® SPECIFICATION SUBMITTAL Page Job Name: Job Number: Model Numbers: Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers 369-241d 1 11.08.10 Energi Savr NodeTM 0-10 V/Softswitch® The Energi Savr Node family is a group of modular prod- ucts for the control of lighting and other loads. This document describes the following products: Energi Savr Node unit for 0-10 V (model QSN-4T16-S — 0-10 V Control / Softswitch) Softswitch Energi Savr Node unit (model QSN-4S16-S — Softswitch) Features Energi Savr Node unit. lights in 4 zones. levels based on the amount of natural light entering through the windows. ® Softswitch - time. ® System. System Example 120-277 V 120-277 V 4 0-10 V Channels (QSN-4T16-S only) Contact Closure Contact Closure (16 A Softswitch 120-277 V ) Wireless Communication Sensors (up to 4) 2 Wired Sensors (up to 4) Sensors (up to 4) Wired Sensors (up to 4) 1 Wired Wallstation Wired Wallstation (up to 4) 1 ® Class 2/ Switch (up to 4) (by others) Notes: 1 Up to 4 wired sensors total (of any type). 2 The maximum number of daylight sensors (wired and wireless) that an Energi Savr Node unit can support is four (1 per zone). QSM seeTouch® QS Wallstation TM Sensor (up to 10 per QSM) TM (up to 10 per QSM) 2 ® Wireless Controller (up to 10 per QSM) 1

Energi Savr Node 0-10 V/Softswitch - Platt Electric Supply QSN-4S16-S.pdf · 2011-04-24 · Energi Savr Node TM QSN 0-10 V/SoftSwitch ® Fixture Controllers Energi Savr Node 369-241d

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Energi Savr Node 0-10 V/Softswitch - Platt Electric Supply QSN-4S16-S.pdf · 2011-04-24 · Energi Savr Node TM QSN 0-10 V/SoftSwitch ® Fixture Controllers Energi Savr Node 369-241d

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers

369-241d 1 11.08.10

Energi Savr NodeTM 0-10 V/Softswitch®

The Energi Savr Node family is a group of modular prod-ucts for the control of lighting and other loads. This document describes the following products:

Energi Savr Node unit for 0-10 V (model QSN-4T16-S — 0-10 V Control / Softswitch)

Softswitch Energi Savr Node unit (model QSN-4S16-S — Softswitch)

Features

Energi Savr Node unit.

lights in 4 zones.

levels based on the amount of natural light entering through the windows.

®

Softswitch -time.

® System.

System Example

LUTRON

R

LUTRON

R

120-277 V

120-277 V

4 0-10 V

Channels

(QSN-4T16-S only)

Contact

Closure

Contact

Closure

(16 A Softswitch

120-277 V )

Wireless

Communication

Sensors (up to 4)2

Wired

Sensors

(up to 4)

Sensors (up to 4)

Wired

Sensors

(up to 4)1

Wired Wallstation

Wired

Wallstation

(up to 4)1

® Class 2/

Switch (up to 4)

(by others)

Notes:

1 Up to 4 wired sensors total (of any type).

2 The maximum number of daylight sensors (wired and wireless) that an

Energi Savr Node unit can support is four (1 per zone).

QSMseeTouch® QS

Wallstation

TM

Sensor (up to 10 per QSM)

TM

(up to 10 per QSM)2

® Wireless Controller (up to 10 per QSM)

1

Page 2: Energi Savr Node 0-10 V/Softswitch - Platt Electric Supply QSN-4S16-S.pdf · 2011-04-24 · Energi Savr Node TM QSN 0-10 V/SoftSwitch ® Fixture Controllers Energi Savr Node 369-241d

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers

369-241d 2 11.08.10

Specifications

Energi Savr NodeTM

Power

; 220-240 V ; 277 V 50/60 Hz

62.41-1991. Can withstand voltage surges of up to 6000 V and current surges of up to 3000 A

prior to power interruption

when control power feed is lost

Standards

®

Environment

®

used for environmental air”

Terminal Wiring

(2.5 mm2 2)

2 2)2 2)

2 2) — maximum wire run length to each input not to

exceed 150 ft (46 m)2 2)

2 2)

Physical Design and Mounting

Load Types (relay ratings)

Input Default Associations

Inputs/Outputs Zone 1 Zone 2 Zone 3 Zone 4

Gro

up

1

X

X

X

Switch X

Gro

up

2

X

X

X

Switch X

Gro

up

3

X

X

X

Switch X

Gro

up

4

X

X

X

Switch X

X X X X

X X X X

Softswitch®

(120 V - 277 V )

Softswitch relay is rated for 16 A continuous use

Softswitch circuit eliminates arcing at

mechanical contacts when loads are switched.

