SJ512 ,P121 etc

    Most of the drawings are showing relays in inactive forms , but remember when relay shown in drawing

    is active it must be mention in drawings.

    in drawing, first page is dedicated to front view of panel where relays, indication LEDs, and control

    equipmentof relays and panels are shown

    then main circuit protection layout is given , in which source of power, conductor , load with protection

    devices are shown. but for direct purposes the protection detailed lay outs are mention in many drawing

    , if you are designated for particular section drawing you need to concentrate on that section only no

    need to tele complete grid drawing, but it is necessary to give keen and thoroughly look on assigned

    section drawings.

  • 8/18/2019 Engineering Control Drawing

    5/18

     

    here you can see the protection circuit, which is linked with 13.8KV busbar, here one Potential

    Transformer is connected line to ground for protection purposes. whenever PT is connected line to line

    then line to line voltage would be the PT output voltage, but when VT connected between line to ground

    the out put voltage would be nominated voltage/sqrt(3)

    here nominal voltage is 120V , so pt output would be 120/sqrt(3)=69.282V

    here line need to be protected is 13.8Kv so voltage ratio would be like

    13.8KV/sqrt(3):120V/sqrt(3):120v/sqrt(3)

    here i mention two output because my VT is multicore , each core with dual class of metering and

    protection , this is advancement in technology .

    VT metering classes are 0.1,0.2,0.5,1 and 3 and protection classes are 3p and 6p , here i adopted 0.2 for

    metering and 3p for protection purpose. burdens are 25VA in both cases of metering and protection.

    We protected Out pt by fuses (HRC) from Primary side and Miniature circuit Breakers(MCBs) from

    secondary side as per recommended practices.

    we have multifunction relays SEL-487V and C-70 here for under/over Voltage (27/59),

    instantaneous/Inverse Over Current relay(50/51), instantaneous/Inverse Over Current earth fault

    relay(50/51N), non directional Overcurrent relay(59ND),Directional Overcurrent Relay(67), Inter tripping

    or circuit breaker failure relay(CBF), Trip circuit supervision Relay(TCS) , negative sequence overcurrent

    relay (46). in C-70 you have thermal overload protection function also 49.

  • 8/18/2019 Engineering Control Drawing

    6/18

    now see there are five test sockets , all sockets are used for capacitor bank protection check . these

    sockets must be wired properly , also one thing which must be kept in during testing is that never

    remove test socket cover while system is alive , it is not recommended.

    another micom relay is installed P139, metering arrangement is shown also PM and DPDM.

    TS2 have PT connection and SEL 487 connection

    TS1 have CT connection and SEL 487V connection

    TS3 have metering connection, CT connection amd C-70 Relay connection

    TS4 have PT connection and C-70 relay connection.

    TS6 have P139 relay connection

    Test Socket is used for testing and metering purpose of Protection and metering equipment , always use

    when circuit is dead, live line testing is not recommended. with help of test sockets we can test ourrelays and other equipments with disturbing the equipment wirings.

    here we have one multi core and multi ratio current transformer, the difference in it is simple ,in multi

    core you can utilize all core for the protection,metering and control purpose , unused ct cores must be

    short. in muti ratio CT you can use only one particular or reuired ratio at a time i.e if you have

    800:400/1A , then either you used this CT as 400/1 or 800/1, not both at a time . this multi coring or

    multi ratio thing is done by tappings at CT secondary cores.

    in multi ratio CTs , the secondary sides are already short so no need to short used CT secondary, but in

    multi core CTs unused CTs must be short because in multi core CT each Core represent separate

    unshorted CT.

    now we are moving to next drawing pages.

    i have in my drawings the AC circuit Protection Logic Drawing

  • 8/18/2019 Engineering Control Drawing

    7/18

     

    here you can see our 13.8 Kv circuit breaker is coupled with two breakers and one reactor, reactor is

    current limiting device and harmonic suppressor. neutral balance CT is low rated CT with 10/5A rating,

    the current in neutral while capacitor bank is healthy will be ZERO, but during unbalancing some current

    flow in this CT and relay associated with this CT signalled breaker to get trip. in this case class of CT is 5pwith ALF of 20 , means this CT will have errors less then 5% upto 200A in primary neutral circuit which

    will be accidental but not usual.

    we now moving forward , now we have DC logic Drawing , remember we always kept DC in back up in

    any substation , and also run our most controlling and protection euipment via DC so when in case of

    power failure we can get stored DC supply for protection and control panel.

