4
1360 Elmwood Ave., Cranston, RI 02910 TF: 800.222.1208 | P: 401.461.1200 | F: 401.941.5310 www.leonardvalve.com Mixing Safety & Performance for Over 100 Years EMERGENCY MIXING VALVES TA-300-LF TM-850-LF TA-350-LF TM-800-LF ASSE 1071 | LOW LEAD CERTIFIED Made in the USA with Domestic and Imported Parts

EMERGENCY MIXING VALVESleonardvalve.industrysuite.com/Assets/External... · Toll-free technical support Temperature Override Protection (TM-850-LF only) A redundant thermostatic control

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: EMERGENCY MIXING VALVESleonardvalve.industrysuite.com/Assets/External... · Toll-free technical support Temperature Override Protection (TM-850-LF only) A redundant thermostatic control

1360 Elmwood Ave., Cranston, RI 02910TF: 800.222.1208 | P: 401.461.1200 | F: 401.941.5310 www.leonardvalve.com

Mixing Safety & Performance for Over 100 Years

EMERGENCY MIXING VALVES

TA-300-LF

TM-850-LF

TA-350-LF

TM-800-LF

A S S E 10 71 | L O W L E A D C E R T I F I E DMade in the USA with Domestic and Imported Parts

Page 2: EMERGENCY MIXING VALVESleonardvalve.industrysuite.com/Assets/External... · Toll-free technical support Temperature Override Protection (TM-850-LF only) A redundant thermostatic control

2 ASSE 1071

SINGLE EYEWASH OR EYE / FACE WASH

Leonard Thermostatic Water Mixing Valves

� Controls water temperature to provide tepid water for emergency showers, eyewash and eye/face wash units

� DURA-trol® bi-metal thermostatic control

� Locked temperature regulator set for 85°F (29°C)

� High temperature limit stop set for 90°F (32°C)

� Internal cold water by-pass on failure of hot water supply standard on all models

� On failure of hot water supply, internal cold water by-pass delivers cold water to the emergency fixture, minimum of 4 GPM at 30 PSI

� ANSI/ISEA Z358.1-2014 requires water to emergency equipment to be “tepid”

� Optional systems with temperature override protection available

� All systems are factory tested before shipment

� On failure of cold water supply, hot water is shut down

� Color coded outlet dial thermometer to view temperature

� Toll-free technical support

TA-350-LFTA-300-LF TA-300-LF-STSTL-REC

Locked temperature setting at 85°F (29°C)

DURA-trol® solid bi-metal thermostat not subject to failure due to rupture or fatigue

Internal parts of bronze, brass and stainless steel

ModelsTA-300-LF Eye/Face Wash, 1/2” inlets, 1/2” outlet,

2 - 9 GPM (7.6-34 l/min)TA-350-LF Eye/Face Wash, 3/4” inlets, 3/4” outlet, 2 - 9 GPM (7.6-34 l/min)

TA-300-LF Standard System / TA-350-LF Dual System with Temperature Override Protection Selection Guide

Temperature Override Protection (TA-350-LF only) A redundant thermostatic control valve on the outlet opens on temperature rise at 90°F (32°C) to introduce cold water and maintain tepid flow to the fixture

Page 3: EMERGENCY MIXING VALVESleonardvalve.industrysuite.com/Assets/External... · Toll-free technical support Temperature Override Protection (TM-850-LF only) A redundant thermostatic control

© 2018 Leonard Valve | www.leonardvalve.com 3

SINGLE / MULTIPLE DRENCH OR COMBINATION SHOWERS

DURA-trol® solid bi-metal thermostat directly linked to valve porting

Internal parts of bronze, brass and stainless steel

Locked temperature adjustment setting

Adjustable high temperature limit stop

Union angle checkstops (with strainers) for top or bottom supplies

TM-600-LF, TM-800-LF Standard System / TM-850-LF Dual System with Temperature Override Protection Selection Guide

