19
Frankfurt (Germany), 6-9 June 2011 EN 50160 voltage dips and swells classification as an instrument for responsibility sharing Maurizio Delfanti Department of Energy– Politecnico di Milano CENELEC TC 8X/WG1 Secretary [email protected]

EN 50160 voltage dips and swells classification as an instrument for responsibility sharing

  • Upload
    ally

  • View
    60

  • Download
    0

Embed Size (px)

DESCRIPTION

Maurizio Delfanti Department of Energy – Politecnico di Milano CENELEC TC 8X/WG1 Secretary [email protected]. EN 50160 voltage dips and swells classification as an instrument for responsibility sharing. TC8X Organization. TC8X System Aspects of Electricity Supply. WG 3 - PowerPoint PPT Presentation

Citation preview

Page 1: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

EN 50160 voltage dips and swells classification as an instrument for responsibility sharing

Maurizio Delfanti

Department of Energy– Politecnico di Milano

CENELEC TC 8X/WG1 Secretary

[email protected]

Page 2: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

TC8X Organization

TC8XSystem Aspects of Electricity Supply

WG 1Physical

Characteristics Of Electrical Energy

WG 3Requirements for

connection of generators to distribution networks

WG 4Endorsement Of IEC 60038 as European

Standard

TF 1 ... 8

WG 5Smart Grid

Requirements

Page 3: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

First edition: November 1994

EN 50160: Voltage characteristics of electricity supplied by public distribution systems.

Subjects: LV and MV distribution networks

Further Editions: 1999, 2007

Current Edition: EN 50160:2010

prEN 50160:2009 voted positively on May, 2009

Ratification postponed by CLC BT due to comments received

Finally ratified by BT on March 2010 and dispatched on July 2010

Corrigendum December 2010 (d.o.w. of conflicting std2013-03-01)

Implemented at national level by March,1st 20113

Editions of EN 50160

Page 4: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

This European Standard defines, describes and specifies the main characteristics of the voltage at a network user's supply terminals in public low, medium and high voltage electricity networks under normal operating conditions.

This standard describes the limits or values within which the voltage characteristics can be expected to remain at any supply terminal in public European electricity networksand does not describe the average situation usually experienced by an individual network user.

4

EN 50160:2010 new title and scope

Page 5: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

In the new edition (EN 50160:2010), a distinction is made between:

continuous phenomena, i.e. small deviations from the nominal value that occur continuously over time - such phenomena are mainly due to load pattern, changes of load or nonlinear loads;voltage events, sudden and significant deviations from normal or desired wave shape.

Voltage events are typically due to unpredictable events (e.g., faults) or to external causes (e.g., weather, third party actions)

For some continuous phenomena limits are specified;for voltage events, only indicative values can be given at present.

5

New edition (EN 50160:2010)continuous phenomena / voltage events

Page 6: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

Voltage events, sudden and significant deviations from normal or desired wave shape.

Interruptions of the supply voltage

Supply voltage dips/swells

Transient overvoltages between live conductors and earth

It is possible to give only indicative values (incl. RVCs): such phenomena are difficult to predict; more investigation is needed

6

Voltage events

Page 7: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

Definition: a temporary reduction of the voltage at a point in the electrical supply system below a specified start threshold.

Note 1: For the purpose of this standard, the dip start threshold is equal to 90 % of the reference voltage.

Note 2: Typically, a dip is associated with the occurrence and termination of a short circuit or other extreme current increase on the system or installations connected to it.

Note 3: For the purpose of this standard, a voltage dip is a two dimensional electromagnetic disturbance, the level of which is determined by both voltage and time (duration).

7

Voltage events:voltage dips

Page 8: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

Reference was made to test levels given in

EN 61000-4-11 (different test levels for different classes: 1, 2, 3, X) EN 61000-4-11 contains a reference to the “network performance”

8

Network performance &equipment test levels

Test levels for appliances in EN 61000-4-11, class 3

It is useful to describe the possible behavior of the network with the same parameters used for testing appliances

(Product Standards)

Page 9: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

Measurement uncertainty (addressed in EN 61000-4-30) has to be considered. The duration of a voltage dip depends on the protection strategy adopted,

which may differ from case to case (network structure, neutral earthing, etc) Durations do not necessarily match the boundaries of the columns of the Table.9

The new classification in EN 50160:2010,Tables 2, 5 and 8

Page 10: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

For a given class of appliances (f.i., class 3), the cells above the curve represent an immunity area

Classes are referred to different electromagnetic environment, as defined in EN 61000-2-4

Duration t [ms]

Range of res. voltage Ur (in % of Un or Ud) 10 < t ≤ 200 200 < t ≤ 500 500 < t ≤ 5000

90 > Ur ≥ 80 A1 A2 A3+A4

80 > Ur ≥ 70 B1 B2 B3+B4

70 > Ur ≥ 40 C1 C2 C3+C4

40 > Ur ≥ 5 D1 D2 D3+D4

10

Equipment immunity

Page 11: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

For the cells below the curve, a regulation can be enforced at a national level

Expected values (for each bus? for each area? for worst served customers?) can be given by TSO/DSO

