Upload
arnold-de-leon
View
143
Download
0
Tags:
Embed Size (px)
Citation preview
Energy Savings on Fan Applications
Compiled by Arnold S. De Leon
2
Types of Fans Axial or Propeller Fans
In an axial fan the air flows in parallel to the shaft.
Axial fans are suited for relatively large volumes compared to pressure.
PropellerVane Axial
ADL 06/07/2010
Roof Ventilator
3
Types of Fans
Centrifugal Fan In a centrifugal fan the air
flows is in a radial direction relative to the shaft.
Suitable for higher airflow and pressure
ADL 06/07/2010
4
Classification of Centrifugal Fans
Straight radial blades. Self cleaning. Suitable for material transportCurved backward blades. High efficiency, low
energy consumption, changing in pressure have little influence on air volume. Low noise emission, stable in parallel running.
Curved forward blades. High efficiency, small dimensions, changing in pressure have little influence on pressure head
ADL 06/07/2010
5
Basic Terms in Fan Application
Static Head is defined as “the pressure exerted by a still liquid or gas,
especially water or air.
Figure 1, Showing Equal Air Pressure inside and outside the building. Here no exhaust fan running
Figure 2, with Exhaust Fan running Inside Air is lesser than Outside Air.
ADL 06/07/2010
6
Basic Terms in Fan Application
Flow (Q) Amount of liquid or gas necessary to maintain Static Pressure
express is Cubic Feet per Minute or Cubic Meters per Minute.
Point to remember 2.44 ft2 of vent box opening
can accommodate approximately 1500 CFM of air or 42 cu. Meters per minute
ADL 06/07/2010
7
Basic Terms in Fan Application
Brake Horse Power (BHP) The brake horsepower is the amount of real horsepower going to
the pump, not the horsepower used by the motor. In the metric system kilowatts (kW) is used.
Due to hydraulic, mechanical and volumetric losses in a pump or turbine the actual horsepower available for work on or from the fluid is less than the total horsepower supplied.
P BHP = * Q * h / 3300 /
P BHP = Brake Horse Power
= specific weight of air Q = is for flow in CFM h= is for head = stands for efficiency
P EL = P BHP / EL
P EL = Electric Motor Power
EL = stands for motor efficiency
ADL 06/07/2010
8
How to read a Fan Curve?
Points to Remember:
•The most valuable pieces of information supplied by fan manufacturers is the fan performance curve.
•Each Fan, has its own performance curve on a particular application.
ADL 06/07/2010
9
Fan Curve Basics
Fan Curve Figure on the right shows a typical
centrifugal fan produce at its outlet at a given RPM.
The curve is a plot of outlet pressure in inches of water versus the flow of air in CFM of a Fan. System Curve
The System Curve is added to the Fan Curve
This shows the requirement of the vent system from the fan to overcome losses and produce an air flow..
Fan Curve
System Curve
OperatingPoint
Operating Point The point where pressure and flow
requirement of the system can meet by the fan.
Without external influences, the fan will operate only at this point.ADL 06/07/2010
10
Fan Curve Basics
Fan Curve
System Curve
OperatingPoint
BHP
BHP Curve Now the BHP curve is added. At Static Pressure of 4 units Head,
and Flow of 6.2 units CFM, the motor shaft will exert 6.2 BHP of power.
Computing for the Motor HP Say motor at full load efficiency of
90% P EL = P BHP / EL
P EL = 6.2 / 0.90
P EL = 6.8 HP Commercially available motors
are 5.5 and 7.5 HP, choose 7.5 HP ADL 06/07/2010
11
Fan Curve Basics
Fan Curve
BHP
Effect of Resistance to the fan System Curve can shift due to
following factors,▪ Dirt in the filters▪ Damper throttling
Increase resistance
decreaseresistance
ADL 06/07/2010
12
Methods of Regulation in Fans
• Outlet Dampers
• Variable Inlet Vanes
• Pitch Control
• AC Drives or Variable Frequency Drive
ADL 06/07/2010
13
Outlet Damper
The outlet dampers affect the system curve.
As the outlet damper is closed, the fan’s point of operation moves left from the initial design point on the static pressure curve.
Depending on where the design point is, damper horsepower may be less, the same, or more than the full flow of horsepower.
Outlet dampers are typically the least expensive first cost option but also offer the least potential for energy savings.
ADL 06/07/2010
14
Variable Inlet Vane
Inlet-vane dampers affect the Fan Curve.
It spins the air in the direction of wheel rotation as it enters the fan. With this pre-spin, the wheel cannot develop its full output, yielding a reduced CFM at reduced horsepower.
Each damper setting creates new pressure and horsepower curves. With inlet-vane dampers, reduced airflow always results in reduced horsepower.
More expensive initially than outlet dampers, but inlet-vane dampers offer greater potential for energy savings.
ADL 06/07/2010
15
Variable Pitch Axial Fan
It has a sophisticated hub which carries the blades. Each blade is connected to a spindle, which is rotated by a lever. A servo-controlled hydraulic cylinder moves all the levers simultaneously while the fan impeller is rotating. This varies the output of the fan.
The blade/hub assembly is mounted on a shaft which rotates in a casing, and is then referred to as the rotor.
The casing may have an open inlet, but more commonly it will have a right angled bend to allow the motor to sit outside the ductwork. The discharge casing gently expands to slow down the air or gas flow and convert kinetic energy into useful static pressure.
