Engineering. Design Issues for Essential Facilities and Shelters. Florida Emergency Operations Centers Design and Evaluation Criteria. Danny Kilcollins, FPEM Planning Manager Division of Emergency Management. Features of a Survivable EOC. - PowerPoint PPT Presentation

Citation preview

Page 1: Engineering

Engineering

Design Issues for Essential Facilities and Shelters

Page 2: Engineering

Florida Emergency Operations Centers Design and Evaluation

Criteria

Danny Kilcollins, FPEM

Planning Manager

Division of Emergency Management

Page 3: Engineering

Features of a

Survivable EOC

Page 4: Engineering

Minimum Hurricane

Safety Criteria for

Critical Facilities

Page 5: Engineering

ARC 4496 Hurricane Hazards

Wind

Storm Surge Flooding

Rainfall Flooding

Hazardous Materials

Page 6: Engineering

High Performance

Design Criteria:

DOE-STD-1020

Page 7: Engineering

DOE-STD-1020 Natural Hazards

Wind

Flooding

Earthquake

Page 8: Engineering

Hurricane Wind Design

Page 9: Engineering

DOE 1020 Wind Design

Page 10: Engineering

Return Period Years

Page 11: Engineering

ASCE 7-02

Page 12: Engineering

Florida Building Code – Basic Wind Speeds and Windborne Debris Impact Regions

Page 13: Engineering

Basic Wind Speed Conversions

Equivalent Basic Wind SpeedsWind Speed Conversion

3-second gust, fastest-mile and 1-min. sustained velocities (mph)

Wind Measurement Scale

Hurricane Category 1

Hurricane Category 2

Hurricane Category 3

Hurricane Category 4

Hurricane Category 5

Extreme Hurricane Category 5

3-second Gust (ASCE 7 and 2004 Florida Building Code)

90 117 135 160 190 230

Fastest Mile (Standard Building Code)

75 100 117 141 170 209

1-minute Sustained (National Hurricane Center)

74 96 111 131 156 188

Page 14: Engineering

1,000-yr Return Period

Page 15: Engineering

1,000-yr Recurrence Wind Speeds for Florida

Page 16: Engineering

Fla. PC 3 Wind Design Criteria

Page 17: Engineering

TORNADO EVENTS IN FLORIDA

54%31%

13%2%

F0F1F2F3+

F0

Page 18: Engineering

10,000-yr Return Period

Page 19: Engineering

10,000-yr Recurrence Wind Speeds for Florida

Page 20: Engineering

Fla. PC 4 Wind Design Criteria

Page 21: Engineering

Probable Minimum Central Pressure Limit Estimate for Hurricanes; Source: K. Emanuel (1996)

Page 22: Engineering

Minimum Central Pressure to Wind Velocity Conversion

Source: Hurricanes and Typhoons: Past, Present and Future; Landsea, etal

880 mb = 190 mph (232 mph, 3-sec gust)

885 mb = 185 mph (226 mph, 3-sec gust)

890 mb = 180 mph (220 mph, 3-sec gust)

900 mb = 170 mph (208 mph, 3-sec gust)

910 mb = 165 mph (202 mph, 3-sec gust)

Page 23: Engineering

Representative Wind Design Criteria

Applies to the EOC and essential ancillary structures and service equipmentWind Load Design per ASCE 7 StandardMinimum Design Wind Speed = 190 mph, 3-second gustWind Importance Factor, I=1.00Exposure Category = C

Directionality Factor, Kd=1.00

Internal Pressure Coefficient, GCpi= +/-0.18

Page 24: Engineering

Representative Wind Design Criteria

The EOC designated as a threshold building, and special structural inspections required

Special inspections conducted in compliance with section 553.79, Florida Statutes and other applicable statutes, laws and rules

Page 25: Engineering

Representative Wind Design Criteria

Design Windborne Debris Missile = 15 lb 2x4 propelled at 50 mph (74 ft/sec)

34 lb-sec of momentum

Design missile applies to all exterior enclosure components, claddings and assemblies (i.e., walls, roofs, louvers, windows, doors, etc.)