TM-850-LFTM-600-LF-STSTL-REC-VIEW TM-600-LF

ModelsTM-600-LF Single or Combination Shower, 3/4” inlets, 1” outlet,

3 - 51 GPM (11 - 193 l/min)TM-800-LF Single or Multiple Drench or Combination Shower,

1” inlets, 1-1/4” outlet, 3 - 56 GPM (11 - 212 l/min)TM-850-LF Single or Multiple Drench or Combination Shower, 1-1/4” inlets, 1-1/4” outlet, 3 - 56 GPM (11 - 212 l/min)

Leonard Thermostatic Water Mixing Valves

� Controls water temperature to provide tepid water for emergency showers, eyewash and eye/face wash units

� DURA-trol® bi-metal thermostatic control

� Locked temperature regulator set for 85°F (29°C)

� High temperature limit stop set for 90°F (32°C)

� Internal cold water by-pass on failure of hot water supply standard on all models

� On failure of hot water supply, internal cold water by-pass delivers cold water to the emergency fixture, minimum of 20 GPM at 30 PSI

� ANSI/ISEA Z358.1-2014 requires water to emergency equipment to be “tepid”

� Optional systems with temperature override protection available

� All systems are factory tested before shipment

� On failure of cold water supply, hot water is shut down

� Color coded outlet dial thermometer to view temperature

� Toll-free technical support

Temperature Override Protection (TM-850-LF only) A redundant thermostatic control valve on the outlet opens on temperature rise at 90°F (32°C) to introduce cold water and maintain tepid flow to the fixture

Page 4: EMERGENCY MIXING VALVESleonardvalve.industrysuite.com/Assets/External... · Toll-free technical support Temperature Override Protection (TM-850-LF only) A redundant thermostatic control

4

SINGLE / MULTIPLE DRENCH COMBINATION SHOWERS

TM-5100-LF Standard System / TM-5125-LF Dual System with Temperature Override Protection Selection Guide

TM-5100-LF TM-5100-LF-STSTL-RECTM-5125-LF

OptionsCP Chrome Plated Finish

IT Inlet Thermometers

BWE-EXP Exposed Baked White Steel Cabinet

BWE-REC Recessed Baked White Steel Cabinet

VIEW Viewport in Door (Standard except for TA-300-LF)

TOP Top Inlets

Leonard Thermostatic Water Mixing Valves

� Controls water temperature to provide tepid water for emergency showers, eyewash and eye/face wash units

� DURA-trol® bi-metal thermostatic control

� Locked temperature regulator set for 85°F (29°C)

� High temperature limit stop set for 90°F (32°C)

� Internal cold water by-pass on failure of hot water supply standard on all models

� On failure of hot water supply, internal cold water by-pass delivers cold water to the emergency fixture, minimum of 40 GPM at 30 PSI

� ANSI/ISEA Z358.1-2014 requires water to emergency equipment to be “tepid”

� Optional systems with temperature override protection available

� All systems are factory tested before shipment

� On failure of cold water supply, hot water is shut down

� Color coded outlet dial thermometer to view temperature

� Toll-free technical support

ModelsTM-5100-LF Multiple Drench or Combination Showers, 1-1/4” inlets, 1-1/2” outlet, 3 - 126 GPM (11 - 477 l/min)TM-5125-LF Multiple Drench or Combination Showers, 1-1/4” inlets, 1-1/2” outlet, 3 - 126 GPM (11 - 477 l/min)

1360 Elmwood Ave., Cranston, RI 02910 TF: 800.222.1208 | P: 401.461.1200

F: 401.941.5310 | www.leonardvalve.com

LV -115 R E V 0 6 / 2 018 | © 2 018 L E O N A R D VA LV E C O M PA N Y | P R I N T E D I N T H E U . S . A

Temperature Override Protection (TM-5125-LF only) A redundant thermostatic control valve on the outlet opens on temperature rise at 90°F (32°C) to introduce cold water and maintain tepid flow to the fixture