Mechanically unreliableHigh Electrical Efficiency
ADL 06/07/2010
16
Variable Pitch Axial Fan
Mechanically Linked Variable Pitch Axial Fan
Servo ControlledVariable Pitch Axial Fan
ADL 06/07/2010
17
AC Drive or VFD
VFD controllers provide energy savings by directly controlling fan speed.
From the fan laws, CFM varies directly with the change in fan speed and horsepower varies by the change in fan speed cubed.
For example, a 20% reduction in fan speed yields a 20% reduction in airflow and a 49% reduction in BHP.
VFD provides the greatest potential for energy savings.
ADL 06/07/2010
18
Which the best Regulation Method?
Outlet Damper Inlet VaneVFD
ADL 06/07/2010
ADL 06/07/2010 19
Mathematical Concept
System Curve Formula;
P = K * Q2
Where
P = the pressure required to produce a given flow in the system
K = is a function of the system and represents the friction to air flow. The outlet vanes affect the K factor.
Q = is the airflow desired
Fan Affinity Law;
Volume CapacityQ1 / Q2 = (n1 / n2) (1a)
Head or PressureP1 / P2 = (n1 / n2)2 (2a)
PowerHP1 / HP2 = (n1 / n2)3 (3a)
Where
P = the pressure required to produce a given flow in the system
n= is the motor speedQ = is the airflow desiredHP = is the Horse Power of Motor
ADL 06/07/2010 20
Mathematical Concept
Note that when System Curve Formula and Affinity Law are combine,
P = K * Q2 ; K = P / Q2
From Affinity Laws Volume Capacity:
Q1 / Q2 = (n1 / n2) ; {Q1 / Q2} 2 = (n1 / n2) 2
From Affinity Laws Pressure Vs. Speed:
P1 / P2 = (n1 / n2)2 ; P1 / P2 = {Q1 / Q2} 2
P1 / Q12 = P2 / Q22 (This is same equation for System Curve “K”)
21
Mathematical Concept
The mathematical equation shows, that VFD regulation can achieves flow control in a way that closely matches the system or load curve
As the fan speed is reduced, a
significant reduction in power requirement is achieved.
For example, a 20% reduction in fan speed yields a 20% reduction in airflow and a 49% reduction in BHP.
ADL 06/07/2010
ADL 06/07/2010 22
Sample Calculation
A Fan was selected to run at 300 RPM, 100 CFM and 4 inches of Static Pressure.
Determine the best regulation method.
ADL 06/07/2010 23
Sample Calculation- Outlet Damper
CFM Duty HPFrom Fan
Curve
Weighted HP
100 10% 35 3.5
80 40% 35 14.0
60 40% 31 12.4
40 10% 27 2.7
Total 32.6CFM
Dwell timeOutlet
DamperWithout
Regulation
Weighted HP 32.6 35
Equivalent in KW
24.3 26.1
Dwell time 496 496
Power rate PHP 8/ kW-hr
PHP 8/ kW-hr
Total Energy Cost/month
PHP 96,424 PHP 103,565
Savings using Outlet Damper PHP 7,141.00
ADL 06/07/2010 24
Sample Calculation- VFD Regulation
CFM Duty HPUsing Affinity
Law
Weighted HP
100 10% 35 3.5
80 40% 18 7.2
60 40% 7.56 3.02
40 10% 2.24 0.22
Total 13.94CFM
Dwell timeVFD
RegulationWithout
Regulation
Weighted HP 13.94 35
Equivalent in KW
10.4 26.1
Dwell time 496 496
Power rate PHP 8/ kW-hr
PHP 8/ kW-hr
Total Energy Cost/month
PHP 55,314 PHP 103,565
Savings Using VFD PHP48,251
Using Fan Affinity Law;
Power versus Speed or Cube LawHP = n 3
@ 100% CFM ; HP = 100%
@ 80% CFM ; HP = (0.8)*(0.8)*(0.8)= 0.512*
35HP= 18HP
@ 60% CFM ; HP = (0.6)*(0.6)*(0.6)= 0.216*
35HP= 7.56HP
@ 40% CFM ; HP = (0.4)*(0.4)*(0.4)= 0.064*
35HP= 2.24HP
ADL 06/07/2010
Savings Comparison
25
Without Regulation
Outlet Damper
VFD Regulation
Weighted HP 35 32.6 13.94
Equivalent in KW
26.1 24.3 10.4
Dwell time 496 496 496
Power rate PHP 8/ kW-hr PHP 8/ kW-hr PHP 8/ kW-hr
Total Energy Cost/month
PHP 103,565 PHP 96,424 PHP 55,314
Savings using Outlet Damper
PHP 7,141.00
Savings Using VFD per Month PHP48,251
Difference in Savings per Month PHP 41,110.00
ADL 06/07/2010 26
Welcome to VACON
ADL 06/07/2010 27
Vacon HVAC Proven Technology
Heathrow Airport, Terminal 5, UK
Inox multiplex cinema, Pune, India
DR multimedia house, Copenhagen, Denmark
Raffl es private hospital, Singapore
Jumeirah Emirates Towers, Dubai, UAE
Sello shopping centre, Espoo, Finland
ADL 06/07/2010 28
Questions?