-

tive sources.

0–10 V Product Ratings

(QSN-4T16-S only)

supply).

NEC

2

Page 3: Energi Savr Node 0-10 V/Softswitch - Platt Electric Supply QSN-4S16-S.pdf · 2011-04-24 · Energi Savr Node TM QSN 0-10 V/SoftSwitch ® Fixture Controllers Energi Savr Node 369-241d

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers

369-241d 3 11.08.10

Specifications (continued)

Occupancy Sensors

®

one or more zones.Lutron occupancy sensors in vacancy mode to au-

tomatically turn the lights off in an area after it becomes vacant.Lutron occupancy sensors can be programmed to auto-matically turn the lights on in area when it becomes oc-cupied and turn the lights off in an area after it becomes vacant.

Lutron occupant sensor.

be programmed independently.Lutron

TM

assigned when associated with a QS Sensor Module (QSM) with manual programming.

Energi Savr Node unit when programming with an Apple

iPod touch or iPhonesection for details.

seeTouch® QS Controls

seeTouchEnergi Savr Node unit scenes or zones.

one or more zones on any Energi Savr Node unit con-

more Energi Savr Node

Table 1: seeTouch QS Wallstation Configurations

# Buttons

Wallstation Function 1 2 3 5 7Zone Toggle ü ü ü ü ü

Scene(toggle)

N/A

IR Wallstation or Receiver Input

control of lighting zones can be connected di-rectly to the Energi Savr Node unit

Lutron -stations to control one or more zones.

Lutron mount sensors to control one or more zones.

receivers can be assigned when associated with a QS Sensor Module (QSM).

with Energi Savr Node unit when programming

with an Apple iPod touch or iPhone

Daylight Sensors

Lutron daylight sensors allow daylight harvesting with programmable effect on light output.

to the Energi Savr Node unit.Lutron

more zones.Lutron Wired

TM

Sensors) can be assigned when associated with a QS Sensor Module (QSM).

Lutron daylight sensors

unit or indirectly (associated with a QSM) cannot exceed four.

with Energi Savr Node unit when programming

with an Apple iPod touch or iPhone

Contact Closure Input (CCI) Default behavior:

Activate scenes using momentary or maintained closures from an external device such as a time-

closure.

closure or solid-state output.-

ly-Closed (NC) operation.

.

other countries.

3

Page 4: Energi Savr Node 0-10 V/Softswitch - Platt Electric Supply QSN-4S16-S.pdf · 2011-04-24 · Energi Savr Node TM QSN 0-10 V/SoftSwitch ® Fixture Controllers Energi Savr Node 369-241d

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers

369-241d 4 11.08.10

Specifications (continued)

Emergency Contact Closure Input

to full output when emergency state is detected.

closed (NC). The Energi Savr Node unit is

output and ignore control inputs.

signal is cleared.

closure or solid-state output..

Energi Savr

Node units.

Functionality with GRAFIK Eye® QS

Energi Savr Node unit follows GRAFIK Eye QS

scene activations when associated with the

GRAFIK Eye QS.

Energi Savr Node unit responds to commands

initiated by the GRAFIK Eye QS astronomic time

GRAFIK Eye QS.

Energi Savr Node unit operates in afterhours

mode when associated with a GRAFIK Eye QS

that is in afterhours mode.

Functionality with QSE-IO

Energi Savr Node unit responds to scene com-

switches have been set to either scene selection

-

cupancy sensor mode.

Functionality with QSE-CI-NWK-E

Energi Savr Node unit with touch-

systems and devices.

NEC® Class 2/PELV Dry Contact Switches

NEC

switches can be assigned to turn on and off one

or more zones.

-

tion.

QS Link Limits

Energi Savr Node unit can provide up to 14

zones.

Energi Savr Node unit counts as 1 device

towards the 100 device limit.

Energi Savr Node unit counts as 4 zones

towards the 100 zone limit.

QSM (QS Sensor Module)

TM

Radio Powr Savr

® Wireless Controllers to

control zones on the Energi Savr Node unit.

Energi Savr Node unit with

manual programming.

Energi Savr Node

unit with Apple iPod touch or iPhone program-

Radio Powr Savr

sensors per Energi Savr Node unit via QSM.