11

Duration t [ms]

Range of res. voltage Ur (in % of Un or Ud)

10 < t ≤ 200 200 < t ≤ 500 500 < t ≤ 5000

90 > Ur ≥ 80 A1 A2 A3+A4

80 > Ur ≥ 70 B1 B2 B3+B4

70 > Ur ≥ 40 C1 C2 C3+C4

40 > Ur ≥ 5 D1 D2 D3+D4

Voltage quality requirements

Page 12: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

As some standard/national documents (France, South Africa) already foresee, it is useful to set a bound between: events for which appliances have to be immune events that can be limited by the DSO/TSO

The concept of a “responsibility sharing curve” is much wider and complex (see next presentation by M. Bollen)

In the new edition of the Standard (EN 50160:2010) the concept has been applied to voltage dips

12

Responsibility sharing curve

Page 13: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

This annex is aimed at providing the reader with some information about indicative values currently available at a European level for some of the events defined and described in the standard.

Some information is also given about the way of using values given in the standard, and about the way of collecting further measurement data, in order to allow for comparisons between different systems and to have homogeneous data at a EU level.

As many monitoring systems are in place in some countries, further information is available at a national level.At a national level, more precise figures can be found; furthermore, some regulations may exist.

13

Annex B:B.1 General

Page 14: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

QuEEN monitors about 10% of the main MV bus-bars.

The sample is representative of the network characteristics in terms of: number of HV/MV substations per region length of the MV lines type of MV lines: cable, overhead, mixed neutral compensation or isolated neutral number/density of MV/LV customers

The system is managed by RSE

(Ricerca sul Sistema Energetico)

QuEEN: 400 monitoring units installed on MV bus-bars of HV/MV substations

Page 15: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

QuEEN report, year 2008(data collected on 10% of MV main busbars)

Average number of dips per bus: 124,1 97,7 voltage dips would be overcome by class 3 equipment 26,4 voltage dips would impair the operation of class 3 equipment

Duration t [ms]

Range of res. voltage Ur (in % of Un or Ud)

10 < t ≤ 200 200 < t ≤ 500 500 < t ≤ 5000

90 > Ur ≥ 80 29,2 5,6 2,0

80 > Ur ≥ 70 18,6 4,3 0,6

70 > Ur ≥ 40 40,0 6,8 0,7

40 > Ur ≥ 5 15,4 2,6 0,3

Page 16: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

QuEEN report, year 2009(data collected on 10% of MV main busbars)

Average number of dips per bus: 114,2 95,6 voltage dips would be overcome by class 3 equipment 18,6 voltage dips would impair the operation of class 3 equipment

Duration t [ms]

Range of res. voltage Ur (in % of Un or Ud)

10 < t ≤ 200 200 < t ≤ 500 500 < t ≤ 5000

90 > Ur ≥ 80 34,9 7,5 2,6

80 > Ur ≥ 70 17,1 5,3 0,8

70 > Ur ≥ 40 28,2 5,3 0,7

40 > Ur ≥ 5 9,9 1,7 0,2

Page 17: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

QuEEN report, year 2010(data collected on 10% of MV main busbars)

Average number of dips per bus: 98,3 82,4 voltage dips would be overcome by class 3 equipment 15,9 voltage dips would impair the operation of class 3 equipment

Duration t [ms]

Range of res. voltage Ur (in % of Un or Ud)

10 < t ≤ 200 200 < t ≤ 500 500 < t ≤ 5000

90 > Ur ≥ 80 31,5 6,4 2,0

80 > Ur ≥ 70 15,5 4,4 0,6

70 > Ur ≥ 40 22,6 4,8 0,5

40 > Ur ≥ 5 8,5 1,3 0,2

Page 18: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

Towards VQ regulation in Italy

Based on the EN 50160:2010, on the data collected by QuEEN,

and on an economic analysis of the impact of microinterruptions

(transient interruptions+voltage dips, PoliMI – DIG 2006) on the Italian economy,

Autorità per l’energia elettrica e il gas published two Consultation Documents

(DCO 42/10; DCO 15/11); some proposals regard:

1)extension of VQ monitoring to all MV busbars of HV/MV stations

(about 4000 VQ meters needed)

2)publication of expected/registered values of microinterruptions

(transient interruptions+voltage dips) by the DSO for each MV main busbar

(publication of long and short interruptions already in force)

The availability of such data would allow a sensitive user to evaluate

on a sound technical base if further immunization / mitigation is needed for his

specific production process (equipment class; UPS; PQ contract).

Page 19: EN 50160  voltage dips and swells classification as an instrument for responsibility sharing

Frankfurt (Germany), 6-9 June 2011

THANK YOU!

Maurizio Delfanti – Italy – RT 2a