Design missile applies to enclosure surfaces located within 60 feet in height above finish grade

Page 26: Engineering

Tornado Wind Design

Page 27: Engineering

FEMA 361 – Tornado Winds

Page 28: Engineering

FEMA 361 Wind Zones

Page 29: Engineering

TORNADO EVENTS IN FLORIDA

54%31%

13%2%

F0F1F2F3+

F0

Page 30: Engineering

Flood & Rainfall Design

Page 31: Engineering

DOE 1020 Flood Criteria

Page 32: Engineering

NOAA HMR No. 51 and

No. 52Probable

Maximum Precipitation

Estimates

Page 33: Engineering

24-hour PMP @ 10 sq.mi. Basin

Page 34: Engineering

72-hour PMP @ 10 sq.mi. Basin

Page 35: Engineering

Estimated 24-hour Rainfall Rates w/Recurrence Intervals

Local Precipitation & Site Drainage Design (24 hr Rainfall, inches) - 12" @ 100-yr

Basin Size, sq.mi. X

0(100-yrs)

1(500-yrs)

2(2,000-yrs)

3(10,000-yrs)

4(100K-yrs) PMP

1 l.t. 100-yr 14.5 22.4 29.2 37.0 48.5 57.1

10   12.0 18.5 24.1 30.5 40.0 47.1

100   10.5 16.2 21.1 26.7 35.0 41.2

200   10.1 15.5 20.2 25.6 33.6 39.5

500   9.3 14.3 18.6 23.6 30.9 36.4

1,000   8.5 13.0 17.0 21.5 28.2 33.2

5,000   5.6 8.6 11.2 14.2 18.6 21.9

10,000   4.5 6.9 9.0 11.4 15.0 17.6

20,000   3.5 5.3 6.9 8.8 11.6 13.6

               

Page 36: Engineering

Conversion of 10 sq.mi. PMPs to 1

sq.mi. PMPs

Page 37: Engineering

1-hour PMP @ 1 sq.mi. Basin

Page 38: Engineering

Estimated 1-hour Rainfall Rates w/Recurrence Intervals

Local Precipitation & Roof Drainage Design (1 hr Rainfall, inches)

Basin Size, sq.mi. X

0(100-yrs)

1(500-yrs)

2(2,000-yrs)

3(10,000-yrs)

4(100K-yrs) PMP

1 l.t. 4.30 4.3 6.0 8.0 11.0 16.5 19.4

10   3.54 4.95 6.60 9.06 13.60 16.00

100   2.49 3.48 4.64 6.37 9.56 11.25

200   2.06 2.88 3.84 5.27 7.91 9.31

500   1.55 2.16 2.88 3.96 5.95 7.00

1,000   1.16 1.62 2.16 2.97 4.45 5.24

2,000   0.73 1.02 1.37 1.88 2.80 3.30

5,000   0.52 0.72 0.96 1.32 1.98 2.33

10,000   0.39 0.54 0.72 1.00 1.49 1.75

20,000   0.30 0.42 0.56 0.80 1.16 1.36

               

Page 39: Engineering

Summary of Flood Design Criteria

Summary of Flood Design Criteria

Performance Category X

0(100-yrs)

1(500-yrs)

2(2,000-yrs)

3(10,000-yrs)

4(100K-yrs)

Flood Hazard Return Period, yrs l.t. 100 g.e. 100 g.e. 500 g.e. 2,000 g.e. 10,000 g.e. 100,000

Design Reqm'ts

Does not meet ASCE 24, FBC and ARC 4496

ASCE 24, FBC plus ARC 4496

ASCE 24, FBC Essential Facility plus ARC 4496 ASCE 24 ASCE 24 ASCE 24

Minimum Design Floor Elevation

Floor Elev. Below BFE

BFE or DFE, whichever is

greater

BFE + 1.5 ft. or local DFE,

whichever is greater

BFE + 2.0 ft. or local DFE,

whichever is greater

BFE + 3.0 ft. or local DFE,

whichever is greater

BFE + 4.0 ft. or local DFE,

whichever is greater

Riverine Flooding

FIRM Zone Shaded A, AE,

AH or V

FIRM Zone Shaded X; apply

design precip event to basin

FIRM Zone Shaded X; apply

design precip event to basin

FIRM Zone Shaded X; apply

design precip event to basin

FIRM Zone Shaded X; apply

design precip event to basin

FIRM Zone Shaded X; apply

design precip event to basin

Page 40: Engineering

Summary of Flood Design Criteria

Summary of Flood Design Criteria

Performance Category X

0(100-yrs)