  • 8/18/2019 Engineering Control Drawing

    8/18

     

    here you can see the SEL 487V relays is supplied from DC supply 1 , BCPU,trip coil 1 via tripping relay 94,BCPU via tripping relay 94,HMI /SAS signalling via tripping relay 94 and DC supply 1 via tripping relay

    94,close block with lock out relay 86, Trip coil -1 with lock out relay 86 ,BCPU with lock out relay 86,

    HMI/SAS signalling with lock out relay 86, DC supply with lock out relay 86,

  • 8/18/2019 Engineering Control Drawing

    9/18

    now in next drawing page we will review the panel illumination and Heater circuit.

    both heater and lightning panel is supplied via 220V ac Supply, we provide thermal MCBs, these MCBs

    will trip when thermal affect increase due to over current, or itself current raise above the current

    setting of MCB.

    in socket circuit we provide 1 fluorescent light with sockets. across contact 1,2 and 3,4 and 13,14

    selector switch is given , when selector switch is at 1,2 your heater is at auto position humidistat(HMT)

    will sense heat insight cubicle and will auto off heater when set limit cross. at 3,4 heater can be

    manually off and on , at 13,14 you can test healthiness of your heater circuit.

  • 8/18/2019 Engineering Control Drawing

    10/18

    in next page we are observing the DC supply Distribution circuit ,

    both main protection circuit Main-1 and Main-2 power will be supplied from 125V dc supply, both

    supply is equipped with MCBs. this shows that our protection panel is DC powered so in case of grid ACsupply failure or fault in Grid the relays will remain effective.

  • 8/18/2019 Engineering Control Drawing

    11/18

    in next drawing , we will review CT circuit

    in this the CT is wired 1st in Test block , then from test block it is wired to the relay , here you can CT is

    Star connected , see contact 3S1 contact of R,Y and B phase CTs are connect with each other to form

    Earth (return path) .

  • 8/18/2019 Engineering Control Drawing

    12/18

     

    then we have metering CTs connection , again via Test block , so you can check any time the Meter

    accuracy and Metering CTs characteristics , remember that safety factor it is the margin by which your

    metering CT is safe , here it is 5 which means up to 5 times of current the metering CT will be safe to

    operate , for knowledge please remember that saturation point of metering is always less than the

    protection CTs.

    below metering CTs, we have Protection CTs for Main-2 protection circuit via Test block. when CT is not

    in used for protection or metering it must be short circuit by wire or metallic jumpers , nowadays many

    test block are equipped with inside short jumpers , means if you remove test block cover the CT side

    should be shorted automatically.

    but here if you want to short your CT following operation required

    Metering CT

    2,5,8 and 10 must be open and 1,4,7,9,and 14 must be closed

    Protection CT

    10,12,14 and 16 will be open 11,13,15 and 18 must be closed. so CT will be short with system earthing.

  • 8/18/2019 Engineering Control Drawing

    13/18

    in next drawing we are observing the Neutral unbalance CT and PT circuit.

    one neutral unbalance CT via Test block is connected to C-70 relay , in C-70 relay there is function

    named as 46UB, which is unbalanced detection relay due to negative sequence current.

    basically these relays equipped with two stage of tripping , 1st one is activate when value increase upto

    110% of nominal voltage , in second stage it will activate when value get exceed from 110 % of nomianl

    value.

    also one PT connection to Main-1 protection is shown here.

  • 8/18/2019 Engineering Control Drawing

    14/18

    in next drawing we have two PT connection drawing for Main-1 and Main-2 Protection circuit.

    these are PTs circuit of 13.8 KV switchgear, both PTs are 3p class protection PTs.

  • 8/18/2019 Engineering Control Drawing

    15/18

    in this we will review Relays connection with Test Blocks

    from this drawing you can easily Test relays by just removing cover of block and injecting current. here

    TS1 test block is from Current Transformer connection and TS2 block for VT connection (phase and

    unbalance compensation VTs)

  • 8/18/2019 Engineering Control Drawing

    16/18

    in next drawing we are going to examine the Main -1 Cap Protection Binary input module

    from left you see different relaying condition , after which 86(lock out relay) and 94(tripping relay of

    breaker) activated. lock out relay will prevent breaker to get on until lock out relay electrically or by

    hand reset .

    tripping relay is auxiliary relay of breaker which mount within circuit breaker assembly.

  • 8/18/2019 Engineering Control Drawing

    17/18

    now let see trip/lock out relay circuit.

    when in case of fault , the tripping relay 94 activated and same time lock out relay 86 operated , and

    break switch 27 will close and Reset Switch (make switch) will be at apart(off) position , the lock out

    relay can be reset electrically or manually , wiring shows that manual connection is bypassing the

    electrical reset circuit. when we reset electrically or manually the 25 make switch will be make but

    sensing from 27 will remain intact , if fault still in circuit the relay will not reset and circuit remain off.

    also not 27 and 25 are coupled ,one will on at a time.

    here we provide DC supply provision relay which detect low voltage or absence of voltage in this control

    circuit. but this DC supply provision only alarm or indicate the low voltage or absence of voltage as there

    is no breaker trip provision is provided in it.

  • 8/18/2019 Engineering Control Drawing

    18/18

    hope that document will provide some help in understanding Electrical control drawings.

    thank you for reading this material.

    in case of any flaw or mistake please inform me so i can correct it.

    Regards,

    Engr. Qazi Arsalan Hamid

    Testing and Commissioning Engineer

    [email protected]