Radio Powr Savr

per Energi Savr Node unit via QSM.

Pico Wireless Controllers per

Energi Savr Node unit via QSM.

Pico Wireless Controllers

associated with the QSM should be mounted

information.

other countries.

4

Page 5: Energi Savr Node 0-10 V/Softswitch - Platt Electric Supply QSN-4S16-S.pdf · 2011-04-24 · Energi Savr Node TM QSN 0-10 V/SoftSwitch ® Fixture Controllers Energi Savr Node 369-241d

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers

369-241d 5 11.08.10

QS System Limits

maximums for zones and devices.

Softswitch or 0-10 V Energi Savr Node unit can supply 14

power draw units.

Table 2: QS System Limits

QS Device

Description

Zone

Count

Device

Count

Power

Draw Units

(supplied)

Power

Draw Units

(consumed)

Softswitch Energi Savr Node unit (QSN-4S16-S) 4 1 14 0

Energi Savr Node unit for 0-10 V/Softswitch (QSN-4T16-S) 4 1 14 0

EcoSystem Energi Savr Node up to 100 1 30 0

Energi Savr Node 0 1 0 2

0 1 0 3

® 0 0 0 2

Lutron 0 0 0 0.5

Lutron 0 0 0 0.5

® QS 3 1 3 0

4-zone GRAFIK Eye QS 4 1 3 0

6-zone GRAFIK Eye QS 6 1 3 0

6-zone GRAFIK Eye ® 6 1 3 0

8-zone GRAFIK Eye QS with EcoSystem 8 1 3 0

16-zone GRAFIK Eye QS with EcoSystem 16 1 3 0

seeTouch® QS 0 1 0 1

QS contact closure interface up to 5 1 0 3

0 1 0 2

0 0 8 0

*Note:

connected directly to the Energi Savr Node unit.

5

Page 6: Energi Savr Node 0-10 V/Softswitch - Platt Electric Supply QSN-4S16-S.pdf · 2011-04-24 · Energi Savr Node TM QSN 0-10 V/SoftSwitch ® Fixture Controllers Energi Savr Node 369-241d

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers

369-241d 6 11.08.10

Programming Options

Manual Programming:

Use buttons on the front of the Energi Savr Node unit.

Use manual programming in installations with only one Energi Savr Node unit and with one QS Sensor Module

HHD Programming

Apple iPod touch or iPhone mobile digital device.

Use the intuitive programming application for the Apple iPod touch or iPhone to program systems with multiple

Energi Savr Node

Apple iPod touch or iPhone.

Energi Savr Node

Energi Savr Node

Lutron recommends that an Energi Savr Node Energi Savr Node -

router.

Apple iPod touch or iPhone can program all Energi Savr Node QS units connected to an Energi Savr Node

® system).

Energi Savr Node Apple iTunes Store

QSM QSM QSM

Energi Savr

Node

Unit

Apple iPod touch or iPhone mobile digital device

Wireless

(by others)

Energi Savr Node

Connection for Energi Savr Node

units

Energi Savr

Node

Unit

Energi Savr

Node

Unit

registered in the U.S. and other countries.

2 Note: Energi Savr Node units are not designed to exist on an open

6

Page 7: Energi Savr Node 0-10 V/Softswitch - Platt Electric Supply QSN-4S16-S.pdf · 2011-04-24 · Energi Savr Node TM QSN 0-10 V/SoftSwitch ® Fixture Controllers Energi Savr Node 369-241d

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers

369-241d 7 11.08.10

Programming Options and Features

Manual Programming

HHD Programming:

Apple iPod touch or iPhone mobile

Energi Savr Node units (ESNs)

Connected to 1 QS Link

Not more than 1 Multiple—100 QS devices and 100 zone limits apply

QS Sensor Modules (QSMs)

Connected to 1 QS link

Not more than 1 Multiple—100 QS devices limit applies

Wired Occupancy Sensors

System Limits 4 connected directly to ESN unit

Up to 4 wired to QSM

Up to 100 total occupancy sensors per QS link

(wired + wireless)

Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same

QS link

Occupancy Dependency

Supported

No Yes

Wireless Occupancy Sensors

System Limits Associate 10 occupancy sensors to QSM

to control zones on the ESN unit

Up to 100 total occupancy sensors per QS link

(wired + wireless)

Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same

QS link

Occupancy Dependency

Supported

No Yes

Wired Daylight Sensors

System Limits Maximum of 1 daylight sensor per zone

4 connect directly to the ESN unit

Additional daylight sensors can connect to

the QSM

Maximum of 2 daylight sensors per zone

Up to 100 total daylight sensors per QS link

(wired + wireless)

Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same

QS link

Disable daylighting in Scenes No Yes

Wireless Daylight Sensors

System Limits Maximum of 1 daylight sensor per zone

Associate wireless daylight sensors to the

QSM

Maximum of 2 daylight sensors per zone

Associate up to 10 wireless daylight sensors per QSM

Up to 100 total daylight sensors per QS link

(wired + wireless)

Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same

QS link

Disable daylighting in Scenes No Yes

7

Page 8: Energi Savr Node 0-10 V/Softswitch - Platt Electric Supply QSN-4S16-S.pdf · 2011-04-24 · Energi Savr Node TM QSN 0-10 V/SoftSwitch ® Fixture Controllers Energi Savr Node 369-241d

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers

369-241d 8 11.08.10

Programming Options and Features (continued)

Manual Programming

HHD Programming:

Apple iPod touch or iPhone mobile

Pico® Wireless Controllers

System Limits Associate 10 Pico wireless controllers to

QSM to control zones on the ESN unit

Up to 100 total controls per QS link (wired wallstations,

Pico wireless controllers, IR receivers)

Can be assigned to… Any zone on the local ESN unit Zones on ESN unit or share to other ESN units on

same QS link

IR Receivers and Wallstations

System Limits 4 connect directly to the ESN unit

Up to 4 wired to the QSM

Up to 100 total controls per QS link (wired wallstations,

Pico wireless controllers, IR receivers)

Can be assigned to… Any zone on the local ESN unit Zones on ESN unit or share to other ESN units on

same QS link

NEC® dry contact Switches Inputs

Can be assigned to… Any zone(s) on the connected ESN Any zone(s) on the connected ESN

Contact Closure Input

Can be assigned to… Any zone(s) on the ESN unit Any or all local ESN unit zones

Functions

Afterhours Con!guration afterhours timeout- 15 minutes

blink-warn timeout- 5 minutes

Afterhours timeout and blink-warn

timeouts are con!gurable

Emergency Contact Closure Input

Can be assigned to… Any zone(s) on the ESN unit Any or all local ESN zones

Emergency Light level Con!gurable Con!gurable

8

Page 9: Energi Savr Node 0-10 V/Softswitch - Platt Electric Supply QSN-4S16-S.pdf · 2011-04-24 · Energi Savr Node TM QSN 0-10 V/SoftSwitch ® Fixture Controllers Energi Savr Node 369-241d

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers

369-241d 9 11.08.10

Programming Options and Features (continued)

Manual Programming

HHD Programming:

Apple iPod touch or iPhone mobile

seeTouch® QS wallstations

Scene Keypads assigned to… Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link

Scene + off keypads assigned

to…

Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link

Zone toggle keypad buttons

assigned to…

Any zone(s) on the ESN unit Any zone(s) on on or more ESN units on the link

Change Keypad to Scene or

Zone

Yes Yes

Changing keypads to shade,

panic, !ne tune

No Yes

Zone Configuration Parameters

Load type 0-10, 10-0, or switched 0-10, 10-0, or switched

High-end trim Adjustable Adjustable

Low-end trim Adjustable Adjustable

Absolute minimum level Adjustable Adjustable

Scenes

Available scenes Scenes 1-16 Scenes 1-16

GRAFIK Eye® QS Share scenes, timeclock events, or

afterhours events to ESN units on QS Link

QSE-IO Scene, zone toggle, occupancy Scene, zone toggle, occupancy

QSE-CI-NWK-E Yes Yes

9

Page 10: Energi Savr Node 0-10 V/Softswitch - Platt Electric Supply QSN-4S16-S.pdf · 2011-04-24 · Energi Savr Node TM QSN 0-10 V/SoftSwitch ® Fixture Controllers Energi Savr Node 369-241d

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers

369-241d 10 11.08.10

Mechanical Dimensions

All dimensions shown as inches (mm)

11.25 (285.75)

0.20 (5.16) dia.