1(500-yrs)

2(2,000-yrs)

3(10,000-yrs)

4(100K-yrs)

Flood Hazard Return Period, yrs l.t. 100 g.e. 100 g.e. 500 g.e. 2,000 g.e. 10,000 g.e. 100,000

Local Precipitation/Site Drainage

l.t.100-year, 1-day Precip

Design

g.e. 100-year, 1-day Precip

Rate; apply

design precip

event to site

~ 22 inch, 1-day Precip

Rate; apply design precip

event to site

~ 29 inch, 1-day Precip

Rate; apply design precip

event to site

~ 37 inch, 1-day Precip

Rate; apply design precip

event to site

~ 48.5 inch, 1-day Precip

Rate; apply design precip

event to site

Roof Design Drainage; ref: Figure 1106.1, FBC-Plumbing

l.t.100-year, 1-hour

rainfall rate; l.t.

~4.3 inchs/hr

g.e.100-year, 1-hour

rainfall rate; g.e. ~4.33 to

5.0 inchs/hr g.e. 6 inchs/hr g.e. 8 inchs/hr g.e. 11 inchs/hr g.e. 16.5 inchs/hr

Storm Surge

l.t. Cat. 5 minus 1.0 ft. elev.

g.e. Cat 5 minus 1.0 ft. elev. g.e. Cat 5 elev.

g.e. Cat 5 elev. plus 10%

g.e. Cat 5 elev. plus 15%

g.e. Cat 5 elev. plus 20%

Page 41: Engineering

Storm Surge Flooding

SLOSH Storm Surge ModelCategory 5 inundation depth/elevation, NGVD

Maximum Envelope of Water

Margin of Error = +/- 20%

Category 5 elev. + 20% = Probable Maximum Inundation

Page 42: Engineering

Storm Surge Flooding

Fla. Performance Category 3 = Cat. 5 + 15%

Fla. Performance Category 4 = Cat. 5 + 20%

Performance suggested per county based on PC 4 (10,000-yr) Wind Map

Design wind speeds at coast that are greater than or equal to 190 mph (3-sec. gust) = Cat. 5 + 20%

Design wind speeds at coast that are less than 190 mph (3-sec. gust) = Cat. 5 + 15%

Page 43: Engineering

Representative Flood Design Criteria

Applies to lowest floor for the EOC and essential ancillary structures and service equipment

Finished Floor Elevation NGVD determined by:Category 5 storm surge elev. + 20%

BFE + 3.0 feet

500-yr elevation + 2.0 feet

Highest recorded flood elevation + 3.0 feet

Whichever flood elevation is highest

Page 44: Engineering

Representative Flood Design Criteria

The site (point maximum, one square mile) hydrologic design shall ensure that the EOC and essential ancillary structures and service equipment are not flooded due to a 24 hour, 37.0 inch rainfall event applied over a precedent 24 hour, 100-year rainfall event

Opinion of design professional is acceptable

Basin-wide analysis not required

Page 45: Engineering

Representative Flood Design Criteria

Where secondary (emergency) roof drains or scuppers are required by the Florida Building Code—Plumbing, the secondary system shall be sized for a rainfall rate of eleven (11.0) inches per hour

Page 46: Engineering

Earthquake Design

Page 47: Engineering
Page 48: Engineering

Earthquake 10,000-yr

Design Criteria for

Florida

Page 49: Engineering

Earthquake 10,000-yr

Design Criteria for

Florida

Page 50: Engineering

QUESTIONS??? http://floridadisaster.org/bpr/Response/engineers/index.htm