1.00 (25.40)

1.22 (30.99)

1.66 (42.16)

1.31 (33.27)

0.88 (22.35)

9.25 (234.95)

7.50 (190.50)

3.16 (80.26)

13.25 (336.55)

use side

Line Voltage Shield

10

Page 11: Energi Savr Node 0-10 V/Softswitch - Platt Electric Supply QSN-4S16-S.pdf · 2011-04-24 · Energi Savr Node TM QSN 0-10 V/SoftSwitch ® Fixture Controllers Energi Savr Node 369-241d

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers

369-241d 11 11.08.10

Wiring: QS Link

Terminal 2 NEVER connected

between devices that supply PDUs

Terminal 2 (+24 V)

COM

+24 V

MUX

MUX

COM

MUX

MUX

Energi Savr Node QS unit

Energi Savr Node QS unit

QS

Output

Interface

Wired

QS

Keypad

QSM

QSMQSMWired

QS

Keypad

Wired

QS

Keypad

Wired

QS

Keypad

QS

Output

Interface

QS

Link

power

supply

all 4 terminals

no t

erm

inal 2

no t

erm

inal 2

all 4 terminals

all 4 terminals

Terminal 2 (+24 V)

Terminal 2 (+24 V)

**

QS Link Wiring Rules

*

**

for the specific power supply model being used.

11

Page 12: Energi Savr Node 0-10 V/Softswitch - Platt Electric Supply QSN-4S16-S.pdf · 2011-04-24 · Energi Savr Node TM QSN 0-10 V/SoftSwitch ® Fixture Controllers Energi Savr Node 369-241d

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers

369-241d 12 11.08.10

Wiring: NEC® Class 2/PELV Inputs

Sensor

Transmitter

Transmitter

Note: Maximum wire run length to each input not to exceed 150 ft (46 m).

or Wired NEC Class 2/

Switch

Yello

w

NEC

LUTRON

LUTRON

R

(0.5 mm2 to 4.0 mm2)

m)

same inputs as shown in the diagram below.

* Note:

versa.

**

20V

LUTRON

R

12

Page 13: Energi Savr Node 0-10 V/Softswitch - Platt Electric Supply QSN-4S16-S.pdf · 2011-04-24 · Energi Savr Node TM QSN 0-10 V/SoftSwitch ® Fixture Controllers Energi Savr Node 369-241d

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers

369-241d 13 11.08.10

Wiring: Contact Closure Inputs (CCI and Emerg)

(0.5 mm2 to 4.0 mm2)

m)

13

Page 14: Energi Savr Node 0-10 V/Softswitch - Platt Electric Supply QSN-4S16-S.pdf · 2011-04-24 · Energi Savr Node TM QSN 0-10 V/SoftSwitch ® Fixture Controllers Energi Savr Node 369-241d

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers

369-241d 14 11.08.10

Wiring Diagram: Example A – 4 circuits, multiple feeds

Sw

itche

d H

ot (1

B)

Hot

Fee

d (1

A)

Hot

Fee

d (2

A)

Hot

Fee

d (3

A)

Hot

Fee

d (4

A)

Sw

itche

d H

ot (2

B)

Sw

itche

d H

ot (3

B)

Sw

itche

d H

ot (4

B)

Ground Bar

Hot

Hot

Hot

Hot

Neutral

Neutral

Neutral

Neutral

Neutral

Ground

Hot

Neutral

Neutral Wires

Distribution Panel

LOAD

LOAD

LOAD

LOAD

0-10 V Wiring(QSN-4T16-S only)

0-10 V Zones:

(QSN-4T16-S only)

Zone Switching:

120-277 V

0-10 V Wiring (QSN-4T16-S only)2 2)

®

NEC

14

Page 15: Energi Savr Node 0-10 V/Softswitch - Platt Electric Supply QSN-4S16-S.pdf · 2011-04-24 · Energi Savr Node TM QSN 0-10 V/SoftSwitch ® Fixture Controllers Energi Savr Node 369-241d

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

Energi Savr NodeTM QSN 0-10 V/SoftSwitch® Fixture Controllers

369-241d 15 11.08.10

Wiring Diagram: Example B – 4 circuits, single feed

Zone Switching:

120-277 V

0-10 V Zones:

(QSN-4T16-S only)

Hot

Neutral

Ground

Ground Bar

Neutral Wires

Distribution Panel A

LOAD

LOAD

LOAD

LOAD

0-10 V Wiring(QSN-4T16-S only)

Sw

itche

d H

ot (1

B)

Hot

Fee

d (1

A)

Sw

itche

d H

ot (2

B)

Sw

itche

d H

ot (3

B)

Sw

itche

d H

ot (4

B)

Hot

Neutral

Ground

Distribution Panel B

0-10 V Wiring (QSN-4T16-S only)2 2)

®

NEC

15